CCU Current control relay AC / DC Controllers Ltd R sk PSK Controllers Ltd. Current Monitoring Relay Dimensions & weight Width: 62 mm Height: 65 mm Depth (excl. DIN-profile): 73 mm Weight: 238 gram Specifications Protection class open air: IP20 Self-extinguishing plastic housing UL V0 acc IEC 529 Mounting position: on DIN-rail TS 35 according to EN 50022 Mounting position: vertically Supply voltage: 230VAC, 110VAC, 24VAC 50-60 Hz (Galvanic isolation by transformer) 24 V DC (No galvanic isolation) Supply tolerance: ± 10% Rated power consumption: 2.3 VA Hysteresis: adjustable between 5 and 50% of displayed threshold. Display accuracy: ± 10% of preselected threshold. Repeating accuracy: ± 0.1% with constant parameters Power on inhibit timing (T1): 1 to 10 sec ± 30% Timing on upward crossing of threshold (T2): 1 to 4 sec +20% (including response time of the unit itself) Power on: LED green (Un) Indicates of supply voltage Relay energized: LED red (R) indicates of relay energized Terminal : acc IEC 60947-7-1, IEC 60998-1 Terminal Capacity:1x4mm 2 without multicore cable end 1x0.5 to 2.5mm 2 with/without multicore cable end Output circuit Relay: 1 C/O Rated voltage: 250 Vac Switching cazpacity ac: 1000 VA (8A / 250V) COS = 1 Switching capacity dc: 3 A 30 Vdc Max switching capacity ac: 10 A Mechanical life: 1 x 10 6 operations Electrical life at 1000 VA COS =1: 200.000 operations Environmental conditions Permissible ambient temperature: -25°C….+55°C Storage temperature: -25°C….+70°C Transport temperature: -25°C….+70°C Relative humidity (acc. IEC 721-3-3 CLASS 3K3): 15% to 85% Vibration resistance (acc. IEC 68-2-6): 10 TO 55 H 1. Control of AC/DC current WITHOUT latching: When the value of the AC or DC current being controlled reaches threshold displayed on the front panel, the output relay changes status at the end of T2 (adjustable between 1 to 4 sec.). The relay immediately returns to its initial status when the current drops to bellow 5 to 50% of the threshold (hysteresis) or if the power supply is cut. Changing the hyster- esis value (via front panel) does not change the value of the preselected threshold. 2. Control of AC/DC current WITH latching: (Terminals Z1 and Z2 connected) When the value of the AC or DC current being controlled reaches the threshold displayed , the output relay changes status at the end of T2 and remains latched in this position. To reset the relay, contact between Z1 and Z2 must be opened or the power supply to the unit must be cut. Operang CONTROLS AC AND DC CURRENTS 5mA TO 10A MEASUREMENT RANGE THRESHOLD ADJUSTMENT HYSTERESIS ADJUSTMENT NORMAL OR REVERSE RELAY STATUS ADJUSTMENT ON FRONT 2 LEDS DISPLAY RELAY STATUS AND POWER SUPPLY POWER ON INHIBIT TIME ADJUSTABLE FROM 1 TO 10 SEC (T1). TIMING ON UPWARD CROSSING OF THRESHOLD ADJUSTABLE FROM 1 TO 4 s. Function Threshold Output Relay Un on off T2 Hysteresis Hysteresis T1 T2 t Controlled current Output relay normal position (N) Threshold Output Relay Un on off Hysteresis T1 T2 T2 T2 t Hysteresis Controlled current Output relay reverse position (R) T1 T2 T2 2 sec Threshold Output Relay Z1 / Z2 Un on off Hysteresis t Controlled current Latching contact Hysteresis With latching

Upload: others

Post on 06-Feb-2021

6 views

Category:

Documents


6 download

TRANSCRIPT

  • CCUCurrent control relay AC / DC

    Controllers Ltd

    R

    sk

    PSK Controllers Ltd.

    Cur

    rent

    Mon

    itorin

    g R

    elay

    Dimensions & weight

    Width: 62 mmHeight: 65 mmDepth (excl. DIN-profile): 73 mmWeight: 238 gram

    Speci�cations

    Protection class open air: IP20Self-extinguishing plastic housing UL V0 acc IEC 529Mounting position: on DIN-rail TS 35 according to EN 50022Mounting position: verticallySupply voltage: 230VAC, 110VAC, 24VAC 50-60 Hz (Galvanic isolation by transformer) 24 V DC (No galvanic isolation)Supply tolerance: ± 10%Rated power consumption: 2.3 VAHysteresis: adjustable between 5 and 50% of displayed threshold.Display accuracy: ± 10% of preselected threshold.Repeating accuracy: ± 0.1% with constant parametersPower on inhibit timing (T1): 1 to 10 sec ± 30%Timing on upward crossing of threshold (T2): 1 to 4 sec +20% (including response time of the unit itself) Power on: LED green (Un) Indicates of supply voltageRelay energized: LED red (R) indicates of relay energizedTerminal : acc IEC 60947-7-1, IEC 60998-1Terminal Capacity:1x4mm2 without multicore cable end 1x0.5 to 2.5mm2 with/without multicore cable end

    Output circuit

    Relay: 1 C/ORated voltage: 250 VacSwitching cazpacity ac: 1000 VA (8A / 250V) COS = 1Switching capacity dc: 3 A 30 VdcMax switching capacity ac: 10 AMechanical life: 1 x 106 operationsElectrical life at 1000 VA COS =1: 200.000 operations

    Environmental conditions

    Permissible ambient temperature: -25°C….+55°CStorage temperature: -25°C….+70°C Transport temperature: -25°C….+70°C Relative humidity (acc. IEC 721-3-3 CLASS 3K3):15% to 85%Vibration resistance (acc. IEC 68-2-6): 10 TO 55 H

    1. Control of AC/DC current WITHOUT latching:When the value of the AC or DC current being controlled reaches threshold displayed on the front panel, the output relay changes status at the end of T2 (adjustable between 1 to 4 sec.). The relay immediately returns to its initial status when the current drops to bellow 5 to 50% of the threshold (hysteresis) or if the power supply is cut. Changing the hyster-esis value (via front panel) does not change the value of the preselected threshold.

    2. Control of AC/DC current WITH latching:(Terminals Z1 and Z2 connected)When the value of the AC or DC current being controlled reaches the threshold displayed , the output relay changes status at the end of T2 and remains latched in this position. To reset the relay, contact between Z1 and Z2 must be opened or the power supply to the unit must be cut.

    Operating

    CONTROLS AC AND DC CURRENTS5mA TO 10A MEASUREMENT RANGETHRESHOLD ADJUSTMENTHYSTERESIS ADJUSTMENTNORMAL OR REVERSE RELAY STATUS ADJUSTMENT ON FRONT2 LEDS DISPLAY RELAY STATUS AND POWER SUPPLYPOWER ON INHIBIT TIME ADJUSTABLE FROM 1 TO 10 SEC (T1).TIMING ON UPWARD CROSSING OF THRESHOLD ADJUSTABLE FROM 1 TO 4 s.

    Function

    Threshold

    OutputRelay

    Unon

    off

    T2

    Hysteresis

    Hysteresis

    T1T2

    t

    Controlled current

    Output relay normal position (N)

    Threshold

    OutputRelay

    Unon

    off

    Hysteresis

    T1T2 T2 T2

    t

    Hysteresis

    Controlled current

    Output relay reverse position (R)

    T1T2 T22 sec

    Threshold

    OutputRelay

    Z1 / Z2

    Unon

    off

    Hysteresis

    t

    Controlled current

    Latching contact

    Hysteresis

    With latching

  • Controllers Ltd

    R

    sk

    PSK Controllers Ltd.

    Cur

    rent

    Mon

    itorin

    g R

    elay

    Dimensions

    SIDE 1

    2465

    45

    E1 - M:E2 - M:E3 - M:

    5 - 100mA50mA - 1A0.5 - 10A

    DCAC

    Y1 Y2Y1 Y2

    ono�

    Z1 Z2Z1 Z2

    RELAY UL 508 CSA LR68004

    Monitored current Latching

    15

    S1

    16 18(-)~

    (+)~

    M

    E1

    E2E3

    10A250VACcos =1φ

    SIDE 2

    Unlatched operation

    R

    TrHld

    T0 T1 T2

    Hyst.

    Norm.

    Revr.

    U

    0

    230VACA1 - A2A2 - A3A2 - B1

    A2(-) B2(+)

    110VAC

    24VDC24VAC

    Z2 Y2Z1 Y1

    16 1518 B1 A1A2 A3

    E3 E1M E2

    R Un

    CCU

    N R

    10s

    T1

    1

    24 6

    83s

    T2

    0

    THRESHOLD100

    5

    50

    %

    HYSTERESIS50

    5

    30

    % Ie

    TOP

    62

    73

    Connections

    Z1 Z2 Y2

    DC

    MemoryS2

    Y1

    18 16 15

    M E3 E1

    (-) 0V

    E2

    A2 B1 A1A3

    RN

    D1

    S T

    U V

    W

    M3~

    STOP

    d1START

    (+) 5 - 100 mA ~ (+) 50mA - 1A ~

    (+) 0.5 - 10A ~

    Ordering information

    CCU V230VAC110VAC

    24VDC24VAC

    Function

    Measurement ranges ... Permitted overloads

    T1T2 T2

    Threshold

    OutputRelay

    Z1 / Z2

    Un on

    off

    Hysteresis

    t

    Hysteresis

    Controlled current

    Latching contact

    With latching

    E1 - M: (5-8)

    InputsOverload

    Permanent peak, less than 1 sec

    Inputresistance

    AC or DCvoltage (ms)

    E2 - M: (6-8)E3 - M: (7-8)

    5 mA - 100 mA50 mA - 1 A0.5 A - 10 A

    1 Ω0.1 Ω

    0.01 Ω

    1.5 A5 A

    10 A

    5 A10 A15 A

    NOTE: Higher AC currents can be controlled using a current transformer.