protection test case - ieee power & energy society · protection test case t. e. mcdermott...

15
Protection Test Case T. E. McDermott Univ. of Pittsburgh [email protected] 1-412-648-9585 1

Upload: others

Post on 26-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Protection Test Case

T. E. McDermottUniv. of [email protected]

1

Page 2: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

A DG protection test feeder has been defined for utility-fed, DG-fed and both-fed fault calculations.

F1B

C

F2

1

4

2

3A

D

Bx B0

B1 B2Bm

Bp

Bt Bg

Lat1 Lat2

T. E. McDermott, "A test feeder for DG protection analysis," PSCE 2011.• 34.5/12.47 kV Substation Transformer, 5 MVA, 7.19% Impedance• 29 kft to 1.65-MW Wind Turbine, Induction Generator,

6x Locked Rotor Current• Lat1 is 21.2 kft, Lat2 is 105.6 kft• Based on UVIG’s Illinois Rural Electric Case Study

2

Page 3: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Interconnection transformer with ground source; limits temporary overvoltage on the high side; simplifies ground fault detection on the low side.

MAIN FAULTCONTRIBUTION

FROM EPSCONTRIBUTION

FROM DRTRANSFORMER

(MULTI-GROUNDED NEUTRAL)

FAULT

DG

V=0

3

Page 4: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Transformer without ground source allows high-side temporary overvoltage; complicates ground fault detection from the low side.

ARRESTERSSUBJECTED TO LINE-TO-LINE VOLTAGES

PERMANENT LINE-TO-GROUND FAULT

UTILITYINTERRUPTINGDEVICE OPEN

UNGROUNDEDTRANSFORMERCONNECTION

G

4

Page 5: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Protection with ∆-Y Transformer can be achieved with high-side voltage transformers (VT or “PT”).

DELTA / WYETRANSFORMER

PTs (3-phase) for59N relay

59N (or 59G)

5

Page 6: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Test Case Setup

• Solved in OpenDSS– http://sourceforge.net/projects/electricdss– Program and input files publicly available

• Input Variations– 4 Fault Locations– 5 Fault Types (25-Ω SLGF; 0-Ω SLGF, 3-phase,

phase-phase, phase-phase-ground)– Utility Source present or not– DG (Off; On with Y-∆, Y(Rn=4Ω)-∆, ∆-Y

6

Page 7: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Test Case Outputs

• All Device and Fuse Currents; Phase & Ground– Fault detection– Phase and ground coordination

• Phase and Sequence Voltages at POI– IEEE Std. 1547 voltage trip, 59N trip, etc.– Temporary Overvoltage (TOV)

• Sequence Currents at POI– Unbalance trip

7

Page 8: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

0-Ω SLGF at Bm, ∆-Y Transformer

• A sees 920 Amps Phase and Ground < 2 s• C sees 125 Amps no trip• 0.6 per-unit voltage at C > 2 s• 0.34 per-unit V0 or V2 at B and C• 4.8% I2 at C

F1B

C

F2

1

4

2

3A

D

Bx B0

B1 B2Bm

Bp

Bt Bg

Lat1 Lat2

8

Page 9: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

… After Recloser A Trips

• All Device Currents Approach Zero• 1.7 per-unit voltage on two phases at B• Normal phase voltages at C; IEEE 1547 won’t trip• 1.0 per-unit V0 at B Can Trip C on This• Transfer Trip from A is another option (expensive)

F1B

C

F2

1

4

2

3A

D

Bx B0

B1 B2Bm

Bp

Bt Bg

Lat1 Lat2

9

Page 10: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Time-Current Curves apply to overcurrent protection; not directly related to the feeder model.

0.01

0.1

1

10

100 1000 10000

Tim

e [s

]

Primary Current [Amps]

Example Time-Current Curves

40K Fuse B:Phase A:Phase B:Grnd A:Grnd

10

Page 11: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Functional definitions can be used for most relay and recloser time-current curves. What about fuses?

3/17/2014 ECE 2774: System Protection; Part 2

11

Description Curve p α β

Moderately Inverse U1 0.02 0.0104 0.0226

Inverse U2 2 5.95 0.18

Very Inverse U3 2 3.88 0.0963

Extremely Inverse U4 2 5.67 0.0352

Short-time Inverse U5 0.02 0.00342 0.00262

( 1)trip p

TDt TDM

α β×= + ×

( 1)trip p

TDtM

α×=

Description Curve p α

Inverse C1 0.02 0.14

Very Inverse C2 1 13.5

Extremely Inverse C3 2 80

Long-time Inverse C4 1 120

Short-time Inverse C5 0.04 0.05

IEEE (U.S.) Form

IEC (International) Form

Page 12: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Should implement the IEEE Std. 1547 Voltage Trip Curve (this is now more adjustable per 1547a-2013).

0

0.2

0.4

0.6

0.8

1

1.2

1.4

0 0.5 1 1.5 2 2.5

Volta

ge T

hres

hold

[p.u

.]

Trip Time [s]

IEEE 1547 Voltage Trip Curves

• Trip on any RMS phase-to-phase voltage, except• Y-Y grounded or single-phase

trip on any phase-neutral voltage

12

Page 13: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Sequence networks applied to fault analysis with DG; may need to use Norton equivalent with superposition.

12 0LZ −

12 0LZ −0SZ −

02 YZ − 02 YZ −

1 0TZ −

12 1LZ −

12 1LZ −1SZ −

12 YZ − 12 YZ −

1 1TZ −

12 1LZ −

12 1LZ −1SZ − 1 1TZ −

+

1.05puSV =

0 1 2F F FI I I− − −⇐ = =

XI

YI

Fault at the midpoint.

12 YZ − 12 YZ −

Zero seq.

Positive seq.

Negative seq.

UTILITY DG-THEV

0THZ −

+1THZ −

DGV

2THZ −

DG-NORT

1.1puDGI =

+

NORTZ

DG-XFMR

2 0TZ −

3 NZ

2 1TZ −

2 1TZ −

1mB −

2mB −

0mB −

13

Page 14: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

With PV inverters back-feeding a fault, the temporary overvoltage depends on grounding, load and controls.

14

Page 15: Protection Test Case - IEEE Power & Energy Society · Protection Test Case T. E. McDermott Univ. of Pittsburgh. tem42@pitt.edu 1-412-648-9585 . 1. A DG protection test feeder has

Conclusions

• Test Feeder Uses– Technical paper examples– Software vendor examples– P1729; Recommended Practice for DSA

• DG Protection Studies– Sequence & Phase; Voltages and Currents– With or without Utility Source– Representation of time-dependent curves (TCC)

15