protection and control hv/mv substation sepam range · pdf file · 2009-07-17hv mv...
TRANSCRIPT
![Page 1: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/1.jpg)
Protectionand control
HV/MV substationSepam rangeBusbar differential
![Page 2: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/2.jpg)
2 Busbar differential
Presentation
Contents page
HV
MV
presentation 2Sepam 100 LD high impedance differential protection 4determination of sensors 6surge limiter 7functional and connection scheme 8characteristics 11installation 12current circuit monitoring /use of busbar differential protection: Sepam 2000 W 13protection 14control and monitoring 15operation 20set-up 21functional and connection schemes 22communication 29characteristics 30installation 31ordering information 32
Sepam 2000 W01, W02.
DescriptionSepam busbar differential protection includes:c Sepam 100LD high impedance differential protection,c current circuit monitoring up to the sensors:c management of the different zones to be protected when there are multipleor split busbars.
The faults which appear on busbars are generally violent and they cause majordamage, with serious consequences for energy availability since the busbar is anode of the electrical network.
High impedance differential protection is suitable for busbar protection since it isvery fast and sufficiently sensitive to detect short-circuits.
The principle of busbar differential protection involves installing the current sensorsof all the circuits connected to the busbar in parallel. This parallel mountingarrangement results in a large number of lengthy short-circuits which are spreadacross an extended zone, in particular for open substations. The cutting of currentcircuit wiring can cause degradation of the differential circuit, leading to a loss ofprotection which is not detected or unstable operation (tripping due to a faultoutside the busbar).
Monitoring of the current circuits enables the necessary measures to be taken toavoid such drawbacks and inform the remote monitoring and control system of thedowngraded situation.
Busbars may be single or multiple (double or triple busbars). They may also besplit (busbar isolation or coupling). In this case, one differential protection is usedfor each zone with an overall validation protection to reduce the possibilities ofunwanted operation.
The logical processing of the operation of the different zone protections, thepossibilities of putting in and out of service, annunciation and communication arethe management functions which are connected to the busbar differentialprotection.
Sepam 100 LD.
![Page 3: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/3.jpg)
3Busbar differential
PrincipleThe principle of high impedance differential protectionis based on the creation of a differential circuitthrough which the sum of the currents of the circuitsconnected to the protected zone flow. To do this:c the current sensors of all the circuits connected tothe protected zone have the same ratios and areinstalled in parallel,c the differential circuit, composed of the differentialrelay, series-mounted with the stabilizing resistor Rs,is supplied by the parallel-mounted current sensors.
OperationA short-circuit outside the protected zone may causesaturation of the current sensors and the appearanceof a differential current, but should not trip thedifferential relays. The stabilizing resistor should bechosen so as to limit the value of the current flowingin the differential circuit when one of the currentsensors is completely saturated.
A fault inside the protected zone should the flow of adifferential current which the differential relay candetect: the saturation voltage Vk of the CTs should besufficient for the relay set point to be reached even ifthe current sensors are saturated. Correct operationof the high impedance differential protection isassured if the different components are correctlysized to ensure stability.
StabilityThe stability of a differential protection is its capabilityto detect faults inside the protected zone and not besensitive to faults outside that zone.
Sizing of high impedance differential protectioncomponentsc stabilizing resistor determined in accordance with:v internal resistance of the CTs,v wiring resistance,v differential relay setting,v short circuit current.c current transformers:v all the CTs should have the same transformer ratio,v the knee-point voltage Vk is determined inaccordance with the value of the chosen stabilizingresistor and the differential relay setting.c surge limiter:v determined in accordance with the knee-pointvoltage Vk, the internal resistance of the CTs, wiringresistance and the earth fault current value.
Current circuit monitoringWhen there are no busbar faults present, there is no current in the differentialcircuit since the sum of the currents going to the busbar is zero. The opening ofa CT circuit therefore causes the appearance of a continuous current in thedifferential circuit which corresponds to the strength of the current going into thebay concerned. The flow of this continuous current into the stabilizing resistorproduces a temperature rise which may destroy the resistor, which would inhibitthe differential protection.
Monitoring of the current circuits is therefore based on the detection of acontinuous current in the differential circuit in a normal situation.
c It is performed by a time-delayed low-set point overcurrent current protection.c It causes the making of a circuit which bypasses the differential circuit bythe closing of a contact connected between points A and B.c It indicates that the busbar differential protection is out of service.
Use of busbar differential protection:c “in service” or “out of service”,c zone management:the busbar of a substation is generally split into zones by a busbar coupling circuitbreaker. Busbar faults are detected by a differential protection per zone and thetripping of the zone is validated by an overall differential protection for all thezones,c annunciation: the “in service” and “out of service” modes and zone managementgive rise to:v annunciation by messages on the display unit and by output contacts,v remote annunciation via the communication link.
A
B
Sepam100LD
![Page 4: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/4.jpg)
4 Busbar differential
Sepam 100 LD high impedance differential protection
sepam 100S01 LD
on
trip
20 6025
3035
515
10
40
80
50
70
% In
reset
DescriptionThere are two versions of Sepam 100 LD for busbar protection:c 3-phase 50 Hz: 100 LD X53,c 3-phase 60 Hz: 100 LD X63.
Sepam 100 LD includes the following on the front panel:c 2 signal lamps:v “on” indicator: device energized,v latching type “trip” indicator which indicates tripping of the output relays.c a protection set point selector switch.c a “reset” button for acknowledgment of the output relays and the “trip” indicator.
This button activates a “trip” indicator test lamp while it is activated.
The back panel of Sepam 100 LD comprises:c input/output connectors:v an 8-pin connector for the core balance CT inputs and remote acknowledgment,v an 8-pin connector for the “tripping” outputs and for the power supply,v a 4-pin connector for the “tripping” outputs.c a microswitch used to configure the relay “with” or “without” latching.
Sepam 100 LD X53 and X63 have:c 3 common-point current inputs,c an (insulated) logic input for remote acknowledgment,c “tripping” output relays with 5 contacts (3 normally open and 3 normally closed).
Sepam 100 LD operates in 5 supply voltage ranges(to be specified when ordered):c 24-30 Vdc,c 48-125 Vdc,c 220-250 Vdc,c 100-127 Vac,c 220-240 Vac.
Sepam 100 LD is combined with a stabilizing plate which includes variableresistors which allow it to operate with 1 A or 5 A current transformers.
Sepam 100 LD.
![Page 5: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/5.jpg)
5Busbar differential
Operating curve - settings
0
10
20
30
40
50
60
70
80
90
100
t (ms)
10 2 3 4 5 6 7 8 9 10 l/ls
settings (1) setting values
Is current set point 5 to 40% In by steps of 5% In40 to 80% In by steps of 10% In
plate Rs = 0 Ω to 68 Ω P = 280 WRs = 0 Ω to 150 Ω P = 280 WRs = 0 Ω to 270 Ω P = 280 WRs = 0 Ω to 470 Ω P = 180 WRs = 0 Ω to 680 Ω P = 180 W
accuracy / performance
set point ± 5 %
pick up / drop out ratio 93 % ± 5 %
response time i 10 ms for I u 10.Isi 16 ms for I u 5.Isi 25 ms for I u 2.Is
memory time i 30 ms
(1) Setting made using selector switch on front panel.
Set-upThe choice of “with” or “without” latching is made using the SW1 microswitchon the rear of the Sepam 100 LD .
SW1
SW1
without latching:
with latching:
![Page 6: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/6.jpg)
6 Busbar differential
Sepam 100 LD high impedance differential protection (cont’d)
Determination of sensorsTo ensure the stability and sensitivity of theSepam 100 LD , the stabilizing resistance and currenttransformer (CT) characteristics are calculatedas follows.The following diagram shows the connection of eachCT to the differential circuit AB of the correspondingphase.
p : Number of CTs in paralleln : CT transformer ratioRCT : CT secondary circuit resistanceim : CT magnetizing currentVk : CT knee-point voltageRf : Resistances of wiring between CT
and differential circuit.Rs : Stabilizing resistancei s : Protection set pointRl : Surge limiteri f : Current in surge limiter (RI)i sc : Maximum short-circuit
current in CT secondary circuits
Choice of current transformersc transformer ratio n.n is the same for all the current transformersconnected to the differential circuit of the highimpedance protection.c Knee-point voltage Vk:Vk > 2 x (RCT + Rf) x isc
Choice of the stabilizing resistance
Surge limiterThe voltage which appears at the terminals of a CTwhen a fault occurs in the protected zone is:
V = 2rx Vk x [isc x (RCT + Rf + Rs) - Vk]
If this value exceeds 3 kV, it is necessary to use asurge limiter RI in parallel with the differential circuitto protect the CTs.Sizing of the surge limiter:c it consists of N elementary limiter blocks which maybe installed in parallel,c each block can accept a maximum current of 40 Arms for 1 second,c the number of blocks in parallel is:
Protection sensitivityThe minimum fault current detected I
d is the fault current that triggers the circulation
of a current in the differential circuit equal to the relay setting is.
However, the present of current is in the differential circuit is accompanied byvoltage Rs x Is at the circuit terminals, which causes the appearance of leakagecurrents:c magnetizing currents Im of the CTs connected in parallel to the differential circuit(im may be read in the CT magnetizing curves),c leakage currents if of the N surge limiter blocks that may be connected in parallelto the differential circuit (if is read in surge limiter curves).
Id = n x (Σ im + N x if + is)
ExampleThe busbar being protected comprises 10 incomer and feeder cubicles(or bushings) with no coupling.The maximum fault current in the protected zone is ID = 30 kA.CT ratio: 2000/5 A
RCT = 1.76 ΩThe maximum short-circuit current in the CT secondary circuits is therefore
isc = 30000 x = 75 A
Distance between CTs and relays: 15 mWiring: 2.5 mm2 copper
Rf = 0.02 x = 0.24 Ω
Number of CTs in parallel on the differential circuit: p = 10desired setting: is = 25% In, i.e. is = 1.25 A
c CT knee-point voltage(RCT + Rf) x icc = (1.76 + 0.24) x 75 = 150 VVk > 2 x 150 = 300 VFor example: Vk = 320 V.
c stabilizing resistance
< Rs i
120 Ω < Rs i 128 ΩThe resistance chosen may be adjusted from 0 to 150 Ω. for example 125 Ωc surge limiter ?V = 2r x 320 [75 (1.76 + 0.24 + 125) - 320]V = 4854 V > 3 kVA surge limiter must be installed in parallel on the differential circuit.Number of limiter blocks required:
c minimum fault current detectedThe voltage Rs x is = 125 x 1.25 = 156 V.The CT magnetizing curve may be used to determine im for 156 Vfor example Im = 20 mA.
The surge limiter leakage current curve gives il = 4 mA for 156 V.The minimum fault current detected is therefore:
Id = (10 x 0.02 + 2 x 0.004 + 1.25) = 583,2 A
Sepam 100 LD
Rf
RI
R
Rs
CT A
B
x isc < Rs <R
CT + R
f
is
Vk
2 x is
IDn x 40
ID: maximum fault currentin the protected zone, in A rms.N u
5
2000
2 x15
2.5
150
1.25320
2 x 1.25
7540
= 2N ≥
2000
5
![Page 7: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/7.jpg)
7Busbar differential
Surge limiterA triple unit, compressing three independent blocksmounted on the same rod.
0.001 0.01Ib (A rms)
0.1100
U (V rms)
1000
Single unit
weight: 1.2 kg max.
Leakage currentc a block accepts a maximum continuous voltageof 325 V rms, and presents a leakage current ib:
124
62
250
M10mounting isolatedsupport
Ø 10.4connection
30
![Page 8: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/8.jpg)
8 Busbar differential
Functionaland connection scheme
Relays
annunciationand trippingoutputs
4
5
7
8
6
4
3
21
3
5
8
7
4
2
1
3
6
F0phase 1
phase 2
phase 3
remote reset
80 %5 %
S≥1
2aux.Supply
1
&
R
on
trip
without withlatching
≥1
+-
reset button
SW1
F0
F0
0A
1A
1A
1B
Stabilizing plateConnection of CTs and surge limiters:c 5 A rating: between terminals 1-2 and 3-4,c 1 A rating: between terminals 1-2 and 5-6.
123456
1
CSH30: measurementring CT2
RsCT 5A
CT 1A
Sepam 100 LD high impedance differential protection (cont’d)
![Page 9: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/9.jpg)
9Busbar differential
Connection1A : 8-pin CCA 608.
1B : 4-pin CCA 604 connector.
0A : 8-pin CCA 608 connector
1
2
3
4
5
6
7
8
1
2
3
4
1
2
3
4
5
6
7
8
A
B
AAS LD
1 0
SW1
1~3~
1 A 4
slot number on board(0 to 1)connector identification letter(A or B)
connector terminal n°
Terminal identification.Each terminal is identified by 3 characters.
4
1
2
5
tripping7
04
6
4
3
2
1
3
05
02
03
01
annunciation
annunciation
- auxiliary
+ power supply
81A
1B
Stabilizing platec Screw 1 to 6: screw-clamp connections for 6 mm2 cable.c Screw 1, 2: secondary winding of CSH30 ring CT, connected to 0A .Cable to be used:v sheathed, shielded cable,v min. cross-section 0.93 mm2 (AWG 18)(max. 2.5 mm2),v resistance per unit length < 100 mW/m,v min. dielectric withstand: 1000 V,v max. length: 2 m.
Connect the cable shielding to 0A in the shortest manner possible.
The shielding is grounded in Sepam 100 LD. Do not ground the cable by any othermeans.Flatten the cable against the metallic frame of the cubicle to improve immunityto radiated disturbances.
123456
2
1
2
1
CSH30 0A
2
1
remote reset
6
4
3
7
8
5 phase 3 input
phase 2 input
phase 1 input
0A
: grounding terminal
Cabling via screw terminals for wire 0.6 to 2.5 mm2.Each terminal accepting two 1.5 mm2 cables.
Sepam 100 LD
![Page 10: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/10.jpg)
10 Busbar differential
Connection
Correspondence between primary and secondary connections (e.g. P1, S1).
Sepam 100 LD high impedance differential protection (cont’d)
Sepam100LD
123456
0A
2
1
43
123456
2
1
123456
2
1
21
65
B
A3
A2
A1
L1
L2
L3
plate 2
plate 1
plate 3
![Page 11: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/11.jpg)
11Busbar differential
Electrical characteristics
Environmental characteristics
analog inputs (with stabilizing plate)
continuous current 10 In
3s current 500 In
logic inputs (remote reset)
voltage 24/250 Vdc 127/240 Vac
maximum consumption 3.5 W 3.7 VA
logic outputs
continuous current 8 A
voltage 24/30 Vdc 48 Vdc 127 Vcc/Vac 220 Vdc/Vac
breaking capacity: DC resistive load 7 A 4 A 0.7 A 0.3 A
(contact 01) AC resistive load 8 A 8 A
breaking capacity: DC resistive load 3.4 A 2 A 0.3 A 0.15 A
(contacts 02 to 05) AC resistive load 4 A 4 A
power supply
range de-activated max. inrushconsumption consumption current
24/30 Vdc ±20 % 2.5 W 6 W < 10 A for 10 ms
48/125 Vdc ±20 % 3 W 6 W < 10 A for 10 ms
220/250 Vdc -20 %, +10 % 4 W 8 W < 10 A for 10 ms
100/127 Vac -20 % +10 % 6 VA 10 VA < 15 A for 10 ms
220/240 Vac -20 % +10 % 12 VA 16 VA < 15 A for 10 ms
operating frequency 47.5 to 63 Hz
“ ” marking on our products guarantees their compliance with European directives.
climatic
operation CEI 60068-2 - 5 °C to 55 °Cstorage CEI 60068-2 - 25 °C to 70 °Cdamp heat CEI 60068-2 95% to 40 °Ceffect of corrosion CEI 60654-4 class I
mechanical
degree of protection CEI 60529 IP 41 on front panel
vibrations CEI 60255-21-1 class I
shocks and jolts CEI 60255-21-2 class I
earthquake CEI 60255-21-3 class I
fire risks CEI 60695-2-1 glow wire
electrical insulation
power frequency CEI 60255-5 2 kV - 1 mn
1.2/50 ms impulse wave CEI 60255-5 5 kV
electromagnetic compatibility
immunity to radiation CEI 60255-22-3 class x 30 V/m
electrostatic discharge CEI 60255-22-2 class III
one-way transients (1) CEI 601000-4-5
1 MHz damped oscillating wave CEI 60255-22-1 class III
5 ns fast transients CEI 60255-22-4 class IV
![Page 12: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/12.jpg)
12 Busbar differential
Sepam 100 LD high impedance differential protection (cont’d)
Sepam 100 LD relays
201
20 175
max. 86
202222
mounting latch
88 max. 84
th = 3 mm max.
weight: 1.9 kg
Stabilizing plate
352.5
104
12
110
weight: 1.7 kg
M6 - 16 mm
Cut-outInstallation
Dimensions and weights
![Page 13: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/13.jpg)
13Busbar differential
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W
functions ANSI types of Sepamcode W01 W02
protectionpercentage-based single-phase overcurrent (I1, I2, I3) 50/51 1 1
percentage-based single-phase overcurrent (I’1, I’2, I’3) 50/51 1
metering
disturbance recording c csingle-phase current (I1, I2, I3) (as % of 1 A or 5 A) c csingle-phase current (I’1, I’2, I’3) (as % of 1 A or 5 A) ccontrol and monitoring
differential circuit short-circuiting c czone In/Out of service c clockout relay 86 c cinhibit closing 69 c cannunciation 30 c cSepam disturbance recording triggering c cdetection of plugged connectors (DPC) 74 c cpower supply monitoring c cbusbar fault trip counter c cSepam models
standard S36 YR KR
standard number of logic I/O boards 2 2
Selection table
Measurements neededfor operation
Disturbance recordingRecording of electrical signals and logical informationbefore and after a fault recorder triggering order isgiven.
Measurements usedfor commissioningand maintenance
CurrentMeasurement of the current in the differential circuitfor each of the 3 phases.
Characteristics
(1) transfer of records with SFT 2801 software, use of records with SFT 2826 software.(2) measurement available on the TSM 2001 pocket terminal.(3) typical accuracy with nominal values according to IEC 60255-6.
functions ranges accuracy (3)
disturbance recording (1) 12 samples per period
ammeter (2) I1, I2, I3 1%In to 999% of 1A ou 5A ± 5%
ammeter (2) I’1, I’2, I’3 1%In to 999% of 1A ou 5A ± 5%
![Page 14: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/14.jpg)
14 Busbar differential
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
Protection
Percentage-based single-phase overcurrent(ANSI 50/51) F031, F041, F051, F111, F127, F132Protects the differential circuit (stabilizing resistor)by detection of a continuous differential currentcharacteristic of the breaking of a high impedancedifferential protection CT circuit. The action, witha constant time delay, consists of actuating thedifferential circuit short-circuiting mechanism.(triphase BT connector, ≥ 660 V, ≥ 5A, not supply).
Current sensor sizingThe current sensors are those of the busbardifferential protection. They are sized for highimpedance differential protection.
functions Fxxx (1) settings time delays
percentage-based single-phase overcurrent (I1, I2, I3) F031, F041, F051
3% to 200% of1A or 5A t : 0,05 to 655 s
percentage-based single-phase overcurrent (I’1, I’2, I’3) F111, F121, F131
3% to 200% of 1A or 5A t : 0,05 to 655 s(1) function identification for protection setting using the pocket terminal.
Setting ranges
![Page 15: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/15.jpg)
15Busbar differential
Control and monitoring
Differential circuit short-circuitingTriggers short-circuiting of the differential circuit toprotect the differential circuit and avoid operationof the high impedance differential protection.
Zone In/Out of serviceUsed to put a high impedance differential protectionfor a zone In/Out of service to cancel the protection ofzone 1 or 2 or to force validation of the check zone,for maintenance for example.
Lockout relay (ANSI 86)Stores tripping orders (lockout) and requires useraction to be put back into operation (reset).
Inhibit closing (ANSI 69)Inhibits the closing of the circuit breaker accordingto operating conditions. (1) The counters are read using the pocket terminal.
Annunciation (ANSI 30)Keeps the user informed by the display of messages.
Sepam disturbance recording triggeringInitiates the recording of differential currents and logic states by:c intentional local or remote action,c zone tripping information.
Detection of plugged connectors (DPC) (ANSI 74)Indication on the display unit that one or more connectors are not plugged in(the detector itself must be connected: see connection schemes).
Power supply monitoringDetects the loss of auxiliary power or relay failure (watchdog).
Fault trip counter (1)
Counts the number of operations for which breaking performances are required,in order to facilitate equipment maintenance.
![Page 16: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/16.jpg)
16 Busbar differential
Sepam W01 put in/out of service
I2: check zonedifferential operation
KP4
I15: zone 1 busbardifferential operation
KP53
KTC33≥1
I14: put out of service
KP54
KTC34≥1
&I13: put into service
&
I14: put out of service
KTS2
message: ZONE OUTO1
KTS1
&
1
0
1
0≥1
I22: acknowlegment
KTC35
RESET key
KTS5
O13zonetripinformation
≥1
O14inhibitcircuit breakerclosing
&KP3 message:ZONE TRIP
&KP3
message:CHECK ZONE
C1KP49 (RAZ)
&
≥1
≥1
KP3
≥1
KTC35
I11:busbar isolation closed
t0
T1 = 0,2 s
Sepam 100 LDacknowledgment
O22
O1 = 0zone in serviceO1 = 1zone out of service
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
(1) only for busbar with 1 busbar disconnector and a circuit breaker and a busbar differential protection with two zones validated by a protective check zone.
(1)
![Page 17: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/17.jpg)
17Busbar differential
Sepam W02 put in/out of zone 1 and zone 2
message : ZONE 1 TRIP
message : ZONE 1 TRIP
RESET key
I22: acknowledgment
I2: check zone differential operation
&
≥1KTC36
KP55
I24: put into service
KP53
KTC33
I14: put out of service
KP54
KTC34≥1
&I13: put into service
&I14: put out of service
KTS2
message: ZONE 1 OUTO1
KTS1
1
0
&
≥1
≥1
KTC35
I11:busbar isolation closed
t0
T1 = 0,2 s
Sepam 100LDacknowledgment
O22
I24: put out of service
KTC37
KP56
I23: put into service 1
0
O2
KTS4
message: ZONE 2 OUT
KTS3
I15: zone 1 busbar differential operation
KP4
O13KTS5
zone 1tripinformation
≥1
O14inhibitcircuit breakerclosing
C1KP49 (RAZ)
&
&
≥1
KP4
I2: check zone differential operation≥1
I25: zone 2 busbar differential operation
KP4
≥1KTC35
O23KTS6
zone 2tripinformation
≥1
O24
inhibitcircuit breakerclosing
C2KP49 (RAZ)
1
0
1
0
O1 = 0zone 1 in serviceO1 = 1zone 1 out of service
O2 = 0zone 2 in serviceO2 = 1zone 2 out of service
≥1
(1) only for busbar with 1 busbar disconnector and a circuit breaker and a busbar differential protection with two zones validated by a protective check zone.
(1)
![Page 18: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/18.jpg)
18 Busbar differential
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
Sepam W01 short-circuiting of the differential circuit
RESET key
KTC35
phase overcurrent I1F111
≥1
KTS7
message:CT1 WIRE
phase overcurrent I2F121
KTS8
message:CT2 WIRE
1
0
1
0
O11closingof short-circuitingdevice
1
0≥1
phase overcurrent I3F131
I22: acknowledgment
KTS9
message:CT3 WIRE
O12klaxon
1
0KP57
KTC38 ≥1
I1: stop klaxon
KTS13
![Page 19: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/19.jpg)
19Busbar differential
Sepam W02 differential circuit short-circuiting
phase overcurrent I1F111
≥1
KTS7
message:CT1 WIRE Z1
phase overcurrent I2F121
KTS8
message:CT2 WIRE Z1
1
0
1
0
O11closing of zone 1differential circuitshort-circuitingdevice
1
0
phase overcurrent I3F131
KTS9
message:CT3 WIRE Z1
O12klaxon
1
0
KTS13
phase overcurrent I’1F031
≥1
KTS10
message:CT1 WIRE Z2
phase overcurrent I’2F041
KTS11
message:CT2 WIRE Z2
1
0
1
0
O21closing of zone 2differential circuitshort-circuitingdevice
phase overcurrent I’3F051
KTS12
message:CT3 WIRE Z2
1
0RESET button
KTC35
I22: acknowledgment
≥1
KP57
KTC38 ≥1
I1: stop klaxon
≥1
![Page 20: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/20.jpg)
20 Busbar differential
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
functions short- short- inhibit inhibit lockout alarm alarm messages (1)
circuiting circuiting closing closing trip tripdiff. cir.1 diff. cir.1 zone 1 zone 2 zone 1 zone 2O11 O21 O14 O24 O13 O23
overcurrent I1 c CT1 WIREovercurrent I2 c CT2 WIREovercurrent I3 c CT3 WIRE
CT1 WIRE Z1 (W02)CT2 WIRE Z1 (W02)CT3 WIRE Z1 (W02)
overcurrent I’1 c CT1 WIRE Z2 (W02)overcurrent I’2 c CT2 WIRE Z2 (W02)overcurrent I’3 c CT3 WIRE Z2 (W02)
busbar fault zone/ c c c ZONE TRIP/ (2)
or check zone CHECK ZONE (2)
busbar fault c c c ZONE1 TRIP(W02)zone 1
busbar fault c c c ZONE2 TRIP(W02)zone 2
detection of CONNECTORplugged connectors (DPC)
Operation
(1) on Sepam 2000 display unit (according to language versions).(2) parameter KP3 according.
![Page 21: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/21.jpg)
21Busbar differential
function parameters message (1)
zone protection / check zone
zone protection (W01) KP3=0
check zone (W01) KP3=1
check zone protection
with check zone protection KP4=0
without check zone protection KP4=1
remote setting
remote setting active KP38=0
remote setting inactive KP38=1
counters
resetting of busbar fault counter KP49=1
disturbance recording
storage KP50
automatic triggering KP51
manual triggering KP52
zone In/Out of service
zone 1 In service or check zone KP53
zone 1 Out of service or check zone KP54 ZONE 1 OUT or ZONE OUT
zone 2 In service KP55
zone 2 Out of service KP56 ZONE 2 OUT
other
stop klaxon KP57=1
Set-up
(1) on Sepam 2000 display unit (according to language versions).Parameters KP49 to KP57 are of the impulse type.
![Page 22: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/22.jpg)
22 Busbar differential
CE40 1B
1A 4
23
1
21
1
6AESTOR1
21
1
7AESTOR2
ESB 5A
DPC
O2
O1
l2
l1
CDG
2120
19
1716
131211
5
10
1415
18
76
4
2
98
3
1
14
52
63
56
4321
2A
DPC
ECM2B 5051
A1 A2 A3
Rs
sepam 100 LDzone 2
B’
30 A2 A
short-circuitingnot supplied
Functionaland connection schemes
Standard S36YR Sepam 2000.
W01 type
N.B.DPC: detection of plugged connectors.CDG: watchdog.
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
![Page 23: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/23.jpg)
23Busbar differential
CE40 1B
1A 4
23
1
21
1
6AESTOR1
21
1
7AESTOR2
ESB 5A
DPC
O2
O1
l2
l1
CDG
2120
19
1716
131211
5
10
1415
18
76
4
2
98
3
1
14
52
63
56
4321
2A
DPC
ECM2B 5051
A’1 A’2 A’3
Rs
sepam 100 LDzone 2
B’
30 A2 A
14
52
63
56
4321
2A
DPC
ECM2B 5051
A1 A2 A3
Rs
sepam 100 LDzone 2
B
30 A2 A
short-circuitingnot supplied
short-circuitingnot supplied
W02 type
Standard S36KR Sepam 2000.N.B.DPC: detection of plugged connectors.CDG: watchdog.
![Page 24: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/24.jpg)
24 Busbar differential
Differential protection
CHECK ZONE
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
Sepam 2000W01
Sepam 100LD
+_
check zone
5A3
5A47A8
7A7O22
I2
5A9
5A6 O1
check zone
1A8
1A7
0A8
0A7
1A5
1A6O2
O1
![Page 25: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/25.jpg)
25Busbar differential
Differential protection zone 1
Sepam 100LD
Sepam 2000W01
Sepam 100LD
Sepam 2000W01
zone1A8
1A7 1A6
1A5
O1
O2
Sepam 100LD
+_
check zone
0A8
0A7
6A16
6A135A3
5A47A8
7A7
O22
I2
I15
5A9
5A6
O1trippingcircuit breaker zone
![Page 26: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/26.jpg)
26 Busbar differential
Differential protectionzone 2
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
Sepam 100LD
Sepam 2000W01
Sepam 100LD
Sepam 100LD
Sepam 2000W02
zone 1
1A8
1A7 1A6
1A5
O1
O2
+_
check zone
0A8
0A7
1A6
1A5
0A8
0A7
7A16
7A136A16
6A135A3
5A47A8
7A7
O22
I2
I15
I25
O2
O1
1A7
1A8
zone 2
5A9
5A65A13
5A10
O1
O2
tripping circuit breaker zone 1
tripping circuit breaker zone 2
![Page 27: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/27.jpg)
27Busbar differential
Connection of logicinputs/outputs
ESB board
ESB
DPC21
20
19
17
16
13
12
11
5
O2
10
14
15
18
O1
9
8
7
6
4
3
2
1
l2
l1
CDG
A
ESTOR1 board
ESTOR
DPC21
20
O11
7
4
3
2
1
l12
l11
8
5
6
10
9
12
11
O12
O13
O14
13
19
17
16
18
14
15
l13
l14l15
l16
l17
l18
A
terminals connected data ESB board
19181716 watchdog1514
1312 O2 O2 = 0 zone 2 In service11 O2 = 1 zone 2 Out of service10
98 O1 O1 = 0 zone 1 or check zone In service7 O1 = 1 zone 1 or check zone Out of service6
4 I2 high impedance differential check zone operation3 (Sepam 100 LD check zone)
2 I1 Stop klaxon1
terminals connected data ESTOR1 board
19 I18 reserved
18 I17 reserved
17 I16 reserved
16 I15 high impedance differential zone 1 operation(Sepam 100 LD zone 1)
15 I14 zone 1 protection Out of service
14 I13 zone 1 protection In service
13 common
12 O14 inhibit CB closing in zone 1 (1)
11
10 O13 zone 1 tripping information9
8 O12 klaxon7
6 O11 short-circuit differential circuit zone 15
4 I12 reserved3
2 I11 busbar isolation closed (contact closed)1
N.B. The inputs are potential-free and require an external power supply source.
(1) O14: open contact = inhibit closing
![Page 28: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/28.jpg)
28 Busbar differential
terminals data connected to ESTOR219 I28 reserved18 I27 reserved17 I26 reserved16 I25 hight impedance differential operation zone 2
(Sepam 100 LD zone 2)15 I24 zone 2 protection out of service14 I23 zone 2 protection in service13 common12 O24 inhibit CB closing in zone 2 (1)
1110 O23 zone 2 tripping information98 O22 hight impedance differential acknowledgment7 (Sepam 100 LD)6 O21 short-circuit differential circuit zone 254 I22 fault acknowledgment32 I21 reserved for external synchronization1 of communication
ESTOR2 board
ESTOR
DPC21
20
O21
7
4
3
2
1
l22
l21
8
5
6
10
9
12
11
O22
O23
O24
13
19
17
16
18
14
15
l23
l24l25
l26
l27
l28
A
Nota : the inputs are potential-free and require an external power supply source.
(1) O24: open contact = inhibit closing.
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
![Page 29: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/29.jpg)
29Busbar differential
IntroductionThe communication option can be used to connect Sepam 2000 to a remote monitoringand control system equipped with a communication channel.c Jbus/Modbus (Modbus sub-group), master-slave protocol with a physical linkof the RS485 type in 2-wire mode (rate of 300 to 38400 bauds).
Communication
remote indications addresses
logic input status
logic output status
zone 1 trip counter C1
zone 2 trip counter C2
zone 1 In service KTS1
zone 1 Out of service KTS2
zone 2 In service KTS3
zone 2 Out of service KTS4
zone 1 tripping KTS5
zone 2 tripping KTS6
wiring fault phase 1 zone 1 KTS7
wiring fault phase 2 zone 1 KTS8
wiring fault phase 3 zone 1 KTS9
wiring fault phase 1 zone 2 KTS10
wiring fault phase 2 zone 2 KTS11
wiring fault phase 3 zone 2 KTS12
stop klaxon KTS13
Sepam not reset KTS36
disturbance recording storage KTS50
remote setting not activated KTS51
Communnication tableMERLIN GERIN
remote control orders addresses
zone 1 In service KTC33
zone 1 Out of service KTC34
fault acknowledgment (RESET) KTC35
zone 2 In service KTC36
zone 2 Out of service KTC37
stop klaxon KTC38
disturbance recording storage KTC50
automatic disturbance KTC51recording triggering
manual disturbance KTC52recording triggering
remote reading - remote setting
protection function curves, set points, time delays,angles...
program logic time delays
![Page 30: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/30.jpg)
30 Busbar differential
Electrical characteristics
Environmental characteristics
analog inputs
current transformer TC 1 A < 0.001 VA10 A to 6250 A ratings TC 5 A < 0.025 VA
voltage transformer 100 à 120 V > 100 kΩ220 V to 250 kV ratings
logic inputs
voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
consumption 10 mA 10 mA 4 mA
logic outputs (relays)
voltage 24/48 Vdc 127 Vdc 220 Vdc
rated current 8 A 8 A 8 A
breaking capacity: DC resistive load 4 A 0.7 A 0.3 A
AC resistive load 8 A 8 A 8 A
auxiliary power supply
DC voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
consumption when de-activated 18 W 19.5 W 21 W
“ ” marking on our products guarantees their compliance with European directives.
dielectric
power frequency CEI 60255-5 2 kV - 1 mn
climatic
operation CEI 60068-2 - 5 °C to 55 °Cstorage CEI 60068-2 - 25 °C to 70 °C
damp heat CEI 60068-2 95% to 40 °Ceffect of corrosion CEI 60654-4 class I
mechanical
degree of protection CEI 60529 IP 51 on front panel
vibrations CEI 60255-21-1 class I
shocks CEI 60255-21-2 class I
fire CEI 60695-2-1 glow wire
electromagnetic
radiation CEI 60255-22-3 class X 30 V/m
electrostatic discharge CEI 60255-22-2 class III
electrical
1.2/50 ms impulse wave CEI 60255-5 5 kV
1 MHz damped oscillating wave CEI 60255-22-1 class III
5 ns fast transients CEI 60255-22-4 class IV
Current circuit monitoring / use of busbar differential protection:Sepam 2000 W (cont’d)
![Page 31: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/31.jpg)
31Busbar differential
Installation Dimensions and weights
201
20 300
222
mounting latches (x2)
th = 3 mm max.
Standard Sepam (S36) Cut-out
weight: 9 kg
type wiring accessoriesreference type
current transformers screw for Ø 4 i 6 mm2 CCA 660 (1) connecteureye lug
CSH sensors screw i 2,5 mm2 CCA 606 (1) connecteur
voltage transformers vis i 2,5 mm2 CCA 608 (1) connecteur
temperature sensors vis i 2,5 mm2 CCA 621 (1) connecteur
logic inputs/outputs vis i 2,5 mm2 CCA 621 (1) connecteur
power supply vis i 2,5 mm2 CCA 604 (1) connecteur
Jbus/Modbus communication 9-pin sub-D CCA 602 cable (length: 3 m)connector with 2 9-pin sub-D
connectors
CCA 619 9-pin sub-Dconnector box
352 338
222 202
Sepam (S36) rear face withstandard connectors.
(1) accessories supplied with Sepam.
Connections
![Page 32: Protection and control HV/MV substation Sepam range · PDF file · 2009-07-17HV MV presentation 2 Sepam 100 LD high impedance differential protection 4 determination of sensors 6](https://reader031.vdocuments.us/reader031/viewer/2022022500/5aa337997f8b9ab4208e0aa4/html5/thumbnails/32.jpg)
32 Busbar differential
Sepam 2000Sepam type (1) .............................................................................................
Quantity .......................................................................................................(1) example: W01
Ordering information
Communication ......................................................... none ..................................
..................................................................................... Jbus/Modbus .....................
Working language ..................................................... French ...............................
..................................................................................... English ..............................
..................................................................................... Spanish .............................
..................................................................................... Italian ................................
Auxiliary power supply ............................................. 24/30 Vdc ..........................
..................................................................................... 48/127 Vdc ........................
..................................................................................... 220/250 Vdc ......................
Options
AccessoriesPocket terminal ............................................................ TSM 2001 .............
Setting software with PC connection kit ..................... SFT 2801 ..............
AInterposing ring CTfor residual current input ............................................. CSH 30 ..................
Jbus/Modbus communicationc 9-pin sub-D connector box ....................................... CCA 619 ................c Jbus/Modbus network connection box .................... CCA 609 ................c cable (length: 3 m) with two 9-pinsub-D connectors ........................................................ CCA 602 ................c RS485/RS232 interface box .................................... ACE 909 ................
quantity
Sepam 100 S01 LD(supplied with connectors and mounting latches)
Quantity: ..........................................
Rated frequency: 50 Hz ................................
60 Hz ................................
Version: single-phase .....................
3-phase .............................
Auxiliary power supply: 24 à 30 Vdc ......................
48 à 125 Vdc ....................
220 à 250 Vdc ..................
100 à 127 Vac ..................
220 à 240 Vac ..................
Stabilizing plate
Resistor 68 Ω - 280 W ........................
150 Ω - 280 W ......................
270 Ω - 280 W ......................
470 Ω - 180 W ......................
680 Ω - 180 W ......................
quantity
Surge limiter
Single module: ..............................................
Triple module: ..............................................
quantity
02 / 1999PCRED398037ENART.06800
This document has beenprinted on ecological paper.
Schneider Electric SA Postal addressF-38050 Grenoble cedex 9Tel: 33 (0)4 76 57 60 60Telex: merge 320842 Fhttp://www.schneider-electric.com
As standards, specifications and designs change fromtime to time, please ask for confirmation of the informationgiven in this publication.
Publishing: Schneider Electric SADesign, production: IdraPrinting:Rcs Nanterre B 954 503 439