PROJECT 5004 - 166 WOODWARD AVENUE, NORWALK, CT COMMUNITY DEVELOPMENT BLOCK GRANT DISASTER RECOVERY PROGRAM SCATTERED SITE REHABILITATION AND REBUILDING CONNECTICUT DEPARTMENT OF HOUSING HARTFORD, CONNECTICUT 06118 STREET VIEW DRAWING INDEX SHEET NUMBER GENERAL NOTES: MCA PROJECT 5004 166 WOODWARD AVENUE NORWALK, CONNECTICUT 06854 TITLE SHEET SHEET TITLE

Upload: truongbao

Post on 24-May-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

PROJECT 5004 - 166 WOODWARD AVENUE, NORWALK, CT

COMMUNITY DEVELOPMENT BLOCK GRANTDISASTER RECOVERY PROGRAM

SCATTERED SITE REHABILITATION AND REBUILDINGCONNECTICUT DEPARTMENT OF HOUSING

HARTFORD, CONNECTICUT 06118

STREET VIEW

DRAWING INDEXSHEET NUMBER

GENERAL NOTES:

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

TITLE SHEET

SHEET TITLE

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

IMPROVEMENT PLAN

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

SOIL EROSION ANDSEDIMENT CONTROL/

DEMOLITION PLAN

SOIL EROSION AND SEDIMENT CONTROL/DEMOLITION NOTES:

LEGEND

GENERAL NOTES

WORK NOTES

LEGEND

GENERAL NOTES

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

GENERAL NOTESAND SITE PLAN

WORK NOTES

LEGEND

GENERAL NOTES

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

BUILDING UTILITY PLAN

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

SOIL EROSION ANDSEDIMENT CONTROL

DETAILS

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

MISCELLANEOUSSITE DETAILS

GENERAL NOTES

SOIL EROSION AND SEDIMENT CONTROL/DEMOLITION NOTES

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

EXISTING BUILDINGELEVATIONS

EXISTING CONDITIONSWEST ELEVATION

EXISTING CONDITIONSNORTH ELEVATION

PROPOSED CONDITIONSWEST ELEVATION

PROPOSED CONDITIONSSOUTH ELEVATION

GENERAL NOTES

WORK NOTES

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

PROPOSED BUILDINGELEVATIONS

MCA PROJECT 5004166 WOODWARD AVENUE

NORWALK, CONNECTICUT 06854

DECK AND STAIRDETAILS

WFCM-2001 WOOD FRAME CONSTRUCTION MANUAL FOR ONE- AND TWO-FAMILY DWELLINGS4.

NATIONAL DESIGN SPECIFICATION (NDS-05) FOR WOOD CONSTRUCTION3.

ACI 318-08 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE2.

2005, 2009 and 2013 MODIFICATIONS AND SUPPLEMENTS)

2005 STATE OF CONNECTICUT RESIDENTIAL BUILDING CODE (IRC 2009 WITH CONNECTICUT 1.

GOVERNING DESIGN CODES

GENERAL NOTES

SERVICEABILITY OR PERFORMANCE OF THE COMPLETED STRUCTURE.

OR ANY OTHER TEMPORARY CONDITION SHALL NOT ADVERSELY AFFECT THE

CONSTRUCTION LOADS IMPOSED, THE ADDITION OR REMOVAL OF TEMPORARY COMPONENTS 4.

THE WORK.

DESIGN LOADS AND THEIR EFFECTS ON ALL STRUCTURES THROUGHOUT THE PROGRESS OF

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DETERMINATION OF ALL CONSTRUCTION 3.

UNLESS INDICATED IN THE CONTRACT DOCUMENTS.

TEMPORARY SUPPORTS, OR FOR THE TEMPORARY USE OF INCOMPLETE STRUCTURES,

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN OF TEMPORARY STRUCTURES, 2.

ACCORDANCE WITH ASCE 37-02 "DESIGN LOADS ON STRUCTURES DURING CONSTRUCTION."

LOADS, AND THE EFFECTS THEREOF, ON STRUCTURES DURING CONSTRUCTION SHALL BE IN

DETERMINATION OF DEAD LOADS, LIVE LOADS, ENVIRONMENTAL LOADS, CONSTRUCTION 1.

LOADS ON STRUCTURES DURING CONSTRUCTION

AND ALL APPLICABLE LOCAL, STATE AND FEDERAL REGULATIONS.

ALL WORK SHALL BE IN ACCORDANCE WITH THE STATE OF CONNECTICUT BUILDING CODE 2.

METHODS, TECHNIQUES, AND PROCEDURES FOR WORK UNDER HIS CONTRACT.

THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, 1.

GENERAL

FLOOR LIVE LOADS

DESIGN LOADS

30BEDROOM SPACES

ALL OTHER SPACES 40

OCCUPANCY / USE

(psf)

UNIFORM

ATTICS W/ STORAGE 20

1.0THERMAL FACTOR, Ct:

1.0SNOW LOAD IMPORTANCE FACTOR, Is:

1.0SNOW EXPOSURE FACTOR, Ce:

30 psfMINIMUM ROOF SNOW LOAD:

21 psfFLAT-ROOF SNOW LOAD, Pf:

30 psfGROUND SNOW LOAD, Pg:

ROOF SNOW LOADS: (IBC-02 SECTION 1608)

-0.18

+0.18INTERNAL PRESSURE COEFFICIENTS:

CBUILDING EXPOSURE CATEGORY:

1.0WIND LOAD IMPORTANCE FACTOR, Iw:

110 mphBASIC WIND SPEED (3 sec GUST):

WIND DESIGN DATA: (IBC-02 SECTION 1609)

SEISMIC DESIGN CATEGORY: B

BALCONIES (100 s.f. OR LESS) 60

36" SCOUR @ COLUMNS

12" EROSIONEROSION AND SCOUR DEPTHS:

7 ftBASE FLOOD DEPTH:

8.75 ft / secWATER VELOCITY:

EL. 14'DESIGN FLOOD ELEVATION:

AEFLOOD HAZARD AREA ZONE:

HYDROSTATIC PRESSURE AND FLOOD LOADS:

AND SIZE OF CONNECTORS PER THE MANUFACTURER'S PUBLISHED INSTRUCTIONS.

ALL CONNECTORS SHALL BE INSTALLED USING THE MANUFACTURER'S REQUIRED QUANTITY 4.

SIMPSON STRONG-TIE OR BETTER WHEN IN CONTACT WITH PRESSURE-TREATED LUMBER.

ALL CONNECTORS (JOIST HANGERS, TIES, STRAPS, ETC.) SHALL HAVE A "Z-GALV" FINISH BY 3.

FASTENERS BY SIMPSON STRONG-TIE MAY BE SUBSTITUTED WITH PRIOR APPROVAL.

CONTACT WITH PRESSURE-TREATED LUMBER. ALTERNATELY, "Z-GALV" FINISHED

ALL NAILS, SCREWS, AND OTHER FASTENERS SHALL BE STAINLESS STEEL WHEN IN 2.

SPECIAL ORDERING AND MAY HAVE LONG LEAD TIMES.

SUPPORT CONDITIONS. JOIST HANGERS AND OTHER METAL FABRICATIONS MAY REQUIRE

REQUIRED OR INDICATED, SHALL BE OF APPROPRIATE SIZE AND TYPE FOR MEMBERS AND

JOIST HANGERS, COLUMN CAPS OR BASES, AND OTHER METAL FABRICATIONS, AS 1.

STRUCTURAL WOOD CONNECTORS

SUBSTITUTION PRIOR TO INSTALLATION.

THE DESIGNER OF RECORD SHOULD EVALUATE AND GIVE WRITTEN APPROVAL FOR

LOAD CAPACITY BASED ON RELIABLE PUBLISHED TESTING DATA OR CALCULATIONS.

REQUIREMENTS OF THE DESIGN. BEFORE SUBSTITUTING ANOTHER BRAND, CONFIRM

SIMPSON STRONG-TIE CONNECTORS ARE SPECIFIED TO MEET THE STRUCTURAL

COMMENT.

IMMEDIATELY REPORTED TO MARTINEZ, COUCH & ASSOCIATES FOR REVIEW AND

FIELD. ANY DISCREPANCIES OR VARIATIONS FROM DRAWINGS SHALL BE

"V.I.F." INDICATES CONTRACTOR SHALL VERIFY THE IDENTIFIED CONDITION IN THE1.

LEGEND

50-deg F.MEAN ANNUAL TEMPERATURE:

1,500 OR LESSAIR-FREEZING INDEX:

TBD LOCALLY - SEE BELOWFLOOD-HAZARD:

REQUIREDICE SHIELD UNDERLAYMENT:

7-deg F.WINTER DESIGN TEMPERATURE:

SLIGHT TO MODERATEDECAY:

MODERATE TO HEAVYTERMITE:

42 INCHES MINIMUMFROST LINE DEPTH:

SEVEREWEATHERING:

SUBJECT TO DAMAGE FROM:

OTHER DESIGN DATA:

BEAMS, COLUMNS 2"

CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:

BARS LARGER THAN #5 2"

CONCRETE PLACED IN FORMS BUT EXPOSED TO WEATHER:

CONCRETE PLACED AGAINST EARTH 3"

MINIMUM CONCRETE PROTECTION FOR REINFORCING UNLESS OTHERWISE NOTED SHALL BE:6.

CONCRETE CURING PROCEDURES SHALL BE IN ACCORDANCE WITH ACI 301.5.

AND THE CONCRETE REINFORCING STEEL INSTITUTE RECOMMENDATIONS.

ALL REINFORCING BARS SHALL BE FABRICATED AND PLACED IN ACCORDANCE WITH ACI 315 4.

ALL CONCRETE REINFORCEMENT SHALL BE EPOXY COATED.3.

MAY BE GRADE 40.

ALL REINFORCING BARS SHALL CONFORM TO ASTM A615, GRADE 60, EXCEPT TIES, WHICH 2.

REQUIREMENTS FOR STRUCTURAL CONCRETE," LATEST EDITION.

ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 318 "BUILDING CODE 1.

CONCRETE

GALVANIZED IN ACCORDANCE WITH ASTM A123 AFTER FABRICATION.

ALL STRUCTURAL STEEL AND STRUCTURAL STEEL HARDWARE SHALL BE HOT DIPPED 8.

AMERICAN WELDING SOCIETY (AWS D1.1)

PRESCRIBED IN THE "STANDARD CODE OF WELDING IN BUILDING CONSTRUCTION" OF THE

ALL WELDS SHALL BE MADE ONLY BY WELDERS WHO HAVE BEEN QUALIFIED AS 7.

THE DRAWINGS.

STEEL COLUMNS SHALL BE SET ON CONCRETE OR STEEL UNLESS OTHERWISE SHOWN ON 6.

ANCHOR BOLTS SHALL CONFORM TO ASTM A-449 WITH D-4 NUTS AND F-436 WASHERS.5.

STRENGTH BOLTS UNLESS NOTED OTHERWISE.

ALL STRUCTURAL STEEL BOLTED CONNECTIONS SHALL BE MADE WITH ASTM A325 HIGH 4.

HSS SECTIONS SHALL CONFORM TO ASTM A500 GRADE B, GR. 46.d.

ANGLES AND PLATES SHALL CONFORM TO ASTM A-36.c.

INDICATED.

M-, S-, C-, AND MC-SHAPES SHALL CONFORM TO ASTM A-36 OR ASTM A-572, GR. 50 AS b.

W-SHAPES SHALL CONFORM TO ASTM A-992.a.

ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:3.

WITH THE LATEST PROVISIONS OF THE AISC MANUAL OF STEEL CONSTRUCTION.

STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE 2.

THE AISC MANUAL OF STEEL CONSTRUCTION.

ALL STRUCTURAL STEEL IS DESIGNED ACCORDING TO THE LATEST PROVISIONS OF AISC 1.

(GENERAL)STRUCTURAL STEEL

INSTRUCTIONS. RECTANGULAR HOLES ARE NOT PERMITTED IN W.P.S.L. MEMBERS.

HOLES ARE PERMITTED ONLY AS ALLOWED BY MANUFACTURER'S PUBLISHED 6.

W.P.S.L. MEMBERS SHALL NOT BE NOTCHED WITHOUT ENGINEER'S PRIOR APPROVAL.5.

BY WEYERHAEUSER. ALTERNATE PRODUCTS SHALL MEET OR EXCEED PROPERTIES LISTED.

E = 1 460 000 psi. DESIGNS ARE BASED ON "PARALLAM PLUS" LUMBER AS MANUFACTURED

FOLLOWING MINIMUM PROPERTIES FOR SERVICE LEVEL 2: Fb = 1827 psi Fv = 197 psi

"W.P.S.L." INDICATES WOLMANIZED PARALLEL STRAND LUMBER AND SHALL HAVE THE 4.

INSTRUCTIONS. RECTANGULAR HOLES ARE NOT PERMITTED IN LVL MEMBERS.

HOLES ARE PERMITTED ONLY AS ALLOWED BY MANUFACTURER'S PUBLISHED 3.

LVL MEMBERS SHALL NOT BE NOTCHED WITHOUT ENGINEER'S PRIOR APPROVAL.2.

SHALL MEET OR EXCEED THE PROPERTIES LISTED.

"VERSALAM" LUMBER AS MANUFACTURED BY BOISE CASCADE, LLC. ALTERNATE PRODUCTS

PROPERTIES: Fb = 3100 psi Fv = 285 psi E = 2 000 000 psi. DESIGNS ARE BASED ON

"LVL" INDICATES LAMINATED VENEER LUMBER AND SHALL HAVE THE FOLLOWING MINIMUM 1.

ENGINEERED WOOD PRODUCTS

CONCRETE MIX DESIGN SHALL CONFORM TO ACI CODE 4.2.1 EXPOSURE CATEGORY C, CLASS C2.10.

COLUMNS.

RECOMMENDED SLUMP IS 3" (±1/2") AT GRADE BEAMS & FOOTINGS, AND 4" (±1/2") AT CONCRETE 9.

(±1%) ABOVE GRADE. A MAXIMUM WATER/CEMENT RATIO OF 0.40

psi MINIMUM 28-DAY COMPRESSIVE STRENGTH. AIR ENTRAINMENT: 5 to 7% (±1%) BELOW GRADE; 3 to 5%

DESIGN MIXES SHALL PROVIDE NORMAL WEIGHT CONCRETE WITH THE FOLLOWING PROPERTIES: 5,000 8.

NOT PERMITTED.

CHLORIDE IONS WHICH WILL EXCEED THE MAXIMUM TOTAL CONCENTRATIONS SPECIFIED HEREIN ARE

PROHIBITED ADMIXTURES: CALCIUM CHLORIDE THYOCYANATES OR ADMIXTURES CONTAINING 7.

CONCRETE CONSTRUCTION ALONG THE COAST.

MATERIAL) OF THE REQUIRED PORTLAND CEMENT. FEMA RECOMMENDS THE ADDITION OF FLY ASH FOR

6.0%. FLY ASH MAY BE USED TO REPLACE UP TO A MAXIMUM OF 25% (BY MASS OF CEMENTITIOUS

FLY ASH: ASTM C 618, CLASS C or CLASS F. LOSS ON IGNITION FOR EITHER CLASS SHALL NOT EXCEED 6.

PERCENT CHLORIDE IONS.

WATER-REDUCING ADMIXTURE: ASTM C 494, TYPE A, D, E, OR F, CONTAINING NOT MORE THAN 0.1 5.

AIR-ENTRAINING MIXTURE: ASTM C 260.4.

WATER: POTABLE AND COMPLYING WITH ASTM C 94.3.

OF THE MINIMUM CLEAR SPACE BETWEEN REINFORCING BARS.

ONE-FIFTH THE DISTANCE BETWEEN FORMS, ONE-THIRD THE DEPTH OF SLABS, NOR THREE-FOURTHS

COARSE AGGREGATE SHOULD BE WASHED AND GRADED. AGGREGATE SIZE SHALL NOT EXCEED

NORMAL WEIGHT AGGREGATES: ASTM C 33. SAND SHALL BE CLEAN AND FREE OF CONTAMINANTS. 2.

PORTLAND CEMENT: ASTM C 150, TYPE 1.1.

CONTRIBUTIONS FROM WATER, AGGREGATES, CEMENTITIOUS MATERIALS, AND ADMIXTURES.

EXCEED 0.30 PERCENT (0.003) BY WEIGHT OF CEMENT. THIS INCLUDES, BUT IS NOT LIMITED TO,

NOTE: MAXIMUM WATER SOLUBLE CHLORIDE ION CONCENTRATIONS IN HARDENED CONCRETE SHALL NOT

CONCRETE MIX DESIGN

IRC 2003 CODE, AND AS AMENDED BY THE CONNECTICUT SUPPLEMENT.

NAILING SHALL BE IN ACCORDANCE WITH THE "FASTENING SCHEDULE" CONTAINED IN THE 3.

ALL LUMBER IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED.2.

CODE.

MINIMUM RETENTION MEETING OR EXCEEDING THE REQUIREMENTS OF THE BUILDING

E SHALL BE PRESSURE-TREATED SOUTHERN YELLOW PINE #2 OR BETTER, WITH A

WEATHER, WITHIN 8" OF SOIL, OR LESS THAN 18" FROM THE FLOOR OF A CRAWL SPAC

EXTERIOR EXPOSURE: ALL STRUCTURAL LUMBER EXPOSED TO MOISTURE, THE b.

MAY BE STUD GRADE.

WEATHER SHALL BE DOUG FIR #2 OR BETTER. UNLESS NOTED OTHERWISE, STUDS

INTERIOR EXPOSURE: ALL STRUCTURAL LUMBER PROTECTED FROM MOISTURE AND a.

FOLLOWING MINIMUM PROPERTIES:

UNLESS OTHERWISE SHOWN IN THE DRAWINGS, STRUCTURAL LUMBER SHALL HAVE THE 1.

STRUCTURAL LUMBER

D698 STANDARD PROCTOR.

BACK FILL SHALL BE PLACED IN 8" LIFTS AND COMPACTED TO 95% COMPACTION AS PER ASTM 5.

NO CONCRETE SHALL BE PLACED IN WATER OR ON FROZEN GROUND.4.

COMPACTED MATERIAL TO THE REQUIRED BOTTOM OF FOOTING ELEVATIONS.

SOIL FROM BELOW THE PROPOSED STRUCTURE FOUNDATION AND PLACE APPROVED

IF UNSATISFACTORY SOIL IS ENCOUNTERED, REMOVE ALL UNSATISFACTORY3.

ALL FOOTING ELEVATIONS MEET THESE CRITERIA.

MINIMUM OF 4'-0" BELOW FINISHED GRADE ELEVATIONS. THE CONTRACTOR SHALL VERIFY

FOOTINGS SHALL EXTEND A MINIMUM OF 2'-0" BELOW EXISTING GRADE ELEVATIONS AND A 2.

INORGANIC SOIL OR PREPARED FOOTING BASE MATERIAL.

10-13-2014, FOR A BEARING VALUE OF 3000 psf AND SHALL BEAR ON NATIVE UNDISTURBED,

FOUNDATIONS ARE DESIGNED AS PER THE GEOTECHNICAL ENGINEER REPORT DATED 1.

FOUNDATION

RE-SURVEYED AND REPORTED PRIOR TO FINAL INSPECTION.

BOTTOM OF THE LOWEST HORIZONTAL STRUCTURAL MEMBER ELEVATION SHALL BE 2.

& 323.1.9)

PRIOR TO ANY FURTHER VERTICAL CONSTRUCTION PROCEEDING. (IRC-02 SECTIONS 109.1.3

SURVEYED AND REPORTED TO AND APPROVED BY THE REGISTERED DESIGN PROFESSIONAL

BOTTOM OF THE LOWEST HORIZONTAL STRUCTURAL MEMBER ELEVATION SHALL BE 1.

MARTINEZ, COUCH & ASSOCIATES, LLC SHALL CERTIFY BUILDING ELEVATIONS AS FOLLOWS:

CERTIFICATION OF ELEVATION

RIFAT H. SALEH, P.E.

NORWALK, CONNECTICUT 06855

166 Woodward Avenue

PROJECT 5004

5004

CHKREVISIONSDATENO. BY APPV

AND SEAL

WITHOUT A LIVE SIGNATURE

THIS MAP IS NOT VALID

1084 Cromwell Avenue, Suite A-2

Rocky Hill, CT 06067

Telephone: (860) 436-4364

Fax: (860) 436-4626

www.martinezcouch.com

MCADRAWN BY: CHECKED BY: SCALE: DATE:ELR/TOD RHS AS NOTED

RHS Design, LLC

Consulting

ENGINEERS - DEVELOPERS - CONSTRUCTION MANAGERS

250 WOLCOTT RD., WOLCOTT, CT 06716

TEL. 203-879-2065 - FAX 203-879-2952

GENERAL NOTES

JOB NO.

1

DRAWING NO. SHEET

S-12-16-2015

ISSUED FOR PERMITTING03/06/151 AMM AMM RHS

3'-6" ± VIF 6'-10 3/4" ± VIF 17'-1 1/2" ± VIF 10'-7 3/4" ± VIF 8'-5 1/4" ± VIF 3'-6" ± VIF 3'-6" ± VIF

0.2

A

0.4

0.6

1

2

3

3.2

3.4

3.6

A.2

A.6

A.9

B

A

A.4

A.7

A.8

B

8'-0" ± VIF

2'-3 5/8" ± VIF

1'-10 7/8" ± VIF

2'-0" ± VIF

A.1

2.5

A.5

A.4.5

2'-0"

VIF

6'-8" ± VIF

7'-10" ± VIF

3'-6 1/8" ± VIF

4'-8 3/8" ± VIF

A.7.2

3'-9"VIF

3'-6"VIF

7'-3"VIF

4'-4 3/4 "4'-6"

1

S-2

PROPOSED FOUNDATION PLAN

1/4" = 1'-0"

RIFAT H. SALEH, P.E.

NORWALK, CONNECTICUT 06855

166 Woodward Avenue

PROJECT 5004

5004

CHKREVISIONSDATENO. BY APPV

AND SEAL

WITHOUT A LIVE SIGNATURE

THIS MAP IS NOT VALID

1084 Cromwell Avenue, Suite A-2

Rocky Hill, CT 06067

Telephone: (860) 436-4364

Fax: (860) 436-4626

www.martinezcouch.com

MCADRAWN BY: CHECKED BY: SCALE: DATE:ELR/TOD RHS AS NOTED 17 FEB 2015

RHS Design, LLC

Consulting

ENGINEERS - DEVELOPERS - CONSTRUCTION MANAGERS

250 WOLCOTT RD., WOLCOTT, CT 06716

TEL. 203-879-2065 - FAX 203-879-2952

3

S-4

TYP. @

16" COLS

TYP. U.O.N.

16"x16" CONC. COL.

18"x18" CONC. COL.

18"x18" CONC. COL.

18"x18" CONC. COL.

18"x18" CONC. COL.

18"x18" CONC. COL.

6

S-4

TYP.

GRADE BM.

TYP. U.O.N.

16"x16" CONC. COL.

CONC. COL.

18"x18"

18"x18" CONC. COL.

CONC. COL.

18"x18"

2 S-2

JOB NO. DRAWING NO. SHEET

FOUNDATION PLAN

CONC. COL.

18"x18"

CONC. COL.

18"x18"

S-4

8

MARTINEZ, COUCH & ASSOCIATES, LLC AND THEIR CONSULTANTS.

AND ALL OF UNSATISFACTORY SOILS AS REQUIRED FOR NEW CONSTRUCTION APPROVED SITE BY

IT IS THE CONTRACTOR RESPONSIBILITY TO DEMOLISH AND DISPOSE OF EXISTING FOUNDATION 8.

SEE GENERAL NOTES ON SHEET S-1 FOR ADDITIONAL INFORMATION.7.

VERIFICATION.

SHALL OCCUR BASED ON THE DIMENSIONS SHOWN ON THESE DRAWINGS WITHOUT PRIOR FIELD

. NO FABRICATION CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO ORDER OF MATERIALS6.

.ENGINEER OF RECORD

WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL GRADE BEAMS ARE NOT PERMITTED

COORDINATE NEW CONSTRUCTION WITH EXISTING UTILITIES. PENETRATIONS IN COLUMNS AND 5.

MATERIAL IN LIFTS -- SEE GENERAL NOTES.

FILL RESULTING EXCAVATED AREAS WITH APPROVED, SATISFACTORY SOIL. PLACE AND COMPACT 4.

PROOF ROLL OR COMPACT BOTTOM OF RESULTING EXCAVATED AREAS FOLLOWING DEMOLITION.3.

BASEMENT SLABS PRIOR TO INSTALLATION OF PROPOSED NEW FOUNDATION ELEMENTS.

UNLESS OTHERWISE NOTED, DEMOLISH COMPLETELY ALL EXISTING FOOTINGS, FOUNDATIONS, AND 2.

"DEMOLISH" INDICATES "DEMOLISH AND LEGALLY DISPOSE OF FROM THE SITE..."1.

FOUNDATION NOTES:

1 03/06/15 ISSUED FOR PERMITTING AMM AMM RHS

3x8 (TYP) 3x8 (TYP)

3x8 SILL PL.

4x3 JOIST

2x6 (TYP)

4x3 JOIST

3x8 HEADER

2x6

15'-3"

1'-

4"

11 3/

4"

8'-

2"

2'-

9"

24'-

0"

26'-

8"

2'-

9"

8'-

6 1/

2"

9 3/

4"

1'-

4"

9'-4" 3'-4" 2'-7"

4'-0"

2'-4" 2'-9"

28'-10"

1'-3"

11'-0"

5"

12'-

9 1/

2"

1'-

8"

4'-

10"

4'-

2"

12'-

0"

5'-11"

4 1/

2"

7'-7"

7'-9"

7'-7"

1'-

11"

22'-

10"

1'-

11"

3'-6" ± VIF 6'-10 3/4" ± VIF 17'-1 1/2" ± VIF 10'-7 3/4" ± VIF 8'-5 1/4" ± VIF 3'-6" ± VIF 3'-6" ± VIF

0.2

A

0.4

0.6

1

2

3

3.2

3.4

3.6

A.2

A.6

A.9

B

A

A.4

A.7

A.8

B

8'-0" ± VIF

W12x45

W12x45

W12x45

W6x25

W12x45 W

6X25

(4) 2x6

(4) 2x6

(3) 2x10

2x8 @ 16" o.c.

MA

X

2x8 @ 16" o.c.

MA

X

(3) 2x10

2'-3 5/8" ± VIF

1'-10 7/8" ± VIF

2'-0" ± VIF

A.1

2.5

W6X25

W6X25

A.5

A.4.5

2'-0"

VIF

6'-8" ± VIF

7'-10" ± VIF

3'-6 1/8" ± VIF

4'-8 3/8" ± VIF

(3) 2x10

2X8 @ 16" O.C.

2X8 @ 16"

O.C.

A.7.2

3'-9"VIF

3'-6"VIF

7'-3"VIF

4'-4 3/4 "4'-6"

EL. 10.0'±

EL. 4.0'±

EL. 2.57'±

EL. 6.57'±

EL. 11.7'

EL. 14.75'

EL. 16.75'

EL. 15.75'

EL. 16.25'

1

S-3

EXISTING FRAMING

AND DEMOLITION PLAN

1/4" = 1'-0"

RIFAT H. SALEH, P.E.

NORWALK, CONNECTICUT 06855

166 Woodward Avenue

PROJECT 5004

5004

CHKREVISIONSDATENO. BY APPV

AND SEAL

WITHOUT A LIVE SIGNATURE

THIS MAP IS NOT VALID

1084 Cromwell Avenue, Suite A-2

Rocky Hill, CT 06067

Telephone: (860) 436-4364

Fax: (860) 436-4626

www.martinezcouch.com

MCADRAWN BY: CHECKED BY: SCALE: DATE:ELR/TOD RHS AS NOTED 16 FEB 2015

RHS Design, LLC

Consulting

ENGINEERS - DEVELOPERS - CONSTRUCTION MANAGERS

250 WOLCOTT RD., WOLCOTT, CT 06716

TEL. 203-879-2065 - FAX 203-879-2952

3

S-3

PROPOSED FRAMING PLAN

1/4" = 1'-0"

9'-6 1/2"±

8'-11"±

8'-3"±

2

S-3

EXISTING FRAMING

AND DEMOLITION SECTION

1/4" = 1'-0"

EXIST. BSMNT FLOOR

FOUNDATION (TYP)

DEMOLISH EXISTING

NEW W12x45

4

S-3

PROPOSED FRAMING & FOUNDATION SECTION

1/4" = 1'-0"

EXIST. 3X8 FRAMING EXIST. 2x6 FRAMING

EXIST. POST

DEMOLISH

NEW 16"x16" COL.S

NEW 18"x18" COL NEW 18"x18" COL NEW 18"x18" COL

NEW W12x45 NEW W12x45 NEW W6X25 NEW W6X25

NEW 6x6 POST (TYP)

NEW 6x6 POST (TYP)

SEE GENERAL NOTES ON SHEET S-1 FOR ADDITIONAL INFORMATION.4.

CONTRACTOR SHALL COORDINATE ALL WORK WITH THE HOUSE LIFTING CONTRACTOR.3.

. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS AS REQUIRED2.

"DEMOLISH" INDICATES "DEMOLISH AND LEGALLY DISPOSE OF FROM THE SITE..."1.

FRAMING NOTES:

S-5

4

FRAMING PLANS

7

S-5

NEW W6X25

JOB NO. DRAWING NO.

3

SHEET

S-3

EXIST. 3X8 FRAMING

NEW 16"x16" COL.

EL. 12.5'

LANDING EL. 12.5'

LANDING EL. 15.75'

DECK EL. 15.75'

16.25'

REAR ROOM PROP. EL. FLOOR EL. 16.75'

MAIN HOUSE PROP.

LANDING EL. 13.0'

LANDING EL. 16.25'

FOUNDATION

EXIST.

DEMOLISH

EL. 13.0'

1 03/06/15 ISSUED FOR PERMITTING AMM AMM RHS

(TYP.)

POWER BEAM HEADER

3 1/2"x16" ANTHONY

PROPOSED FRAMING PLAN OR APPROVED EQUAL.

USE 3 1/2"X16" POWER BEAM HEADER MANUFACTURED BY ANTHONY FOREST PRODUCTS AS SHOWN ON THE 5.

SEE GENERAL NOTES ON SHEET S-1 FOR ADDITIONAL INFORMATION.4.

ALL STRUCTURAL STEEL BEAMS SHOWN ARE CONTINUOUS, UNLESS OTHERWISE NOTED. 3.

THE DIMENSIONS SHOWN ON THESE DRAWINGS WITHOUT PRIOR FIELD VERIFICATION.

. NO FABRICATION SHALL OCCUR BASED ON CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS AS REQUIRED2.

.EXISTING STRUCTURE WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD

COORDINATE NEW CONSTRUCTION WITH EXISTING UTILITIES. DO NOT CUT, NOTCH, OR ALTER ANY NEW OR 1.

FRAMING NOTES:

OUTER BEAMS

FRAMING AND (2) 2X8

NEW 2X8 @ 12" O.C.

OUTER BEAMS

FRAMING AND (2) 2X8

NEW 2X8 @ 12" O.C.

1'-0" 1'-0"

2'-0"

FIN. GRADE

@ 10" o.c.

BA

LA

NC

E

MAINTAIN DOWEL POSITION

PROVIDE 3 SETS OF TIES TO

1'-4"

1'-

4"

CCOL.

CCOL.

(12) #5 CONT.

ELEV. FOR SPACING

#4 COL. TIES - SEE

4'-

0"

MIN

ON ALL CORNERS

" CHAMFER 43PROVIDE

3 1/

2"

3 1/

2"

(12) #5 CONT.

CGRADE BEAM

1'-

6"

o.c.

@ 3"

#4

TIE

S

1'-

6"

o.c.

@ 3"

#4

TIE

S

3

S-4

TYP. CANOPY & PATIO COLUMN DETAIL

3/4" = 1'-0"

6

S-4

3/4" = 1'-0"

3/4" PROCESSED STONE

5

S-4

TYPICAL TRENCHING LIMITS

NOT TO SCALE

4

S-4

TYPICAL GRADE BEAM

INTERSECTION REINFORCING DETAIL

NOT TO SCALE

1

S-4

TYPICAL GRADE BEAM

CORNER REINFORCING DETAIL

NOT TO SCALE

TYP

48 db

0"

48 db

MIN

MIN

@ ALL CONSTRUCTION JOINTS

MIN. BAR LAPS

CORNER BAR ZONE - PROVIDE

NO CONSTRUCTION JOINTS WITHIN

HORIZONTAL BARS

SAME SIZE AS

BENT CORNER BARS OF

0"

TYP

48 db

48 db

HORIZONTAL BARS

MIN

MIN

HORIZONTAL BARS

OF SAME SIZE AS

BENT CORNER BARS

CONSTRUCTION JOINTS

W/ MIN. LAPS @ ALL

JOINT - PROVIDE BENT BARS

OPTIONAL CONSTRUCTION

CUT IN THIS AREA

TRENCHES SHALL NOT BE

TR

EN

CH

45°

BETWEEN OPPOSING FACES

ANGLE (7 : 12 SLOPE)

SHALL NOT EXCEED A 30°

ADJACENT B/FTG ELEV.S

45°

30° MAX

2'-0"

2'-

0"

6"

6"

TYP

3" CLR

TOP & BOT.

(4) #6 CONT.

EA. FACE

(2) #6 CONT.

10" o.c. MAX

#4 TIES @

2" CLR

TYP

EL. 11.7'

ADJUST AS REQ'D

BEYOND

GRADE BEAM

SEE OTHER DETAILS

GRADE BEAM REINF. -

CCOL.

2

S-4

TYP. CANOPY & PATIO COLUMN REINFORCEMENT

3/4" = 1'-0"

1'-6" 1'-6"

3'-0"

2'-

0"

1'-

6"

@ 10" o.c.

BA

LA

NC

E

4'-

0"

MIN

(12) #5 CONT.

CGRADE BEAM

o.c.

@ 3"

#4

TIE

S

o.c.

@ 3"

#4

TIE

S

ON ALL CORNERS

" CHAMFER 43PROVIDE

8

S-4

TYP. EXTERIOR COLUMN DETAIL

3/4" = 1'-0"

ADJUST AS REQ'D

CCOL.

SEE OTHER DETAILS

GRADE BEAM REINF. -

BEYOND

GRADE BEAM

GRADE BEAM BEYOND

3'-

0"

3'-0" SECTION - SEE BELOW

ADD'L TOP & BOT BARS @

GR

AD

E

BE

AM

TERMINATION OF BEAM

REINFORCING AT

TURN UP/DN GRADE BEAM

OF 3'-0" SECTION

ADD'L #6 BARS AT EDGES

REINF. THRU INTERSECTIONS

CONTINUE GRADE BEAM

1'-6"

1'-

6"

CCOL.

CCOL.

(12) #5 CONT.

4"

4"

7

S-4

TYP. EXTERIOR COLUMN REINFORCEMENT

3/4" = 1'-0"

2" CLR

TYP

ELEV. FOR SPACING

#4 COL. TIES - SEE

MIN

3/4" PROCESSED STONE

MIN

ABOVE

COLUMN

FOR CLARITY

COLUMN REINF. NOT SHOWN

2'-

0"

1'-

6"

6"

2'-

0"

6"

8"

8"

3'-0"

FOR CLARITY

FOOTING REINFORCING NOT SHOWN

FOR CLARITY

FOOTING REINFORCING NOT SHOWN

EL. 14.75'

EL. 6.57' +/-

EL. 6.57' +/-

TYP. GRADE BEAM DETAIL

RIFAT H. SALEH, P.E.

NORWALK, CONNECTICUT 06855

166 Woodward Avenue

PROJECT 5004

5004

CHKREVISIONSDATENO. BY APPV

AND SEAL

WITHOUT A LIVE SIGNATURE

THIS MAP IS NOT VALID

1084 Cromwell Avenue, Suite A-2

Rocky Hill, CT 06067

Telephone: (860) 436-4364

Fax: (860) 436-4626

www.martinezcouch.com

MCADRAWN BY: CHECKED BY: SCALE: DATE:

FOUNDATION DETAILS

ELR/TOD RHS AS NOTED 16 FEB 2015

RHS Design, LLC

Consulting

ENGINEERS - DEVELOPERS - CONSTRUCTION MANAGERS

250 WOLCOTT RD., WOLCOTT, CT 06716

TEL. 203-879-2065 - FAX 203-879-2952 JOB NO. DRAWING NO.

4

SHEET

S-4

1 03/06/15 ISSUED FOR PERMITTING AMM AMM RHS

9

S-5

TYPICAL FRAMING DETAIL

AT PERIMETER COLUMN

3/4" = 1'-0"

PERIMETER

W12x45 AT HOUSE

SEE OTHER DETAILS

18" x 18" CONC. COL.

W12x45 BEYOND

CCOL.

AT PERIMETER COLUMNS

*SEE TYPICAL CONNECTION DETAIL

BRG PLATE

" STEEL43

1'-6"

C

C

9" 9"

(TYP.)

12" MIN. EMBED.

" ANCHOR BOLT43GALV. STEEL PL.

3/4"x16"x1'-4"

18"x18" CONC. COL

W12x45

W12x45

1 1/2"

TYP.1/4

TYP

CLIP CONNECTION

5/16" MIN THICK

1/4

4

S-5

TYPICAL FRAMING DETAIL

NOT TO SCALE

EXISTING FLOOR

S-5

TYPICAL FRAMING DETAIL

NOT TO SCALE

2

S-5

TYPICAL FRAMING DETAIL

AT MAIN CORNER COLUMN

3/4" = 1'-0"

PROVIDE 12" MIN. EMBED

ON BOTH SIDES (TYP) -

S.S. BOLTS & WASHERS

3/4" DIA.. MIN. GALV. OR

CCOL. & POST

" x 3" EA. SIDE43L8x4x

16"x16" CONC. COL.

WOOD POST

PROPOSED P.T. 6x6

6

S-5

NOT TO SCALE

3

S-5

NOT TO SCALE

SYSTEM

POST-INSTALLED ANCHOR

CCOL. & POST

EQUAL

SIMPSON STRONG-TIE OR

"ABU66" POST BASE BY

16"x16" CONC. COL.

WOOD POST

PROPOSED P.T. 6x6

1/4

1'-6"

9" 9"

GALV. STEEL PL.

3/4"x16"x1'-4"18"x18" CONC. COL

1 1/2"

C

TYP.

1'-

4"

(TYP.)

12" MIN. EMBED.

" ANCHOR BOLT43

C W6x25

1/4TYP

1/4

1

S-5

TYPICAL FRAMING DETAIL

3/4" = 1'-0"

8"

8"

SHEET S-3.

A.1 3 AND A.8 3. REFER TO

NOTE: THIS DETAIL APPLIES AT

3" (TYP.)

W6x25

1'-6"

9" 9"

GALV. STEEL PL.

3/4"x16"x1'-4"18"x18" CONC. COL

1 1/2"

C

TYP.

1'-

4"

(TYP.)

12" MIN. EMBED.

" ANCHOR BOLT43

C W6x25

1/4TYP

1/4

8"

8"

2" (TYP.)

W12x45

SHEET S-3.

A 2.5 AND B 2.5. REFER TO

NOTE: THIS DETAIL APPLIES AT

S-3.

A 2 AND B 2. REFER TO SHEET

NOTE: THIS DETAIL APPLIES AT

5

S-5

TYPICAL FRAMING DETAIL

3/4" = 1'-0"

1'-6"

9" 9"

GALV. STEEL PL.

3/4"x16"x1'-4"18"x18" CONC. COL

1 1/2"

C

TYP.

1'-

4"

(TYP.)

12" MIN. EMBED.

" ANCHOR BOLT43

C1/4

TYP

1/4

8"

8"

2" (TYP.)

W12x45

W12x45

S-3.

A 1 AND B 1. REFER TO SHEET

NOTE: THIS DETAIL APPLIES AT

PROPOSED (4) 2x6

ADD SOLID WOOD BLOCK

ADD SOLID WOOD BLOCKING

EXISTING BEAM TO REMAIN

8"

NEW 2x8 PLATE TOP & BOTTOM

TYPICAL FRAMING DETAIL AT DECK & CANOPY

REFER TO SHEET S-3.

A.4 3.4&A.7 3.4

A.8 3.2&A.9 0.6

A.6 0.6&A.6 0.4

A.6 0.4&A.4.5 0.6

A.4.5 0.4&A.2 0.6

THIS DETAIL APPLIES AT:

NOTE:

ALTERNATE FRAMING DETAIL AT DECK & CANOPY

REFER TO SHEET S-3.

A.4 3.4&A.7 3.4

A.8 3.2&A.9 0.6

A.6 0.6&A.6 0.4

A.6 0.4&A.4.5 0.6

A.4.5 0.4&A.2 0.6

THIS DETAIL APPLIES AT:

NOTE:

1'-6"

C

9" 9"

(TYP.)

12" MIN. EMBED.

" ANCHOR BOLT43GALV. STEEL PL.

3/4"x16"x1'-4"

18"x18" CONC. COL

W12x45

1/4

8

S-5

TYPICAL FRAMING DETAIL

3/4" = 1'-0"

A.5 2.5. REFER TO SHEET S-3.

NOTE: THIS DETAIL APPLIES AT

CW6x25

WASHER @ 3'-0" O.C. MAX.

BOLTS WITH NUTS AND

TOP PLATE. USE 1/2" GALV.

PROPOSED W6x25 WITH 2X6

SHEET S-3.

A.1 2.5 & A.8 2.5. REFER TO

NOTE: THIS DETAIL APPLIES AT

7

S-5

TYPICAL FRAMING DETAIL

NOT TO SCALE

CW6x25 PROPOSED (4) 2x6

WASHER @ 3'-0" O.C. MAX.

BOLTS WITH NUTS AND

TOP PLATE. USE 1/2" GALV.

PROPOSED W6x25 WITH 2X6

WASHER @ 3'-0" O.C. MAX.

BOLTS WITH NUTS AND

TOP PLATE. USE 1/2" GALV.

PROPOSED W6x25 WITH 2X6

PROPOSED 2x8 PLATE

EXISTING HEADERS TO REMAIN

EXISTING 2x6 TO REMAIN

EXISTING 2x6 TO REMAIN

10

EXIST. 4X3 STRINGERS

ENGINEER & SIMPSON STRONG-TIE REQUIREMENTS.

USE 10dx1-1/2 NAILS ONLY AT SINGLE 2x PLATES AND AS LIMITED BY 3.

USE 1/2" DIA.. BOLTS IN LIEU OF "TB" SCREWS WHEN REQUIRED.2.

"TB" SCREW USE SUBJECT TO SIMPSON STRONG-TIE LIMITATIONS.1.

NOTES:

S-3.

& A.8 2.5. REFER TO SHEET

THIS DETAIL APPLIES AT A.1 2.5

TYP.

L4X4X1/2 (TYP.)

CW6x25

SPACING REQUIREMENTS

OTHER DET.S FOR QUANTITY &

STRONG-TIE OR EQUAL - SEE

"TB" SCREWS BY SIMPSON

RIFAT H. SALEH, P.E.

NORWALK, CONNECTICUT 06855

166 Woodward Avenue

PROJECT 5004

5004

CHKREVISIONSDATENO. BY APPV

AND SEAL

WITHOUT A LIVE SIGNATURE

THIS MAP IS NOT VALID

1084 Cromwell Avenue, Suite A-2

Rocky Hill, CT 06067

Telephone: (860) 436-4364

Fax: (860) 436-4626

www.martinezcouch.com

MCADRAWN BY: CHECKED BY: SCALE: DATE:ELR/TOD RHS AS NOTED 17 FEB 2015

RHS Design, LLC

Consulting

ENGINEERS - DEVELOPERS - CONSTRUCTION MANAGERS

250 WOLCOTT RD., WOLCOTT, CT 06716

TEL. 203-879-2065 - FAX 203-879-2952

MISCELLANEOUS DETAILS

JOB NO. DRAWING NO. SHEET

S-55

1 03/06/15 ISSUED FOR PERMITTING AMM AMM RHS