profisafe field distributor · manual – drive system for decentralized installation - profisafe®...
TRANSCRIPT
Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services
Drive System for Decentralized PROFIsafe® Field Distributor
ManualEdition 05/200711381426 / EN
SEW-EURODRIVE – Driving the world
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 3
1 Valid Components.................................................................................................. 5
2 Important Notes...................................................................................................... 7
3 General Safety Notes ............................................................................................. 93.1 Safety notes for MOVIMOT® drives ............................................................................. 93.2 Supplementary safety notes for field distributors ....................................................... 10
4 Integrated Safety Technology ............................................................................ 114.1 PROFIsafe® field distributor safety concept............................................................... 114.2 Safety concept of the MOVIMOT® frequency inverter ............................................... 12
5 Safety Conditions................................................................................................. 145.1 Notes on stop categories ........................................................................................... 145.2 Installation requirements ............................................................................................ 165.3 External sensor and actuator requirements ............................................................... 175.4 Startup requirements ................................................................................................. 175.5 Operation requirements ............................................................................................. 17
6 Unit Design ........................................................................................................... 186.1 Fieldbus interfaces..................................................................................................... 186.2 Field distributor .......................................................................................................... 196.3 MOVIMOT® frequency inverter (integrated in field distributors Z.7/Z.8) .................... 22
7 Mechanical Installation........................................................................................ 237.1 Installation regulations ............................................................................................... 237.2 Field distributor .......................................................................................................... 24
8 Electrical Installation ........................................................................................... 288.1 Installation planning taking EMC aspects into account .............................................. 288.2 Installation regulations for field distributors ................................................................ 308.3 Connecting field distributors MFZ26, MFZ27, MFZ28 with MQS.. ............................. 358.4 Connecting safety-oriented inputs and outputs.......................................................... 378.5 Connecting standard inputs/outputs .......................................................................... 428.6 Bus connection with optional connection technology................................................. 448.7 Connecting prefabricated cables ............................................................................... 48
9 Startup with PROFIBUS (MQS) ........................................................................... 509.1 Startup procedure ...................................................................................................... 509.2 Project planning for MQS on PROFIBUS-DP with STEP7......................................... 54
10 Functionality of the PROFIBUS Interface MQS ................................................. 5910.1 Data exchange with MQS .......................................................................................... 5910.2 Integrated control function ......................................................................................... 6110.3 Default program ......................................................................................................... 6110.4 Control via PROFIBUS-DP ........................................................................................ 6110.5 Configuration via PROFIBUS-DP............................................................................... 6210.6 Configuration via PROFIBUS-DPV1 .......................................................................... 7110.7 Meaning of LED display ............................................................................................. 7910.8 Error states of the standard section ........................................................................... 8010.9 Error states in the safety section................................................................................ 8210.10 Diagnostics via PROFIBUS........................................................................................ 83
4 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
11 Supplementary Field Distributor Startup Information ...................................... 8511.1 Field distributor MQS.../Z.6. ....................................................................................... 8511.2 Field distributor MQS.../MM../Z.7. .............................................................................. 8611.3 Field distributor MQS.../MM../Z.8. .............................................................................. 8711.4 MOVIMOT® frequency inverter integrated in the field distributor............................... 89
12 MOVILINK® Unit Profile ....................................................................................... 9112.1 Coding of process data .............................................................................................. 9112.2 Sample program for Simatic S7 and fieldbus............................................................. 94
13 Parameters............................................................................................................ 9613.1 MQ.. parameter list .................................................................................................... 96
14 MOVIMOT® Diagnostics....................................................................................... 9814.1 Status LED................................................................................................................. 9814.2 Error table .................................................................................................................. 99
15 Error Tables for MQS ......................................................................................... 10115.1 Error table for the standard section.......................................................................... 10115.2 Error table for the standard section.......................................................................... 101
16 Technical Data .................................................................................................... 10316.1 Technical data for the PROFIBUS MQS.. interface ................................................. 10316.2 Technical data for field distributors .......................................................................... 106
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 5
1Valid Components
Handbuch1 Valid ComponentsBrief description The PROFIsafe® MQS.2F/Z2.F field distributors provide a connection between
MOVIMOT® drives and the safety-oriented communication system PROFIsafe®.The fieldbus interface of MQS22F has four standard binary inputs and two standardbinary outputs. The fieldbus interface of MQS32F has six standard binary inputs and nostandard binary outputs.The PROFIsafe® MQS.2F interface also has a safety-oriented binary output and twosafety-oriented binary inputs. The safe binary output can be used in conjunction with asafety controller to implement the "Safe stop" function of the MOVIMOT® drive viaPROFIsafe®.
Unit designations The unit designations for the PROFIsafe® MQS interfaces are as follows:• MQS22F 4DI / 2DO (via M12 plug connector) + 2F-DI / 1F-DO (2-pole)• MQS32F 6DI / 0DO (via M12 plug connector) + 2F-DI / 1F-DO (2-pole)Only the following field distributor combinations are permitted with MOVIMOT® forapplications with safe disconnection of the drive according to stop category 0 or 1 toEN 60204-1 and fail-safe protection against restart according to EN 954-1, category 3:
The following options are not possible:• Combinations with Z.1 field distributors• Combinations with Z.3 field distributors• Variants without M12
Permitted field distributor combinations
Field distributor Z.6
MQS22F / Z26F / AF0MQS22F / Z26F / AF2MQS22F / Z26F / AF3
MQS32F / Z26F / AF0MQS32F / Z26F / AF2MQS32F / Z26F / AF3
Field distributor Z.7
MQS22F / MM.../ Z27F .MQS22F / MM.../ Z27F . / AVT2/AWT2
MQS32F / MM.../ Z27F .MQS32F / MM.../ Z27F . / AVT2/AWT2
Field distributor Z.8
MQS22F / MM.../ Z28F . / AF0MQS22F / MM.../ Z28F . / AF2MQS22F / MM.../ Z28F . / AF3
MQS32F / MM.../ Z28F . / AF0MQS32F / MM.../ Z28F . / AF2MQS32F / MM.../ Z28F . / AF3
Any combinations and options listed in other publications are not permitted.
6 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
1 Valid Components
Overview The following overview lists the possible field distributor variants in conjunction with thePROFIsafe® MQS interface. The "Safe stop" function with MOVIMOT® is controlled bythe PROFIsafe® field distributors via the standard PROFIBUS connection. In this case,the 24 V supply to the MOVIMOT® drive is disconnected via the safe binary output(wired internally).
59782AEN
P R O F I
B U S
®
PROCESS FIELD BUS
I am
PR
O FIsa
fe
BB UU SS
PP RR OO FF II®
PROCESS FIELD BUS
MOVIMOT®
4 DI
2 F-DI
MQS.2F/Z26F/AF.
MQS.2F/Z28F/AF.
MQS.2F/MM../Z27F
2 F-DI 2 F-DI
2 DO
Profibus
2 x DC 24V
400V mains
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 7
2Important Notes
2 Important NotesName In this documentation, the abbreviation "F" for " failsafe is used to identify safety-
oriented units and mechanisms.
Safety and warning notes
Always observe the safety and warning information in this documentation.
Other applicable documentation
• "MOVIMOT® MM..C" operating instructions• DR / DT / DV AC motors, CT / CV asynchronous servomotors operating instructions
Electrical hazardPossible consequences: Severe or fatal injuries.
Hazard. Possible consequences: Severe or fatal injuries.
Hazardous situation.Possible consequences: Slight or minor injuries.
Harmful situation.Possible consequences: Damage to the unit and the environment.
Tips and useful information.
8 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
2 Important Notes
Designated use • These MOVIMOT® drives are intended for industrial systems. They comply with theapplicable standards and regulations and meet the requirements of the Low VoltageDirective 2006/95/EC.
• The use of MOVIMOT® drives for hoist applications is limited.• Technical data and information on approved conditions on site can be found on the
nameplate and in these operating instructions.• You must comply with this information!• Do not start up the unit (take it into operation in the designated fashion) until you have
established that the machine complies with the EMC Directive 89/336/EEC and thatthe conformity of the end product has been determined in accordance with theMachinery Directive 98/37/EC (with reference to EN 60204).
• Use only those components in safety applications that were explicitlydelivered in this design by SEW-EURODRIVE!
Operational environment
The following uses are prohibited unless the unit has been designed expressly forthis purpose:• Use in potentially explosive atmospheres• Use in areas exposed to harmful oils, acids, gases, vapors, dust, radiation, etc.• Use in non-stationary applications that are subject to mechanical vibration and shock
loads in excess of the requirements in EN 50178• Use in applications in which the MOVIMOT® inverter undertakes independent safety
functions (without higher-level safety systems) to ensure the safety of machines andpersonnel
Disposal This product consists of:• Iron• Aluminum• Copper• Plastics • Electronic components Dispose of all components in accordance with applicable regulations!
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 9
3Safety notes for MOVIMOT® drivesGeneral Safety Notes
3 General Safety Notes3.1 Safety notes for MOVIMOT® drives
• Never install damaged products or take them into operation. Submit a complaint tothe shipping company immediately in the event of damage.
• Only specialists with the appropriate accident prevention training are allowed toperform installation, startup and service work. These specialist must also comply withthe regulations in force (e.g. EN 60204, VBG 4, DIN-VDE 0100/0113/0160) whenperforming this work.
• Preventive measures and protection devices must meet the regulations in force (e.g.EN 60204 or EN 50178).Required preventive measures: Grounding of MOVIMOT®.
• The unit meets all requirements for safe isolation of power and electronicconnections in accordance with EN 61800-5-1. All connected circuits must alsosatisfy the requirements for safe disconnection.
• Before removing the MOVIMOT® inverter, disconnect it from the power supplysystem. Dangerous voltages may still be present for up to one minute afterdisconnection from the power supply.
• As soon as supply voltage is present at the MOVIMOT® unit or field distributor, closethe terminal box or field distributor and install the MOVIMOT® inverter.
• If the status LED and other display elements are no longer illuminated, this does notindicate that the unit has been disconnected from the power supply and no longercarries any voltage.
• Mechanical blocking or internal safety functions of the unit can cause a motor stand-still. Removing the cause of this problem or performing a reset can result in the motorre-starting on its own. If, for safety reasons, this is not permitted for the drivenmachine, the MOVIMOT® inverter must be disconnected from the power supplybefore correcting the problem.
• Danger of burns: The surface temperature of MOVIMOT® and the external options,e.g. braking resistors (particularly the heat sink), can reach temperatures of morethan 60 °C during operation.
• In safety applications, use only components that were explicitly designed forthis purpose by SEW-EURODRIVE.
• The guidelines in this documentation must be strictly observed for safetyapplications. This applies particularly to the conditions resulting from the testreports of the TÜV (German Technical Control Board).
10 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
3 Supplementary safety notes for field distributorsGeneral Safety Notes
3.2 Supplementary safety notes for field distributors
MFZ.6. • Before removing the terminal box cover for the power supply connection, disconnectthe unit from the power supply system. Dangerous voltages may still be present forup to one minute after disconnection from the power supply.
• During operation, the terminal box cover for the power supply connection and theconnector of the hybrid cable must be connected to the field distributor and fastened.
MFZ.7. • Before removing the MOVIMOT® inverter, disconnect the unit from the power supplysystem. Dangerous voltages may still be present for up to one minute after discon-nection from the power supply.
• The MOVIMOT® inverter and the connector of the hybrid cable must be connectedto the field distributor and fastened during operation.
MFZ.8. • Disconnect the unit from the power supply system before removing the terminal boxcover for the power supply connection or the MOVIMOT® inverter. Dangerousvoltages may still be present for up to one minute after disconnection from the powersupply.
• The terminal box cover for the power supply connection, the MOVIMOT® inverterand the connector of the hybrid cable must be connected to the field distributor andfastened during operation.
• Important: The maintenance switch only disconnects the MOVIMOT® unit from thepower supply system. The terminals of the field distributor are still connected to thepower supply after activating the maintenance switch.
• Important: The maintenance switch only disconnects the connected motor from thepower supply system. The terminals of the field distributor are still connected to thepower supply after activating the maintenance switch.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 11
4PROFIsafe® field distributor safety conceptIntegrated Safety Technology
4 Integrated Safety Technology 4.1 PROFIsafe® field distributor safety concept
• The PROFIsafe® field distributors have an integrated safety-oriented electronicssubassembly with safety inputs and outputs (F-DI, F-DO) in the PROFIsafe® MQS..interface. The safety concept of this subassembly is based on the fact that there is asafe state for all safety-oriented process values. For the PROFIsafe® MQS..interface, this value is "0" for all F-DI inputs and F-DO outputs.
• The requirements in accordance with SIL 3 to EN 61508, category 4 to EN 954-1 andperformance level e to EN ISO 13849-1 are met through the 2-channel redundantsystem structure of the safety subassembly using suitable monitoring mechanisms.When the system detects an error, it responds by switching to the safe state. In thisway, the safety function is realized in the form of safety inputs and outputs withconnection to a higher-level safety control via the PROFIsafe® communication. Theinputs / outputs on the safety subassembly of the MQS interface are not evaluatedlocally or processed logically.
• The safety output F-DO can be used to disconnect the 24 V supply of theMOVIMOT® frequency inverter, thus bringing the drive to a safe stop. In this context,observe the following safety concept of the MOVIMOT® frequency inverter and allsafety notes, conditions and installation regulations in this publication.
Important:The safety function of MOVIMOT® frequency inverters is only permitted forapplications up to category 3 according to EN 954-1 (see certificate).
12 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
4 Safety concept of the MOVIMOT® frequency inverterIntegrated Safety Technology
4.2 Safety concept of the MOVIMOT® frequency inverter• In case of danger, any potential risk to a machine must be eliminated as quickly as
possible. Standstill with restart prevention is generally the safe condition for prevent-ing dangerous movements.
• Disconnecting the 24 V supply voltage ensures that the supply voltages required foroperation of the frequency inverter are safely interrupted, preventing automaticrestart.
• Instead of galvanic separation of the drive from the supply system using relays orswitches, the disconnection of the 24 V supply described here safely prevents thecontrol of the power semiconductors in the frequency inverter. This process discon-nects the rotating field generation for the respective motor. The individual motorcannot develop any torque in this state even though the mains voltage is still present.
Limitations• Important: The safety concept is only suitable for performing mechanical work
on system/machine components.Important: When using a thermistor, protection against restart is not guaranteedwhen the thermistor is triggered. This fact must be taken into account in the riskanalysis and, if necessary, appropriate measures must be taken.
• Important: A system/machine-specific risk analysis must be carried out by thesystem/machine manufacturer and taken into account when using the drive systemwith MOVIMOT®.
• Danger of fatal injury: If the 24 V supply voltage is disconnected, the mains supplyvoltage is still present at the frequency inverter DC link.
• Important: If work is carried out on the electrical section of the drive system,the supply voltage must be disconnected using an external maintenanceswitch.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 13
4Safety concept of the MOVIMOT® frequency inverterIntegrated Safety Technology
Schematic representation of the "Safety concept for MOVIMOT®"
20166AXX
[1] Safety-oriented field distributor MQS.2F/Z2.F for PROFIsafe®
[2] Disconnection of supply voltage for controller to prevent generation of pulse patterns[3] Terminals for RS-485 and binary signals[4] Disconnection of supply voltage for the control of upper power transistors[5] Disconnection of supply voltage for the control of lower power transistors[6] Switched-mode power supply controller[7] Electrical isolation[8] Control of upper power transistors[9] Level shifter[10] Control of lower power transistors[11] Control module[12] Controller[13] Mains[14] Fieldbus connection to PROFIBUS-DP with PROFIsafe®
0V24
+5V
+5V
+15V
U V W
U_O
U_U
UZ-
+24V
UZ-
UZ-
[1]
[3]
[4]
[8]
[9]
[12]
[13]
[10]
[14]
[11]
[5]
[6]
[7]
[2]
MOVIMOT®
+24V
0V24
14 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
5 Notes on stop categoriesSafety Conditions
5 Safety ConditionsFor installation and operation of PROFIsafe® field distributors and MOVIMOT® MM..Cin safety applications in accordance with the safety classes mentioned above (see page11) the following conditions are mandatory. The conditions are divided into the followingsections:• Installation requirements• Sensor and actuator requirements• Startup requirements• Operation requirements
5.1 Notes on stop categories• For stop category 0, the control signals must be disconnected at the same time as
the safety 24 V supply.• For stop category 1, observe the following procedure:
– Decelerate the drive using an appropriate brake ramp specified by the setpoint.– Disconnect the safety 24 V supply voltage.
When using temperature sensors and automatic disconnection in the case ofovertemperature, note that the motor restarts automatically once it has cooleddown. If dangers could result from automatic restarts, additional measures mustbe taken to prevent access to the hazardous areas that are connected to the drive.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 15
5Notes on stop categoriesSafety Conditions
Hazard caused by drive coasting
Note that if the drive does not have a mechanical brake, or if the brake is defective, thedrive may coast to a halt.
The additional protective measures must be designed and integrated in such a way thatthey meet the safety category required for the machine.After activation of the stop command, access to the machine must be prevented until thedrive has reached a standstill, or the access time has to be determined to ensure thatan adequate safety distance is maintained.
Principle of the emergency stop function
NoteIf coasting to a halt should result in application-specific dangers, additionalprotective measures (e.g. movable covers with closure) must be taken which cov-er the dangerous area until persons are no longer in danger.
59815AEN
Operation
Stop
A person becomes aware of the necessity of anEMERGENCY STOP
Actuation of the EMERGENCY STOP
Reset (unlocking) of theEMERGENCY STOP
Status achieved by EMERGENCY STOP
Start command
EN 418Machine can be started again
Time
Design variants with a brake motor ensure that the brake is applied automaticallywhen the 24 V supply is disconnected.
16 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
5 Installation requirementsSafety Conditions
5.2 Installation requirements• Use only SEW hybrid cables for applications with PROFIsafe® field distributors and
MOVIMOT® in conjunction with safe disconnection of the drive according to stopcategory 0 or 1 to EN 60204-1 and fail-safe protection against restart to EN 954-1safety category 3.
• Do not shorten SEW hybrid cables. Use cables in their original lengths withprefabricated connectors. Check for proper connection.
• For applications with PROFIsafe® field distributors and MOVIMOT® in conjunctionwith safe disconnection of the drive according to stop category 0 or 1 to EN 60204-1and fail-safe protection against restart to EN 954-1 safety category 3, the powercables and 24 V supply must be routed in separate cables.
• Only the voltage for the safety-oriented 24 V supply is permitted for connecting thedirection of rotation signals and setpoint changeover (terminals R, L. f1/f2).
• Observe the notes in the "MOVIMOT® MM..C" operating instructions on EMCcompliant installation.
• The 24 V supply voltage(s) of the PROFIsafe® field distributors and all stationsconnected to the fieldbus must be designed for safe protective extra low voltage. Thevoltage must be within the limits specified in the technical data. Moreover, thefollowing voltage values may not be exceeded in case of error (in accordance withEN 60950):– Max. DC 60 V – Max. DC 120 V for 200 ms
• The protective extra low voltage requirement applies to all components and 24 Vcircuits in the system.
Refer to page 40 for information on correct wiring.
• For applications with safe disconnection of the drive according to stop category 0 or1 to EN 60204-1 and fail-safe protection against restart according to EN 954-1,category 3, the jumpers between "X40" and "X29" in the field distributor with the label"Caution, remove jumper for safety operation" must be removed (see illustrationbelow.)
54124AXX
CA
UT
ION
rem
ove jum
per
for
safe
ty o
pera
tion
CA
UT
ION
rem
ove jum
per
for
safe
ty o
pera
tion
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 17
5External sensor and actuator requirementsSafety Conditions
5.3 External sensor and actuator requirements• The project planning engineer and system/machine operator are responsible for
selecting and implementing external sensors and actuators for connection to thesafety inputs/outputs of the PROFIsafe® MQS.. interface. Note that most of the hazardous errors that may occur in the safety classes arecaused by the sensors and actuators. Therefore, to achieve the required safety category and/or SIL class, use suitablesensors and actuators and observe the permitted wiring diagram in the section"Connecting safety-oriented inputs and outputs" on page 37 .
• For the PROFIsafe® MQS.. interfaces, only connect sensors with contact accordingto the fail-safe principle to the safety inputs F-DIx. They must be supplied from theinternal sensor supply voltage F-SSx.
• To make sure that the sensor signals can be detected correctly by the safety inputs,the signals must be active for a minimum of 15 ms.
5.4 Startup requirements• Startup must be documented and proof of the efficacy of the safety functions is
required.• Perform and document startup tests for the emergency stop relay and wiring for
applications with PROFIsafe® field distributors and MOVIMOT® with safedisconnection of the drive to stop category 0 or 1 in accordance with EN 60204-1 andfail-safe protection against restart to EN 954-1 safety category 3.
• During the startup/function test, measure the voltage supplies (e.g. safety powerX40, bus module supply X29 or X20) to check whether they are assigned correctly.
• The function test must be carried out in succession for all potentials, i.e. separately.
5.5 Operation requirements• Operation is only allowed within the limits specified in the data sheets. This principle
applies to PROFIsafe® field distributors, MOVIMOT® units, and approved options.• The safety functions must be checked at regular intervals to ensure that they work
properly. The period of time between tests must be specified in accordance with therisk analysis.
18 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
6 Fieldbus interfacesUnit Design
6 Unit Design6.1 Fieldbus interfacesFieldbus inter-face MQS22F, MQS32F
Bottom of the module
20151AXX
[1] Status LED[2] M12 connection sockets[3] Diagnostic interface (behind the screw plug)[4] Diagnostic LEDs
4
3
2
1
20152AXX
[1] Connection to connection module[2] DIP switch S1 for PROFIBUS DP address[3] DIP switch S2 for PROFIsafe® address[4] Gasket
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 19
6Field distributorUnit Design
6.2 Field distributorField distributor MQS.../Z.6.
05903AXX
[1] Hybrid cable connection, connection to MOVIMOT® (X9)[2] Equipotential bonding connection[3] Maintenance switch with line protection (triple lock, color: black/red)[4] Terminals for mains and PE connection (X1)[5] 2 x M25 x 1.5[6] Terminals for bus, sensor, actuator, 24 V connection (X20)[7] 6 x M20 x 1.5 (scope of delivery includes 2 EMC cable glands)[8] Terminal block for 24 V through-wiring (X29), internal connection to 24 V on X20[9] Pluggable [Safety Power] terminal for 24 V MOVIMOT® supply (X40)
1 2 3 4 5 6 7 9 2 8
20 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
6 Field distributorUnit Design
Field distributor MQS.../MM../Z.7.
51174AXX
[1] MOVIMOT® frequency inverter[2] Hybrid cable connection, connection to AC motor (X9)[3] Equipotential bonding connection[4] Terminals for bus, sensor, actuator, 24 V connection (X20)[5] Pluggable [Safety Power] terminal for 24 V MOVIMOT® supply (X40)[6] 5 x M20 x 1.5 cable gland (scope of delivery includes 2 EMC cable glands)[7] Terminal block for 24 V through-wiring (X29), internal connection to 24 V on X20[8] 2 x M25 x 1.5 cable glands[9] Terminals for mains and PE connection (X1)[10]Connection to frequency inverter[11] Terminal for integrated braking resistor[12]Terminals for enabling the direction of rotation
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 21
6Field distributorUnit Design
Field distributor MQS.../MM../Z.8.
05902AXX
[1] Terminals for mains and PE connection (X1)[2] Maintenance switch (triple lock, color: black/red)
03546AXX[3] 2 x M25 x 1.5 cable glands[4] Terminals for bus, sensor, actuator, 24 V connection (X20)[5] 6 x M20 x 1.5 cable gland (scope of delivery includes 2 EMC cable glands)[6] MOVIMOT® frequency inverter[7] Equipotential bonding connection[8] Hybrid cable connection, connection to AC motor (X9)[9] Terminal block for 24 V through-wiring (X29), internal connection to 24 V on X20[10]Pluggable [Safety Power] terminal for 24 V MOVIMOT® supply (X40)
3 5 7
8
62
1
4
10
9
I ON I ON
0 OF
F
0 OF
F
Ø 5...Ø 8 mm
22 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
6 MOVIMOT® frequency inverter (integrated in field distributors Z.7/Z.8)Unit Design
6.3 MOVIMOT® frequency inverter (integrated in field distributors Z.7/Z.8)
05900AXX
[1] Heat sink[2] Plug for connection unit with inverter[3] Electronic nameplate[4] Protection cover for inverter electronics[5] Setpoint potentiometer f1 (not visible), accessible through a cable gland on the top of the
terminal box cover[6] Setpoint switch f2 (green)[7] Switch t1 for integrator ramp (white)[8] DIP switches S1 and S2 (for settings see Sec. "Startup")[9] Status LED (visible from the top of the terminal box cover,
see Sec. "Meaning of the LED display")
3 4 5 6 7 8 91 2
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 23
7Installation regulationsMechanical Installation
7 Mechanical Installation7.1 Installation regulations
Installation • Mount field distributors on a level, vibration-proof and torsionally rigid supportstructure only.
• Use M6 screws and suitable washers for installing MFZ.6, MFZ.7 or MFZ.8 fielddistributors. Tighten screws with a torque wrench (permitted tightening torque 3.1 to3.5 Nm (27...31 lb.in)).
Installation in damp locations or in the open
• Use suitable screw fittings for the cables (use reducing adapters if necessary).• Seal open cable entries and M12 connection sockets with screw plugs.• When the cable entry is on the side of the unit, route the cable using a drip loop.• Check the sealing surfaces before reassembling the bus module/connection box
cover. Check and, if necessary, clean the surfaces.
On delivery, field distributors are equipped with transportation protection cover-ing the plug connector of the outgoing motor circuit (hybrid cable).This cover only guarantees enclosure IP40. To obtain the specified enclosure,remove the transportation protection and install and fasten the appropriatemating connector.
24 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
7 Field distributorMechanical Installation
7.2 Field distributorInstalling field distributors MQS.../Z.6.
The following figure shows the mounting dimensions for ..Z.6. field distributors:
51239AXX
M6
M6
365 mm
180 m
m
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 25
7Field distributorMechanical Installation
Installing field distributors MQS.../MM../Z.7.
The following figure shows the mounting dimensions for ..Z.7. field distributors:
51243AXX
59,5
mm
253.7 mm
M6
M6
26 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
7 Field distributorMechanical Installation
Installing field distributors MQS.../MM03-MM15/Z.8. (size 1)
The following figure shows the mounting dimensions for ..Z.8. field distributors (size 1):
57649AXX
29
0 m
m
200 mm
270 mm
M6
M6
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 27
7Field distributorMechanical Installation
Installing field distributors MQS.../MM22-MM3X/Z.8. (size 2)
The following figure shows the mounting dimensions for ..Z.8. field distributors (size 2):
57650AXX
35
0m
m
205 mm
290 mm
M6
M6
28 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Installation planning taking EMC aspects into accountElectrical Installation
8 Electrical Installation8.1 Installation planning taking EMC aspects into accountNotes on arranging and routing installation components
Successful installation of decentralized drives depends on selecting the correct cables,providing correct grounding and a functioning equipotential bonding.You should always apply relevant standards. You must also consider the followingpoints:• Equipotential bonding
– Low-impedance HF-capable equipotential bonding must be provided indepen-dent of the functional ground (PE terminal) (see also VDE 0113 or VDE 0100 Part540). This can be done, for example through– Connecting flat metal (system) components– Using flat grounding strips (HF litz wire)
– Do not use the cable shield of data cables for equipotential bonding.• Data lines and 24 V supply
– These lines must be routed separately from cables subject to interference (e.g. control cables for solenoid valves, motor cables).
• Field distributor– We recommend using prefabricated SEW hybrid cables especially designed for
connecting field distributors and motors.
• Cable glands– Select a cable gland with large contact surface shielding (see the notes on
selection and correct installation of cable glands).
03643AXX
03047AXX
��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 29
8Installation planning taking EMC aspects into accountElectrical Installation
• Cable shield– Must have good EMC characteristics (high shield attenuation)– May not only serve as a means of mechanical protection for the cable– Must be connected with the unit’s metal housing (via EMC metal cable glands) at
the flat contact surface cable ends (see the notes on selection and correct instal-lation of cable glands).
• For more information, see the SEW publication "Drive Engineering – PracticalImplementation, Electromagnetic Compatibility (EMC) in Drive Engineering."
30 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Installation regulations for field distributorsElectrical Installation
8.2 Installation regulations for field distributorsConnecting supply system cables
• The rated voltage and frequency of the MOVIMOT® inverter must correspond to thedata for the power supply system.
• Line cross section: according to input current Imains for rated power (see Sec."Technical Data").
• Install line fuses at the beginning of the supply system line behind the supply busjunction. Use D, D0, NH fuses or circuit breakers. Select the fuse size according tothe line cross section.
• Do not use a conventional earth leakage circuit-breaker as a protective device.Universal current-sensitive earth-leakage circuit breakers ("type B") are permitted asa protective device. During normal operation of MOVIMOT® drives, earth-leakagecurrents > 3.5 mA can occur.
• In accordance with EN 61800-5-1, a second PE connection (with at least the samecross-section as the supply system line) is required parallel to the protective earth viaseparate points of connection. Leakage currents > 3.5 mA may arise during opera-tion.
• Use contactor switch contacts from utilization category AC-3 according to IEC 158 toconnect MOVIMOT® drives .
• SEW recommends using earth-leakage monitors with pulse-code measurement forvoltage supply systems with non-grounded star point (IT system). Using suchdevices prevents the earth-leakage monitor mis-tripping due to the ground capaci-tance of the inverter.
Permitted con-nection cross section and current carrying capacity of the terminals
The permitted tightening torque of the power terminals is 0.6 Nm (5.3 Ib.in).
Power terminals X1, X21(screw terminals)
Control terminals X20(cage clamp terminals)
Connection cross section (mm2)
0.2 mm2 – 4 mm2 0.08 mm2 – 2.5 mm2
Connection cross section (AWG)
AWG 24 – AWG 10 AWG 28 – AWG 12
Current carrying capacity (maximum continuous current)
32 A 12 A
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 31
8Installation regulations for field distributorsElectrical Installation
Additional con-nection options for MFZ.6, MFZ.7 and MFZ.8 field distributors
• The connection part of the DC 24 V supply comprises a X29 terminal block with twoM4 x 12 studs and a pluggable X40 terminal.
• The X29 terminal block can be used an an alternative to terminal X20 for daisy-chaining the DC 24 V supply voltage. Both studs are connected internally to the 24 Vconnection at terminal X20.
• The plug-in terminal X40 ("Safety Power") is provided for the DC 24 V supply of theMOVIMOT® inverter via the safety-oriented output of the PROFIsafe® MQS.2F fielddistributor.
• Terminal X40/1 is jumpered with X20/31 and X40/2 with X20/33 at the factory toconnect the MOVIMOT® inverter to the safe binary output of the MOVIMOT®
MQS.2F field distributor.• The current carrying capacity of both studs is 16 A. The permitted tightening torque
of the hex nuts is 1.2 Nm (10.6 Ib.in) ± 20 %.• The current carrying capacity of screw terminal X40 is 10 A. The connection cross
section is 0.25 mm2 to 2.5 mm2 (AWG 24 to AWG 12). The permitted tighteningtorque is 0.6 Nm (5.3 Ib.in).
05237AXX
Terminal assignment
No. Name Function
X29 1 24 V 24 V voltage supply for module electronics , (F) sensors and standard actuators (studs bridged with terminal X20/11)
2 GND Reference potential 0V24(studs, jumpered with terminal X20/13)
Terminal assignment
No. Name Function
X40 1 24 V 24 V voltage supply for MOVIMOT® for safe stop
2 GND 0V24 reference potential for MOVIMOT® for safe stop
32 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Installation regulations for field distributorsElectrical Installation
Installation 1,000 m above sea level
MOVIMOT® drives with supply voltages of 380 to 500 V can be used at altitudes above1,000 msl up to 4,000 msl under the following conditions.• The rated continuous power decreases due to the reduced cooling above 1,000 m
(see MOVIMOT® operating instructions).• Above 2,000 msl, the air and creeping distances are only sufficient for overvoltage
class 2. If the installation calls for overvoltage class 3, you will have to installadditional external overvoltage protection to limit overvoltage peaks to 2.5 kV phase-to-phase and phase-to-ground.
• If safe electrical disconnection is required, it must be implemented outside the deviceat altitudes above 2,000 msl (safe electrical disconnection in accordance withEN 61800-5-1 and EN 60204).
• The permitted rated supply voltage of 3 x 500 V up to 2,000 msl is reduced by 6 V forevery 100 m to a maximum of 3 x 380 V at 4,000 msl.
Protection devices
• MOVIMOT® drives are equipped with integrated protective overload devices, whichmeans that external devices are no longer required.
UL-compliant installation for field distributors
• Use only copper cables in the temperature range 60 / 75 °C as the connection lead.• MOVIMOT® units are suited for operation on voltage supply systems with grounded
star (TN and TT systems) supplying a maximum supply current of AC 5,000 A and amaximum rated voltage of AC 500 V. To ensure UL-compliant installation forMOVIMOT®, use fuses that do not exceed 35 A/600 V.
• Use only tested units with limited output voltage (Vmax = DC 30 V) and limited outputcurrent (I = 8 A) as external DC 24 V voltage supply sources.
• UL certification only applies to operation on voltage networks with voltages to groundup to a maximum of 300 V.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 33
8Installation regulations for field distributorsElectrical Installation
EMC metal cable glands
Install the EMC metal cable glands from SEW as follows:
[1] Important: Cut off insulation foil, do not fold it back.06175AXX
[1]
34 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Installation regulations for field distributorsElectrical Installation
Wiring check Check the wiring before connecting power to the system for the first time to preventwiring errors causing injury to persons and damage to machinery and systems.• Remove all bus modules from the connection module• Disconnect all MOVIMOT® inverters from the connection module (only with MFZ.7,
MFZ.8)• Disconnect all plug connectors of the motor connection (hybrid cable) from the field
distributor• Check the insulation of the cabling in accordance with applicable national standards• Check the grounding• Check insulation between the supply system cable and the DC 24 V cable • Check insulation between supply system cable and communication line• Check the polarity of the DC 24 V cable• Check the polarity of the communication line• Check the mains phase sequence• Ensure equipotential bonding between the fieldbus interfaces
After the wiring check
• Connect and fasten all motor connections (hybrid cable)• Connect and fasten all bus modules• Install and fasten all MOVIMOT® inverters (for MFZ.7, MFZ.8 only)• Install all terminal box covers• Cover any plug connections not in use
Connecting the PROFIBUS cable in the field distributor
Note that the PROFIBUS connector cores inside the field distributor must be kept asshort as possible and are always of equal length for the incoming and outgoing bus.Moreover, for EMC reasons, unshielded PROFIBUS cores should not be routed directlynext to other supply or signal cables.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 35
8Connecting field distributors MFZ26, MFZ27, MFZ28 with MQS..Electrical Installation
8.3 Connecting field distributors MFZ26, MFZ27, MFZ28 with MQS..MFZ26, MFZ27, MFZ28 connection modules with fieldbus module MQS.2 and 2 DC 24V voltage circuits
20153AXX
0 = Potential level 0 1 = Potential level 1
[1] EMC metal cable gland[2] See Sec."'Connecting safety-oriented inputs and outputs", page 37[3] Safety bridge (wired at the factory) Do not remove!
Terminal assignment
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (for test purposes only)
4 A Output PROFIBUS-DP data line A (outgoing)
5 B Output PROFIBUS-DP data line B (outgoing)
6 DGND - Data reference potential for PROFIBUS-DP (for test purposes only)
7 - - Reserved
8 VP Output +5 V output (max. 10 mA) (for test purposes only)
9 DGND - Reference potential for VP (terminal 8, for test purposes only)
10 - - Reserved
11 24 V Input 24 V voltage supply for module electronics, (F) sensors and standard actuators
12 24 V Output 24 V voltage supply (jumpered with terminal X20/11)
13 GND Input Reference potential 0V24
14 GND Output 0V24 Reference potential (jumpered with X20/13)
15 24V_LS Input 24 V load voltage supply for safety output (F-DO0)
16 24V_LS Output 24 V load voltage supply (jumpered with terminal X20/15)
17 GND Input Reference potential 0V24V
18 GND Output 0V24V Reference potential (jumpered with X20/17)
+
MFZ26
MFZ27
MFZ28
MQS22
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
16
34
17
35
18
36
A B
DG
ND A B
DG
ND
res.
VP
DG
ND
res.
24V
24V
GN
D
GN
D
24V
_LS
24V
_LS
GN
D
GN
D
1 2 3 4 5 6 7 8
PE
L1 L1 L2 L2 L3 L3 PE
L3
L2
L1
PE
L3
L2
L1
PE
4 mm (AWG10)
A
B
A
B
24V
GND
24V_LS
GND
X1
[1]
0
1
PROFIBUS-DP
2.5 mm (AWG12)2
[1]
X20
MQS32
[2]
2 x 24 VDC
24V
GND
24V_LS
GND
15
33
2
1
[3]
36 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Connecting field distributors MFZ26, MFZ27, MFZ28 with MQS..Electrical Installation
MFZ26, MFZ27, MFZ28 connection modules with fieldbus module MQS.2 and shared DC 24 V voltage circuits
20168AXX
0 = Potential level 0 1 = Potential level 1
[1] EMC metal cable gland[2] See Sec. 'Connecting safety-oriented inputs and outputs,' page 37[3] Safety bridge (wired at the factory) Do not remove!
Terminal assignment
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (for test purposes only)
4 A Output PROFIBUS-DP data line A (outgoing)
5 B Output PROFIBUS-DP data line B (outgoing)
6 DGND - Data reference potential for PROFIBUS-DP (for test purposes only)
7 - - Reserved
8 VP Output +5 V output (max. 10 mA) (for test purposes only)
9 DGND - Reference potential for VP (terminal 8, for test purposes only)
10 - - Reserved
11 24 V Input 24 V voltage supply for module electronics, (F) sensors and standard actuators
12 24 V Output 24 V voltage supply (jumpered with terminal X20/11)
13 GND Input Reference potential 0V24
14 GND Output 0V24 Reference potential (jumpered with X20/13)
15 24V_LS Input 24 V load voltage supply for safety output (F-DO0)
16 24V_LS Output 24 V load voltage supply (jumpered with terminal X20/15)
17 GND Input Reference potential 0V24V
18 GND Output 0V24V Reference potential (jumpered with X20/17)
+
MFZ26
MFZ27
MFZ28
MQS22
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
16
34
17
35
18
36
A B
DG
ND A B
DG
ND
res.
VP
DG
ND
res.
24V
24V
GN
D
GN
D
24V
_LS
24V
_LS
GN
D
GN
D
1 2 3 4 5 6 7 8
PE
L1 L1 L2 L2 L3 L3 PE
L3
L2
L1
PE
L3
L2
L1
PE
4 mm (AWG10)
A
B
A
B
24V
GND
X1
[1]
0
1
PROFIBUS-DP
2.5 mm (AWG12)2
[1]
X20
MQS32
[2]
1x 24 VDC
24V
GND
15
33
2
1
[3]
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 37
8Connecting safety-oriented inputs and outputsElectrical Installation
8.4 Connecting safety-oriented inputs and outputsThe top row of terminal strip X20 (terminals 19..36) is used to connect safety-orientedinputs (F-DIx) and the safety-oriented output (F-DO0). The following sections explainand describe the terminal assignments and the permitted connection options. All safety inputs and outputs are processed within the PROFIsafe® MQS.. interface,usually in 2 channels. As a result, the safety inputs and outputs are suited to applicationsup to category 4 to EN 954-1, performance level e to EN ISO 13849-1 and SIL 3 toEN 61508 The external sensors and actuators and their wiring must meet the require-ments of the appropriate safety class.In this context, please observe the following wiring diagrams and the lists of knownerrors. In addition, note the "Sensor and actuator requirements", page 17 .
Connection via terminal strip X20
20154AXX
No. Name Direction Function
X20 19 F-DI0 Input Safety binary input #0
20 GND - 0V24 reference potential
21 res. - Reserved
22 F-SS0 Output Safety-oriented sensor supply for F-DI0
23 GND - 0V24 reference potential
24 res. - Reserved
25 F-DI1 Input Safety binary input #1
26 GND - 0V24 reference potential (must be jumpered with X20/36)
27 res. - Reserved
28 F-SS1 Output Safety-oriented sensor supply for F-DI1
29 GND - 0V24 reference potential
30 res. - Reserved
31 F-DO0_P Output "High side" channel of safety output #0
32 GND - 0V24 reference potential
33 F-DO0_M Output "Low side" channel of safety output #0
34 GND - 0V24 reference potential
35 24V_LS Input 24 V voltage supply for actuators (jumpered with terminal X20/15+16)
36 GND2 Input 0V24 reference potential (jumpered with terminal X20/17+18 and must also be jumpered with terminal X20/26!)
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
F-D
I0
GN
D
res.
F-S
S0
GN
D
res.
F-D
I1
GN
D
res.
F-S
S1
GN
D
res.
F-D
O0_P
GN
D
F-D
O0_M
GN
D
24V
_LS
.
GN
D
1
X20
38 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Connecting safety-oriented inputs and outputsElectrical Installation
Connecting F-DIx / F-SSx
Notes on sensor wiring:• You do not have to use shielded cables for safety binary inputs.• Only connect sensors with contact according to the fail-safe principle to the safety
inputs F-DIx (e.g. emergency stop button, door contact switch, etc.).• The two sensor power supplies F-SS0 and F-SS1 are generally clocked.
When connecting the sensors, make sure that – F-SS0 is connected to F-DI0 via the sensor (fixed assignment) and– F-SS1 is connected to F-DI1 via the sensor (fixed assignment)
• Inputs that are not used do not have to be connected. An open input is alwaysevaluated as a "0" signal.
Only the following wiring options are permitted for safety applications:
a) Two sensors with unipolar connection
The following errors are detected by means of tests and monitoring functions:• Short circuit in the supply voltage• Cross fault between the two input signals• A wire break or short circuit in the reference potential is evaluated as a "0" signal (no
fault state)
If the system detects an error, it switches to the safe state, which means that all safety-oriented process values (F-DI and F-DO) are set to "0." Furthermore, the safetysubassembly is passivated (see section "Error table for the safety section", page 82).The fault state is displayed by the LED "F-STATE" (see section "Meaning of the LED-display," page 79).
59776AXX
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
F-D
I0
GN
D
res.
F-S
S0
GN
D
res.
F-D
I1
GN
D
res.
F-S
S1
GN
D
res.
F-D
O0_
P
GN
D
F-D
O0_
M
GN
D
24V
_LS
.
GN
D
1X20
Important:A short circuit between the sensor supply F-SSx and the safe input F-DIx (bridged viasensor) is not detected. This type of short circuit must be prevented by installing the cables correctly.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 39
8Connecting safety-oriented inputs and outputsElectrical Installation
b) One sensor with bipolar connection
The following errors are detected by means of tests and monitoring functions:• Short circuit in the supply voltage• Cross fault between the two input signals• A wire break or short circuit in the reference potential is evaluated as a "0" signal (no
fault state)
If the system detects an error, it switches to the safe state, which means that all safety-oriented process values (F-DI and F-DO) are set to "0." Furthermore, the safetysubassembly is passivated (see section "Error table for the safety section", page 82).The fault state is displayed by the LED "F-STATE" (see section "Meaning of the LED-display," page 79).
59777AXX
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
F-D
I0
GN
D
res.
F-S
S0
GN
D
res.
F-D
I1
GN
D
res.
F-S
S1
GN
D
res.
F-D
O0_
P
GN
D
F-D
O0_
M
GN
D
24V
_LS
.
GN
D
1X20
Important:For this connection variant, there is no internal connection and no discrepancy time eval-uation between the two input signals. The F-DI0 and F-DI1 signals are usually trans-ferred to the higher-level safety control separately. The logical connection and discrep-ancy time evaluation must take place there.
Important:A short circuit between the sensor supply F-SSx and the safe input F-DIx (bridged viasensor) is not detected. This type of short circuit must be prevented by installing the cables correctly.
40 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Connecting safety-oriented inputs and outputsElectrical Installation
Connecting F-DO0
• The safety binary output is bipolar, P-M switching and is controlled via PROFIsafe®
by a higher-level safety control.• An actuator must usually be connected to the safe output F-DO0 in a bipolar arrange-
ment between the P and the M switching output (F-DO0_P and F-DO0_M).• The unipolar connection between F-DO0_P and the reference potential GND is not
permitted and causes an error state as soon as the output is activated.• The safe output is tested internally in cycles. However, when decoupled, the test
pulses are not visible at the connection terminals and do not have to be taken intoaccount during operation.
Only the following wiring option is permitted for safety applications:
A range of external faults can be detected using internal tests and monitoring functions:When the output is activated, the following faults can be detected:• Short circuit between the P output and the reference potential• Short circuit between the M output and the +24 V supply voltage• Short circuit between the P output and the M output
When the output is deactivated, the following faults can be detected:• Short circuit between the P output and the reference potential• Short circuit between the M output and the reference potential• Short circuit between the P output and the +24 V supply voltage• Short circuit between the M output and the +24 V supply voltage
If the system detects an error, it switches to the safe state, which means that all safety-oriented process values (F-DI and F-DO) are set to "0." Furthermore, the safetysubassembly is passivated (see section "Error table for the safety section", page 82).The fault state is displayed by the LED "F-STATE" (see section "Meaning of the LED-display," page 79).
59778AXX
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
F-D
I0
GN
D
res.
F-S
S0
GN
D
res.
F-D
I1
GN
D
res.
F-S
S1
GN
D
res.
F-D
O0_
P
GN
D
F-D
O0_
M
GN
D
24V
_LS
.
GN
D
1X20
RL
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 41
8Connecting safety-oriented inputs and outputsElectrical Installation
For safe stop of the MOVIMOT® drive with PROFIsafe®, connect the safe output F-DO0to the 24 V voltage supply of the MOVIMOT® frequency inverter as follows:
When you order a complete PROFIsafe® MQS.2F/Z2.F field distributor from SEW-EURODRIVE, these connections are made prior to delivery. However, you must stillcheck the wiring. During startup, you must verify and document that the safety functionoperates correctly.
20172AXX
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
F-D
I0
GN
D
res.
F-S
S0
GN
D
res.
F-D
I1
GN
D
res.
F-S
S1
GN
D
res.
F-D
O0_
P
GN
D
F-D
O0_
M
GN
D
24V
_LS
GN
D
1X20
Important:The safety function of the MOVIMOT® frequency inverter is only permitted forapplications up to category 3 according to EN 954-1. Please see the notes and conditions in sections 4 and 5.
42 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Connecting standard inputs/outputsElectrical Installation
8.5 Connecting standard inputs/outputsConnection via M12 plug connector for...
Fieldbus interface MQS22 with 4 digital inputs and 2 digital outputs:• Only connect sensors / actuators via M12 sockets!• Connect dual-channel sensors/actuators to DI0, DI2 and DO0. DI1, DI3 and DO1 can
no longer be used.
20155AXX
DIO DI2 DO0
DI3 DO1DI1
24 V(V024)
24 V(V024)
GND GND GND
GND GND GND
DI1 DI3 DO1
24 V(V024)
24 V(V024)
DI2 DO0
DI3 DO1
DI0
DI1
1 4 5 3 2
Important: Connections that are not in use must be covered with M12 closingcaps to guarantee enclosure IP65.
Safety-oriented sensors/actuators must be connected to terminal strip X20.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 43
8Connecting standard inputs/outputsElectrical Installation
Connection via M12 plug connector for...
Fieldbus interface MQS32 with 6 digital inputs: • Only connect sensors via M12 sockets!• Connect dual-channel sensors to DI0, DI2 and DI4. DI1, DI3 and DI5 can no longer
be used.
05785AXX
DIO DI2 DI4
DI3 DI5DI1
24 V(V024)
24 V(V024)
24 V(V024)
GND GND GND
GND GND GND
DI1 DI3 DI5
24 V(V024)
24 V(V024)
DI2 DI4
DI3 DI5
DI0
DI1
24 V(V024)
1 4 5 3 2
Important: Connections not in use must be covered with M12 closing caps toguarantee enclosure IP65.
Safety-oriented sensors/actuators must be connected to terminal strip X20.
44 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Bus connection with optional connection technologyElectrical Installation
8.6 Bus connection with optional connection technologyConnecting flange AF2 or ../Z27F/ AVT2/AWT2
As an alternative to the standard design, connecting flange AF2 can be combined withfield distributors for PROFIBUS MFZ26F and MFZ28F. Connecting flange AF2 comesequipped with an M12 connector system for PROFIBUS connection. The unit comesequipped with an X11 connector for the incoming PROFIBUS and an X12 socket for theoutgoing PROFIBUS. The M12 connectors have a "reverse-key coding design" alsoreferred to as B or W coding. Identical M12 connection technology is available for the MFZ27F field distributors. In thiscase, the unit designation is ../Z27F/AVT2/AWT2.
The M12 connection technology corresponds to the recommendations from PROFIBUSDirective no. 2.141 "Connection technology for PROFIBUS."
51340AXX
[1] Front panel[2] Connector M12, incoming PROFIBUS (X11)[3] Protection cap[4] Socket M12, outgoing PROFIBUS (X12)[5] Screw plug M20[6] Screw plug M25
[1]
[6]
[2]
[4]
[3]
[5]
In contrast to the standard design, the switchable bus terminator on the MQS model mayno longer be used. Instead, a plug-in bus terminator (M12) should be used in the laststation in place of the outgoing X12 bus connection.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 45
8Bus connection with optional connection technologyElectrical Installation
Wiring and pin assignment for AF2 or ../Z27F/AVT2/ AWT2
51339AXX
M12 connector X11
Pin 1 Not assigned
Pin 2 A line PROFIBUS (incoming)
Pin 3 Not assigned
Pin 4 B line PROFIBUS (incoming)
Pin 5 Not assigned
Thread Shield / protective earth
M12 socket X12
Pin 1 VP supply voltage 5V for terminating resistor
Pin 2 A line PROFIBUS (outgoing)
Pin 3 DGND reference potential to VP (Pin 1)
Pin 4 B line PROFIBUS (outgoing)
Pin 5 Not assigned
Thread Shield / protective earth
BUBNRDGN
GN
RD
1 2 4 5 8 9
X12X11
46 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Bus connection with optional connection technologyElectrical Installation
Connecting flange AF3
As an alternative to the standard design AF0, connecting flange AF3 can be combinedwith field distributors for PROFIBUS MFZ26F and MFZ28F.Connecting flange AF3 comes equipped with an M12 connector system for PROFIBUSconnection. The unit comes equipped with an X11 connector for the incoming PROFI-BUS and an X12 socket for the outgoing PROFIBUS. The M12 connectors have a"reverse-key coding design" also referred to as B or W coding.In addition, connecting flange AF3 features an M12 connector plug X15 (4-pin, regularcoding) for supplying the 24 V supply voltage(s).
Mounting flange AF3 corresponds to the recommendations from PROFIBUS Directiveno. 2.141 "Connection technology for PROFIBUS"
51336AXX
[1] Front panel[2] Connector M12, incoming PROFIBUS (X11)[3] Socket M12, outgoing PROFIBUS (X12)[4] Reduction[5] Connector M12, 24 V voltage supply (X15)[6] Screw plug M20[7] Protection cap [8] Screw plug M25
[1]
[8]
[6]
[7]
[2][3]
[4][5]
[6]
In contrast to the standard design, the switchable bus termination at the MQS module isnot available if connecting flange AF3 is used. Instead, a plug-in bus terminator (M12)should be used in the last station in place of the outgoing X12 bus connection.
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 47
8Bus connection with optional connection technologyElectrical Installation
AF3 wiring and pin assignment
51335AXX
M12 connector X11
Pin 1 Not assigned
Pin 2 A line PROFIBUS (incoming)
Pin 3 Not assigned
Pin 4 B line PROFIBUS (incoming)
Pin 5 Not assigned
Thread Shield / protective earth
M12 socket X12
Pin 1 VP supply voltage 5 V for terminating resistor
Pin 2 A line PROFIBUS (outgoing)
Pin 3 DGND reference potential for VP (pin 1)
Pin 4 B line PROFIBUS (outgoing)
Pin 5 Not assigned
Thread Shield / protective earth
M12 plug X15
Pin 1 24V voltage supply, 24 V for module electronics and sensors
Pin 2 V2I24 - voltage supply, 24 V for actuators
Pin 3 GND - 0V24 reference potential, 24 V for module electronics and sensors
Pin 4 GND2 - 0V24 reference potential for actuators
BU BU WH BKBN BNRDGN
GN
RD
X12
X15
X11
1 2 4 5 8 9 11 13 15 17
48 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
8 Connecting prefabricated cablesElectrical Installation
8.7 Connecting prefabricated cablesConnection between field dis-tributor MFZ.6. and MOVIMOT® (part number 0 186 725 3)
Observe the enable for the direction of rotation
20167AXX
DT/DV..MM MFZ.6
+
The outer shield of the cable must be attached to the housing of the MOVIMOT®
terminal box using an EMC metal cable gland.
Cable assignment
MOVIMOT® terminal Core color / designation
L1 Black/L1
L2 Black/L2
L3 Black/L3
24 V Red/24V
⊥ White / 0V, white / 0V
RS+ Orange/RS+
RS- Green/RS-
PE terminal Green/yellow + shield end
Both directions of rotation are enabled
Only CCW operation enabledSetpoint specifications for CW rotation result in standstill of drive
Only CW operation is enabled;Preselected setpoints for CCW rotation result in standstill of drive
Drive is blocked or brought to a stop
24V
LR LR24V
LR24V
LR24V
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 49
8Connecting prefabricated cablesElectrical Installation
Connection between field distributor MFZ.7. or MFZ.8. and AC motors (part number 0 186 742 3)
51245AXX
DT/DV MFZ.7
+
MFZ.8
The outer shield of the cable must be attached to the housing of the motorterminal box using an EMC metal cable gland.
Cable assignment
Motor terminal Core color / designation
U1 Black/U1
V1 Black/V1
W1 Black/W1
4a Red/13
3a White/14
5a Blue/15
1a Black/1
2a Black/2
PE terminal Green/yellow + shield end (internal shield)
50 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
9 Startup procedureStartup with PROFIBUS (MQS)
9 Startup with PROFIBUS (MQS)9.1 Startup procedure
1. Check that MOVIMOT® and the PROFIBUS connection module (MFZ26, MFZ27 orMFZ28) are connected correctly.
2. Set DIP switch S1/1 (on MOVIMOT®) to ON (= address 1).
3. Use setpoint potentiometer f1 to set the maximum speed.
4. Reinstall screw plug of the cover (with gasket).5. Use switch f2 to set the minimum frequency fmin.
• We recommend turning off the DC 24 V power supply before removing/installing thebus module (MQS).
• The bus connection of the incoming and outgoing PROFIBUS is integrated in theconnection module, which means the PROFIBUS can be operated even when themodule electronics have been disconnected.
• In addition, please observe the notes in the section "Supplementary Field DistributorStartup Information," page 85.
06164AXX
05066BXX
[1] Potentiometer setting
Function Setting
Detent setting 0 1 2 3 4 5 6 7 8 9 10
Minimum frequency fmin [Hz]
2 5 7 10 12 15 20 25 30 35 40
1
ON
S1
6 7 854321
ON
S1
32
1 2 3 4 5 6 7 8 9 100
100f [Hz
[1]
]
2
75
25
50
65f1
34
56
78
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 51
9Startup procedureStartup with PROFIBUS (MQS)
6. If the ramp is not set using the fieldbus (2 PD), use switch t1 on MOVIMOT® to setthe ramp time. The ramp times are based on a setpoint step change of 50 Hz.
7. Set the PROFIBUS address on the MQS (factory setting: address 4). ThePROFIBUS address is set using the DIP switch S1 (1 to 7).
The following table uses address 17 as example to show how to determine the DIPswitch settings for any bus address.
Function Setting
Detent setting 0 1 2 3 4 5 6 7 8 9 10
Ramp time t1 [s] 0,1 0,2 0,3 0,5 0,7 1 2 3 5 7 10
05995AXX
[1] Example: Address 17[2] Switch 8 = reserved
Address 0 through 125: Valid addressAddress 126, 127: Not supported
Calculation Remainder DIP switch setting Significance
17 / 2 = 8 1 DIP 1 = ON 1
8 / 2 = 4 0 DIP 2 = OFF 2
4 / 2 = 2 0 DIP 3 = OFF 4
2 / 2 = 1 0 DIP 4 = OFF 8
1 / 2 = 0 1 DIP 5 = ON 16
0 / 2 = 0 0 DIP 6 = OFF 32
0 / 2 = 0 0 DIP 7 = OFF 64
34
56
78
2 x 0 = 06
2 x 0 = 05
2 x 1 = 164
2 x 0 = 03
2 x 0 = 02
2 x 0 = 01
2 x 1 = 101
ON
67
54
32
17
[1]
[2]8
00
I
52 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
9 Startup procedureStartup with PROFIBUS (MQS)
8. Set the PROFIsafe® address on the MQS (factory setting: Address 255). ThePROFIsafe® address is set using DIP switch S2. Addresses 1 to 1022 are permitted.Make sure that the setting on the MQS matches the PROFIsafe® address in theSTEP 7 HW Config.The following figure shows the position of DIP switch S2 for the addressing examplewith address 1012.
The table below gives a sample calculation for determining the DIP switch setting forthe address 1012:
20164AXX
Example: Address 1012
Calculation Remainder DIP switch setting Significance
1012 / 2 0 DIP 1 = OFF 1
506 / 2 0 DIP 2 = OFF 2
253 / 2 1 DIP 3 = ON 4
126 / 2 0 DIP 4 = OFF 8
63 / 2 1 DIP 5 = ON 16
31 / 2 1 DIP 6 = ON 32
15 / 2 1 DIP 7= ON 64
7 / 2 1 DIP 8 = ON 128
3 / 2 1 DIP 9 = ON 256
1 1 DIP 10 = ON 512
ON 1
23
45
67
89
10 2 x 19
2 x 18
2 x 17
2 x 16
2 x 15
2 x 14
2 x 03
2 x 12
2 x 01
2 x 00
=
=
=
=
=
=
=
=
=
=
512
256
128
64
32
16
0
4
0
01012
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 53
9Startup procedureStartup with PROFIBUS (MQS)
9. Activate the bus terminating resistors on the MQS fieldbus interface at the last busstation.• If the MQS is located at the end of a PROFIBUS segment, it is only connected to
the PROFIBUS network via the incoming PROFIBUS cable (terminals 1/2).• To prevent malfunctions in the bus system due to reflections, etc., the PROFIBUS
segment must be terminated using bus terminating resistors at the first and laststations.
• The bus terminating resistors are already implemented on the MQS and can beactivated using two DIP S1 switches (see following figure). Bus termination isimplemented for cable type A to EN 50170 (volume 2)!
Observe the following information when using field distributors withconnection technology AF2, AF3 or ../Z27F/AVT2/AWT2:If M12 connection technology is used for PROFIBUS, the switchable bus terminatoron the MQS.. module may not be used. Instead, a plug-in bus terminator (M12)should be used in the last station in place of the outgoing X12 bus connection.
10.Reinstall and secure the MOVIMOT® inverter and the MQS interface.
11.Switch on the 24 V voltage supply. The green LED "RUN" on the MQS must now lightup.
12.Perform project planning for the PROFIsafe® MQS interface in the DP master.
Bus termination ON Bus termination OFFFactory setting
05072AXX 05073AXX
9
ON
109
ON
10
9
ON
10
00
I
54 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
9 Project planning for MQS on PROFIBUS-DP with STEP7Startup with PROFIBUS (MQS)
9.2 Project planning for MQS on PROFIBUS-DP with STEP7Configure the fail-safe MQS fieldbus modules as usual for PROFIBUS-DP operationusing the STEP7 HW Config.To operate MQS with PROFIsafe® as a fail-safe application, you will need the"Distributed Safety (from V5.4)" option package to configure and set the parameters forthe module using STEP7.
Installing the GSD filePlease use the following GSD and image files for the fail-safe fieldbus module MQS withPROFIsafe® functionality:• SEW_6005.GSD• SEW6005N.BMP• SEW6005S.BMP• SEW6005N.DIB• SEW6005S.DIBOnce the GSD file has been installed, the module appears in the STEP7/HW Confighardware catalog under:
Profibus-DP [1]
20156AXX
+---Additional Field Devices [2]
+---Drives [3]
+---SEW [4]
+---PROFIsafe [5]
+----MQS + MOVIMOT [6][1]
[2]
[3][4]
[5]
[6]
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 55
9Project planning for MQS on PROFIBUS-DP with STEP7Startup with PROFIBUS (MQS)
Configuring the MQS in HW ConfigIn the HW Config, move the "MQS + MOVIMOT" device to the bus cable using drag &drop. The device will appear as shown in the figure below. 4 PD (4 words) is set as thedefault configuration.With this setting, you can operate the MQS as the standard fieldbus module MQP. Thisdefault configuration does not contain safety functionality via PROFIsafe®.
20157AXX
00
I
56 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
9 Project planning for MQS on PROFIBUS-DP with STEP7Startup with PROFIBUS (MQS)
Planning a new configurationYou will usually have to adapt the project planning in the HW Config to suit yourapplication. In this case, assign slots 1..3 with the modules you need. Each slot has afixed functionality. Once you have deleted the default configuration from slot 1..3, thefunction of the slot is displayed in the column "DP ID." The following table gives an over-view of the slot functions.
Option slot DP ID Description of the function
1 F-Channel The PROFIsafe® channel is configured in slot 1. The following modules can be assigned to this slot:• "F module I/O (2 bytes)" = PROFIsafe® channel is used• "Empty" = PROFIsafe® channel is not used
IMPORTANT!If a PROFIsafe® channel is not configured, the safety section of MQS remains in a safe state and the safe output FDO0 remains deactivated.
2 Param-Channel
The 8-byte parameter channel is configured in slot 2 if you want to reach MQS parameters via the cyclic PROFIBUS-DP data. This channel is not safety-oriented and can be assigned the following modules:• "Param (4 words)" = Parameter channel is used• "Empty" = Parameter channel is not used
3 PD channel The process data for controlling MOVIMOT® is configured in slot 3. The same amount of process data is always input and output. The process data channel must always be configured. This channel is not safety-oriented and can be assigned the following modules: • "1 PD" = Control via 1 process data word• "2 PD" = Control via 2 process data words• "3 PD" = Control via 3 process data words• "4 PD" = Control via 4 process data words • "5 PD" = Control via 5 process data words• "6 PD" = Control via 6 process data words• "7 PD" = Control via 7 process data words• "8 PD" = Control via 8 process data words• "9 PD" = Control via 9 process data words• "10 PD" = Control via 10 process data words
20158AXX
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 57
9Project planning for MQS on PROFIBUS-DP with STEP7Startup with PROFIBUS (MQS)
Configuring PROFIsafe® propertiesYou can configure the PROFIsafe® properties of the fail-safe MQS in the STEP7 HWConfig by double-clicking on the configured F module in slot 1. The window [Properties- DP slave] is displayed with the tab pages [Address/ID,] [Parameter Assignment] and[PROFIsafe.]
The parameter F_Dest_Add contains the PROFIsafe® address that was set at the DIPswitch S2 on the MQS module.
Description of the F parametersWhen PROFIBUS-DP starts up, the safety-relevant parameters for PROFIsafe® opera-tion are sent from the PROFIBUS-DP master to the MQS in an F parameter block.These are checked for plausibility in the safety section of MQS. Once the plausibility ofthe F parameter block has been confirmed, MQS accepts the data exchange withPROFIBUS-DP. Below is a list of the safety-oriented parameters that are transferred to MQS. You canset the following parameters for your safety application:• F_CRC_Length • F_Par_Version• F_Dest_Add • F_WD_Time
Parameter "F_Check_SeqNr" (fix)
The parameter determines whether the consecutive number should be included in theconsistency check (CRC calculation) of the F user data telegram. MQS supports the following setting:• F_Check_SeqNr = "No check"
59779AXX
00
I
58 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
9 Project planning for MQS on PROFIBUS-DP with STEP7Startup with PROFIBUS (MQS)
Parameter "F_SIL" (fix)
With this parameter, the F stations are able to check the agreement between the safetyclass and the F host. Safety circuits with different safety classes SIL 1 to SIL 3 (SIL =safety integrity level) are available for these safety-relevant cases according to the risk.MQS supports the following setting:• F_SIL = SIL 3
Parameter "F_CRC_Length" (adjustable)
The length of the CRC test value can be set depending on the length of the F user data(process values) and the PROFIsafe® version. This parameter informs the Fcomponents of the expected length of the CRC2 key in the safety telegram. The MQS uses a user data length of less than 12 bytes, which means that a 2-byte CRCis used for PROFIsafe® V1 and a 3-byte CRC is used for PROFIsafe® V2. MQS supports the following settings:
Parameter "F_Par_Version" (adjustable)
This parameter identifies the PROFIsafe® version implemented in the MQS. You canchoose from PROFIsafe® V1 and PROFIsafe® V2. MQS supports both versions.
Parameter "F_Source_Add" (fix)
The PROFIsafe® addresses are used for unique identification of source(F_Source_Add) and target (F_Dest_Add). The combination of source and targetaddress must be unique across the network and all stations. The source addressF_Source_Add is assigned automatically via STEP7 independent of the master projectplanning.Values between 1 and 65534 can be set for the parameter "F_Source_Add." The parameters cannot be changed directly in the STEP7 HW Config.
Parameter "F_Dest_Add" (adjustable)
This parameter specifies the PROFIsafe® address that was set at the DIP switch S2 onthe MQS module.Values between 1 and 1022 can be set for the parameter "F_Dest_Add."
Parameter "F_WD_Time" (adjustable)
This parameter defines a monitoring time in the fail-safe part of MQS. A valid safety telegram must arrive from the F-CPU within this monitoring time. Other-wise the MQS switches to the safe state.Set the monitoring time high enough so that telegram delays are tolerated by the com-munication but low enough so that your safety application can operate withoutrestrictions.For the MQS, you can set parameter "F_WD_Time" in increments of 1 ms - 10 s.
• F_CRC_Length = 2-byte CRC (only for PROFIsafe® V1) 3-byte CRC (only for PROFIsafe® V2)
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 59
10Data exchange with MQSFunctionality of the PROFIBUS Interface MQS
10 Functionality of the PROFIBUS Interface MQSPROFIsafe® MQS modules with integrated control and safe stop of MOVIMOT® supportthe parallel operation of standard functions and safety functions via a PROFIBUS-DPcable. The PROFIsafe® MQS interface provides the following communication functions:• Standard process data communication, functionality as with MQP modules (not
safety-oriented)• 8-byte parameter channel (not safety-oriented)• PROFIBUS-DPV1 functionality for configuring and diagnosing MQS and
MOVIMOT® (not safety-oriented)• Safety-oriented PROFIsafe® communication for safe inputs and outputs
10.1 Data exchange with MQSData exchange between the PROFIBUS master and MQS takes place via PROFIBUS-DP, which is also the "gray channel" for the safety-oriented application. Therefore, trans-ferred DP telegrams contain standard information for classic operation of MQS withMOVIMOT® on PROFIBUS-DP and the PROFIsafe® safety telegram. Depending on theproject planning and the design of the system, PROFIsafe® safety data, parameterchannel and process data is the maximum amount of data that can be exchangedbetween the DP master and MQS as shown in the figure below.
20160AEN
DP
mas
terStandard
CPU
ParamPD
Param PD
PROFIBUSDP slave
MQS
MQ
Sst
anda
rdfu
nctio
n
PROFIsafe
PROFIsafe
F-CPU
F-
func
tion
"gray channel"
PROFIBUS DP
safety-oriented
00
I
60 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Data exchange with MQSFunctionality of the PROFIBUS Interface MQS
Mapping MQS in the PLC address rangeThe user data information transferred via PROFIBUS-DP is mapped in the controller inthe input and output address range. The standard user data (process data and possiblythe 8-byte parameter channel) are used by the standard CPU for processing.PROFIsafe® data can only be used by the F CPU. The following figures are based onthe following PROFIBUS project planning:
16 input and output bits are available for safety functions in the F CPU. Only two inputbits (for F-DI0 and F-DI1) and one output bit (for F-DO0) are used. All other bits are tobe seen as reserved and assigned a "0."The following figure shows the input data in the PLC input address range.
The following figure shows the MQS data in the PLC output address range.
I-address O-address
F module I/O (2 bytes) 0...5 0...5
Param (4 words) 284...291 284...291
4 PD (4 words) 292...299 292...299
59780AEN
59781AEN
PROFIsafe Header
4 input wordsparameter channel
PEB 284...291
4 processinput words
PEB 292...299
PROFIBUS user data MQS >> master
SPS input address range
EB2EB1EB0 EB3 EB4 EB5
8 Byte Param 4 P D6 Byte PROFIsafe
0 0 0 0
reserved reserved
F-DI0 (safe input)F-DI1 (safe input)
0: not switched1: switched
0 0 0 0
7Bit: 6 5 4 3 2 1 00 0 0 0 0 0 0 0
7 6 5 4 3 2 1 0
4 output wordsparameter channel
PAB 284...291
4 processoutput words
PAB 292...299
0 0 0 0
reserved reserved
F-DO0 (safe output)0: not switched1: switched
0 0 0 0
7Bit: 6 5 4 3 2 1 00 0 0 0 0 0 0 0
7 6 5 4 3 2 1 0
PLC output address range
AB2AB1AB0 AB3 AB4 AB5
PROFIBUS user data master >> MQS
8 Byte Param 4 P D6 Byte PROFIsafe
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 61
10Integrated control functionFunctionality of the PROFIBUS Interface MQS
10.2 Integrated control functionThe PROFIsafe® MQS interfaces are equipped with integrated control functionality inthe same way as the PROFIBUS MQP interfaces. In addition, they are equipped withcontrol functions that help you determine to a large extent the response of the drive toexternal specifications via fieldbus and integrated IOs. For example, you can processsensor signals directly at the fieldbus interface or define your own communication profilevia the fieldbus interface. The NV26 or ES16 proximity encoder makes for a simplepositioning system that can be integrated in your application in combination with anMQS control program.The control functionality of the MQS modules is enabled through IPOSplus®. The diag-nostics and programming interface (under the screw plug on the front) of the modulesprovides access to the integrated IPOS® control. Option UWS21B or USB11A is usedfor connection to a PC. Programming takes place using the MOVITOOLS® Compiler.For more information on programming, refer to the "IPOSplus® Positioning andSequence Control" manual.
10.3 Default programThe MQS modules are supplied as standard with an IPOS® program that simulates themost of the functionality of the MFP modules.Set address 1 of the MOVIMOT® unit and observe the instructions for startup. Theprocess data width is fixed at four words (take into account for project planning/startup).The first three words are exchanged transparently with MOVIMOT® and correspond tothe MOVILINK® unit profile (see the section "MOVILINK® Unit Profile"). The I/Os of theMQS modules are transmitted in the fourth word.
Fault response If the connection between the MQS module and MOVIMOT® is interrupted, the systemshuts down after 1 s. The fault is displayed via status word 1 (error 91). Since this sys-tem fault generally indicates wiring problems or a missing 24 V supply of theMOVIMOT® inverter, a RESET via control word is not possible. As soon as thecommunication link is reestablished, the error automatically resets itself. If theconnection between the fieldbus master and MQS module is interrupted after the field-bus timeout interval has expired, the process output data to MOVIMOT® is set to 0. Thisfault response can be deactivated using parameter 831 in MOVITOOLS® Shell.
59826AXX
MOVIMOT +MQS®
PO1 PO2 PO3
Master
-+
PI1 PI2 PI3
PO
PI
PO4
PI4
5 4 3 2 1 0
5 4 3 2 1 0
(DI5) (DI4) DI3 DI2 DI1 DI0
DO1 DO0
00
I
62 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Control via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
10.4 Control via PROFIBUS-DPThe standard process output data sent by the PROFIBUS master can be processed inthe IPOS® program of MQS. The standard process input data sent to the PROFIBUSmaster is specified via the IPOS® program of MQS.The process data width can be set as required (1-10 words).If a PLC is used as the PROFIBUS master, the process data lies within the input/outputrange or peripheral area of the PLC.
10.5 Configuration via PROFIBUS-DPWith PROFIBUS-DP, the MQS parameters are accessed via the MOVILINK® parameterchannel, which offers further parameter services in addition to the conventional READand WRITE services.Only MQS parameters can be addressed via the parameter channel.
Structure of the parameter channel
Key functions and services, such as READ and WRITE for reading and writing param-eters, must be simulated in order to configure field devices via fieldbus systems that donot provide an application layer. For example, you will have to define a parameterprocess data object (PPO) for PROFIBUS-DP. This PPO is transmitted cyclically andcontains the process data channel as well as a parameter channel that can be used toexchange acyclical parameter values.
The following table shows the structure of the parameter channel. It is made up of amanagement byte, a reserved byte, an index word and four data bytes.
51439AXX
PARAM Parameter dataPD Process data
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Manage-ment
Reserved Index high Index low MSB data Data Data LSB data
Manage-ment
Reserved=0 Parameter index 4-byte data
PD
PARAM PD
PARAM
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 63
10Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Management of the parameter channel
The entire configuration sequence is coordinated with byte 0 (Management). This byteprovides important service parameters such as service identifier, data length, versionand status of the service performed. The following figure shows that bits 0, 1, 2 and 3contain the service identifier, and define which service is performed. Bit 4 and bit 5specify the data length in bytes for the write service; it should be set to 4 bytes for allSEW parameters.
Bit 6 is used as an acknowledgment between the controller and the MQS. It triggers theimplementation of the transmitted service in the MQS. Since the parameter channel istransmitted cyclically with the process data particularly with PROFIBUS-DP, the execu-tion of the service in the MQS must be edge-triggered via the "handshake bit." For thispurpose, the value of this bit is altered (toggled) for each new service that is to beexecuted. The MQS uses the handshake bit to signal whether the service has beenexecuted or not. The service was executed if the handshake bit received in the controlleris identical with the transmitted handshake bit. The status bit indicates whether it waspossible to carry out the service properly or if there were errors.
Reserved byte Byte 1 should be viewed as reserved and must always be set to 0x00.
Index addressing Byte 2 (Index high) and byte 3 (Index low) determine the parameter to be read or writtenvia the fieldbus system. The parameters of the MQS are addressed with a uniform indexregardless of the fieldbus system connected. The section "MQ.. Parameter List"contains all MQx parameters with index.
MSB Byte 0: Management LSB
Bit: 7 6 5 4 3 2 1 0
Service identifier:0000 = No service0001 = Read parameter0010 = Write parameter0011 = Write parameter volatile0100 = Read minimum0101 = Read maximum0110 = Read default0111 = Read scale1000 = Read attribute
Data length:00 = 1 byte01 = 2 bytes10 = 3 bytes11 = 4 bytes (must be set)
Handshake bitMust be changed in cyclical transfer with every new job
Status bit0 = No error during service execution1 = Error during service execution
00
I
64 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Data range As shown in the following table, the data is contained in byte 4 through byte 7 of theparameter channel. This means up to 4 bytes of data can be transmitted per service.The data is always entered with right-justification; that is, byte 7 contains the leastsignificant data byte (Data LSB) whereas byte 4 is the most significant data byte (DataMSB).
Incorrect service execution
The status bit in the management byte is set to signal that a service has been executedincorrectly. If the received handshake bit is identical to the transmitted handshake bit,the MQS has executed the service. If the status bit now signals an error, the error codeis entered in the data range of the parameter telegram. Bytes 4 through 7 provide thereturn code in a structured format (see the section Return Codes).
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Manage-ment
Reserved Index high Index low MSB data Data Data LSB data
High byte 1
Low byte1
High byte2
Low byte 2
High word Low word
Double word
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Manage-ment
Reserved Index high Index low Error class
Error code
Add. code high
Add. code low
Status bit = 1: Incorrect execution of a service
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 65
10Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Configuration return codes
If configuration is incorrect, the MQS returns various return codes to the configurationmaster, providing detailed information about the cause of the error. All of these returncodes are structured in accordance with EN 50170. The MQI distinguishes between thefollowing elements: • Error class• Error code• Additional codeThese return codes apply to all MQS communication interfaces.
Error class The error class element provides a more exact classification of the error type. The MQSsupports the following error classes defined in accordance with EN 50170(V2):
Error class is generated by the communication software of the fieldbus interface in theevent of an error in communication. The error can be more precisely identified using theelements Error code and Additional code.
Error code The error code element provides a means of more precisely identifying the cause of theerror within the error class. It is generated by the communication software of the MQSin the event of an error in communication. Only error code 0 (Other error code) is definedfor error class 8, "Other error." In this case, detailed identification is made using theadditional code.
Class (hex) Designation Meaning
1 vfd state Status error of the virtual field device
2 application reference Error in application program
3 definition Definition error
4 resource Resource error
5 service Error during execution of service
6 access Access error
7 OV Error in the object list
8 other Other error (see additional code)
00
I
66 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Additional code The additional code contains SEW-specific return codes for incorrect MQS configura-tions. They are returned to the master under Error Class 8 = "Other Error". The followingtable shows all possible codings for the additional code.Error class: 8 = "Other error:":
Special return codes (special cases)
Configuration errors that cannot be identified either automatically by the application lay-er of the fieldbus system or by the system software of the MQS module are treated asspecial cases. The possible causes for such errors are as follows:• Incorrect coding of a service via parameter channel• Incorrect length specification of a service via parameter channel• Project planning error in station communication
Add. code high (hex)
Add. code low (hex)
Meaning
00 00 No error
00 10 Illegal parameter index
00 11 Function / parameter not implemented
00 12 Read access only
00 13 Parameter lock is active
00 14 Factory setting is active
00 15 Value for parameter too large
00 16 Value for parameter too small
00 17 Required option card missing for this function/parameter
00 18 Error in system software
00 19 Parameter access via RS-485 process interface on X13 only
00 1A Parameter access via RS-485 diagnostic interface only
00 1B Parameter is access-protected
00 1C Controller inhibit required
00 1D Invalid value for parameter
00 1E Factory setting was activated
00 1F Parameter was not saved in EEPROM
00 20 Parameter cannot be changed with enabled output stage
00 21 Copypen end string reached
00 22 Copypen not enabled
00 23 Parameters may be changed at IPOS program stop only
00 24 Parameter may only be changed with deactivated Autosetup
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 67
10Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Incorrect service identifier in the parameter channel
An invalid service identifier was specified in the management byte during configurationvia the parameter channel. The following table shows the return code for this specialcase.
Incorrect length specification in parameter channel
A data length other than 4 data bytes was specified in a write service during configura-tion via the parameter channel. The following table displays the return codes.
Correcting the error:Check bit 4 and bit 5 for the data length in the management byte of the parameterchannel.
Project planning error in station communication
The return code listed in the following table is returned if an attempt is made to issue aparameter service to a station even though no parameter channel was configured for thestation.
Troubleshooting:Configure a parameter channel for the desired station.
Code (dec) Meaning
Error class: 5 Service
Error code: 5 Illegal parameter
Add. code high: 0 –
Add. code high: 0 –
Code (dec) Meaning
Error class: 6 Access
Error code: 8 Type conflict
Add. code high: 0 –
Add. code high: 0 –
Code (dec) Meaning
Error class: 6 Access
Error code: 1 Object not existent
Add. code high: 0 –
Add. code high: 0 –
00
I
68 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Reading and writing parameters using PROFIBUS-DPReading a parameter using PROFIBUS-DP (Read)
To execute a READ service via parameter channel, the handshake bit may be changedonly after the complete parameter channel was set up for the specific service becauseof the cyclical transfer of the parameter channel. As a result, adhere to the followingsequence when reading a parameter:1. Enter the index of the parameter to be read in byte 2 (Index high) and byte 3 (Index
low).2. Enter the service identifier for the read service in the management byte (byte 0).3. Transfer the read service to the MQS by changing the handshake bit.
Since this is a read service, the sent data bytes (bytes 4...7) and the data length (in themanagement byte) are ignored and do not need to be set. The MQS now processes theread service and sends back the service confirmation by changing the handshake bit.
The figure shows the coding of a READ service in the management byte. The datalength is not relevant, you only need to enter the service identifier for the READ service.This service is now activated in the MQS when the handshake bit changes. Forexample, it would be possible to activate the read service with management byte coding01hex or 41hex.
Byte 0: Management
7 6 5 4 3 2 1 0
0 0/1 X X 0 0 0 1
Service identifier:0001 = Read parameter
Data length:Not relevant for Read service
Handshake bitMust be changed with every new job
Status bit0 = No error in service execution1 = Error in service execution
X = Not relevant0/1 = Bit value is changed
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 69
10Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Writing a parameter via PROFIBUS-DP (Write)
To execute a WRITE service via parameter channel, the handshake bit may be changedonly after the complete parameter channel was set up for the specific service becauseof the cyclical transfer of the parameter channel. Observe the following sequence whenwriting a parameter:1. Enter the index of the parameter to be written in byte 2 (Index high) and byte 3 (Index
low).2. Enter the data to be written in bytes 4 through 7.3. Enter the service identifier and the data length for the write service in the manage-
ment byte (byte 0).4. Transfer the write service to the MQS by changing the handshake bit.The MQS now processes the write service and sends the service confirmation back bychanging the handshake bit.The figure shows the coding of a WRITE service in the management byte. The datalength is 4 bytes for all parameters in the MQS. This service is transferred to the MQSwhen the handshake bit changes. This means a write service to the MQS generally hasthe management byte coding 32hex or 72hex.
Byte 0: Management
7 6 5 4 3 2 1 0
0 0/1 1 1 0 0 1 0
Service identifier:0010 = Write
Reserved
Data length:11 = 4 bytes
Handshake bitMust be changed with every new job
Status bit0 = No error in service execution1 = Error in service execution
0/1 = Bit value is changed
00
I
70 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPFunctionality of the PROFIBUS Interface MQS
Configuration procedure for PROFIBUS-DP
Using the WRITE service as an example, the following figure is used to show theconfiguration procedure between the controller and MQS via PROFIBUS-DP. To simpli-fy the sequence, only the management byte of the parameter channel is shown in thefigure. The parameter channel is only received and returned by the MQS while thecontroller is preparing the parameter channel for the write service. The service is notactivated until the moment when the handshake bit is changed (in this example, when itchanges from 0 to 1). The MQS now interprets the parameter channel and processesthe write service, but continues to answer all telegrams with handshake bit = 0. Theexecuted service is acknowledged with a change of the handshake bit in the responsetelegram of the MQS. The controller now detects that the received handshake bit is onceagain the same as the one that was sent. It can now prepare another configurationprocedure.
Parameter data format
When parameters are set via the fieldbus interface, the same parameter coding is usedas with the serial RS-485 interfaces. The list of the individual parameters can be foundin the section "Parameter List."
05471AEN
0 1100100
0 1100100
0 1100100
0 1100100
0 1100101
0 1100100
0 1100101
0 1100100
0 1100101
0 1100101
0 1100101
0 1100101
0 1100100
0 1100100
0 1100100
0 1100100
0 1100101
0 1100100
0 1100101
0 1100100
0 1100101
0 1100101
0 1100101
0 1100101
Control
RS-485
MQP(Slave)
Parameter channelbeing prepared forwrite service.
Handshake bit is beingchanged and serviceis delegated to driveinverter.
Service confirmationhas been receivedsince send and receipthand-shake bit areidentical once again.
Parameter channelbeing received butnot evaluated.
is
Parameter channelbeing received butnot evaluated.
Write service executed,handshake bit beingchanged.
Writebeing
serviceprocessed.
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 71
10Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
10.6 Configuration via PROFIBUS-DPV1The PROFIBUS-DPV1 specification introduced new acyclical read/write services withinthe context of the PROFIBUS-DP expansions. These acyclical services are added to thecurrent cyclical bus operation in special telegrams to ensure compatibility ofPROFIBUS-DP (version 0) and PROFIBUS-DPV1 (version 1).The acyclical read/write services can be used to exchange larger data quantitiesbetween master and slave (drive inverter) than it would be possible to transfer in thecyclical input or output data using the 8-byte parameter channel. The advantage of theacyclical data exchange via DPV1 lies in the minimum load on the cyclical bus operationsince DPV1 telegrams are only added to the bus cycle if required.
51654AXX
PARAM Parameter dataPD Process dataA R/W Acyclical read/write servicesC R/W Cyclical read/write services
PD
PARAM PD
PARAM
A R/W
C R/W
00
I
72 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
Structure of the DPV1 parameter channel
Data sets (DS)The user data transported via a DPV1 service is grouped in a data set. Each data set isrepresented uniquely by its length, a slot number and an index. DPV1 communicationwith MQS.. uses the structure of data set 47, which is defined as DPV1 parameter chan-nel for drives in the PROFIdrive profile "Drive engineering" of the PROFIBUS userorganization from V3.1. Different procedures for accessing parameter data in the driveinverter are provided via this parameter channel.The drive parameters are usually set according to the PROFIdrive DPV1 parameterchannel of profile version 3.0 via data set index 47. The 'Request ID' entry is used todistinguish between parameter access based on PROFIdrive profile or via SEW-EURODRIVE MOVILINK® services. The section "Elements of data set DS47" shows thepossible codings of the individual elements. The data set structure is the same forPROFIdrive and MOVILINK® access.
The following MOVILINK® services are supported:• 8-byte MOVILINK® parameter channel with all the services supported by the drive
inverter such as:• Read parameter• Write parameter• Write parameter volatile
The following PROFIdrive services are supported:• Reading (request parameter) individual parameters of type double word• Writing (change parameter) individual parameters of type double word
DPV1Read/Write
PROFIdriveParameter channelDS47
SEW-EURODRIVE MOVILINK®
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 73
10Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
Elements of data set DS47
The following table shows the elements of data set DS47.
Field Data Type Values
Request reference Unsigned8 0x00 Reserved
0x01..0xFF
Request ID Unsigned8 0x01 Request parameter (PROFIdrive)
0x02 Change parameter (PROFIdrive)
0x40 SEW-EURODRIVE MOVILINK® Service
Response ID Unsigned8 Response (+):
0x00 Reserved
0x01 Request parameter (+) (PROFIdrive)
0x02 Change parameter (+) (PROFIdrive)
0x40 SEW-EURODRIVE MOVILINK® service (+)
Response (-):
0x81 Request parameter (-) (PROFIdrive)
0x82 Change parameter (-) (PROFIdrive)
0xC0 SEW-EURODRIVE MOVILINK® service (-)
Axis Unsigned8 0x00..0xFF Number of axis 0..255
No. of parameters Unsigned8 0x01..0x13 1..19 DWORDs (240 DPV1 data bytes)
Attributes Unsigned8 0x10 Value
For SEW-EURODRIVE MOVILINK® (Request ID = 0x40):
0x00 No service
0x10 Read parameter
0x20 Write parameter
0x30 Write parameter volatile
0x40 Read Minimum
0x50 Read Maximum
0x60 Read Default
0x70 Read Scale
0x80 Read Attribute
0xA0..0xF0 Reserved
No. of elements Unsigned8 0x00 For non-indexed parameters
0x01..0x75 Quantity 1.0.117
Parameter Number Unsigned16 0x0000..0xFFFF MOVILINK® parameter index
Subindex Unsigned16 0x0000 SEW-EURODRIVE: always 0
Format Unsigned8 0x43 Double word
0x44 Error
No. of Values Unsigned8 0x00..0xEA Quantity 0..234
Error Value Unsigned16 0x0000..0x0064 PROFIdrive error codes
0x0080 + MOVILINK® AdditionalCode Low
For SEW-EURODRIVE MOVILINK® 16 Bit Error Value
00
I
74 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
Procedure for setting parameters via data set 47 for PROFIBUS- DPV1
Parameter access takes place with the combination of the DPV1 services "Write" and"Read". The parameter setting service is transferred to the slave with Write.req, followedby slave-internal processing. The master now sends a Read.req to pick up the configu-ration response. The master repeats the Read.req if the answer (Read.res) from theslave is negative. As soon as parameter processing in MQS is concluded, it answerswith a positive response (Read.res). The user data now contains the parameter settingresponse of the parameter setting request that was previously sent with Write.req (seefollowing figure). This mechanism applies to both a C1 and a C2 master.
51658AXX
Parameter
Response
Parameter
Response
Parameter
Request
Parameter
Request
ParameterParameter
ProcessingProcessing
Write.req DS47
with data (parameter request)
Write.res
without data
Read.req DS47
without data
Read.res(-)
without data
Read.req DS47
without data
Read.res (+)
with data (parameter response)
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 75
10Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
MOVILINK® parameter requests
The parameter channel of the MQS is mapped directly in the structure of data set 47.The Request ID 0x40 (SEW MOVILINK® service) is used to exchange MOVILINK®
parameter setting requests. Parameter access with MOVILINK® services usually takesplace according to the structure described below. The typical telegram sequence fordata set 47 is used.
Request ID: 0x40 SEW MOVILINK® serviceThe actual service is defined by the data set element Attribute in the MOVILINK®
parameter channel. The high nibble of this element corresponds to the service nibble inthe management byte of the DPV0 parameter channel.
Example for reading a parame-ter via MOVILINK® (reading a parame-ter via DPV1)
The following tables give an example of the structure of the Write.req and Read.res userdata for reading an individual parameter via the MOVILINK® parameter channel.
Sending a parameter request:The following tables show the coding of the user data for the Write.req service includingthe DPV1 header. The Write.req service is used to transfer the parameter settingrequest to the drive inverter.
Query parameter response:The following table shows the coding of the Write.req user data including the DPV1header.
Service: Write.request Description
DPV1 header
Slot_Number 0 random, (is not evaluated)
Index 47 Index of the data set; constant index 47
Length 10 10 byte user data for parameter request
Byte Field Value Description
PROFIdriveParameter channel
0 Request reference 0x01 Individual reference number for the param-eter setting request is mirrored in the parameter response
1 Request ID 0x40 SEW MOVILINK® service
2 Axis 0x00 Axis number; 0 = single axis
3 No. of parameters 0x01 1 parameter
4 Attributes 0x10 MOVILINK® service 'Read parameter'
5 No. of elements 0x00 0 = access to direct value, no subelement
6 to 7 Parameter Number 0x206C MOVILINK® index 8300 = firmware version
8 to 9 Subindex 0x0000 Subindex 0
Service: Read.request Description
DPV1 header
Slot_Number 0 Random, (is not evaluated)
Index 47 Index of the data set; constant index 47
Length 240 Maximum length of response buffer in the DPV1 master
00
I
76 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
Positive MOVILINK® parameter response: The tables shows the Read.res user data with the positive response data of theparameter setting request. The parameter value for index 8300 (firmware version) isreturned as an example.
Example for writing a parameter via MOVILINK® (writing a parameter via DPV1)
The following tables show the sequence of the Write and Read services for the non-volatile writing of the value 12345 to IPOS variable H0 (parameter index 11000) as anexample. The MOVILINK® service Write Parameter volatile is used for this purpose.
After sending this Write.request, the Write.response is received. If there was no statusconflict in processing the parameter channel, a positive Write.response occurs. Other-wise, the status error is located in Error_code_1.
Service: Read.request Description
DPV1 header
Slot_Number 0 Random, (is not evaluated)
Index 47 Index of the data set: constant index 47
Length 10 10 byte user data for order buffer
Byte Field Value Description
0 Response reference 0x01 Reflected reference number from the parameter setting order
1 Response ID 0x40 Positive MOVILINK® response
2 Axis 0x00 Reflected axis number: 0 for single axis
3 No. of parameters 0x01 1 parameter
4 Format 0x43 Parameter format: Double word
5 No. of values 0x01 1 value
6 to 7 Value Hi 0x311C Higher-order part of the parameter
8 to 9 Value Lo 0x7289 Lower-order part of the parameter
Decoding:0x 311C 7289 = 823947913 dec→ Firmware version 823 947 9.13
Service: Read.request Description
DPV1 header
Slot_Number 0 Random (is not evaluated)
Index 47 Index of the data set: constant index 47
Length 16 16 byte user data for order buffer
Byte Field Value Description
0 Request reference 0x01 Individual reference number for the parameter setting request is mirrored in the parameter response
1 Request ID 0x40 SEW MOVILINK® service
2 Axis 0x00 Axis number; 0 = single axis
3 No. of parameters 0x01 1 parameter
4 Attributes 0x30 MOVILINK® service Write parameter volatile
5 No. of elements 0x00 0 = access to direct value, no subelement
6 to 7 Parameter Number 0x2AF8 Parameter index 11000 = ’IPOS variable H0’
8 to 9 Subindex 0x0000 Subindex 0
10 Format 0x43 Double word
11 No. of values 0x01 Change 1 parameter value
12 to 13 Value HiWord 0x0000 Higher-order part of the parameter value
14 to 15 Value LoWord 0x0BB8 Lower-order part of the parameter value
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 77
10Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
Query parameter responseThe following tables show the coding of the Write.req user data including the DPV1header.
Positive response to "Write Parameter volatile"
Configuration return codes
Negative parameter responseThe following tables show the coding of a negative response of a MOVILINK® service.Bit 7 is entered in the the response ID if the response is negative.
Byte Field Value Description
DPV1 header
Function_Num Read.req
Slot_Number X Slot_Number not used
Index 47 Index of data set
Length 240 Maximum length of response buffer in DP master
Service: Read.response Description
DPV1 header
Slot_Number 0 Random, (is not evaluated)
Index 47 Index of the data set; constant index 47
Length 4 12 byte user data in response buffer
Byte Field Value Description
0 Response ref-erence
0x01 Reflected reference number from the parameter setting request
1 Response ID 0x40 Positive MOVILINK® response
2 Axis 0x00 Reflected axis number; 0 = single axis
3 No. of parame-ters
0x01 1 parameter
Service: Read.response Description
DPV1 header
Slot_Number 0 Random, (is not evaluated)
Index 47 Index of the data set; constant index 47
Length 8 8 byte user data in response buffer
Byte Field Value Description
0 Response ref-erence
0x01 Reflected reference number from the parameter setting request
1 Response ID 0xC0 Negative MOVILINK® response
2 Axis 0x00 Reflected axis number; 0 = single axis
3 No. of parame-ters
0x01 1 parameter
4 Format 0x44 Error
5 No. of values 0x01 1 error code
6 to 7 Error value 0x0811 MOVILINK® return code, e.g. ErrorClass 0x08, Add. code 0x11 (see the table MOVILINK® return codes for DPV1)
00
I
78 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Configuration via PROFIBUS-DPV1Functionality of the PROFIBUS Interface MQS
MOVILINK® parameter responseThe following table shows the return codes that are returned by the MQS in case of anerror in the DPV1 parameter access.
MOVILINK® return code (hex)
Description
0x0810 Invalid index, parameter index does not exist in the unit
0x0811 Function / parameter not implemented
0x0812 Read access only
0x0813 Parameter lock activated
0x0814 Factory setting is active
0x0815 Value for parameter too large
0x0816 Value for parameter too small
0x0817 Required option card not installed
0x0818 Error in system software
0x0819 Parameter access via RS-485 process interface only
0x081A Parameter access via RS-485 diagnostic interface only
0x081B Parameter is access-protected
0x081C Controller inhibit is required
0x081D Invalid value for parameter
0x081E Factory setting was activated
0x081F Parameter was not saved in EEPROM
0x0820 Parameter cannot be changed with output stage enabled/reserved
0x0821 Reserved
0x0822 Reserved
0x0823 Parameter may only be changed with IPOS program stop
0x0824 Parameter may only be changed with deactivated Autosetup
0x0505 Incorrect coding of management and reserved byte
0x0602 Communication error between inverter system and fieldbus option card
0x0502 Timeout of secondary connection (e.g. during reset or with Sys-Fault)
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 79
10Meaning of LEDsFunctionality of the PROFIBUS Interface MQS
10.7 Meaning of LEDsMQS is equipped with seven LEDs to indicate the operating states:• LED "RUN" (green) for indicating the normal operating status• LED "BUS-F" (red) for indicating faults on the PROFIBUS-DP• LED "SYS-F" (red) for indicating system faults on the MQS or MOVIMOT®
• LED "F-STATE" (green/red) for indicating the operating state of the safety system• LED "F-DI0" (yellow) for indicating safe input 0• LED "F-DI01" (yellow) for indicating safe input 1• LED "F-DO0" (yellow) for indicating the safe output
Warning: The LEDs "FDI..", "FDO.." and "F-STATE" are not designed for safety and may not beused as safety functions.
57567AXX
MQ
S P
RO
FIs
afe
F-DO0F-DO0
SYS-FSYS-F
F-DI1F-DI1
BUS-FBUS-F
F-DI0F-DI0
F-STATEF-STATE
RUNRUN
DI4DI4
DI5DI5
DI2DI2
DI3DI3
DI0DI0
DI1DI1
00
I
80 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Meaning of LEDsFunctionality of the PROFIBUS Interface MQS
Overview of the LED displays
LED State Meaning Remedy
RUN
Green • MQS circuit board hardware OK• Correct MQS operation -
Off • No 24 V power supply • Check voltage supply
Flashing green
• PROFIBUS address is set higher than 125 • Check the PROFIBUS address
BUS-F
Red
• Connection to the DP master has failed
• MQS does not detect a baud rate• Bus interruption• DP master not in operation
• Check the PROFIBUS-DP connec-tion to the MQS
• Check the DP master• Check all cables in your
PROFIBUS-DP network
Off • MQS is currently exchanging data with the DP master (data exchange) -
Flashing red
• Baud rate is detected, however not addressed by DP master
• MQS was not configured in DP master or configured incorrectly
• Check project planning of the DP master
SYS-F
Red
• The MQS is not exchanging data with the connected MOVIMOT®
• The MQS was not configured, or the connected MOVIMOT® unit does not respond
• Maintenance switch on the field distributor is set to OFF
• MOVIMOT® safe stop is active (switched off)
• Check the voltage supply of MOVIMOT®
• Check the address on MOVIMOT®
• Check whether the IPOS program has been started
• Check the setting of the mainte-nance switch on the field distributor
Off• Normal operating state MQS is
exchanging data with the connected MOVIMOT® unit
-
Flashing red
• The MQS is in error state• An error message is displayed in the
MOVITOOLS® status window • Please see the corresponding error
description (see error table)
F-STATE
Green• The MQS safety section is currently
exchanging data cyclically with the F host (data exchange)
• Normal operating state -
Red• Error state in the safety section
• Read off diagnosis in F module• Remedy cause of error and
acknowledge the repair in the F host
• F module is not configured in the DP master (slot 1 is empty)
• Check the project planning of the bus master
Off• 24 V supply voltage missing• MQS is currently in the initialization
phase• Check voltage supply
Flashing Red/green
• There was an error in the safety section; cause of error has been repaired - acknowledge repair
• Acknowledge error in the F host (Reintegration)
F-DI0Yellow • HIGH level at input F-DI0 -
Off • LOW level at input F-DI0 or open -
F-DI1Yellow • HIGH level at input F-DI1 -
Off • LOW level at input F-DI1 or open (switched) -
F-DO0Yellow • Output F-DO0 active -
Off • Output F-DO0 inactive (switched off) -
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 81
10Error states of the standard sectionFunctionality of the PROFIBUS Interface MQS
10.8 Error states of the standard sectionFieldbus timeout Switching off the fieldbus master or an open circuit in the fieldbus cabling results in a
fieldbus timeout in the MQS. The connected MOVIMOT® units are stopped by sending"0" in each process output data word. In addition, the digital outputs are set to "0."This corresponds, for example, to a rapid stop at control word 1.
This error response can be deactivated via P831 in MOVITOOLS® Shell.
RS-485 timeout If one or more MOVIMOT® units can no longer be addressed by the MQS via RS-485,error code 91 "System error" is displayed in status word 1. The "SYS-F" LED lights up.The error is also transmitted via diagnostics interface.MOVIMOT® units that do not receive any data will stop after 1 second. The prerequisitefor this is that data exchange between the MQS and MOVIMOT® is enabled viaMOVCOMM commands. MOVIMOT® units that continue to receive data can becontrolled as usual.The timeout resets itself automatically, i.e. the current process data is exchangedimmediately with MOVIMOT® once communication has been restarted.
Unit errors The MQS fieldbus interfaces can detect a series of hardware defects. After detecting ahardware defect, the devices are inhibited. The exact error responses and remedialmeasures are listed in the section "Error table for the standard section." A hardware defect causes error 91 to be displayed in the process input data in statusword 1 of all MOVIMOT® units. The "SYS-F" LED on the MQS module flashes regularly. The exact error code can be displayed via the diagnostics interface in MOVITOOLS® inthe MQS status. The error code can be read and processed in the IPOS® program withthe command "GETSYS".
Important: When MOVIMOT® is controlled with 3 process data words, the ramp is specifiedwith 0 s in the 3rd word! The "Fieldbus timeout" error resets itself automatically. The MOVIMOT® unit willonce again receive the current process output data from the controller as soon asthe fieldbus communication has been reestablished.
00
I
82 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Error states in the safety sectionFunctionality of the PROFIBUS Interface MQS
10.9 Error states in the safety section
Errors in the safety section
The safety subassembly in the PROFIsafe® MQS interface can identify a series of inter-nal and external faults (at the safe inputs/outputs). The error types, exact error respons-es and remedial measures are listed in the section "Error table for the standard section,"page 102.If errors occur in the safety section, MQS usually responds by passivating the moduleand switching off the output. In doing so, all safety-oriented process values (F-DI and F-DO) are set to "0" (=> safe state). Once the error has been remedied, the passivationmust be acknowledged by reintegrating the module.
PROFIsafe® timeout
If safety-oriented PROFIsafe® communication is interrupted or delayed, the MQSmodule responds once the monitoring time "F_WD_Time" expires (see description ofthe F parameters) by passivating and switching to the safe state.This monitoring time also has to be set in the safety controller. There, once the timeexpires the module affected is passivated and the corresponding safety-orientedprocess values are set to "0" for the safety application (=> safe state).A passivation must always be acknowledged by reintegrating the module in question.
Depending on the safety control used, the terms "passivation" and "reintegration" maybe named differently in the safety control documentation.For more information, refer to the safety control documentation.
Important:Automation reintegration can also be set in the safety controller. We recommend thatyou do not use this function in safety-oriented applications.
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 83
10Diagnostics via PROFIBUSFunctionality of the PROFIBUS Interface MQS
10.10 Diagnostics via PROFIBUSThe state of PROFIsafe® communication and error messages of the MQS safety sectionare reported to the DP master using the status PDU in accordance with the PROFIBUS-DPV1 standard.
The following figure shows the structure of the diagnostics data for PROFIsafe®
communication via slot 1. The F module for the MQS safety section is configured inslot 1. Byte 11 is used to transfer diagnostics messages. These are defined in the PROFIsafe®
specification.Bytes 12 and 13 transfer the status and error status of the MQS safety section to thehigher-level DP master.
The following figure shows the structure of the diagnostics data for PROFIBUS DPV1:
Diagnostics messages of the PROFIsafe® layer
The following table shows the diagnostics messages of the PROFIsafe® layer:
Status block
Byte 1...6 Byte 7 Byte 8 Byte 9 Byte 10 Byte 11 Byte 12 Byte 13
6 bytes Standard diagnostics Header Status
TypeSlot
NumberStatus
SpecifierDiag User
Data 0Diag User
Data 1Diag User
Data 2
... 0x07 0x81 0x00 0x00 PROFIsafe® F-State 1
↑ ↑ ↑ ↑ ↑ ↑
7 bytesModule-specific
diagnostics
0x81 =Status block with status message
0x00 =Slot 1
(F-channel)
No DPV1 specifier
PROFIsafe® diagnostics information
in accor-dance with
PROFIsafe®
profile V2.0
Cyclic F_Stateof the MQS field distributor
Byte 11 PROFIBUS diagnostics text(German)
PROFIBUS diagnostics text (English)
0hex / 0dec No error ---
40hex / 64dec
F_Dest_Add stimmt nicht überein Mismatch of F_Dest_Add
41hex / 65dec
F_Dest_Add ist ungültig F_Dest_Add not valid
42hex / 66dec
F_Source_Add ist ungültig F_Source_Add not valid
43hex / 67dec
F_WD_Time ist 0 ms F_WD_Time is 0 ms
44hex / 68dec
SIL Level größer max SIL Level F_SIL exceeds SIL f. application
45hex / 69dec
Falsche F_CRC_Length F_CRC_Length does not match
46hex / 70dec
Falsche F-Parameter Version F-Parameter set incorrectly
47hex / 71dec
Fehler im CRC1-Wert CRC1-Fault
For more information on the meaning and remedy of error messages, refer to themanuals on PROFIBUS-DP.
00
I
84 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
10 Diagnostics via PROFIBUSFunctionality of the PROFIBUS Interface MQS
Error codes for the MQS safety section
The following table shows the error codes of the MQS safety section:
Byte 12 Byte 13 Designation Meaning / remedy
0hex / 0dec 0hex / 00dec No error
See Error table for the safety section,page 102
01hex / 01dec
Internal processing error
02hex / 02dec
Internal system error
03hex / 03dec
Communication error
04hex / 04dec
Error in the electronics supply
05hex / 05dec
Error in the load voltage supply
14hex / 20dec
Internal error at safe input (F-DIx)
15hex / 21dec
Short circuit at safe input (F-DIx)
32hex / 50dec
Internal error at safe output (F-DO0)
33hex / 51dec
Short circuit at safe output (F-DO0)
34hex / 52dec
Overload at safe output (F-DO0)
6Fhex / 111dec
Internal communication error in F option
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 85
11Field distributor MQS.../Z.6.Supplementary Field Distributor Startup Information
11 Supplementary Field Distributor Startup InformationThe startup procedure is described in the section "Startup with PROFIBUS (MQS)." Inaddition, please observe the following notes about the startup of field distributors.
11.1 Field distributor MQS.../Z.6.Maintenance switch
The maintenance/line protection switch of the Z.6. field distributor protects the hybridline against overload and switches the– power supply of the MOVIMOT®
– DC 24 V power supply for MOVIMOT®
Important:The maintenance/line protection switch only disconnects the MOVIMOT® motorfrom the power supply system, not the field distributor.
00
I
86 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
11 Field distributor MQS.../MM../Z.7.Supplementary Field Distributor Startup Information
11.2 Field distributor MQS.../MM../Z.7.Checking the connection type for the con-nected motor
Use the following figure to check that the selected connection type is identical for thefield distributor and the connected motor.
Internal wiring of the MOVIMOT® inverter in the field distributor
03636AXX
U1 V1 W1
W2 U2 V2
U1 V1 W1
W2 U2 V2� �
Important:For brake motors: Do not install brake rectifiers inside the terminal box of themotor!
05986AXX
[1] DIP switch for setting the connection typeMake sure that the method of connection for the connected motor matches the setting of the DIP switch.
[2] Note the enabled direction of rotation(Both directions of rotation are enabled as standard)Both directionsare enabled
Only directioncounterclockwise is enabled
Only directionclockwise is enabled
04957AXX
[3] Connection for internal braking resistor (in motors without brake only)
24
V
TH L R 1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
�
TH
�
�[1]
[2]
[3]
X4
X6
X1
13
15
24V
TH L R 24V
TH L R 24V
TH L R
ϑ ϑ ϑTH TH TH
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 87
11Field distributor MQS.../MM../Z.8.Supplementary Field Distributor Startup Information
11.3 Field distributor MQS.../MM../Z.8.Maintenance switch
The maintenance switch of the Z.8. field distributor switches the– power supply of the MOVIMOT®
– DC 24 V power supply for MOVIMOT®
Checking the connection type for the connected motor
Use the following figure to check that the selected connection type is identical for thefield distributor and the connected motor.
Important:The maintenance switch disconnects the MOVIMOT® inverter with connectedmotor from the power supply system, but not the field distributor.
03636AXX
U1 V1 W1
W2 U2 V2
U1 V1 W1
W2 U2 V2� �
Important:For brake motors: Do not install brake rectifiers inside the terminal box of themotor!
00
I
88 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
11 Field distributor MQS.../MM../Z.8.Supplementary Field Distributor Startup Information
Internal wiring of the MOVIMOT® inverter in the field distributor
05981AXX
[1] DIP switch for setting the connection typeMake sure that the method of connection for the connected motor matches the setting of the DIP switch.
[2] Note the enabled direction of rotation(Both directions of rotation are enabled as standard)Both directionsare enabled
Only directioncounterclockwise is enabled
Only directionclockwise is enabled
04957AXX
[3] Connection for internal braking resistor (in motors without brake only)[4] Maintenance switch
24
V
TH L R
13
14
15
L1
L2
L3
L1
L2
L3
+2
4V
DC
�
TH
�
�
[4]
[1]
[2]
[3]
X4
24V
TH L R 24V
TH L R 24V
TH L R
ϑ ϑ ϑTH TH TH
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 89
11MOVIMOT® frequency inverter integrated in the field distributorSupplementary Field Distributor Startup Information
11.4 MOVIMOT® frequency inverter integrated in the field distributorThe following section describes the changes that are necessary to operate theMOVIMOT® frequency inverter integrated in the field distributor compared to the use ofthe inverter when it is integrated in the motor.
Different factory settings when MOVIMOT® is integrated in the field distributor
Note the changes to the factory settings when using MOVIMOT® integrated in Z.7or Z.8. field distributors. The remaining settings are identical with MOVIMOT®
integrated in the motor. Refer to the MOVIMOT® MM..C" operating instructions.
DIP switch S1:
Setpoint potentiometer f1:
S1 1 2 3 4 5
Motorprotec-
tion
6
Motorpower rating
7
PWMFrequency
8
No-loaddamping
Meaning RS-485 address
20 21 22 23
ON 1 1 1 1 Off Motor one sizesmaller
Variable(16,8,4 kHz) On
OFF 0 0 0 0 On Adjusted 4kHz Off
51261AXX
[1] Factory setting
1 2 3 4 5 6 7 8 9 100
100f [Hz]
2
75
25
50
10 f1
[1]
00
I
90 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
11 MOVIMOT® frequency inverter integrated in the field distributorSupplementary Field Distributor Startup Information
Additional functions for MOVIMOT® integrated in field distributor
The following additional functions are available (to a limited extent) when MOVIMOT® isintegrated in the Z.7/Z.8 field distributor. A detailed description of the additionalfunctions can be found in the "MOVIMOT® MM..C" operating instructions.
Additional function Restriction
1 MOVIMOT® with increased ramp times –
2 MOVIMOT® with adjustable current limitation (fault if exceeded)
–
3 MOVIMOT® with adjustable current limitation (can be changed using using terminal f1/f2)
–
4 MOVIMOT® with bus configuration Only possible with MQ.. fieldbus interfaces
5 MOVIMOT® with motor protection in Z.7/Z.8 field dis-tributor
Parameter settings can only be made for the bus in combination with the MQ.. fieldbus interface
6 MOVIMOT® with maximum 8 kHz PWM frequency –
7 MOVIMOT® with rapid start/stop The mechanical brake can only be controlled by MOVIMOT®. Do not control the brake using the relay output.
8 MOVIMOT® with minimum frequency 0 Hz –
10 MOVIMOT® with minimum frequency 0 Hz and reduced torque at low frequencies
–
11 Monitoring of supply-phase fault deactivated –
12 MOVIMOT® with rapid start/stop and motor protection in Z.7 and Z.8 field distributors
The mechanical brake can only be controlled by MOVIMOT®. Do not control the brake using the relay output.
14 Deactivation of slip compensation –
Do not use additional function 9 "MOVIMOT® for hoist applications" andadditional function 13 "MOVIMOT® for hoist applications with extended n-monitoring" when the MOVIMOT® inverter is integrated in the Z.7/Z.8 fielddistributor.
00
I
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 91
12Coding of process dataMOVILINK® Unit Profile
12 MOVILINK® Unit Profile12.1 Coding of process data
The same process data information is used for control and setpoint selection in all field-bus systems. The process data is coded according to the standard MOVILINK® profilefor SEW drive inverters. The following variants are available for MOVIMOT® inverters:• 2 process data words (2 PD) • 3 process data words (3 PD)
2 process data words
The higher-level controller sends the process output data "Control word" and "Speed[%]" to the MOVIMOT® unit to control MOVIMOT® using two process data words; theprocess input data "Status word 1" and "Output current" are sent from the MOVIMOT®
unit to the higher-level controller.
3 process data words
When control uses 3 process data words, the ramp is sent as the additional processoutput data word and status word 2 is sent as the third process input data word.
51334AXX
PO = Process output data PI = Process input data
PO1 = Control word PI1 = Status word 1
PO2 = speed (%) PI2 = Output current
PO3 = Ramp PI3 = Status word 2
MOVIMOT®
PO1 PO2 PO3
Master
PI1 PI2 PI3
PO
PI
92 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
12 Coding of process dataMOVILINK® Unit Profile
Process output data
Process output data is sent from the higher-level controller to the MOVIMOT® inverter(control information and setpoints). However, the data only comes into effect in MOVI-MOT® when the RS-485 address in MOVIMOT® (DIP switch S1/1 to S1/4) is set to avalue other than 0. MOVIMOT® can be controlled using the following process outputdata:• PO1: Control word• PO2: Speed [%] (setpoint)• PO3: Ramp
Control word, bits 0 – 2
The "Enable" control command is specified with bits 0...2 by entering the control word =0006hex. The CW and/or CCW input terminal must also be set to +24 V (jumpered) toenable the MOVIMOT® unit.The "Stop" control command is issued by resetting bit 2 = "0". Use the stop command0002hex to enable compatibility with other SEW inverter series. MOVIMOT® alwaystriggers a stop at the current ramp whenever bit 2 = "0", regardless of the status of bit 0and bit 1.
Control word bit 6 = Reset
In the event of a malfunction, the fault can be acknowledged with bit 6 = "1" (Reset). Forreasons of compatibility, any control bits not assigned must be set to the value 0.
Speed [%] The speed setpoint is specified as a percentage value based on the maximum speedset with the f1 setpoint potentiometer.Coding: C000hex = -100 % (CCW rotation)
4000hex = +100 % (clockwise rotation)→ 1 digit = 0.0061 %
Example: 80 % fmax, CCW rotation:Invoice: –80 % / 0.0061 = –13115dec = CCC5hex
Ramp The current integrator in the process output data word PO3 is transferred if the processdata exchange takes place using three process data words. The ramp generator set withswitch t1 is used if MOVIMOT® is controlled by two process data.Coding: 1 digit = 1 msRange: 100...10000 msExample: 2.0 s = 2000 ms = 2000dec = 07D0hex
Virtual terminals for releasing the brake without drive enable, only when MOVIMOT® switch S2/2 = "ON"(See the MOVIMOT® operating instructions)
Basic control block
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PO1: Control word Reserved for special functions = "0" "1" = Reset Reserved = "0" "1 1 0" = Enable
otherwise stop
PO2: Setpoint Signed percentage / 0.0061 %Example: -80 % / 0.0061 % = - 13115 = CCC5hex
PO3: Ramp (for3-word protocol only)
Time from 0 to 50 Hz in ms (range: 100...10000 ms)Example: 2.0 s = 2000 ms = 07D0hex
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 93
12Coding of process dataMOVILINK® Unit Profile
Process input data
The MOVIMOT® inverter sends back process input data to the higher-level controller.The process input data consists of status and actual value information. MOVIMOT®
supports the following process input data:• PI1: Status word 1• PI2: Output current• PI3: Status word 2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Controller enabled = "1"
PI1: Status word 1
Unit status (bit 5 = "0")0 = Inverter not ready2 = No enable4 = Enabled
Fault number (bit 5 = "1")
Unit enabled = "1"
PO data enabled = "1"
Reserved
Reserved
Fault/warning = "1"
Reserved
Reserved
PI2: Current actualvalue
16 bit integer with sign x 0.1 % INExample: 0320hex = 800 x 0.1 % IN = 80 % IN
PI3: Status word 2(for
3-word protocol only)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Controller enabled = "1"
Unit enabled = "1"
PO data enabled = "1"
Reserved
Reserved
Fault/warning = "1"
Reserved
ReservedO1 (brake) "1" = Brake applied"0" = Brake releasedO2 (ready)
I1 (CW)
I2 (CCW)
I3 (setpoint f2)
Reserved 0
Reserved 0
Reserved 0
94 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
12 Sample program for Simatic S7 and fieldbusMOVILINK® Unit Profile
12.2 Sample program for Simatic S7 and fieldbusA sample program for Simatic S7 demonstrates the processing of process data as wellas the digital inputs and outputs of the MF fieldbus interface.
Assigning the addresses of the process data in the higher-level controller
In the example, the process data of the MOVIMOT® fieldbus interface is stored in thePLC memory range PW132 – PW136.The additional output/input word is administered in AW 100 or EW 100.
Processing digital inputs/outputs of the MF..
The AND operation of digital inputs DI 0..3 controls the digital outputs DO 0 and DO 1on the MF...:
This section simply demonstrates how to create a PLC program using a non-binding example. SEW is not liable for the content of the sample program.
61726AXX
[1] Address range[2] Output addresses[3] Input addresses
PO Process output dataPO1 Control wordPO2 Speed [%]PO3 RampDO Digital outputs
PI Process input dataPI1 Status word 1PI2 Output currentPI3 Status word 2DI Digital inputs
AW132
AW134
AW136
EW132
EW134
EW136
PO1
PO2
PO3
PI1
PI2
PI3
[2]
[3]
[1]
MOVIMOT®
-+
+ MQ..AW100
EW100 DI
DO
PO1 PO2 PO3
PI1 PI2 PI3
PO
DO
DI
PI
Master
U E 100.0 // When DI 0 = "1"U E 100.1 // DI 1 = "1"U E 100.2 // DI 2 = "1"U E 100.3 // DI 3 = "1"= A 100.0 // then DO 0 = "1"= A 100.1 // DO 1 = "1"
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 95
12Sample program for Simatic S7 and fieldbusMOVILINK® Unit Profile
Controlling MOVIMOT®
You enable the MOVIMOT® drive with input DI0:• E 100.0 = "0": Control command "Stop"• E 100.0 = "1": Control command "Enable"
Direction of rotation and speed are set via input DI1:• E 100.1 = "0": 50 % fmax clockwise direction• E 100.1 = "1": 50 % fmax counterclockwise directionThe drive is accelerated and decelerated with an integrator ramp of 1 s.The process input data is saved until further processing in the flag word 20 to 24.
U E 100.0 // Give control command "Enable" with input 100.0SPB FREI
L W#16#2 //Control command "Stop"T PAW 132 // Write to PO1 (control word 1)SPA SOLL
FREI: L W#16#6 // MOVIMOT control command "Enable" (0006hex)T PAW 132 // Write to PO1 (control word 1)
SOLL: U E 100.1 // Set direction of rotation with input 100.1.SPB LINK // When input 100.1 = "1", then CCW
L W#16#2000 // Set speed = 50% fmax CW rotation (=2000hex)T PAW 134 // Write to PO2 (speed [%])SPA ISTW
LINK: L W#16#E000 // Set speed = 50% fmax CCW rotation (=E000hex)T PAW 134 // Write to PO2 (speed [%])
ISTW: L 1000 // Ramp = 1s (1000dec)T PAW 136 // Write to PO3 (Ramp)
L PEW 132 // Load PI1 (status word 1)T MW 20 // and save in buffer
L PEW 134 // Load PI2 (output current)T MW 22 // and save in buffer
L PEW 136 // Load PI3 (status word 2)T MW 24 // and save in buffer
BE
96 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
13 MQ.. parameter listParameters
13 Parameters13.1 MQ.. parameter list
Parame-ters
Parameters Index Unit Access Default Meaning / Value range
010 Inverter status 8310 RO 0 Low word coded, as status word 1
011 Operating state 8310 RO 0 Low word coded, as status word 1
012 Error status 8310 RO 0 Low word coded, as status word 1
013 Current parameter set 8310 RO 0 Low word coded, as status word 1
015 Hours of operation 8328 [s] RO 0
030 Binary input DI00 8844 RW 16 0: No function16: IPOS input32: MQX Encoder In031 Binary input DI01 8335 RW 16
032 Binary input DI02 8336 RO 16
033 Binary input DI03 8337 RO 16
034 Binary input DI04 8338 RO 16
035 Binary input DI05 8339 RO 16
036 Binary inputs DI00 – DI05 8334 RO 16
050 Binary output DO00 8843 RW 21 0: No function21: IPOS output22: IPOS error051 Binary output DO01 8350 RW 21
053 Binary output DO00... 8360 RO
070 Unit type 8301 RO
076 Firmware basic unit 8300 RO
090 PD configuration 8451 RO
091 Fieldbus type 8452 RO
092 Fieldbus baud rate 8453 RO
093 Fieldbus address 8454 RO
094 PO1 setpoint 8455 RO
095 PO2 setpoint 8456 RO
096 PO3 setpoint 8457 RO
097 PI1 actual value 8458 RO
098 PI2 actual value 8459 RO
099 PI3 actual value 8460 RO
504 Encoder monitoring 8832 RW 1 0: OFF 1: ON
608 Binary input DI00 8844 RW 16 0: No function16: IPOS input32: MQX Encoder In600 Binary input DI01 8335 RW 16
601 Binary input DI02 8336 RO 16
602 Binary input DI03 8337 RO 16
603 Binary input DI04 8338 RO 16
604 Binary input DI05 8339 RO 16
628 Binary output DO00 8843 RW 21 0: No function21: IPOS output22: IPOS error620 Binary output DO01 8350 RW 21
802 Factory setting 8594 R/RW 0 0: No1: Yes2: Delivery condition
810 RS-485 address 8597 RO 0
812 RS-485 timeout delay 8599 [s] RO 1
819 Fieldbus timeout delay 8606 [s] RO
P6..
P60.
P600
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 97
13MQ.. parameter listParameters
831 Response fieldbus timeout 8610 RW 10 0: No response10: PO DATA = 0
840 Manual reset 8617 RW 0: OFF 1: ON
870 Setpoint description PO1 8304 RO 12 IPOS PO-DATA
871 Setpoint description PO2 8305 RO 12 IPOS PO-DATA
872 Setpoint description PO3 8306 RO 12 IPOS PO-DATA
873 Actual value description PI1 8307 RO 9 IPOS PI-DATA
874 Actual value description PI2 8308 RO 9 IPOS PI-DATA
875 Actual value description PI3 8309 RO 9 IPOS PI-DATA
- IPOS control word 8691 RW 0
- IPOS program length 8695 RW 0
- IPOS variables H0 – H9 11000-11009
RW – Memory variable
- IPOS variable H10s – H511 11010-11511
RW 0
- IPOS code 16000-17023
RW 0
Parame-ters
Parameters Index Unit Access Default Meaning / Value range
P6..
P60.
P600
98 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
14 Status LEDMOVIMOT® Diagnostics
14 MOVIMOT® Diagnostics14.1 Status LED
The status LED is located on the top of the MOVIMOT® inverter (see the followingfigure).
Meaning of the status LEDs
The three-color LED signals the operating and fault states.
50867AXX
[1] MOVIMOT® status LED
[1]
LED color
LED status Operating state Description
– Off Not ready for operation
No 24 V power supply
Yel-low
Flashes steadily Not ready for operation
Self-test phase active or 24 V power supply present but supply voltage not OK
Yel-low
Flashing evenly, fast Ready for operation Brake release without drive enable active(only with S2/2 = "ON")
Yel-low
Steady light Ready, but unit inhibited
24 V power supply and supply voltage OK, but no enable signal
Green / yel-low
Flashing with alter-nating colors
Ready, but timeout
Faulty communication with cyclical data exchange
Green Steady light Unit enabled Motor in operation
Green Flashing evenly, fast Current limit active Drive operating at current limit
Red Steady light Not ready for operation
Check theDC 24 V supply.Make sure that there is a smoothed DC voltage with low ripple (residual ripple max. 13 %) present
Red 2x flashing, break Error 07 DC link voltage too high
Red Flashing slowly Error 08 Fault speed monitoring (only with S2/4 = "ON")
Error 90Error 09
Motor – inverter assignment incorrect (e.g. MM03 – DT71D4 m)
Errors 17 to 24, 37 CPU error
Errors 25, 94 EEPROM error
Red 3x flashing, breakError 01 Overcurrent in output stage
Error 11 Overtemperature in output stage
Red 4x flashing, break Error 84 Overtemperature in motor Motor – frequency inverter assignment incorrect
Red 5x flashing, break Error 89 Overtemperature in brakeMotor – frequency inverter assignment incorrect
Red 6x flashing, break Error 06 Mains phase failure
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 99
14Error tableMOVIMOT® Diagnostics
14.2 Error table
Error Cause / Solution
Communication timeout (motor comes to a stop without error code)
• Missing connection ⊥, RS+, RS- between MOVIMOT® and RS-485 master. Check and establish connection, especially earth.
• EMC influence Check shielding of data lines and improve, if necessary.• Incorrect type (cyclical) for acyclical data traffic, protocol period between the individual tele-
grams is longer than 1 s (timeout).Check the number of MOVIMOT® units connected to the master (a maximum of 8 MOVIMOT® units can be connected as slaves for cyclic communication).Reduce telegram cycle or select telegram type "acyclic."
DC link voltage too low, supply system off was detected(motor stops without error code)
Check supply system leads, supply voltage and 24 V electronics supply voltage for interrup-tion. Check the 24 V electronics supply voltage (permitted voltage range 24 V ± 25 %, EN 61131-2 residual ripple max. 13 %)Motor restarts automatically as soon as the voltage reaches normal values.
Error code 01 Overcurrent in output stage
Short circuit on inverter output.Check the connection between the inverter output and the motor as well as the motor winding for short circuits.Reset the fault by switching off the DC 24 V supply voltage or resetting the error.
Error code 06 Phase failure(The fault can only be detected when the drive is at load)
Check the supply system cable for phase failure. Reset the fault by switching off the DC 24 V supply voltage or resetting the error.
Error code 07 DC link voltage too high
• Ramp time too short => Increase ramp time.• Faulty connection between brake coil/braking resistor
→ Check the connection between braking resistor/brake coil. Correct, if necessary.• Incorrect internal resistance of brake coil/braking resistor
→ Check the internal resistance of the brake coil/braking resistor(see Sec. "Technical Data").
• Thermal overload in braking resistor → Wrong size of braking resistor selected.• Invalid voltage range of the supply input voltage → check supply input voltage for permitted
voltage rangeReset the error by switching off the DC 24 V supply voltage or performing a reset.
Error code 08Speed monitoring
Speed monitoring has tripped, drive is overloaded → Reduce drive load.Reset the error by switching off the DC 24 V supply voltage or performing a reset.
Error code 11 Thermal overload of the output stage or internal unit fault
• Clean the heat sink• Lower ambient temperature• Prevent heat build-up• Reduce the load on the driveReset the error by switching off the DC 24 V supply voltage or performing a reset.
Error codes 17 to 24, 37CPU error
Reset the error by switching off the DC 24 V supply voltage or performing a reset.
Error code 25, 94EEPROM error
Reset the error by switching off the DC 24 V supply voltage or performing a reset.
Error code 84 Thermal overload of motor
• When the MOVIMOT® inverter is installed close to the motor, set DIP switch S1/5 to "ON".• For combinations of "MOVIMOT® and motor with one lower power rating", check the set-
ting of DIP switch S1/6.• Lower ambient temperature• Prevent heat build-up• Reduce the load on the motor • Increase the speed• Check the combination of the drive and MOVIMOT® frequency inverter if the fault is sig-
naled shortly after the first enable.• The temperature monitoring in the motor (TH winding thermostat) has tripped when using
MOVIMOT® with the selected extra function 5 → Reduce load on the motor.Reset the error by switching off the DC 24 V supply voltage or performing a reset.
100 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
14 Error tableMOVIMOT® Diagnostics
Error code 89 Thermal overload of brake coil or brake coil defective, brake coil connected incorrectly
• Increase the set ramp time• Brake inspection (see Sec. "Inspection and Maintenance")• Check brake coil connection• Contact SEW Service• Check the combination of the drive (brake coil) and MOVIMOT® frequency inverter if the
fault is signaled shortly after the first enable.• For combinations of "MOVIMOT® and motor with one lower power rating", check the
setting of DIP switch S1/6. Reset the error by switching off the DC 24 V supply voltage or performing a reset.
Error code 91 Communication error between fieldbus gateway and MOVIMOT® (this error is generated by the bus module)
• Check electrical connection between fieldbus gateway and MOVIMOT® (RS-485).• The error is automatically reset after removing the cause, a reset via control word is not
possible.
Error Cause / Solution
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 101
15Error table for the standard sectionError tables for MQS
15 Error tables for MQS15.1 Error table for the standard section
Error code/ Designation
Response Cause Measure
10 IPOS ILLOP IPOS program stoppedDO = 0
• Error in IPOS program, see IPOS variable H469 for more information
• Correct, load and reset IPOS program
14 Encoder error Communication to MOVIMOT® stopsDO = 0
• Interruption of one or both connec-tions to proximity encoder NV26
• Check the electrical connection between MQ.. and NV26.
17 Stack overflow • Inverter electronics is faulty, possibly due to EMC influence
• Check grounding and shielding and repair, if necessary.
• If the error occurs again, contact SEW service.
18 Stack underflow
19 NMI
20 Undefined Opcode
21 Protection fault
22 Illegal word oper-and access
23 Illegal instruc-tion access
24 Illegal external bus access
25 EEPROM • Error while accessing EEPROM • Call up the factory setting "Delivery state", perform a reset and set parameters again (Caution: The IPOS program will be deleted)
• If the fault occurs again, contact SEW service
28 Fieldbus timeout Process output data = 0DO = 0(can be switched off)
• No master-slave communication took place within the configured response monitoring period
• Check communications routine of the master
32 IPOS index overflow
IPOS program stoppedDO = 0
• Programming principles violated leading to system internal stack overflow
• Check IPOS user program and correct if necessary.
37 Watchdog error Communication to MOVIMOT® stopsDO = 0
• Error during execution of system software
• Consult SEW Service
41 Watchdog option • IPOS Watchdog, IPOS program execution time is longer than adjusted Watchdog time
• Check the time specified in the "_WdOn()" command.
45 Initialization error • Error after self-test during reset • Perform a reset. If the fault reoccurs, contact SEW service
77 Invalid IPOS control value
IPOS program stoppedDO = 0
• An attempt was made to set an invalid automatic mode
• Check write values of external controller
83 Short circuit output
None • DO0, DO1 or the voltage supply of the VO24 sensors is shorted
• Check the cabling/load of the DO0 and DO1 outputs as well as the voltage supplies of the sensors
91 System error No • One or several stations (MOVIMOT®) could not be addressed by the MQ.. within the timeout interval
• Check voltage supply and RS-485 wiring
• Check address of configured stations
97 Copy data Communication to MOVIMOT® stopsDO = 0
• Error occurred when data set was being copied Data is not consistent
• Try again to copy the data, or restore the factory setting "Delivery state" and perform a reset first.
102 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
15 Error table for the standard sectionError tables for MQS
15.2 Error table for the standard section
Error code/ Designation
Response Cause Measure
00 No error -
01 Internal process-ing error
• F-DO0 = 0 (discon-nection of safe out-put)
• F-DIx = 0 (=> safe state)
• Passivation of module
• Malfunction in safety electronics, possibly due to EMC interference
• Check the installation (EMC)• Switch the 24 V voltage off and on
again• Reintegrate the module• If the fault occurs again, replace
the MQS module or contact SEW Service!
02 Internal system error
03 Communication error
• PROFIsafe® communication inter-rupted
• Check the project planning (e.g. PROFIsafe® monitoring time)
• Reintegrate the module
04 Error in the elec-tronics supply
• Electronics supply is outside the specified limits
• Check the installation (EMC)• Switch the 24 V voltage off and on
again• Reintegrate the module• If the fault occurs again, replace
the MQS module or contact SEW Service!
05 Error in the load voltage supply
• Load voltage supply is missing or is outside the specified limits
• Check the 24 V load voltage sup-ply
• Reintegrate the module
20 Internal error at safe input (F-DIx)
• F-DIx = 0 (=> safe state)
• Passivation of module
• Malfunction in safety electronics, possibly due to EMC interference
• Check the installation (EMC)• Switch the 24 V voltage off and on
again• Reintegrate the module• If the fault occurs again, replace
the MQS module or contact SEW Service!
21 Short circuit at safe input (F-DIx)
• Short circuit on the 24 V supply voltage or
• Cross-fault between F-DI0 and F-DI1 or F-SS0 and F-SS1
• Check the installation / cabling and repair the short circuit
• Reintegrate the module
50 Internal error at safe output (F-DO0)
• F-DO0 = 0 (discon-nection of safe out-put)
• Passivation of module
• Malfunction in safety electronics, possibly due to EMC interference
• Check the installation (EMC)• Switch the 24 V voltage off and on
again• Reintegrate the module• If the fault occurs again, replace
the MQS module or contact SEW Service!
51 Short circuit at safe output (F-DO0)
• Short circuit on the 24 V supply voltage or reference potential
• Short circuit between F-DO0_P and F-DO0_M
• Check the installation / cabling and repair the short circuit
• Reintegrate the module
52 Overload at safe output (F-DO0)
• Overload at F-DO0 (current is too high!)
• Check the installation / cabling and remedy the overload
• Reintegrate the module
111 Internal commu-nication error
• F-DO0 = 0 (discon-nection of safe output)
• F-DIx = 0 (=> safe state)
• Passivation of module
• Malfunction in safety electronics, possibly due to EMC interference
• Check the installation (EMC)• Switch the 24 V voltage off and on
again• Reintegrate the module• If the fault occurs again, replace
the MQS module or contact SEW Service!
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 103
16Technical data for the PROFIBUS MQS.. interfaceTechnical Data
16 Technical Data16.1 Technical data for the PROFIBUS MQS.. interface
General technical data for MQS
MQS electronics and F sensor/actuator supply
UIN = DC 24 V -15 % / +20 % to EN 61131-2IE ≤ 250 mA + output current of the actuator + sensor supply + F sensor supply
Load voltage supply(for safe output)
UIN = DC 24 V -15 % / +20 % to EN 61131-2IE ≤ 1.3 A
Electrical isolation • PROFIBUS-DP connection potential-free• Separate standard electronics from safety electronics
Bus connection technology Two cage clamp terminals each for incoming and outgoing bus cables (optional M12)
Shielding via EMC metal cable glands
Standard binary inputs (sensors) PLC-compatible to EN 61131-2 (digital inputs type 1), Ri ≈ 3.0 kΩ, sampling interval about 5 ms
Signal level +15 V ... +30 V-3 V ... +5 V
→ “1” = Contact closed→ “0” = Contact open
Standard sensor supplyRated currentInternal voltage drop
DC 24 V to EN 61131-2 interference voltage proof and short-circuit proofΣ 500 mAmax. 1 V
Standard binary outputs (actuators)Signal levelRated currentLeakage currentInternal voltage drop
PLC-compatible to EN61131-2, interference voltage proof and short-circuit proof"0" = 0 V, "1" = 24 V500 mAmax. 0.2 mAmax. 1 V
Length of RS485 cable Max. 30 m between MQS.. and MOVIMOT® if installed separately
Cable length for standard inputs (DIx) Max. 30 m
Cable length for sensor supply (VO24) max. 30 m
Cable length for standard outputs (DOx) max. 30 m
EMC Meets EN 61800-3
Ambient temperature -25 °C to +55°C
Climate class Class 3K3 to EN 60721-3-3
Storage temperature -25 °C to +85°C
Enclosure IP65 (installed on MFZ.. connection module, all plug connections sealed)
Overvoltage category III according to IEC 60664-1 (VDE 0110-1)
Pollution class 2 according to IEC 60664-1 (VDE 0110-1) within the housing
Vibration Meets EN 50178
Pi
fkVA
Hz
n
104 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
16 Technical data for the PROFIBUS MQS.. interfaceTechnical Data
Technical data for the MQS safety section
Safety featuresMaximum possible safety class SIL 3 to EN 61508, category 4 to EN 954-1
and performance level e to EN ISO 13849-1
System structure 2-channel with diagnostics (1oo2D)
Operating mode "High demand" to EN 61508
Probability of a hazardous breakdown per hour (PFH value)
< 1,00E-09 (1 FIT)
Proof test interval (EN 61508) 10 years, then the components have to be replaced
Repair time 100 hours
Safe state Value "0" for all safety-oriented process values – F-DI and F-DO (output deactivated)
Safe inputsF-DI0, F-DI1
Level to EN 61131-2 DC24V, type, no electrical isolation
Signal level +15 V ... +30 V-3 V ... +5 V
→ “1” = Contact closed→ “0” = Contact open
Input resistance Approximately 4 kΩ
Input filter time 4 ms
Minimum input signal duration 15 ms
Response time (sensor switches -> F-DIx updated in PROFIsafe® user data)
≤ 25 ms (incl. filter time)
Sensor supply (clock outputs)F-SS0, F-SS1
DC 24 V output short-circuit proof and protected against overload to EN 61131-2, no electrical isolation
Rated current Each 250 mA
Leakage current Max. 0.5 mA
Internal voltage drop Max. 2 V
Short circuit protection Electronic, trigger value: 0.7 A ... 2.1 A
Safe outputP-M switching(from load voltage supply)
DC24V output short-circuit proof and protected against overload to EN 61131-2
Rated current 1 A
Leakage current (for "0" signal) Typically -2 mA (at 2 V / 1 kΩ load resistance)(Note: current flows from F-DO_M to FDO_P)
Internal voltage drop (P and M output) Max. 3 V
Short circuit protection Electronic, trigger value: 2.8 A ... 9 A
Overload protection Trigger value: 1.4 A ... 1.6 A
Load resistance range 24 Ω ... 1 kΩ
Voltage limitation for disconnectionof an inductive load
Typically -70 V
Response time (command viaPROFIsafe® → output switches)
≤ 25 ms
Cable length Safe binary input (F-DIx)
max. 30 m
Cable length Safe voltage supply (F-SSx)
max. 30 m
Cable lengthSafe output (F-DO0_P, F-DO0_M)
Max. 30 m
Important:The safety function of MOVIMOT® frequency inverters is only permitted forapplications up to category 3 according to EN 954-1 (see certificate).
Pi
fkVA
Hz
n
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 105
16Technical data for the PROFIBUS MQS.. interfaceTechnical Data
PROFIBUS specifications
PROFIBUS protocol option PROFIBUS-DPV1 (PROFIsafe® V1/V2)
Supported baud rates 9.6 kBaud ...12 MBaud (with automatic detection)
Bus terminator integrated, can be set via DIP switch (to EN 50170)
Permitted cable length for PROFIBUS • 9,6 kBaud: 1200 m• 19,2 kBaud: 1200 m• 93.75 kBaud: 1200 m• 187.5 kBaud: 1000 m• 500 kBaud: 400 m• 1.5 MBaud: 200 m• 12 Mbaud: 100 mTo extend the length, several segments can be coupled via repeater. The max. expan-sion/cascading depth can be found in the manuals for the PROFIBUS DP master or the repeater modules.
DP ident. number 6005 hex (24577 dec)
DP Configuration One process data word with and without parameter channel (see the section "Process data configuration")
Set-Prm application data Max. 10 bytes, without function
Length of diagnostics data 6 byte to EN 50170 (V2)
Address settings "Set-Slave-Address" not supported, can be set using DIP switch
Number of parallel C2 connections 2
Supported data record Index 47
Supported slot number Recommendation: 0
Manufacturer code 10A hex (SEW-EURODRIVE)
Profiles ID 0
C2 response timeout 1 s
Max. length C1 channel 240 Byte
Max. length C2 channel 240 Byte
Name of the GSD file SEW_6005.GSD
Name of bitmap file SEW6005N.BMPSEW6005S.BMP
Pi
fkVA
Hz
n
106 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
16 Technical data for field distributorsTechnical Data
16.2 Technical data for field distributorsTechnical data for MQ../Z.6.
MQ../Z.6.
Maintenance switch Load interrupter switch and line protectionType: ABB MS 325 – 9 + HK20Switch activation: black/red, triple lock
Ambient temperature -25 °C...55°C
Storage temperature -25 °C...85 °C
Enclosure IP65 (fieldbus interface, power supply connection cover and motor connection cable attached and fastened, all plug connections sealed)
Interface PROFIBUS, InterBus, DeviceNet, CANopen, AS-Interface
Permitted motor cable lengths
max. 30 m (with SEW hybrid cable, type B)
Weight ca. 3.6 kg
Pi
fkVA
Hz
n
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 107
16Technical data for field distributorsTechnical Data
Technical data for field distributor MQ../MM../Z.7. Field distributor type MQ../MM..-503-00/Z.7
MM03C MM05C MM07C MM11C MM15C
Apparent output power with Umains = 380...500 V
SN 1.1 kVA 1.4 kVA 1.8 kVA 2.2 kVA 2.8 kVA
Supply voltagesPermitted range
Umains 3 x 380 VAC / 400 VAC /415 VAC /460 VAC /500 VAC Vmains = 380 VAC - 10 %...500 VAC + 10 %
Supply frequency fmains 50 Hz ... 60 Hz ±10 %
Rated mains current(at Umains = AC 400 V)
Imains 1.3 AAC 1.6 AAC 1.9 AAC 2.4 AAC 3.5 AAC
Output voltage UA 0... Umains
Output frequencyResolutionOperating point
fA 2...100 Hz0.01 Hz400 V at 50 Hz / 100 Hz
Rated output current IN 1.6 AAC 2.0 AAC 2.5 AAC 3.2 AAC 4.0 AAC
Motor power S1PMot 0.37 kW 0.55 kW 0.75 kW 1.1 kW 1.5 kW
Motor power S3 25 % ED
PWM frequency 4 / 8 / 161) kHz
1) 16 kHz PWM frequency (low-noise). When DIP SWITCH S1/7 = ON (factory setting), the units operatewith a 16 kHz PWM frequency (low-noise) and switch back in steps to lower switching frequencies depen-ding on the heat sink temperature.
Current limitation Imax motor: 160 % with � and �regenerative: 160 % with � and �
Maximum motor cable length 15 m (with SEW hybrid cable, type A)
External braking resistor Rmin 150 Ω
Interference immunity Meets EN 61800-3
Interference emission Meets EN 61800-3 and class A limit to EN 55011 and EN 55014
Ambient temperature ϑU -25 °C...40°C (PN reduction: 3 % IN per K to max. 60 °C)
Storage temperature ϑL -25 °C...85 °C
Enclosure IP65 (fieldbus interface, power supply connection cover and motor connection cable attached and fastened, all plug con-nections sealed)
Operating mode DB (EN 60149-1-1 and 1-3), S3 max. cycle duration 10 min-utes
Cooling type (DIN 41 751) Self-cooling
Installation altitude h ≤1000 m (PN reduction: 1 % per 100 m starting at an alti-tude of 1000 m, see also the section "Electrical Installation – Installation instructions" in the MOVIMOT® operating instruc-tions)
Ext. power supply to control electronics
Tl. 11Tl. 13
U = +24 V ± 25 %, EN 61131-2, residual ripple max. 13 %IE ≤ 250 mA, typ. 150 mA at 24 V (only MOVIMOT®)Input capacitance 100 μF
Interface PROFIBUS, InterBus, DeviceNet, CANopen, AS-Interface
Weight ca. 3.6 kg
Pi
fkVA
Hz
n
108 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
16 Technical data for field distributorsTechnical Data
Technical data for field distributor MQ../MM../Z.8.
Field distributor type MQ../MM..-503-00/Z.8
MM03C MM05C MM07C MM11C MM15C MM22C MM30C MM3XC
Apparent output power with Umains = 380...500 V
SN 1.1 kVA 1.4 kVA 1.8 kVA 2.2 kVA 2.8 kVA 3.8 kVA 5.1 kVA 6.7 kVA
Supply voltagesPermitted range
Umains
3 x 380 VAC / 400 VAC /415 VAC /460 VAC /500 VAC Vmains = 380 VAC - 10 %...500 VAC + 10 %
Supply frequency fmains 50 Hz ... 60 Hz ±10 %
Rated mains current(at Umains = AC 400 V)
Imains 1.3 AAC 1.6 AAC 1.9 AAC 2.4 AAC 3.5 AAC 5.0 AAC 6.7 AAC 8.6 AAC
Output voltage UA 0... Umains
Output frequencyResolutionOperating point
fA 2...100 Hz0.01 Hz400 V at 50 Hz / 100 Hz
Rated output current IN 1.6 AAC 2.0 AAC 2.5 AAC 3.2 AAC 4.0 AAC 5.5 AAC 7.3 AAC 9.6 AAC
Motor power S1PMot 0.37 kW 0.55 kW 0.75 kW 1.1 kW 1.5 kW 2.2 kW 3.0 kW
3.0 kW
Motor power S3 25 % ED 4.0 kW
PWM frequency 4 / 8 / 161) kHz
1) 16 kHz PWM frequency (low-noise). When DIP SWITCH S1/7 = ON (factory setting), the units operate with a 16 kHz PWM frequency(low-noise) and switch back in steps to lower switching frequencies depending on the heat sink temperature.
Current limitation Imax motor: 160 % with � and �regenerative: 160 % with � and �
Maximum motor cable length
15 m (with SEW hybrid cable, type A)
External braking resistor Rmin 150 Ω 68 Ω
Interference immunity Meets EN 61800-3
Interference emission Meets EN 61800-3 and class A limit to EN 55011 and EN 55014
Ambient temperature ϑU -25 °C...40°C (PN reduction: 3 % IN per K to max. 55 °C) 2)
2) -25 °C...40 °C with S3 25 % cdf (to max. 55 °C with S3 10 % cdf)
Storage temperature ϑL -25 °C...85 °C
Enclosure IP65 (fieldbus interface, power supply connection cover and motor connection cable attached and fastened, all plug connections sealed)
Operating mode DB (EN 60149-1-1 and 1-3), S3 max. cycle duration 10 minutes
Cooling type (DIN 41 751) Self-cooling
Installation altitude h ≤1000 m (PN reduction: 1 % per 100 m starting at an altitude of 1000 m, see also the sec-tion "Electrical Installation – Installation instructions" in the MOVIMOT® operating instruc-tions)
ext. power supply to control electronics
Tl. 11Tl. 13
U = +24 V ± 25 %, EN 61131-2, residual ripple max. 13 %IE ≤ 250 mA, typ. 150 mA at 24 V (only MOVIMOT®)Input capacitance 100 μF
Maintenance switch Switch disconnector Type: ABB OT16ET3HS3ST1Switch activation: black/red, triple lock
Interface PROFIBUS, InterBus, DeviceNet, CANopen, AS-Interface
Weight Size 1: ca. 5.2 kgSize 2: ca. 6.7 kg
Pi
fkVA
Hz
n
Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor 109
Index
AAdditional code ...................................................66BBus terminating resistors ....................................53CCable
Field distributor MFZ.6. - MOVIMOT® ...............48Field distributors MFZ.7. / MFZ.8. - motor ..........49
Cable shield ........................................................29Coding of process data .......................................91Components, valid ................................................5Conditions, safety ...............................................14Configuration
Procedure for PROFIBUS-DP ...........................70Procedure for PROFIBUS-DPV1 .......................74PROFIsafe properties ......................................57Via PROFIBUS DPV1 ......................................71Via PROFIBUS-DP ..........................................62
Configuring MQS ................................................55Connecting flange
AF2 ...............................................................44AF3 ...............................................................46M12 ...............................................................44
Connecting supply system cables .......................30Connection
Bus (optional) .................................................44F-DIx / F-SSx ..................................................38F-DO0 ............................................................40Field distributor ...............................................35PROFIBUS cable ............................................34Safety-oriented inputs + outputs ........................37Sensors / actuators ..........................................37Standard inputs/outputs ...................................42Standard inputs/outputs via M12 connector ........42Terminal strip X20 ...........................................37
Connection cross section ....................................30Connection modules .................................... 35, 36Contactor switch contacts ...................................30Control function of MQS ......................................61Control via PROFIBUS-DP .................................61Current carrying capacity ....................................30DData exchange with MQS ...................................59Data set DS47 .....................................................73Default program ..................................................61Designated use .....................................................8Diagnostics
MOVIMOT® ....................................................98
Via PROFIBUS .............................................. 83DIP switch on MOVIMOT® ................................ 50Disposal ............................................................... 8EEarth leakage circuit breakers ........................... 30Earth-leakage monitors ...................................... 30EMC ............................................................. 28, 33Equipotential bonding ........................................ 28Error class .......................................................... 65Error code .......................................................... 65Error states
Safety section ................................................ 82Standard section ............................................ 80
Error tableMOVIMOT® ................................................... 99MQS standard section ................................... 101
FF parameters ...................................................... 57Fault response ................................................... 61Feldbus-Schnittstelle MQS22F, MQS32F .......... 18Field distributor
MQS.../Z.6. .................................................... 19MQS../Z.7. ..................................................... 20MQS../Z.8. ..................................................... 21
Field distributor fuse ........................................... 30Fieldbus interface MQS22F ............................... 18Fieldbus interface MQS32F ............................... 18Fieldbus timeout ................................................. 80Functionality of PROFIBUS interface MQS ........ 59GGSD file, Installation .......................................... 54HHazard caused by drive coasting ....................... 15IImportant notes .................................................... 7Index addressing ................................................ 63Installation .......................................................... 23
Field distributor MQS.../MM/Z.7. ....................... 25Field distributor MQS.../MM03-MM15/Z.8. ......... 26Field distributor MQS.../MM22-MM3X/Z.8. ......... 27Field distributor MQS.../Z.6. ............................. 24
Installation 1,000 m above sea level .................. 32Installation in damp locations or in the open ...... 23Installation regulations ....................................... 23Installation regulations for field distributors ........ 30Installation, mechanical ...................................... 23
110 Manual – Drive System for Decentralized Installation - PROFIsafe® Field Distributor
Index
LLEDs der MQS
Bedeutung ......................................................80LEDs of MQS
Meaning .........................................................80Overview ........................................................79
MMaintenance switch ..................................... 85, 87Mapping input/ output data in the PLC address ran-ge ........................................................................60Maximum frequency ............................................50Maximum speed ..................................................50Metal cable glands ..............................................33MOVILINK® parameter requests ........................75MOVILINK® unit profile ......................................91MOVIMOT factory settings® ...............................89MOVIMOT® ........................................................22MOVIMOT® additional functions ........................90MOVIMOT® LEDs ..............................................98MOVIMOT® safety concept ................................12OOperational environment .......................................8Other applicable documentation ...........................7Overview ...............................................................6PParameter channel
Data range .....................................................64Incorrect service execution ...............................64Management ...................................................63Structure ........................................................62
Parameter channel DPV1 ...................................72Parameterkanal
Rкckkehr-Codes ............................................65Parameters .........................................................96
Reading and writing via PROFIBUS-DP .............68Prefabricated cables ...........................................48Principle of emergency stop function ..................15Process input data ..............................................93Process output data ............................................92PROFIBUS address on MQS ..............................51PROFIsafe® safety concept ...............................11PROFIsafe Timeout ............................................82Project planning ..................................................56
MQS ..............................................................54
Protection devices .............................................. 32RRкckkehr-Codes .............................................. 77Requirements
External sensors and actuators ........................ 17Installation ..................................................... 16Operation ...................................................... 17Startup .......................................................... 17
Reserved byte .................................................... 63Return codes ................................................ 65, 77RS-485 timeout .................................................. 81SSafety notes ......................................................... 7
Field distributors ............................................. 10General information .......................................... 9MOVIMOT® drives ........................................... 9
Safety technology .............................................. 11Sample program for Simatic S7 and fieldbus ..... 94Startup
Procedure ...................................................... 50Startup information
Field distributor MQS.../MM../Z.7. ..................... 86Field distributor MQS.../MM../Z.8. ..................... 87Field distributor MQS.../Z.6. ............................. 85MOVIMOT® frequency inverters ...................... 89
TTechnical data
Field distributor MQ../MM../Z.7. ...................... 107Field distributor MQ../MM../Z.8. ...................... 108Field distributor MQ../Z.6. .............................. 106MQS safety section ....................................... 104PROFIBUS .................................................. 105PROFIBUS MQS interface, general information 103
UUL-compliant installation .................................... 32Unit design ......................................................... 18
Field distributor .............................................. 19Fieldbus interfaces ......................................... 18
Unit designations ................................................. 5Unit errors .......................................................... 81WWarning notes ...................................................... 7Wiring
AF2 ............................................................... 45AF3 ............................................................... 47
Wiring check ...................................................... 34
Address List
07/2007 111
Address ListGermany
HeadquartersProductionSales
Bruchsal SEW-EURODRIVE GmbH & Co KGErnst-Blickle-Straße 42 D-76646 BruchsalP.O. BoxPostfach 3023 • D-76642 Bruchsal
Tel. +49 7251 75-0Fax +49 7251 75-1970http://[email protected]
Service Competence Center
Central SEW-EURODRIVE GmbH & Co KGErnst-Blickle-Straße 1 D-76676 Graben-Neudorf
Tel. +49 7251 75-1710Fax +49 7251 [email protected]
North SEW-EURODRIVE GmbH & Co KGAlte Ricklinger Straße 40-42 D-30823 Garbsen (near Hannover)
Tel. +49 5137 8798-30Fax +49 5137 [email protected]
East SEW-EURODRIVE GmbH & Co KGDänkritzer Weg 1D-08393 Meerane (near Zwickau)
Tel. +49 3764 7606-0Fax +49 3764 [email protected]
South SEW-EURODRIVE GmbH & Co KGDomagkstraße 5D-85551 Kirchheim (near München)
Tel. +49 89 909552-10Fax +49 89 [email protected]
West SEW-EURODRIVE GmbH & Co KGSiemensstraße 1D-40764 Langenfeld (near Düsseldorf)
Tel. +49 2173 8507-30Fax +49 2173 [email protected]
Electronics SEW-EURODRIVE GmbH & Co KGErnst-Blickle-Straße 42 D-76646 Bruchsal
Tel. +49 7251 75-1780Fax +49 7251 [email protected]
Drive Service Hotline / 24 Hour Service +49 180 5 SEWHELP+49 180 5 7394357
Additional addresses for service in Germany provided on request!
France
ProductionSalesService
Haguenau SEW-USOCOME 48-54, route de Soufflenheim B. P. 20185F-67506 Haguenau Cedex
Tel. +33 3 88 73 67 00 Fax +33 3 88 73 66 00http://[email protected]
Production Forbach SEW-EUROCOME Zone Industrielle Technopôle Forbach SudB. P. 30269F-57604 Forbach Cedex
Tel. +33 3 87 29 38 00
AssemblySalesService
Bordeaux SEW-USOCOME Parc d'activités de Magellan62, avenue de Magellan - B. P. 182F-33607 Pessac Cedex
Tel. +33 5 57 26 39 00Fax +33 5 57 26 39 09
Lyon SEW-USOCOME Parc d'Affaires RooseveltRue Jacques TatiF-69120 Vaulx en Velin
Tel. +33 4 72 15 37 00Fax +33 4 72 15 37 15
Paris SEW-USOCOME Zone industrielle 2, rue Denis Papin F-77390 Verneuil I'Etang
Tel. +33 1 64 42 40 80Fax +33 1 64 42 40 88
Additional addresses for service in France provided on request!
Algeria
Sales Alger Réducom 16, rue des Frères ZaghnounBellevue El-Harrach16200 Alger
Tel. +213 21 8222-84Fax +213 21 8222-84
Argentina
AssemblySalesService
Buenos Aires SEW EURODRIVE ARGENTINA S.A.Centro Industrial Garin, Lote 35Ruta Panamericana Km 37,51619 Garin
Tel. +54 3327 4572-84Fax +54 3327 [email protected]
Address List
112 07/2007
Australia
AssemblySalesService
Melbourne SEW-EURODRIVE PTY. LTD.27 Beverage DriveTullamarine, Victoria 3043
Tel. +61 3 9933-1000Fax +61 3 9933-1003http://[email protected]
Sydney SEW-EURODRIVE PTY. LTD.9, Sleigh Place, Wetherill Park New South Wales, 2164
Tel. +61 2 9725-9900Fax +61 2 [email protected]
Townsville SEW-EURODRIVE PTY. LTD.12 Leyland StreetGarbutt, QLD 4814
Tel. +61 7 4779 4333Fax +61 7 4779 [email protected]
Austria
AssemblySalesService
Wien SEW-EURODRIVE Ges.m.b.H. Richard-Strauss-Strasse 24A-1230 Wien
Tel. +43 1 617 55 00-0Fax +43 1 617 55 00-30http://[email protected]
Belgium
AssemblySalesService
Brüssel SEW Caron-Vector S.A.Avenue Eiffel 5B-1300 Wavre
Tel. +32 10 231-311Fax +32 10 231-336http://[email protected]
Brazil
ProductionSalesService
Sao Paulo SEW-EURODRIVE Brasil Ltda.Avenida Amâncio Gaiolli, 50Caixa Postal: 201-07111-970Guarulhos/SP - Cep.: 07251-250
Tel. +55 11 6489-9133Fax +55 11 6480-3328http://[email protected]
Additional addresses for service in Brazil provided on request!
Bulgaria
Sales Sofia BEVER-DRIVE GmbHBogdanovetz Str.1BG-1606 Sofia
Tel. +359 2 9151160Fax +359 2 [email protected]
Cameroon
Sales Douala Electro-ServicesRue Drouot AkwaB.P. 2024Douala
Tel. +237 4322-99Fax +237 4277-03
Canada
AssemblySalesService
Toronto SEW-EURODRIVE CO. OF CANADA LTD. 210 Walker Drive Bramalea, Ontario L6T3W1
Tel. +1 905 791-1553Fax +1 905 791-2999http://[email protected]
Vancouver SEW-EURODRIVE CO. OF CANADA LTD.7188 Honeyman Street Delta. B.C. V4G 1 E2
Tel. +1 604 946-5535Fax +1 604 [email protected]
Montreal SEW-EURODRIVE CO. OF CANADA LTD.2555 Rue Leger LaSalle, Quebec H8N 2V9
Tel. +1 514 367-1124Fax +1 514 [email protected]
Additional addresses for service in Canada provided on request!
Chile
AssemblySalesService
Santiago de Chile
SEW-EURODRIVE CHILE LTDA.Las Encinas 1295Parque Industrial Valle GrandeLAMPARCH-Santiago de ChileP.O. BoxCasilla 23 Correo Quilicura - Santiago - Chile
Tel. +56 2 75770-00Fax +56 2 75770-01http://[email protected]
Address List
07/2007 113
China
ProductionAssemblySalesService
Tianjin SEW-EURODRIVE (Tianjin) Co., Ltd.No. 46, 7th Avenue, TEDA Tianjin 300457
Tel. +86 22 25322612Fax +86 22 [email protected]://www.sew-eurodrive.com.cn
AssemblySalesService
Suzhou SEW-EURODRIVE (Suzhou) Co., Ltd.333, Suhong Middle RoadSuzhou Industrial ParkJiangsu Province, 215021P. R. China
Tel. +86 512 62581781Fax +86 512 [email protected]
Additional addresses for service in China provided on request!
Colombia
AssemblySalesService
Bogotá SEW-EURODRIVE COLOMBIA LTDA. Calle 22 No. 132-60Bodega 6, Manzana BSantafé de Bogotá
Tel. +57 1 54750-50Fax +57 1 54750-44http://[email protected]
Croatia
SalesService
Zagreb KOMPEKS d. o. o.PIT Erdödy 4 IIHR 10 000 Zagreb
Tel. +385 1 4613-158Fax +385 1 [email protected]
Czech Republic
Sales Praha SEW-EURODRIVE CZ S.R.O.Business Centrum Praha Lužná 591CZ-16000 Praha 6 - Vokovice
Tel. +420 220121234Fax +420 220121237http://[email protected]
Denmark
AssemblySalesService
Kopenhagen SEW-EURODRIVEA/SGeminivej 28-30DK-2670 Greve
Tel. +45 43 9585-00Fax +45 43 9585-09http://[email protected]
Estonia
Sales Tallin ALAS-KUUL ASReti tee 4EE-75301 Peetri küla, Rae vald, Harjumaa
Tel. +372 6593230Fax +372 [email protected]
Finland
AssemblySalesService
Lahti SEW-EURODRIVE OYVesimäentie 4FIN-15860 Hollola 2
Tel. +358 201 589-300Fax +358 3 [email protected]://www.sew-eurodrive.fi
Gabon
Sales Libreville Electro-ServicesB.P. 1889Libreville
Tel. +241 7340-11Fax +241 7340-12
Great Britain
AssemblySalesService
Normanton SEW-EURODRIVE Ltd.Beckbridge Industrial Estate P.O. Box No.1GB-Normanton, West- Yorkshire WF6 1QR
Tel. +44 1924 893-855Fax +44 1924 893-702http://[email protected]
Greece
SalesService
Athen Christ. Boznos & Son S.A.12, Mavromichali StreetP.O. Box 80136, GR-18545 Piraeus
Tel. +30 2 1042 251-34 Fax +30 2 1042 251-59http://[email protected]
Address List
114 07/2007
Hong Kong
AssemblySalesService
Hong Kong SEW-EURODRIVE LTD.Unit No. 801-806, 8th FloorHong Leong Industrial ComplexNo. 4, Wang Kwong Road Kowloon, Hong Kong
Tel. +852 2 7960477 + 79604654Fax +852 2 [email protected]
Hungary
SalesService
Budapest SEW-EURODRIVE Kft.H-1037 BudapestKunigunda u. 18
Tel. +36 1 437 06-58Fax +36 1 437 [email protected]
India
AssemblySalesService
Baroda SEW-EURODRIVE India Pvt. Ltd.Plot No. 4, GidcPor Ramangamdi • Baroda - 391 243Gujarat
Tel. +91 265 2831086Fax +91 265 2831087http://[email protected]
Technical Offices Bangalore SEW-EURODRIVE India Private Limited308, Prestige Centre Point7, Edward RoadBangalore
Tel. +91 80 22266565Fax +91 80 [email protected]
Ireland
SalesService
Dublin Alperton Engineering Ltd. 48 Moyle RoadDublin Industrial EstateGlasnevin, Dublin 11
Tel. +353 1 830-6277Fax +353 1 [email protected]
Israel
Sales Tel-Aviv Liraz Handasa Ltd. Ahofer Str 34B / 22858858 Holon
Tel. +972 3 5599511Fax +972 3 [email protected]
Italy
AssemblySalesService
Milano SEW-EURODRIVE di R. Blickle & Co.s.a.s.Via Bernini,14 I-20020 Solaro (Milano)
Tel. +39 02 96 9801Fax +39 02 96 799781http://[email protected]
Ivory Coast
Sales Abidjan SICASte industrielle et commerciale pour l'Afrique165, Bld de MarseilleB.P. 2323, Abidjan 08
Tel. +225 2579-44Fax +225 2584-36
Japan
AssemblySalesService
Toyoda-cho SEW-EURODRIVE JAPAN CO., LTD 250-1, Shimoman-no,IwataShizuoka 438-0818
Tel. +81 538 373811Fax +81 538 373814http://[email protected]
Korea
AssemblySalesService
Ansan-City SEW-EURODRIVE KOREA CO., LTD. B 601-4, Banweol Industrial Estate Unit 1048-4, Shingil-DongAnsan 425-120
Tel. +82 31 492-8051Fax +82 31 492-8056http://[email protected]
Latvia
Sales Riga SIA Alas-KuulKatlakalna 11CLV-1073 Riga
Tel. +371 7139253Fax +371 7139386http://[email protected]
Address List
07/2007 115
Lebanon
Sales Beirut Gabriel Acar & Fils sarlB. P. 80484Bourj Hammoud, Beirut
Tel. +961 1 4947-86 +961 1 4982-72+961 3 2745-39Fax +961 1 4949-71 [email protected]
Lithuania
Sales Alytus UAB IrsevaNaujoji 19LT-62175 Alytus
Tel. +370 315 79204Fax +370 315 [email protected]://www.sew-eurodrive.lt
Luxembourg
AssemblySalesService
Brüssel CARON-VECTOR S.A.Avenue Eiffel 5B-1300 Wavre
Tel. +32 10 231-311Fax +32 10 231-336http://[email protected]
Malaysia
AssemblySalesService
Johore SEW-EURODRIVE SDN BHD No. 95, Jalan Seroja 39, Taman Johor Jaya81000 Johor Bahru, JohorWest Malaysia
Tel. +60 7 3549409Fax +60 7 [email protected]
Mexico
AssemblySalesService
Queretaro SEW-EURODRIVE MEXIKO SA DE CVSEM-981118-M93Tequisquiapan No. 102Parque Industrial QueretaroC.P. 76220Queretaro, Mexico
Tel. +52 442 1030-300Fax +52 442 1030-301http://[email protected]
Morocco
Sales Casablanca Afit5, rue Emir AbdelkaderMA 20300 Casablanca
Tel. +212 22618372Fax +212 [email protected]
Netherlands
AssemblySalesService
Rotterdam VECTOR Aandrijftechniek B.V. Industrieweg 175 NL-3044 AS RotterdamPostbus 10085NL-3004 AB Rotterdam
Tel. +31 10 4463-700Fax +31 10 4155-552http://[email protected]
New Zealand
AssemblySalesService
Auckland SEW-EURODRIVE NEW ZEALAND LTD. P.O. Box 58-428 82 Greenmount driveEast Tamaki Auckland
Tel. +64 9 2745627Fax +64 9 2740165http://[email protected]
Christchurch SEW-EURODRIVE NEW ZEALAND LTD. 10 Settlers Crescent, FerrymeadChristchurch
Tel. +64 3 384-6251Fax +64 3 [email protected]
Norway
AssemblySalesService
Moss SEW-EURODRIVE A/SSolgaard skog 71N-1599 Moss
Tel. +47 69 241-020Fax +47 69 241-040http://[email protected]
Peru
AssemblySalesService
Lima SEW DEL PERU MOTORES REDUCTORES S.A.C.Los Calderos, 120-124Urbanizacion Industrial Vulcano, ATE, Lima
Tel. +51 1 3495280Fax +51 1 3493002http://[email protected]
Address List
116 07/2007
Poland
AssemblySalesService
Lodz SEW-EURODRIVE Polska Sp.z.o.o.ul. Techniczna 5 PL-92-518 Łódź
Tel. +48 42 67710-90Fax +48 42 67710-99http://[email protected]
Portugal
AssemblySalesService
Coimbra SEW-EURODRIVE, LDA. Apartado 15 P-3050-901 Mealhada
Tel. +351 231 20 9670Fax +351 231 20 3685http://[email protected]
Romania
SalesService
Bucureşti Sialco Trading SRL str. Madrid nr.4 011785 Bucuresti
Tel. +40 21 230-1328Fax +40 21 230-7170 [email protected]
Russia
AssemblySalesService
St. Petersburg ZAO SEW-EURODRIVE P.O. Box 36 195220 St. Petersburg Russia
Tel. +7 812 3332522 +7 812 5357142Fax +7 812 3332523http://[email protected]
Senegal
Sales Dakar SENEMECA Mécanique GénéraleKm 8, Route de Rufisque B.P. 3251, Dakar
Tel. +221 849 47-70Fax +221 849 [email protected]
Serbia and Montenegro
Sales Beograd DIPAR d.o.o.Ustanicka 128aPC Košum, IV floorSCG-11000 Beograd
Tel. +381 11 347 3244 / +381 11 288 0393Fax +381 11 347 [email protected]
Singapore
AssemblySalesService
Singapore SEW-EURODRIVE PTE. LTD. No 9, Tuas Drive 2 Jurong Industrial Estate Singapore 638644
Tel. +65 68621701Fax +65 68612827http://[email protected]
Slovakia
Sales Bratislava SEW-Eurodrive SK s.r.o.Rybničná 40SK-83554 Bratislava
Tel. +421 2 49595201Fax +421 2 [email protected]
Žilina SEW-Eurodrive SK s.r.o.ul. Vojtecha Spanyola 33SK-010 01 Zilina
Tel. +421 41 700 2513Fax +421 41 700 [email protected]
Banská Bystrica SEW-Eurodrive SK s.r.o.Rudlovská cesta 85SK-97411 Banská Bystrica
Tel. +421 48 414 6564Fax +421 48 414 [email protected]
Slovenia
SalesService
Celje Pakman - Pogonska Tehnika d.o.o.UI. XIV. divizije 14SLO - 3000 Celje
Tel. +386 3 490 83-20Fax +386 3 490 [email protected]
South Africa
AssemblySalesService
Johannesburg SEW-EURODRIVE (PROPRIETARY) LIMITEDEurodrive House Cnr. Adcock Ingram and Aerodrome RoadsAeroton Ext. 2Johannesburg 2013P.O.Box 90004Bertsham 2013
Tel. +27 11 248-7000Fax +27 11 494-3104http://[email protected]
Address List
07/2007 117
Capetown SEW-EURODRIVE (PROPRIETARY) LIMITED Rainbow ParkCnr. Racecourse & Omuramba RoadMontague GardensCape TownP.O.Box 36556Chempet 7442 Cape Town
Tel. +27 21 552-9820Fax +27 21 552-9830Telex 576 [email protected]
Durban SEW-EURODRIVE (PROPRIETARY) LIMITED2 Monaceo PlacePinetownDurbanP.O. Box 10433, Ashwood 3605
Tel. +27 31 700-3451Fax +27 31 [email protected]
Spain
AssemblySalesService
Bilbao SEW-EURODRIVE ESPAÑA, S.L. Parque Tecnológico, Edificio, 302E-48170 Zamudio (Vizcaya)
Tel. +34 94 43184-70Fax +34 94 43184-71http://[email protected]
Sweden
AssemblySalesService
Jönköping SEW-EURODRIVE ABGnejsvägen 6-8S-55303 JönköpingBox 3100 S-55003 Jönköping
Tel. +46 36 3442-00Fax +46 36 3442-80http://[email protected]
Switzerland
AssemblySalesService
Basel Alfred lmhof A.G.Jurastrasse 10 CH-4142 Münchenstein bei Basel
Tel. +41 61 417 1717Fax +41 61 417 1700http://[email protected]
Thailand
AssemblySalesService
Chonburi SEW-EURODRIVE (Thailand) Ltd.700/456, Moo.7, DonhuarohMuang Chonburi 20000
Tel. +66 38 454281Fax +66 38 [email protected]
Tunisia
Sales Tunis T. M.S. Technic Marketing Service5, Rue El Houdaibiah 1000 Tunis
Tel. +216 71 4340-64 + 71 4320-29Fax +216 71 [email protected]
Turkey
AssemblySalesService
Istanbul SEW-EURODRIVE Hareket Sistemleri San. ve Tic. Ltd. Sti. Bagdat Cad. Koruma Cikmazi No. 3 TR-34846 Maltepe ISTANBUL
Tel. +90 216 4419163 / 164 3838014/15Fax +90 216 3055867http://[email protected]
Ukraine
SalesService
Dnepropetrovsk SEW-EURODRIVEStr. Rabochaja 23-B, Office 40949008 Dnepropetrovsk
Tel. +380 56 370 3211Fax +380 56 372 2078http://[email protected]
Sales Kiev SEW-EURODRIVE GmbHS. Oleynika str. 2102068 Kiev
Tel. +380 44 503 95 77Fax +380 44 503 95 [email protected]
USA
ProductionAssemblySalesService
Greenville SEW-EURODRIVE INC. 1295 Old Spartanburg Highway P.O. Box 518Lyman, S.C. 29365
Tel. +1 864 439-7537Fax Sales +1 864 439-7830Fax Manuf. +1 864 439-9948Fax Ass. +1 864 439-0566Telex 805 550 http://[email protected]
South Africa
Address List
118 07/2007
AssemblySalesService
San Francisco SEW-EURODRIVE INC. 30599 San Antonio St.Hayward, California 94544-7101
Tel. +1 510 487-3560Fax +1 510 [email protected]
Philadelphia/PA SEW-EURODRIVE INC. Pureland Ind. Complex 2107 High Hill Road, P.O. Box 481Bridgeport, New Jersey 08014
Tel. +1 856 467-2277Fax +1 856 [email protected]
Dayton SEW-EURODRIVE INC.2001 West Main Street Troy, Ohio 45373
Tel. +1 937 335-0036Fax +1 937 [email protected]
Dallas SEW-EURODRIVE INC.3950 Platinum Way Dallas, Texas 75237
Tel. +1 214 330-4824Fax +1 214 [email protected]
Additional addresses for service in the USA provided on request!
Venezuela
AssemblySalesService
Valencia SEW-EURODRIVE Venezuela S.A.Av. Norte Sur No. 3, Galpon 84-319Zona Industrial Municipal NorteValencia, Estado Carabobo
Tel. +58 241 832-9804Fax +58 241 838-6275http://[email protected]@cantv.net
USA
SEW-EURODRIVE – Driving the world
www.sew-eurodrive.com
How we’re driving the world
With people whothink fast anddevelop thefuture with you.
With a worldwide service network that isalways close at hand.
With drives and controlsthat automaticallyimprove your productivity.
With comprehensiveknowledge in virtuallyevery branch ofindustry today.
With uncompromisingquality that reduces thecost and complexity ofdaily operations.
With a global presencethat offers responsive and reliable solutions. Anywhere.
With innovativetechnology that solvestomorrow’s problemstoday.
With online informationand software updates,via the Internet, availablearound the clock.
Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services
SEW-EURODRIVEDriving the world
SEW-EURODRIVE GmbH & Co KGP.O. Box 3023 · D-76642 Bruchsal / GermanyPhone +49 7251 75-0 · Fax +49 7251 [email protected]