PROFILE IP3 | SPECIFICATION SPECIFICATION RANGE ACCURACY RESOLUTION
DC Current Measurement: ± 200 A ±5% ±100mA
DC Voltage Measurement: ±330 V ±5% ±50mV
AC Current Pickup Threshold (MCon timing): 10 mA ±0.5mA
Timing parameters: ±0.2 ms ±0.1 ms
Handset Power Supply: 10-15 V DC, 24W
Inline Power Supply: 85-265 V AC
50 / 60 Hz
Profile Battery Supply : 8x AA (Rechargeable (NiMH) or standard alkaline)
8 hours under normal usage
Screen: 5.7” Color Display, 640 x 480 (VGA)
Operating temperature: -20ºC to +50ºC (-4ºF to +122ºF)
Handset record storage: ≥ 1000 records
Head Office Camlin Power 31 Ferguson Drive Knockmore Hill Industrial Park Lisburn BT28 2EX Northern Ireland
+44 (0)28 9262 6989 [email protected]
International Sales & Support Offices
North America Europe Camlin Power Inc Camlin Power 1765 N. Elston Ave. Unit 105 Zum Brückenberg 31A Chicago, IL 60642 59872 Meschede USA Germany
+1 (773) 598 4126 +49 (0)172 283 72 02 [email protected] [email protected]
China South America Camlin Power Camlin Power Room 101, Building No.6, Azuil Loureiro, 910 600 West Yunling Road, SP/Brasil
PROFILE IP3 accessories
• 2 Interface units
• 3 DC Probe (Hall Effect CT)
• 3 Peg CTs
PROFILE IP3 Offline Interface Unit
• Interface unit (provides 24V DC signal across circuit
breakers) • AC power lead • Four 5 metre colour coded leads
Putuo District, Shanghai, 200333 São Paulo China Brazil
+86 (0)159 2160 1457 +55 (13) 3386 2571 [email protected] [email protected]
• 3 DC Voltage leads & probes
• 2 DC power leads
• Carry case with strap
• Breakout box • Carry case with strap
Asia Pacific Camlin Power Suite 1A ,Level 2 802 Pacific Highway Gordon NSW, 2072 Australia
+61 (0)426 118 101 [email protected]
South Africa Nugen Technologies (Pty) Ltd
No 17A Knights Gate
Complex, Corner of Jack &
Jonas roads, Germiston, 1400
South Africa
+27(0)82 464 5671 [email protected] www.nugentechnologies.co.za
Russia Business centre “Pollars”, bld. A, office A620, Derbenevskaya emb. 11, Moscow, Russian Federation, 115114 Russia
+7(985)757-00-46 [email protected]
PROFILE IP3
Circuit Breaker Analyser
Multiple Trip Coils
PROFILE IP3 - INDEPENDENT POLE & DUAL TRIP COIL
Today many Transmission System Operators (TSO) use Independent Pole Circuit Breakers to
enhance power system stability and reliability. Each pole can be independently tripped and so the
circuit breaker requires three trip coils.
PROFILE IP3 | FEATURES
PROFILE IP3 is designed specifically for circuit breakers with multiple trip coils such as independent
pole and transmission circuit breakers with dual trip coils, provides a unique insight into their true
condition. Capturing the vital ‘first trip’ simultaneously on multiple trip coils, combined with powerful
analysis algorithms, shows how the breaker would perform in a real-life fault situation.
REPLAY PRO
The REPLAY PRO software is an integral part of the
PROFILE IP3 system which enables efficient profile
record storage, retrieval and analysis.
PROFILE IP3 | REPLAY PRO
Key Features Include: • Efficient storage of PROFILE IP3 records
Transmission Circuit Breakers often have dual trip coils to reduce the risk from a single coil
failure. The PROFILE IP3 can be used for both applications by connecting one or two interface
units as shown below.
Problem
Solution
Test Result On PROFILE IP3
It provides the critical link between the PROFILE
IP3 and those within the organisation who need
to access the Profile data in order to
• Multiple search criteria for record retrieval • Display and overlay (up to 9) Profile records for analysis • Automated analysis function to determine if key
PEG CT’S
PH A SINGLE POLE
INTERRUPTORS PH B
PH C
V+ TC
PROTECTION TC TC COMMAND
MODULE
V-
DC PROBE
INTERFACE UNIT
INTERFACE UNIT
DC V+ V-
DC V+ V-
PROFILE IP3
Figure 1 - Independent Pole Circuit Breaker Online Test
Online Test Schematic diagrams (Figures 1 & 2) show how
the PROFILE IP3 is connected for testing an
independent pole circuit breaker and
transmission circuit breaker with dual trip coils to
capture the first trip operation.
• The DC current flowing through the trip
coils is measured by a Hall-Effect CT and provides analysis of both the trip coils and main mechanism operations
• The voltage probe measurement provides a
clear indication of the condition of the DC battery and associated wiring
• Peg CT’s indicate when the current flowing in each pole has been interrupted, which gives main contact time
A slow tripping transmission
circuit breaker can cause major
disruptions on power networks
resulting in:
• System instability • Widespread loss of supply • Damage to plant • Potential safety issues • CI / CML financial penalties
Conventional testing requires a circuit
breaker to be isolated. However this
first trip operation can often
temporarily clear any slow tripping
problem.
Therefore capturing the first trip
operation is essential for effective
circuit breaker condition monitoring.
The PROFILE IP3 offers a cost
effective solution by enabling:
• Fast and simple online test • Capture vital first trip operation • Simultaneous acquisition of
multiple trip coil profiles • Onsite analysis of breaker defects • Efficiently target critical
resources
PROFILE IP3 is a powerful
diagnostic tool for analysing:
• Main contacts operating time • Auxiliary contacts operating time • ‘Health’ of Close & Trip coils • Condition of DC battery circuit • Auxiliary contact condition
After a ‘First Trip’ test has been completed,
results will be displayed on the PROFILE IP3
as shown below.
The values of the key parameters, such as
Buffer, Acon & Mcon can be individually
selected and displayed for each phase.
Analysing Test Results on PROFILE IP3
effectively manage their assets.
The REPLAY PRO software can be downloaded
from the Camlin Power website to any PC where the
data can be accessed locally or made available to
multiple users on a central server.
SQL DATABASE
PROFILE IP3
parameters are outside preset tolerances
• Export records in CSV format for trending in graph format • Export of data to create graphs in other spreadsheet
programmes • View AC data during trip and close operations
DUAL RELAY
TRIP COILS
CIRCUIT BREAKER
PLUNGER PLUNGER
OPERATING MECH
INTERFACE
UNIT
DC + - DC
Figure 2 - Transmission Circuit Breaker Dual Trip Coil Test
PH A
PH B
PH C
V+ TC
TC PROTECTION
TC COMMAND
MODULE
V-
DC PROBE INDEPENDENT POLE
INTERFACE UNIT
BREAKOUT
DC V+ V- BOX
INDEPENDENT POLE
INTERFACE UNIT
DC V+ V- OFFLINE INTERFACE
PROFILE IP3
• Comparison of the first trip for each coil
with subsequent operations can be done on the PROFILE IP3 and REPLAY PRO.
Offline Test The schematic diagram (Figure 3), shows how the
PROFILE IP3 is connected for an independent
pole Offline Test when the circuit breaker has been
isolated.
The connections for measuring the Main Contact
Time (MCON) are the same for a standard
transmission circuit breaker.
The addition of an offline Interface unit enables DC
current to be injected through each pole of the
circuit breaker.
This enables the main contact and ‘pole-spread’
times to be accurately measured.
Independent Pole Trip Coil Profile
DC Voltages
Imax F
G pk1
B
D
C u r r e n t ( A m p s )
C
V o l t s
A
E L1
L2
L3
0 Time (ms)
H
0-A . Coil energised, plunger actuated Latch C-D. Plunger strikes latch
Bu er
E. Plunger strikes bu er
Mcon
F. Main contacts open
G. Auxiliary contacts open Acon
H. Trip coil de-energised End
After tests have been completed they can be
saved for subsequent retrieval from the
Auxilary menu. A record can be selected and
graphed, which displays a Trip / Close profile
for each phase as shown below. Up to four test records can be graphed for comparison and analysis. The First Trip / Close profiles on any phase can be compared with subsequent Trip / Close profiles.
PC
LOCAL EMBEDDED DATABASE
3 FIRST TRIP TRIP COIL PROFILES
MAIN CONTACT TIMES