Level measurementof bulk solidsRadar

VEGAPULS 67VEGAPULS 68

Product Information

Page 2: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Contents

2 Radar – Level measurement of bulk solids

Contents

1 Description of the measuring principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Type overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Electrical connection

4.1 General prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114.2 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114.3 Connection cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114.4 Connection of the cable screen and grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114.5 Wiring plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5 Operation5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135.2 Adjustment with the indicating and adjustment module PLICSCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . 135.3 Adjustment with PACTware™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135.4 Adjustment with other adjustment programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 Product code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

31488-EN-070320

Page 3: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Take note of safety instructions for Ex applicationsPlease note theEx specific safety informationwhich you can find on our homepagewww.vega.com\services\downloads andwhich comes with every instrument. In hazardous areas you should take note of the appropriate regulations, conformity andtype approval certificates of the sensors and power supply units. The sensors must only be operated on intrinsically safecircuits. The permissible electrical values are stated in the certificate.

Contents

Radar – Level measurement of bulk solids 3

3148

8-EN-

0703

20

Page 4: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

1 Description of the measuring principle

Measuring principleExtremely short microwave pulses with low emitted power aretransmitted by the antenna system to the measured product, re-flected by the product surface and received back by the antennasystem. Radar waves travel at the speed of light. The time fromemission to reception of the signals is proportional to the level inthe vessel. A special time stretching procedure ensures reliableand precise measurement of the extremely short transmissionperiods.The latest microprocessor technology and the proven softwareECHOFOX select the level echo from among a large number offalse echoes and measure it precisely.By simply entering the vessel dimensions, a level-proportionalsignal is generated out of the distance. Filling the vessel is notnecessary for the adjustment.

Wide application rangeVEGAPULS 67 and 68 radar sensors are particularly suitable forlevel measurement of bulk solids. The mechanical constructionas well as the electronics were optimized for this application.Through the special horn and parabolic antennas and the im-proveddynamic rangeof the receiver, levels inmeasuring rangesup to 70m (230 ft) can be measured. A reliable measurement ispossible with dielectric values from 1.6.

Versions for real-world applicationsAdaptable sensors are required for the widely varying productcharacteristics andmounting situations. That is whyVEGAPULS67 and 68 radar sensors are available with flange fittings,mount-ingstrapaswell as swivellingholder.An integratedconnectionforair rinsing is also available with VEGAPULS 68. An optional tem-perature adapter extends the application range to product tem-peratures up to 200 °C (392 °F). Mounting is very easy and re-quires no additional work on the measurement loop.

Independent of product characteristicsFluctuations in product composition or even complete productchanges do not influence the measuring result. A fresh adjust-ment is not necessary.

Device selectionVEGAPULS 67 and 68 radar sensors are available with differenthorn and parabolic antennas. This yields a variety of instrument-specific beam angles and measurement characteristics. Selec-tion of a suitable antenna depends on the respective application.For detailed selection you can use the tools "Finder" and "Con-figurator" on our website or contact our respective agency.

1.1 Application examplesPlastic granules

Fig. 1: Level measurement in a plastic granules silo with VEGAPULS 67

Plastic granulesandpowder are often stored in high, narrowsiloswhichare filled pneumatically.Typical conditionsare filling noise,material cones and poor reflective properties.The high sensitivity of the VEGAPULS 67 sensor provides suffi-cient power reserves for a reliable level measurement even withwidely varying product surface geometries.

Clinker silo

Fig. 2: Level measurement in a clinker silo with VEGAPULS 68

Clinker is an additive for concrete and is stored in large silos orbunkers. Its abrasive properties as well as extreme dust gener-ation during filling place heavy demands on the level measure-ment.The VEGAPULS 68 sensor is the optimum solution for levelmeasurement. Its parabolic antenna powerfully focuses the mi-crowaves, generating a strong useful signal. Interference fromstruts or installations is excluded.

Description of the measuring principle

4 Radar – Level measurement of bulk solids

31488-EN-070320

Page 5: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

2 Type overview

VEGAPULS 67 VEGAPULS 68

Preferred application: Solids SolidsMeasuring range: 15m (49.21 ft) 70m (229.66 ft)Process fitting: Mounting strap, compression flange, adapter flange Thread, swivelling holder, flangeMaterial: PPH 316L, Hastelloy C22 plated, Hastelloy C22Process temperature: -40… +80 °C (-40… +392 °F) -40… +200 °C (-40… +176 °F)Process pressure: -1 … 3 bar/-100… 300 kPa (-14.5 … 43.51 psi) -1 … 6 bar/-100… 600 kPa (-14.5 … 87.02 psi)Signal output: 4… 20mA/HART in two-wire, four-wire, Profibus PA,

Foundation Fieldbus technology4… 20mA/HART in two-wire, four-wire, Profibus PA,Foundation Fieldbus technology

Adjustment/Indication: PLICSCOM PLICSCOMRemote adjustment/indication:

VEGADIS 61 VEGADIS 61

Type overview

Radar – Level measurement of bulk solids 5

3148

8-EN-

0703

20

Page 6: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Indicating and adjustmentmodule

PLICSCOM

Housing

Plastic Stainless steel Aluminium Aluminium (doublechamber)

Electronics

4 … 20 mA/HART 4 … 20 mA/HARTfour-wire

Profibus PA Foundation Field-bus

Process fitting

Thread Flange Flange with swivel-ling holder

Sensors

Plastic horn anten-na

Stainless steel hornantenna

Parabolic antenna

Approvals

FM CSA

Type overview

6 Radar – Level measurement of bulk solids

31488-EN-070320

Page 7: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

3 Mounting instructions

Measuring range VEGAPULS 67The referenceplane for themeasuring rangeof the sensors is thecontact surface on the side of the antenna.

1 32100%

0%

4

Fig. 3: Measuring range (operating range) and max.measuring distance1 full2 empty (max.measuring distance)3 Measuring range4 Reference plane

Measuring range VEGAPULS 68The referenceplane for themeasuring rangeof the sensors is thelower edge of the flange or the seal surface of the thread.

1 32

100%

0%

4

Fig. 4: Measuring range (operating range),max.measuring distance and referenceplane1 full2 empty (max.measuring distance)3 Measuring range4 Reference plane

Installation positionMount the sensor 200mm (7.874 in) away from the vessel wall.Tomeasureasmuchof thevessel volumeaspossible, thesensorshouldbealignedso that themeasuringbeamreaches the lowestlevel in the vessel. In a cylindrical silo with conical outlet, theeasiest way is to mount the instrument in the center of the silo.

Mounting and orientationVEGAPULS 67

Fig. 5: Mounting with mounting strap and orientation in open vessel

Fig. 6: Flange mounting and orientation in closed vessel

Mounting instructions

Radar – Level measurement of bulk solids 7

3148

8-EN-

0703

20

Page 8: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Mounting and orientation of VEGAPULS 68

Fig. 7: Orientation of VEGAPULS 68 when mounting in the silo center

If mounting in the center of the silo is not possible, the sensor canbe directed to the vessel center by means of an optional swivel-ling holder. The description in the operating instructions manualof the sensors gives a simple overview of how to determine theinclination angle.

d

a

α

Fig. 8: Installationand orientationofVEGAPULS68whenmountingoutside the silocenter.

Socket VEGAPULS 67FormountingVEGAPULS 67 on a socket, a respective compres-sion flange for DN 80 (ASME 3" or JIS 80) as well as a suitableadapter flange are available.To keep false reflections from a vessel socket to a minimum, thesocket should be as short as possible. The socket end should berounded.

Fig. 9: Recommended socket mounting

If themediumhas good reflective properties,VEGAPULS 67 canalso be mounted on a longer socket piece. Recommended val-ues for socket heights are specified in the operating instructionsmanual. You must carry out a false echo storage afterwards.

Tip:In new plants, it is useful to incline the vessel socket inthe directionof emptying. False reflections from the ves-sel wall are thus reduced and measurement all the waydown to the conical outlet is possible.

Fig. 10: Orientation in silos

Socket VEGAPULS 68The socket piece should be dimensioned in such a way that theantenna end protrudes slightly out of the socket.

Mounting instructions

8 Radar – Level measurement of bulk solids

31488-EN-070320

Page 9: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

ca. 1

0 m

m

Fig. 11: Recommended socket mounting

When using a swivelling holder, keep in mind that the distancebetweenantennaandsocket gets smaller as the inclinationof thesensor increases. Additional false reflections may be generatedwhich can influence the measuring result at close range.If themediumhas good reflective properties,VEGAPULS 68 canalso be mounted on a longer socket piece. Recommended val-ues for socket heights are specified in the operating instructionsmanual of the sensor.Mounting in a multiple chamber siloThe silo walls of multiple chamber silos are often made of profilewalls, such as e.g. profile sheeting, to ensure the required stabil-ity. If the radar sensor is mounted very close to a heavily struc-tured vessel wall, considerable false reflections can be gener-ated. Hence the sensor should be mounted at a large distancefrom the separating wall. The optimal mounting position is theouter wall of the silo with the sensor directed towards the empty-ing aperture in the silo center.

Fig. 12: Installation in multiple chamber silos

Fig. 13: Orientation in multiple chamber silos

Vessel installationsSilo installations such as e.g. ladders, level switches, struts, andalso structured vessel walls, can cause false echoes that getsuperimposed on the useful echo. The mounting location of theradar sensor should be a place where no installations cross themicrowavesignals.Make surewhenplanningyourmeasurementloop that the radar signals have a "clear view" to the product.Material heapsLarge material heaps are best measured with several instru-ments, which can be mounted on e.g. traverse cranes. For thistypeof application it is advantageous to orient the sensor perpen-dicular to the bulk solid surface.The sensors cannot influence each other.

Mounting instructions

Radar – Level measurement of bulk solids 9

3148

8-EN-

0703

20

Page 10: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Fig. 14: Radar sensors on traverse crane

Mounting instructions

10 Radar – Level measurement of bulk solids

31488-EN-070320

Page 11: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

4 Electrical connection

4.1 General prerequisitesThe supply voltage range can differ depending on the instrumentversion. You can find exact specifications in chapter "Technicaldata".Take note of country-specific installation standards (e.g. theVDEregulations in Germany) as well as prevailing safety regulationsand accident prevention rules.

In hazardous areas you should take note of the appro-priate regulations, conformity and type approval certifi-cates of the sensors and power supply units.

4.2 Voltage supply4… 20mA/HART two-wireThe VEGA power supply units VEGATRENN 149AEx, VEGAS-TAB 690, VEGADIS 371 as well as VEGAMET signal condition-ing instruments are suitable for power supply.When one of theseinstruments is used, a reliable separation of the supply circuitsfrom the mains circuits according to DIN VDE 0106 part 101 isensured for the sensor.4… 20mA/HART four-wirePower supply and current output are carried on two separateconnection cables.The standard version can be operated with an earth-connectedcurrent output, the Exd version must be operated with a floatingoutput.The instrument is designed in protection class I. To maintain thisprotection class, it is absolutely necessary that the ground con-ductor be connected to the internal ground conductor terminal.Profibus PAPower is supplied by a Profibus DP/PA segment coupler or aVEGALOG 571 EP input card.

Fig. 15: Integrationof instruments in aProfibusPA system via segment couplerDP/PA or data recording systems with Profibus PA input card

Foundation FieldbusPower supply via the H1 Fieldbus cable.

4.3 Connection cableGeneralThe sensors are connected with standard cable without screen.Anoutercablediameterof5…9mmensures theseal effectof thecable entry.4… 20mA/HART two-wire and four-wireIf electromagnetic interference is expected which is above thetest values of EN 61326 for industrial areas, screened cableshould be used. In HART multidrop mode the use of screenedcable is generally recommended.Profibus PA, Foundation FieldbusThe installation must be carried out according to the appropriatebus specification. The sensor is connected respectively withscreened cable according to the bus specification. Make surethat the bus is terminated via appropriate terminating resistors.For power supply, an approved installation cable with PE con-ductor is also required.

In Ex applications, the corresponding installation regu-lations must be noted for the connection cable.

4.4 Connection of the cable screen andgrounding

If screened cable is necessary, the cable screen must be con-nected on both ends to ground potential. If potential equalisationcurrents are expected, the connection on the evaluation sidemust be made via a ceramic capacitor (e.g. 1 nF, 1500 V).Profibus PA, Foundation FieldbusIn systems with potential separation, the cable screen is con-nected directly to ground potential on the power supply unit, inthe connection box and directly on the sensor.In systems without potential equalisation, connect the cablescreen directly to ground potential only at the power supply unitand at the sensor - do not connect to ground potential in theconnection box or T-distributor.

Electrical connection

Radar – Level measurement of bulk solids 11

3148

8-EN-

0703

20

Page 12: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

4.5 Wiring planSingle chamber housing

I2C

Display

1

1 2 5 6 7 8

Fig. 16: ConnectionHART two-wire, Profibus PA, Foundation Fieldbus1 Voltage supply and signal output

Double chamber housing - two-wire

I2C

1

1 2

Fig. 17: ConnectionHART two-wire, Profibus PA, Foundation Fieldbus1 Voltage supply and signal output

Double chamber housing - 4… 20mA/HART four-wire

4 ... 20 mA

PE

/ L/ N

L1 N GND

1 2

1 2 3 4

4...20mA IS

Fig. 18: Connection 4… 20mA/HART four-wire1 Voltage supply2 Signal output

Electrical connection

12 Radar – Level measurement of bulk solids

31488-EN-070320

Page 13: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

5 Operation

5.1 OverviewThe sensors can be adjusted with the following adjustment me-dia:l with the indicating and adjustment modulel anadjustmentsoftwareaccording toFDT/DTM standard,e.g.

PACTware™ and PC

and, depending on the signal output, also with:l a HART handheld (4… 20mA/HART)l the adjustment program AMS (4 … 20 mA/HART and Foun-

dation Fieldbus)l the adjustment program PDM (Profibus PA)l a configuration tool (Foundation Fieldbus)

The entered parameters are generally saved in the sensor, op-tionally also in PLICSCOM or in the adjustment program.

5.2 Adjustment with the indicating and adjust-ment module PLICSCOM

Setup and indicationPLICSCOM is a pluggable indication and adjustment module forplics® sensors. It can be placed in four different positions on theinstrument (each displaced by 90°). Indication and adjustmentare made via four keys and a clear, graphic-capable dot matrixindication. The adjustment menu with language selection isclearly structured and enables easy setup. After setup,PLICSCOMservesas indicating instrument: throughthescrewedcover with glass insert, measured values can be read directly inthe requested unit and presentation style.The integratedbackground lightingof thedisplaycanbeswitchedon via the adjustment menu.1)

PLICSCOM adjustment

1.1

2

3

1

Fig. 19: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysKey functions

l [OK] key:- move to the menu overview

- confirm selected menu- Edit parameter- Save value

l [->] key to select:- menu change- list entry- Select editing position

l [+] key:- Change value of a parameter

l [ESC] key:- interrupt input- jump to the next higher menu

5.3 Adjustment with PACTware™PACTware™/DTMIndependent of the signal output 4… 20mA/HART, Profibus PAor FoundationFieldbus, the sensors can be operated directly onthe instrument via PACTware™. An instrument driver for the re-spective sensor is necessary for the adjustment withPACTware™. All currently available VEGA DTMs are includedasDTMCollectionwith thecurrentPACTware™ versiononaCD.They are available for a protective fee from our respectiveVEGAagency. In addition, thisDTMCollection incl. the basic version ofPACTware™ can be downloaded free-of-charge from the Inter-net.To use the entire range of functions of a DTM, incl. project doc-umentation, a DTM licence is required for that particular instru-ment family. This licence can be bought from the VEGA agencyserving you.Connecting the PC directly to the sensor

~

=

Power supply

VEGACONNECT 3

PACTware /TM

>PA<

2

3 1

Fig. 20: Connection directly to the sensor1 RS232 connection2 Sensor3 I²C adapter cable for VEGACONNECT 3ToadjustwithPACTware™,aVEGACONNECT3with I²Cadapt-er cable (art. no. 2.27323) as well as a power supply unit is nec-essary in addition to the PC and the suitable VEGA-DTM.

Operation

Radar – Level measurement of bulk solids 13

1) For instruments with national approvals, such as e.g. according to FM and CSA, only available at a later date.3148

8-EN-

0703

20

Page 14: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Connecting the PC to the signal cable (4… 20mA/HART)

2

3

1

4~

=

Power supply

VEGACONNECT 3

PACTware /TM

Fig. 21: Connecting the PC to the signal cable1 RS232 connection2 Sensor3 HART adapter cable for VEGACONNECT 34 HART resistance 250 OhmTo adjust with PACTware™, a VEGACONNECT 3 with HARTadapter cable (art. no. 2.25397) as well as a power supply unitand aHART resistor with approx. 250Ohm is required in additionto the PC and the suitable VEGA DTM.

Note:With power supply units with integrated HART resist-ance (internal resistance approx. 250 Ohm), an addi-tional external resistance is not necessary. This applies,e.g. to the VEGA instruments VEGATRENN 149A, VE-GADIS 371, VEGAMET 381). Also usual Ex separatorsare most of the time equipped with a sufficient currentlimitation resistor. In such cases, VEGACONNECT 3can be connected parallel to the 4… 20mA cable.

Connecting the PC to the signal cable (4 … 20 mA/HARTfour-wire)

2

3

1

4

5

Power supply

VEGACONNECT 3

PACTware /TM

Fig. 22: Connecting the PC to the signal cable1 RS232 connection2 Sensor3 HART adapter cable for VEGACONNECT 34 HART resistance 250 Ohm5 4… 20mA processingTo adjust with PACTware™, a VEGACONNECT 3 with HARTadaptercable (art. no.2.25397) andaHART resistorwith approx.250Ohm is required in addition to the PC and the suitableVEGADTM.

5.4 Adjustment with other adjustment pro-grams

PDMFor VEGA PA sensors, device descriptions are also available asEDD for the adjustment program PDM. The device descriptionsare already implemented in the current versions ofPDM. For old-er versions of PDM they are available as a free-of-charge down-load from the Internet.AMSFor VEGA FF sensors, device descriptions are also available asDD for the adjustment program AMS™. The device descriptionsare already implemented in the current version of AMS™. Forolder versions of AMS™, a free-of-charge download is availablevia Internet.

Operation

14 Radar – Level measurement of bulk solids

31488-EN-070320

Page 15: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

6 Technical data

General data VEGAPULS 67316L corresponds to 1.4404 or 1.4435, 304 corresponds to1.4301Materials, wetted parts- Horn antenna PBT-GF30- Focussing lens PP- Adapter flange PPH- Seal, adapter flange FKM (Viton)Materials, non-wetted parts- Compression flange PPH- Mounting strap 304- Fixing screws,mounting strap 316L- Fixing screws, adapter flange 304- Housing Plastic PBT (Polyester), Alu die-casting powder-coated, 316L- Seal ring between housing and housing cover NBR (stainless steel housing), silicone (Alu/plastic housing)- Inspection window in housing cover for PLICSCOM Polycarbonate (UL-746-C listed)- Ground terminal 316Ti/316LWeight 0.7… 3.4 kg (1.5… 7.5 lbs),depending on the process fitting and housing

material

General data VEGAPULS 68316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting 316L, Hastelloy C22, Hastelloy C22 plated- Seal - process fitting 316L Klingersil C-4400- Antenna 316L, 316L electropolished, Hastelloy C22- Antenna cone PTFE (TFM 1600)- seal, antenna system FKM (Viton), Kalrez 2035, 6230, 6375Materials, non-wetted parts- Housing Plastic PBT (Polyester), Alu die-casting powder-coated, 316L- Seal ring between housing and housing cover NBR (stainless steel housing), silicone (Alu/plastic housing)- Inspection window in housing cover for PLICSCOM Polycarbonate (UL-746-C listed)- Ground terminal 316Ti/316LWeight with horn antenna- Process fitting - thread 2… 2.8 kg (4.4… 6.2 lbs), depending on thread size and housing- Process fitting - flange 4.2 … 15.4 kg (9.3 … 34 lbs), depending on flange size and housing- Process fitting - swivelling holder with flange 5.2… 16.4 kg (11.5…35.2 lbs),dependingon the flangesize andhousingWeight with parabolic antenna- Process fitting - thread 2.8 … 3.6 kg (6.2 … 13.7 lbs), depending on thread size and housing- Process fitting - flange 5… 16.2 kg (11… 35.7 lbs), depending on the flange size and housing- Process fitting - swivelling holder with flange 6… 17.2 kg (13.2… 37.9 lbs), depending on the flange size and housing

Output variable4… 20mA/HARTOutput signal 4… 20mA/HARTSignal resolution 1.6 µAFailure message Current output unchanged 20.5 mA, 22 mA, <3.6 mA (adjustable)Max. output current 22mALoad- 4… 20mA/HART two-wire instrument see load diagram under Power supply- 4… 20mA/HART four-wire instrument max. 500 Ohm2)

Damping (63% of the input variable) 0… 999 s, adjustableFulfilled NAMUR recommendations NE 43

Technical data

Radar – Level measurement of bulk solids 15

2) With inductive load ohmic share min. 25 Ohm/mH.3148

8-EN-

0703

20

Page 16: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Profibus PAOutput signal digital output signal, format according to IEEE-754Sensor address 126 (default setting)Current value 10mA, ±0.5 mAIntegration time (63% of the input variable) 0… 999 s, adjustableFoundation FieldbusOutput- Signal digital output signal, Foundation Fieldbus protocol- Physical layer according to IEC 61158-2Channel Numbers- Channel 1 Primary Value- Channel 2 Secondary Value 1- Channel 3 Secondary Value 2Transmission rate 31.25 Kbit/sCurrent value 10mA, ±0.5 mAIntegration time (63% of the input variable) 0… 999 s, adjustable

Input variable VEGAPULS 67Parameter distance between process fitting and product surfaceMin. distance from antenna end 50mm (2 in)3)Measuring range up to 15m (49.213 ft)

Input variable VEGAPULS 68Parameter distance between process fitting and product surfaceMin. distance from antenna end 400mm (15.7 in)Max.measuring range 70m (230 ft)

Meas. accuracyVEGAPULS 67Resolution, general max. 1 mm (max. 0.039 in)Deviation4) see diagrams

1,0 m 20 m

30 mm

15 mm

-15 mm

-30 mm

Fig. 23: Deviation VEGAPULS 67 in mm,meas. range in m

Technical data

16 Radar – Level measurement of bulk solids

3) In products with low dielectric value up to 50 cm (19.7 in).4) Incl. non-linearity, hysteresis and non-repeatability.

31488-EN-070320

Page 17: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

3.280 ft 65.62 ft

0.180 in

0.590 in

- 0.590 in

- 0.180 in

Fig. 24: Deviation VEGAPULS 67 in Inch,meas. range in ft

Meas. accuracyVEGAPULS 68Resolution, general max. 1 mm (max. 0.039 in)Deviation5) see diagrams

1,0 m 70 m

30 mm

15 mm

-15 mm

-30 mm

Fig. 25: Accuracy VEGAPULS 68 with horn antenna in mm,measuring range in m

3.280 ft 229.7 ft

1.180 in

0.590 in

- 0.590 in

- 1.180 in

Fig. 26: Accuracy VEGAPULS 68 with horn antenna in Inch, measuring range in ft

2,0 m 70 m

40 mm

15 mm

-15 mm

-40 mm

Fig. 27: Accuracy VEGAPULS 68 with parabolic antenna in mm,measuring range in m

Technical data

Radar – Level measurement of bulk solids 17

5) Incl. non-linearity, hysteresis and non-repeatability.3148

8-EN-

0703

20

Page 18: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

6.562 ft 229.7 ft

1.574 in

0.590 in

- 0.590 in

- 1.574 in

Fig. 28: Accuracy VEGAPULS 68 with parabolic antenna in Inch,measuring range in ft

Influence of the ambient temperature to the sensor electronics6)

Average temperature coefficient of the zero signal (tempera-ture error)

0.03 %/10 K

Ambient conditionsAmbient, storage and transport temperature- Standard version -40… +80 °C (-40… +176 °F)- Version IP 66/IP 68 1 bar with connection cable PE -20… +60 °C (-4 … +140 °F)

Process conditionsVEGAPULS 67Vessel pressure -1 … 2 bar/-100… 300 kPa (-14.5 … 29.0 psi)Process temperature (measured on the process fitting) -40… +80 °C (-40… +176 °F)Vibration resistance mechanical vibrations with 4 g and 5 … 100 Hz7)

Process conditionsVEGAPULS 68Vessel pressure - horn antenna- without swivelling holder -1 … 40 bar/-100… 4000 kPa (-14.5… 580 psi)- with swivelling holder -1 … 1 bar/-100… 100 kPa (-14.5 … 14.5 psi) not sealingVessel pressure - parabolic antenna- without swivelling holder -1 … 6 bar/-100… 6000 kPa (-14.5 … 87 psi)- with swivelling holder -1 … 1 bar/-100… 100 kPa (-14.5 … 14.5 psi) not sealingProcess temperature (measured on the process fitting), depending on the seal of the antenna system- FKM (Viton) -40… +130 °C (-40… +266 °F)- Kalrez 2035, 6230 -15… +130 °C (+5 … +266 °F)- Kalrez 2035, 6230 with temperature adapter -15… +200 °C (+5 … +392 °F)- Kalrez 6375 -20… +130 °C (-4… +266 °F)- Kalrez 6375 with temperature adapter -20… +200 °C (-4… +392 °F)Vibration resistance mechanical vibrations with 4 g and 5 … 100 Hz8)

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug9)

- Single chamber housing l 1x closing cap½ NPT, 1x blind plug½ NPTor:l 1x plug (depending on version), 1x blind stopper½ NPT

- Double chamber housing l 1x closing cap½ NPT, 1x blind stopper½ NPT, plugM12x1 for VE-GADIS 61 (optional)

Technical data

18 Radar – Level measurement of bulk solids

6) Relating to the nominal measuring range.7) Tested according to the regulations of German Lloyd, GL directive 28) Tested according to the regulations of German Lloyd, GL directive 29) Depending on the version M12x1, according to DIN 43650, Harting, Amphenol-Tuchel, 7/8" FF; note plug protection.

31488-EN-070320

Page 19: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

or:l 1x plug (depending on version), 1x blind stopper½NPT; plugM12x1

for VEGADIS 61 (optional)Spring-loaded terminals for wire cross-sections up to 2.5 mm²

Indicating and adjustmentmodulePower supply and data transmission through the sensorIndication LC display in Dot matrixAdjustment elements 4 keysProtection- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Polyester foil

Supply voltage - 4… 20mA/HARTSupply voltage- Non-Ex instrument 15… 36 V DC- EEx ia instrument 15… 30 V DC- EExd ia instrument 20… 36 V DCSupply voltage with lighted indicating and adjustment module10)

- Non-Ex instrument 20… 36 V DC- EEx ia instrument 20… 30 V DC- EExd ia instrument 20… 36 V DCPermissible residual ripple- <100 Hz Uss <1 V- 100 Hz … 10 kHz Uss <10mVLoad see diagram

1000

750

500

250

15 1816 20 22 24 26 28 30 32 34 36

Ω

V

4

1 2

3

Fig. 29: Voltage diagram sensor1 HART load2 Voltage limit EEx ia instrument3 Voltage limit non-Ex-/Exd ia instrument4 Supply voltage

Voltage supply - 4… 20mA/HART four wire instrumentSupply voltage- Non-Ex and Exd instrument 20… 72 V DC, 20… 253 V AC, 50/60 Hz (with and without lighting of the

indicating and adjustment module)Power consumption max. 4 VA,max. 2.1 W

Technical data

Radar – Level measurement of bulk solids 19

10) For instruments with national approvals such as e.g. according to CSA only available at a later date.3148

8-EN-

0703

20

Page 20: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Electrical protective measuresProtection- Plastic housing IP 66/IP 67- Double chamber Alu-housing, four-wire instruments IP 66/IP 67- Alu and stainless steel housing, two-wire instruments IP 66/IP 68 (0.2 bar)11)Overvoltage category IIIProtection class- two-wire, Profibus PA, Foundation Fieldbus II- four-wire I

Approvals12)

FM (NI) CL I, DIV2, GP ABCD; (DIP) CL II, III, DIV1, GP EFG; (IS) CL I, II, III,DIV1, GP ABCDEF; (XP-IS) CL I, II, III, DIV1, GP ABCDEFG

CSA (NI) CL I, DIV2, GP ABCD; (DIP) CL II, III, DIV1, GP EFG; (IS) CL I, II, III,DIV1, GP ABCDEFG; (XP-IS) CL I, II, III, DIV1, GP ABCDEFG

CE conformityEMC (89/336/EWG) Emission EN 61326: 1997 (class A), susceptibility EN 61326: 1997/A1:

1998R & TTE directive R&TTE directive: I-ETS 300-440ExpertOpinionNo. 05-111723,Notified

Body No. 0700LVD (73/23/EWG) EN 61010-1: 2001

FCC conformity (only for USA/Canada)Conformity to part 15 of the FCC regulations

Environmental instructionsVEGA environment management system13) certified according to DIN EN ISO 14001

Technical data

20 Radar – Level measurement of bulk solids

11) Prerequisite for maintaining the protection is a suitable cable.12) Deviating data in Ex applications: see separate safety instructions.13) You can find detailed information under www.vega.com.

31488-EN-070320

Page 21: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

7 Dimensions

Housing in protection IP 66/IP67 and IP 66/IP 68; 0.2 bar

112m

m (4

13/ 3

2")

117m

m (4

39/ 6

4")

116m

m (4

9 /16

")

120m

m (4

23/ 3

2")

~ 69mm(2 23/32") ø 77mm

(3 1/32")

~ 69mm(2 23/32") ~ 116mm (4 9/16")

~ 87mm (3 27/64")ø 77mm(3 1/32") ø 84mm (3 5/16")

ø 84mm(3 5/16")

M20x1,5M20x1,5/½ NPT

M20x1,5/½ NPT

M20x1,5/½ NPT

M20x1,5/½ NPT

M16x1,5

1 2 3 4

Fig. 30: Housing versions in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar, withintegrated indicating and adjustment module the housing is 9mm (1/64") higher1 Plastic housing2 Stainless steel housing3 Aluminium double chamber housing4 Aluminium housing

VEGAPULS 67, version with mountin loop

15 m

m(1

9 /32

")98

mm

(3 55

/ 64"

)

2,5 mm(1/8")

125 mm(4 59/64")

170

mm

/(6

11/ 1

6") /

300

mm

(11

3 /4"

)

19 m

m(3

/ 4")

8,5

mm

(21 /

64")

75 mm(2 61/64")107 mm(4 7/32")115 mm(4 17/32")

9 mm(23/64")

85 m

m(3

11/ 3

2")

12 m

m(1

5 /32

")9

mm

(23 /

64")

12 mm(15/32")

PP

PBT-GF30

1.4301

Fig. 31: VEGAPULS 67, version with mounting strap 170mm or 300mm long

VEGAPULS 67, version with compression flange

ø 21mm(53/64")

ø 107mm (4 7/32")

ø 115mm(4 17/32")

ø 156mm(6 9/64")

ø 200mm(7 7/8")

ø 75mm(2 61/64")

10,5

mm

(13 /

32")

19m

m(3

/ 4")

126m

m

(4 61

/ 64"

)

Fig. 32: VEGAPULS 67, compression flange DN 80/3"/JIS80

VEGAPULS 67, version with adapter flange

ø 107 mm(4 7/32")

ø 143 mm(5 5/8")

ø 98 mm(3 55/64")

ø 126 mm(4 61/64")k

D

ø 75 mm(2 61/64")

ø 115 mm(4 17/32")

ø d

138

mm

(5 7 /

16")

20 m

m(2

5 /32

")

31 m

m(1

7 /32

")

8 m

m(5

/ 16"

)15

mm

(19 /

32")

2

1

DN100 PN16DN150 PN16ASME" 150psiASME" 150psiJIS DN100 10KJIS DN150 10K

øD220285

228,6279,4210280

øk180240

190,5241,3175240

ød1822

19,122,41923

8x45°(=360°)8x45°(=360°)8x45°(=360°)8x45°(=360°)8x45°(=360°)8x45°(=360°)

DN100 PN16DN150 PN16ASME" 150psiASME" 150psiJIS DN100 10KJIS DN150 10K

øD7 21/32"

11 14/64"9”

11”7 17/64"11 1/32"

øk7 3/32"9 29/64"

7 1/2"9 1/2"

6 57/64"9 29/64"

ød45/64"55/64"

3/4"7/8"3/4"

29/32"

8x45°(=360°)8x45°(=360°)8x45°(=360°)8x45°(=360°)8x45°(=360°)8x45°(=360°)

inch

mm

Fig. 33: VEGAPULS 67, adapter flange DN 100/DN 1501 Adapter flange2 Seal

Technical data

Radar – Level measurement of bulk solids 21

3148

8-EN-

0703

20

Page 22: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

VEGAPULS 68, horn antenna in threaded version

mm

inch

38m

m (

1 1 /

2")

22m

m (

55/ 6

4")

22m

m (

55/ 6

4")

118m

m (

4 41

/ 64"

)

46mm(1 13/16")

3 15/16" ø1 37/64"ø1 57/64"ø2 61/64"ø3 47/64"

4 23/32"8 1/2"

16 59/64"

xy

100 ø40

120 ø48

216 ø75

430 ø95

1½"

2"

3"

4"

xy

1½"

2"

3"

4"

x

y

G1½A / 1½ NPT

x

y

21

Fig. 34: VEGAPULS 68, horn antenna in threaded version1 Standard2 with temperature adapter

VEGAPULS 68, horn antenna in flange version

60m

m(2

23/ 6

4")

140m

m (5

33/ 6

4")

4xø3/4"4xø3/4"

8xø55/64"

8xø3/4"8xø7/8"

4xø45/64"8xø45/64"8xø45/64"

4 3/4"

4 59/64"6 19/64" 2 61/64"

3 47/64"3 47/64"

16 59/64"16 59/64"

1 57/64" 4 23/32"

8 1/2"

1 37/64"1 57/64" 4 23/32"

3 15/16"

2 61/64"3 47/64"3 47/64"

16 59/64"16 59/64"

8 1/2"

7 3/32"9 29/64"

25/32"

25/32"55/64"

15/16"

3/4"

15/16"

15/16"6 1/2"

4xø45/64"4 21/64"45/64"5 29/32"

7 7/8"8 21/32"11 7/32"

7 1/2"7 1/2"9 1/2"

6"6"

9"11" 1"

Dmm b k d x

DN 50 PN 40 165 20 125 4xø18DN 80 PN 40 200 24 160 8xø18DN 100 PN 16 220 20 180 8xø18DN 150 PN 16 285 22 240 8xø222" 150 lb 152,4 19,1 120,7 4xø19,13" 150 lb 190,5 23,9 152,4 4xø19,14" 150 lb 228,6 23,9 190,5 8xø19,16" 150 lb 279,4 25,4 241,3 8xø22,4

y

48 12075 21695 43095 43048 120

x y

75 21695 43095 430

Dinch b k d

DN 50 PN 40DN 40 PN 40 150 18 110 4xø18 40 100 DN 40PN 40

DN 80 PN 40DN 100 PN 16DN 150 PN 162" 150 lb3" 150 lb4" 150 lb6" 150 lb

Dkx

d

by

21

Fig. 35: VEGAPULS 68, horn antenna in flange version1 Standard2 with temperature adapter

VEGAPULS 68, horn antenna and swivelling holder

mm

inch

Dmm b k dDN 50 / 2" 165 11,5 122,8 4xø19DN 80 / 3" 200 11,5 156,2 4xø21DN 100 / 4" 220 11,5 182,5 4xø22

Dinch b k dDN 50 / 2"DN 80 / 3"DN 100 / 4"

120m

m (4

23 / 3

2")

20m

m(2

5 / 32"

)

20m

m(2

5 / 32"

)

6 1/2" 4 53/64" 4xø3/4"4xø53/64"8xø55/64"

6 5/32"7 3/16"

29/64"

29/64"

29/64"7 7/8"

8 21/32"

3 15/16" ø1 37/64"ø1 57/64"ø2 61/64"ø3 47/64"

4 23/32"8 1/2"

16 59/64"

d

b

Dk

x

y

x

y

21

xy100 ø40120 ø48216 ø75430 ø95

1½"2"3"4"

xy1½"2"3"4"

max. 15°(19/32")

40m

m(1

37 / 6

4")

Fig. 36: VEGAPULS 68, horn antenna and swivelling holder1 Standard2 with temperature adapter

VEGAPULS 68, parabolic antenna in threaded version

38m

m (1

1 /2"

)

22m

m (5

5 /64

")

22m

m (5

5 /64

")

118m

m (4

41/ 6

4")

138m

m(5

7 /16

")

ø 244mm (9 39/64")

46mm(1 13/16")

G1½A / 1½ NPT

21

Fig. 37: VEGAPULS 68, parabolic antenna in threaded version1 Standard2 with temperature adapter

Dimensions

22 Radar – Level measurement of bulk solids

31488-EN-070320

Page 23: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

VEGAPULS 68, parabolic antenna in flange version

D mm b k d

DN 50 PN 40 165 20 125 4xø18 DN 80 PN 40 200 24 160 8xø18 DN 100 PN 16 220 20 180 8xø18 DN 150 PN 16 285 22 240 8xø22 2" 150 lb 152,4 19,1 120,7 4xø19,1 3" 150 lb 190,5 23,9 152,4 4xø19,1 4" 150 lb 228,6 23,9 190,5 8xø19,1 6" 150 lb 279,4 25,4 241,3 8xø22,4

D inch b k d

DN 50 PN 40 DN 40 PN 40 150 18 110 4xø18 DN 40PN 40

DN 80 PN 40 DN 100 PN 16 DN 150 PN 16 2" 150 lb 3" 150 lb 4" 150 lb 6" 150 lb

2 1 D

k

b 60

mm

(2

23/ 6

4")

138m

m

(5 7 /

16") 14

0mm

(5 33

/ 64"

)

4xø3/4" 4xø3/4"

8xø55/64"

8xø3/4" 8xø7/8"

4xø45/64" 8xø45/64" 8xø45/64"

4 3/4"

4 59/64" 6 19/64" 7 3/32" 9 29/64"

25/32"

25/32" 55/64"

15/16"

3/4"

15/16"

15/16" 6 1/2"

4xø45/64" 4 21/64" 45/64" 5 29/32"

7 7/8" 8 21/32" 11 7/32"

7 1/2" 7 1/2" 9 1/2"

6" 6"

9" 11" 1"

d

ø 244mm (9 39/64")

Fig. 38: VEGAPULS 68, parabolic antenna in flange version1 Standard2 with temperature adapter

VEGAPULS 68, parabolic antenna and swivelling holder

d

Dmm b k dDN 50 / 2" 165 11,5 122,8 4xø19DN 80 / 3" 200 11,5 156,2 4xø21DN 100 / 4" 220 11,5 182,5 4xø22

Dinch b k dDN 50 / 2"DN 80 / 3"DN 100 / 4"

6 1/2" 4 53/64" 4xø3/4"4xø53/64"8xø55/64"

6 5/32"7 3/16"

29/64"

29/64"

29/64"7 7/8"

8 21/32"

120m

m (4

23 / 3

2")

130m

m (5

1 /8"

)

ø 243mm (9 9/16")

b

Dk

21

40m

m(1

37 / 6

4")

max. 15°(19/32")

Fig. 39: VEGAPULS 68, parabolic antenna and swivelling holder1 Standard2 with temperature adapter

Dimensions

Radar – Level measurement of bulk solids 23

3148

8-EN-

0703

20

Page 24: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

8 Product code

VEGAPULS 68AgrémentXX sansGX ATEX II 1/2 D IP6X TGI IECEx Ex tD A20/21 IP66 T, A21

Version / Matériau / Température processB Avec antenne cône ø80mm / PP / -40...80°C

Raccord process / MatériauXX sans bride tournanteXC Equerre de montage 170mm / inox 304XD Equerre de montage 300mm / inox 304 YD Bride tournante DN80PN16, ANSI3", JIS DN80 10K / PPHAE Bride d'adaptation DN100PN16 / PPHAH Bride d'adaptation DN150PN16 / PPHFK Bride d'adaptation ANSI 4"150psi / PPHFM Bride d'adaptation ANSI 6"150psi / PPHUC Bride d'adaptation JIS DN100 10K / PPH UE Bride d'adaptation JIS DN150 10K / PPH

ElectroniqueH 4...20mA / HART® (Technique 2 fils)V 4...20mA/HART® (Technique 4 fils) 1)

P Profibus PAF Foundation Fieldbus

Boîtier / ProtectionK Plastique / IP66/IP67 A Aluminium / IP66/IP68 (0,2bar)D Aluminium 2 chambres / IP66/IP68 (0,2bar) V Inox 316L / IP66/IP68 (0,2bar)

Presse-étoupe / ConnecteurM M20x1,5 / sansN ½NPT / sans

Affichage - Réglage (PLICSCOM)X sansA intégré (au-dessus)

Equipement complémentaireX sans

PS67.

1) Uniquement en liaison avec Boîtier / Protection "D"

VEGAPULS 68ApprovalUX FM Cl.I, Div2 (NI)+Cl.II, III, Div1 (DIP) UF FM Cl.I-III, Div 1(IS) UG FM Cl.I-III, Div 1(IS)+Cl.I-III,Div 1 Gr.C-G(XP) KX CSA Cl.I,Div2 (NI)+ Cl. II,III Div1 (DIP)KF CSA Cl. I-III, Div 1 (IS) KG CSA Cl.I-III,Div1(IS)+ Cl.I-III,Div1,Gr.C-G(XP)

Version / MaterialB with horn antenna ø40 mm / 316LC with horn antenna ø48 mm / 316LD with horn antenna ø75 mm / 16LE Horn antenna ø95 mm / 316LK with parabolic antenna ø245 mm / 316L

Process connection / MaterialND Thread 1½NPT PN40 / 316L 1F Swivelling holder with flange 2" / 316L 1G Swivelling holder with flange 3" / 316L 1H Swivelling holder with flange 4" / 316LAE Flange 2" 150lb RF, ANSI B16.5 / 316L AI Flange 3" 150lb RF, ANSI B16.5 / 316L

AK Flange 4" 150lb RF, ANSI B16.5 / 316L AM Flange 6" 150lb RF, ANSI B16.5 / 316L AN Flange 8"150lb RF,ANSI B16.5/316L AP Flange 10"150lb RF,ANSI B16.5/316L

Seal / Process temperature2 FKM (Viton) / -40...130°C 3 Kalrez 6375 / - 20...130ºC4 FKM (Viton) / -40...200°C5 Kalrez 6375 / -20...200°C

ElectronicsH Two-wire 4...20mA/HART® V Four wire 4...20mA/HART® 1)

P Profibus PA F Foundation Fieldbus

Housing / ProtectionK Plastic / IP66/IP67A Aluminium / IP66/IP68 (0.2 bar)D Aluminium double chamber / IP66/IP67 V Stainless steel 316L / IP66/IP68 (0.2bar)

Cable entry / Plug connectionN ½NPT / without

Indicating/adjustment module (PLICSCOM)X withoutA top mounted B side mounted

PS68.

1) Only in conjunction with Housing / Protection "D"

Product code

24 Radar – Level measurement of bulk solids

31488-EN-070320

Page 25: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Radar – Level measurement of bulk solids 25

3148

8-EN-

0703

20

Page 26: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

26 Radar – Level measurement of bulk solids

31488-EN-070320

Page 27: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

Radar – Level measurement of bulk solids 27

3148

8-EN-

0703

20

Page 28: Product Information VEGAPULS 67 / VEGAPULS 68literature.puertoricosupplier.com/017/WT16507.pdf · The VEGAPULS 68 sensor is the optimum solution for level measurement. Its parabolic

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-Mail: [email protected]

You can find at www.vega.comdownloads of the followingl operating instructions manualsl menu schematicsl softwarel certificatesl approvalsand much, much more