© 2020 Carrier Form 48-50P-11PD Rev. A 48/50P2,P3,P4,P5,P6,P7,P8,P9 030-100 Single-Package Gas Heating/Electric Cooling Rooftop Units and Electric Cooling Rooftop Units with Optional Electric Heat with ComfortLink Controls and Puron ® Refrigerant (R-410A) Product Data WeatherMaster ® Single-Package Rooftop Units 30 to 100 Nominal Tons

Upload: others

Post on 02-Mar-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • © 2020 Carrier Form 48-50P-11PD Rev. A

    48/50P2,P3,P4,P5,P6,P7,P8,P9 030-100Single-Package Gas Heating/Electric Cooling Rooftop Unitsand Electric Cooling Rooftop Units with Optional Electric Heatwith ComfortLink Controls and Puron® Refrigerant (R-410A)

    Product Data

    WeatherMaster®

    Single-Package Rooftop Units30 to 100 Nominal Tons

  • 2

    Carrier’s 48/50P commercial packaged unit offers design flexibility, quality, reliability, interoperability and ComfortLink controls.Carrier’s 48/50P Series commercialpackaged rooftops offer:• Puron® refrigerant (R-410A)• Novation® heat exchanger technol-

    ogy with microchannel coil• scroll compressors• variable capacity digital scroll com-

    pressor option• constant volume (CV)• staged air volume (SAV™)• variable air volume (VAV)• vertical supply/return units• horizontal supply/return units• flexible chassis and plenum options• optional return fan or power exhaust• Greenspeed® Intelligence control

    option• staged or modulating gas heat control• hydronic heat option• high-capacity evaporator coil• optional airfoil fan• Humidi-MiZer® adaptive dehumidifi-

    cation optionComfortLink controlsFactory-installed ComfortLink controlsprovide the capability for free standingoperation or may be linked with a moreextensive system. Optional factory-installed and programmed BACnet1communication capability provides sim-ple integration with the building HVACsystem (e.g., terminal devices), an i-Vu®Open control system or a BACnet build-ing automation system.ComfortLink controls also have thecapability to communicate with theCarrier Comfort Network® (CCN) sys-tem. This communication flexibilityallows simple system integration as wellas data collection, trending, monitoringand alarm displays.The 48/50P Series may also be con-figured to communicate via MODBUS2or LonWorks3 protocols, if required bythe application.The ComfortLink controls can alsointerface directly with Carrier Open orCCN controls on 35 and 45 SeriesVAV terminals to form a system foroptimal efficiency and tenant comfort.

    All units may also be applied to non-communicating building control sys-tems via switch and/or 4 to 20 mA sig-nal to provide remote occupancycontrol, fire shutdown and smoke con-trol modes, IAQ (indoor air quality)modes, and demand limit sequences.In addition, VAV units can interfacewith other control systems via a 4 to20 mA signal capability which permitscontrol of supply-air temperature reset.Standard ComfortLink controls func-tions include:• easy-to-use, plain English display• supply-fan control based on occu-

    pancy schedule• up to 6 steps of cooling capacity con-

    trol with standard scroll compressors• digital scroll compressor option that

    allows variable control of compres-sor capacity to match load require-ment of the space

    • lead-lag circuit control to equalizethe operating hours between thedual refrigeration circuits

    • 2-stage heat control• adaptive optimal start/morning

    warm-up• 2 stage thermostat control (SAV/CV

    only)• head pressure control to 32°F ambi-

    ent outdoor-air temperature• economizer and ventilation control• economizer sequence enabled by

    standard outside air enthalpy switch• adjustment of space set point in the

    occupied space on CV applications

    • selectable supply air set point inboth CV, SAV™, and VAV modes

    • control of optional variable fre-quency supply-fan drives

    • interface with 35 or 45 Series VAVterminals to create a system

    • IAQ and demand controlled ventila-tion control support

    • space temperature reset (VAV applications)

    • local or remote unit alarm and alertmonitoring

    • filter maintenance alarm• building ventilation mode purge• self-monitoring diagnostics• demand limiting• external input to permit supply-air

    temperature reset using a 4 to 20 mAsignal from another control system

    • easy replacement of select legacy30-100 ton Carrier rooftop units

    A self-diagnostic microprocessor man-ages all unit sequences, includingstages of cooling and unit safety con-trols. The microprocessor also con-trols stages of cooling and unit safetycontrols. At start-up, the self-diagnostictest verifies component operation andcalibration. Fault codes and expandedfault descriptions reduce service trou-bleshooting time and difficulty.Unique designA unique feature of these units withComfortLink controls is that the con-trols will support both CV, SAV, andVAV unit operations. The controls areconfigured in the factory, based on theunit model and options installed.

    1. BACnet is a registered trademark of ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers).

    2. Modbus is a registered trademark of Schneider Electric.

    3. LonWorks is a registered trademark of Echelon corporation.

    Features/Benefits

    Table of contentsPage

    Features/Benefits ...................................................................................... 2Model Number Nomenclature ..................................................................... 6Ratings and Capacities ............................................................................... 7Physical Data........................................................................................... 15Options and Accessories........................................................................... 47Base Unit Dimension Examples................................................................. 54Accessory Dimensions.............................................................................. 63Selection Procedure ................................................................................. 68Performance Data.................................................................................... 69Electrical Data ....................................................................................... 150Controls................................................................................................ 151Application Data.................................................................................... 160Typical Piping and Wiring....................................................................... 168Typical Wiring Schematics ...................................................................... 169Guide Specifications............................................................................... 176

  • 3

    System functions like adaptive optimalstart, nighttime free cooling, buildingsmoke control modes, occupied heat-ing and IAQ support are resident in thecontrols and can be easily integratedinto the control system strategy.Environmentally balancedPuron refrigerant (R-410A) is an HFCrefrigerant that does not contain chlo-rine that is damaging to the ozone layer.This refrigerant is a safe, efficient, andenvironmentally balanced refrigerant.Quality and reliabilityExcellent full and part load efficienciesare achieved by using multiple scrollcompressors and indoor coils withintertwined dual refrigerant circuits.The compressors are equipped withcrankcase heaters and protected byelectronic sensors and logic to controlminimum on and off times and reverserotation. The refrigerant circuits areboth electrically and mechanically inde-pendent, to provide standby capabilityshould one circuit require service.Novation® heat exchanger technologyThe Novation heat exchanger designwith microchannel condenser coil is arobust, cost effective alternative to tradi-tional coil design for standard applica-tions. Microchannel coils are also sturdierthan other coil types, making them eas-ier to clean without causing damage tothe coil.Due to the compact, all-aluminumdesign, microchannel coils reduce over-all unit operating weight. The stream-lined microchannel coil also reducesrefrigerant charge by up to 40%.Microchannel coils are not recom-mended by Carrier for marine, coastal,or industrial environments, unless aCarrier-approved coating is applied.

    Variable capacity digital scroll compressorIn air conditioning applications, theload may vary significantly, requiring ameans to vary the system coolingcapacity for optimal system perfor-mance and control. The 48/50P serieslarge rooftop units with digital scrollcompression provide a highly efficientmeans of capacity control using scrollcompressors. The digital compressortechnology provides smooth, vibrationfree operation by axially unloading thecompliant scrolls. By varying theamount of time that the scrolls areunloaded, the unit is able to preciselymatch the system capacity to the spaceload. This feature can reduce energyconsumption, provide better dehumidi-fication, reduce compressor cycling,and improve comfort in the space.Humidi-MiZer® adaptive dehu-midification systemCarrier’s Humidi-MiZer adaptive dehu-midification system is an all-inclusivefactory-installed option that can beordered with any Weathermaster®commercial rooftop unit.This system expands the envelope ofoperation of the rooftop to provideunprecedented flexibility that will meetyear-round comfort conditions. TheHumidi-MiZer adaptive dehumidificationsystem has the industry’s only dual dehu-midification mode setting. The Weather-master rooftop, coupled with theHumidi-MiZer adaptive dehumidificationsystem, is capable of operating in normaldesign cooling mode, subcooling mode,and hot gas reheat mode.Normal design cooling mode will oper-ate under the normal sequence ofoperation. Subcooling mode will oper-ate to satisfy part load type conditions

    by providing both cooling andenhanced dehumidification. Hot GasReheat mode will operate when thereis a demand for dehumidification butno demand for space cooling. Hot GasReheat mode will provide neutral airfor maximum dehumidification opera-tion without over-cooling the zone.The Weathermaster 48/50P Seriesnext generation version of Carrier’sHumidi-MiZer system includes refriger-ant modulating valves that provide vari-able flow bypass around the condenser.This innovative feature ensures exactcontrol of the supply-air temperatureas the unit lowers the evaporator tem-perature to increase latent capacity.Additionally, when the space requiresdehumidification only, the Humidi-MiZersystem can increase hot discharge gasbypass to the Humidi-MiZer coil in orderto heat the air to the exact neutral staterequired – no overcooling or overheatingwith similar latent capacity as that pro-vided in the full subcooling mode. Greenspeed intelligence optionGreenspeed intelligence allows lowambient mechanical cooling and maxi-mizes unit mechanical cooling efficiencyby continuously monitoring refrigerantcircuit efficiency and ambient conditionsto optimize condenser fan operation. Greenspeed also reduces the unit acous-tic footprint through the condenser fanspeed modulation, included low soundcondenser fans, and factory installedcompressor sound blankets. Staged/modulating gas controlStaged and modulating gas controloptions provide a supply air temperingheat function during conditions of lowmixed air temperature while the systemis still in Ventilation mode.

    SPRING ISOLATION HINGED ACCESS DOORS

    NOVATION® HEAT EXCHANGERTECHNOLOGY WITH

    MICROCHANNEL COILS

    TUBES

    FINS

    MICROCHANNELS

    MANIFOLD

  • 4

    These low, mixed air conditions occurwhen the outdoor temperature is lowand the outside-air damper is in its min-imum position, so that the mixing ofcold outside air and return air results inmixed-air temperatures below 50°F.Both staged and modulating gas con-trol options will raise the air tempera-ture leaving the unit up to thetempering mode set point. Modulatinggas control option offers an enhancedcontrol of leaving air temperature setpoint by continuously modulating theheat load. The modulating gas controlreduces the burners on/off cycles intempering mode. The staged gas control option also pro-vides additional control stages of heat-ing operation during the normal spacedemand heating function. The modu-lating gas control option provides con-tinuous heating modulation to satisfythe space demand for heat. Design flexibilityThe 48/50P Series rooftop units withComfortLink controls are designed tomeet all customer requirements fornew construction, replacement jobs, orspecial applications.The customer can choose from thefollowing:• CV, SAV™ or VAV applications• variable capacity digital scroll

    compressors• 4 or more supply-fan motor sizes • 2 sizes of natural gas heat (48 Series

    units)• electric heat (50 Series units)• hydronic heat (50 Series units)• Novation® MCHX (microchannel

    heat exchanger) condenser coils ore-coated MCHX condenser coils

    • integrated economizer with low-leakdampers and barometric relief,return fan, or power exhaust

    • ultra low leak economizer• Greenspeed intelligence control• extended chassis units are provided

    with space and mounting tracks for afactory or field-installed heating coil

    • standard 2-in. filter tracks are pro-vided but can be field-modified toaccept 4-in. panel filters

    • Humidi-MiZer® adaptive humidifica-tion system

    Discharge optionsUnits can be used for vertical discharge,discharge plenum vertical discharge, orspecial horizontal applications, such asreplacement or sound-sensitive applica-tions. The horizontal installation allowssound to be attenuated before the ductpenetrates the roof.

    Exhaust and return optionsFor applications requiring mechanicalexhaust, all 48/50P series units withan economizer are available with non-modulating (CV) or modulating powerexhaust. The 75-100 ton units are alsoavailable with high capacity powerexhaust for higher airflow or staticrequirements. Multiple exhaust fancontrol methods are available. For applications requiring high returnduct static pressure (>0.5 in. static) afactory installed return fan is availablefor all 48/50P units with an economizerand vertical return. The return fan helpsovercome the return duct static pres-sure, which allows a reduction in thesupply fan motor capacity. The returnfan option includes a VFD for CFM off-set control or building static pressurecontrol. Superior space pressure control is pro-vided by specifying one of the modulat-ing power exhaust or return fansystems. Modulating power exhaustand return fan systems control exhaustfan airflow rates to maintain a user-established space pressure set point.The ComfortID™ solutionThe 48/50P ComfortLink controls fullysupport the ComfortID system. TheComfortID system is a completely inte-grated control system that uses state-of-the-art Direct Digital Controls (DDC) tocontinually monitor and communicatethe varying heating and cooling condi-tions in each zone of the building.The ComfortID system capabilities gowell beyond temperature control. Byadding humidity, CO2, or other IAQ sen-sors, indoor air quality and consistentcomfort conditions can be tailor-madefor each zone. Proper ventilation basedon number of occupants can be preciselymaintained. Using the ComfortID systemfor demand-controlled ventilation (DCV)allows for compliance with ASHRAE(American Society of Heating, Refriger-ating and Air-Conditioning Engineers)standard 62 and helps keep energy costsdown. The ComfortID system does notmerely monitor air quality — it maintainsair quality, adjusting to promote buildinghealth.Indoor air quality (IAQ)All units incorporate a sloped, stainlesssteel condensate drain pan to preventstanding water from accumulating insidethe rooftop air-conditioning unit. Thecondensate pan has a recessed nonfer-rous condensate drain connection.Interior cabinet surfaces (except insupply fan discharge section) are insu-lated with a flexible fire-retardant dual-density fiberglass blanket, coated on

    the air side. The coating contains anEnvironmental Protection Agency(EPA) registered immobilized anti-microbial agent to effectively resist thegrowth of bacteria and fungi.Double wall construction in the air-stream is available as an option. Dou-ble wall construction with Agion1 anti-microbial coating can also be provided.These units and controls have beendeveloped to provide the design com-munity with the flexibility to meet indi-vidual job needs for both comfort andIAQ. The design features include:• Optional two position OA damper or

    integral economizer for the introduc-tion of high quality ventilation air.

    • Optional OA station to control theeconomizer to meet the requiredventilation airflow.

    • Multiple filter options, including car-tridge filters and MERV 15 bag filters.

    • Multiple cooling capacity options tohelp match the unit size to thespace load.

    • Multiple, small scroll compressorsprovide multiple steps of coolingcapacity to help prevent over-cool-ing the space.

    • Optional variable capacity compres-sor for more precise supply air tem-perature control.

    • Large diameter, low RPM supply fansfor reduced discharge sound levels.

    • SAV and VAV fan control providereduced discharge sound levels tothe space at part load.

    • Refrigeration system designed tooperate down to 32°F outdoor-airtemperature.

    • Multiple heat capacity options tomatch the application load and helpprevent overheating.

    • Multi-staged or modulating heat con-trol for precise supply air temperaturecontrol.

    • Humidi-MiZer adaptive dehumidifi-cation system.

    Fan modulationSupply fan duct pressure control on VAVmodels is accomplished via a variable fre-quency (inverter) drive (VFD). The VFDcontrols supply fan airflow to maintain auser-established duct pressure set point inthe unit’s supply duct. Supply duct pres-sure control can be used for both multi-zone VAV systems with air terminal unitsand single zone VAV systems with orwithout air terminal units.

    1. Agion is a trademark of Sciessent.

    Features/Benefits (cont)

  • 5

    Installation and serviceabilityAccess panelsAll full-size access panels are hinged foreasy access to serviceable components.No fasteners need to be removed fromany units, which reduces servicing timeand prevents roof leaks caused by dis-carded screws puncturing the roof.Electrical connectionsSingle point electrical connections arestandard on all units. Electrical serviceaccess can be made through roof curbor side of unit. All 48P units provide asingle point gas connection.Run testingTo ensure a successful start-up, everyrooftop unit is factory run tested.Unit designUnit design is ETL and ETL, Canada,listed according to UL (Underwriters Lab-oratories) Standard 1995.Scrolling marqueeWhen using the standard scrolling mar-quee, serviceability becomes even easier,including:• local or remote alarm and alert

    monitoring• self-diagnostic run testing to confirm

    control and component operation• expedited troubleshooting and unit

    repair through self-diagnostic dis-play of unit troubleshooting alertand alarm codes with expanded textdescriptions to immediately identifyreason for unit outage

    • filter maintenance alarm• monitoring of supply-air fan run

    time, permitting easy service sched-ule planning

    TransducersServiceability is further facilitated withsuction and discharge pressure trans-ducers. These allow suction pressureand discharge pressure to be monitoredremotely with alarm capability. Thesetransducers also control condenser headpressure to maintain the minimum dif-ferential pressure required across thethermostatic expansion valve (TXV) forproper operation, which reduces energyconsumption.Non-fused disconnectA factory-installed non-fused discon-nect (NFD) option is available to simplifyunit installation and improve unit ser-viceability. The location of the NFD in

    the main control box simplifies fieldpower supply routing into the unit. TheNFD incorporates an access panel inter-lock feature, ensuring that all power tothe unit will be disconnected before aservice person opens the control box.Gas heat units (48P units)The 48P units are gas heating units,using natural gas combustion, with twoheat sizes available for every unit.The unit heating systems employ multi-ple heat exchanger sections, with eachsection equipped with a 2-stage redun-dant gas valve and independent igni-tion control, with all sections operatingin parallel.Units with gas modulating heating areequipped with an additional modulatinggas valve installed downstream of the2-stage redundant gas valve.Heat exchangerThe tubular steel heat exchanger designoptimizes heat transfer for improved effi-ciency. The tubular design permits multi-ple passes across the supply air path.Each tube has an individual inshotburner, ensuring uniform combustion ineach tube of the heat exchangers. Tubesare dimpled to create a turbulent gas flowto maximize heat efficiency and toensure uniform surface temperatures forreduced corrosion effects, improveddurability and long-life service. Heatexchanger material is aluminized steel orstainless steel, for improved corrosionresistance and reliability.Integrated gas unit controllerThe IGC (integrated gas unit controller)ignition and safety control system isused on each heat exchanger section.The IGC, unique to Carrier rooftopunits, simplifies system evaluation andtroubleshooting by providing systemstatus and visual fault notification via anon-board LED (light-emitting diode).Ignition is initiated by a direct sparkignition system; flame status is deter-mined by flame rectification process.Combustion fan operation is proven bya Hall Effect speed sensor circuit forunits equipped with 2-stage or stagedgas heat. For units equipped with mod-ulating gas heat, combustion fan oper-ation is proven with a pressure switch.Safeties include flame rollout and limitswitch. Auto reset with manual lockoutis also provided for repeated limitswitch trips. The IGC also preventsshort-cycling due to thermostat jiggle

    by ensuring a full minute heating cycleoperation on each call for heat.Gas heat systemThe induced draft fan system draws hotcombustion gas through the heatexchanger tubes at the optimum rate forthe most effective heat transfer and com-bustion process. The heat exchangeroperates under a negative pressure, pre-venting flue gas leakage into the indoorsupply air.Flue outlet hoods with wind baffles arelocated on the side of the unit, to mini-mize the effects of wind on heatingoperations.Standard units use 2-stage control forunoccupied, morning warm-up andoccupied space heating.Additional control stages for heatingoperation are available by specifyingthe staged gas control option.Modulating control option is availableby specifying the modulating gas con-trol option.A single hinged panel gains access to thecomplete heat exchanger assembly andcontrols, for improved serviceability.A single point gas connection providesfor easy installation.An LP (liquid propane) conversionaccessory can be field-installed on gasunits without staged or modulating gascontrol option (sizes 030-070 for verti-cal low heat units and sizes 030-050for vertical high heat units).Optional modulating gas heatThe modulating gas heat option moni-tors unit supply-air temperature andcontrols the unit heat exchanger toprovide first-stage demand heatingcontrol, with modulation to maintainuser-configured heating supply air tem-perature set point.The option also provides full-firedemand heating on heating controlcommand and tempering heat control,based on user-configured ventilationsupply air temperature set point, toeliminate cold draft conditions with lowmixed-air temperatures.The modulating gas control optionconsists of a modulating controllercapable of ensuring the proper fuel airmixture at operating firing rates, sup-ply air temperature thermistors withduct-mounting base, a limit switch tem-perature thermistor, and stainless steelheat exchanger tubes.

  • 6

    50 P2 D 030 6 1 Option Code

    Factory Options50 – Cooling Unit with Electric Heat See note below

    ConfigurationDesign Revision Level

    Voltage Options1 – 575-3-60

    Heat and Chassis Options

    2 – 380-3-60

    - – No Heat

    5 – 208/230-3-60

    A – Low Electric Heat

    6 – 460-3-60

    B – Medium Electric HeatC – High Electric Heat

    Unit Size – Nominal Tons030 – 30 060 – 60035 – 35 070 – 70040 – 40 075 – 75

    J – No Heat with Discharge Plenum, Humidi-MiZer System

    050 – 50 090 – 90055 – 55 100 – 100

    P – No Heat with Discharge Plenum and Extended ChassisR – No Heat with Extended ChassisS – Low Electric Heat with Extended ChassisT – Medium Electric Heat with Extended ChassisV – High Electric Heat with Extended ChassisW – No Electric Heat with Extended Chassis and Hot Water CoilY – No Electric Heat with Discharge Plenum, Extended Chassis

    and Hot Water Coil

    D – No Heat, Humidi-MiZer SystemE – Low Electric Heat, Humidi-MiZer SystemF – Medium Electric Heat, Humidi-MiZer SystemG – High Electric Heat, Humidi-MiZer SystemH – No Heat with Discharge Plenum

    Z – Low Electric Heat, Humidi-MiZer with SCR Control2 – Medium Electric Heat, Humidi-MiZer with SCR Control3 – High Electric Heat, Humidi-MiZer with SCR Control4 – Low Electric Heat, with Extended Chassis with SCR Control5 – Medium Electric Heat, with Extended Chassis with SCR Control6 – High Electric Heat, with Extended Chassis with SCR Control

    P2 – Vertical Supply/Return, CV/SAV ComfortLink ControlsP3 – Vertical Supply/Return, VAV ComfortLink ControlsP4 – Horizontal Supply/Return, CV/SAV ComfortLink ControlsP5 – Horizontal Supply/Return, VAV ComfortLink ControlsP6 – Vertical Supply/Return, CV/SAV ComfortLink Controls

    with GreenspeedP7 – Vertical Supply/Return, VAV ComfortLink Controls

    with GreenspeedP8 – Horizontal Supply/Return, CV/SAV ComfortLink Controls

    with GreenspeedP9 – Horizontal Supply/Return, VAV ComfortLink Controls

    with Greenspeed

    0 – Initial Release1 – First Revision2 – 35T Release3 – Third Revision4 – Fourth Revision

    48 P2 D 030 6 1 Option Code

    Factory Options48 – Cooling Unit with Gas Heat See note below

    ConfigurationDesign Revision Level0 – Initial Release

    Voltage Options1 – 575-3-60

    Heat and Chassis Options

    5 – 208/230-3-606 – 460-3-60

    B – Low Gas Heat, Stainless Steel C – High Gas Heat, Stainless Steel

    Unit Size – Nominal Tons

    D – Low Gas Heat

    030 – 30 060 – 60

    E – High Gas Heat

    035 – 35 070 – 70040 – 40 075 – 75050 – 50 090 – 90

    H – Low Staged Gas Heat, Stainless Steel

    055 – 55 100 – 100

    J – High Staged Gas Heat, Stainless Steel

    P – Low Gas Heat, Stainless Steel, Extended ChassisQ – High Gas Heat, Stainless Steel, Extended ChassisR – Low Gas Heat with Extended ChassisS – High Gas Heat with Extended ChassisW – Low Staged Gas Heat, Stainless Steel, with Extended ChassisX – High Staged Gas Heat, Stainless Steel, with Extended Chassis

    – – Low Gas Heat, Humidi-MiZer® System A – High Gas Heat, Humidi-MiZer System

    F – Low Staged Gas Heat, Stainless Steel, Humidi-MiZer SystemG – High Staged Gas Heat, Stainless Steel, Humidi-MiZer System

    M – Low Gas Heat, Stainless Steel, Humidi-MiZer SystemN – High Gas Heat, Stainless Steel, Humidi-MiZer System

    K – Low Modulating Gas Heat, Stainless SteelL – High Modulating Gas Heat, Stainless Steel

    Y – Low Modulating Gas Heat, Stainless Steel, Humidi-MiZer SystemZ – High Modulating Gas Heat, Stainless Steel, Humidi-MiZer System2 – Low Modulating Gas Heat, Stainless Steel, with Extended Chassis3 – High Modulating Gas Heat, Stainless Steel, with Extended Chassis

    1 – First Revision2 – 35T Release3 – Third Revision4 – Fourth Revision

    P2 – Vertical Supply/Return, CV/SAV ComfortLink ControlsP3 – Vertical Supply/Return, VAV ComfortLink ControlsP4 – Horizontal Supply/Return, CV/SAV ComfortLink ControlsP5 – Horizontal Supply/Return, VAV ComfortLink ControlsP6 – Vertical Supply/Return, CV/SAV ComfortLink Controls

    with GreenspeedP7 – Vertical Supply/Return, VAV ComfortLink Controls

    with GreenspeedP8 – Horizontal Supply/Return, CV/SAV ComfortLink Controls

    with GreenspeedP9 – Horizontal Supply/Return, VAV ComfortLink Controls

    with Greenspeed

    NOTE: Because of the large number of options and the many resultingcombinations, the Applied Rooftop Builder software must be used togenerate the 8-digit option code for the unit model number. Refer to thesoftware for the different choices for unit factory-installed options. Onceall of the options have been selected, the software will generate the cor-rect code. Unit options and accessories are listed in the Options andAccessories section on page 47.

    NOTE: Because of the large number of options and the many resultingcombinations, the Applied Rooftop Builder software must be used togenerate the 8-digit option code for the unit model number. Refer to thesoftware for the different choices for unit factory-installed options. Onceall of the options have been selected, the software will generate the cor-rect code. Unit options and accessories are listed in the Options andAccessories section on page 47.

    50P2,P3,P4,P5,P6,P7,P8,P9 UNITS

    48P2,P3,P4,P5,P6,P7,P8,P9 UNITS

    LEGENDCV — Constant VolumeSAV — Staged Air VolumeSCR — Silicon Controlled Rectifier Electric HeatVAV — Variable Air Volume

    Quality AssuranceCertified to ISO 9001:2015

    LEGENDCV — Constant VolumeSAV™ — Staged Air VolumeVAV — Variable Air Volume

    Model number nomenclature

  • 7

    UNIT DESIGN AIRFLOW LIMITS

    NOTE: Refer to Application Data section for more information concern-ing minimum operating airflow in Cooling mode.

    TWO-STAGE GAS HEATING CAPACITIES — 48P2,P3,P6,P7 UNITS(NATURAL GAS ON ALL UNITS AND LP GAS ON 030-070 UNITS)

    LEGEND

    LP — Liquid Propane

    NOTES:1. Ratings are approved for altitudes to 2000 ft. At altitudes over 2000

    ft, ratings are 4% less for each 1000 ft above sea level.2. At altitudes up to 2000 ft, the following formula may be used to calcu-

    late air temperature rise:

    3. At altitudes above 2000 ft, the following formula may be used:

    4. Minimum allowable temperature of mixed air entering the heatexchanger during half-rate (first stage) operation is 35°F. There is nominimum mixture temperature limitation during full-rate operation.

    5. Temperature rise limits: see table.6. On VAV (variable air volume) applications set the zone terminals to

    provide minimum unit heating airflow as indicated in the table uponcommand from Heat Interlock Relay (HIR) function.

    UNIT SIZE UNIT TYPE MINIMUM COOLING CFM MAXIMUM CFM

    03048P Low Heat 6,000 15,00048P High Heat 6,000 15,00050P 6,000 15,000

    03548P Low Heat 7,000 15,00048P High Heat 7,000 15,00050P 7,000 15,000

    04048P Low Heat 8,000 20,00048P High Heat 8,000 20,00050P 8,000 20,000

    05048P Low Heat 9,000 20,00048P High Heat 9,000 19,50050P 9,000 20,000

    05548P Low Heat 10,000 25,00048P High Heat 10,000 25,00050P 10,000 25,000

    06048P Low Heat 12,000 30,00048P High Heat 12,000 30,00050P 12,000 30,000

    07048P Low Heat 14,000 30,00048P High Heat 14,000 30,00050P 14,000 30,000

    07548P Low Heat 15,000 30,00048P High Heat 15,000 30,00050P 15,000 30,000

    09048P Low Heat 17,000 40,00048P High Heat 17,000 37,00050P 17,000 40,000

    10048P Low Heat 20,000 44,00048P High Heat 20,000 37,00050P 20,000 44,000

    UNIT48P2,P3,P6,P7

    GAS INPUT (1000 Btuh) EFFICIENCY(%)

    OUTPUT CAPACITY (1000 Btuh) TEMP RISE(F)

    AIRFLOW (Cfm)Stage 1 Stage 2 Stage 1 Stage 2 Min Max

    030-050 Low Heat 244 325 81.0% 197 263 10-40 6,094 20,000030-050 High Heat 488 650 81.0% 395 527 25-55 8,864 19,259055-070 Low Heat 488 650 80.0% 390 520 10-40 12,142 30,000055-070 High Heat 731 975 80.0% 585 780 20-50 14,571 30,000075-100 Low Heat 488 650 80.0% 390 520 10-40 12,172 44,000075-100 High Heat 731 975 80.0% 585 780 20-50 14,517 36,292

    t =maximum output capacity

    1.10 x air quantity

    t =maximum output capacity

    (.24 x specific weight of air x 60) (air quantity)

    Ratings and capacities

  • 8

    TWO-STAGE GAS HEATING CAPACITIES — 48P4,P5,P8,P9 UNITS(NATURAL GAS ON ALL UNITS AND LP GAS NOT AVAILABLE)

    LEGEND

    LP — Liquid Propane

    NOTES:1. Ratings are approved for altitudes to 2000 ft. At altitudes over 2000

    ft, ratings are 4% less for each 1000 ft above sea level.2. At altitudes up to 2000 ft, the following formula may be used to calcu-

    late air temperature rise:

    3. At altitudes above 2000 ft, the following formula may be used:

    4. Minimum allowable temperature of mixed air entering the heatexchanger during half-rate (first stage) operation is 35°F. There is nominimum mixture temperature limitation during full-rate operation.

    5. Temperature rise limits: see table.6. On VAV (variable air volume) applications set the zone terminals to

    provide minimum unit heating airflow as indicated in the table uponcommand from Heat Interlock Relay (HIR) function.

    GAS HEATING CAPACITIES — UNITS WITH TWO-STAGE GAS CONTROL OPTION

    48P2,P3,P6,P7 030-050 LOW HEAT

    48P4,P5,P8,P9 030-050 LOW HEAT

    GAS HEATING CAPACITIES — UNITS WITH MULTI-STAGE GAS CONTROL OPTION

    48P2,P3,P6,P7 030-050 HIGH HEAT

    48P4,P5,P8,P9 030-050 HIGH HEAT

    UNIT48P4,P5,P8,P9

    GAS INPUT (1000 Btuh) EFFICIENCY(%)

    OUTPUT CAPACITY (1000 Btuh) TEMP RISE(F)

    AIRFLOW (Cfm)Stage 1 Stage 2 Stage 1 Stage 2 Min Max

    030-050 Low Heat 244 325 80.0% 195 260 10-40 6,019 20,000030-050 High Heat 488 650 80.0% 390 520 25-55 8,754 19,259055-070 Low Heat 488 650 80.0% 390 520 10-40 12,037 30,000055-070 High Heat 731 975 80.0% 585 780 20-50 14,444 30,000075-100 Low Heat 488 650 80.0% 390 520 10-40 12,037 44,000075-100 High Heat 731 975 80.0% 585 780 20-50 14,444 36,111

    t =maximum output capacity

    1.10 x air quantity

    t =maximum output capacity

    (.24 x specific weight of air x 60) (air quantity)

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 75% 81.0% 197.4 197.4 N/A N/A2 325 100% 81.0% 263.3 263.3 N/A N/A

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 75% 80.0% 195.0 195.0 N/A N/A2 325 100% 80.0% 260.0 260.0 N/A N/A

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 38% 81.0% 197.4 197.4 0.0 N/A2 325 50% 81.0% 263.3 263.3 0.0 N/A3 488 75% 81.0% 394.9 197.4 197.4 N/A4 569 88% 81.0% 460.7 263.3 197.4 N/A5 650 100% 81.0% 526.5 263.3 263.3 N/A

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0 0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0 260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A

    Ratings and capacities (cont)

  • 9

    GAS HEATING CAPACITIES — UNITS WITH STAGED GAS CONTROL OPTION (CONT)

    48P2,P3,P6,P7 055-070 LOW HEAT

    48P4,P5,P8,P9 055-070 LOW HEAT

    48P2,P3,P6,P7 055-070 HIGH HEAT

    48P4,P5,P8,P9 055-070 HIGH HEAT

    48P2,P3,P6,P7 075-100 LOW HEAT

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY

    (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0 0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0 260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY

    (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0 0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0 260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0 0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0 260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0% 585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 165.08 894 92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0 260.0

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0 0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0 260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0% 585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 195.08 894 92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0 260.0

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0 0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0 260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A

  • 10

    GAS HEATING CAPACITIES — UNITS WITH STAGED GAS CONTROL OPTION (CONT)

    48P4,P5,P8,P9 075-100 LOW HEAT

    48P2,P3,P6,P7 075-100 HIGH HEAT

    48P4,P5,P8,P9 075-100 HIGH HEAT

    GAS HEATING CAPACITIES — UNITS WITH MODULATING GAS CONTROL OPTION

    48P2,P3,P6,P7 030-050 LOW HEAT

    48P4,P5,P8,P9 030-050 LOW HEAT

    48P2,P3,P6,P7 030-050 HIGH HEAT

    LEGEND

    HF — High FireLF — Low Fire

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0 0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0 260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0 0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0 260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0% 585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 165.08 894 92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0 260.0

    HEATINGSTAGES

    INPUTCAPACITY(1000 Btuh)

    % FULL FIRE THERMAL EFFICIENCY %

    OUTPUT CAPACITY (1000 Btuh)

    OUTPUT CAPACITY PER SECTION (1000 Btuh)

    SECTION 1 SECTION 2 SECTION 3

    1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0 0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0 260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0% 585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 195.08 894 92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0 260.0

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 28 - 100% 68 - 263 Modulating — —

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 28 - 100% 68 - 260 Modulating — —

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265 - 455 Modulating LF —416 - 650 64 - 100% 333 - 527 Modulating HF —

    Ratings and capacities (cont)

  • 11

    GAS HEATING CAPACITIES — UNITS WITH MODULATING GAS CONTROL OPTION (CONT)

    48P4,P5,P8,P9 030-050 HIGH HEAT

    48P2,P3,P6,P7 055-070 LOW HEAT

    48P4,P5,P8,P9 055-070 LOW HEAT

    48P2,P3,P6,P7 055-070 HIGH HEAT

    48P4,P5,P8,P9 055-070 HIGH HEAT

    48P2,P3,P6,P7 075-100 LOW HEAT

    48P4,P5,P8,P9 075-100 LOW HEAT

    LEGEND

    HF — High FireLF — Low Fire

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265 - 455 Modulating LF —416 - 650 64 - 100% 333 - 520 Modulating HF —

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265 - 455 Modulating LF —416 - 650 64 - 100% 333 - 525 Modulating HF —

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265 - 455 Modulating LF —416 - 650 64 - 100% 333 - 520 Modulating HF —

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 - 455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579 - 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 - 721 Modulating HF LF741 - 975 76 - 100% 593 - 787 Modulating HF HF

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 - 455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579 - 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 - 721 Modulating HF LF741 - 975 76 - 100% 593 - 780 Modulating HF HF

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265 - 455 Modulating LF —416 - 650 64 - 100% 333 - 526 Modulating HF —

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265 - 455 Modulating LF —416 - 650 64 - 100% 333 - 520 Modulating HF —

  • 12

    GAS HEATING CAPACITIES — UNITS WITH MODULATING GAS CONTROL OPTION (CONT)

    48P2,P3,P6,P7 075-100 HIGH HEAT

    48P4,P5,P8,P9 075-100 HIGH HEAT

    LEGEND

    HF — High FireLF — Low Fire

    ELECTRIC HEATER CAPACITIES

    NOTES:1. Electric heat options are NOT AVAILABLE on discharge plenum

    units or size 030-070 horizontal units.2. Electric heat is available on horizontal size 075-100 units with air-

    foil fan option only.

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 - 455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579 - 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 - 719 Modulating HF LF741 - 975 76 - 100% 593 - 784 Modulating HF HF

    GAS INPUT(1000 Btuh)

    PERCENTFULL FIRE

    OUTPUTCAPACITY(1000 Btuh)

    FIRING STAGE

    1 2 3

    92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 - 455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579 - 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 - 715 Modulating HF LF741 - 975 76 - 100% 593 - 780 Modulating HF HF

    UNIT SIZE NO. STAGES LOW(kW)

    CAPACITYPER

    STAGE (%)

    MED(kW)

    CAPACITYPER

    STAGE (%)

    HIGH(kW)

    CAPACITYPER

    STAGE (%)

    MINCFM

    MAXCFM

    50P2,P3,P6,P7030-050208 v 2 29 50,100 59 50,100 88 67,100 9,000 20,000230 v 2 36 50,100 72 50,100 108 67,100 9,000 20,000380 v 2 25 50,100 51 50,100 76 67,100 9,000 20,000460 v 2 36 50,100 72 50,100 108 67,100 9,000 20,000575 v 2 36 50,100 72 50,100 108 67,100 9,000 20,000

    50P2,P3,P6,P7055-070208 v 2 29 50,100 59 50,100 88 67,100 15,000 30,000230 v 2 36 50,100 72 50,100 108 67,100 15,000 30,000380 v 2 25 50,100 51 50,100 76 67,100 15,000 30,000460 v 2 36 50,100 72 50,100 108 67,100 15,000 30,000575 v 2 36 50,100 72 50,100 108 67,100 15,000 30,000

    50P5075-100460 v 2 — — 108 67,100 216 50,100 15,000 44,000

    Ratings and capacities (cont)

  • 13

    CAPACITY CONTROL STAGING SEQUENCES

    SIZES 030,035

    *Hot Gas Bypass.SIZES 030,035 WITH DIGITAL COMPRESSOR

    *On units with optional digital scroll compressor, compressor A1 modu-lates from minimum to maximum capacity to provide increased stages.

    SIZE 040 WITH HGBP

    *Hot Gas Bypass.SIZE 040 WITH DIGITAL COMPRESSOR

    *On units with optional digital scroll compressor, compressor A1 modu-lates from minimum to maximum capacity to provide increased stages.

    SIZE 040 WITHOUT HGBP

    COMP

    STAGE0 1* 1 2

    Compressor StatusA1 OFF ON ON ONB1 OFF OFF OFF ON

    UNIT Capacity 48/50P030 0% 36% 50% 100%035 0% 38% 50% 100%

    COMP

    STAGE0 1 2

    Compressor StatusA1* OFF ON ONB1 OFF OFF ON

    UNIT Capacity 48/50P030 0% 25% to 50% 75% to 100%035 0% 25% to 50% 75% to 100%

    COMP

    STAGE0 1* 1 2 3

    Compressor StatusA1 OFF ON ON ON ONB1 OFF OFF OFF ON ONB2 OFF OFF OFF OFF ON

    UNIT Capacity 48/50P040 0% 36% 47% 73% 100%

    COMP

    STAGE0 1 2 3

    Compressor StatusA1* OFF ON ON ONB1 OFF OFF ON ONB2 OFF OFF OFF ON

    UNIT Capacity 48/50P040 0% 23% to 47% 50% to 73% 77% to 100%

    COMP

    STAGE0 1 2 3 4

    Compressor StatusA1 OFF OFF ON ON ONB1 OFF ON OFF ON ONB2 OFF OFF OFF OFF ON

    UNIT Capacity 48/50P040 0% 27% 47% 73% 100%

  • 14

    CAPACITY CONTROL STAGING SEQUENCES (CONT)

    SIZES 050-075

    *Hot Gas Bypass.SIZES 050-075 WITH DIGITAL COMPRESSOR

    * On units with optional digital scroll compressor, compressor A1 modu-lates from minimum to maximum capacity to provide increased stages.

    SIZES 090-100

    *Hot Gas Bypass.SIZES 090-100 WITH DIGITAL COMPRESSOR

    * On units with optional digital scroll compressor, compressor A1 modu-lates from minimum to maximum capacity to provide increased stages.

    COMP

    STAGE0 1* 1 2 3 4

    Compressor StatusA1 OFF ON ON ON ON ONA2 OFF OFF OFF OFF ON ONB1 OFF OFF OFF ON ON ONB2 OFF OFF OFF OFF OFF ON

    UNIT Capacity 48/50P050 0% 15% 23% 50% 73% 100%055 0% 17% 25% 50% 75% 100%060 0% 18% 25% 50% 75% 100%070 0% 16% 23% 46% 73% 100%075 0% 19% 25% 50% 75% 100%

    COMP

    STAGE0 1 2 3 4

    Compressor StatusA1* OFF ON ON ON ONA2 OFF OFF OFF ON ONB1 OFF OFF ON ON ONB2 OFF OFF OFF OFF ON

    UNIT Capacity 48/50P050 0% 12% to 23% 38% to 50% 62% to 73% 88% to 100%055 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%060 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%070 0% 11% to 23% 34% to 46% 61% to 73% 89% to 100%075 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%

    COMP

    STAGE0 1* 1 2 3 4 5 6

    Compressor StatusA1 OFF ON ON ON ON ON ON ONA2 OFF OFF OFF OFF ON ON ON ONA3 OFF OFF OFF OFF OFF OFF ON ONB1 OFF OFF OFF ON ON ON ON ONB2 OFF OFF OFF OFF OFF ON ON ONB3 OFF OFF OFF OFF OFF OFF OFF ON

    UNIT Capacity 48/50P090 0% 12% 17% 33% 50% 67% 83% 100%100 0% 11% 15% 33% 49% 67% 82% 100%

    COMP

    STAGE0 1 2 3 4 5 6

    Compressor StatusA1* OFF ON ON ON ON ON ONA2 OFF OFF OFF ON ON ON ONA3 OFF OFF OFF OFF OFF ON ONB1 OFF OFF ON ON ON ON ONB2 OFF OFF OFF OFF ON ON ONB3 OFF OFF OFF OFF OFF OFF ON

    UNIT Capacity 48/50P090 0% 8% to 17% 25% to 33% 42% to 50% 58% to 67% 75% to 83% 92% to 100%100 0% 8% to 15% 26% to 33% 41% to 49% 59% to 67% 74% to 82% 92% to 100%

    Ratings and capacities (cont)

  • 15

    48P 030,035

    LEGEND

    BASE UNIT 48P 030 48P 035NOMINAL CAPACITY (tons) 30 35OPERATING WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base UnitLow Heat 5310 5810 5410 5910High Heat 5440 5940 5540 6040

    With EconomizerLow Heat 5610 6110 5710 6210High Heat 5740 6240 5840 6340

    COMPRESSORS ScrollQuantity...Type 1...ZP154/1...ZP154 1...ZP182/1...ZP182Oil Charge (oz) per Compressor 110 110Number of Refrigerant Circuits 2 2

    REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2

    Standard Evaporator Coil 15.4/14.8 17.1/17.5Standard Evaporator with Humidi-MiZer® System 15.4/24.9 17.1/27.6Alternate High-Capacity Evaporator Coil 18.8/17.8 N/AAlternate High-Capacity Evaporator with Humidi-MiZer 18.8/27.9 N/A

    CONDENSER COILS Aluminum Novation® Heat Exchanger with Microchannel CoilsQuantity 1 1Total Face Area (sq ft) 33.3 33.3

    EVAPORATOR COILSQuantity 1Total Face Area (sq ft) 32.1Refrigerant Feed Device...No. per Circuit TXV...1Standard Evaporator Coils

    Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 4...15.0 N/AFin Type Double Wavy N/ATube Type Cross Hatched N/A

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Coil Construction E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 Face Area (sq ft) 26.7 26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum plate fins, galvanized steel frame

    Face Area (sq ft) 22.6 22.6 Rows...Fins Per Inch 2...8 2...8 Circuit Arrangement Half Half Connections — (Qty) Dim Supply (in.) Return (in.)

    (1) 2 1/2 NPT(1) 2 1/2 NPT

    (1) 2 1/2 NPT(1) 2 1/2 NPT

    Header Material Steel Steel Internal Volumes (cu ft) 0.5272 0.5272HEATING SECTION Low Heat High Heat Low Heat High Heat

    Number of Heat Exchangers 7 14 7 14Input (MBtuh) 325 650 325 650Output (MBtuh) (Vertical/Horizontal) 263/260 527/520 263/260 527/520Temperature Rise Range (F) 10-40 25-55 10-40 25-55Efficiency (%) (Vertical/Horizontal) 81/80 81/80 81/80 81/80Burner Orifice Diameter

    Quantity (in. ...drill no.) 7 (.1285...30) 14 (.1285...30) 7 (.1258...30) 14 (.1258...30)Manifold Pressure (in. wg) 3.5 3.5 3.5 3.5Line Pressure (in. wg) (min...max) 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0Firing Stages 2 2 2 2Number of Gas Valves 1 2 1 2

    CONDENSER FANS Propeller TypeQuantity...Diameter (in.) 2...30 2...30Nominal Cfm 18,000 19,500Motor Hp...Rpm 1.0...1140 1.0...1140

    SUPPLY FAN Centrifugal 25 x 25 in.Nominal Cfm 12,000 14,000Maximum Allowable Cfm 15,000 15,000Maximum Allowable Rpm 900 900Shaft Diameter at Pulley (in.) 111/16 111/16

    SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any unit)Motor Hp 7.5 10 15 20 25Motor Frame Size 213T 215T 254T 256T 284TEfficiency at Full Load (%) 91.7 91.7 93.0 93.6 93.6Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 13.7 13.7Motor Pulley Pitch Diameter (in.) 3.4 4.3 4.9 5.5 6.5Resulting Fan Speed (rpm) 438 549 626 703 830 Belts Quantity...Type 2...BX60 2...5VX630 2...5VX630 2...5VX630 2...5VX650Center Distance Range (in.) 17.74-14.30 17.74-14.30 17.63...14.01 17.63...14.01 16.63...12.87

    MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve

    Physical data — 48 series units

  • 16

    48P 030,035 (CONT)

    LEGEND

    BASE UNIT 48P 030 48P 035NOMINAL CAPACITY (tons) 30 35OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any unit)

    Quantity...Motor Hp 2...3.0 2...5.0 2...7.5 2...10Motor Frame Size 182T 184T 213T 215TEfficiency at Full Load (%) 88.5 89.5 91.7 91.7Fan Pulley Pitch Diameter (in.) 11.0 10.4 12 12Motor Pulley Pitch Diameter Range (in.) 4.1-3.1 4.7-3.7 6.0-4.8 7.0-5.8Motor Pulley Pitch Diameter Factory Setup (in.) 4.1 4.2 5.4 6.4Blower Shaft Diameter at Pulley (in.) 17/16 17/16 17/16 17/16Fan Rpm Range 500-656 621-785 717-882 854-1000Factory Setup Fan Rpm 656 703 800 927Maximum Allowable Rpm 1000 1000 1000 1000

    OPTIONAL RETURN FAN Plenum Fan, 30 in. (Any motor available on any unit)Quantity …Motor HP 1…10 1…15 1…20 1…25Motor Frame Size 215T 254T 256T 284TEfficiency at Full Load (%) 91.7 93 93.6 93.6Fan Pulley Pitch Diameter (in.) 6.6 7.4 6.8 8Motor Pulley Pitch Diameter (in.) 4.9 6.6 6.6 8Shaft Diameter at Pulley (in.) 1-7/16 1-7/16 1-7/16 1-7/16Resulting Fan Rpm 1300 1540 1700 1730Maximum Allowable Rpm 1750 1750 1750 1750

    FILTERSStandard Efficiency Throwaway (Standard)

    Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x 25 x 2, 8...20 x 20 x 2Medium Efficiency (30%) Pleated (Optional)

    Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x 25 x 2, 8...20 x 20 x 2High Efficiency (90%) Bag Filters

    with High Velocity Prefilters (Opt)Quantity...Size (in.)

    Bag Filter 6...20 x 24 x 22, 6...20 x 20 x 22 6...20 x 24 x 22, 6...20 x 20 x 22Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16 x 20 x 2, 3...20 x 24 x 2

    Cartridge Filters with High Velocity Prefilters (Opt)Quantity...Size (in.)

    Cartridge Filter 6...20 x 24 x 12, 6...20 x 20 x 12 6...20 x 24 x 12, 6...20 x 20 x 12Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16 x 20 x 2, 3...20 x 24 x 2

    OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.) None None

    OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent

    Quantity...Size (in.) 5...20 x 20 x 22...20 x 25 x 15...20 x 20 x 12...20 x 25 x 1

    MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve

    Physical data — 48 series units (cont)

  • 17

    48P 040,050

    LEGEND

    * 460-3-60 only.

    BASE UNIT 48P 040 48P 050NOMINAL CAPACITY (tons) 40 50OPERATING WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base UnitLow Heat 5810 6310 6025 6525High Heat 5940 6440 6155 6655

    With EconomizerLow Heat 6110 6610 6325 6825High Heat 6240 6740 6455 6955

    COMPRESSORS ScrollQuantity...Type 2...ZP103/1...ZP182 2...ZP120/2...ZP137Oil Charge (oz) per Compressor 110 110Number of Refrigerant Circuits 2 2

    REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2

    Standard Evaporator Coil 22.6/27.9 29.4/29.0Standard Evaporator with Humidi-MiZer® System 22.6/40.6 29.4/41.4Alternate High-Capacity Evaporator Coil 31.1/37.2 35.2/36.5Alternate High-Capacity Evaporator with Humidi-MiZer 31.1/49.6 35.2/48.9

    CONDENSER COILS Aluminum Novation® Heat Exchanger with Microchannel CoilsQuantity 2 2Total Face Area (sq ft) 66.7 66.7

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 45.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16.0 6...16.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Coil Construction E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 Face Area (sq ft) 26.7 26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum plate fins, galvanized steel frame

    Face Area (sq ft) 22.6 22.6 Rows...Fins Per Inch 2...8 2...8 Circuit Arrangement Half Half Connections — (Qty) Dim Supply (in.) Return (in.)

    (1) 2 1/2 NPT(1) 2 1/2 NPT

    (1) 2 1/2 NPT(1) 2 1/2 NPT

    Header Material Steel Steel Internal Volumes (cu ft) 0.5272 0.5272HEATING SECTION Low Heat High Heat Low Heat High Heat

    Number of Heat Exchangers 7 14 7 14Input (MBtuh) 325 650 325 650Output (MBtuh) (Vertical/Horizontal) 263/260 527/520 263/260 527/520Temperature Rise Range (F) 10-40 25-55 10-40 25-55Efficiency (%) (Vertical/Horizontal) 81/80 81/80 81/80 81/80Burner Orifice Diameter

    Quantity (in. ...drill no.) 7 (.1285...30) 14 (.1285...30) 7 (.1285...30) 14 (.1285...30)Manifold Pressure (in. wg) 3.5 3.5 3.5 3.5Line Pressure (in. wg) (min...max) 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0Firing Stages 2 2 2 2Number of Gas Valves 1 2 1 2

    CONDENSER FANS Propeller TypeQuantity...Diameter (in.) 3...30 4...30Nominal Cfm 30,000 38,000Motor Hp...Rpm 1.0...1140 1.0...1140

    SUPPLY FAN Centrifugal 25 x 25 in.Nominal Cfm 16,000 20,000Maximum Allowable Cfm 20,000 20,000Maximum Allowable Rpm 900 900Shaft Diameter at Pulley (in.) 111/16 111/16

    SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any unit)Motor Hp 7.5 10 15 20 25 30*Motor Frame Size 213T 215T 254T 256T 284T 286TEfficiency at Full Load (%) 91.7 91.7 93.0 93.6 93.6 93.6Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 13.7 13.7 12.5Motor Pulley Pitch Diameter (in.) 3.4 4.3 4.9 5.5 6.5 6.5Resulting Fan Speed (rpm) 438 549 626 703 830 910Belts Quantity...Type 2...BX60 2...5VX630 2...5VX630 2...5VX630 2...5VX650 3...5VX630Center Distance Range (in.) 17.74-14.30 17.74-14.30 17.63...14.01 17.63...14.01 16.63...12.87 16.63...12.87

    MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve

  • 18

    48P 040,050 (CONT)

    LEGEND

    BASE UNIT 48P 040 48P 050NOMINAL CAPACITY (tons) 40 50OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any unit)

    Quantity...Motor Hp 2...3.0 2...5.0 2...7.5 2...10Motor Frame Size 182T 184T 213T 215TEfficiency at Full Load (%) 88.5 89.5 91.7 91.7Fan Pulley Pitch Diameter (in.) 11.0 10.4 12 12Motor Pulley Pitch Diameter Range (in.) 4.1-3.1 4.7-3.7 6.0-4.8 7.0-5.8Motor Pulley Pitch Diameter Factory Setup (in.) 4.1 4.2 5.4 6.4Blower Shaft Diameter at Pulley (in.) 17/16 17/16 17/16 17/16Fan Rpm Range 500-656 621-785 717-882 854-1000Factory Setup Fan Rpm 656 703 800 927Maximum Allowable Rpm 1000 1000 1000 1000

    OPTIONAL RETURN FAN Plenum Fan, 30 in. (Any motor available on any unit)Quantity …Motor HP 1…10 1…15 1…20 1…25Motor Frame Size 215T 254T 256T 284TEfficiency at Full Load (%) 91.7 93 93.6 93.6Fan Pulley Pitch Diameter (in.) 6.6 7.4 6.8 8Motor Pulley Pitch Diameter (in.) 4.9 6.6 6.6 8Shaft Diameter at Pulley (in.) 1-7/16 1-7/16 1-7/16 1-7/16Resulting Fan Rpm 1300 1540 1700 1730Maximum Allowable Rpm 1750 1750 1750 1750

    FILTERSStandard Efficiency Throwaway (Standard)

    Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x 25 x 2, 8...20 x 20 x 2Medium Efficiency (30%) Pleated (Optional)

    Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x 25 x 2, 8...20 x 20 x 2High Efficiency (90%) Bag Filters

    with High Velocity Prefilters (Opt)Quantity...Size (in.)

    Bag Filter 6...20 x 24 x 22, 6...20 x 20 x 22 6...20 x 24 x 22, 6...20 x 20 x 22Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16 x 20 x 2, 3...20 x 24 x 2

    Cartridge Filters with High Velocity Prefilters (Opt)Quantity...Size (in.)

    Cartridge Filter 6...20 x 24 x 12, 6...20 x 20 x 12 6...20 x 24 x 12, 6...20 x 20 x 12Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16 x 20 x 2, 3...20 x 24 x 2

    OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.) None None

    OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent

    Quantity...Size (in.) 5...20 x 20 x 22...20 x 25 x 15...20 x 20 x 12...20 x 25 x 1

    MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve

    Physical data — 48 series units (cont)

  • 19

    48P 055-070

    LEGEND

    BASE UNIT 48P 055 48P 060 48P 070NOMINAL CAPACITY (tons) 55 60 70OPERATING WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base UnitLow Heat 7810 8360 7865 8415 8205 8755High Heat 7940 8490 7995 8545 8335 8885

    With EconomizerLow Heat 8340 8890 8395 8945 8735 9285High Heat 8470 9020 8525 9075 8865 9415

    COMPRESSORS ScrollQuantity...Type 2...ZP137/2...ZP137 2...ZP154/2...ZP154 1...ZP154,1...ZP182Oil Charge (oz) per Compressor 110 110 110Number of Refrigerant Circuits 2 2 2

    REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2

    Standard Evaporator Coil 37.6/37.9 37.6/37.9 41.2/44.8Standard Evaporator with Humidi-MiZer®

    System 37.6/50.3 37.6/50.3 41.2/57.2

    Alternate High-Capacity Evaporator Coil 43.5/42.8 44.6/43.5 52.5/52.0Alternate High-Capacity Evaporator with

    Humidi-MiZer43.5/55.2 44.6/55.9 52.5/64.4

    CONDENSER COILS Aluminum Novation® Heat Exchanger with Microchannel CoilsQuantity 2 2 4Total Face Area (sq ft) 66.7 66.7 106.7

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16 6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Coil Construction E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 1 1 1 1 Face Area (sq ft) 26.7 26.7 26.7 26.7 26.7 26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum plate fins, galvanized steel frame

    Face Area (sq ft) (2) sections: total 27.1 (2) sections: total 27.1 (2) sections: total 27.1 Rows...Fins Per Inch 2...11 2...11 2...11 Circuit Arrangement Half Half Half Connections — (Qty) Dim Supply (in.) Return (in.)

    (2) 1 1/2 NPT(2) 1 1/2 NPT

    (2) 1 1/2 NPT(2) 1 1/2 NPT

    (2) 1 1/2 NPT(2) 1 1/2 NPT

    Header Material Steel Steel Steel Internal Volumes (cu ft) 0.6327 0.6327 0.6327HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat High Heat

    Number of Heat Exchangers 14 21 14 21 14 21Input (MBtuh) 650 975 650 975 650 975Output (MBtuh) (Vertical/Horizontal) 525/520 787/780 525/520 787/780 525/520 787/780Temperature Rise Range (F) 10-40 20-50 10-40 20-50 10-40 20-50Efficiency (%) (Vertical/Horizontal) 81/80 81/80 81/80 81/80 81/80 81/80Burner Orifice Diameter

    Quantity (in. ...drill no.) 14 (.1285...30) 21 (.1285...30) 14 (.1285...30) 21 (.1285...30) 14 (.1285...30) 21 (.1285...30)Manifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5Line Pressure (in. wg) (min...max) 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0Firing Stages 2 2 2 2 2 2Number of Gas Valves 2 3 2 3 2 3

    CONDENSER FANS Propeller TypeQuantity...Diameter (in.) 4...30 4...30 4...30Nominal Cfm 36,000 36,600 39,000Motor Hp...Rpm 1.0...1140 1.0...1140 1.0...1140

    SUPPLY FAN Centrifugal 30 x 27.5 in.Nominal Cfm 22,000 24,000 28,000Maximum Allowable Cfm 25,000 30,000 30,000Maximum Allowable Rpm 800 800 800Shaft Diameter at Pulley (in.) 111/16 111/16 111/16

    SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any unit)Motor Hp 15 20 25 30 40Motor Frame Size 254T 256T 284T 286T S324TEfficiency at Full Load (%) 93.0 93.6 93.6 93.6 94.5Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 15.5 16.1Motor Pulley Pitch Diameter (in.) 4.5 5.1 5.5 5.9 6.7Resulting Fan Speed (rpm) 575 651 703 711 740

    Belts Quantity...Type 2...5VX1230 2...5VX1230 2...5VX1230 2...5VX1230 3...5VX1250

    Center Distance Range (in.) 48.25-44.00 48.25-44.00 48.50-44.25 48.50-44.25 48.25-44.00

    MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve

  • 20

    48P 055-070 (CONT)

    LEGEND

    BASE UNIT 48P 055 48P 060 48P 070NOMINAL CAPACITY (tons) 55 60 70OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any unit)

    Quantity...Motor Hp 2...5 2...7.5 2...10Motor Frame Size 184T 213T 215TEfficiency at Full Load (%) 89.5 91.7 91.7Resulting Fan Rpm 740 820 920Maximum Allowable Rpm 1000 1000 1000

    OPTIONAL RETURN FAN Plenum Fan, 36 in. (Any motor available on any unit)Quantity …Motor HP 1…15 1…20 1…25 1…30Motor Frame Size 254T 256T 284T 286TEfficiency at Full Load (%) 93 93.6 93.6 93.6Fan Pulley Pitch Diameter (in.) 9.1 9.1 9.1 9.1Motor Pulley Pitch Diameter (in.) 5.9 6.1 6.7 6.9Shaft Diameter at Pulley (in.) 1-11/16 1-11/16 1-11/16 1-11/16Resulting Fan Rpm 1150 1200 1300 1327Maximum Allowable Rpm 1750 1750 1750 1750

    FILTERSStandard Efficiency Throwaway (Standard)

    Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2Medium Efficiency (30%) Pleated (Optional)

    Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2High Efficiency (90%) Bag Filters

    with High Velocity Prefilters (Optional)Quantity...Size (in.)

    Bag Filter 6...24 x 24 x 22, 6...24 x 20 x 22 6...24 x 24 x 22, 6...24 x 20 x 22 6...24 x 24 x 22, 6...24 x 20 x 22 Prefilter 6...24 x 24 x 2, 6...20 x 24 x 2 6...24 x 24 x 2, 6...20 x 24 x 2 6...24 x 24 x 2, 6...20 x 24 x 2

    Cartridge Filters with High Velocity Prefilters (Optional)

    Quantity...Size (in.) Cartridge Filter 6...24 x 24 x 12, 6...24 x 20 x 12 6...24 x 24 x 12, 6...24 x 20 x 12 6...24 x 24 x 12, 6...24 x 20 x 12 Prefilter 6...24 x 24 x 2, 6...20 x 24 x 2 6...24 x 24 x 2, 6...20 x 24 x 2 6...24 x 24 x 2, 6...20 x 24 x 2

    OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.) 4...25 x 16 x 1, 2...20 x 16 x 1 4...25 x 16 x 1, 2...20 x 16 x 1 4...25 x 16 x 1, 2...20 x 16 x 1

    OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent Quantity...Size (in.) 12...16 x 25 x 1, 2...16 x 20 x 1 12...16 x 25 x 1, 2...16 x 20 x 1 12...16 x 25 x 1, 2...16 x 20 x 1

    MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve

    Physical data — 48 series units (cont)

  • 21

    48P 075-100

    LEGEND

    BASE UNIT 48P 075 48P 090 48P 100NOMINAL CAPACITY (tons) 75 90 100OPERATING WEIGHT (lb) Standard

    ChassisExtendedChassis

    StandardChassis

    ExtendedChassis

    StandardChassis

    ExtendedChassis

    Base UnitLow Heat 9065 9615 9665 10,215 9685 10,235High Heat 9195 9745 9795 10,345 9815 10,365

    With EconomizerLow Heat 9595 10,145 10,195 10,745 10,215 10,765High Heat 9725 10,275 10,325 10,875 10,345 10,895

    COMPRESSORS ScrollQuantity...Type 2...ZP182/2...ZP182 3...ZP154,3...ZP154 3...ZP154,3...ZP182Oil Charge (oz) per Compressor 110 110 110Number of Refrigerant Circuits 2 2 2

    REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2

    Standard Evaporator Coil 41.2/44.8 50.4/51.3 50.8/52.8Standard Evaporator with Humidi-MiZer® System 41.2/57.2 50.4/69.1 50.8/70.6Alternate High-Capacity Evaporator Coil 52.5/52.0 61.5/62.9 59.3/62.8Alternate High-Capacity Evaporator withHumidi-MiZer

    52.5/64.4 61.5/80.7 59.3/80.6

    CONDENSER COILS Aluminum Novation® Heat Exchanger with Microchannel CoilsQuantity 4 6 6Total Face Area (sq ft) 106.7 160.0 160.0

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16 6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER® ADAPTIVE DEHUMIDIFICATION SYSTEM Coil Construction E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 1 Face Area (sq ft) 26.7 33.3 33.3OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum plate fins, galvanized steel frame

    Face Area (sq ft) (2) sections: total 27.1 (2) sections: total 27.1 (2) sections: total 27.1 Rows...Fins Per Inch 2...11 2...11 2...11 Circuit Arrangement Half Half Half Connections — (Qty) Dim Supply (in.) Return (in.)

    (2) 1 1/2 NPT(2) 1 1/2 NPT

    (2) 1 1/2 NPT(2) 1 1/2 NPT

    (2) 1 1/2 NPT(2) 1 1/2 NPT

    Header Material Steel Steel Steel Internal Volumes (cu ft) 0.6327 0.6327 0.6327

    HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat High HeatNumber of Heat Exchangers 2 3 2 3 2 3Input (MBtuh) 650 975 650 975 650 975Output (MBtuh) (Vertical/Horizontal) 526/520 784/780 526/520 784/780 526/520 784/780Temperature Rise Range (F) 10-40 20-50 10-40 20-50 10-40 20-50Efficiency (%) (Vertical/Horizontal) 81/80 81/80 81/80 81/80 81/80 81/80Burner Orifice Diameter

    Quantity (in. ...drill no.) 7 (.1285...30) 7 (.1285...30) 7 (.1285...30) 7 (.1285...30) 7 (.1285...30) 7 (.1285...30)Manifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5Line Pressure (in. wg) (Min...Max) 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0Number of Gas Valves 2 3 2 3 2 3

    CONDENSER FAN Propeller TypeQuantity...Diameter (in.) 4...30 6...30 6...30Nominal Cfm 39,000 58,000 58,000Motor Hp (ea)...rpm 1.0...1140 1.0...1140 1.0...1140

    STANDARD SUPPLY FAN Forward Curved Centrifugal 36 x 30 in.Nominal Cfm 30,000 36,000 40,000Maximum Allowable Cfm 30,000 36,000 40,000Maximum Allowable Rpm 680 680 680Shaft Diameter at Pulley (in.) 111/16 111/16 111/16

    STANDARD SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any unit)Motor Hp 30 40 50 60Motor Frame Size S268T S324T S326T S364TEfficiency at Full Load (%) 93.6 94.5 94.5 95.4Fan Pulley Pitch Diameter (in.) 18.5 18.5 18.5 18.5Motor Pulley Pitch Diameter (in.) 5.3 5.7 6.5 7.1Resulting Fan Rpm 501 539 615 672Belts Quantity...Type 3...5VX1320 4...5VX1320 4...5VX1320 4...5VX1320Center Distance Range (in.) 47.88-45.01 47.64-44.76 47.42-44.52 47.42-44.52

    DWDI — Double Width, Double InletMBtuh — Btuh in ThousandsSWSI — Single Width, Single InletTXV — Thermostatic Expansion Valve

  • 22

    48P 075-100 (CONT)

    LEGEND

    BASE UNIT 48P 075 48P 090 48P 100ALTERNATE, AIRFOIL FAN DWDI Airfoil, 33 in.

    Nominal Airflow (cfm) 30,000 36,000 40,000Maximum Allowable Airflow (cfm) 30,000 36,000 40,000Maximum Allowable Wheel Speed (rpm) 1846 1846 1846Shaft Diameter at Pulley (in.) 211/16 211/16 211/16

    ALTERNATE SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any unit)

    Motor Hp 30 40 50 60 75Motor Frame Size S268T S324T S326T S364T 365TEfficiency at Full Load (%) 93.6 94.5 94.5 95.4 95.4Fan Pulley Pitch Diameter (in.) 9.7 10.2 8.9 8.9 10.8Motor Pulley Pitch Diameter (in.) 7.5 8.7 8.1 8.7 11.1Resulting Fan Rpm 1353 1493 1593 1711 1799Belts Quantity...Type 2...5VX1150 2...5VX1180 3...5VX1150 3...5VX1150 3...5VX1230Center Distance Range (in.) 42.96...45.82 42.96...45.57 42.96...45.57 42.45...45.35 42.45...45.35

    OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any unit.)Quantity...Motor Hp 2...5 2...7.5 2...10Motor Frame Size 184T 213T 215TEfficiency at Full Load (%) 89.5 91.7 91.7Fan Pulley Pitch Diameter (in.) 10.6 10.6 10.6Motor Pulley Pitch Diameter (in.) 4.5 5.0 5.6Shaft Diameter at Pulley (in.) 17/16 17/16 17/16Resulting Fan Rpm 740 820 920Maximum Allowable Rpm 1000 1000 1000

    OPTIONAL HIGH-CAPACITY POWER EXHAUST

    Centrifugal, 22 x 20 in., 111/16 in. shaft diameter (Any motor available on any unit)

    Total HpQuantity...Motor HpMotor Frame SizeEfficiency at Full Load (%)Fan Sheave Pitch Diameter (in.)

    Motor Sheave Pitch Diameter (in.)Resulting Fan Rpm

    Maximum Allowable RpmBelts Quantity...Type

    OPTIONAL RETURN FAN SWSI Plenum Fan, 47.13 in. (Any motor available on any unit.)Quantity...Motor HpMotor Frame SizeEfficiency at Full Load (%)Fan Pulley Pitch Diameter (in.)Motor Pulley Pitch Diameter (in.)Shaft Diameter at Pulley (in.)Resulting Fan RpmMaximum Allowable Rpm

    FILTERSStandard Efficiency Throwaway (Standard)

    Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 230% and 65% Pleated (Optional)

    Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2OUTSIDE AIR SCREENS

    Standard Hood (25%) Quantity...Size (in.) 4...25 x 16 x 1, 2...20 x 16 x 1 4...25 x 16 x 1, 2...20 x 16 x 1 4...25 x 16 x 1, 2...20 x 16 x 1OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent

    Quantity...Size (in.) 12...16 x 25 x 1, 2...16 x 20 x 1 12...16 x 25 x 1, 2...16 x 20 x 1 12...16 x 25 x 1, 2...16 x 20 x 1

    20 30 40 50 602...10 2...15 2...20 2...25 2...30S215T D254T S256T S284T S286T

    91.7 93.0 93.6 93.6 93.612.4 12.4 11.1 11.1 11.14.8 5.8 5.9 6.5 6.9714 841 928 1020 10941175 1175 1175 1175 1175

    1...20 1...25 1...30 1...40256T 284T 286T 324T93.6 93.6 93.6 93.88.5 9.8 8.5 8.55.3 6.7 6.1 6.7

    215/16 215/16 215/16 215/161104 1209 1271 13961447 1447 1447 1447

    DWDI — Double Width, Double InletMBtuh — Btuh in ThousandsSWSI — Single Width, Single InletTXV — Thermostatic Expansion Valve

    Physical data — 48 series units (cont)

  • 23

    48P 030,035 WITH RETURN/EXHAUST FAN OPTION

    LEGEND

    BASE UNIT 48P 030 48P 035NOMINAL CAPACITY (tons) 30 35OPERATING WEIGHT (lb) (without IFM or R/E FM/VFD) Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base Unit (with Econ)Low Heat 6123 6623 6223 6723High Heat 6253 6753 6353 6853

    COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 1...ZP154 / 1...ZP154 1...ZP182 / 1...ZP182

    Oil Charge (oz) per Compressor 110 110Capacity Steps (%) CV 50, 100 50, 100 VAV (with digital scroll) 25 to 100 25 to 100Number of Refrigerant Circuits 2 2REFRIGERANT R-410A

    Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil 15.4 / 14.8 17.1 / 17.5Standard Evaporator with Humidi-MiZer® System 15.4 / 24.9 17.1 / 27.6Alternate High-Capacity Evaporator Coil 18.8/17.8 N/AAlternate High-Capacity Evaporator with Humidi-MiZer 18.8/27.9 N/A

    CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger with Microchannel Coils

    Quantity 1 1Total Face Area (sq ft) 33.3 33.3

    EVAPORATOR COILSQuantity 1Total Face Area (sq ft) 32.1Refrigerant Feed Device...No. per Circuit TXV...1Standard Evaporator Coils

    Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 4...15.0 N/AFin Type Double Wavy N/ATube Type Cross Hatched N/A

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material, Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 Total Face Area (sq ft) 26.7 26.7CONDENSER FANS Propeller Type

    Quantity...Diameter (in.) 2...30 2...30Nominal Cfm 18,000 19,500Motor Hp...Rpm 1.0...1140 1.0...1140

    HEATING SECTION Low Heat High Heat Low Heat High HeatManifold Pressure (in. wg) 3.5 3.5 3.5 3.5

    FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD — Variable Frequency Drive

  • 24

    48P 040,050 WITH RETURN/EXHAUST FAN OPTION

    LEGEND

    BASE UNIT 48P 040 48P 050NOMINAL CAPACITY (tons) 40 50OPERATING WEIGHT (lb) (without IFM or R/E FM/VFD) Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base Unit (with Econ)Low Heat 6623 7123 6838 7338High Heat 6753 7253 6968 7468

    COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 2...ZP103 / 1...ZP182 2...ZP120 / 2...ZP137

    Oil Charge (oz) per Compressor 110 110Capacity Steps (%) CV 47,73,100 23,50,73, 100 VAV (with digital scroll) 23 to 100 12 to 100Number of Refrigerant Circuits 2 2REFRIGERANT R-410A

    Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil 22.6 / 27.9 29.4 / 29.0Standard Evaporator with Humidi-MiZer® System 22.6 / 40.6 29.4 / 41.4Alternate High-Capacity Evaporator Coil 31.1 / 37.2 35.2 / 36.5Alternate High-Capacity Evaporator with Humidi-MiZer 31.1 / 49.6 35.2 / 48.9

    CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger with Microchannel Coils

    Quantity 2 2Total Face Area (sq ft) 66.7 66.7

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 45.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16.0 6...16.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material, Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 Total Face Area (sq ft) 26.7 26.7CONDENSER FANS Propeller Type

    Quantity...Diameter (in.) 3...30 4...30Nominal Cfm 30,000 38,000Motor Hp...Rpm 1.0...1140 1.0...1140

    HEATING SECTION Low Heat High Heat Low Heat High HeatManifold Pressure (in. wg) 3.5 3.5 3.5 3.5

    FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD — Variable Frequency Drive

    Physical data — 48 series units (cont)

  • 25

    48P 055-070 WITH RETURN/EXHAUST FAN OPTION

    LEGEND

    BASE UNIT 48P 055 48P 060 48P 070NOMINAL CAPACITY (tons) 55 60 70OPERATING WEIGHT (lb) (without IFM or R/E FM/VFD) Standard Chassis Extended Chassis Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base Unit (with Econ)Low Heat 9215 9765 9270 9820 9610 10,160High Heat 9345 9895 9400 9950 9740 10,290

    COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 2...ZP137 / 2...ZP137 2...ZP154 / 2...ZP154 1...ZP154 / 1...ZP182

    Oil Charge (oz) per Compressor 110 110 110Capacity Steps (%) CV 25,50,75,100 25,50,75,100 23,46,73,100 VAV (with digital scroll) 13 to 100 13 to 100 11 to 100Number of Refrigerant Circuits 2 2 2REFRIGERANT R-410A

    Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil 37.6 / 37.9 37.6 / 37.9 41.2 / 44.8Standard Evaporator with Humidi-MiZer®

    System 37.6 / 50.3 37.6 / 50.3 41.2 / 57.2

    Alternate High-Capacity Evaporator Coil 43.5 / 42.8 44.6 / 43.5 52.5 / 52.0Alternate High-Capacity Evaporator with

    Humidi-MiZer43.5 / 55.2 44.6 / 55.9 52.5 / 64.4

    CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger with Microchannel Coils

    Quantity 2 2 4Total Face Area (sq ft) 66.7 66.7 106.7

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16 6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material, Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 1 Total Face Area (sq ft) 26.7 26.7 26.7CONDENSER FANS Propeller Type

    Quantity...Diameter (in.) 4...30 4...30 4...30Nominal Cfm 36,000 36,600 39,000Motor Hp...Rpm 1.0...1140 1.0...1140 1.0...1140

    HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat High HeatManifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5

    FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD — Variable Frequency Drive

  • 26

    48P 075-100 WITH RETURN/EXHAUST FAN OPTION

    LEGEND

    BASE UNIT 48P 075 48P 090 48P 100NOMINAL CAPACITY (tons) 75 90 100OPERATING WEIGHT (lb) (without IFM or R/E FM/VFD) Standard Chassis Extended Chassis Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base Unit (with Econ)Low Heat 10618 11168 11218 11768 11238 11788High Heat 10748 11298 11348 11898 11368 11918

    COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 2...ZP182 / 2...ZP182 3...ZP154,3...ZP154 3...ZP154,3...ZP182

    Oil Charge (oz) per Compressor 110 110 110Capacity Steps (%) CV 25, 50, 75, 100 17, 33, 50, 67, 83, 100 15, 33, 49, 67, 82, 100 VAV (with digital scroll) 13 to 100 8 to 100 8 to 100Number of Refrigerant Circuits 2 2 2REFRIGERANT R-410A

    Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil 41.2 / 44.8 50.4 / 51.3 50.8 / 52.8Standard Evaporator with Humidi-MiZer®

    System 41.2 / 57.2 50.4 / 69.1 50.8 / 70.6

    Alternate High-Capacity Evaporator Coil 52.5 / 52.0 61.5 / 62.9 59.3 / 62.8Alternate High-Capacity Evaporator with

    Humidi-MiZer52.5 / 64.4 61.5 / 80.7 59.3 / 80.6

    CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger with Microchannel Coils

    Quantity 4 6 6Total Face Area (sq ft) 106.7 160.0 160.0

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16 6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material, Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 1 Total Face Area (sq ft) 26.7 33.3 33.3CONDENSER FANS Propeller Type

    Quantity...Diameter (in.) 4...30 6...30 6...30Nominal Cfm 39,000 58,000 58,000Motor Hp...Rpm 1.0...1140 1.0...1140 1.0...1140

    HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat High HeatManifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5

    FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD — Variable Frequency Drive

    Physical data — 48 series units (cont)

  • 27

    50P 030,035

    LEGEND

    BASE UNIT 50P 030 50P 035NOMINAL CAPACITY (tons) 30 35OPERATING WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base UnitVertical Discharge 4810 5310 4910 5410Horizontal Discharge and Vertical Discharge

    with Discharge Plenum 5110 5610 5210 5710

    With EconomizerVertical Discharge 5110 5610 5210 5710Horizontal Discharge and Vertical Discharge

    with Discharge Plenum 5410 5910 5510 6010

    COMPRESSORS ScrollQuantity...Type 1...ZP154/1...ZP154 1...ZP182/1...ZP182Oil Charge (oz) per Compressor 110 110Number of Refrigerant Circuits 2 2

    REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2

    Standard Evaporator Coil 15.4/14.8 17.1/17.5Standard Evaporator with Humidi-MiZer® System 15.4/24.9 17.1/27.6Alternate High-Capacity Evaporator Coil 18.8/17.8 N/AAlternate High-Capacity Evaporator with Humidi-MiZer 18.8/27.9 N/A

    CONDENSER COILS Aluminum Novation® Heat Exchanger with Microchannel CoilsQuantity 1 1Total Face Area (sq ft) 33.3 33.3

    EVAPORATOR COILSQuantity 1Total Face Area (sq ft) 32.1Refrigerant Feed Device...No. per Circuit TXV...1Standard Evaporator Coils

    Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 4...15.0 N/AFin Type Double Wavy N/ATube Type Cross Hatched N/A

    OPTIONAL HUMIDI-MIZER® ADAPTIVE DEHUMIDIFICATION SYSTEM Coil Construction E-Coated Aluminum Novation® Heat Exchanger with Microchannel Coil Technology Quantity 1 1 1 1 Face Area (sq ft) 26.7 26.7 26.7 26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum plate fins, galvanized steel frame

    Face Area (sq ft) 22.6 22.6 Rows...Fins Per Inch 2...8 2...8 Circuit Arrangement Half Half Connections — (Qty) Dim Supply (in.) Return (in.)

    (1) 2 1/2 NPT(1) 2 1/2 NPT

    (1) 2 1/2 NPT(1) 2 1/2 NPT

    Header Material Steel Steel Internal Volumes (cu ft) 0.5272 0.5272CONDENSER FANS Propeller Type

    Quantity...Diameter (in.) 2...30 2...30Nominal Cfm 18,000 19,500Motor Hp...Rpm 1.0...1140 1.0...1140

    SUPPLY FAN Centrifugal 25 x 25 in.Nominal Cfm 12,000 14,000Maximum Allowable Cfm 15,000 15,000Maximum Allowable Rpm 900 900Shaft Diameter at Pulley (in.) 111/16 111/16

    SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any unit)Motor Hp 7.5 10 15 20 25Motor Frame Size 213T 215T 254T 256T 284TEfficiency at Full Load (%) 91.7 91.7 93.0 93.6 93.6Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 13.7 13.7Motor Pulley Pitch Diameter (in.) 3.4 4.3 4.9 5.5 6.5Resulting Fan Speed (rpm) 438 549 626 703 830 Belts Quantity...Type 2...BX60 2...5VX630 2...5VX630 2...5VX630 2...5VX650Center Distance Range (in.) 17.74-14.30 17.74-14.30 17.63...14.01 17.63...14.01 16.63...12.87

    OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any unit)Quantity...Motor Hp 2...3.0 2...5.0 2...7.5 2...10Motor Frame Size 182T 184T 213T 215TEfficiency at Full Load (%) 88.5 89.5 91.7 91.7Fan Pulley Pitch Diameter (in.) 11.0 10.4 12 12Motor Pulley Pitch Diameter Range (in.) 4.1-3.1 4.7-3.7 6.0-4.8 7.0-5.8Motor Pulley Pitch Diameter Factory Setup (in.) 4.1 4.2 5.4 6.4Blower Shaft Diameter at Pulley (in.) 17/16 17/16 17/16 17/16Fan Rpm Range 500-656 621-785 717-882 854-1000Factory Setup Fan Rpm 656 703 800 927Maximum Allowable Rpm 1000 1000 1000 1000

    TXV — Thermostatic Expansion Valve

    Physical data — 50 series units

  • 28

    50P 030,035 (CONT) BASE UNIT 50P 030 50P 035NOMINAL CAPACITY (tons) 30 35OPTIONAL RETURN/EXHAUST FAN Plenum Fan, 30 in. (Any motor available on any unit)

    Quantity …Motor HP 1…10 1…15 1…20 1…25Motor Frame Size 215T 254T 256T 284TEfficiency at Full Load (%) 91.7 93 93.6 93.6Fan Pulley Pitch Diameter (in.) 6.6 7.4 6.8 8Motor Pulley Pitch Diameter (in.) 4.9 6.6 6.6 8Shaft Diameter at Pulley (in.) 1-7/16 1-7/16 1-7/16 1-7/16Resulting Fan Rpm 1300 1540 1700 1730Maximum Allowable Rpm 1750 1750 1750 1750

    FILTERSStandard Efficiency Throwaway (Standard)

    Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x 25 x 2, 8...20 x 20 x 2Medium Efficiency (30%) Pleated (Optional)

    Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x 25 x 2, 8...20 x 20 x 2High Efficiency (90%) Bag Filters

    with High Velocity Prefilters (Opt)Quantity...Size (in.)

    Bag Filter 6...20 x 24 x 22, 6...20 x 20 x 22 6...20 x 24 x 22, 6...20 x 20 x 22Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16 x 20 x 2, 3...20 x 24 x 2

    Cartridge Filters with High Velocity Prefilters (Opt)Quantity...Size (in.)

    Cartridge Filter 6...20 x 24 x 12, 6...20 x 20 x 12 6...20 x 24 x 12, 6...20 x 20 x 12Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16 x 20 x 2, 3...20 x 24 x 2

    OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.) None None

    OPTIONAL ECONOMIZER FILTER Aluminum Frame, PermanentQuantity...Size (in.) 5...20 x 20 x 2, 2...20 x 25 x 1 5...20 x 20 x 1, 2...20 x 25 x 1

    Physical data — 50 series units (cont)

  • 29

    50P 040,050

    LEGEND * 460-3-60 only.

    BASE UNIT 50P 040 50P 050NOMINAL CAPACITY (tons) 40 50OPERATING WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis Extended Chassis

    Base UnitVertical Discharge 5310 5810 5525 6025Horizontal Discharge and Vertical Discharge

    with Discharge Plenum 5610 6110 5825 6325

    With EconomizerVertical Discharge 5610 6110 5825 6325Horizontal Discharge and Vertical Discharge

    with Discharge Plenum 5910 6410 6125 6625

    COMPRESSORS ScrollQuantity...Type 2...ZP103/1...ZP182 2...ZP120/2...ZP137Oil Charge (oz) per Compressor 110 110Number of Refrigerant Circuits 2 2

    REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2

    Standard Evaporator Coil 21.6/27.9 29.4/29.0Standard Evaporator with Humidi-MiZer® System 22.6/40.6 29.4/41.4Alternate High-Capacity Evaporator Coil 31.1/37.2 35.2/36.5Alternate High-Capacity Evaporator with Humidi-MiZer 31.1/49.6 35.2/48.9

    CONDENSER COILS Aluminum Novation® Heat Exchanger with Microchannel CoilsQuantity 2 2Total Face Area (sq ft) 66.7 66.7

    EVAPORATOR COILSQuantity 2Total Face Area (sq ft) 45.5Refrigerant Feed Device...No. per Circuit TXV...2Standard Evaporator Coils

    Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16.0 6...16.0Fin Type Double Wavy Double WavyTube Type Cross Hatched Cross Hatched

    OPTIONAL HUMIDI-MIZER® ADAPTIVE DEH