product catalogue - equinoxe · pt100 probe table pg. 48 pt1000 probe table pg. 48 tcj probe table...
TRANSCRIPT
Product catalogueTemperature control and Automation
EFFICIENTCONNECTING
INTUITIVE
Product catalogueTemperature control and Automation
EO (Environmentally Optimised)EO (Environmentally Optimised) refers to the new solutions created by Eliwell designers that are highly efficient, eco-system compliant and designed to deliver the clear environmental benefits for users. Devices are developed with new energy saving algorithms that can guarantee immediate, measurable economic returns. Compatible with the new ecological refrigerants R290 and R600, the products have been designed to guarantee lower operating and maintenance costs and have an active packaging recycling program. Design efforts have also enabled us to simplify installation, maintenance and operational use of Eliwell EO products.
MODBUS-RTUModBus is a serial communication protocol that allows communication between different devices connected to the same network. ModBus is often used to connect a supervisor computer to a remote terminal unit (RTU) in monitoring control and data acquisition systems.
RS-485This is the standard that describes the communication interface for serial connection between a network of devices and the computer. The network, normally with 3 wires, makes it possible to cover much longer distances than the RS232 standard. The protocol used for the communication can either be Eliwell, i.e. created according to Eliwell specifications, or ModBus.
COPY CARDThe Copy Card is an accessory that connects to a TTL type serial port and allows the rapid programming of instrument parameters.
TELEVISSYSTEMTelevisSystem is a remote management and monitoring system for industrial and commercial systems, such as supermarkets and hypermarkets. Data can either be printed or extracted and downloaded in a format which is compatible with the most commonly used office automation software. The monitoring system can be accessed remotely via a web browser, using any PC or handheld device connected to the network.
TEMPERATURE PROBESThanks to the different materials used in the different models, the temperature probes are capable of covering a very wide temperature range; the sensors used are PTC, NTC, thermocouple, Pt100 and Pt1000. Depending on the kind of sensor, the protective casing (usually cylindrical) can be made of either ABS, Aisi 304/316 stainless steel or Inconel. For additional sensor protection, special materials are used (e.g. resins) between sensor and casing. The cable that transmits the signal to the instrument is made of either PVC, Silicone or Vetrotex and is available in different lengths. The range of use depends on the materials used, as well as on the type of sensor.
KEY
4
KEY
HUMIDITY PROBESThe EWHS series of probes are specially made for connection to humidity measurement instruments. EWHS 280 and EWHS 300 probes have one current output (4...20 mA) proportional to the relative humidity. EWHS 310 probes have two current outputs (0...20 mA), one for humidity and one for temperature.
PRESSURE PROBESThe EWPA series of probes are pressure reading devices that have one 4...20 mA current output for transferring the signal to the measuring instrument. The EWPA 007 probes have an operating range up to 7 bar, whereas the EWPA 030 probes operate up to 30 bar.
PIDThe PID function is an alternative to the on-off control for use in situations requiring greater precision and reduced oscillations with regard to the setpoint, in both ‘hot’ and ‘cold’ applications. Controllers with the PID function have a further option known as Autotuning, which automatically calculates the parameters necessary for better process control.
SWITCHING POWER SUPPLYThe switching power supply, that switches from either 100...240 V~ or from 12...24 V~/12...36 V~ offers the installer the option of covering most applications, thus reducing the number of models that would be necessary if a transformer-type power supply was used.
5
INDEX
ELECTRONIC CONTROLS Pg. 07
32x74 cold/hot thermostats ICPlus 902 Pg. 08
ICPlus 915 Pg. 09
TPID 32x74 cold/hot thermostats IC 917/PID (SSR) Pg. 10
Temperature, humidity, pressure indicators EM300 (LX) Pg. 11
LCD thermometers EWTL 300 - EWTL 310 - DST-30 Pg. 12
32x74 timers and counters EWTS 950 LX - EWTS 990 LX Pg. 13
Universal DIN controllers DR4020 Pg. 14
Universal DIN controllers with serial port DR4022 Pg. 15
Universal 48x48 controllers EW4820 (SSR) Pg. 16
Universal 48x48 controllers with serial port EW4822 (SSR) Pg. 17
Universal 72x72 controllers EW7210 - EW7220 Pg. 18
Universal 72x72 controllers with serial port EW7221 - EW7222 Pg. 19
Programmable platform FREE Way Pg. 20
FREE Studio Pg. 21
FREE Panel Pg. 21
FREE Smart Pg. 22
FREE Evolution Pg. 23
SUPERVISION AND MONITORING Pg. 24
Recording and printing temperature Memory 1000 Pg. 25
Monitoring and maintenance systems via web TelevisGo Pg. 26
Data acquisition modules and actuators TelevisIn/TelevisOut Pg. 28
Controller configuration software DeviceManager Pg. 29
ACCESSORIES Pg. 30
Ethernet connectivity for the systems SerialAdapter - Ethernet LanAdapter - WiFi LanAdapter Pg. 31
Wireless connectivity modules RadioAdapter - RadioAdapter (/S) EXT - RadioKey Pg. 32
RS-485 opto-isolated connectivity modules BusAdapter 130 - 150 - 350 Pg. 33
Modem Modem GSM/GPRS Pg. 34
Memory for fast configuration and updating of controllers Unicard - USB Copy Card - Copy Card - Multi Function Key Pg. 35
Drip protection for 32x74 controllers Drip protection Pg. 36
Transformers TF Transformers Pg. 37
Panel switches for ID and IC series Panel switches for ID and IC series Pg. 38
PROBES AND TRANSDUCERS Pg. 39
NTC semi-conductor temperature probes NTC Pg. 40
Special NTC semi-conductor temperature probes Special NTC probes - TC Pg. 41
Pt100 - Pt1000 thermo-resistive temperature probes Pt100 - Pt1000 probes Pg. 42
PTC semi-conductor temperature probes PTC Probes Pg. 43
Pressure transducers EWPA 007 - 030 - 050 Pg. 44
Ratiometric pressure transducers EWPA 010 - 030 - 050 Pg. 45
Humidity probes EWHS 284 - 304 - 314 Pg. 46
APPENDIX Pg. 47
Temperature probe tables NTC probe table Pg. 47
NTC probe table - Extended range Pg. 47
PTC probe table Pg. 47
Pt100 probe table Pg. 48
Pt1000 probe table Pg. 48
TCJ probe table Pg. 49
TCK probe table Pg. 49
6
ELECTRONIC CONTROLS
Eliwell supplies products and solutions that are distinguished by high quality and reliability, the fruit of more than 25 years of experience and of collaboration with the leading manufacturers of appliances that need temperature, humidity and pressure regulators.
The vast range of formats that Eliwell has developed always enables the most suitable solution to be found for any specific application requirements.
Eliwell products are characterised by:
• Reliability
• Simplicity
• Energy saving
• Minimum environmental impact
7
• NTC probe: -50.0...110.0°C• PTC probe: -50.0...140.0°Cno decimal point * 3 and a half digits + sign1 PTC or NTC *not availableTTL port for connection to USB Unicard, TelevisSystem and systems with ModBus protocol1 SPDT 8(4)A 250V~from -50 to 140better than 0.5% of end of scale+1 digit 0.1 or 1°C• 3W for 12…24V~ model• 3W for 230V~ model• 12V~/12..24V~/24V~ ±10% 50/60Hz• 110...115V~/220...230V~±10% 50/60Hz
ICPlus 90232x74 cold/hot thermostats
Common featuresContainer PC+ABS UL94 V-0 plastic resin casing, polycarbonate window, thermoplastic resin keysDimensions front panel 74x32 mm, depth 59 mmInstallation panel mounting with 71x29 mm (+0.2/–0.1 mm) drilling template
Operating temperature -5...55°CStorage temperature -30...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Electronic Controllers 32x74 cold/hot thermostats ICPlus 902
Codes Description Probe Power supplyICP11D0750000 ICPlus 902 NTC-PTC 230V NTC-PTC 230V~ICP11D0450000 ICPlus 902 NTC-PTC 12/24V~/C NTC-PTC 12...24V~
Applications
Technical data ICPlus 902 NTC/PTC
Wiring diagrams
ICPlus 902 controllers are one-step electronic devices, used for the control of temperature. They are compatible with TelevisSystem and with ModBus protocol monitoring systems.
Display range:
Display:
Analogue inputs:Digital inputs:Connections:Digital outputs:Measurement range:Accuracy:
Resolution:Power consumption:
Power supply:
* (selectable by parameter).
ICPlus 902 V/I
230V~
Pb1out1
out1
230V~
12/24Va/c
230V~
12/24Va/c
+-
+12VI
V +-
+-
+12VI
V +-
Pb1
230V~
out1-+
-+
ICPlus 902 NTC/PTC
230V~
12/24Va/c
230V~
out1 Pb1
Pb1 out1out1
TTL TTL TTL
12/24Va/c 12/24Va/c
ICPlus 902 TcJ-TcK/Pt100
12/24Va/c
8
• NTC probe: -50.0...110.0°C• PTC probe: -50.0...140.0°C
no decimal point * 3 and a half digits + sign1 PTC or NTC *1 clean contact at extra low safety voltageTTL port for connection to USB Unicard, TelevisSystem and systems with ModBus protocol1 SPDT 8(4)A 250V~ +1 SPST 8(4)A 250V~from -50 to 140better than 0.5% of end of scale+1 digit
0.1 or 1°C
• 3W for 12…24V~ model• 3W for 230V~ model• 12V~/12...24V~/24V~ ±10% 50/60Hz• 115V~/230V~ ±10% 50/60Hz
• Pt100 probe: -150...650°C• TcJ probe: -40...750°C• TcK probe: -40...1350°Cno decimal point *3 and a half digits + sign1 Pt100 or 1 TcJ/TcK 1 clean contact at extra low safety voltageTTL port for connection to USB Unicard, TelevisSystem and systems with ModBus protocol1 SPST 8(4)A 250V~ +1 SPST 8(4)A 250V~from -150 to 1350Pt100: 0.5% for whole scale + 1 digit, 0.2% from -150 to 300°CTcJ: 0.4% for whole scale + 1 digitTcK: 0.5% for whole scale + 1 digit, 0.3% from -40 to 800°CPt100: 0.1°C (0.1°F) up to199.9°C, 1°C (1°F) overTcJ: 0.1°C (0.1°F) up to 199.9°C (1°F) overTcK: 0.1°C (0.1°F)• 3W for 12…24V~ model• 3W for 230V~ model• 12V~/12...24V~/24V~ ±10% 50/60Hz• 115V~/230V~ ±10% 50/60Hz
• -199...199 *• -199.9...199.9 *• -1999...1999 *no decimal point * 3 and a half digits + sign1 V-I (0...1V,0...5V,0...10V,0...20mA,4...20mA)*not available
TTL port for connection to USB Unicard, TelevisSystem and systems with ModBus protocol1 SPDT 8(4)A 250V~ +1 SPST 8(4)A 250V~ from -999 to 1000better than 0.5% of end of scale+1 digit
0.1 or 1°C
• 3W for 12…24V~ model• 3W for 230V~ model• 12V~/12...24V~/24V~ ±10% 50/60Hz• 115V~/230V~ ±10% 50/60Hz
ICPlus 91532x74 cold/hot thermostats
Common features
Applications
Container PC+ABS UL94 V-0 plastic resin casing, polycarbonate window, thermoplastic resin keysDimensions front panel 74x32 mm, depth 59 mmInstallation panel mounting with 71x29 mm (+0.2/–0.1 mm) drilling template
Operating temperature -5...55°CStorage temperature -30...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Technical data ICPlus 915 NTC/PTC ICPlus 915 V/I ICPlus 915 TC/Pt100
ICPlus 915 V/IPb1
230Va
12/24Va/c
ICPlus 915 TcJ-TcK/Pt100
230Va
12/24Va/c
+-
+12VI
V +-
+-
+12VI
V +-
Pb1
230Va
out1ICPlus 915 NTC/PTC
12/24Va/c 12/24Va/c
230Va
12/24Va/c
230Va
out1 out2
out2out1
230Va
out1 out2
out2out1
out2
out1 out2 DI1
-+
-+
DI1
DI1Pb1
DI1Pb1TTL TTL TTL
12/24Va/c
Wiring diagrams
ICPlus 915 controllers are two-step electronic devices, either dependent or independent or with neutral zone, used for the control of temperature, relative humidity and pressure. They are compatible with TelevisSystem and with Modbus protocol monitoring systems.
Electronic controls 32x74 cold/hot thermostats ICPlus 915
Codes Description Probe Power supplyICP22JI750000 ICPlus 915 J/K PT100 230V J/K PT100 230V~ICP22JI450000 ICPlus 915 J/K PT100 12/24V~/C J/K PT100 12...24V~ICP22DI750000 ICPlus 915 NTC-PTC 230V NTC-PTC 230V~ICP22DI450000 ICPlus 915 NTC-PTC 12/24V~/C NTC-PTC 12...24V~ICP22I0750000 ICPlus 915 V/I 230V V/I 230V~ICP22I0450000 ICPlus 915 V/I 12/24V~/C V/I 12...24V~
Display range:
Display:
Analogue inputs:Digital inputs:
Connections:
Digital outputs:
Measurement range:Accuracy:
Resolution:
Power consumption:
Power supply:
* (selectable by parameter).
9
Codes Description Probe* Power supplyIC12DI0TMD700 IC 917/PID NTC/PTC 230V~IC12ZI0TMD700 IC 917/PID TC/Pt100 230V~IC1RDI0TMD700 IC 917/PID SSR NTC/PTC 230V~IC1RZI0TMD700 IC 917/PID SSR TC/Pt100 230V~IC1TZI0TMD700 IC 917/PID SSR/RELÈ TC/Pt100 230V~* probe not included
IC 917/PID (SSR)PID 32x74 cold/hot thermostats
Applications
Common featuresContainer PC+ABS UL94 V-0 plastic resin casing, polycarbonate
display window, thermoplastic resin buttonsDimensions front panel 74x32 mm, depth 59 mm Installation panel mounting with 71x29 mm (+0.2/–0.1 mm)
drilling template
Operating temperature -5...55°CStorage Temperature -30...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)Soft Start Function present
IC 917/PID controllers are electronic two-step devices, either dependent or independent, with ON/OFF action, PD, PID, Soft Start function and Autotuning.
Technical data• NTC probe: -50.0...110.0°C• PTC probe: -55.0...140.0°C
3 and a half digits + sign1 PTC or NTC *1 clean contact at extra low safety voltageTTL port for connection to Copy Card1 SPDT 8(3)A 1/2hp 250 V~ • 1 SPST 8(3)A 1/2hp 250 V~SSR models: please see wiring diagramfrom -55 to 140°Cbetter than 0.5% of end of scale+1 digit
0.1°C (0.1°F) up to 199.9°C, 1°C (1°F) over
• 1.5W for 12 V~ model• 3W for 230 V~ model• 12 V~/c ±10% 50/60 Hz• 230 V~ ±10% 50/60 Hzoptional
• Pt100 probe: -150...650°C• TcJ probe: -40...750°C• TcK probe: -40...1350°C3 and a half digits + sign1 Pt100 or 1 TcJ/TcK*1 clean contact at extra low safety voltageTTL port for connection to Copy Card2 SPST 8(3)A 1/2hp 250 V~SSR models: please see wiring diagramfrom -150 to 1350°CPt100: 0.5% for whole scale + 1 digit, 0.2% from -150 to 300°CTcJ: 0.4% for whole scale + 1 digitTcK: 0.5% for whole scale + 1 digit, 0.3% from -40 to 800°CPt100: 0.1°C (0.1°F) up to 199.9°C, 1°C (1°F) overTcJ: 0.1°C (0.1°F) up to 199.9°C, (1°F) overTcK: 0.1°C (0.1°F)• 1.5W for 12 V~ model• 3W for 230 V~ model• 12 V~/c ±10% 50/60 Hz• 230 V~ ±10% 50/60 Hzoptional
IC 917/PID NTC/PTC (SSR) IC 917/PID TC/Pt100 (SSR)Display range:
Display:Analogue inputs:Digital inputs:Connections:Digital outputs:
Measurement range:Accuracy:
Resolution:
Power consumption:
Power supply:
Alarm:*(selectable by parameter)
Electronic Controllers PID 32x74 cold/hot thermostats IC 917/PID (SSR)
Wiring diagrams
IC 917 Pt100/TC
230Va
12Va/c1 2 4 5
1 2 4 5 6 7
IC 917 NTC-PTC
230Va
12Va/c1 2 3 4 5
- -++
1 2 3 4 5 6 7 8 9 10 11
Supply Supply
Supply
OUT1 Pb1
6 7 8 9 10 11
OUT2 OUT1 OUT2
OUT1 OUT2
OUT2OUT1 OUT2OUT1Pb1
6 7
Supply
10 11 12
-+
-+
10 11 12
-+
SSRModels
SSRModels
8 9
8 9
D.I.
D.I.
D.I.
D.I.
1 2 3 4
TTL TTL
-
+ -
+OUT1
OUT2
1 2 4
SSR Models/Relay
-+OUT1
1 2 4 5 6 7 8 9
D.I.
Supply
SSR Outputs Version HV 230Va1 SSR (500Ω) VOUT= 11.3 V; IOUT= 22.6 mA (3kΩ) VOUT= 16.2 V; IOUT= 5.4 mA2 SSR (2x500Ω) VOUT= 10.6 V; IOUT= 21.2 mA (2x3kΩ) VOUT= 15.8 V; IOUT= 5.3 mA
Version LV 12Vc1 or 2 SSR (500Ω) VOUT= 7.7 V; IOUT= 15.4 mA1 or 2 SSR (3kΩ) VOUT= 9.9 V; IOUT= 3.3 mA
Version LV 12Va1 or 2 SSR (500Ω) VOUT= 10.7 V; IOUT= 21.4 mA1 or 2 SSR (3kΩ) VOUT= 13.9 V; IOUT= 4.6 mA
OUT2
10 11 12 13
10
EM300 LXTemperature, humidity, pressure indicators
Common features
Applications
Container PC+ABS UL94 V-0 plastic resin casing, polycarbonate display window, thermoplastic resin buttons
Dimensions front panel 32x74 mm, depth 30 mm (no terminals); ‘switching’ models: depth 59 mm
Installation panel mounting with 71x29 mm (+0.2/–0.1 mm) drilling template
Operating temperature -5...55°CStorage temperature -30...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Technical data• NTC probe: -50.0... 110.0°C• PTC probe: -55.0... 140.0°C
no decimal point *3 and a half digits + sign1 NTC or PTC *
from -55 to 140°Cbetter than 0.5% of end ofscale + 1 digit
1 or 0.1°C
• 230 V~ model: 1.8 W max• 12 V~model: 0.5 W max• 12...24 V~model: 3 W max• 230 V~ ±10% 50/60 Hz• 12 V~ ±10% 50/60 Hz• 12...24 V~/c ±10% 50/60 HzTTL port for connection toCopy Card and TelevisSystem
• -99... 100 *• -99.9... 100.0 *• 999... 1000 *no decimal point *3 and a half digits + sign1 voltage input (0-1 V, 0-5 V, 0-10 V)1 current input (0-20 mA, 4-20 mA)from -999 to 1000better than 0.5% of end ofscale + 1 digit
1 or 0.1°C
• 230 V~ model: 1.8 W max• 12 V~model: 0.5 W max
• 230 V~ ±10% 50/60 Hz• 12 V~/c ±10% 50/60 Hz
TTL port for connection toCopy Card and TelevisSystem **
• Pt100 probe: -200...800°C• TCJ probe: -40...760°C• TCK probe: -40...1350°Cno decimal point *3 and a half digits + sign
Pt100: 0.5% / 0.2% from -150 a 300°CTCJ: 0.4%TCK: 0.5% / 0.3% from -40 a 800°CPt100: 0.1°C up to 199.9, 1°CTCJ and TCK: 1°C • 230 V~ model: 1.8 W max• 12 V~model: 0.5 W max• 12...24 V~model: 3 W max• 230 V~ ±10% 50/60 Hz• 12 V~ ±10% 50/60 Hz• 12...24V~/12...36VC ±10% 50/60Hz
TTL port for connection toCopy Card and TelevisSystem **
EM300 LX PTC/NTC EM300 LX V/I EM300 LX Pt100/TCJ/TCK
1 2 3 4
EM300(LX) - 12 Va
5
Pb1
3 4 5
EM300(LX) - 230 Va
+
+12V
3 4 5
V
1 2 3 4
EM300(LX) - 12-24 Va
5
Pb1
3 4 5 3 4 5
EM300(LX) - 12-36 Vc
+ -
Only in LX models Only in LX models
PowerSupply
NTC/PTC V
+
+12V
3 4 5
I
I
3 4 5
+ -
Pt100/TC NTC/PTC Pt100/TC
PowerSupply
--
Wiring diagrams
The EM300 LX is a device for measuring temperature, humidity and pressure in commercial refrigeration and industrial applications.
Electronic Controllers Temperature, humidity, pressure indicators EM300 LX
Display range:
Display:
Analogue inputs:
Measurement range:Accuracy:
Resolution:
Power consumption:
Power supply:
Connections:
* (selectable by parameter). ** use BusAdapter350
Codes Description Probe Power supplyTM10D00X0D700 EM300 LX NTC 230V~TM10Z00X0M700 EM300 LX PT100/TC 230V~TM10I00X0M700 EM300 LX I 4...20mA 230V~ TM10Z00X0M400 EM300 LX PT100/TC 12...24V~/12...36VC TM10D00X0D300 EM300 LX NTC 12V~TM10I00X0M300 EM300 LX I 4...20mA 12V~
11
44,5
48
28,6
13,5
25
11,3
EWTL 300
58
62
30
19
26
EWTL 310DST-30
EWTL 300 - EWTL 310 - DST-30LCD thermometers
Common features
Applications
Codes Description Probe cable length
Installation panel-mounted
Dimensions
The EWTL 300/310 is a range of LCD digital temperature gauges with temperature probes connected to the instrument via a cable of length 1.5, 2 or 3 metres.DST-30 is a solar-cell thermometer specifically designed for refrigerated counters and display units.
Electronic Controllers LCD thermometers EWTL 300 - EWTL 310 - DST-30
Technical dataLCD with 2 and 1/2 digits1 or 0.1°C±1°C from 0 to 40°Cconnected to instrument, cable length 1.5 m10 seconds-20...70°Cfront panel 48x28.6 mmdepth 13.5 mmone 1.5 V LR 44 battery or equivalent - duration 12 months
LCD with 2 and 1/2 digits1 or 0.1°Cbetter than 0.5% of end of scaleconnected to instrument, cable length 0.5 m, 1 m, 2 m or 3 m12 seconds-20...70°Cfront panel 62x30 mmdepth 19 mmone 1.5 V LR 44 battery or equivalent - duration 12 months
24x14 mm LCD0.1°C±1°Cconnected to instrument, cable length 1 m
-20...80°Cfront panel 66x30 mmdepth 11.6 mmintegrated solar cells
IP68
EWTL 300 EWTL 310 DST-30Display:Resolution:Accuracy:Probe:
Updating display:Display range:Dimensions:
Power supply:
Enclosure rating:
T1M1BT0100 (A) EWTL 300 1,5mT1M1BT0101 (B) EWTL 310 1,5mT1M1BT0105 (C) DTS-30 1m
(B)
(C)
(A)
12
32x74 timers and counters
Common features
Applications
Codes Description Power supply
Container PC+ABS UL94 V-0 plastic resin casing, polycarbonate display window, thermoplastic resin buttons
Dimensions front panel 32x74 mm, depth 59 mm Installation panel mounting with 71x29 mm (+0.2/–0.1 mm)
drilling template
Operating temperature -5...55°CStorage Temperature -30...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Technical data9999 hours / 99 hours and 59 minutes / 99 minutes and 59 seconds / 99 seconds and 99 hundredths of a secondno decimal point * 4 digits + sign2 clean contacts at extra low safety voltageTTL port for connection to Copy Card and TelevisSystem1 SPDT 8(3)A 1/2hp 250 V~
3.6 sec/h3 VA max12 V~/c or 230 V~ ±10% 50/60 Hz• power supply 9 Vc
• battery duration: based on model, with 9 Vc /10 mA/h battery duration 1h• instrument absorption with power supply from 10 mA battery
9999 hours / 99 hours and 59 minutes / 99 minutes and 59 seconds / 99 seconds and 99 hundredths of a secondno decimal point * 4 digits + sign2 clean contacts at extra low safety voltageTTL port for connection to Copy Card and TelevisSystem1 SPDT 8(3)A 1/2hp 250 V~1 SPST 8(3)A 1/2hp 250 V~ 3.6 sec/h3 VA max12 V~/c or 230 V~ ±10% 50/60 Hz• power supply 9 Vc
• battery duration: based on model, with 9 Vc /10 mA/h battery duration 1h• instrument absorption with power supply from 10 mA battery
EWTS 950 LX EWTS 990 LX
Wiring diagrams
The Eliwell series of digital timers are the ideal measuring solution for use in commercial refrigeration and light industry. The range, which consists of 2 different models, can be used in all applications requiring precision control of processing stages and the management of functions linked to preset time intervals.
ET010I0XTT700 EWTS 950 LX 230 V~ET020I0XTT700 EWTS 990 LX 230 V~
Display range:
Display:Digital inputs:Connections:Digital outputs:
Accuracy:Power consumption:Power supply:External battery:
Electronic Controllers 32x74 timers and counters EWTS 950 LX - EWTS 990 LX
EWTS 950 LX - EWTS 990 LX
EWTS 950 LX
12Va
230Va
12Va1 2 3
1 2 3 8 9 10 11
out1 DI1
6 7 8 9 10 11
out1
+
DI2
DI1
+
DI2
EWTS 990 LX
12Va
230Va
12Va1 2 3 4 5
1 2 3 4 5
out1
6 7
230Va
6 7 8 9 10 11
out2
out2out1
8 9 10 11
DI1
+
DI2 9Vc
DI1
+
DI2 9Vc
9Vc
9Vc
6 7
230Va
13
Codes Description Probe* Power supplyE4D12E00BH710 DR4020 Pt100 100...240V~E4D12A00BD710 DR4020 TCJ 100...240V~E4D12I00BN710 DR4020 4...20mA 100...240V~E4D12N00BH710 DR4020 NTC 100...240V~E4D12V00BN710 DR4020 0...5V 100...240V~E4D12E00BH410 DR4020 Pt100 12...24V~/CE4D12A00BD410 DR4020 TCJ 12...24V~/CE4D12I00BN410 DR4020 4...20mA 12...24V~/CE4D12N00BH410 DR4020 NTC 12...24V~/CE4D12V00BN410 DR4020 0...5V 12...24V~/C* probe not included
DR4020Universal DIN controllers
Common features
Technical datano decimal point *2 4-digit displays + sign1 input* (see Probes table)not availableTTL port for connection to Copy Card and Unicard1 SPDT 8(3)A 250 V~1 SPST 8(3)A 250 V~ not availableaccording to probe usedaccording to probe usedaccording to probe used4W max• 12...24 V~/12...36 Vc ±10% 50/60 Hz• 100...240 V~ ±10% 50/60 Hz
DR4020
Wiring diagrams
ApplicationsThe new Eliwell thermoregulators in the Universal Controller series are ideal for all industrial applications requiring high precision temperature control.
Display:
Analogue inputs:Digital inputs:Connections:Digital outputs:
Analogue output:Measurement range:Accuracy:Resolution:Power consumption:Power supply:
*(selectable by parameter)
Electronic Controllers Universal DIN controllers DR4020
Container plastic casing with 4 DIN modulesDimensions front panel 70x85 mm, depth 61 mm Installation on DIN rail (Omega) or panel mounting,
with 70x45 mm (+0.2/-0.1 mm) drilling template
Operating temperature -5...55°CStorage Temperature -20...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Probes1 2
out2
out 1
22 23 2418 19 2113 14 15
12...24Va12...36Vc
out 1
22 23 2413 14 15
100...240Va
TTL
TTL
19 20 2112...24Va12...36Vc
100...240Va
DR4020
-+
NTCPt100
TC+ -
+12V
IV (0...5/0...10Vc)
+ -V
I (0...20/4...20mA)V (0...1Vc)
PTC/Pt1000
V+ -
222324 222324 222324
222324 22232421 222324
1 2
out2
out 1
22 23 2418 19 2113 14 15
12...24Va12...36Vc
out 1
22 23 2413 14 15
100...240Va
19 20 2112...24Va12...36Vc
100...240Va
DR4022
9876 10 11 125
- + +
IV
- + GND
RS-485D.I.
Probes1 2
out2
out 1
22 23 2418 19 2113 14 15
12...24Va12...36Vc
out 1
22 23 2413 14 15
100...240Va
TTL
TTL
19 20 2112...24Va12...36Vc
100...240Va
DR4020
-+
NTCPt100
TC+ -
+12V
IV (0...5/0...10Vc)
+ -V
I (0...20/4...20mA)V (0...1Vc)
PTC/Pt1000
V+ -
222324 222324 222324
222324 22232421 222324
1 2
out2
out 1
22 23 2418 19 2113 14 15
12...24Va12...36Vc
out 1
22 23 2413 14 15
100...240Va
19 20 2112...24Va12...36Vc
100...240Va
DR4022
9876 10 11 125
- + +
IV
- + GND
RS-485D.I.
14
Codes Description Probe* Power supplyE4D12EASBH710 DR4022 Pt100 100...240V~E4D12NASBH710 DR4022 NTC 100...240V~E4D12AASBD710 DR4022 TCJ 100...240V~E4D12IASBN710 DR4022 4/20ma 100...240V~E4D12VASBN410 DR4022 0...5V 12...24V~/C* probe not included
DR4022Universal DIN controllers with serial port
Common features
Technical datano decimal point * 2 4-digit displays + sign1 input* (see Probes table)1 clean contact at extra low safety voltageTTL port and internal RS-485 for connection to Copy Card, Unicard, TelevisSystem and ModBus protocol systems1 SPDT 8(3)A 250 V~1 SPST 8(3)A 250 V~V-I: 0...1 V, 0...5 V, 0...10 V / 0...20 mA, 4...20 mAaccording to probe usedaccording to probe usedaccording to probe used4W max• 12...24 V~/12...36 Vc ±10% 50/60 Hz• 100...240 V~ ±10% 50/60 Hz
DR4022
Wiring diagrams
ApplicationsThe new Eliwell thermoregulators in the Universal Controller series are ideal for all industrial applications requiring high precision temperature control.
Display:
Analogue inputs:Digital inputs:Connections:Digital outputs:
Analogue output:Measurement range:Accuracy:Resolution:Power consumption:Power supply:
*(selectable by parameter)
Container plastic casing with 4 DIN modulesDimensions front panel 70x85 mm, depth 61 mm Installation on DIN rail (Omega) or panel mounting,
with 70x45 mm (+0.2/-0.1 mm) drilling template
Operating temperature -5...55°CStorage Temperature -20...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Probes1 2
out2
out 1
22 23 2418 19 2113 14 15
12...24Va12...36Vc
out 1
22 23 2413 14 15
100...240Va
TTL
TTL
19 20 2112...24Va12...36Vc
100...240Va
DR4020
-+
NTCPt100
TC+ -
+12V
IV (0...5/0...10Vc)
+ -V
I (0...20/4...20mA)V (0...1Vc)
PTC/Pt1000
V+ -
222324 222324 222324
222324 22232421 222324
1 2
out2
out 1
22 23 2418 19 2113 14 15
12...24Va12...36Vc
out 1
22 23 2413 14 15
100...240Va
19 20 2112...24Va12...36Vc
100...240Va
DR4022
9876 10 11 125
- + +
IV
- + GND
RS-485D.I.
Electronic Controllers Universal DIN controllers with serial port DR4022
15
Codes Description Probe* Power supplyE481BI0XBH700 EW4820 4...20mA 100...240V~E481SI0XBN700 EW4820 SSR Output 4...20mA 100...240V~E481BP0PMH700 EW4820 Pt100 100...240V~E481SP0PMH700 EW4820 SSR Output Pt100 100...240V~E481BP0PMH400 EW4820 Pt100 12...24V~/CE481SP0PMH400 EW4820 SSR Output Pt100 12...24V~/C*probe not included
EW 4820 (SSR)Universal 48x48 controllers
Common features
Applications
Technical datano decimal point * 2 4-digit displays + sign1 input* (see Probes table)not availableTTL port for connection to Copy Card or TelevisSystem 1 SPDT 3A 250 V~1 SPST 2A 250 V~
not availableaccording to probe usedaccording to probe usedaccording to probe used• 2.45W 12...24 V~/12...36 Vc model• 2.40W for 100...240 V~model• 12...24 V~/12...36 Vc ±10% 50/60 Hz• 100...240 V~ ±10% 50/60 Hz
EW 4820 (SSR)
Wiring diagrams
The Eliwell thermoregulators in the Universal Controller series are ideal for all industrial applications requiring high precision temperature control, ranging from the moulding of plastic materials and packaging, to raw material transformation process control.
Electronic Controllers Universal 48x48 Controllers EW 4820 (SSR)
Container PC+ABS UL94 V-0 resin plastic casing, switch keys with adhesive polycarbonate film
Dimensions front panel 48x48 mm, depth 113 mm Installation panel-mounting, with 45x45 mm (+0.2/-0.1 mm)
drilling template
Operating temperature -5...55°CStorage Temperature -20...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Vout = 0...12 VC / Imax = 0...15 mA / Vmin = 7.5 V 1 SPST 2A 250 V~
Digital outputs - SSR models:
Display:
Analogue inputs:Digital inputs:Connections:Digital outputs:
Analogue output:Measurement range:Accuracy:Resolution:Power consumption:
Power supply:
*(selectable by parameter)
4321
321
out1
TTL
out1
5
9876
PowerSupply
+
-
out2
98
1098
10
98
10
-
+
PTC/NTC/Pt1000 Pt100 TC 10
++
−I
V98
10
V (0...1/0...5/0...10V)I (0...20/4...20mA)
EW4820
SSRModels
ProbesProbes
SeeProbes 4
321
321
out1
TTL
out1
5
9876
PowerSupply
+
-
out2
98
1098
10
98
10
-
+
PTC/NTC/Pt1000 Pt100 TC 10
++
−I
V98
10
V (0...1/0...5/0...10V)I (0...20/4...20mA)
EW4820
SSRModels
ProbesProbes
SeeProbes
16
EW4822 (SSR)Universal 48x48 controllers with serial port
Applications
Wiring diagrams
The Eliwell thermoregulators in the Universal Controller series are ideal for all industrial applications requiring high precision temperature control.
Codici Descr. Sonda* Alim.E481BIISBH700 EW4822 AO 4...20mA 4...20mA 100...240V~E481BPIQMH700 EW4822 AO 0...20mA Pt100 100...240V~E481BPVQMH700 EW4822 AO 0/10V Pt100 100...240V~E481SPIQMH700 EW4822 AO 0...20mA SSR Output Pt100 100...240V~E481BPIQMH400 EW4822 AO 0...20mA Pt100 12...24V~/CE481SPIQMH400 EW4822 AO 0...20mA SSR Output Pt100 12...24V~/C*probe not included
TTL
4321
out1
5
9876
10Power
Supply
out2EW4822
14131211
15
-
+GN
D
RS-485
0...1 V 20mA - minimum load resistance 50 Ω0...5 V 20mA - minimum load resistance 250 Ω0...10 V 20mA - minimum load resistance 500 Ω0...20mA 350 Ω4...20mA 350 Ω
1415
-
+
V - I
1415
D.I.
Outputs/D.I.
321
out1
+
-
SSRModels
Analogue outputs maximum pilotable loads
SeeOutputs/D.I.
SeeProbes 4
321
321
out1
TTL
out1
5
9876
PowerSupply
+
-
out2
98
1098
10
98
10
-
+
PTC/NTC/Pt1000 Pt100 TC 10
++
−I
V98
10
V (0...1/0...5/0...10V)I (0...20/4...20mA)
EW4820
SSRModels
ProbesProbes
SeeProbes
Electronic Controllers Universal 48x48 Controllers with serial port EW4822 (SSR)
Common featuresContainer PC+ABS UL94 V-0 resin plastic casing, switch keys
with adhesive polycarbonate filmDimensions front panel 48x48 mm, depth 113 mm Installation panel-mounting, with 45x45 mm (+0.2/-0.1 mm)
drilling template
Operating temperature -5...55°CStorage Temperature -20...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
no decimal point * 2 4-digit displays + sign1 input* (see Probes table)1 clean contact at extra low safety voltageTTL port for connection to Copy Card or TelevisSystem + internal RS-485 for connection to systems with ModBus protocol 1 SPDT 3A 250 V~1 SPST 2A 250 V~
V: 0...1 V, 0...5 V, 0...10 V or I: 0...20 mA, 4...20 mAmaximum pilotable loads: please see wiring diagramsaccording to probe usedaccording to probe usedaccording to probe used• 2.80W for 12...24 V~/12...36 Vc model• 2.60W for 100...240 V~model• 12...24 V~/12...36 Vc ±10% 50/60 Hz• 100...240 V~ ±10% 50/60 Hz
Vout = 0...12 VC / Imax = 0...15 mA / Vmin = 7.5 V1 SPST 2A 250 V~
Digital outputs - SSR models:
Technical data EW4822 (SSR)Display:
Analogue inputs:Digital inputs:Connections:Digital outputs:
Analogue output:
Measurement range:Accuracy:Resolution:Power consumption:
Power supply:
*(selectable by parameter)
17
EW7210 - EW7220Universal 72x72 controllers
Applications
1110
12
1110
12
1110
12
1110
12
PTC/NTC/Pt1000 Pt100 TC V (0...1/0...5/0...10V)I (0...20/4...20mA)
Probes
98 10 11 121 2 3
PowerSupply
Probes
Probes
out 1
EW7210
76 10 11 121 2 3
PowerSupply
12...24Va12...36Vc
100...240Va
out 1
++
−
I
V
98 10 11 121 2 3 4 5
PowerSupply
Probes
Probes
out 1 out 2
EW7220
76 10 11 121 2 3 4 5
PowerSupply
12...24Va12...36Vc
100...240Va
out 1 out 2
+
-
Wiring diagrams
The Eliwell thermoregulators in the Universal Controller series are ideal for all industrial applications requiring high precision temperature control.
Codes Description Probe* Power supplyE7211A0XHD700 EW7210 TC 100...240V~E7211E0XHD700 EW7210 Pt100 100...240V~E7211N0XHD700 EW7210 NTC 100...240V~E7211A0XHD400 EW7210 TC 12...24V~/=E7211E0XHD400 EW7210 Pt100 12...24V~/=E7211N0XHD400 EW7210 NTC 12...24V~/=E7212E0XBH700 EW7220 Pt100 100...240V~E7212A0XBD700 EW7220 TC 100...240V~E7212I0XBH700 EW7220 V/I 100...240V~E7212N0XBD700 EW7220 NTC/PTC/Pt1000 100...240V~E7212E0XBH400 EW7220 Pt100 12...24V~/CE7212A0XBD400 EW7220 TC 12...24V~/CE7212I0XBH400 EW7220 V/I 12...24V~/CE7212N0XBD400 EW7220 NTC/PTC/Pt1000 12...24V~/C
* probe not included
Technical data EW7210 EW7220Display: no decimal point *
2 4-digit displays + signno decimal point * 2 4-digit displays + sign
Analogue inputs: 1 input*(see Probes table) 1 input* (see Probes table)
Digital inputs: not available not available
Connections: TTL port for connection to Copy Card, TelevisSystemor systems with ModBus protocol
TTL port for connection to Copy Card, TelevisSystemor systems with ModBus protocol
Digital outputs: 1 SPDT 8(3)A 250V~ 1 SPDT 8(3)A 250V~1 SPST 8(3)A 250V~
Analogue output: not available non disponibile
Measurement range: according to probe used according to probe used
Accuracy: according to probe used according to probe used
Resolution: according to probe used according to probe used
Power consumption: 4W max 4W max
Power supply: • 12...24V~/12...36VC ±10% 50/60Hz• 100...240V~ ±10% 50/60Hz
• 12...24V~/12...36VC ±10% 50/60Hz• 100...240V~ ±10% 50/60Hz
*(selectable by parameter)
Common featuresContainer PC+ABS UL94 V-0 resin plastic casing, switch keys
with adhesive polycarbonate filmDimensions front panel 72x72 mm, depth 80 mm Installation panel mounting with 67x67 mm (+0.2/–0.1 mm)
drilling template
Operating temperature -5...55°CStorage Temperature -20...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Electronic Controllers Universal 72x72 controllers EW7210 - EW7220
18
1110
12
1110
12
1110
12
1110
12
+
-PTC/NTC/Pt1000 Pt100 TC V (0...1/0...5/0...10V)
I (0...20/4...20mA)
Probes
Probes
Probes
98 10 11 121 2 3 4 5
PowerSupply
76 10 11 121 2 3 4 5
PowerSupply
21201918 22 23 2414 15 17
- + +
IV
- + GND
RS-485out3D.I.
out 1 out 2
out 1 out 2
EW7222
++
−
I
V
12...24Va12...36Vc
100...240VaProbes
Probes
98 10 11 121 2 3 4 5
PowerSupply
76 10 11 121 2 3 4 5
PowerSupply
2120191814 15 17
- + +
IVout3D.I.
out 1 out 2
out 1 out 2
EW7221
12...24Va12...36Vc
100...240Va
Wiring diagrams
EW7221 - EW7222Universal 72x72 controllers with serial port
ApplicationsThe Eliwell thermoregulators in the Universal Controller series are ideal for all industrial applications requiring high precision temperature control.
Codes Description Probe* Power supplyE7213PAXBH700 EW7221 Univ. Pt100 100...240V~E7213IAXBH700 EW7221 4...20mA 100...240V~E7213PAXBD700 EW7221 Univ. - RS485 Pt100 100...240V~E7213PAXBH400 EW7221 Univ. Pt100 12...24V~/CE7213PASBH700 EW7222 Univ.-RS485 Pt100/TC/PTC/NTC/Pt1000 100...240V~E7213IASBH700 EW7222 Pt100/V/I 100...240V~E7213PASBH400 EW7222 Univ.-RS485 Pt100/TC/PTC/NTC/Pt1000 12...24V~/C
* probe not included
Technical data EW7221 EW7222Display: no decimal point *
2 4-digit displays + signno decimal point * 2 4-digit displays + sign
Analogue inputs: 1 input* (see Probes table) 1 input* (see Probes table)
Digital inputs: 1 clean contact at extra low safety voltage 1 clean contact at extra low safety voltage
Connections: TTL port for connection to Copy Card, TelevisSystemor systems with ModBus protocol
TTL port and internal RS-485 for connection to Copy Card, TelevisSystem or systems with ModBus protocol
Digital outputs: 1 SPDT 8(3)A 250V~1 SPST 8(3)A 250V~1 SPST 5A 250V~
1 SPDT 8(3)A 250V~1 SPST 8(3)A 250V~1 SPST 5A 250V~
Analogue output: V-I: 0...1V, 0...5V ,0...10V / 0...20mA, 4...20mA V-I: 0...1V, 0...5V ,0...10V / 0...20mA, 4...20mA
Measurement range: according to probe used according to probe used
Accuracy: according to probe used according to probe used
Resolution: according to probe used according to probe used
Power consumption: 4W max 4W max
Power supply: • 12...24V~/12...36VC ±10% 50/60Hz• 100...240V~ ±10% 50/60Hz
• 12...24V~/12...36VC ±10% 50/60Hz• 100...240V~ ±10% 50/60Hz
*(selectable by parameter)
Common featuresContainer PC+ABS UL94 V-0 resin plastic casing, switch keys
with adhesive polycarbonate filmDimensions front panel 72x72 mm, depth 80 mm Installation panel mounting with 67x67 mm (+0.2/–0.1 mm)
drilling template
Operating temperature -5...55°CStorage Temperature -20...85°CAmbient humidity for operation and storage 10...90% RH (non-condensing)
Electronic Controllers Universal 72x72 controllers with serial port EW7221 - EW7222
19
Electronic Controllers Programmable platform FREE Way
FREE WayProgrammable platform
ApplicationsEliwell's new programmable platformFREE Way: Eliwell's new approach to programmability, giving customers the tools to fi nd their own faster and more effective solutions.
FREE Way is the new programmable platform from Eliwell, consisting of the FREE Studio software suite, FREE Smart, FREE Panel and FREE Evolution, the new range of programmable controllers available in various formats to choose from.
The simple and fl exible FREE Studio software suite is compatible with the 5 standard programming languages (IEC61131-3), and is structured to manage a whole range of controllers of different sizes and with varying levels of complexity, in order to fully satisfy the customer's system customization requirements.
FREE Smart features • User interface with confi gurable keys
• Available in three formats
• FREE Smart SMP* 32x74mm
• FREE Smart SMD* 4 Din with LED display
• FREE Smart SMC* 4 Din with no display
* Electrical connections compatible with existing Eliwell product platforms (e.g. Energy Flex); versions available 100...240V~
• Can be connected to RS-485, Modbus RTU
• Can be connected to standard Eliwell peripherals and user interfaces
FREE Panel features• FREE Panel EVP system controller, with gateway functions
and backlit LCD graphic display
• High connectivity: integrates into industrial systems and BMS
• Connects to standard Eliwell or third-party peripheral devices
• Available for panel or wall mounting
FREE Evolution features• Fully customizable graphic user interface
• Available in two formats
• FREE Evolution EVD 8 Din with backlit LCD graphic display
• FREE Evolution EVC 8 Din with no display
• High connectivity: integrates into industrial systems, BMS and networks using dedicated plug-in modules
• Connects to standard Eliwell peripheral devices (including FREE Smart)
• Connects to standard third-party peripheral devices
FREE Studio features• Quick and easy programming
• Single software suite
• Complete and effective online help
• Advanced debugging and simulation options
• Protection of the applications and Different levels of use
• Application revision log
• Interfaccia personalizzabile
20
Wiring diagram
160x96x10mm panel (°) IP65backlit 128x64 pixel LCD graphic display24V~/c - 48Vc
AI1 1 x NTC on boardAI2 1 x NTC / D.I. remoteAI4 1 x %RH on boardCANOpen / RS485 / ETHERNETYES
160x96x10mm panel (°) IP65backlit 128x64 pixel LCD graphic display24V~/c - 48Vc
AI1 1 x NTC on boardAI2 1 x NTC / D.I. remoteAI3 1 x 4...20 mA / 0-5V / 0-10V remoteCANOpen / RS485 / ETHERNETYES
Electronic Controllers Programmable platform
FREE StudioProgrammable platform
Programmable platform
ApplicationsThe FREE Studio software suite is compatible with all 5 standard programming languages (IEC61131-3).Each project may consist of several programs. The developer may use one or more languages in the same project.
Each new programme can be chosen from the 5 programming languages, 2 text and 3 graphic:• ST, Structured Text• FBD, Functional Block Diagram• LD, Ladder• IL, Instruction List• SFC, Sequential Function Chart
ApplicationComponent for software developers to allow them
to develop and modify applications in the 5 standard
programming languages
DeviceComponent dedicated to
less skilled users for the management
of parameters, application downloads, fi eld tests, etc.
ConnectionNetwork confi guration
component, for both fi eld and open networks in
order to integrate other systems.
User InterfaceComponent for developing
and personalizingthe graphic interface on
user terminals.
SimulationComponent for simulating
the application on a PC.
FREE Panel
Codes DescriptionEVP3300010B00 EVP3300/CEVP3500010B00 EVP3500/C/RH
ApplicationFREE Panel (EVP) is the panel solution, with an LCD display that can be used as a system controller, with the function of a gateway, used in association with the other FREE Evolution and FREE Smart or third-party controllers.FREE Panel ensures high performance in terms of memory, connectivity and user interface as well as straightforward programming, maintenance and servicing.FREE Panel is designed for panel mounting: a special backplate, available as an accessory, enables it to be wall mounted. Confi dentiality with appropriate protection.
Technical data EVP3300/C EVP3500/C/RHFormat:Display:Power supply:Analogue inputs 3
Connectivity:Buzzer:
IEC61131-3 DEVELOPMENTSOFTWARE
Application Device Connection User Interface Simulation
FREE Studio - FREE Panel
RS485 CAN+ - GS
24 Va/c48 Vc
RS485 CAN
GS H LEthernet
RemoteProbes
AI2 AI3 G
RTERM
EVP3500/C/RHEVP3300/C
AI4RH Sensor Built-in
AI1NTC Sensor Built-in
AI1
AI1 AI4
AI2 AI3
AI2
EVP3300
EVP3500
Probes
Built-in RemotePOWER
21
FREE SmartProgrammable platform
The models are available as a DIN rail-mounted version (SMD with display, SMC with no display), which saves time in terms of wiring, and in the compact 32x74 Eliwell (SMP) size for panel-mounting. Eliwell supplies various expansion modules (SE, SME) and terminals (SKP, SKW) for use in conjunction with the corresponding models in the FREE Smart range. All inputs and outputs are independent and confi gurable, meaning they can be adapted to fi t any system.
Code Model Digitaloutputs (*)
TRIACoutputs (*)
O.C. outputsPWM / PPM
(**)
Analogueoutputs
(**)
Digitalinputs(***)
Analogueinputs
(**)
O.C.outputs
FREE Smart 12...24V~ • /M models Modbus Master • /S models integrated RS485•/C indicates that there is an RTC – Real Time Clock
SMP5500050400 SMP5500/C/S 5 - 2 3 6 5 1
SMP4600050400 SMP4600/C/S 4 1 2 3 6 5 1
SMD550005M400 SMD5500/C/S/M 5 - 2 3 6 5 1
SMD5500050400 SMD5500/C/S 5 - 2 3 6 5 1
SMD4600050400 SMD4600/C/S 4 1 2 3 6 5 1
SMD3600050400 SMD3600/C/S 3 2 1 3 6 5 2
SMC5500050400 SMC5500/C/S 5 - 2 3 6 5 1
SMC4600050400 SMC4600/C/S 4 1 2 3 6 5 1
SMC3600050400 SMC3600/C/S 3 2 1 3 6 5 2
Expansion modules 12...24V~
SE63020310400 SE632 3 - 2 - 6 3 1
SE64123510400 SE646 4 1 2 3 6 5 1
SE65023510400 SE655 5 - 2 3 6 5 1
Code Model Digitaloutputs (*)
O.C. Outputs:PWM / DI (**)
0-10VOutputs(**)
4..20mA / 0…20mA
Outputs (§)
Analogueinputs
(**)
FREE Smart 4500 100-240V~ • /M models Modbus Master • /S models integrated RS485•/C indicates that there is an RTC – Real Time Clock
SMD450005MH00 SMD4500/C/S/M 4 2 2 1 5
SMD4500050H00 SMD4500/C/S 4 2 2 1 5
SMC4500050H00 SMC4500/C/S 4 2 2 1 5
Expansion module 4500 100-240V~
SME4500000H00 SME4500 4 2 2 1 5
Code Model Mounting Dimensions Display Analogue inputs (**) Power supply
Terminali
SKP1000000000 SKP10 panel 74x32x30mm LED / 4 digit - from base board
SKW2200000000 SKW22wall 137x96.5x31.3mm
LCD 1 integrated NTCfrom base board
SKW22L0000000 SKW22L Backlit LCD1 NTC/
DI/4...20mA input
SKP2200000000 SKP22panel(°) 160x96x10mm
LCD 1 NTC inputfrom base board
SKP22L0000000 SKP22L Backlit LCD1 NTC/
DI/4...20mA input
(*) high voltage (**) low voltage (SELV: SAFETY EXTRA LOW VOLTAGE)(***) no voltage • (§) or 0-10V on dedicated model(°) Contact the Eliwell Sales Offi ce for wall-mounting accessoriesPPM Pulse Position Modulation • PWM Pulse Width ModulationTTL supplied as standard • OC Open Collector^ check availability with the Eliwell Sales Offi ce
Applications
Electronic Controllers Programmable platform FREE Smart
22
FREE EvolutionProgrammable platform
ApplicationsThe models (EVD with display, EVC with no display) are available in the version with 8 DIN rail mounting, with screw terminals that can be disconnected to make installation easier and faster. Eliwell supplies models with relay or SSR outputs. Each model (EVD, EVC) can be connected to 12 expansion modules (EVE) via CANOpen or RS485 serial ports.
Code Model Relayoutputs (*)
SSRoutputs
(§)
Analogueoutputs
(**)
Digitalinputs
(**)
Digitalinputs(***)
Analogueinputs
(**)
IntegratedRS485 /MPBUS
FREE Evolution with display • /C indicates that there is an RTC – Real Time Clock • CANOpen integrated as standard
EVD7500060B00 EVD7500/C/U 7 - 5 8 1 6 RS485
EVD7500010B00 EVD7500/C 7 - 5 8 1 6 RS485
EVD75SS060B00 EVD75SS/C/U^ 5 2 5 8 1 6 RS485
EVD75SS010B00 EVD75SS/C^ 5 2 5 8 1 6 RS485
EVD75MP060B00 EVD75MP/C/U^ 7 - 5 8 1 6 MPBUS
EVD75MP010B00 EVD75MP/C^ 7 - 5 8 1 6 MPBUS
FREE Evolution without display • /C indicates that there is an RTC – Real Time Clock • CANOpen, integrated as standard
EVC7500060B00 EVC7500/C/U 7 - 5 8 1 6 RS485
EVC7500010B00 EVC7500/C 7 - 5 8 1 6 RS485
EVC75SS060B00 EVC75SS/C/U^ 5 2 5 8 1 6 RS485
EVC75SS010B00 EVC75SS/C^ 5 2 5 8 1 6 RS485
EVC75MP060B00 EVC75MP/C/U^ 7 - 5 8 1 6 MPBUS
EVC75MP010B00 EVC75MP/C^ 7 - 5 8 1 6 MPBUS
Expansion modules • RS485/CANOpen, integrated as standard
EVE7500000B00 EVE7500 7 - 5 8 1 6 RS485
Code Model Mounting Dimensions Display Serial
Terminals
EVK1000000B00 EVK1000 panel (°) 160x96x10mm LCD backlit CANOpen
Code Model Output (*) Mounting Serial Notes
Plug-in
EVS10R2000000 EVS RS232 1x5A 250V~
2DIN
RS232
Power Supplyfrom base board
EVS00R4000000 EVS RS485
-
RS485
EVS00CA000000 EVS CAN CANOpen
EVS00ET000000 EVS ETH ETHERNET
EVS00PB000000 EVS Profibus Profibus DP Slave-V0
Power supply 24V~/c - 48Vc excluding EVK1000 from the base(*) high voltage(**) low voltage (SELV: SAFETY EXTRA LOW VOLTAGE)(***) voltage free(°) Contact the Eliwell Sales Office for wall-mounting accessories(§) SSR Solid State RelayTTL as standard / OC Open Collector^ check availability with the Eliwell Sales Office
Electronic Controllers Programmable platform FREE Evolution
23
SUPERVISION AND MONITORING
Eliwell offers a wide range of instruments and components for the monitoring and remote management of a system.
The solutions we propose range from devices for data recording and temperature display in real time to software for the remote management of alarms and graphic display of systems.
24
Memory 1000Recording and printing temperature
Applications
Codes Description Temperature inputM1K04N03D1X00 MEMORY 1040 F* 4M1K04N03D0X00 MEMORY 1045 F 4M1K08N03D1X00 MEMORY 1080 F* 8M1K08N03D0X00 MEMORY 1085 F 8M1K26N03D1X00 MEMORY 1080 F 2AI* 8M1K26N03D0X00 MEMORY 1085 F 2AI 8M1K26N03D1X00 MEMORY 1180/15 F 2AI* 8M1K26N03D0X00 MEMORY 1185/15 F 2AI 8
RC444444 Thermal paper roll* models with printer
Memory 1000 is available in a wide range of models, combining the capabilities of a monitoring system with the ease-of-use of a data logger in order to meet various customer requirements.
Supervision and monitoring Recording and printing temperatures Memory 1000
Basic Models
Standard Models NTC probes
RS485 models
Standard Models NTC probes + 4...20mA Inputs
Common features
Powerful and easy to use thanks to:• fast data download on SD CARD, without using the PC• soft key to enter the report printing menu directlyCompatible with RadioAdapter wireless networks
Manages all aspects of network controller alarms12 months+ data logging capacityA wide range of models to fit all application requirementsUp to 10 digital and analogue inputs
Wiring diagrams
Technical dataBacklit graphic LCD8 polycarbonate keys• max 8 NTC / 4 NTC based on model• max 2 4...20 mA (just for models 2AI)2 fixed D.I. Max 8 / 4 configurable based on model1 SPDT 5(2)A 250 V~ RS-485 port for input expansion via compatible Eliwell Televis controllersRS-232 port for exporting data using Microsoft Windows® software (supplied)SD memory card slot for downloading datapresentpresent20W max (printer in use)230 V~ ±10% 50/60 HzIntegrated thermal printer
Backlit graphic LCD7 polycarbonate keys• max 8 NTC / 4 NTC based on model• max 2 4...20 mA (just for models 2AI)2 fixed D.I. Max 8 / 4 configurable based on model1 SPDT 5(2)A 250 V~RS-485 port for input expansion via compatible Eliwell Televis controllersRS-232 port for exporting data using Microsoft Windows® software (supplied)SD memory card slot for downloading datapresentpresent5W max230 V~ ±10% 50/60 Hz-
Memory 1000 with printer Memory 1000 without printerUser interface:
Analogue inputs:
Digital inputs:Digital outputs:Connections:
Clock:Buzzer:Power consumption:Power supply:Printer:
Accessories
Thermal paper rollRC444444Codes Description
25
TelevisGoMonitoring and maintenance systems via web
Supervision and monitoring Monitoring and maintenance systems via web TelevisGo
TelevisGo
SerialAdapter
RadioAdapter LanAdapter
LanAdapter
BusAdapterx2
ModBus ModBus
RS485
RS485
RS485
Ethernet
Features
Connectivity
ApplicationsTelevisGo is a family of devices to monitor, control and manage commercial refrigeration installations remotely. The product is based on a PC Embedded standard platform to offer greater calculation power, data filing space and, thanks to the Microsoft Embedded operating system, easy system expansion using widely available peripherals. TelevisGo is the monitoring system recommended for supermarkets with 30 or more controllers, up to a maximum of 224.
Technical Specificationsfrom web browser• Internet Explorer 7 or later• Mozilla Firefox 3.5 or later• Google Chrome 16.0.x or laterIT-EN-ES-DE-FR-RUMS Windows XP Embedded12 VC with external power supply100...240V~ ±10%10W max6 USB port2 RS-232 ports (for analogue modem or GSM)2 RS-232 ports (for SerialAdapter)1 Ethernet port (LANRJ45)VGA monitor connectionPS2 keyboard connector
TelevisGo 30 / 60 / 224User interface:Browsers supported:
User language interfaces pre-loaded:Operating System:Power supply:
Power consumption:Connections:
For the end user • recording of HACCP temperatures • information on energy consumption • complete, easy to use system • open, expandable systemFor the maintenance • compact, reliable, ready-to-use systemtechnician • intuitive user interface easy to learn • alarm signalled by e-mail, SMS and configurable
priorities • distance access via web for diagnostics and control • dedicated maintenance tools: parameters
instruments, controls, detailed diagnostics and recording of all operational status
• system fully updatable via web: software, languages, driver controllers
• instruments for off line configuration and fast modification of settings
For chains and system • solution scalability based on size of plantsintegrators • instruments for off line configuration, plant cloning
and series modification of configurations • Compatible with third party ModBus instruments:
energy measurement and HVAC controls • XML protocol open: - data sent periodically (push function) - sending on occurrence of data and alarms - acquisition of real-time data - interrogation of historical data and alarm base
- remote execution of controls / modification controller parameters
- SOCKS protocol integrated for routing of TCP and UDP communications
Codes Description ApplicationsTGOAXE301E00K KIT TelevisGo 30* up to 30 controllersTGOAXE601E00K KIT TelevisGo 60* up to 60 controllersTGOAXE2H0E000 KIT TelevisGo 224* up to 224 controllers*contains No.1 SerialAdapter + 1.5 m serial cable
26
Supervision and monitoring Monitoring and maintenance systems via web TelevisGo
TelevisGoMonitoring and maintenance systems via web
Graphic display of the plantTelevisGo offers an advanced user interface, for data analysis and full control of plant operations that is accessible from a web browser on a personal computer, tablet and mobile devices.
TelevisGo also has a graphic interface that the user can customise with a powerful drawing and configuration tool using pre-loaded, freely expandable symbol libraries.
The TelevisGo web interface makes information and controls easily accessible from a variety of devices.
Graphic interface configuration instrument
Through the Aggregated items you can create easily reusable interactive items
Drawing operations are speeded up by dragging and ‘copy and paste’ of items
The intelligent ‘copy and paste" of aggregated items makes it possible to quickly create tables with data, controls and parameters
A graphic page can be designed for a single controller and assigned to all similar ones
When displayed via the web, details of the associated resource are displayed automatically by passing the mouse over them
A symbol library, with typical supermarket elements is available and is easy to expand with jpeg, png, gif images, etc
you can create
dragging
The intelligent ‘copy and paste" of aggregated
of the
, with typical supermarket
Codes Description ApplicationsTGOAXE301E00K KIT TelevisGo 30* up to 30 controllersTGOAXE601E00K KIT TelevisGo 60* up to 60 controllersTGOAXE2H0E000 KIT TelevisGo 224* up to 224 controllers*contains No.1 SerialAdapter + 1.5 m serial cable
27
Supervision and monitoring Data acquisition modules and actuators TelevisIn / TelevisOut
TelevisIn / TelevisOutData acquisition modules and actuators
TelevisIn100-240Va
+–
TelevisOut100-240Va
+– 8 9 10 11 12
Codes Description Power supply
ApplicationsTelevisIn and TelevisOut are data acquisition, alarm signalling and user control modules which can be connected via the ModBus protocol to Televis or third-party systems. The TelevisIn controller, connected to specific probes, enables the acquisition of temperature, humidity and pressure data, and digital signals. It will also calculate dew points. TelevisOut provides alarm signalling and utility monitoring functions. It can be used to connect warning devices or telephone diallers and, in combination with the supervisor, to deliver energy savings via the management of lights and other utilities.
TAMID152RS700 TelevisIn 100...240 V~TAMOD602RS700 TelevisOut 100...240 V~
Wiring diagrams
Common featuresCompatible with third-party and ModBus systemsUp to 8 configurations for fast installation
Two models to cover all applicationsRemovable ‘T’ connector for fast installation of the RS-485 line
Technical data4 DIN moduleson DIN Omega bar support• NTC probe: -50.0...110.0°C• PTC probe: -55.0...140.0°C• Pt1000 probe: -55.0...400.0°C• Vin probe: 0-1 V, 0-5 V and 0-10 V• Ain probe: 0..20 mA and 4...20 mA3 NTC/PTC/Pt1000/DI inputs +1 V (0-1 V / 0-5 V / 0-10 V) input + 1 I (0...20 mA / 4...20 mA) input2 digital inputs (DI1 / DI2)
1 SPST 2A 250 V~
• 1 RS-485 for connection to TelevisSystem monitoring and systems based on ModBus protocol• 1 TTL to connect to Eliwell Unicard USB, Copycard and DMI interface for DeviceManagerRemovable screw terminalsAP1=Temperature; AP2=Analogue Inputs;AP3=Digital Inputs; AP4=Dew Point;AP5...8=Free5WSMPS 100...240 V~ ±10% 50/60 Hz
4 DIN moduleson DIN Omega bar support• NTC probe: -50.0...110.0°C• PTC probe: -55.0...140.0°C• Pt1000 probe: -55.0...400.0°C• Vin probe: 0-1 V, 0-5 V and 0-10 V• Ain probe: 0...20 V and 4...20 mA-
2 clean contact digital inputs (DI1 / DI2) also configurable as analogue outputs with no dangerous voltage2 (SELV) Open Collector: PWM3 SPST 2A 250 V~1 SPDT 2A 250 V~• 1 RS-485 for connection to TelevisSystem monitoring and systems based on ModBus protocol• 1 TTL to connect to Eliwell Unicard USB, Copycard and DMI interface for DeviceManagerRemovable screw terminalsAP1=Alarm signalling;AP2...8=Free
5WSMPS 100...240 V~ ±10% 50/60 Hz
TelevisIn TelevisOutDimensions:Mounting:Display range:
Analogue inputs:
Digital inputs:
Digital outputs:
Connectivity:
Connectors:Applications:
Power consumption:Power supply:
28
Supervision and monitoring Controller configuration software DeviceManager
DeviceManagerController configuration software
Applications
FeaturesGraphic interfaceEliwell instrument parameter managementReal-time variable monitoring and management
Device alarm log managementFirmware updating
DeviceManager is windows based software used to manage and install Eliwell devices. The software can be used to create and save parameter mapping and transfer it to and from the controller.DeviceManager needs the USB communication interface DeviceManager Interface (DMI) to communicate directly with controllers. It is compatible with Unicard USB and Multi Function Key to transfer maps, parameters and controller firmware updates.For information on compatibility and functions for each controller family, please check the compatibility table on www.eliwell.com
Minimum system requirements• Windows XP Pro SP2, Italian and English.• Windows XP Home SP2, Italian and English.• Windows 2000 Professional SP4, Italian and English.• Windows 7 Premium, Windows 7 Professional, Windows 7 Ultimate, versions 32bit, Italian-English• .NET Framework 2.0
• graphics resolution 1024x768• 700 MHz CPU• 256 MB RAM• HD 1 GB• Mouse or equivalent navigation systemApprox. 500 MB for normal installation (2 languages, 50 models)
DeviceManagerOperating system:
Software components requiredbesides operating system:Minimum hardware:
Space required on disk:
Accessories
TTL cableUSB-A/A 2MT extension lead
1 m reinforced cableLength 2 m
CO111127COLV000016200
Code Description Details
Codes DescriptionDMP1000002000 CD DeviceManagerDMI1001002000 DMI 100-1 End User DMI1002002000 DMI 100-2 ServiceDMI1003002000 DMI 100-3 ManufacturerCO111127 TTL CableCOLV000016200 USB-A/A extension cable
29
ACCESSORIES
Eliwell has developed a wide range products, from accessories for connectivity to a wide range of transformers, switches, protections and even memory devices such as Memory Cards for the rapid transfer of the controller parameters.
Eliwell has developed these devices to provide customers with instruments that allow ever increasing quality of performance and a better productive yield.
30
SerialAdapter - Ethernet LanAdapter - WiFi LanAdapter Connectivity modules for systems
Accessories Connectivity modules for systems SerialAdapter - Ethernet LanAdapter - WiFi LanAdapter
Connectivity
ApplicationsSerialAdapter is a galvanically isolated RS-232/RS-485 adapter for use on networks with TelevisGo.LanAdapter is an Ethernet/RS-485 (or TTL) interface module enabling communication between a LAN and a network of instruments compatible with the Televis protocol. In this way, the LAN network monitoring system can manage data, alarms and connected instrument network functions. The LanAdapter can be configured via the web from any PC on the LAN.
General technical specificationsplastic, 2 DIN moduleson DIN Omega bar support12 VC through TelevisGo serial port---5...+55°C-30...+75°C10...90% RH (non-condensing)
screw terminals to connect electric cables with a section of max. 2.5 mm2
(one connector per terminal).
• RS-485 port for connection to TelevisSystem
plastic, 4 DIN moduleson DIN Omega bar support100...240 V~ ±10% 50/60 Hz4W maxII0...+55°C-20...+85°C10...90% RH (non-condensing)
screw terminal to connect electric cables with a section of max. 2.5 mm2 (one wire per terminal).RJ-45 connector for connection to Ethernet network• RS-485 port for connection to TelevisSystem• TTL port for connection to instruments• LAN 10/100 MBps
plastic, 4 DIN moduleson DIN Omega bar support100...240 V~ ±10% 50/60 Hz4W maxII0...+55°C-20...+85°C10...90% RH (non-condensing)
screw terminal to connect electric cable with a section of max. 2.5 mm2 (one wire per terminal).Antenna (external)
• RS-485 port for connection to TelevisSystem• TTL port for connection to instruments• Standard: IEEE 802.15.4• Frequency band: ISM 2.400 GHz...2.485 GHz (<100 mW e.i.r.p.)• Selection of channel: manual/automatic
SerialAdapter Ethernet LanAdapter WiFi LanAdapterCasing:Mounting:Power supply:Power consumption:Insulation class:Ambient operating temperature:Ambient storage temperature:Ambient operation and storage humidity:Terminals:
Connectivity:
FeaturesRS-232, Ethernet and WiFi connectivityUp to 2 SerialAdapter networks with TelevisGo
Multiple networks using existing LAN infrastructuresTelevis and ModBus protocol compatibility
Codes DescriptionSAT1AMM100000 SerialAdapter 232 LA0ET00X700 Ethernet LanAdapter LA0WF00X700 WiFi LanAdapter
LanAdapter WiFi
RS485
RS485
LanAdapter Ethernet
Ethernet
RadioAdapter
BusAdapter
ModBus
ModBus
Internet
Switch/Access pointTelevisGo
SerialAdapter
x2RS485
31
RadioAdapter - RadioAdapter (/S) EXT - RadioKeyWireless connectivity modules
PAN-C
NODO
NODO
NODO
RadioKey
Power Supply
TTL
10 11
TTL
TTL
TTLRadioKey
RadioAdapter
RS-485*
* only for /S models
TTLRadioKey
Power Supply100...240Va
Power Supply
TTL
10 11
TTL
TTL
TTLRadioKey
RadioAdapter
RS-485*
SMAconnector cable for
externalantenna
externalantenna
* only for /S models
TTLRadioKey
Power Supply100...240Va
ApplicationsRadioAdapter provides a cost-effective, reliable way of building communication networks between monitoring systems and controllers by replacing cables or extending existing networks.RadioKey is a device needed to configure the network.
Common featuresFrequency band ISM 2.400 GHz…2.485 GHzMESH communication technology with automatic directory selectionExtensive surface coverage
Ability to act as a repeater for adjacent nodesEC certification for European marketFCC certification for American market
Wiring diagrams
General technical specifications
3 DIN moduleson DIN Omega bar support100...240 V~ ±10% 50/60 Hz2WII-5...+60°C-20...+85°C10...90% RH (non-condensing)
Class 4, ISA classification SP100.11 (not to be used for safety equipment)MESHTelevis or ModBus RTU100 max240 max800 msec max.TTL port for connection to RS-485 serial port devices - just models /S 2 x 4 GHz integrated, multi-directional-
3 DIN moduleson DIN Omega bar support100...240 V~ ±10% 50/60 Hz2WII-5...+60°C-20...+85°C10...90% RH (non-condensing)
Class 4, ISA classification SP100.11 (not to be used for safety equipment)MESHTelevis or ModBus RTU100 max240 max800 msec max. TTL port for connection to RS-485 serial port devices - just models /Sexternal - not included (see Accessories)External antenna kit + SMA 90° con-nector + 1 m cable.To be ordered separately
-------10...90% RH (non-condensing)
-
------
-needed for network configuration. Available for Televis or ModBus RTU networks
RadioAdapter RadioAdapter/S
RadioAdapter EXT RadioAdapter/S EXT
RadioKey
Casing:Mounting:Power supply:Power consumption:Insulation class:Ambient operating temperature:Ambient storage temperature:Ambient operation and storage humidity:Operating class:
Type of network:Protocol supported:Number of nodes per network:Number of controllers per node:Radio response time:Connectivity:
Antenna:Accessories/notes:
Codes DescriptionBARF0TT00NH00 RadioAdapter V2.0 BARF0DT00NH00 RadioAdapter/S V2.0BARF0TT20NH00 RadioAdapterEXT V2.0BARF0DT20NH00 RadioAdapter/S EXT V2.0MD0000003 External antenna kit for EXTCCA0B0T01Tx00 RadioKey (Televis)CCA0B0T01Mx00 RadioKey (ModBus RTU)x = based on setting of ModBus RTU serial:0: 9600, 8, N, 1 - 1: 9600, 8, O, 1 - 2: 9600, 8, E, 1 - 3: 19200, 8, N, 14: 19200, 8, O, 1 - 5: 19200, 8, E, 1
Accessories Wireless connectivity modules RadioAdapter - RadioAdapter (/S) EXT - RadioKey
32
BusAdapter 130 - 150 - 350RS-485 opto-isolated connectivity modules
A
GND
+ - GND
+ -
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
BusAdapter 350
Power Supply230VA
TTL
BusAdapter 130
TTL
Power Supply12VA/C
Power Supply230VA
A
GND
+ - GND
+ -
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
A
GND
+ - GND
+ -
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
BusAdapter 150
Power Supply230VA
TTL
Accessories RS-485 opto-isolated connectivity modules BusAdapter 130 - 150 - 350
Applications
Wiring diagrams
BusAdapter 130-150-350 is a family of devices used to connect Eliwell controllers to wired supervision and monitoring networks in RS-485 mode.
General technical specifications3 DIN moduleson DIN Omega bar support230 V~ / 115 V~ ±10% 50/60 Hz6WII-5...+55°C-30...+75°C10...90% RH (non-condensing)
screw-on terminal block to connect electric cables with a section of max. 2.5 mm2 (one wire per terminal for power connections)• double RS-485 port for connection to TelevisSystem• TTL port for connection to instruments2400...9600 Baud12 V~ / C ±10% 50/60 Hz
3 DIN moduleson DIN Omega bar support230 V~ / 115 V~ ±10% 50/60 Hz1.5WII-5...+60°C-30...+75°C10...90% RH (non-condensing)
screw-on terminal block to connect electric cables with a section of max. 2.5 mm2 (one wire per terminal for power connections)• double RS-485 port for connection to TelevisSystem• TTL port for connection to instruments2400...9600 Baud/
3 DIN moduleson DIN Omega bar support230 V~ / 115 V~ ±10% 50/60 Hz1.5WII-5...+60°C-30...+75°C10...90% RH (non-condensing)
screw-on terminal block to connect electric cables with a section of max. 2.5 mm2 (one wire per terminal for power connections)• double RS-485 port for connection to TelevisSystem• TTL port for connection to instruments2400...9600 Baud/
BusAdapter 130 BusAdapter 150 BusAdapter 350Casing:Mounting:Power supply:Power consumption:Insulation class:Ambient operating temperature:Ambient storage temperature:Ambient operation and storage humidity:Terminals:
Connectivity:
Baud rate:Auxiliary output:
Features130 models have an auxiliary 12 V (5 VA) output to power the instrument.150 models are equipped with reinforced electric insulation350 models are equipped with reinforced electric insulation and should be used with EM300 LX
Codes DescriptionBA11250N370x BusAdapter130 BA10000R370x BusAdapter150x=0: cable 1 m; x=3: cable 2.5 mBA10000R370x BusAdapter350x=1: cable 1 m; x=4: cable 2.5 m
33
Accessories Modems
Modem GSM/GPRSModems
Modem GSM/GPRS
Unit of Measure: mm
Applications
Technical SpecificationsMetal91x58.5x22 mm (BxHxD)195gEGSM900/GSM1800 MHz, GSM850/900/1800GSM phase 2/2+class 10 - 85.6Kbps GSM850/900: <33dBm;GSM1800: <30dBm<-107dBm• DB9 port RS-232 serial port, with 15KV ESD protection• SMA 50 Ohm antenna connection, female connector • connector powering 3-pole jack with protection for overvoltages and inverted polarity• SIM/USIM 3 V/1.8 V slot with 15KV ESD protection5...35 VC 12 V<200 mA (12 V)Speed 110 ... 230400 bps5, 6, 7, 8 data bit1, 1.5, 2 stop bitParity none, even, odd, space, mark-25...+65°C (-13...+149°F)-40...+85°C (-40...+185°F)10...95% RH (non-condensing)
Modem GSM/GPRS
The GSM/GPRS modem can be used to send SMS and for backup connectivity.
Case:Dimensions:Weight:Frequency bands:GSM standard:GPRS standard:Transmission power:
Reception sensitivity:Connections:
Power supply:Power consumption:Serial configuration:
Operating temperature:Storage temperature:Operation and storage humidity:
Codes DescriptionSAMGPRS35AL00 GSM/GPRS W/ANT PSU MODEM KIT Includes: power supply unit (European 10A plug) + antenna with 1.5 m cable
Dimensions
34
Unicard - USB Copy Card - Copy Card - Multi Function KeyMemory for fast configuration and updating of controllers
Accessories Memory for fast configuration and updating of controllers Unicard - USB Copy Card - Copy Card - Multi Function Key
Common featuresUnicard has a standard USB port for connection to the most widely-used power supply units and adapters on the market (mains-powered, machine-powered, battery-powered, etc.).Updating device parameter values
Updating device firmware/applicationsDownloading parameter values from the instrumentDownloading alarm log from the instrument
ApplicationsThe new USB/TTL Unicard is a memory device for rapid parameter configuration/duplication, specifically designed for controllers in the IDPlus family.By downloading the DeviceManager software from www.eliwell.com, maps for instruments in the ID and IDPlus families can be read and written onto the Unicard device without having to use other interfaces/licences.Copy Card and USB Copy Card are memory devices for rapid Eliwell controller parameter configuration/duplication. Multi Function Key is used with DeviceManager to transfer maps, parameters and controller firmware updates.
KEY •: Reading/writing maps parameters F: Updating Firmware L: Updating Interface Languages D: Download Data/Alarms
Counter power supply examples
Field power supply examples
0110 011010100111010100010101
0110 011010100111010100010101
0110 011010100111010100010101
power supplyUnicard - controller
0110 011010100111010100010101
0110 011010100111010100010101
0110 011010100111010100010101
0110 011010100111010100010101
0110 011010100111010100010101
0110 011010100111010100010101
power supplycontroller
Unicard
Unicard
Unicard
controller
controller
controller
power supplyUnicard
Use••••••••••••••--•---•
--------------••--•-•
-----------------•-
• / F / L / D-
••---•---•--•
• / F• / F• / F
•-
• / F--
Copy Card Multi Function key USB Copy CardUnicardIDPlus seriesEW - EWPlus (EO LVD) seriesIC seriesID seriesEM300 seriesDR4020 - DR4022EW4820 - EW4822EW7220 - EW7222EWTS 950 LX - EWTS 990 LXEWRC 300 - EWRC 500 seriesEWDR seriesIWC seriesIWP 750TelevisIn TelevisOutRTN seriesRTX - RTD seriesID 985/VV800 Pulse EEV driverV910 - XVD Step EEV DriverEWCM 8000…9000 EOEWCM 4000
Codes DescriptionCCA0BHT00UU00 UNICARD USB/TTLCCA0BUI02N000 USB Copy CardCOLV000016200 Extension lead for USB Copy CardCC0S00A00M000 Standard Copy Card MKF100T000000 Multi Function Key 100
35
Drip protectionDrip protection for 32x74 controllers
Accessories Drip protection for 32x74 controllers Drip protection
ApplicationsDrip protection for devices in the ID, IC, IDPlus, EW, EWPlus series.Applied to the rear of the instrument, this product protects electrical connectors against dripping liquid.
Part numberDrip protectionPack of 20
DescriptionZZ000270
36
TF TransformersTransformers
CodeTF 100...115...120VTF 100...115...120VTF 100...115...120VTF 12...24...48VTF 12...24...48VTF 200...250VTF 200...250VTF 200...250VTF 200...250VTF 200...250VTF 200...250VTF 200...250VTF 200...250V
115/12V 3VA - cert. UL115/12V 3VA110-230/12-12-12 o 12 15VA24/12V 3VA24/12V 5,6VA230/12V 3VA230/12V 5VA protected230/12V 3VA approved VDE240/12V 3VA approved VDE230/12V 6VA protected230/12V 11VA protected230/24V 25VA230/24V 35VA
Models DetailsTF511113TF111145TF11115ATF111115 TF111162TF111173TF411200TF411173TF411117TF411205TF411210TF111202TF111205
Accessories Transformers TF Transformers
ApplicationsTF transformers are resin-coated in plastic containers, equipped with fixing tabs and screw terminals for wires ≤ 2.5 mm2.Models with different power supply voltages are available.
37
Panel switches for ID and IC seriesPanel switches for IC - ID - Ammeter transformers
Accessories Panel switches for IC - ID - Ammeter transformers Panel switches for ID and IC series
ApplicationsSwitches specifically designed for use in conjunction with the Digifrost Line and Universal Controllers range. Available in different luminous/non-luminous colours or with luminous dot.
CodeBipolar switchBipolar switchBipolar switchBipolar switchBipolar switchBipolar switch
non-luminous grey buttonfull green lightgreen luminous dotfull red lightred luminous dotfull yellow light
grey frame 220 V serigraphed 0/1grey frame 220 V serigraphed 0/1grey frame 220 Vgrey frame 220 V serigraphed 0/1grey frame 220 Vgrey frame 220 V serigraphed 0/1
Model Colour DetailsSW22023A000SW22223D000SW22123D000SW22223B000SW22123B000SW22223E000
Dimensions
Unit of Measure: mm
38
PROBES AND TRANSDUCERS
To complete the range of electronic instruments, Eliwell supplies a series of temperature probes and humidity and pressure transducers that are recognised on the market for their reliability and quality of construction.
39
NTCNTC semi-conductor temperature probes
Probes and transducers NTC semi-conductor temperature probes NTC
NTC co-moulded with double insulation
NTC co-moulded with double insulated cable
Codes
Codes
NTC with double insulationNTC with double insulation
NTC co-moulded with double insulated cableNTC co-moulded with double insulated cableshieldedNTC co-moulded with double insulated cableNTC co-moulded with double insulated cableNTC co-moulded with double insulated cableNTC co-moulded with double insulated cableNTC co-moulded with double insulated cable
6x40
6x40
5x20
5x20
5x20
5x20
6x20
6x20
6x50
IP67
IP67
IP68
IP68
IP68
IP68
IP68
IP68
IP68
-50...+120°C
-30...+105°C
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
AISI 304
AISI 304
Thermoplastic rubber
Thermoplastic rubber
Thermoplastic rubber
Thermoplastic rubber
AISI 304
AISI 304
AISI 304
silicone
PVC
Thermoplastic rubbershieldedThermoplastic rubber
Thermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber
4000 V
4000 V
2000 V
2000 V
2000 V
2000 V
2000 V
2000 V
2000 V
1.5 m
1.5 m
10.0 m
1.5 m
1.5 m
3.0 m
1.5 m
3.0 m
1.5 m
Description
Description
Cable type
Cable type
CapsuleMaterial
CapsuleMaterial
Level of protec-tion
Level of protec-tion
Operating range
Operatingrange
Size of capsule mm (ØxL)
Size of capsule mm(ØxL)
Dielectricstrength
Dielectricstrength
Length of probe
Length of probe
SN8SAA1502
SN8PAA1500
SN8T6H0005
SN8T6H1505
SN8DED11502C0
SN8DED13002C0
SN8DAE11502C0
SN8DAE13002C0
SN8T6N1502
40
Special NTC probes - TCSpecial NTC semi-conductor temperature probes
Probes and transducers Special NTC semi-conductor temperature probes
NTC special versions
TCK
TCJ
Codes
Codes
Codes
NTC clamp-on
NTC clamp-on
NTC clamp-on probe IP67Fast response
NTC probeFast response
NTC probeFast response
TckTck
TcjTcjTcj
6x20
6x20
4x16
4x40
4x40
6x1006x200
6x1006x1006x100
IP68
IP68
IP67
IP67
IP67
IP45IP45
IP44IP44IP45
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
0...400°C-40...1150°C
0...350°C0...350°C0...350°C
Thermoplastic rubber
Thermoplastic rubber
Copper
AISI 304
AISI 304
AISI 304Inconel 600
AISI 316AISI 316AISI 304
Thermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber (Outer)Polypropylene (Inner)
Thermoplastic rubber (Outer)Polypropylene (Inner)
TTSTTS
VetrotexVetrotexTTS
2000 V
2000 V
1500 V
2000 V
2000 V
--
---
1.5 m
3.0 m
1.5 m
1.5 m
3.0 m
3.0 m1.0 m
3.0 m1.5 m3.0 m
Description
Description
Description
Cable type
Cable type
Cable type
CapsuleMaterial
CapsuleMaterial
CapsuleMaterial
Level of protec-tion
Level of protec-tion
Level of protec-tion
Operatingrange
Operatingrange
Operatingrange
Size of capsule mm (ØxL)
Size of capsule mm (ØxL)
Size of capsule mm(ØxL)
Dielectricstrength
Dielectricstrength
Dielectricstrength
Length of probe
Length of probe
Length of probe
SN8DEB21502C0
SN8DEB23002C0
SN8DNB11502A0
SN8DAC11502AV
SN8DAC13002AV
SN400000SN400004
SN300000SN300008SN300042
Special NTC probes - TC
41
Pt100 - Pt1000 probesPt100 - Pt1000 thermo-resistive temperature probes
Probes and transducers Pt100 - Pt1000 thermo-resistive temperature probes Pt100 - Pt1000 probes
Code
Pt100, 3 wires with steel tubePt100, 3 wires with steel tubeP100 with steel tube
6x1006x1006x50
IP44IP67IP68
0...+600°C-40...200°C-50...+110°C
AISI 316AISI 316AISI 304
Vetrotexsiliconethermoplastic rubber
3 mm3 mm1.5 mm
Description Cable typeCapsuleMaterial
Level of protec-tion
Operatingrange
Size of capsule mm(ØxL)
Length of probe
SN200009SN206000SN2TAE51502C0
Pt100
Codes
Pt1000 with two wiresPt1000 co-moulded with double insulated cable
Pt1000 co-moulded with double insulated cable
Pt1000 co-moulded with double insulated cable
Pt1000 co-moulded with double insulated cable
6x406x20
6x20
5x20
5x20
IP67IP68
IP68
IP68
IP68
-50...+200°C-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
AISI 304AISI 304
AISI 304
Thermoplastic rubber
Thermoplastic rubber
SiliconeThermoplastic rubber (Outer)Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)
2000 V2000 V
2000 V
2000 V
2000 V
2.5 m1.5 m
3.0 m
1.5 m
3.0 m
Description Cable typeCapsuleMaterial
Level of protec-tion
Operatingrange
Size of capsule mm(ØxL)
Dielectricstrength
Length of probe
SN9S0A2500SN9DAE11502C6
SN9DAE13002C6
SN9DED11502C6
SN9DED13002C6
Pt1000
42
PTC ProbesPTC semi-conductor temperature probes
Probes and transducers PTC semi-conductor temperature probes PTC Probes
Common features
Applications
Accuracy of temperature measurement: +/- 1%
Eliwell temperature probes are devices that provide the instruments to which they are connected with temperature measurement through a physical process.
Codes
PTC co-moulded with double insula-ted cable
PTC co-moulded with double insula-ted cable
PTC co-moulded with double insula-ted cable
PTC co-moulded with double insula-ted cable
PTC co-moulded with double insula-ted cable
PTC for ambient temperaturePTC for piercing, with PVC grip
6x40
6x20
6x20
5x20
6x20
15x70
3x150
IP68
IP68
IP68
IP68
IP68
IP54
IP65
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
-50...+110°C
-40...+120°C
-20...+110°C
AISI 304
AISI 304
AISI 304
Thermoplastic rubber
AISI 304
Plastic
AISI 316
Thermoplastic rubber (Outer) Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)Thermoplastic rubber (Outer) Polypropylene (Inner)-
Silicone
2000
2000
2000
2000
2000
-
-
1.5 m
1.5 m
3.0 m
1.5 m
3.0 m
-
3.0 m
Description Cable typeCapsuleMaterial
Level of protec-tion
Operatingrange
Size of capsule mm(ØxL)
Dielectricstrength
Length of probe
SN7T6A1502
SN7DAE11502C0
SN7DAE13002C0
SN7DED11502C0
SN7DED13002C0
SN6070000
SN603008
43
EWPA 007 - 030 - 050Pressure transducers
Probes and transducers Pressure transducers EWPA 007 - 030 - 050
ApplicationsEWPA pressure transducers are sensors with a voltage output through which they transmit the signal to the measurement instruments they are connected to.
Codes Description Connector Electric connection IPTD220030 EWPA 030 1/4 SAE MALE 2 m cable 54TD240030 EWPA 030 1/4 SAE MALE 2 m cable with Packard connector 67TD250030 EWPA 030 1/4 SAE MALE mPm connector 65TD320030 EWPA 030 1/4 SAE FEMALE 2 m cable 54TD340030 EWPA 030 1/4 SAE FEMALE 2 m cable with Packard connector 67TD220050 EWPA 050 1/4 SAE MALE 2 m cable 54TD240050 EWPA 050 1/4 SAE MALE 2 m cable with Packard connector 67TD320050 EWPA 050 1/4 SAE FEMALE 2 m cable 54TD340050 EWPA 050 1/4 SAE FEMALE 2 m cable with Packard connector 67TD220007 EWPA 007 1/4 SAE MALE 2 m cable 54TD240007 EWPA 007 1/4 SAE MALE 2 m cable with Packard connector 67TD320007 EWPA 007 1/4 SAE FEMALE 2 m cable 54TD340007 EWPA 007 1/4 SAE FEMALE 2 m cable with Packard connector 67TD320010 EWPA 010 1/4 SAE FEMALE 2 m cable 54TD340010 EWPA 010 1/4 SAE FEMALE 2 m cable with Packard connector 67
Technical data0.5...8 bar (absolute)2 wires 4...20 mA2 times pressure range8...32 Volts± 0.5% FS max(linearity, hysteresis, repeatability)0...50°C2 m cable, wired2 m cable with PACKARD connector
male connector/female connector¼ SAE (7/16"-20UNF)-40...100°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealPackard: IP67Cable: IP54
0...10 bar (absolute)2 wires 4...20 mA2 times pressure range8...32 Volts± 0.5% FS max(linearity, hysteresis, repeatability)0...50°C2 m cable, wired2 m cable with PACKARD connector
male connector/female connector¼ SAE (7/16"-20UNF)-40...100°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealPackard: IP67Cable: IP54
0...30 bar (absolute)2 wires 4...20 mA2 times pressure range8...32 Volts± 0.5% FS max(linearity, hysteresis, repeatability)0...50°C2 m cable wired2 m cable withPACKARD connectormPm connectormale connector/female connector¼ SAE (7/16"-20UNF)-40...100°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealPackard: IP67mPm plug: IP65 Cable: IP54
0...50 bar (absolute)2 wires 4...20 mA2 times pressure range8...32 Volts± 0.5% FS max(linearity, hysteresis, repeatability)0...50°C2 m cable, wired2 m cable withPACKARD connector
male connector/female connector¼ SAE (7/16"-20UNF)-40...100°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealPackard: IP67Cable: IP54
EWPA 007 EWPA 010 EWPA 030 EWPA 050Operating range:Output signal:Overload:Power supply:Accuracy:
Compensated temperature:Electrical connections:
Mechanical connections:
Operating temperature:Global error at T 0...50°C:Global error at T -10...80°C:Response time:Material in contact with the environmentEnclosure rating:
44
EWPA 010 - 030 - 050Ratiometric pressure transducers
Probes and transducers Ratiometric pressure transducers EWPA 010 - 030 - 050
Applications
Technical data0...145 psi / 0...10 bar3 wires 0.5...4.5 V ratiometric2.5 times pressure range5.0 Vc ± 0.5 V± 0.25% FS max(linearity, hysteresis, repeatability)8 mA max> 5KΩ2 m cable with PACKARD connectorfemale connector¼ SAE (7/16"-20UNF)-40...125°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealIP67
0...515 psi / 0...35 bar3 wires 0.5...4.5 V ratiometric2.5 times pressure range5.0 Vc ± 0.5 V± 0.25% FS max(linearity, hysteresis, repeatability)8 mA max> 5KΩ2 m cable with PACKARD connectorfemale connector¼ SAE (7/16"-20UNF)-40...125°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealIP67
0...667 psi / 0...46 bar3 wires 0.5...4.5 V ratiometric2.5 times pressure range5.0 Vc ± 0.5 V± 0.25% FS max(linearity, hysteresis, repeatability)8 mA max> 5KΩ2 m cable with PACKARD connectorfemale connector¼ SAE (7/16"-20UNF)-40...125°Cmax. ± 1.0% FSmax. ± 1.5% FS(0...99%) < 5 msAISI 316LViton outer sealIP67
EWPA 010 EWPA 030 EWPA 050Operating range at 0.5...4.5 V:Output signal:Overload:Power supply:Accuracy:
Energy consumption:Load resistance:Electrical connections:Mechanical connections:
Operating temperature:Global error at T 0...50°C:Global error at T -10...80°C:Response time:Material exposed to environment:
Enclosure rating:
EWPA ratiometric pressure transducers are sensors capable of transmitting a signal by way of a current output to the measuring instruments with which they are connected. They offer accurate performance across a wide temperature range.
Codes Description Connector Electric connectionTD420010 EWPA 010 1/4 SAE FEMALE 2 m cable with Packard connectorTD420030 EWPA 030 1/4 SAE FEMALE 2 m cable with Packard connectorTD420050 EWPA 050 1/4 SAE FEMALE 2 m cable with Packard connector
45
Humidity probes
ApplicationsHumidity probes of the EWHS284-304-314 series are intended for connection to humidity and humidity/temperature measuring instruments of superior dependability.
EWHS 284 - 304 - 314
EWHS284 EWHS304 EWHS314
Technical data EWHS284 EWHS304 EWHS314Enclosure rating IP54 IP65 IP65
Installation Use the clip supplied with the probe via 2 external slots via 2 external slots
Electrical connections PVC two core cable Screw terminals Screw terminals
Dimensions 103X25mm 80X80X52mm 80X80X52mm
Power supply 9...28Vm 9...30Vm 15...40Vm or 12...28V˜
Current draw 20mA max 20mA max <50mA max
Ambient temperature -10...60°C -40...60°C -40...60°C (-40...140°F)
Humidity sensor resistive HygroMer* IN-1 HygroMer* IN-1
Humidity measurement range 15...90% RH 0...100% RH 0...100% RH
Output current of humidity measurement
4 (0%)...20mA (100%) 4 (0%)...20mA (100%) 4 (0%)...20mA (100%)
Response time in steady state (63%) at 23 °C
60 secs typically 10 secs typically 10 secs
Recovery timefrom saturation
360 secs depending on air flow rate depending on air flow rate
Storage temperature -20...70°C -50...70°C -50...70°C
Accuracy of humidity measurement (at 23°C):
±5% RH (in the range 15...90% RH)±2% RH (in the range 10...95% RH)±3% RH (for values <10% or >95% RH)
±2% RH
Number of wires per connection 2 (blue: power; brown: output) 2 4
Air filter metal wire mesh polyethylene polyethylene
Temperature sensor - - Pt100B
Temperature range - - -40...60°C (-40...140°F)
Temperature measurement output current
- - 4 (-30°C)...20mA (70°C)
Accuracy of temperature measurement (at 0 °C and 23 °C)
- - ±0,3K
Temperature compensation - with NTC with Pt100B
Connection cable 1m or 3m - -
Maximum load 250 Ohm 0 Ohm at 6Vc and 5V~500Ohm at 15Vc and 12V~
0 Ohm at 6Vc and 5V~500Ohm at 15Vc and 12V~
Part NumberEWHS284 1m cable: SN5PPN116I3M0EWHS284-3 3m cable: SN5PPN131I3M0
EWHS304: SN5NPM1A6I4M0 EWHS314: SN0NPM1A6I4M0
Common featuresAmbient humidity: 0...100% RHMaximum air speed: 20m/sPolarity inversion protection: diode
Probes and transducers Humidity probes EWHS 284 - 304 - 314
46
Appendices
Temperature probe tables
Appendices Temperature probe tables NTC probe table - NTC probe table Extended range - PTC probe table
PTC probe table
NTC probe table
-67-58-40-22-4143250687786104122140158176194212230248257266284302
24,4618,6814,4311,238,8346,9985,5944,5013,6512,9792,4492,0241,6841,4081,1841,0000,84860,72290,61890,53160,45870,39490,34460,30000,26220,22850,19990,17510,1536----
154,60116,5088,9168,1952,8741,2132,4425,6620,4816,4313,2910,808,8407,2676,0135,0004,1793,5082,9612,5092,1371,8261,5671,3501,1681,0140,88350,77220,67710,59610,52650,46540,4128
1253890,50642,00465,80342,50253,60190,00143,20109,1083,7564,8850,5339,7131,3624,9620,0016,1213,0610,658,7167,1815,9414,9434,1273,4642,9162,4682,0961,7881,5301,3151,1340,9807
47149554760366272679486594198010181097118012661355144715431642174518491900195020442124
500524576632691754820889962100010411125121313051402150216071716182819432000205614622254
Temperatureenvironment
Temp. environment
Temperature coefficient
Resistance (Ohm)
KTY81-121
(°C) (°F) (%/K) Error - tem-perature
Resistance (Ohm)Minimum
(°C) 102AT 202AT 502AT 103AT 203AT 503AT
Standard Maximum0,990,980,960,930,910,880,850,830,800,790,780,750,730,710,690,670,650,630,610,580,550,520,450,35
-55-50-40-30-20-10010202530405060708090100110120125130140150
55,6642,1732,3426,9619,4815,2912,119,6557,7636,2775,1144,1883,4542,8622,3872,0001,6841,4241,2111,0330,88540,76200,65870,57130,49750,43430,38070,33460,2949----
-50-45-40-35-30-25-20-15-10-505101520253035404550556065707580859095100105110
329,50247,70188,50144,10111,3086,4347,7753,4142,4733,9027,2822,0517,9614,6912,0910,008,3136,9405,8274,9114,1603,5363,0202,5882,2281,9241,6681,4511,2661,1080,97310,85720,7576
3168225716321186872,80646,30484,30364,60277,50212,30164,00127,5099,9978,7762,5650,0040,2032,4826,4321,5917,7514,6412,1510,138,4827,1296,0225,1054,3453,7123,1852,7412,369
NTC probe table - Extended range
333,562241,072176,082129,92596,80772,80955,25342,29232,64025,39119,90215,71312,49310,0008,0556,5305,3254,3673,6012,9852,4872,0821,7511,4801,2561,0700,9160,7860,6780,5870,5100,4440,3880,3400,2990,2640,2340,2070,184
-40-35-30-25-20-15-10-505101520253035404550556065707580859095100105110115120125130135140145150
Temp. environment Resistance (KOhm)
(°C) Minimum Standard Maximum321,654233,032170,611126,17694,22171,01554,00441,41932,02824,96219,60115,50412,3489,9007,9626,4445,2474,2963,5372,9282,4362,0371,7111,4441,2241,0420,8900,7640,6580,5690,4930,4290,3750,3280,2890,2540,2240,1990,177
345,877249,364181,710133,7739945474,64056,52543,1793326025,82420,20515,92412,63910,1008,1506,6165,4034,4383,6653,0422,5382,1271,7921,5161,2881,0990,9410,8100,6990,6050,5260,4590,4020,3530,3100,2740,2430,2150,192
48551056261767774080787795199010291111119612861378147515751679178618961950200321032189
±3,02±2,92±2,74±2,55±2,35±2,14±1,91±1,67±1,41±1,27±1,39±1,64±1,91±2,19±2,49±2,80±3,12±3,46±3,83±4,33±4,66±5,07±6,28±8,55
47
Appendices
Temperature probe tables
Appendices Temperature probe tables Pt100 probe table - Pt1000 probe table
Pt100 probe table
Pt1000 probe table
18,5222,8327,1031,3435,5439,7243,8848,0052,1156,1960,2664,3068,3372,3376,3380,3184,2788,2292,1696,09100,00103,90
185,281228,327271,029313,408355,484397,277432,903480,081521,127561,954602,578643,012683,267723,355763,286903,068842,71882,218921,6960,85910001039,025
107,7911,67115,54119,40123,24127,08130,90134,71138,51142,29146,07149,83153,58157,33161,05164,77168,48172,17175,86179,53183,19
1077,9361116,7311155,4111193,9761232,4261270,9611308,9811347,0851385,0751422,9491460,7091498,3531535,8821573,2961610,5951647,7791684,8481721,8011758,6401795,3631831,972
186,84190,47194,10197,71201,31204,90208,48212,05215,61219,15222,68226,21229,72233,21236,70240,18243,64247,09250,53253,96257,38
1868,4651904,8431941,1061977,2542013,2872049,2052085,0072120,6952156,2672191,7252227,0672262,2942297,4062332,4032367,2852402,0522436,7032471,2402505,6612539,9682574,159
260,78264,18267,56270,93274,29277,64280,98284,30287,62290,92294,21297,49300,75304,01307,25310,49313,71316,92320,12323,30326,48
2608,2352642,1962676,0422709,7732743,3892776,8892810,2752843,5452876,7012909,7412942,6662975,4763008,1713040,7513073,2163105,5653137,8003169,9193201,9243233,8133265,587
329,64332,79335,93339,06342,18345,28348,38351,46354,53357,59360,64353,67366,70369,71372,71375,70378,68381,65384,60387,55390,48
3297,2463328,7903360,2193391,5333422,7313453,8153484,7833515,6373546,3753576,9983607,5063637,8993668,1773698,3403728,3873758,3203788,1373917,8403847,4273876,8993906,256
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Temp. environment
Resistance
Resistance
Resistance
Resistance
Resistance
Resistance
Resistance
Resistance
Resistance
Resistance
(°C)
(°C)
(°C)
(°C)
(°C)
(°C)
(°C)
(°C)
(°C)
(°C)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
(Ohm)
-200-190-180 -170-160-150-140-130-120-110-100-90-80-70-60-50-40-30-20-10010
-200-190-180 -170-160-150-140-130-120-110-100-90-80-70-60-50-40-30-20-10010
2030405060708090100110120130140150160170180190200210220
2030405060708090100110120130140150160170180190200210220
230240250260270280290300310320330340350360370380390400410420430
230240250260270280290300310320330340350360370380390400410420430
440450460470480490500510520530540550560570580590600610620630640
440450460470480490500510520530540550560570580590600610620630640
650660670680690700710720730740750760770780790800810820830840850
650660670680690700710720730740750760770780790800810820830840850
48
Appendices
Temperature Probe Tables
Appendices Temperature Probe Tables TCJ probe table - TCK probe table
TCJ probe table
TCK probe table
-7,890-4,6330,000
-5,730-3,5540,000
--5,426-0,995
-6,158-4,138-0,778
--6,159-1,961
-6,344-4,669-1,527
--6,821-2,893
-6,441-5,141-2,243
--7,403-3,786
--5,550-2,920
Temp.
Temp.
0°C
0°C
-10°C
-10°C
-20°C
-20°C
-30°C
-30°C
-40°C
-40°C
-50°C
-50°C
-60°C
-60°C
-70°C
-70°C
-80°C
-80°C
-90°C
-90°C
-200°C-100°C0°C
-200°C-100°C0°C
-8,095-5,037-0,501
-6,035-3,852-0,392
--5,801-1,482
-6,262-4,411-1,156
--6,500-2,431
-6,404-4,913-1,889
--7,123-3,344
-6,458-5,354-2,587
--7,659-4,215
--5,730-3,243
10°C
10°C
20°C
20°C
30°C
30°C
40°C
40°C
50°C
50°C
60°C
60°C
70°C
70°C
80°C
80°C
90°C
90°C
100°C
100°C
0,0005,26910,77916,32721,84827,39333,10239,13245,49451,87757,95363,79269,553
1,0196,36011,88917,43422,95228,51634,27940,38246,78653,11959,13464,948-
2,0597,45913,00018,53824,05929,64735,47041,64548,07454,34760,30766,102-
3,1168,56214,11019,64224,16430,78836,67542,91949,35355,56161,47367,255-
4,1879,66915,21920,74526,27631,93937,89644,20350,62256,76362,63468,406-
0°C100°C200°C300°C400°C500°C600°C700°C800°C900°C1000°C1100°C1200°C
0,5075,81411,33416,881222,40027,95333,68939,75546,14152,50058,54564,370-
1,5376,90912,44517,98623,50429,08034,87341,01247,43153,73559,72165,525-
2,5858,01013,55519,09024361030,21636,07142,28148,71554,95660,89066,679-
3,6509,11514,66520,19425,72031,36237,28443,55949,98956,16462,05467,831-
4,72610,22415,77321,29726,83432,51938,51244,84851,25157,36063,21468,980-
0,0004,0968,13812,20916,39720,64424,90529,12933,27537,32641,27645,11948,83852,410
0,7984,9208,94013,04017,24321,49725,75529,96534,09338,12442,05345,87349,56553,106
1,6125,7359,74713,87418,09122,35026,60230,79834,90838,91842,82626,62350,28653,795
2,4366,54010,56114,71318,94123,20327,44731,62835,71839,70843,59547,36751,00054,479
3,2677,34011,38215,55419,79224,05528,28932,45336,52440,49044,35948,10551,708-
0°C100°C200°C300°C400°C500°C600°C700°C800°C900°C1000°C1100°C1200°C1300°C
0,3974,5098,53912,62416,82021,07125,33029,54833,68537,72541,66545,49749,20252,759
1,2035,3289,34313,45717,66721,92426,17930,38234,50138,52242,44046,24949,92653,451
2,0236,13810,15314,129318,51622,77627,02531,21335,31339,31443,21146,99550,64454,138
2,8516,94110,97115,13319,36623,62927,86932,04136,12110,10143,97847,73751,35554,819
3,6827,73911,79515,97520,21824,48028,71032,86536,92540,88544,74048,47352,060-
49
This document is the exclusive property of Eliwell Controls s.r.l. and may not be reproduced or circulated unless expressly authorised by Eliwell
Controls s.r.l. While all possible care has been taken to ensure the accuracy of this document, Eliwell Controls s.r.l. cannot accept liability for
any damage resulting from its use. The same applies to any person or company involved in the creation and preparation of this document.
Eliwell Controls s.r.l. reserves the right to make changes or improvements at any time without notice.
Approval marks may vary across products. Check details and availability with sales department.
DISCLAIMER
Eliwell is a brand of the Invensys Group, a company that operates at global level, with a vast range of industrial and commercial customers for the planning and supply of advanced technologies that optimise their operating performance and increase profitability. Invensys is a market leader for systems and components that enable their customers to monitor, control and automate their products and processes, thus achieving maximum efficiency, reliability and ease of use. Eliwell has been operating on the refrigeration and air conditioning market for more than 30 years, offering control systems and services for refrigeration units, both commercial and industrial, and for air conditioning.
The company website www.eliwell.com provides up-to-date information on solutions and products offered by the company.The newsletter for installers and dealers provides a direct line through which Eliwell is able to reach its customers and keep them updated on new developments and improvements made to products. The reserved area of the website affords easy access at any time to dedicated content and software upgrades.
Contacts
ITALIA - Eliwell Controls s.r.l. - Pieve d’Alpago (Belluno)
Tel +39 0437 986 111
Fax +39 0437 989 066
Sales +39 0437 986 100
E-mail [email protected]
Technical support +39 0437 986 300
E-mail [email protected]
www.eliwell.it
SPAIN - Eliwell Iberica S.A. - Valencia
Tel +34 (0) 96 313 42 04
Fax +34 (0) 96 350 07 87
E-mail [email protected]
www.eliwell.es
GERMANY - Eliwell Deutschland - Nürnberg
Tel +49 (0) 911 56 93 430
Fax +49 (0) 911 56 93 536
E-mail [email protected]
www.eliwell.de
FRANCE - Eliwell France - Paris
Tel +33 (0) 1 41 47 71 71
Fax +33 (0) 1 47 99 95 95
E-mail [email protected]
www.eliwell.com
RUSSIA - Moscow
Tel +7 499 611 79 75
Fax +7 499 611 78 29
www.eliwell.com
CHINA - Invensys Automation & Controls Systems Co. Ltd - Shanghai
Tel +86 21 614 511 88
Fax +86 21 614 511 89
E-mail [email protected]
www.eliwell.cn
UNITED STATES - Invensys Controls - Carol Stream, IL
Technical support
and Customer service +1 800 304 6563
Technical support +1 800 445 8299
www.eliwell.com
OTHER COUNTRIESTel +39 0437 986 111
Fax +39 0437 989 066
Sales +39 0437 986 200
E-mail [email protected]
Technical support +39 0437 986 300
E-mail [email protected]
www.eliwell.com
CT123194 - EN • rel. 07/13© Copyright Eliwell Controls s.r.l. 2013 - All rights reserved