SHEET INDEX E-1 SHEET # DESCRIPTION E-2 E-4 E-3 DEMOLITION/ELECTRICAL PLAN PLAN TITLE-24 TITLE SHEET, SCHEDULES, NOTES, LEGEND MOORPARK, CA TITLE-24 APPLICATION CATEGORIES SITE ADDRESS: 500 POINDEXTER AVENUE MOORPARK, CA. 93021 SEE SHEET E-4 FOR MANDATORY MEASURES. A LIGHTING POWER ALLOWANCE FOR GENERAL HARDSCAPE-ALL DRIVEWAY'S, PARKING STALLS AND PLANTING ISLANDS, SIDEWALKS, STAIRS=18,680 WATTS. TOTAL INSTALLED WATTS=3,859. COMPLIES. (OLTG-1C PART 4 OF 4) CATALOG NO. LAMPS LUMINAIRE SCHEDULE SYMBOL 120 FIXTURE LED LPS INDUC HPS MH 480 208 240 VOLTS TYPE NO. SPECIAL MOUNTING WATTS H20 WELL SURF DESCRIPTION POLE MFR & HALOG TYPE COUNT 40 1 AREA LIGHT (DETAIL A/E-3) 31 36 LED ANP LIGHTING FIXTURE: BVA01-H 40W/350mA/4000K/TYPE5/SMALL DISK PRIVATE ELECTRICAL SYSTEM SHALL NOT BE JOINT TRENCH WITH PUBLIC UTILITY SYSTEM. CONSTRUCTION NOTES ALL 90 DEGREE ELBOWS TO BE FACTORY MADE BENDS. ALL WORK TO BE IN ACCORDANCE WITH THE 2010 CEC AND ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES. ALL MATERIALS AND EQUIPMENT SHALL BE COMMERCIAL AND SHALL CARRY A U.L. LABEL. 14. 15. 4. A. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW AND SUCH AS APPEAR ON THE UNDERWRITER'S LABORATORIES LIST OF APPROVED ITEMS AND SHALL MEET REQUIREMENTS OF ASTM, IEEE, 2010 NEC, NEMA, AND OTHER RECOGNIZED STANDARDS AND SHALL BE SIZED IN CONFORMITY WITH REQUIREMENTS OF THE NATIONAL ELECTRIC CODE AND OTHER APPLICABLE CODES, WHICHEVER ARE MORE STRINGENT. B. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS TO PERFORM ELECTRICAL WORK SHOWN, NOTED OR SCHEDULED FOR A COMPLETE AND FINISHED INSTALLATION. 2. 1. THE GENERAL CONDITIONS AND SUPPLEMENTARY GENERAL CONDITIONS SHALL BE CONSIDERED AS PART OF THE SPECIFICATION. THE WORD "PROVIDE" AS USED HEREIN MEANS TO FURNISH AND INSTALL COMPLETE. 3. SECURE AND PAY FOR ALL REQUIRED PERMITS AND INSPECTION CERTIFICATES. 5. ABOVE GRADE CONDUIT SHALL BE STANDARD RIGID STEEL ACCORDING TO CODE REQUIREMENTS. CONDUIT SHALL BE CONCEALED IN FINISHED AREAS, EXCEPT AS OTHERWISE APPROVED BY ARCHITECT. RIGID CONNECTIONS SHALL BE COMPRESSION TYPE. UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 OR 80 PVC BURIED A MINIMUM OF 24". 6. WIRE SHALL BE SINGLE CONDUCTOR COPPER WITH 600 VOLT INSULATION. ALUMINUM CONDUCTORS ARE NOT PERMITTED. #12 AND SMALLER SHALL BE SOLID. #10 AND LARGER SHALL BE STRANDED. MINIMUM WIRE SIZE SHALL BE #10. ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE SITE IN UNBROKEN PACKAGES. ALL WIRING OF ANY TYPE SHALL BE IN CONDUIT. 7. GENERAL WIRING SHALL BE THWN OR THHN. A. ABOVE GRADE WIRE CONNECTORS SHALL BE BY "SCOTCHLOCK" OR EQUAL FOR #8 OR SMALLER AND T&B "LOCK-TITE" FOR #6 AND LARGER. 8. THIS CONTRACTOR SHALL DO ALL CUTTING, CHASING OR CHANNELING AND PATCHING REQUIRED FOR ANY WORK UNDER THIS DIVISION. ANY CUTTING SHALL HAVE PRIOR APPROVAL OF THE OWNER. 9. PROVIDE SAFETY AND DISCONNECT SWITCHES, SHALL BE FUSED OR NON-FUSED AS CALLED FOR ON DRAWINGS AND AS REQUIRED BY CODE. SWITCHES SHALL BE HEAVY DUTY, LOAD AND HORSEPOWER RATED AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC OR EQUAL. 10. JUNCTION, PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL, CODE GAUGE SIZE AND ACCESSIBLE. 11. ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN HIS WORK AS THE JOB PROGRESSES, AND UPON COMPLETION SHALL TURN OVER TO THE OWNER A "RECORD" SET OF PRINTS SHOWING THE CHANGES. 12. ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING MAINTAINING AND REPAIRING. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL, SUCH AS CHANNELS, RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK AND SHALL BE FASTENED TO STEEL, CONCRETE OR MASONRY, BUT NOT TO PIPING. ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. EXPOSED CONDUITS SHALL BE IN STRAIGHT LINES PARALLEL WITH OR AT RIGHT ANGLES TO COLUMN LINES OR BEAMS AND SEPARATED AT LEASED 3" FROM WATER LINES WHEREVER THEY RUN ALONGSIDE OR ACROSS SUCH LINES. CONDUCTORS SHALL BE ON CONDUIT, DUCTS, OR APPROVED RACEWAYS. 13. CONTRACTOR TO MAINTAIN PROPER SEPARATION AS REQUIRED BY THE UTILITY COMPANIES. 16. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING FOR ANY AND ALL UTILITY AND CITY INSPECTIONS. 17. 18.ALL GROUND CONDUCTORS SHALL BE SPLICED TOGETHER WITH APPROVED CONNECTOR AT PULL BOXES AND CONNECTED TO GROUND LUG INSIDE POLE. 19.SEE IMPROVEMENT PLANS FOR SITE, SEWER AND WATER (ETC.) IMPROVEMENTS PRIOR TO START OF CONSTRUCTION. 20.CONTRACTOR SHALL CONTACT "DIG ALERT" FOR MARK-OUT PRIOR TO TRENCHING AS REQUIRED. 21. THESE PLANS ARE SCHEMATIC AND ARE FOR THE PURPOSE OF SHOWING HOW TO CONNECT THE ELECTRICAL SYSTEM. WHILE THE DRAWING IS AT ACTUAL SCALE, THE SYMBOLS REFERENCED ARE NOT, AND MAY APPEAR TO SHOW THE EQUIPMENT IN PLACES NOT INTENDED. THE CONTRACTOR IS TO FIELD VERIFY ALL UTILITY COMPANY SERVICE POINTS/METER LOCATIONS, POLES, PULL BOXES BUILDING LIGHT LOCATIONS, SERVICE EQUIPMENT LOCATIONS AND OTHER ELECTRICAL APPURTENANCES PRIOR TO START OF CONSTRUCTION. ANY DISCREPANCIES ARE TO BE ADDRESSED TO THE CITY BY MEANS OF A "REQUEST FOR INFORMATION" (RFI). CONTRACTOR IS TO VERIFY ALL LIGHT LOCATIONS WITH THE CITY PRIOR TO START OF CONSTRUCTION AND DURING STAKING. REFER TO LIGHT STANDARD DETAIL FOR STANDARDS. CONTRACTOR SHALL CONTACT "DIG ALERT" FOR MARK-OUT PRIOR TO TRENCHING AS REQUIRED.CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS PRIOR TO START OF CONSTRUCTION AS THE BASE MAP IS NOT A CIVIL ENGINEER GENERATED MAP, BUT HAS BEEN DRAWN FROM A GOOGLE EARTH IMAGE AND MAY NOT BE ENTIRELY SCALED AND DRAWN CORRECTLY. 22.PANEL CIRCUIT DIRECTORY TO COMPLY WITH SECTION 408.4, CEC. 23.NATIVE SOIL SHALL BE ACCEPTABLE FOR TRENCH BACK FILL PROVIDED THAT THE FILL MATERIAL USED SHALL PASS THROUGH A 1" SIEVE (CITY OF MOORPARK BACKFILL ORDINANCE). SEE NOTES & DETAIL C/E-3. 24.CONTRACTOR SHALL LABEL EACH CIRCUIT WITH PHENOLIC PLASTIC LABEL TAGS IN ANY DEVICE THAT HAS ACCESS. THIS SHALL INCLUDE LIGHT POLES, PULL BOXES, PANELS, AND ETCETERA. PANEL, CIRCUIT NUMBER AND VOLTAGE SHALL BE IDENTIFIED. TAGS SHALL BE AFFIXED WITH NYLON ZIP-TIES. LEGEND NEW TYPE 'B' SINGLE HEAD TYPE 5 LED AREA/ PARKING LIGHT. SEE DETAIL B/E-3 SPECIFICATIONS 6. ALL SPLICES BELOW GRADE SHALL BE MADE IN APPROVED PULL BOXES AND SHALL BE WATERTIGHT. USE ONLY EPOXY ENCAPSULATED TYPE 3M BAGS OR EQUAL. 1. ALL PULL BOXES TO BE TYPE 3-1/2 PB (10-1/2" X 17-1/2" X 12"D) WITH CONCRETE BOLT DOWN COVER MARKED "ELECTRICAL" (BL WALLACE DISTRIBUTION (714) 761-2071, BOX-C9EB, LID-C9R06). WHEN CONDUIT SIZE IS 2" AND ABOVE, CONTRACTOR SHALL USE TYPE 5 PB (18" X 28" X 18"D) WITH CONCRETE BOLT DOWN COVER MARKED "ELECTRICAL" (BL WALLACE DISTRIBUTION (714) 761-2071, BOX-N30, LID-N30R) . LEAVE 3' SLACK OF CONDUCTORS IN PULLBOX. SIZE PER SECTION 370-28, CEC. PROVIDE WITH McCAIN VANDAL RESISTANT PULL BOX INSERTS. 760/727-8100. SEE DETAIL D/E-3. 2. FUSE HOLDERS TO BE WATERPROOF AND UL LISTED. 3. ALL CONDUIT BELOW GRADE AND OUTSIDE OF PARKING LOT OR ROADWAY TO BE MINIMUM 1" PVC SCHEDULE 40. 5. ALL CONDUIT EXPOSED ABOVE GRADE AND INTERIOR TO BUILDINGS TO BE MINIMUM 1/2" EMT. 7. ALL BELOW GRADE CONDUIT SHALL BE SEALED UPON COMPLETION OF INSTALLATION. 4. ALL CONDUIT UNDER ROADWAY OR PARKING LOT TO BE SCHEDULE 80. 8. ALL ELECTRICIANS TO HAVE PROOF OF CALIFORNIA ELECTRICIANS CERTIFICATE/CREDENTIALS. CONCRETE UNDERGROUND PULLBOX. SEE DETAIL D/E-3 AND SPEC. 1. BELOW GRADE ELECTRICAL CONDUIT AND WIRE RUN. SEE PLANS FOR TYPE AND # OF WIRES. EXISTING ELECTRICAL PANEL. VERIFY EXACT LOCATION. INSTALLATION DETAILS 73 1 AREA LIGHT (DETAIL B/E-3) 10 30 LED BETA LIGHTING STR-LWY-3M-HT-03-E-UL-BK-700-40K-ML ADAPTER: PD-1H4-BK NEW POLE: PS4S20C-BK. EXISTING SINGLE HEAD 100 WATT MH LIGHT AND POLE TO BE REMOVED NEW TYPE 'A' SINGLE HEAD TYPE 5 LED AREA LIGHT. SEE DETAIL A/E-3 VICINITY MAP N.T.S. PROJECT SITE PRINCETON AVE PRINCETON AVE W. LOS ANGELES AVE MOOREPARK AVE SPRING ROAD 118 25.PLANS CONFORM WITH CAL GREEN BUILDING CODE 2011, WHICH REQUIRES ALL NEW LIGHTING SYSTEMS TO REDUCE ENERGY TO A MINIMUM OF 50%. * 146 2 AREA LIGHT (DETAIL C/E-3) 6 30 LED BETA LIGHTING (2) STR-LWY-3M-AA-03-E-UL-BK-700-40K 30 1 BUILDING LIGHT (DETAIL F/E-3) 5 18 LED NEW LIGHTING SYSTEM FIXTURES SHALL BE EQUIPPED WITH INTEGRAL OCCUPANCY SENSORS TO REDUCE POWER LEVELS TO 50% IN COMPLIANCE WITH CALIFORNIA GREEN BUILDING CODE 2011. * NEW TYPE 'C' SINGLE HEAD TYPE 4 LED AREA LIGHT. SEE DETAIL C/E-3 NEW TYPE 'D' BUILDING LIGHT WITH VANDAL CAGE. SEE DETAIL F/E-3 EXISTING LIGHTS TO BE REMOVED AND EXISTING POLES TO REMAIN. REPLACE FIXTURE ONLY. + + + + CONTRACTOR SHALL PROVIDE SUBMITTALS ON ALL LIGHTING PRODUCTS FOR CITY APPROVAL PRIOR TO PROCUREMENT. CONTRACTOR SHALL ALSO VERIFY QUANTITY OF LIGHTS PRIOR TO PROCUREMENT. C. 9. CONTRACTOR SHALL PROVIDE (4) REPLACEMENT POLES/ARMS. REPLACEMENT LIGHT POLES SHALL BE HADCO, MODEL# CPA10937 * MAXLITE MLSWP30LED50DS (WIREGAURD) 1 1 1 8 + PARKING LIGHT (DETAIL B/E-3) BETA LIGHTING STR-LWY-3M-HT-03-E-UL-BK-700-40K-ML ADAPTER: OKF-DB-2-8-BK 30 LED 73 NEW TYPE 'E' SINGLE HEAD TYPE 3 LED PARKING LIGHT. SEE DETAIL B/E-3 * 1 1

Upload: vutram

Post on 20-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

SHEET INDEX

E-1

SHEET # DESCRIPTION

E-2

E-4

E-3

DEMOLITION/ELECTRICAL PLAN PLAN

TITLE-24

TITLE SHEET, SCHEDULES, NOTES, LEGEND

MOORPARK, CA

TITLE-24 APPLICATION CATEGORIESSITE ADDRESS:500 POINDEXTER AVENUEMOORPARK, CA. 93021SEE SHEET E-4 FOR MANDATORY MEASURES.

A LIGHTING POWER ALLOWANCE FOR GENERAL HARDSCAPE-ALL DRIVEWAY'S, PARKINGSTALLS AND PLANTING ISLANDS, SIDEWALKS, STAIRS=18,680 WATTS.TOTAL INSTALLED WATTS=3,859. COMPLIES. (OLTG-1C PART 4 OF 4)

CATALOG NO.

LAMPS

LUMINAIRE SCHEDULESYMBOL

12

0

FIXTURE

LED

LPS

IND

UC

HPS

MH

48

0

20

82

40

VOLTS

TYPENO

.

SPE

CIA

L

MOUNTING

WATT

S

H2

0

WEL

LSURF DESCRIPTION

POLE

MFR &

HALO

G

TYPECOUNT

401

AREA LIGHT(DETAIL A/E-3)31 36

LED

ANP LIGHTINGFIXTURE: BVA01-H40W/350mA/4000K/TYPE5/SMALL DISK

PRIVATE ELECTRICAL SYSTEM SHALL NOT BE JOINT TRENCH WITH PUBLIC UTILITY SYSTEM.

CONSTRUCTION NOTES

ALL 90 DEGREE ELBOWS TO BE FACTORY MADE BENDS.

ALL WORK TO BE IN ACCORDANCE WITH THE 2010 CEC AND ALL APPLICABLE FEDERAL, STATE AND LOCALCODES.

ALL MATERIALS AND EQUIPMENT SHALL BE COMMERCIAL AND SHALL CARRY A U.L. LABEL.

14.15.

4.

A.MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW ANDSUCH AS APPEAR ON THE UNDERWRITER'S LABORATORIES LIST OF APPROVED ITEMS AND SHALL MEETREQUIREMENTS OF ASTM, IEEE, 2010 NEC, NEMA, AND OTHER RECOGNIZED STANDARDS AND SHALL BESIZED IN CONFORMITY WITH REQUIREMENTS OF THE NATIONAL ELECTRIC CODE AND OTHER APPLICABLECODES, WHICHEVER ARE MORE STRINGENT.

B.

FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS TO PERFORM ELECTRICAL WORK SHOWN,NOTED OR SCHEDULED FOR A COMPLETE AND FINISHED INSTALLATION.

2.

1. THE GENERAL CONDITIONS AND SUPPLEMENTARY GENERAL CONDITIONS SHALL BE CONSIDERED AS PARTOF THE SPECIFICATION.

THE WORD "PROVIDE" AS USED HEREIN MEANS TO FURNISH AND INSTALL COMPLETE.3.

SECURE AND PAY FOR ALL REQUIRED PERMITS AND INSPECTION CERTIFICATES.5.ABOVE GRADE CONDUIT SHALL BE STANDARD RIGID STEEL ACCORDING TO CODE REQUIREMENTS.CONDUIT SHALL BE CONCEALED IN FINISHED AREAS, EXCEPT AS OTHERWISE APPROVED BY ARCHITECT.RIGID CONNECTIONS SHALL BE COMPRESSION TYPE. UNDERGROUND CONDUIT SHALL BE SCHEDULE 40OR 80 PVC BURIED A MINIMUM OF 24".

6.

WIRE SHALL BE SINGLE CONDUCTOR COPPER WITH 600 VOLT INSULATION. ALUMINUM CONDUCTORS ARENOT PERMITTED. #12 AND SMALLER SHALL BE SOLID. #10 AND LARGER SHALL BE STRANDED. MINIMUMWIRE SIZE SHALL BE #10. ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE SITE INUNBROKEN PACKAGES. ALL WIRING OF ANY TYPE SHALL BE IN CONDUIT.

7.

GENERAL WIRING SHALL BE THWN OR THHN.A.

ABOVE GRADE WIRE CONNECTORS SHALL BE BY "SCOTCHLOCK" OR EQUAL FOR #8 OR SMALLER AND T&B"LOCK-TITE" FOR #6 AND LARGER.

8.

THIS CONTRACTOR SHALL DO ALL CUTTING, CHASING OR CHANNELING AND PATCHING REQUIRED FOR ANYWORK UNDER THIS DIVISION. ANY CUTTING SHALL HAVE PRIOR APPROVAL OF THE OWNER.

9.

PROVIDE SAFETY AND DISCONNECT SWITCHES, SHALL BE FUSED OR NON-FUSED AS CALLED FOR ONDRAWINGS AND AS REQUIRED BY CODE. SWITCHES SHALL BE HEAVY DUTY, LOAD AND HORSEPOWERRATED AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC OR EQUAL.

10.

JUNCTION, PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL, CODE GAUGE SIZE AND ACCESSIBLE.11.

ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN HIS WORK AS THE JOB PROGRESSES,AND UPON COMPLETION SHALL TURN OVER TO THE OWNER A "RECORD" SET OF PRINTS SHOWING THECHANGES.

12.

ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICINGMAINTAINING AND REPAIRING. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL, SUCH AS CHANNELS,RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK AND SHALL BE FASTENED TO STEEL,CONCRETE OR MASONRY, BUT NOT TO PIPING. ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE.EXPOSED CONDUITS SHALL BE IN STRAIGHT LINES PARALLEL WITH OR AT RIGHT ANGLES TO COLUMN LINESOR BEAMS AND SEPARATED AT LEASED 3" FROM WATER LINES WHEREVER THEY RUN ALONGSIDE ORACROSS SUCH LINES. CONDUCTORS SHALL BE ON CONDUIT, DUCTS, OR APPROVED RACEWAYS.

13.

CONTRACTOR TO MAINTAIN PROPER SEPARATION AS REQUIRED BY THE UTILITY COMPANIES. 16.CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING FOR ANY AND ALL UTILITY AND CITY INSPECTIONS. 17.

18.ALL GROUND CONDUCTORS SHALL BE SPLICED TOGETHER WITH APPROVED CONNECTOR AT PULL BOXESAND CONNECTED TO GROUND LUG INSIDE POLE.

19.SEE IMPROVEMENT PLANS FOR SITE, SEWER AND WATER (ETC.) IMPROVEMENTS PRIOR TO START OFCONSTRUCTION.

20.CONTRACTOR SHALL CONTACT "DIG ALERT" FOR MARK-OUT PRIOR TO TRENCHING AS REQUIRED.

21.THESE PLANS ARE SCHEMATIC AND ARE FOR THE PURPOSE OF SHOWING HOW TO CONNECT THEELECTRICAL SYSTEM. WHILE THE DRAWING IS AT ACTUAL SCALE, THE SYMBOLS REFERENCED ARE NOT,AND MAY APPEAR TO SHOW THE EQUIPMENT IN PLACES NOT INTENDED. THE CONTRACTOR IS TO FIELDVERIFY ALL UTILITY COMPANY SERVICE POINTS/METER LOCATIONS, POLES, PULL BOXES BUILDING LIGHTLOCATIONS, SERVICE EQUIPMENT LOCATIONS AND OTHER ELECTRICAL APPURTENANCES PRIOR TO STARTOF CONSTRUCTION. ANY DISCREPANCIES ARE TO BE ADDRESSED TO THE CITY BY MEANS OF A "REQUESTFOR INFORMATION" (RFI). CONTRACTOR IS TO VERIFY ALL LIGHT LOCATIONS WITH THE CITY PRIOR TOSTART OF CONSTRUCTION AND DURING STAKING. REFER TO LIGHT STANDARD DETAIL FOR STANDARDS.CONTRACTOR SHALL CONTACT "DIG ALERT" FOR MARK-OUT PRIOR TO TRENCHING ASREQUIRED.CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS PRIOR TO START OF CONSTRUCTION AS THEBASE MAP IS NOT A CIVIL ENGINEER GENERATED MAP, BUT HAS BEEN DRAWN FROM A GOOGLE EARTHIMAGE AND MAY NOT BE ENTIRELY SCALED AND DRAWN CORRECTLY.

22.PANEL CIRCUIT DIRECTORY TO COMPLY WITH SECTION 408.4, CEC.23.NATIVE SOIL SHALL BE ACCEPTABLE FOR TRENCH BACK FILL PROVIDED THAT THE FILL MATERIAL USED

SHALL PASS THROUGH A 1" SIEVE (CITY OF MOORPARK BACKFILL ORDINANCE). SEE NOTES & DETAIL C/E-3.24.CONTRACTOR SHALL LABEL EACH CIRCUIT WITH PHENOLIC PLASTIC LABEL TAGS IN ANY DEVICE THAT HAS

ACCESS. THIS SHALL INCLUDE LIGHT POLES, PULL BOXES, PANELS, AND ETCETERA. PANEL, CIRCUITNUMBER AND VOLTAGE SHALL BE IDENTIFIED. TAGS SHALL BE AFFIXED WITH NYLON ZIP-TIES.

LEGEND

NEW TYPE 'B' SINGLE HEAD TYPE 5 LED AREA/ PARKING LIGHT. SEE DETAIL B/E-3

SPECIFICATIONS

6. ALL SPLICES BELOW GRADE SHALL BE MADE IN APPROVED PULL BOXES AND SHALL BE WATERTIGHT.USE ONLY EPOXY ENCAPSULATED TYPE 3M BAGS OR EQUAL.

1. ALL PULL BOXES TO BE TYPE 3-1/2 PB (10-1/2" X 17-1/2" X 12"D) WITH CONCRETE BOLT DOWN COVERMARKED "ELECTRICAL" (BL WALLACE DISTRIBUTION (714) 761-2071, BOX-C9EB, LID-C9R06). WHENCONDUIT SIZE IS 2" AND ABOVE, CONTRACTOR SHALL USE TYPE 5 PB (18" X 28" X 18"D) WITHCONCRETE BOLT DOWN COVER MARKED "ELECTRICAL" (BL WALLACE DISTRIBUTION (714) 761-2071,BOX-N30, LID-N30R) . LEAVE 3' SLACK OF CONDUCTORS IN PULLBOX. SIZE PER SECTION 370-28, CEC.PROVIDE WITH McCAIN VANDAL RESISTANT PULL BOX INSERTS. 760/727-8100. SEE DETAIL D/E-3.

2. FUSE HOLDERS TO BE WATERPROOF AND UL LISTED.3. ALL CONDUIT BELOW GRADE AND OUTSIDE OF PARKING LOT OR ROADWAY TO BE MINIMUM 1" PVC

SCHEDULE 40.

5. ALL CONDUIT EXPOSED ABOVE GRADE AND INTERIOR TO BUILDINGS TO BE MINIMUM 1/2" EMT.

7. ALL BELOW GRADE CONDUIT SHALL BE SEALED UPON COMPLETION OF INSTALLATION.

4. ALL CONDUIT UNDER ROADWAY OR PARKING LOT TO BE SCHEDULE 80.

8. ALL ELECTRICIANS TO HAVE PROOF OF CALIFORNIA ELECTRICIANS CERTIFICATE/CREDENTIALS.

CONCRETE UNDERGROUND PULLBOX. SEE DETAIL D/E-3 AND SPEC. 1.

BELOW GRADE ELECTRICAL CONDUIT AND WIRE RUN. SEE PLANS FOR TYPE AND # OF WIRES.

EXISTING ELECTRICAL PANEL. VERIFY EXACT LOCATION.

INSTALLATION DETAILS

731

AREA LIGHT(DETAIL B/E-3)10 30

LED

BETA LIGHTINGSTR-LWY-3M-HT-03-E-UL-BK-700-40K-MLADAPTER: PD-1H4-BKNEW POLE: PS4S20C-BK.

EXISTING SINGLE HEAD 100 WATT MH LIGHT AND POLE TO BE REMOVED

NEW TYPE 'A' SINGLE HEAD TYPE 5 LED AREA LIGHT. SEE DETAIL A/E-3

VICINITY MAP N.T.S.

PROJECT SITEPRINCETON AVE

PRINCETON AVE

W. LOS ANGELES AVE

MO

OREP

ARK

AVE

SPR

ING

RO

AD

118

25.PLANS CONFORM WITH CAL GREEN BUILDING CODE 2011, WHICH REQUIRES ALL NEW LIGHTING SYSTEMSTO REDUCE ENERGY TO A MINIMUM OF 50%.

*146

2

AREA LIGHT(DETAIL C/E-3)6 30

LED

BETA LIGHTING(2) STR-LWY-3M-AA-03-E-UL-BK-700-40K

301

BUILDING LIGHT(DETAIL F/E-3)5 18

LED

NEW LIGHTING SYSTEM FIXTURES SHALL BE EQUIPPED WITH INTEGRAL OCCUPANCY SENSORS TO REDUCE POWER LEVELS TO 50% IN COMPLIANCE WITH CALIFORNIA GREEN BUILDING CODE 2011.*

NEW TYPE 'C' SINGLE HEAD TYPE 4 LED AREA LIGHT. SEE DETAIL C/E-3

NEW TYPE 'D' BUILDING LIGHT WITH VANDAL CAGE. SEE DETAIL F/E-3

EXISTING LIGHTS TO BE REMOVED AND EXISTING POLES TO REMAIN. REPLACE FIXTURE ONLY.+

+

+

+

CONTRACTOR SHALL PROVIDE SUBMITTALS ON ALL LIGHTING PRODUCTS FOR CITY APPROVAL PRIOR TOPROCUREMENT. CONTRACTOR SHALL ALSO VERIFY QUANTITY OF LIGHTS PRIOR TO PROCUREMENT.

C.

9. CONTRACTOR SHALL PROVIDE (4) REPLACEMENT POLES/ARMS. REPLACEMENT LIGHT POLES SHALL BEHADCO, MODEL# CPA10937

*MAXLITEMLSWP30LED50DS (WIREGAURD)

1

1

18+PARKING LIGHT(DETAIL B/E-3)

BETA LIGHTINGSTR-LWY-3M-HT-03-E-UL-BK-700-40K-MLADAPTER: OKF-DB-2-8-BK

30LED

73

NEW TYPE 'E' SINGLE HEAD TYPE 3 LED PARKING LIGHT. SEE DETAIL B/E-3

*

1

1

1

PLAN NOTES

EXISTING LIGHTING CONTROLS/ELECTRICAL PANEL. VERIFY LOCATION.

ELECTRICAL PULLBOX. SEE INSTALLATION DETAIL E/E-3 AND SPEC. 1/E-12

3

4

PROVIDE 1 1/2" C- 2#10, 1#10 GND. BURY 24" BELOW GRADE.

2

(TYP.ALL)

3

CONTRACTOR TO REMOVE EXISTING LIGHT AND POLE AND DISPOSE OF ACCORDINGLY.CONTRACTOR TO DEMOLISH EXISTING CONCRETE POLE BASE TO 1' BELOW TURF OR ASDIRECTED BY THE CITY AND INSTALL AN ELECTRICAL PULL BOX. SEE INSTALLATION DETAIL E/E-3AND SPEC. 1/E-1

6 CONTRACTOR SHALL POUR CONCRETE COLLAR AROUND POLE BASE. SEE DETAIL B/E-3.

MATCHLINE - SEE ABOVE RIGHT

MATCHLINE - SEE BELOW LEFT

(TYP.ALL)

4

1

5 NEW POLE/LIGHT LOCATION. SEE INSTALLATION DETAIL B/E-3.

(TYP.ALL)

5

(TYP.10)

6

(TYP.ALL)

7

(TYP.ALL)

8 CONTRACTOR TO REMOVE EXISTING LIGHT AND DISPOSE OF ACCORDINGLY AND REPLACEEXISTING LUMINAIRE WITH NEW TYPE 'E' LIGHT. SEE DETAIL B/E-3.

8

(TYP.8)

10

10 ALL LIGHT POLES IN THIS AREA TO BE REMOVED AND REPLACED WITH NEW.

11 SEE DETAIL F/E-3 FOR BUIDING LIGHTS

11 7

(TYP.3)

9

(TYP.6)

9 CONTRACTOR TO REMOVE EXISTING LIGHTS AND DISPOSE OF ACCORDINGLY AND REPLACEEXISTING LUMINAIRES WITH NEW TYPE C LIGHT. SEE DETAIL C/E-3.

12 CONTRACTOR SHALL PROVIDE A SEPARATE LIGHTING CIRCUIT FOR THE LIGHTS SHOWN IN THECLOUDED AREA. WIRE SIZE SHALL BE EQUAL TO WHAT IS CURRENTLY PROVIDED. PROVIDE 20A,1-POLE BREAKER IN SPARE POSITION AND CONTROL VIA PHOTOCELL FOR ALL NIGHT CONTROL.

12

4

7 CONTRACTOR TO REMOVE EXISTING LIGHT AND DISPOSE OF ACCORDINGLY AND REPLACEEXISTING LUMINAIRE WITH NEW TYPE A LIGHT. SEE DETAIL A/E-3.

1 CONTRACTOR SHALL PROVIDE AND INSTALL (4) REPLACEMENT PEDESTRIAN LIGHT POLES ONEXISTING FOUNDATIONS. LOCATIONS TO BE DETERMINED BY CITY'S PARK AND LANDSCAPEMANAGER. SEE SPECIFICATION NOTE 9 ON SHEET E-1.

GENERAL NOTES

1

1

1

Phase 3

Phase 2

Phase 2

Phase 1

JSandifer
Polygon
JSandifer
Polygon
JSandifer
Polygon
JSandifer
Highlight
JSandifer
Highlight
JSandifer
Highlight
JSandifer
Polygon
JSandifer
Highlight

B TYPE 'B, E' LIGHTINSTALLATION DETAIL

SQUARE BOLT COVER

GROUND LUG

20

' MAX

HANDHOLE TOFACE SIDEWALK

NEW AND REPLACEMENT TYPE 'B, E'LED FIXTURE. SEE FIXTURE

SCHEDULE.REPLACEMENT FIXTURE IS FOR

PARKING FIELD ONLY.

GRADE

CONDUIT AND WIRE ASSHOWN ON PLANS

4" SQUARE STRAIGHTSTEEL POLE. SEE

FIXTURE SCHEDULE

1"C-2#10, 1#10 GND.

ALL CONNECTIONS SHALL BEWATER-TIGHT. SEE SPEC. 6.

NON-SHRINKDRY-PACK GROUT

UNDER BASE PLATE

REBAR: 4#4 VERT. x W/ #3HORIZONTAL TIES 12" OC WITH

3#3 WITHIN TOP 12".MIN. 3" CONCRETE COVER.

560-C-3250 P.C.C.AGAINSTUNDISTURBED OR COMPACTED

(95% MIN.) EARTH.

D TRENCHINSTALLATION DETAIL

TRENCH WIDTHAS REQUIREDFOR CONDUITS.

BACKFILL MATERIAL:THE MATERIAL USED FOR BACKFILLING THE TRENCH ABOVETHE SHADING MATERIAL AND EXTENDING UPWARD TO THESUBGRADE SHALL BE FREE OF ROCKS OR CLODS LARGERTHAT 6" IN ANY DIMENSION. THE COARSE MATERIAL SHALL BEWELL DISTRIBUTED THROUGHOUT THE FINER MATERIAL. THEAMOUNT OF ROCKS OR CLODS SHALL BE LIMITED, IN THEOPINION OF THE INSPECTOR. THE BACKFILL MATERIAL SHALLMEET THE REQUIREMENTS OF ALL APPLICABLE CODES,ORDINANCES AND CITY STANDARDS AND BE FREE OF DEBRISAND ORGANIC MATTER. SLURRY BACKFILL MAY BE REQUIREDBY CITY INSPECTOR. CHECK WITH CITY PRIOR TO START OFCONSTRUCTION.

SHADING MATERIAL AND INSTALLATION:NATURAL SAND, MANUFACTURED SAND, DECOMPOSEDGRANITE, ROCK FREE SANDY LOAM. SEE CITY BACKFILLORDINANCE. AGGREGATE MATERIAL SHALL BE CAPABLE OFPASSING THROUGH A 12" SIEVE. GRAVEL SHALL NOT AMOUNTTO MORE THAN 50% OF MIXTURE. SCREENING OR OTHERSUITABLE MEANS MAY BE REQUIRED AT THE INSPECTORSDISCRETION.THE EARTH TRENCH BOTTOM SHALL BE STABLE WITH AUNIFORM GRADE CONTAINING NO HARD CLODS, ROCKS, ANDETCETERA. THAT MAY DAMAGE THE CONDUIT. IF IN THEOPINION OF THE INSPECTOR, THE CONDUIT MAY BE DAMAGEDDURING COMPACTION, A 3" SHADE OF MATERIAL ABOVE ANDBELOW THE CONDUIT MAY BE REQUIRED.

COMPACTION:SHADING AND BACKFILL SHOULD BE COMPACTED INACCORDANCE WITH GOVERNMENTAL AGENCIES AND SHALLHAVE A MINIMUM OF 90% RELATIVE COMPACTION. VERIFYREQUIREMENTS WITH INSPECTOR.

GRADE

CONDUIT ANDWIRING, SEE

PLANS.

CONCRETE UNDERGROUNDPULL BOX.SEE SPEC. 1/E-1

10"

3"

1" SMOOTH ROCKBEDDING 3" BEYONDSIDES OF BOX AND 10"DEEP. 3" INSIDE OF BOX.

ALL BELOW GRADE CONNECTIONSSHALL BE WATER PROOF. SEE SPEC.6/E-1. PROVIDE 3' MIN. SLACK INPULLBOX.

3"

CONDUIT ANDWIRING, SEE PLANS.

GRADE

PULL BOXINSTALLATION DETAILE

12"

ANCHOR BOLTS (4)3/4" R x 30" L x 3" H

WITH APPROVEDGND. CONNECTOR

15' #4 BARE COPPERGROUND WIRE.

HOLD BASE DOWNTHICKNESS OF

SIDEWALK

SIDEWALK

POLEBASE

CONCRETE COLLAR. POUR 1'LARGER THAN POLE BASE. INSTALLCONCRETE EXPANSION JOINT FELTBETWEEN EXISTING SIDEWALK AND

COLLAR

CONCRETE PULLBOX AT EACHPOLE WITHIN 5'. SEE SPEC. 1.

A TYPE 'A' LIGHTINSTALLATION DETAIL

GRADE

10

' MAX

TYPE 'D' LIGHTINSTALLATION DETAILF

C TYPE 'C' LIGHTINSTALLATION DETAIL

TYPE 'D' LIGHT

NO TILT ON LIGHT

REPLACEMENTLIGHTING. TYPE A LEDFIXTURE. SEE FIXTURE

SCHEDULE.

EX. ROUNDSTRAIGHT

STEEL POLE.

MOUNT LUMINAIRE TO EXISTINGBULLHORN MOUNTS WITH THE

PROVIDED ADAPTER. SEE FIXTURESCHEDULE. CONTRACTOR SHALLVERIFY BOLL-HORN SIZE DURING

SUBMITTAL PROCESS AND PRIORTO ORDERING!

REPLACEMENTLIGHTING. TYPE C LEDFIXTURE. SEE FIXTURESCHEDULE.

CONTRACTOR TO REMOVEEXISTING LIGHT AND DISPOSE

OF ACCORDINGLY ANDREPLACE EXISTING LUMINAIREWITH NEW TYPE D LIGHT WITH

VANDAL RESISTANT CAGE.

BASE PLATE FOR EXISTING LIGHT POLES. NEW POLES TO MATCH EXISTING ANCHORBOLT PATTERN

SEE DETAILBELOW

CENTER BULL-HORN WILL NOTHAVE LIGHT. PROVIDE CAP ONHORN TO PROTECT AGAINSTWATER ENTRY. PAINT TO MATCH.SAFE-OFF EXISTING ELECTRICALWIRES WITH APPROVED CAPS.

1

1

1

1

1