PRESTIGE ALUMINIUM Skirting and Dado Trunking System Contents A Introduction E Product Classification B Tools & Sundries F Disposal Instructions C Planning the Installation G Service and Maintenance D Installing the System H Guarantee Please leave this leaflet with the end user for future reference 42998PL Ed.2 A. INTRODUCTION A1 TRUNKING The Prestige Plus trunking system comprises 3 trunking profiles designated as follows:- A2 TRUNKING COMPONENTS Note:- All the trunking components are available individually and assembled to produce the desired profile (as below). Profile L 170 x 50mm Dado Trunking System Profile M 170 x 50mm Skirting Trunking System Profile N 212 x 50mm Skirting Trunking System The profiles are made up using the main carrier VTS/1 ALM on to which are clipped the appropriate trunking covers and base extension (profile N only). Cross Sectional Areas 1= 1463 mm 2 2= 3506 mm 2 3= 1597 mm 2 4= 3602 mm 2 1. Profile L uses: 1 off each VTS/1 ALM, VTS/5 ALM, and 2 off VTS/14 ALM. 2. Profile M uses: 1 off each VTS/1 ALM, VTS/4 ALM, VTS/5 ALM and VTS/14 ALM. 3. Profile N uses: 1 off each VTS/1 ALM, VTS/2 ALM, VTS/14 ALM and 2 off VTS5/ALM. A3. FITTINGS A4. FABRICATED FITTINGS (FLAT ANGLES AND FLAT TEES) EXTERNAL CORNER INTERNAL CORNER COUPLER END CAP PROFILE L PROFILE M PROFILE N PROFILE L PROFILE M PROFILE N UP DOWN UP DOWN FLAT TEES FLAT ANGLES B. TOOLS AND SUNDRIES REQUIRED FOR INSTALLATION C. PLANNING THE INSTALLATION It is IMPORTANT to spend some time planning the installation, before starting. Time spent on planning the layout at this stage can avoid mistakes later on. 1. Surface to which the trunking is to be installed should be flat and prepared for decorating. 2. Establish the layout of the trunking run with particular attention to the following:- 2.1 Changes in direction of the trunking. 2.2 The position of any feeds to or from the system. 2.3 The position of ant connections with existing trunking/wiring systems. 2.4 When mounting profiles L and M, at floor level, a gap of 5.0 mm minimum should be left between the lower edge of the Main Carrier and the top surface of the floor finish. 2.5 When mounting profile n at floor level, a gap of 3.0mm minimum should be left between the underside Extension Carrier and the top surface of the floor finish. 2.6 Minimum distance between two corners is 130mm. See section D2. 1. Fine toothed tenon saw or a hacksaw with an 32-36 TPI blade for cutting trunking or preferably a circular saw with a 350mm diameter fine tungsten tipped blade (100 TPI approx). 2. A suitable mitre block for cutting trunking base and lid. (We recommend the use of a mitre block, MK List no. KB/2). 3. All purpose utility knife for trimming of trunking. 4. Spirit level, Plumb Bob and Chalk Line. 5. A range of screwdrivers (flat or cross point) to suit fixing screws. (see 7 below). 6. A 5.5mm diameter drill bit. 7. Fixing screws for fixing trunking. No. 8, Roundhead or Panhead. 8. Washers to suit fixing screws. 9. Suitable wall fixing (if required) to enable No.8 screws to screw securely into the mounting surface. 10.Soft faced mallet (to aid lid fitting). A7. SPARE PARTS The following items are available separately if required. Description Part No. PROFILE L External Corner Cover VTS/46 Internal Corner Cover VTS/36 Joint Cover VTS/96 End Cap Cover VTS/26 PROFILE M External Corner Cover VTS/47 Internal Corner Cover VTS/37 Joint Cover VTS/97 End Cap Cover (R/H) VTS/27R End Cap Cover (L/H) VTS/27L PROFILE N External Corner Cover VTS/48 Internal Corner Cover VTS/38 Joint Cover VTS/98 End Cap Cover (R/H) VTS/28R End Cap Cover (L/H) VTS/28L Extension Carrier Coupler VTS/17 External Corner Extension Carrier VTS/44 Internal Corner Extension Carrier VTS/34 Extension End Cap Retainer (R/H) VTS/19R Extension End Cap Retainer (L/H) VTS/19L COMMON SYSTEM COMPONENTS Carrier Coupler VTS/16 End Cap Retainer VTS/18 External Corner Carrier VTS/8 Internal Corner Carrier VTS/7 Carrier Earth Connector PAL 1000 Lid Earth Connector PAL 1001 List No. VTS/LE List No. VTS/LI List No. VTS/LC List No. VTS/LS List No. VTS/FAL/ALM List No. VTS/ME List No. VTS/MI List No. VTS/MC List No. VTS/MS List No. VTS/NE List No. VTS/NI List No. VTS/NC List No. VTS/NS List No. VTS/FAS/U/ALM List No. VTS/FAM/D/ALM List No. VTS/TML/ALM List No. VTS/TMD/ALM List No. VTS/FAN/U/ALM List No. VTS/FAN/D/ALM List No. VTS/TNL/ALM List No. VTS/TNK/ALM 1 Gang 2 Gang 25mm Deep 35mm Deep List No. VTS/6025 List No. VTS/7025 List No. VTS/8028 List No. VTS/6035 List No. VTS/7035 List No. K3716 ACCESSORY MOUNTING BOXES A5. COMMON SYSTEM COMPONENTS The following components can be used with any of the 3 profiles, (L, M or N) VTS/82 (YT1-3) and VTS/83 (YT4) Mini Trunking Adaptor VTS/90 Cross Over Bridge VTS/12/ALM Square and Recessed Cable Retainer VTS/11/ALM Straight Cable Retainer VTS/50 Cable Divider 3 Gang 28mm Deep A6. BRASS EARTHING TERMINALS FOR OUTLET BOX Optional push fit earth terminal for maintaining earth continuity in boxes. CARRIERS COVERS VTS/1/ALM Main Carrier VTS/2/ALM Extension Carrier VTS/14/ALM Curved Cover VTS/5/ALM Straight Cover VTS/4/ALM Square Cover Profile L Profile L Profile L Profile L Profile L Profile L Profile M Profile M Profile M Profile M Profile M Profile M Profile M Profile M Profile D Profile N Profile N Profile N Profile N Profile N Profile N Profile L Profile N Profile N Profile K VTS/81 (YT1 -3) and VTS/814 (YT4) Mini Trunking Adaptor VTS/84 (20mm) and VTS/85 (25mm) Conduit Adaptor 1 1 1 2 2 2 1 3 4 List No. VTS/TLL/ALM

Upload: others

Post on 14-May-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PRESTIGE ALUMINIUM A1 TRUNKING A2 TRUNKING … MK... · Please leave this leaflet with the end user for future reference 42998PL Ed.2 A. INTRODUCTION A1 TRUNKING The Prestige Plus

PRESTIGE ALUMINIUM™

Skirting and Dado Trunking System

Contents

A Introduction E Product Classification

B Tools & Sundries F Disposal Instructions

C Planning the Installation G Service and Maintenance

D Installing the System H Guarantee

Please leave this leaflet with the end user for future reference

42998PL Ed.2

A. INTRODUCTION

A1 TRUNKING

The Prestige Plus trunking system comprises 3 trunking profiles designated as follows:-

A2 TRUNKING COMPONENTS

Note:- All the trunking components are available individuallyand assembled to produce the desired profile (as below).

Profile L

170 x 50mm

Dado Trunking System

Profile M

170 x 50mm

Skirting Trunking System

Profile N

212 x 50mm

Skirting Trunking System

The profiles are made up using the main carrier VTS/1 ALM on to which are clipped the appropriate trunking covers and base extension (profile N only).

Cross Sectional Areas1= 1463 mm2

2= 3506 mm2

3= 1597 mm2

4= 3602 mm2

1. Profile L uses:1 off each VTS/1 ALM, VTS/5 ALM,and 2 off VTS/14 ALM.

2. Profile M uses:1 off each VTS/1 ALM, VTS/4 ALM,VTS/5 ALM and VTS/14 ALM.

3. Profile N uses:1 off each VTS/1 ALM, VTS/2 ALM,VTS/14 ALM and 2 off VTS5/ALM.

A3. FITTINGS A4. FABRICATED FITTINGS (FLAT ANGLES AND FLAT TEES) EXTERNAL CORNER INTERNAL CORNER COUPLER END CAP

PROFILE

L

PROFILE

M

PROFILE

N

PROFILE

L

PROFILE

M

PROFILE

N

UP DOWN UP DOWN

FLAT TEESFLAT ANGLES

B. TOOLS AND SUNDRIES REQUIRED FOR INSTALLATION

C. PLANNING THE INSTALLATION

It is IMPORTANT to spend some time planning the

installation, before starting. Time spent on planning the

layout at this stage can avoid mistakes later on.

1. Surface to which the trunking is to be installed should

be flat and prepared for decorating.

2. Establish the layout of the trunking run with particular

attention to the following:-

2.1 Changes in direction of the trunking.

2.2 The position of any feeds to or from the system.

2.3 The position of ant connections with existing

trunking/wiring systems.

2.4 When mounting profiles L and M, at floor level, a

gap of 5.0 mm minimum should be left between the

lower edge of the Main Carrier and the top surface

of the floor finish.

2.5 When mounting profile n at floor level, a gap of

3.0mm minimum should be left between the

underside Extension Carrier and the top

surface of the floor finish.

2.6 Minimum distance between two corners is 130mm.

See section D2.

1. Fine toothed tenon saw or a hacksaw with an 32-36

TPI blade for cutting trunking or preferably a circular

saw with a 350mm diameter fine tungsten tipped blade

(100 TPI approx).

2. A suitable mitre block for cutting trunking base and lid.

(We recommend the use of a mitre block, MK List no.

KB/2).

3. All purpose utility knife for trimming of trunking.

4. Spirit level, Plumb Bob and Chalk Line.

5. A range of screwdrivers (flat or cross point) to suit fixing

screws. (see 7 below).

6. A 5.5mm diameter drill bit.

7. Fixing screws for fixing trunking. No. 8, Roundhead or

Panhead.

8. Washers to suit fixing screws.

9. Suitable wall fixing (if required) to enable No.8

screws to screw securely into the mounting surface.

10.Soft faced mallet (to aid lid fitting).

A7. SPARE PARTSThe following items are available separately if required.

Description Part No.PROFILE LExternal Corner Cover VTS/46Internal Corner Cover VTS/36Joint Cover VTS/96End Cap Cover VTS/26PROFILE MExternal Corner Cover VTS/47Internal Corner Cover VTS/37Joint Cover VTS/97End Cap Cover (R/H) VTS/27REnd Cap Cover (L/H) VTS/27LPROFILE NExternal Corner Cover VTS/48Internal Corner Cover VTS/38Joint Cover VTS/98End Cap Cover (R/H) VTS/28REnd Cap Cover (L/H) VTS/28LExtension Carrier Coupler VTS/17External Corner Extension Carrier VTS/44Internal Corner Extension Carrier VTS/34Extension End Cap Retainer (R/H) VTS/19RExtension End Cap Retainer (L/H) VTS/19LCOMMON SYSTEM COMPONENTSCarrier Coupler VTS/16End Cap Retainer VTS/18External Corner Carrier VTS/8Internal Corner Carrier VTS/7Carrier Earth Connector PAL 1000Lid Earth Connector PAL 1001

List No. VTS/LE List No. VTS/LI List No. VTS/LC List No. VTS/LS

List No. VTS/FAL/ALM

List No. VTS/ME List No. VTS/MI List No. VTS/MC List No. VTS/MS

List No. VTS/NE List No. VTS/NI List No. VTS/NC List No. VTS/NS

List No. VTS/FAS/U/ALM List No. VTS/FAM/D/ALM List No. VTS/TML/ALM List No. VTS/TMD/ALM

List No. VTS/FAN/U/ALM List No. VTS/FAN/D/ALM List No. VTS/TNL/ALM List No. VTS/TNK/ALM

1 Gang 2 Gang

25mmDeep

35mmDeep

List No. VTS/6025 List No. VTS/7025 List No. VTS/8028

List No. VTS/6035 List No. VTS/7035 List No. K3716

ACCESSORY MOUNTING BOXESA5. COMMON SYSTEM COMPONENTS

The following components can be used with any of the 3 profiles, (L, M or N)

VTS/82 (YT1-3) and VTS/83 (YT4)Mini Trunking Adaptor

VTS/90 Cross Over Bridge

VTS/12/ALM Square and RecessedCable Retainer VTS/11/ALM Straight Cable RetainerVTS/50 Cable Divider

3 Gang

28mmDeep

A6. BRASS EARTHING TERMINALS FOROUTLET BOX

Optional push fit earth terminal formaintaining earth continuity in boxes.

CARRIERS COVERS

VTS/1/ALMMain Carrier

VTS/2/ALMExtension Carrier

VTS/14/ALMCurved Cover

VTS/5/ALMStraight Cover

VTS/4/ALMSquare Cover

Profile L

Profile L

Profile L

Profile L

Profile L

Profile LProfile M

Profile M

Profile M

Profile M

Profile M

Profile M

Profile M

Profile M

Profile D

Profile N

Profile N

Profile N

Profile N

Profile N

Profile N

Profile L

Profile N

Profile N

Profile K

VTS/81 (YT1 -3) and VTS/814 (YT4) Mini Trunking Adaptor

VTS/84 (20mm) andVTS/85 (25mm) Conduit Adaptor

1 1 1

2 2 2

1 3

4

List No. VTS/TLL/ALM

Page 2: PRESTIGE ALUMINIUM A1 TRUNKING A2 TRUNKING … MK... · Please leave this leaflet with the end user for future reference 42998PL Ed.2 A. INTRODUCTION A1 TRUNKING The Prestige Plus

D. INSTALLING THE SYSTEMTo ensure a safe installation, this product should be installed by a competent person, in accordance with the 16th Edition of the IEE Wiring Regulations (BS 7671).

INSTALLING TRUNKING CARRIERS

For each length of trunking:

1. When mounting trunking at skirting level, allowance should be made for the thickness of floor finish (i.e. carpet, wood blocks etc.) and a suitable gap left below the main carrier (or extension carrier when installing profile N), to accept this.

2. Cut Trunking Carrier, making dimensional allowance for fittings.

3. Both the Main Carrier (VTS/1 ALM) and the Extension Carrier (VTS/2 ALM) are pre-drilled at 300mm intervals along their length to facilitate screwing into the wall. See Note f.

4. Assemble appropriate fittings to carrier and then fix them to the wall havingprepared fixing holes in the wall. Fixings to be at 600mm centres and also at points within 100mm of each end.

5. For profile N repeat the above process having first clipped the Corner Extensions to their respective Corner Carriers.

6. For all further lengths of Trunking repeat the above sequence.

Note:a) On long runs of Trunking, allowance should be made for thermal expansion.

The fixing screws (fitted with suitable washers) should be screwed into the wall, tightened firmly, and then backed off slightly to allow for any movement of the Trunking that may take place. See MK Technical Data Guide.

b) Cut ends should be de-burred before installation.

c) Where possible commence installation at a corner position, having first attached the Corner Carrier to the Main Carrier.

d) Carrier Couplers must be placed at all junctions between carriers.

e) Secure earth carrier connector/braid to base carrier rail using quickfit brackets. Placing it astride any moulded corners or couplers.

f) When fitting the Extension Carrier (VTS2 ALM) to the Main Carrier (VTS1 ALM),earth/retaining screws (supplied) are to be screwed into the mating clip feature at each end and at 1000mm spacing, or at either side of a break in the trunking.

1 FITTING THE ACCESSORY MOUNTING BOXES

1. Determine location of the accessories (see note 1.)2. Remove appropriate knockouts/cutouts to suit cable entry.3. Insert optional push fit earth terminals (K3716) into boxes if required.4. If cables are crossing between compartments, cut the carrier as required A to suit Crossover Bridge

or B to suit Accessory Mounting Box. 5. Insert accessory mounting boxes and Crossover Bridge.

Note:i) The depth of the accessory to be installed will govern the depth of the mounting box used in each case.

It should be noted that:a) 35mm deep boxes cannot be mounted in the extended outer compartment of Profile N.b) When mounted into the centre compartment of all profiles, or the extension compartment of profile N,

the boxes reduce the available cross-sectional area for cables to pass behind the box, as follows:

CSA behind 25mm deep box in centre compartment = 1262 mm2

CSA behind 25mm deep box in extension compartment = 1215 mm2

CSA behind 35mm deep box in centre compartment = 604 mm2

ii) Install Cable Divider (VTS/50) if required to sub-divide compartments after fitting boxes. iii) Adjacent Outlet Boxes should not be less than 25mm apart for convenience when

positioning covers.iv) When mounting deep accessories, the base of the box can be cut out.v) A Cross Over Bridge is used to segregate cables when crossing the centre compartment.vi) When breaking between compartments care must be taken not to leave sharp edges

and the use of a short length of PVC conduit or trunking is recommended.

2

INSTALLING CABLES

Ensure electricity is switched OFF before connecting to any feeds and that it remains switched OFF until installation is complete.

Cables can now be laid into the appropriate trunking compartments.

1. When power cables are installed in the centre compartment, it is normal to install data cables in the outer compartments. When it is required to run cables from the centre compartment into Mini Trunking via Mini Trunking Adaptor, cable segregation can be achieved using a short length of Mini Trunking. For details please consult MK Technical Sales Service Department. (Tel. 01268 563720).

2. It is recommended that Cable Retainers (Straight - VTS/11 ALM and Square VTS/12 ALM) are clipped into the carrier to hold the cables in place prior to fitting covers. These should be placed at intervals of 750mm along the length of a run and within 100mm of all corners.

3 COMPLETING THE INSTALLATION

1. Fit Covers to all fittings (internal and external corners and joint covers) by locating them correctly in position and then pushing firmly until they snap into place.

2. Fit End Cap Covers by pushing them on from the front such that the clips slide behind the retainers and engage in the Main Carrier.

3. Fit Mini Trunking Adaptors by clipping onto the outer compartment of the Main Carrier at the required location.

4. The accessories can now be connected and installed in accordance with their individual installation instructions.

5. Test earth continuity to ensure bonding of metal parts comply with IEE Wiring Regulations.

4CUTTING TRUNKING COVERS

a. Cut Trunking Covers to suit application prior to fitting lid earth connector clips.

b. When cutting Trunking Covers, ends should be de-burred before installation.

c. Allowance should be made for space taken up by fittings i.e. Joint Covers, Boxes, Adaptors etc.

d. Fit lid earth connector clips at 500mm intervals, or to suit shorter trunking lengths, into both base clip features.

REMOVAL OF COVERS

1. Switch OFF the mains electricity supply before removal of Covers.2. Sequence of Cover removal:

a) Remove all Fitting Covers, Corners etc. This is achieved by levering under the edge of a fitting. Care should be taken to protect the surface against damage.

b) Remove accessories.c) The Trunking Covers can now be peeled back and away from the carrier(s).

5

H. GUARANTEE

The Company undertakes to replace or repair atits discretion, products should they becomedefective within 20 years in the case ofelectromechanical Wiring Device products, and10 years in the case of mains related electronicWiring Device products, and all CircuitProtection and Cable Management productssolely as a result of faulty materials orworkmanship.Understandably, if the product has not beeninstalled or maintained in accordance with theCompany s instruction, has not been usedappropriately, or if any attempt has been madeto rectify, dismantled or alter the product inany way, the guarantee will be invalidated.

This Guarantee states that the Company s entireliability. It does not extend to coverconsequential loss or damage or installationcosts arising from the defective product. ThisGuarantee does not restrict or infringe thenormal statutory or other rights of theconsumer.

The product and packaging should be disposedof via standard civic amenity facilities.

Cleaning1. The exterior of the products should only

be cleaned using damp cloth.

2. Do not apply solvents or acids to the products as these may attack the plastics used.

It s simply safer to say MK

MK Electric LimitedThe Arnold Centre, Paycocke Road,

Basildon, Essex SS14 3EATelephone 01268 563000 (National)+44 (0) 1268 563000 (International)Facsimile 01268 563563 (UK Sales)

+44 (0) 1268 563360 (International)E-mail: [email protected]

Website: http://www.mkelectric.co.uk

All marks in this document identified with a fi or symbol adjacent to the mark are Trade Marks of

MK Electric Limited

F. DISPOSAL INSTRUCTIONS

E. PRODUCT CLASSIFICATION

G. SERVICE AND MAINTENANCE

®

1, 2 and 3 Gang BoxesConform to the requirements of BS 4662 where applicable

ALUMINIUM TRUNKING SYSTEMConform to the requirements of BS EN 50085-1:1999

Design Registration, Patents and Trade MarkPRESTIGE PLUS is a Trademark of MK Electric Limited.Patents Applied for.Registered Design Applied for.Design Right MK Electric Limited.

If your are in any doubt regarding theinstallation or application of this product please contact:MK Technical Sales Service Department.Telephone 01268 563720.

130mm

Min

imum

21mm

deep

30mm wide

B17m

m

deep

25mm wide

A

Lid Earth Connector Clip