presentation on electrical and automation system of cgl plant (crm-2) jsw kr
TRANSCRIPT
SUBMITTED TO:
GOVERNMENT ENGINEERING COLLEGE JHALAWAR
By: NEERAJ 12EEJEE029 B-TECH 4th year(7th sem.) ELECTRICAL ENGG. GEC JHALAWAR
SUBMITTED TO:MR. ASHISH KHANDELWALHOD-EEGECJ
1
PRESENTATION ON ELECTRICAL AND AUTOMATION SYSTEM OF COLD ROLL MILL-2 CGL PLANT OF
3.
INDEX CRM-2 PRODUCT
CGL LINE OVERVIEW
PLANT LAYOUT
ENTRY SECTION OF CGL PLANT a)coil inserting sequence b)various sensor used in entry section
CGL POWER DISTRIBUTION SYSTEM a)various level of power supply
VVVF &STARTER
AUTOMATION SYSTEM
CONCLUSION &REFERENCE
Need For Cold Rolled Products in our life
4.
CONTINUOUS GALVANIZING LINE OVERVIEW
5.
PLANT LAYOUT
6.
ENTRY SECTION
1 2.
3.3. 4
7.
AUTOMATION SYSTEM For e.g: COIL INSERTING SEQUENCE1.coil from cradle to mandrel
8.
PHOTO SENSOR PROXY
LIMIT SWITCH LASER SENSOR
ABSOLUTE ENCODER
VARIOUS TYPE OF SENSOR USED IN ENTRY SECTION
9.
10.
33KV AC FROM MSDS 130MVA TRANSFORMER
6.6KV AC FROM POWER TR 25 MVA TRANSFORMER
433V AC DISTRIBUTION TRANSFORMER INSTALLED IN INDIVIDUAL PMCC
110V AC CONTROL VOLTAGE DERIVED INSIDE PMCC & MCC FOR ON/OFF CONTROL OF FEEDERS.
110V DC DERIVED THROUGH BATTERY CHARGER AND BATTERY BANK FOR ON / OFF CONTROL
OF HT FEEDERS.24V DC FOR PLC SIGNALS AND SOV OPERATION. DERIVED THROUGH DC POWER PACKS. Battery Charger
HT switch board operation is very important and critical for any power distribution. The operation, control and protection of this system should be highly reliable, accurate and un interrupted.
Hence, these switch boards are operated on DC supply powered by battery bank, backed up by float and boost battery chargers..
BATTERY CHARGER
DIFFERENT LEVELS OF POWER SUPPLIES
11.
VVVF DRIVES
VVVF Drives are used where speed control, torque control or position control of the driven equipment are required. There are 52nos VVVF drives installed in each furnace. Capacity of these drives varies from 10KVA to 1230KVA.
Application of VVVF Drives
Speed Control—Vibro feeders, Conveyors.Position Control – Rotation and Tilting DrivesTorque Control – Stock Level Indicators,
Cranes, ConveyorsSOFT STARTERSSoft starters are used achieve smooth starting and stopping of the equipment. This will also avoid load fluctuation. Soft starters are used in conveyors, hydraulic pumps of mud gun & drilling machines etc.
12.
INSTRUMENTATIONWHY INSTRUMENTATION?
Instrumentation is required to measure the physical variables or parameters which affects the process and control of these parameters.
ANALOG DIGITAL
LEVEL TRANSMITTER
FLOW TRANSMITTER
PRESSURE TRANSMITTER
CONTROL VALVE
TEMPERATURE SWITCH
PRESSURE SWITCH
SHUT OFF VALVE13.
RTD/THERMOCOUPLE
RADIATION PYAROMETER
Various types used in furnace
Resistance temperature detector (RTD) RTD ’s are used for temperature measurement up to 200Deg C. ‘K’ TYPE THERMOCOUPLE ‘K’ type thermocouples are used for the temperature measurement between 200 Deg to 900 Deg c ‘S’ TYPE THERMOCOUPLE ‘S’ type thermocouples are used for the temperature measurement between 900 Deg C to 1400 Deg c. Mainly used in stove dome and hot blast line RADIATION PYROMETERS Pyrometers are non contact type sensors used for high temperature measurement from 600 to 1600 Deg C. All these sensors are connected through smart temperature transmitter
TEMPERATURE MEASUREMENT
14.
INTERNAL STRUCTURE OF THERMOCOUPLE LAWS OF THERMOCOUPLE
15
PLC OR DCSREMOTE
INPUT/OUTPUT PANEL
FIELD INSTRUMENTS/EQUIPMENTS
ENGINEERING STATION SERVER
CLIENTS ORHMI STATIONS FOR
OPERATORS
CLIENT OR HMI STATIONS FOR
OPERATORS
CLIENT OR HMI STATION FOR
OPERATORS
GENERAL ARCHITECTURE OF AUTOMATION SYSTEM
16.
Topology of LEVEL 1System:ETHERNET
PLC
PLC PRORAMMING TOOL SERVER, HMI SERVERS, WORK STATIONS &CLIENTS
LEVEL 2 SERVERS & WORK STATIONS
Remote Input Output (RIO)
Drives
TC – net
3rd Party Devices
Field Devices
17.
18.
PROCESSOR
O M U OT DP UU LT E
POWERSUPPLY
From SENSORS
Pushbuttons,contacts,
limit switches,etc.
I MN O P D U UT L E
PROGRAMMING DEVICE
ToOUTPUT
Solenoids, contactors,
alarmsetc.
Major Components of a Common PLCPLC OVERVIEW
RIO PANEL• The remote input/output panel consists 1.Digital input cards 2.Digital output cards 3.Analog input card 4.Analog output card 5.Interface module All the signals form the field instruments/ equipments are measured by these cards are transferred to the interface module.
• The interface module is the communication link between I/O cards and PLC which communicates through either optical fiber cable or twisted pair cable
• Interface module uses special communication protocol for communication with PLC designed form the PLC manufacturer. EX.SIEMENS uses Profibus protocol, EMERSON uses device net
19.
SERVER AND CLIENT AND ENGINEERING STATION
• Server and client configuration is used when the system is large and operators are more.• As the name suggests server is a link between operator station (client) and PLC. All the requests generated by the operator from operator station are routed through the server and results of the requests are stored in the server. The operator station fetches these results and displays.• Another important function of Server is data storage. (trends data, alarms etc).• Generally both servers and client are desktop PC loaded with the GUI software• Server uses well known high speed Ethernet communication protocol for communication with PLC and client• Engineering station is used to develop logic or software for PLC and diagnostic services of the PLC, Server and operator station
20.
1.CONCLUSION2.REFERENCES a] various sensor by Omron. b] jsw technical data c]plc by Toshiba&mitsubshi.
21.
THANK YOU