Z.I. - BP 2 - 46120 LEYME (France) - Téléphone : 33.(0)5.65.40.39.39 - Télécopie : 33.(0)5.65.40.39.40. - E-mail : info.lacaze-energies@groupe-cahors.com Installation and commissioning PREPAC ( IU-0002-FR-200906 ) Attention ! This document does not concern the associated tank (Ballon) DHW MODULE

Upload: others

Post on 05-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

Z.I. - BP 2 - 46120 LEYME (France) - Téléphone : 33.(0)5.65.40.39.39 - Télécopie : 33.(0)5.65.40.39.40. - E-mail : [email protected]

Installation and commissioning

PREPAC( IU-0002-FR-200906 )

Attention !This document does not concern the associated tank (Ballon)

DHW MODULE

Page 2: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

2 Installation & Mise en service - PREPAC

SUMMARY

WARNING.................................................................................................................. 3

GENERAL CHARACTERISTICS............................................................................... 4

PLATE EXCHANGER................................................................................................ 4

MOUNTING OF PLATES........................................................................................... 6

CONNECTIONS ......................................................................................................... 8

COMMISSIONING / MAINTENANCE ........................................................................ 9

Page 3: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

3 Installation & Mise en service - PREPAC

WARNING

Note concerning the elaboration and publication of this manual :

This manual was elaborated and published under the direction of LACAZEENERGIES. It covers the most recent features and descriptions of the product. Themanual content and the product features may be modified without prior notice.

The company LACAZE ENERGIES reserves the right to modify without prior noticethe features and elements contained in the following pages. The company LACAZEENERGIES will not be responsible for any damage (including consecutive damage)caused by reliance on the presented elements. This includes, but is not limited to,typing mistakes and other errors linked to the publication© LACAZE ENERGIES

Please read carefully:

● This instruction manual is an integral part of the product and must be given to the final user.

● The appliance was manufactured for the storage of hot or cold water, used in a closed circuit. Any other use shall be considered as inappropriate and dangerous.

● The appliance must not be installed in humid locations (H.R. 80%). Protect theappliance from water or other liquid splashes to prevent damage to the components.

● Installation must be carried out in conformity with the rules, regulations andstandards currently in force, respecting the instructions of the manufacturer, by aqualified professional.

● In the case of the equipment being sold or transferred to another user, this manual must accompany the equipment, so that the new user and the installer can consult it.

● If the equipment is not used during a period of below-freezing conditions, werequest that it should be drained completely. The manufacturer declines allresponsibility for any damage due to frost.

● We recommend that these instructions be read carefully, and advise the exclusive use of spare parts supplied by the manufacturer, in order to obtain the best servicefrom the product and the acknowledgement of the appliance warranty.

Page 4: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

4 Installation & Mise en service - PREPAC

CHARACTERISTICS

The DHW Module "Prepac" is adomestic hot water production systemconsisting of :

A plate heat exchanger withdemountable plates, with a highexchange coefficient.

A single-phase 230V circulator,simple or double.

Stainless Steel pipes.

Two isolation valves.

This system will provide an importantquantity of domestic hot water at atemperature of 45 to 60°C.

PLATE EXCHANGER

Convention

As with any plate exchanger ingeneral, there is a hot fluid which isbeing cooled and a cold fluid which isbeing heated.

Throughout this document we will referto the hot water fluid circuit as thePrimary Circuit, and the cold waterfluid circuit as the Secondary Circuit.

Composition

The plate exchanger is made up of aseries of plates held together betweentwo supporting plates, one fixed, theother mobile. The supporting plates areconnected by braces and held inposition by two tension rods.

On the fixed plate there we find theconnecting orifices:

The two fluids flow between the plates,whose judicious combination, usingjoints, allows the perfect partitioning ofthe circuits, fully guaranteeing theirindependence.

Page 5: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

5 Installation & Mise en service - PREPAC

Materials

The Plates :

The plates are made of AISI 316 Lstainless steel [Z6 CND 17.12], soproviding excellent resistance tocorrosion (for Cl- 70 mg/l contents).

MODELThickness

(mm)Distance

(mm)Surface

(m2)

C12 0.5 3.10 0.032

The gaskets :

These have two main functions:

● To ensure that the exchanger is water tight.● To separate the primary and secondary circuits.

A double gasket around each plateorifice prevents mixing of the fluids. If agasket is faulty, the liquid will leaktowards the exterior of the exchanger.

PLAKEO exchanger plates areequipped with Nitrile (P) gaskets whichare regularly used in heatingappliances for temperatures 100°C

The circulatorBrand Grundfos type UPS operates upto 100°C.

The Frame :Made of S235JRG2 carbon steel,covered with 2 coats of epoxy paint(thickness 15 mm).

MODELFrameweight

(kg)

OperatingPressure

(bar)

C12 18 10

Tension Rods and Braces :

In electro-galvanized steel class 8.8 forthe threaded parts and bolts.

C12

BRACES 2 x 15

TENSION RODS 6 x M12

Main Range of Exchangers:

Primairy 90°CSec.

10/55°CExchangerPower(kW)

Flow(m3/h)

HeadLoss

(mCE)

Flow(m3/h)

41 1,26 2,9 0,79

49 1,26 1,69 0,94

66 2,02 2,7 1,26

77 2,12 2,12 1,48

87 2,41 2,7 1,66

94 2,59 3,1 1,8

100 2,52 2,2 1,91

106 2,48 1,67 2,02

136 3,71 2,88 2,59

143 3,89 3,16 2,74

154 3,89 2,61 2,95

222 5,83 3,09 4,25

252 6,44 2,96 4,82

266 6,77 3,26 5,08

301 7,6 3,06 5,76

332 8,24 3,06 6,34

Page 6: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

6 Installation & Mise en service - PREPAC

PLATE ASSEMBLY

Refer to the following figures and tables to visualize the correct assembly of theplates.

Plate assembly diagram for C12 Plates - Right -

Plate assembly diagram for C12 Plates - Left -

Primary

Primary

Secondary

Secondary

Page 7: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

7 Installation & Mise en service - PREPAC

Reminder :Nt total number of platesNa front plate with 4 holes and a

gasket around each orifice.Nd back plate, without holes.Nb intermediary plate (even

number).Nc intermediary plate (odd number)

We have the following equalities :

Number of plates "EVEN" :

Na = 1Nb = Nt/2 - 1Nc = Nb

Nd = 1

Number of plates "ODD" :

Na = 1Nb = (Nt – 1)/2Nc = Nb - 1Nd = 1

Tightening Code:

The spacing of the plates must be:

Remark :

Only in case when the number ofplates is odd the distribution of primaryand secondary channels is identical. Inall cases, it is necessary to ensure thatthe entries and exits of each fluid arecorrect.

To know the exact characteristics ofthe model supplied, please consult theidentification sticker (nameplate)placed on the heat exchanger(example below).Please note that this is only anexample.

Z.I. – B.P. – 46 120 LEYMEMODULE DE PRODUCTION D'EAU CHAUDE

PREPAC

MODEL = GTI26-12p13s/4FRAME = LEFTPUMP N° = 4NO. PLATES = 26

PRIMARY FLOW = 1.42 kg/sTEMPERATURE = 90 °CENTRY/EXIT = S4/S2NUMBER CANNELS = 12HEAD LOSS = 30.9 kPa

SECONDARY FLOW = 0.86 kg/sTEMPERATURE = 10-60 °CENTRY/EXIT = S3/S1NUMBER CANNELS = 13

E= Nt x 3,1

Page 8: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

8 Installation & Mise en service - PREPAC

HYDRAULIC CONNECTION1 Tank2 Secondary circuit circulator3 Plate Exchanger (DN25 couplings)4 Coupling 15/21 for thermostat5 Isolation valves6 Couplings 15/21 for thermometer7 Coupling 40/49 for anode8 Threaded boss M77 for immersing

heaterI Hot water OutletII Loop returnIII Cold water inlet (baffle)IV DrainageV Primary Entry ExchangerVI Primary Exit Exchanger

Indicative diagram for connecting the PREPAC Module

Feed the Module with primary fluid inaccordance with the nameplate(minimal flow and entry temperature).

Connect electrically the secondarycirculator (pump) with a cable with asection adequate for the powerabsorbed (see motor nameplate).

Warning :In all cases we specifically do NOTrecommend the use of the contactfor regulation of the thermostat tocommand the circulator because itmakes sense to maintain thecirculation of water between theplates even in the absence ofwithdrawal, to prevent scaling of theexchanger.

Provide line protection followingstandards and / or regulations at theplace of installation.

Connection to a grounded outlet(earth) is compulsory.

It should be noted that the suppliedcirculator is provided with anembedded thermal protectionIpsotherm within the motor. Thisthermal protection is generallycomplemented by a fuse protection(short circuit).

Page 9: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

9 Installation & Mise en service - PREPAC

COMMISSIONING /

MAINTENANCE

Commissioning

It is essential to provide isolatingvalves on the 4 exchanger outlets.

It is also necessary to provide anexpansion system for the fluids used ina closed circuit (primary circuit).Always provide safety valves for eachof the circuits.

The air must be bled from the pipes.We advise you to fill the two circuitssimultaneously. Always avoid filling thesystem too rapidly and the ‘waterhammer’ effect, which could affect thestanding to pressure of the exchanger.

Check the entry and exit temperaturesfor each of the two fluids. If necessary,adjust the respective flows by using theregulation valves, in order to obtain therequired temperatures. Note the valuesobtained for temperature and headloss (decrease in pressure) in theexchanger maintenance booklet.

Warning !

Before closing theisolation valves « 5 » ofthe PREPAC, make surethat the feed on Primaryis stopped !

Maintenance

The system is unlikely to becomeclogged up as long as fluidscompatible with plate exchangertechnology are used (water TH<15°F). Systematic maintenance of theexchanger is not necessary if this ruleis followed.

However, regular monitoring of the airvent valves and safety shut-off devicesis necessary.

Careful monitoring of exchanger headloss and the respective temperaturesof the In /Out fluids is essential.

In fact, if clogging occurs, there will bea noticeable increase in head loss(P), due to reduction of the section ofthe fluid passage, as well as animportant variation in the T for theoperating conditions of thecorresponding clogged circuit (variationof the exchange coefficients).

Please note however that variations inexchanger performance do not alwaysmean that it is clogged. It is alwaysnecessary to check the entrytemperatures of the fluids and the flowrate before reaching a conclusion, asthey have a great influence onexchanger performance.

It is strongly recommended that theinlets and outlets for each fluid areequipped with thermometers andmonometers which indicate the correctfunctioning of the appliance as well asflow meters on each of the inlets.

Page 10: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

10 Installation & Mise en service - PREPAC

If clogging is discovered, the exchangesurfaces must be cleaned

Before opening the exchanger, ensurethe following instructions are observed:

● Let the exchanger cool down for as long as necessary. Make sure youisolate hydraulically the primary andsecondary circuits.

● Open the exchanger and mark the plates.

When removing the plates, wearing ofgloves is recommended!!

If two or more plates are stuck to eachother they need to be separatedcarefully, so that the gaskets remainattached to the correct plate. Theexchange surface should then berinsed with a water jet and scrubbedwith a nylon (or equivalent material)brush. Take care not to damage thegasket. If necessary, use a nitric acidsolution at 5%, then rinse abundantly.

Important : Concentrated nitricacid can seriously damage the skinand mucous membranes! Great careis recommended when handlingthese solutions as well as thewearing of protective goggles andgloves.

● A partially or completely detachedgasket must always be glued backbefore replacing the plates.

.

● Reassemble the plates in the same order and same position(top/bottom), respecting thetightening values given (see"Exchanger").

● Tighten the plates in a regular manner (symmetrically and inparallel). In practice, the 4 tensionrods at the extremities should beremoved first and replaced last.

Page 11: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

11 Installation & Mise en service - PREPAC

Nomenclature : ( indicative, mayvary between frame “left” and frame“right”)(from bottom towards the top of thetank)

1 SS coupling FF DN 50 / 50mm1 reduction MF DN 50/251 nipple MM DN 251 isolation valve DN 251 nipple MM DN 251 union fitting 2 parts DN 251 SS coupling MF DN 25

When DN20 circulator used1 reduction MF DN 20/251 union fitting 2 parts DN 201 circulator1 union fitting 2 parts DN 201 reduction MF DN 20/25

When DN25 circulator used1 union fitting 2 parts DN 251 circulator1 union fitting 2 parts DN 25

When DN32 circulator used1 reduction MF DN 32/251 union fitting 2 parts DN 321 circulator1 union fitting 2 parts DN 321 reduction MF DN 32/25

Plate Exchanger :1 fixe frame with entry /exit forprimary/secondary fluid1 mobile frame2 braces6 tension rods1 set of plates

1 SS pipe DN 251 SS bend MF DN 251 isolation valve DN 251 boss MM DN 251 reduction MF DN 50/251 SS coupling FF DN 50 / 50mm

Page 12: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

12 Installation & Mise en service - PREPAC

For water : ρ ~1000kg/m3 and Cp = 1 kcal/kg = 4.18kJ/kg

Monitoring sheet of parameters of plate exchanger Prepac- Primary side -

Date HourTePri.(°C)

TsPri.(°C)

PePri.

(Bar)

PsPri.

(Bar)

QPrim

(m3/h)

Primary Power kWPower=1,162 x Q x (Te-Ts)

Page 13: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

13 Installation & Mise en service - PREPAC

Monitoring sheet of parameters of plate exchanger Prepac- Secondary Side or DHW -

Date HourTe

ECS(°C)

TsECS(°C)

PeECS(Bar)

PsECS(Bar)

QECS

(m3/h)

Power DHW kWPower=1,162 x Q x (Te-Ts)

Page 14: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

14 Installation & Mise en service - PREPAC

Page 15: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

15 Installation & Mise en service - PREPAC

Page 16: PREPAC - Lacaze Energies · 7 Installation & Mise en service - PREPAC Reminder : N t total number of plates N a front plate with 4 holes and a gasket around each orifice. N d back

16 Installation & Mise en service - PREPAC

MODULE FOR THE PRODUCTION

OF DHW

Prepac

INDICATIVE TECHNICAL INSTRUCTIONS

( IU-0002-FR-200906 )