Fire Systems SLC Loop Devices
-
References:
Document 51253 SLC Wiring
Document 15378 Device Compatibility
Datasheets
-
SLC Loop Devices
A Signaling Line Circuit can contain a variety of devices, each with a specific function to perform.
Intelligent Detectors to identify a variety of threat conditions various smoke levels, heat, etc.
Addressable Modules to interface the system to conventional input/output circuits and devices notification appliances, smoke detectors, waterflow and supervisory devices, etc.
Addressable Pull Stations for manual alarm activation. These devices actually contain an Addressable Module inside.
Loop Isolators to prevent total loop failure from a SLC short.
-
Communication Protocols
CLIP Classic Loop Interface Protocol
Polls devices one at a time in serial order. Limited to 99 detectors and 99 modules per SLC
Loop. Compatible with NFS640 NFS2-640 and NFS2-
3030. Solid Technologybut slow. Retrofit solution.
-
Communication Protocols
FlashScanTM
Complete product line.
Permits the largest number of devices per loop in the industry (159 detectors/159 modules).
Response times offers advanced detection options
Faster polling and response time - exceed worldwide code requirements (< 3 sec ).
-
Isolator Application Style 4 Riser Classe B
-
Isolator Application Style 6 Classe A
-
Isolator Application Style 7 Classe A
-
FSI-851 Inico
FSP- 851 Fotoeltrico
FST-851 Temperatura fixa (57oC / 135oF)
FST-851R Termovelocimtrico (8,3oC / min) e Temp. Fixa
FST-851H Temperatura fixa alta (90oC / 195oF)
FAPT-851 Acclimate fotoeltrico / trmico
FSL-751 Fotoeltrico a Laser
FSC-851 Multi-critrio IntelliQuad
FSB-200 Beam (tipo feixe)
FSB-200S Beam (tipo feixe) c/ auto-teste
Detectores FlashScan: Tipos disponveis
-
Acionador Manual enderevel
Chave resetvel
Dupla ao (aperte e puxe)
Pode ser aberto sem causar
uma condio de alarme!
LED indicador bicolor
Verde: normal / Vermelho:
alarme
Visualizao pelo atuador
frontal transparente.
NBG12LXP: Acionador Manual FlashScan
-
Mdulos de entrada Mdulos monitores
Simples
Duplos
Mini-mdulos
Mdulo de zona convencional Detectores convencionais
Mdulos entrada 4-20mA
Compatvel com sensores industriais em geral:
temperatura, presso, concentrao de gases,
etc.
-
Mdulos de sada Mdulos de controle
Incluem Superviso
Alimentao 24V
Mdulos para aplicaes de combate
Fiao para solenides classe A/B
supervisionada
Listados UL/FM
Protocolo redundante
Mdulos de sada rel
Permitem comando de desligamento de
equipamentos (ex. Recolhimento de
elevadores)
-
Mdulos de entradas e sadas Mdulos FDRM-1
2 entradas supervisionadas
2 sadas de rel (NA/NF)
Menor custo de instalao
-
Mdulos isoladores Mdulos ISO-X
Protege contra curto-circuitos
At 200 mdulos por lao, sem
perda de capacidade
Mximo 25 dispositivos entre
isoladores (20 pela ABNT)
-
XP10-M Ten Class B or five Class A Initiating Device Circuits for normally open alarm contact devices.
XP6-MA Six Class B or three Class A Initiating Device Circuits for monitoring UL Listed two-wire smoke detectors (requires filtered, resettable 24 volts).
Mounts in BB-XP backboxes two modules, surface mount. Mount up to six modules on a CHS-6 chassis.
Addressable Input Modules
XP6-MA
BB-XP
-
XP6-C Transponder Control Module. six Notification Appliance Circuits, Class A or B.
SYNC-1 Synchronization daughter module for XP6-C using System Sensor appliances.
XP6-R Transponder Relay Module. Six Form-C Dry Contact Relays.
Mounts in BB-XP backboxes two modules, surface mount. Mount up to six modules on a CHS-6 chassis.
Addressable Output Modules
XP6-C
CHS-6 Chassis
-
Multi-Circuit Module Mounting Options
BB-25 (Black) / BB-6 (Red)
Mounts up to 6 XP Multi-Mods
BB-XP (Black) / BB-2 (Red) Mounts up to two Multi-Mods
-
Mounts in a standard CAB-4 Series enclosure using up to 1-4 CHS-6 chassis for a total of 24 Multi-Mods.
CAB-4 Series Enclosure with CHS-6 Chassis
Multi-Circuit Module Mounting Options
-
Base sonora B200S
Ativa a sirene quando o detector ligado a ela ativado
Pode ser ativada remotamente pela central
Padro Temporal 3 e Temporal 4
Sincroniza com os dispositivos AV da System Sensor
Necessita alimentao 24VDC externa
-
Diversos modelos:
P2R udio/visual
SR somente strobe
HR somente sirene
Opes a prova de tempo
NEMA 4X/IP56
Sinalizador e placa de montagem
Intensidade ajustvel
Montagem simples
Sinalizadores SpectrAlert Advance