    Lighting Control System Pow-R-Command

    Pow-R-Command 2000/2000B

    General Description

    Sheet 0909

    Pow-R-Command 2000/2000B

    Pow-R-Command 2000 Panel

    General Description

    Eatons Cutler-Hammer Pow-R-

    Command 2000 is a microprocessor-based

    programmable lighting controlsystem with an embedded webserverfor robust control. The PRC2000 can be

    used as a stand-alone

    panelboard ornetworked as a system

    . An upgrade canbe purchased to integrate the unit withinBACnet native control networks.

    Components

    Embedded webserver.

    Intelligent power switchingequipment.

    LCD programming displayand keypad.

    Application Specific Controllers(ASCs).

    Software and support.

    Integration components.

    Intelligent PowerSwitching Equipment

    Pow-R-Command 2000 Panelboards

    Pow-R-Command 2000 Panelboardsare offered from 100 through 225amperes in main lug and main breakerconfigurations. Available voltagesare 120/240, 208Y/120 and 480Y/277,single-phase and 3-phase. Thepanelboard utilizes both branchmounted standard breakers through100 amperes, and controllablethermal-magnetic breakers which

    are controlled by the Pow-R-Command2000 System Controller. The Pow-R-Command 2000 controllers providethe ability to directly operate up to eightbreaker control buses. Such a capabilityallows a single controller to directlyoperate up to 168 GHQRSP and BABRSPcontrollable circuit breakers, withindividual control and status feedbackof each controllable breaker.

    The System Controller also includesload override, holiday scheduling,

    one-shot or event schedules, off warning

    to tenants by blinking lights, memoryloss protection, power failure/brown-out protection, hardware diagnostics,

    a real-time clock and 16 dry contactswitch inputs.

    Equipment within the Pow-R-Command2000 System may be networked. Up to120 panelboards may be networkedover a shielded twisted pair networkcable without the need for a personalcomputer in the system.

    The Pow-R-Command 2000 Panelboardis listed UL

    67 for panelboards andUL 916 for energy managementequipment.

    BACnet Protocol

    The PRC2000 unit can be upgraded

    to the B series for integration withinBACnet native control networks.BACnet is a communications protocolwidely used in building automationand controls and adds even moreflexibility to the control system.

  • 8/11/2019 PRC2000 System Guide

    2/6

    3.1-2

    For more information visit: www.eaton.com

    CA08104001E

    January 2008

    Lighting Control System Pow-R-Command

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Pow-R-Command 2000/2000B

    Operational DescriptionSheet 0910

    Pow-R-Command 2000

    PRC2000 LCD Display

    System DescriptionCoupled with an embedded web-server, the PRC2000 system containsnetworkable intelligence and providesautomated switching of branch circuitbreakers.

    Embedded Webserver

    The Pow-R-Command 2000 systemcontains an embedded webserver and

    configurable IP address which allowsfor complete programming andcontrol over a buildings IT network.Access is protected by username andpassword features.

    BACnet Protocol

    If the PRC2000 has been upgraded tothe B series, then it is also capableof communicating across and beingintegrated into BACnet native networks.BACnet is an industry standard com-munications protocol for buildingautomation and controls.

    Distributed Intelligence

    The system is distributed intelligentand operates as a stand-alone devicethat can control its own circuits. A per-sonal computer is not required for thesystem to operate.

    Main Network

    The Pow-R-Command System is capa-ble of globally communicating overthe main RS-485 network with up to120 controllers over an end-to-enddistance of 4,000 feet (1,219 m) using ashielded twisted pair network cable. Itis also possible to place all controllersor clusters of controllers onto thefacilitys Ethernet network.

    LCD Display and KeypadThe PRC2000 LCD display and keypadprovides local programming, overrideand diagnostic functions.

    Memory Loss Protection

    Time schedules, time-of-day clock, day/date, and system configuration param-eters are protected from memory loss ifthere is a power failure. The memoryloss protection is rated for 10 years.

    Power Failure/Brownout Recovery

    When system input power drops belownormal, the system will not lose itsprogrammed information. Upon returnof normal power, breaker positionsscheduled during the power failure

    period are immediately updated.No operator interaction is required.

    Astronomical Real-Time Clock

    Time-of-day, day/date, automatic leapyear and daylight savings time adjust-ments are provided as standard.

    Control Software

    It is possible to program the panel-board directly through its local RS-485maintenance port with a hand-heldprogrammer or with the lightingmanagement software over a shieldedtwisted pair cable by way of a centraloperators station.

    Time SchedulingPow-R-Command 2000 supports 75schedules as local control functions.Any of the 75 local time schedules ina controller can be designated as aback-up schedule to execute only if themaster schedules fail or cease execution.

    Holiday Scheduling

    Pow-R-Command 2000 supports 16system holidays through the NetworkAccess Device and, additionally, eachcontroller can execute 30 local holidaydefinitions.

    Input to Output Switch Matrix

    The input to output switch matrixfeature allows any breaker connectedto any panel to be controlled by anyswitch or any group of switchesconnected to any panel on the samenetwork.

    Messages/Alarms

    The system will maintain an alarm log.The log will record where the alarmoccurred, alarm reason, date and timeof the alarm. The log is maintained innon-volatile memory. The alarm logcan store up to 300 alarms.

    Daylighting Optimization

    Daylighting optimization is availableusing a combination of inputs on thePRC2000 controller or a Switch Over-ride Controller and dimming cable.

    Application Specific ControllersOptional Application Specific Controllersexpand the PRC2000 System throughthe network to customize the systemto meet the needs of the tenant.

    Switch Override Controller (SOC)

    Switch Override Controller (SOC)

    Provides the ability to connect andmonitor up to 48 additional 2-wire drycontact closures from wall switches,occupancy sensors, photocells, build-ing automation system relay contacts

    or any remotely mounted device witha dry contact.

    Input connections to the controller areself-powered.

    It is possible to program any input tothe switch override controller to con-trol any breaker or group of breakersin the system.

    Inputs are capable of being individu-ally time-schedule enabled fordifferent days of the week.

    Telephone Override Controller (TOC)

    Provides a voice prompted methodfor ON/OFF override control of light-ing. It is possible to override an indi-

    vidual breaker or group of breakersON or OFF during scheduled ornonscheduled hours using anytouch-tone analog telephone.

    The Telephone Override Controllerallows voice prompted control oflighting circuits for up to 1,000 indi-vidual users. It is possible to programany of the 1,000 users to control anybreaker or group of breakers in thepanelboard or system.

  • 8/11/2019 PRC2000 System Guide

    3/6

    CA08104001E For more information visit: www.eaton.com

    23January 2008

    Lighting Control System Pow-R-CommandPow-R-Command 2000/2000B

    System ConfigurationsSheet 0911

    System Configurations

    PRC Network Architecture

    Containing an embedded webserver,each Pow-R-Command 2000 system isprogrammed with a unique IP address

    for communication via any standardInternet browser. Web access is stan-dard with the PRC2000. Each controllercan support up to three additionalexpansion panels and can be connectedto a BACnet Client Workstation with anadditional upgrade.

    Breaker Control Busses

    Every Pow-R-Command ExpansionPanelboard can be configured with theleft and/or right breaker control bussesinstalled. This feature not only permitsstandard and remote controllablebreakers to be intermixed within thesame panelboard, but also permits forgreater flexibility and versatility indesign and control when integratingwith the Pow-R-Command SystemController.

    Figure 23.1-1. PRC Network Architecture

    Figure 23.1-2. Breaker Control Busses

    Web Enabled PC

    TCP/IP

    Webserver

    XML/SOAP/BACnet

    Ethernet Ethernet

    RS-485

    Network

    RS-485

    Network

    RS-485

    Network

    PRC2000IntegratedPanelboardIP Address:10.0.0.222

    PRC2000IntegratedPanelboardIP Address:10.0.0.222

    PRC2000IntegratedPanelboardIP Address:10.0.0.222

  • 8/11/2019 PRC2000 System Guide

    4/6

    3.1-4

    For more information visit: www.eaton.com CA08104001E

    January 2008

    Lighting Control System Pow-R-Command

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Pow-R-Command 2000/2000B

    System ConfigurationsSheet 0912

    Sub Network Configuration

    When connecting the Pow-R-CommandExpansion Panelboards to the UniversalSystem Controller, the Breaker ControlBusses must be wired in a daisy chainconfiguration as shown in the figure

    below.

    Figure 23.1-3. Sub Network Configuration

    LegendUSC = Universal SystemController

    PRCEP = Pow-R-CommandExpansion Panelboard

    SLAN = Sub Local Area Network

    PRC2000

    Panelboard

    PRCEP

    PRCEP PRCEP

    SLAN

    PRC2000 Application

    Customizable extension panels allowfor combinations of both regular andremote controllable breakers for indi-vidualized solutions as shown in thisriser diagram. Eatons Cutler-Hammer

    Pow-R-Command 2000 Controller can

    support up to eight Breaker ControlBusses contained within four standardpanelboardsor split between a maxi-mum of eight. When connected to thebuildings Internet, all master andexpansion panels can be controlled.

    Figure 23.1-4. PRC2000 Application

    Legend

    PCR2000 = Pow-R-Command 2000Panelboard withIntegrated Controllerand 2 BCBs

    PRC EP 1 = Pow-R-CommandExpansion Panel with1 BCB

    PRC EP 2 = Pow-R-CommandExpansion Panel with2 BCBs

    RS-485 = RecommendedStandard 485

    PRCEP1

    5th Floor

    PRCEP1

    PRCEP2

    PRCEP2

    PRC2000

    4th Floor

    3rd Floor

    2nd Floor

    Ground

    RS-485

    RS-485

    RS-485

    RS-485

    Internet PC withInternetBrowser

  • 8/11/2019 PRC2000 System Guide

    5/6

    CA08104001E For more information visit: www.eaton.com

    23January 2008

    Lighting Control System Pow-R-CommandPow-R-Command 2000/2000B

    Technical DataSheet 0913

    Technical Data

    Panelboard Ratings

    Voltage:

    240 Vac

    480Y/277 Vac

    Main lugs:

    100 through 225 amperes

    Main breakers:

    100 through 225 amperes

    Branches:

    15 through 100 amperes

    Controllable from 15 through30 amperes

    Interrupting Capacity (Symmetrical)

    240 Vac: 65 kA maximum fully rated.

    240 Vac: 100 kA maximumseries rated.

    480Y/277 Vac

    Service

    3-phase, 4-wire 208Y/120 V,480Y/277 Vac and 240/120 V Delta.

    Single-phase, 3-wire, 120/240 V.

    Mains

    For available mains, refer toTable 23.1-1.

    Branch Circuits

    For available branch circuit devices,refer to Table 23.1-2.

    Main Lugs Only

    The short circuit rating of the MLOassembled panelboard will be fullyrated based upon the lowest ratedbranch device or may be series ratedwith an approved upstream device.

    Main lugs only ampere ratings:100 and 225.

    Main Circuit Breakers

    The short circuit rating shown is thatof the main breaker only. The shortcircuit rating of the assembled panel-board is the rating of the lowest fullyrated main or branch device or therating of an approved series ratingcombination.

    Table 23.1-1. Main Circuit Breakers

    Branch Circuit Breakers

    The type GHQRSP and BABRSP are the controllable circuit breakers. Controllablebreakers are available in 1- and 2-pole styles, from 15 through 30 amperes.Non-controlled circuit breakers can be located within the panelboard chassis.

    Table 23.1-2. Branch Circuit Breakers

    HID (High Intensity Discharge) rated breaker. Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space. Controllable breaker.

    GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. 50 ampere devices are available as 2-pole only.

    Series Ratings

    Eaton has tested the GHQRSP and BABRSP controllable circuit breakers forSeries Rated Combinations up to 200 kAIC with breakers or fuses. For a completelisting of available series ratings, see Section 22(Panelboards) Series RatingsTables 22.0-6through 22.0-16.

    BreakerType

    FrameAmpereRating

    Interrupting Rating(kA Symmetrical)

    240 V 480Y/277 V

    EHDFDB

    100150

    18 18

    14 14

    FDHFDFDC

    225225225

    65100200

    35 65100

    EDEDHEDC

    225225225

    65100200

    JDHJDJDC

    250250250

    65100200

    35 65100

    BreakerType

    AmpereRating

    Numberof Poles

    Interrupting Rating (kA Symmetrical)

    120 V 120/240 V 240 V 277 V 480 V

    BABBABBAB

    15 7015 10015 100

    122, 3

    10

    10

    10

    BAB-D

    BAB-C

    BABRSP

    15 6015 3015 30

    1, 21, 21, 2

    101010

    101010

    GHQRSP 15 20 1, 2 65 14 14

    QBGF, QBGFEP 15 50 1, 2 10 10

  • 8/11/2019 PRC2000 System Guide

    6/6

    3.1-6

    For more information visit: www.eaton.com CA08104001E

    January 2008

    Lighting Control System Pow-R-Command

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    Pow-R-Command 2000/2000B

    LayoutSheet 0914

    Figure 23.1-5. Pow-R-Command PRC2000 Layout

    14 in. - 18 Ckt. ChassisIncludes PRC2000Controller

    20 in. - 30 Ckt. ChassisIncludes PRC2000Controller

    26 in. - 42 Ckt. ChassisIncludes PRC2000Controller

    Note: PRC2000Chassis is located atthe Top of the panel-board immediatelyabove the breakers.

    Main Lug Section 2 in. 100 Amp MLO4 in. 225 Amp MLO

    Vertically Mounted 8 in. 100 AmpereFrame EHD, EDB, EDS,ED, EDH, FD, HFD

    9 in. 225 AmpereFrame EDB, EDS, ED,EDH, FD, HFD, FDC

    ckt1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    41

    ckt2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    22

    24

    26

    28

    30

    32

    34

    36

    38

    40

    42PRC2000

    Controller

    PRC2000 Panel Layout Instructions1. Select PRC2000 Panelboard

    Chassis from Figure 23.1-5.

    a. Determine required mains(lugs or breaker)

    b. Select appropriate Main Lugc. Select appropriate Main Device

    d. Select appropriate branchbreakers

    2. Layout panel as shown inFigure 23.1-5. Total "in." determinebox height shown in Table 23.1-3.(When total "in." units exceedsthe number shown, use nextsize box size.

    Layout Example1. Panel Description:

    a. PRC2000, 3-phase 4-wire, 208Y/120 Vac, interrupting ratingof 10,000 AIC symmetrical:

    225 ampere main lugs only atbottom, surface mounted andthe following branch breakers

    b. 36 20 ampere, 1-pole BABRSP

    c. 6 20 ampere, 1-pole BABRSPspaces

    2. Layout information fromFigure 23.1-5.

    a. PRC2000 with 42-circuit Interior26 in.

    b. 225 ampere Main Lugs Section4 in.

    c. Total Panelboard Height 30 in.

    3. From Table 23.1-3:

    Panel Height: 30 in.20 in. wide x 5.75 in. deep

    Box Height: 48 in.

    Box Catalog Number:YS2048 or EZB2048R

    Trim Catalog Number:LT2048S or EZT2048S

    Table 23.1-3. Box Selection Dimensions in Inches (mm)

    Cabinets

    Trims are code gauge steel, ANSI 61light gray painted finish. Boxes arecode gauge galvanized steel withoutknockout. Standard size is 20 in. wide x5.75 in. deep.

    Top and Bottom Gutters

    6.38 in.

    Minimum Side Gutters

    4 in. (minimum) on 20 in. wide boxsize.

    MaximumPanel Height

    Box Height,Inches

    Catalog Number

    YS Box LT Trim EZ Box EZ Trim

    20-Inch Wide x 5.75-Inch Deep Boxes

    0 22.0023.00 28.0029.00 34.00

    36.0042.0048.00

    YS2036YS2042YS2048

    LT2036S or FLT2042S or FLT2048S or F

    EZB2036REZB2042REZB2048R

    EZT2036S or FEZT2042S or FEZT2048S or F

    35.00 46.0047.00 58.00

    60.0072.00

    YS2060YS2072

    LT2060S or FLT2072S or F

    EZB2060REZB2072R

    EZT2060S or FEZT2072S or F