ppi brochure hydrocal 1008

4
HYDROCAL 1008 Multi-Gas-in-Oil Analysis System with Transformer Monitoring Functions Manufactured by: BM-HC1008/2 www.ppi.ph HYDROCAL 1008 is a permanently-installed multi-gas-in-oil analysis system with transformer monitoring functions. It allows for the individual measurement of moisture and the key gases hydrogen (H 2), carbon monoxide (CO), carbon dioxide (CO 2 ), methane (CH 4 ), acetylene (C 2 H 2 ), ethylene (C 2 H 4 ) and ethane (C 2 H 6 ) dissolved in transformer oil. As hydrogen (H 2 ) is involved in nearly every fault of the isolation system of power transformers and carbon monoxide (CO) is a sign of an involvement of the cellulosic/ paper isolation the presence and increase of acetylene (C 2 H 2 ) and ethylene (C 2 H 4 ) further classifies the nature of a fault as overheating, partial discharge or high energy arcing. The device can serve as a compact transformer monitoring system by the integration / connection of other sensors present on a transformer via it’s analog inputs: 4 analog inputs 0/4-20mADC 6 analog inputs 0/4-20mADC / 0-100VAC configurable by jumpers It is further equipped with digital outputs for the transmission of alarms or the execution of control functions (e.g. control of a cooling system of a transformer) 8 digital relay outputs 5 digital opto-coupler outputs Key Advantages Hydrogen (H2), carbon monoxide (CO), carbon dioxide (CO2), methane (CH4), acetylene (C2H2), ethylene (C2H4) and ethane (C2H6) , measurement. Moisture-in-oil measurement Communication interfaces ETHERNET 10/100 Mbit/s (both copper-wired/fibre-optical) and RS 485 to support proprietary communication protocols and to be open/ prepared for substation communication protocols IEC 61850, MODBUS, DNP 3 etc. Optional on-board GSM and analog modems for remote communication 6 analog AC voltage inputs for the connection of capacitive HV bushing sensors for HV bushing monitoring application.

Upload: reza

Post on 08-Sep-2014

163 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: PPI Brochure Hydrocal 1008

HYDROCAL 1008Multi-Gas-in-Oil Analysis System with Transformer Monitoring Functions

Manufactured by:

BM-HC1008/2

w w w. p p i . p h

HYDROCAL 1008 is a permanently-installed multi-gas-in-oil analysis system with transformer monitoring functions. It allows for the individual measurement of moisture and the key gases hydrogen (H2), carbon monoxide (CO), carbon dioxide (CO2), methane (CH4), acetylene (C2H2), ethylene (C2H4) and ethane (C2H6) dissolved in transformer oil.

As hydrogen (H2) is involved in nearly every fault of the isolation system of power transformers and carbon monoxide (CO) is a sign of an involvement of the cellulosic/ paper isolation the presence and increase of acetylene (C2H2) and ethylene (C2H4) further classifies the nature of a fault as overheating, partial discharge or high energy arcing. The device can serve as a compact transformer monitoring system by the integration / connection of other sensors present on a transformer via it’s analog inputs:

4 analog inputs 0/4-20mADC•6 analog inputs 0/4-20mADC / •0-100VAC configurable by jumpers

It is further equipped with digital outputs for the transmission of alarms or the execution of control functions (e.g. control of a cooling system of a transformer)

8 digital relay outputs•5 digital opto-coupler outputs•

Key AdvantagesHydrogen (H2), carbon monoxide (CO), carbon •dioxide (CO2), methane (CH4), acetylene (C2H2), ethylene (C2H4) and ethane (C2H6) , measurement.Moisture-in-oil measurement•Communication interfaces ETHERNET 10/100 •Mbit/s (both copper-wired/fibre-optical) and RS 485 to support proprietary communication protocols and to be open/ prepared for substation communication protocols IEC 61850, MODBUS, DNP 3 etc.Optional on-board GSM and analog modems •for remote communication6 analog AC voltage inputs for the connection •of capacitive HV bushing sensors for HV bushing monitoring application.

Page 2: PPI Brochure Hydrocal 1008

Transformer monitoring functionsVoltages and Currents(via voltage and current transformers / transducer)

Temperature MonitoringBottom and oil temperature(via additional temperatures sensors)

Free configurationAnalogue inputs can be free allocated to any additional sensor

Further Calculations:Hot spot: (according IEC 60078)Loss-of-lifeAgeing RateCooling Stage / Tap Changer Position(e.g. via current transducer)

HV Bushing Monitoring

HV Bushing / Test Tap / Name Plate Test methods: Leakage current Sum of currents

Test method: tanδ (Dissipation factor) PF (Power factor)

Bushing sensor

Operation Resistive Bridgeprinciple

Voltage range 69kV – 765 kV AC (Bushing / Primary) Max. 2.5 kV AC (Sensor / secondary)Current range: 0 – 140 mA ACThread: 0.75” / 1.25” / 2.25”

Capacity C1 and tanδ / PF under factory testing are documented on name plate of bushing

Configuration 1:Monitoring of high voltage side

Configuration 1:Reference HV bushing (from other transformer)

Configuration 2:Reference CCVT/CCPT

Configuration 2: Monitoring of high voltage and low voltage side

Page 3: PPI Brochure Hydrocal 1008

Sensor firmware main menu

User menuTransformer •administrator dataCustomer / Site •administrator data

Gas-in-oil menuChart diagram•Result table•

Transformer menuAging rate•Hot spot temperature•Loss-of-Live•

PC Software

Transformer administration dataAll administration data of a •transformer can be enteredNetwork of different power •plants and transformer banks can be configuredSelective contact to each •transformer in the networkObtaining information of total •transformer situation

Individual chart diagram for hydrogen (H2), carbon monoxide (CO), carbon dioxide (CO2), methane (CH4), acetylene (C2H2), ethylene (C2H4) and ethane (C2H6) and moisture.

The bushing monitoring setup menu allows the input of all basic parameters required for the bushing monitoring.

Display of alarm list. Details of each alarm and individual settings.

External menuVoltage and current •measurementBottom and top oil •measurementOil humidity •measurement

Alarm menuAlarm overview•Alarm acknowledgement•

Configuration menuAlarm level setting•Communication setting•Transformer setting •Installation

Gas-in-Oil menu Alarm menu Communication menu

Gas-in-Oil Overview menu Alarm setup/ edit menu Bushing monitoring setup menu

Page 4: PPI Brochure Hydrocal 1008

#8 Lapu-Lapu St., Magallanes Village, Makati City, 1232 PhilippinesTel.: +63 2 8675619, 8675620 Fax: +63 2 8520639Email: [email protected] Website: www.ppi.ph

Lot 8 Block 4 Phase 1 Southpark Plaza, Santiago St.Paseo de Magallanes Center, Magallanes Village Makati City, 1232 Philippines

Connections

Technical data HYDROCAL 1008

GeneralAuxiliary supply: 88 VACmin…276 VAC max 88 VDCmin…390 VDCmax. OptionalPower consumption: max. 350 VAHousing: AluminumDimensions: W 263 x H 263 x D 257 mmWeight: approx. 15 kgOperation temperature: -55ºC…+ 55 ºC(ambient)Oil temperature: -20 ºC…+90 ºC(in the transformer)Oil Pressure: 0-800 kpa (negative pressure allowed)

Safety CE certifiedIsolation protection: IEC 61010-1:2002Degree of protection: IP-55

MeasurementsGas / Humidity-in-Oil MeasurementMeasuring Quantiy Range AccuracyHydrogen H2 0…2.000 ppm ±15% ± 25 ppmCarb. Monoxide CO 0…5.000 ppm ±20% ± 25 ppmCarb. Dioxide CO2 0…20.000 ppm ±20% ± 25 ppmMethane CH4 0…2.000 ppm ±20% ± 25 ppmAcetylene C2H2 0…2.000 ppm ±20% ± 5 ppmEthylene C2H4 0...2.000 ppm ±20% ± 10 ppmEthane C2H6 0…2.000 ppm ±20% ± 25 ppmMoisture 0…100 ppm ±3% ± 3 ppm

Operation PrincipleMinimized gas sample production based on head-space •extraction principle (no membrane, negative pressure proof)To the patent registered oil sample system (EP 1 950 560 A1)•Infrared NIR gas sensor unit for CO, CO• 2, CH4, C2H2, C2H4 and C2H6Micro electronic gas sensor for H• 2Capacitive thin film moisture sensor•

Analogue and digital outputs (standard)Analogue DC Outputs Default

FunctionsAlternativefunctionsType Range

Current DC 4…20 mADC H2Con. Free config.Current DC 4…20 mADC CO Con. Free config.Current DC 4…20 mADC CO2Con. Free config.Current DC 4…20 mADC CH4Con. Free config.Current DC 4…20 mADC C2H2 Con. Free config.Current DC 4…20 mADC C2H4Con. Free config.Current DC 4…20 mADC C2H6 Con. Free config.Current DC 4…20 mADC Moisture Con. Free config.

Digital OutputsType Control Voltage Max. Switching CapacityRelay 8 x 12 VDC 220 VDC/ VAC/ 2 A/ 60 W

Analogue inputs and digital outputs (optional)Analogue DC Inputs (External sensors) Accuracy RemarksType Range of the measuring valueCurrent DC 4 x 0/4..20 mADC ≤ 0.5%

Analogue AC Inputs (cap. HV Bushing) Accuracy RemarksType Range of the measuring valueVoltage AC 6x0…100VAC or ≤ 0.5% Samplingor Current DC 6x 0/4…20 mADC ≤ 1.0% rate: 4 kHz

Digital OutputsType Control Voltage Max. Switching Capacity

Opto-Coupler 5x5 VDCUce: 4 V(rated)/ 35 V max.)Uce: 7 V (max.)Uce: 40 mA (max.)

CommunicationETHERNET 10/100 Mbit/s (both copper-wired/fibre-optical)•RS 485 (proprietary communication or MODBUS Protocol)•On-board GSM or analog modem (optional)•