    Big gap between Precast panel &Aluminum Glass window

    Brief introduction to the constructiondefects found in blue zone

    1Cx-TEAM

  • 8/8/2019 Pp Reports

    2/14

    MAJOR DEFECTS

    Corridor FCU are not accessible for maintenance and there is no properinsulation on the chilled waterline.

    Toilet valves should be accessible, existing valves are inside the falseceiling.

    Portion of duct which is heater area it should be insulted.

    FCU should be insulated completely from outside using aero flexinsulation / rubber sheet.

    In Kitchen area are false ceiling should be metallic false ceiling notgypsum board to prevent damages causing from A/C drain pan.

    Toilets are made of precast PODs while are having heavy damages.

    Aluminum sliding doors should have additional handle and locking

    systems.2Cx-TEAM

  • 8/8/2019 Pp Reports

    3/14

  • 8/8/2019 Pp Reports

    4/14

    MAJOR DEFECTS

    Road Defects.

    No Water Proofing in Planter Boxes.

    Exterior building have lot of gaps Cladding.

    4Cx-TEAM

  • 8/8/2019 Pp Reports

    5/14

    CORRIDOR FCU ARE NOT ACCESSIBLE AND NO PROPERCORRIDOR FCU ARE NOT ACCESSIBLE AND NO PROPERINSULATION ON THE CHILLED WATER LINEINSULATION ON THE CHILLED WATER LINE

    Corridor FCU are not accessibleCorridor FCU are not accessible No proper insulation on the chilled water line

    5Cx-TEAM

  • 8/8/2019 Pp Reports

    6/14

  • 8/8/2019 Pp Reports

    7/14

    TOILET VALVES ARE INSIDE THE FALSE CEILINGTOILET VALVES ARE INSIDE THE FALSE CEILING

    Toilets water isolation valves are inside the false ceiling

    7Cx-TEAM

  • 8/8/2019 Pp Reports

    8/14

    NO PROPER PROVISION FOR BACK FLOWNO PROPER PROVISION FOR BACK FLOWPREVENTIONPREVENTION

    The manhole is filled with sewer ofapproximately : 2m depth

    Stagnated water in WC, inside apartments dueto blockage of drain at Zone-E.

    The drain line was blocked due to non functioning of the lift station in

    zone E and no provision of back flow preventer.8Cx-TEAM

  • 8/8/2019 Pp Reports

    9/14

    TOILET PRECAST PODTOILET PRECAST POD

    Toilet Precast POD mostly damaged and bighole were found

    Toilet Precast POD heavy damaged

    9Cx-TEAM

  • 8/8/2019 Pp Reports

    10/14

    Dangerous Beam-Column Joint Connection No connecting dowel bar between beam andbracket support.

    GRC TRELLIS AT THE GARRAGEAREA

    10Cx-TEAM

  • 8/8/2019 Pp Reports

    11/14

    Fresh Air Duct at the Roof top should be more firm and enough strong

    FRESH AIR DUCT AT THE ROOFTOP

    11Cx-TEAM

  • 8/8/2019 Pp Reports

    12/14

    Corner of Road-3 and Road-2 along GolfClub

    RAOD DEFECTS

    12Cx-TEAM

    Bayt Hikmah Boulevard near Trafficlight opposite of Gas Station

  • 8/8/2019 Pp Reports

    13/14

    Planter Box Drain Pipes not fixedproperly

    Planter Box Waterproofing

    13Cx-TEAM

    Planter Box Waterproofing damages

  • 8/8/2019 Pp Reports

    14/14

    Big gap between Precast panel &Aluminum Glass window

    EXTEROIR BLUIDING

    14Cx-TEAM

    Big gap between Precast panel &Aluminum Glass window