Big gap between Precast panel &Aluminum Glass window
Brief introduction to the constructiondefects found in blue zone
1Cx-TEAM
-
8/8/2019 Pp Reports
2/14
MAJOR DEFECTS
Corridor FCU are not accessible for maintenance and there is no properinsulation on the chilled waterline.
Toilet valves should be accessible, existing valves are inside the falseceiling.
Portion of duct which is heater area it should be insulted.
FCU should be insulated completely from outside using aero flexinsulation / rubber sheet.
In Kitchen area are false ceiling should be metallic false ceiling notgypsum board to prevent damages causing from A/C drain pan.
Toilets are made of precast PODs while are having heavy damages.
Aluminum sliding doors should have additional handle and locking
systems.2Cx-TEAM
-
8/8/2019 Pp Reports
3/14
-
8/8/2019 Pp Reports
4/14
MAJOR DEFECTS
Road Defects.
No Water Proofing in Planter Boxes.
Exterior building have lot of gaps Cladding.
4Cx-TEAM
-
8/8/2019 Pp Reports
5/14
CORRIDOR FCU ARE NOT ACCESSIBLE AND NO PROPERCORRIDOR FCU ARE NOT ACCESSIBLE AND NO PROPERINSULATION ON THE CHILLED WATER LINEINSULATION ON THE CHILLED WATER LINE
Corridor FCU are not accessibleCorridor FCU are not accessible No proper insulation on the chilled water line
5Cx-TEAM
-
8/8/2019 Pp Reports
6/14
-
8/8/2019 Pp Reports
7/14
TOILET VALVES ARE INSIDE THE FALSE CEILINGTOILET VALVES ARE INSIDE THE FALSE CEILING
Toilets water isolation valves are inside the false ceiling
7Cx-TEAM
-
8/8/2019 Pp Reports
8/14
NO PROPER PROVISION FOR BACK FLOWNO PROPER PROVISION FOR BACK FLOWPREVENTIONPREVENTION
The manhole is filled with sewer ofapproximately : 2m depth
Stagnated water in WC, inside apartments dueto blockage of drain at Zone-E.
The drain line was blocked due to non functioning of the lift station in
zone E and no provision of back flow preventer.8Cx-TEAM
-
8/8/2019 Pp Reports
9/14
TOILET PRECAST PODTOILET PRECAST POD
Toilet Precast POD mostly damaged and bighole were found
Toilet Precast POD heavy damaged
9Cx-TEAM
-
8/8/2019 Pp Reports
10/14
Dangerous Beam-Column Joint Connection No connecting dowel bar between beam andbracket support.
GRC TRELLIS AT THE GARRAGEAREA
10Cx-TEAM
-
8/8/2019 Pp Reports
11/14
Fresh Air Duct at the Roof top should be more firm and enough strong
FRESH AIR DUCT AT THE ROOFTOP
11Cx-TEAM
-
8/8/2019 Pp Reports
12/14
Corner of Road-3 and Road-2 along GolfClub
RAOD DEFECTS
12Cx-TEAM
Bayt Hikmah Boulevard near Trafficlight opposite of Gas Station
-
8/8/2019 Pp Reports
13/14
Planter Box Drain Pipes not fixedproperly
Planter Box Waterproofing
13Cx-TEAM
Planter Box Waterproofing damages
-
8/8/2019 Pp Reports
14/14
Big gap between Precast panel &Aluminum Glass window
EXTEROIR BLUIDING
14Cx-TEAM
Big gap between Precast panel &Aluminum Glass window