powerpack plus serisi 1-3 kva 0,8 output power factor - · pdf filethe principle of the...
TRANSCRIPT
![Page 1: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/1.jpg)
USERMANUALPOWERPACKPLUSSERIES
1‐3KVA
0,8OutputPowerFactor
![Page 2: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/2.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
2
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
![Page 3: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/3.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
3
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
USERMANUALPOWERPACKPLUSSERIES
1‐3KVA
0,8OutputPowerFactor
![Page 4: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/4.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
4
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
CONTENTS
1. SafetyInstruction .......................................................................................................................... 7
1.1. SafetyInstruction.....................................................................................................................................7
2. ProductIntroduction ..................................................................................................................... 8
2.1. Theappearanceoftheproduct.............................................................................................................8
2.2. ThePrincipleoftheProduct..................................................................................................................9
3. Installation ................................................................................................................................... 11
3.1. UnpackingandInspection....................................................................................................................11
3.2. LongBackupExternalBatteryConnection.......................................................................................11
4. PanelDisplay,OperationandRunning ...................................................................................... 12
4.1. FaceplateDisplayIllumination............................................................................................................12
4.1.1. KeysFunction.................................................................................................................................12
4.1.2. TheFunctionofLEDIndicators..................................................................................................13
4.1.3. LCDDisplayFunctions..................................................................................................................13
4.2. Operation..................................................................................................................................................15
4.2.1. StartupOperation.........................................................................................................................15
4.2.2. TurnoffOperation.........................................................................................................................15
4.2.3. UPSSelf‐Test/MuteTestOperation..........................................................................................16
4.3. ParameterSetting...................................................................................................................................16
4.3.1. BypassModeSetting/OutputVoltageSetting.........................................................................16
4.4. ParametersInquiring............................................................................................................................17
4.5. RunMode..................................................................................................................................................18
4.5.1. BypassMode...................................................................................................................................18
4.5.2. LineMode........................................................................................................................................18
4.5.3. BatteryMode..................................................................................................................................18
4.5.4. FaultMode.......................................................................................................................................19
![Page 5: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/5.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
5
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
5. Maintenance ................................................................................................................................. 20
5.1. BatteryMaintenance..............................................................................................................................20
6. TroubleshootingandPerformanceofProduct ........................................................................ 21
6.1. LEDIndicationandWarningTable....................................................................................................22
6.2. Troubleshooting.....................................................................................................................................24
6.3. EMCStandard/SafetyStandard...........................................................................................................24
6.4. ProductPerformance.............................................................................................................................25
6.5. CommunicationInterface.....................................................................................................................26
6.5.1. RS232...............................................................................................................................................26
6.5.2. RS232CableSpecifications.........................................................................................................26
7. Guarantee ..................................................................................................................................... 27
7.1. TermsofGuarantee................................................................................................................................27
7.2. CasesNotCoveredbytheGuarantee.................................................................................................28
8. ContactInformation .................................................................................................................... 32
![Page 6: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/6.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
6
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
AbouttheManual
ThismanualispreparedfortheusersofPowerpackPlusSerisi1‐3kVA.
CompanionManuals
Forfurtherinformationaboutthisdeviceanditsoptions,pleasevisitwww.makelsan.com.tr
Updates
Pleasevisitwww.makelsan.com.trforupdates.Alwaysusethelatestmanuals.
![Page 7: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/7.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
7
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
1. SafetyInstruction
AbstractThischaptermainlyintroducethesafetymarksandnotesof1KVA‐3KVAserieson‐lineUPS.Readthischaptercarefullybeforeoperatingontheequipment.
1.1. SafetyInstruction
There is dangerous voltage and high temperature inside the UPS. During theinstallation,operationandmaintenance,pleaseabidethelocalsafetyinstructionsandrelativelaws,otherwiseitwillresultinpersonnelinjuryorequipmentdamage.Safetyinstructionsinthismanualactasasupplementaryforthelocalsafetyinstructions.Ourcompanywillnotassumetheliabilitythatcausedbydisobeyofsafetyinstructions.Pleasenotethefollowing:
1. Don'tusetheUPSwhentheactualloadexceedstheratedload.
2. Therearehigh‐capacitybatteriesinthestandardtypeUPS.Youmustn'topenthe
enclosureoritwillleadtoelectricshock.Ifitneedsinternalmaintenanceorbattery
replacement,pleasesendittothedesignatedsite.
3. Internalshort‐circuitoftheUPSwillcauseelectricshockorfire.Sodon'tplace
thecontainersequippedwithliquidonthetopoftheUPSsoasnottocausedangerof
electricshockandsoon.
4. Don'tputtheUPSinaplacewithhightemperatureorhumidityaswellasthe
corrosivegas,muchdust.
5. Keepgoodaircirculationbetweenin‐ventonfrontpanelandout‐ventonback
panel.
6. Avoiddirectsunlightornearheat‐dispensedobjects.
7. In case that the smoke appears on the UPS, please cut off the power as
soonaspossibleandcontactthedealerservicesite.
![Page 8: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/8.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
8
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
2. ProductIntroduction
2.1. Theappearanceoftheproduct
Figure‐2OutputSocketType
Şekil-2 2/3KVA Arka Panel Görünümü Figure‐1 1KVARearPanelview
![Page 9: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/9.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
9
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
2.2. ThePrincipleoftheProduct
Figure3UPSPrincipleDiagram
1. InputFilter:CompletefilteringtheinputACutilitypowertoprovidethecleanpowerforUPS.
2. AC/DCConverter:ConvertthefilteredACmainstoDCandboosttheDCforDC/ACinverter.
3. DC/DCBooster:WhentheUPSworksinbatterymode,thecircuitbooststheDCforDC/ACinverter
4. DC/ACInverter:ConverttheboostedDCtostableACoutput..
5. Bypass:WhenoverloadorfailureofinvertinghappenintheUPS,ittransferstobypassmodetosupplypowertoloads
6. Charger: Standardunitprovides1A;longbackupunitprovides6A.
7. Battery:SealedLeadAcidBattery.
8. OutputFilter:CompletefilteringtheoutputoftheUPStoprovidethecleanpowerforloads.
![Page 10: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/10.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
10
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
3. Installation
3.1. UnpackingandInspection1. Unpacking the UPS and check that whether it's damaged during thetransportation. If damaged or some parts missing, don't start the machine andinformthecarrierandfranchiser.2. Checktheannex(pleaseconsultAppendixTable1).3. Check if the equipment is justwhat youwanted to purchase. You can affirmthroughinspectingthemodelnumberonbackpaneloftheequipment.
NOTES:
1. PleaseplacetheUPSinaclean,stableenvironment,avoidthevibration,dust,toohumidity,flammablegasandliquid,corrosive.2. TheambienttemperaturearoundUPSshouldkeepinarangeof0 ~40 .IfUPSworksabove40 ,itisrequiredthattheratedvalueofthelargestloaddecreases12%whilethetemperatureincreasesevery5 .Thehighesttemperaturecannotbemorethan50 whenUPSworks.3. UPSshouldbeplacedinasufficientlyventilatedplace.
3.2. LongBackupExternalBatteryConnection
Figure4BatteryConnection
![Page 11: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/11.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
11
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
WARNING:
Beforeinstallingbattery,makesurethatUPSandbreakerareallturnedoff.Removeallyourmetallicadornmentsuchasfingerring,watch,andsoonbeforeconnectingbattery. Noanti‐connectionorshortcircuitbetweenthebatteryanodeandcathodeforever.Redcableconnectwithbatteryanode“+”andblackcableconnectwithcathode“‐”. Please use the screwdriver with insulating handle. Do not lay the tools ormetallicgoodsonthebattery.
NOTICE:
Whenusingtheexternalbattery,Itisbesttouseexternalbatterycablewhichmatcheswiththeequipment. WhenconnectingloadtoUPS,firstturnoffloadandthenconnectthepowercableandfinallyturnonloadone‐by‐one. Inductance loads such as motor, fluorescent lamp, photocopier are strictlyprohibitedconnectingtoUPStoavoiddamage.
PlugUPSonthespecialsocketwithover‐currentprotection,thepowersocketthatusedshouldbeconnectedwithgroundwire. UPSislikelytohaveoutputvoltagenomatterwhetherthepowerinputcableispluggedinmainsinputsocket.IfyouwishUPShavenooutput,firstbreakofftheswitchandthencancelthemains. Whenconnect laserprinter, select thecapacityofUPSaccording to theUPSstartpowerbecausethestartuppowerishigher.
![Page 12: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/12.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
12
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
4. PanelDisplay,OperationandRunning
Theoperationissimple,operatorsonlyneedtoreadthemanualandfollowtheoperationinstructionslistedinthismanualwithoutanyspecialtraining.
4.1. FaceplateDisplayIllumination
4.1.1. KeysFunction
Figure5.FrontPanelButtonsInstruction
ONkey( + )
PressandholdthiskeyformorethanhalfasecondtoturnontheUPS.
OFFkey( + )
PressandholdthiskeyformorethanhalfasecondtoturnofftheUPS.
TEST/MUTEkey( + )
Pressandholdthekeyformorethan1secondinLinemodeor
economicalmode:UPSrunstheself‐testfunction.
Pressandholdthekeyformorethan1secondinbatterymode:
UPSrunsthemutefunction.
INQUIRINGkeyorNon‐functionsettingmode:
Pressandholdthekeyformorethanhalfasecond(lessthan2seconds):IndicatetheitemsoftheLCDitemsectionorderly.
Pressandholdthiskeyformorethan2seconds:Circularlyandorderlydisplaytheitemsevery2seconds,whenpressandholdthekeyforsometimeagain,itwillturntooutputstatus.
Functionsettingmode:
Pressandholdthekeyformorethanhalfasecond(lessthan2seconds):Selectthesetoption.
Functionsettingkey
![Page 13: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/13.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
13
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
Non‐functionsettingmode:
Pressandholdthekeyformorethan2seconds:Functionsettinginterface.
Functionsettingmode:
Pressandholdthekeyformorethanhalfasecond(lessthan2seconds):Affirmthesetoption.
Pressandholdthekeyformorethan2seconds,exitfromthisfunctionsettinginterface.
4.1.2. TheFunctionofLEDIndicators
WarningredLEDison:UPSisfault.Forexample:Overloadbeyondtheallowedtime,inverterfault,BUSfault,overtemperaturefaultetc.
BypassyellowLEDison:UPSisalarming.
Forexample:Bypassmodesupplypowerandetc.
BatteryyellowLEDison:UPSisalarming.
Forexample:Batterymodesupplypowerandetc.
InvertergreenLEDison:UPSisnormallypoweredbymainsorbatterymode.
AfterstartingtheUPS,thefourLEDswilllightandgooutone‐by‐one.ItcirculatesseveraltimesuntilstartingtheUPS
successful.
NOTE:
AstotheLEDindicationindifferentmodes,pleaserefertotheLEDdisplaypanelandwarningtable.
4.1.3. LCDDisplayFunctions
LCD display comprises numerical value section, capacity graphics section, fan‐status graphics section and charger‐status graphics section. Numerical valuesection-display the corresponding numerical value of inquiring items(output,load,temperature,input,battery),forexample,asthegraphicsshowsabove,the
![Page 14: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/14.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
14
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
output voltage is 220v, the output frequency is 50Hz. Capacity graphicssection-display the capacity of the battery and load. Every pane represents
20%capacity. As graphics showed above, the capacity of the battery is 80%‐
100% (5panes), the loadreaches40%‐60%(3panes).WhenUPS isoverload,theiconwillflash,whencapacityofbatteryistoolowordisconnected,theiconwillalsoflash.
Fan‐status graphics section-display if the fan works normally. When the fanworks normally, it will show the dynamic fan blades rotating; when the fanworks abnormally, the iconwill keep on flashingwith the warning . Charger‐statusgraphicssection-displaythestatusofthecharger.Whenchargerworksnormally, the corresponding icon will vary dynamically and orderly, just asGraphics(1);
whenchargerworksabnormally,theiconwillflashinawhole,asGraphics(2):
![Page 15: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/15.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
15
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
WhenUPSisinbatterymode,thenumberoftheiconsofthecharger‐statesectionwillvaryaccordingtothechangeablecapacityofthebattery(pane).Forexample,therearefivepanesinFig.A,(astherightpictureoftheGraphics(3)shows),sothecorrespondingnumberoficonsisfiverows(astheleftpictureoftheGraphics(3)shows),followedbythisrule.
4.2. Operation
4.2.1. StartupOperationTurnontheUPSinLineMode
1. Oncemainspower isplugged in, theUPSwillchargethebattery,at themoment,LCD shows that the output voltage is 0, which means UPS has no output. If it isexpectedtohaveoutputofbypass,youcansetthebps“ON”byLCDsettingmenu.
2. PressandholdtheONkeyformorethanhalfasecondtostarttheUPS,thenitwillstarttheinverter.
3. Once started, theUPSwill performa self‐test function, LEDwill light andgooutcircularly and orderly. When self‐test finishes, it will come to line mode, thecorrespondingLEDlights,UPSisworkinginlinemode.
TurnontheUPSbyDCWithoutMainsPower
1. Whenmainspowerisdisconnected,pressandholdtheONkeyformorethanhalfasecondtostartUPS.2. TheoperationofUPSintheprocessofstartisalmostthesameasthatwhenmainspowerisin.Afterfinishingtheself‐test,thecorrespondingLEDlightsandUPSisworkinginbatterymode.
4.2.2. TurnoffOperationTurnofftheUPSinlinemode
1. Press andhold theOFFkey formore thanhalf a second to turnoff theUPSandinverter.
2. AfterUPSshuttingdown,LEDgooutand there isnooutput. Ifoutput isneeded,youcansetbps“ON”onLCDsettingmenu.
![Page 16: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/16.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
16
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
TurnOfftheUPSbyDCWithoutMains
1. PressandholdtheOFFkeyformorethanhalfasecondtoturnofftheUPS.
2. WhenturningofftheUPS,itwilldoself‐testingfirstly.LEDlightandgooutcircularlyandorderlyuntilthereisnodisplayonthepanel.
4.2.3. UPSSelf‐Test/MuteTestOperation
1. WhenUPSisinlinemode,pressandholdtheself‐test/mutekeyformorethan1second,LEDslightandgooutcircularlyandorderly.UPScomestoself‐testmodeandtestsitsstatus.Itwillexitautomaticallyafterfinishingtesting,LEDresume.2. WhenUPSisinbatterymode,pressandholdtheself‐test/mutekeyformorethan1second,thebuzzerstopsbeeping.Ifyoupressandholdtheself‐test/mutekeyforonemoresecond,itwillrestarttobeepagain.
4.3. ParameterSettingUPS has setting function. It can run the setting on any mode. After setting, it willbecomeeffectiveatoncewhenmeetssomestandards.Thesetinformationcanbesavedonlywhen thebattery connectedandnormally turningoff theUPS.Theoperationofsettingisasfollowing:
4.3.1. BypassModeSetting/OutputVoltageSetting
1. Enterthesettinginterface.Pressandholdthefunction setting key for more than 2 seconds,thencometosettinginterface,Pressandholdthefunctionsettingkeyformorethanhalfasecond(lessthan2seconds),selectthefunctionsetting,choosethebypassoutput,Outputvoltagesettinginterface, at the moment, the letters “bPS”“OPU”willflashasfollowing:
![Page 17: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/17.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
17
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
2. EntertheBps/OPUsettinginterface.Pressandholdthefunctionsettingkeyformorethanhalfasecond(lessthan2seconds),thencometosettinginterface of bPS, at this time, the letters “bPS”/”OPU”willlightforalongtime.The“ON”(orOFF)ornumericalvaluebelowtheBps/OPUwillflash.Press and hold the inquiring key or more thanhalf a second(less than 2 seconds) to determinewhether the bPS function is used or not. Ifused,the correspondingword is “ON”, if not, theword is “OFF”, It canbedeterminedbyyourself.Press and hold the inquiring key or more thanhalf a second (less than 2 seconds), select thenumerical value in accordance with “OPU”function. The provided voltages are 208v, 220v,230v, 240,you can choose anyone by yourself(Thedefaultis220v)3. ConfirmtheBypassoutput/outputvoltageselectinginterface.AfterselectingONorOFFornumericalvalue,pressandholdthefunctionsettingkeyformorethanhalfa second(less than2seconds).Now, thebPS/OPUsetting function iscompleted and The “ON”(or OFF) or numerical value below the Bps/OPUwilllightwithoutflash.
4. Exit fromthesetting interface.Pressandhold functionsettingkey formorethan half a second (less than 2 seconds), exit from the setting interface andreturntomaininterface.
NOTE:
Whensettingtheoutputvoltage,you'dbettercutofftheloadoftheUPSfirst.
4.4. ParametersInquiring
Pressandholdtheinquiringkeyorormorethanhalfasecond(lessthan2seconds)toinquireaboutitems.Theinquireditemsincludeinput,battery,output,load,temperature.Pressandholdtheinquiringkeyformorethan2seconds,LCDbeginstodisplaytheitemscircularlyandorderlywhichtransfertoanotherevery2seconds.Pressandholdthekeyforsometimeagain,itwillreturntooutputstatus.
![Page 18: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/18.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
18
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
4.5. RunMode
4.5.1. BypassMode
LEDindicationsonfrontpanelinbypassmodeareasfollowing:
BypassyellowLEDison,thebuzzerbeepsonceevery2minutes.ThewarningredLEDisonwhenbeeping,LCDdisplaysareaccordingtotheexactloadandbatterycapacity.
Turntobypassmodeunderthefollowingtwoconditions:
1. TurnofftheUPSinlinemodewhilestartthebypassoutput.
2. Overloadinlinemode.
NOTE:
WhenUPSisworkinginbypassmode,ithasnobackupfunction.
4.5.2. LineMode
LEDindicationsonfrontpanelinlinemodeareasfollowing:TheinvertergreenLEDison.
WheninputACmainsisinlinewiththeworkingconditions,UPSwillworkinlinemode.
4.5.3. BatteryMode
LED indications on front panel in batterymode are as following: both the invertergreenLEDandbatteryyellowLEDareon,thebuzzerbeepsonceevery4seconds.ThewarningredLEDisonwhenbeeping.
Whenthemainspowerdownorinstable,UPSwillturntobatterymodeatonce.
![Page 19: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/19.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
19
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
4.5.4. FaultMode
LEDindicationsonfrontpanelinfaultmodeareasfollowing:warningredLEDison
Faultmode(LCDinterfaceonwhichthefaultcodedisplay)
WhenUPShasfault.ThewarningLEDisonandthebuzzerbeeps.UPSwillturntofault
mode. UPS cuts off the output and LCD display fault codes. At themoment, you canpress the mute key to make the buzzer stop beeping temporarily to wait formaintenance.YoucanalsopresstheOFFkeytoshutdowntheUPSwhenconfirmthatthereisnoseriousfault.
NOTE:
Asforcorrespondinginformationofthefaultcode,pleaserefertoFaultCode
informationTableinAppendix.
NOTICE:
ThefollowingprocessmustbeperformedifUPSisconnectedwithgenerator:
Firstturnongenerator,afteritrunsstablyconnectoutputpowerofgeneratortoUPS input terminal, then turnonUPS.AfterUPS turnedon,pleaseconnectloadone‐by‐one.
It is recommended that the generator capacity is as twice as UPS ratedcapacity
You'dbetternotusetheECOmodewhenthequalityoftheinputACmainsisnotgood
![Page 20: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/20.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
20
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
5. Maintenance
OnlyminimummaintenanceisrequiredforthisseriesofUPS.Thebatteryissealedleadacidmaintenance free. It only needs to be kept charging to obtain the expected life.Whether it is started or not, the UPSwould charge batteries once it is connected tomainsandprovideprotectionforover‐charginganddeepdischarging.
5.1. BatteryMaintenance
1. ItisrecommendedthatthebatteriesaremanuallychargedordischargedonceeverythreeorfourmonthsifUPShasnotbeenusedforalongtimeorthepowerislong‐termuninterruptible.Thebatterywillbefullydischargetolow‐voltageprotectionshutdown.Thenitneedstobefullychargedonce.
2. Inhightemperaturearea,batteriesshouldbemanuallychargedanddischargedonceeverytwomonths.Theprocessisthesameasthatsaidabove.
3. Undernormalcircumstancesofusing,thebatteryworkinglifeisthreetofiveyears.Ifyoufindthatthebatterydonotactwellsuchasobviouslyshorteningofbackuptime,toomuchimbalanceonbatteryvoltagesoon,thebatteryshouldbereplacedassoonaspossible,whichmustbeperformedbyqualifiedpersonnel.
4. Whenreplacebattery,itisrecommendedtochangebatteryalltogetherinsteadofchangingseparately.
NOTICE:
Before replacing batteries, first please turn off theUPS and break off themains.Removeyourmetallicadornmentsuchasfingerring,watchandsoon.
Whenreplacebatteries,pleaseusethescrewdriverwithinsulatinghandle.Donotlaythetoolsormetallicgoodsonthebattery. Neverreverseorshortcircuitbetweenthebatteryanodeandcathode.
![Page 21: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/21.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
21
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
6. Troubleshootingand PerformanceofProduct
ThefollowingmessagesaretheinformationthatuserswouldfindonUPSwhenitmeetssomeproblems.Userscanjudgeifthefaultiscausedbyexternalfactorsandknowhowtodealwithitbymakingfulluseoftheinformation.
1. Faultindicatoron,indicatesthattheUPShasdetectedsomefaults.
2. Buzzerbeeps,indicatesthatUPSneedtobepaidattentionto,ifbeepsforalongtime,itmeansthatthereissomethingwrongwiththemachine.
3. Ifyouneedhelp,contactourservicedepartment,thefollowingmessagesshouldbeprovidedforanalysis:
◆ UPSMODELNO.andSERIALNO.
◆Dateoffaulthappened
◆Detaileddescriptionoftheproblem(includeindicatorstatementsonpanel)
![Page 22: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/22.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
22
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
6.1. LEDIndicationandWarningTableAppendix1:Thecorrespondingworkingstatusofindications NO WorkingStatus Indication Warning Remarks
Nor Bat Bps Fau
1 LineMode
Normalvoltage 1 None
High/lowvoltage
protection,turntobatterymode
1 1 ♦ Onceeveryfour
seconds
2 BatteryMode
Normalvoltage 1 1 ♦ Onceeveryfour
seconds
BatteryVoltage
abnormalwarning
1 ♦ ♦ Oncepersecond
3 BypassMode
MainACNormal
voltageinbypass
mode
1 ♦ Onceeverytwominutes EliminateafterstartingtheUPS
MainAChigh
voltagewarninginbypassmode
♦ Onceeveryfour
seconds
MainAClow
voltagewarningin
bypassmode
♦ Onceeveryfour
seconds
4 Batterydisconnectwarning
BypassMode 1 ♦ Onceeveryfour
seconds
Affirmifthebatteryswitchisclosed
InvertingMode 1 ♦ Onceeveryfour
seconds
Affirmifthebatteryswitchisclosed
Poweruporstart Sixtimes Affirmifthebatteryisconnected
well
5 Outputoverloadprotection
Overloadwarning
inlinemode,
1 ♦ Twiceperseconds Removethelessimportantloads
Overloadinline
mode,protection
1 1 Longbeeps Removethelessimportantloads
Overloadwarning
inbatterymode
1 1 ♦ Twiceper
second
Removethelessimportantloads
Overloadin
batterymode,protection
1 1 1 Longbeeps Removethelessimportantloads
6 Overloadwarning
inbypassmode
1 ♦ Onceevery2seconds Removethelessimportantloads
7 Fanfault
(faniconflash)
s s s ♦ Onceevery2seconds
Checkifthefanisblockedby
object.
8 Faultmode 1 Longbeeps Ifdisplayfaultcodeandicon
lights,contactformaintenance
whenyoucan’tdealwithitby
yourself.
![Page 23: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/23.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
23
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
Appendix2:Fault Codes
BypassMode
LineMode BatteryMode
BatteryTestMode
EcoMode
BusHigh 00 01 02 03 04
BusLow 05 06 07 08 09
Busunbalance 10 11 12 13 14
BusSoftfail 15 16 17 18 19
inverterhigh 20 21 22 23 24
inverterLow 25 26 27 28 29
invertersoftstartfail 30 31 32 33 34
Busdischargefail 35 36 37 38 39
OverHeat 40 41 42 43 44
OP(inverter)short 45 46 47 48 49
OverLoad 50 51 52 53 54
Opsts&InvRlyShort 55 56 57 58 59
lineNTCbreak 60 61 62 63 64
shutdownfault 65 66 67 68 69
linefuseopen 70 71 72 73 74
● _indicator lights for a long time
★ _indicator flashes
▲ _the status of indicator depends on other conditions
NOTE:WhenUPShasfault,itisconvenientforyoutoknowtheworkingstatusofUPSandtheexactinformationaboutthefaultpromptlybyreferringtothetwotableslistedabove.
![Page 24: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/24.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
24
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
6.2. TroubleshootingWhen the fault occurs, firstly, perform troubleshooting by referring to thetroubleshootingtable.Ifthefaultstillexists,pleasecontactthefranchiser.
Fault Cause Solution
The“INPUT”letterson
LCDdisplaysectionflashes
Anti‐connectionofmainsliveandneutralormainsisoutofrange
Re‐connecttheinputpowercableandmakeacorrectconnection
Batterycapacityindicator
flashes
Batterylowvoltageorbatterydisconnected
CheckUPSbattery,connectbatterywell,ifbatterydamaged,replaceit
Mainsnormal,butUPShasnoinput
UPSinputbreakeropencircuit
Pressthebreakerforreset
Shortbackuptime
Batterynotfullycharged KeepUPSconnectingwithmainspowerformorethan8hours,rechargebattery
UPSoverload Checktheusageofloads,removesome
redundantdevices
Batteryaged Whenreplacebattery,contactfranchisertogetbatteryandrelativeassembly
UPSdoesn’tstartupafter
pressingtheONkey
Didn’tpressthecombinationkeysof“on”
Pressthetwokeysatthesametime
UPShasnobatteryconnectedorbattery
voltagelowandtoomanyloadsconnected
ConnectUPSbatterywell,ifbatteryvoltagelow,pleaseturnoffUPSandremovesomeloads,thenstartUPS
FaultoccursinsideUPS Contactsupplierforservicing
Theiconofchargerstatus
onLCDdisplayflashesand
buzzerbeepsonceper
second
Chargerdoesn’tworknormallyorbattery
aged
Contactsupplierforservicing
6.3. EMCStandard/SafetyStandard
◆OurproductaremanufacturedaccordingtothefollowingEMCinternationalgrade
standardandhaspassedtheCEauthentication:
EMCStandardNumber SafetyStandardNumber
IEC62040‐2 IEC62040‐1
IEC61000‐4‐2 GB4943‐5
IEC61000‐4‐3
IEC61000‐4‐4
IEC61000‐4‐5
![Page 25: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/25.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
25
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
6.4. ProductPerformance
Model 1kVA(AS)
1kVA(AH)
2kVA(AS)
2kVA(AH)
3kVA(AS)
3kVA(AH)
RatedCapacity 800W/1000VA 1600W/2000VA 2400W/3000VA
Input
Phase Singlephaseandearthing
VoltageRange 115±5VAC‐295±5VAC
FrequencyRange 46Hz‐54Hz@50HZ/56Hz‐64Hz@60HZ
PowerFactor ≥0.98
BypassRange (176±5~255±5)VAC(adjustable)
CurrentHarmonic <15%(100%nonlinearload)
Output
Ratedvoltage 208VAC/220VAC/230VAC/240VAC
PowerFactor 0,8
VoltagePrecision ±%2
OutputFrequency
LineModE
1.Wheninputfrequencyisintherange,theoutputfrequencyisthesameasthatofinput.
2.Wheninputfrequencyisoutoftherange, theoutputfrequencyis(50/60±0.2)Hzwhenturntobatterymode.
Bat.Mode
(50/60±0.2)Hz
CrestFactor 3:1
TransferTime Mains←→battery=0ms
Mains←→bypass<4ms
Overload
Capacity
Bat.Mode
108%±5%<load≤150%±5%>30scutoffoutputandwarn,
150%±5%<load<200%±5%>300mscutoffoutputandwarn
LineMode
108%±5%<load≤150%±5%>30stransfertobypassandwarn
150%±5%<load<200%±5%>300mstransfertobypassandwarn
Efficiency LineMode
FullLoad≥86%
Bat.Mode
FullLoad≥84%
OutputVoltage
Distortion
≤3%(100%linearload)
≤5%(100%nonlinearload)
Battery
InputBatteryVoltage 24VDC 48VDC 72VDC
InternalBatteryCapacity 2 4 6
InternalBatteryType 12V/7AHsealedleadacidmaintenancefreebattery
(onlyreferstostandardUPS)
BackupTime Fullload≥4min(onlyreferstostandardUPS, AsforlongbackupUPS,thebackuptimeisdeterminedbythecapacityofbattery.
ChargeCurrent(A) 1 6 1 6 1 6
![Page 26: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/26.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
26
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
Model 1kVA(AS)
1kVA(AH)
2kVA(AS)
2kVA(AH)
3kVA(AS)
3kVA(AH)
RatedCapacity 800W/1000VA 1600W/2000VA 2400W/3000VA
WorkEnvironment
Temperature 0℃~40℃
RelativeHumidity 0~95% (non‐condensing)
Altitude <1500m.when>1500m,lowertheratedpowerforuse
StoreTemperaturet ‐25℃~55℃
MechanicalSpecification
DimensionW*D*H(mm) 144x368x215 191x469x339
NetWeight/(kg) 9,7 5,8 20 11,4 24,6 11,9
GrossWeight/(kg) 10,7 6,8 22 13,4 26,6 13,6
6.5. CommunicationInterface
6.5.1. RS232
ThisUPSprovidesastandardDB9communicationinterfaceonitsrearpanel,thedefinitionofthepinsisasfollowing:
6.5.2. RS232CableSpecifications
WhenconnectingtheUPSwithPCbyRS232cable,itneedstousethestandardRS232cable,thedetailedcableNO.areasfollowing:
PIN1hole tocomputerserialport PIN2 needle toUPSserialport
2 2
3 3
5 5
![Page 27: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/27.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
27
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
7. Guarantee
7.1. TermsofGuarantee
Our products are under a two-year guarantee starting from the date of delivery against malfunctions resulting from production, material and workmanship faults. Malfunctions due to such type of faults will be removed without claiming any price of workmanship or spare parts to be replaced.
Whether aforementioned malfunctions originate from usage faults or not are determined with a report to be issued by service stations, if there exists no service stations, by one of seller, dealer, agency, representative, importer or manufacturer or producer of those products respectively.
Repair time of defective products is twenty business days at most. This period starts from the date when products are delivered to one of seller, dealer, agency, representative, importer or one of manufacturer or producer. Provided that products break down within the period of guarantee, the time passing during the repair process is added to the guarantee time. Provided that faults of products cannot be removed within ten business days, manufacturer-producer or importer is obliged to assign another product having similar features for the use of consumers until the faulty product has been repaired.
Even though consumers exercise their repair rights, they can claim free replacement of products, refund or price discount at the rate of faultin the events;
That, besides, the product,as of the date when the product is delivered to the consumer, breaks down four times a year or six times within the guarantee period to be determined by the manufacturer-producer and/or importer at least, on the condition of being in guarantee period, such malfunctions perpetuate passing over;
That maximum time required for the repair of products is exceeded; That repair of the malfunction is determined as impossible through a report to
be issued by service station, if there exists no service station, one of seller, dealer, agency, representative, importer or manufacturer or producer of the company respectively.
The consumer is, on demand, obliged to submit guarantee certificate in terms of repairs or replacements within the scope of guarantee.
It is essential that you definitely perform damage control over external packaging before receiving the products to be sent through freight. In the event of any damage, delivery person must be made to prepare a “damage determination record”. (For example; duringthe delivery process, the product has been checked and seen that is damaged.)
![Page 28: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/28.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
28
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
After the damage determination record has been issued, we request you to inform the MAKELSAN head office of the case. Products to be received from freight by signature means that products have been received completely and without no damage.
Repairs of plug-and-play products in the places where no service point is around are performed in the factory of MAKELSAN or the nearest service point according to the direction to be made by the MAKELSAN head office. Defective product is delivered by hand to the nearest service point or to the contracted freight company in its original packaging to be sent to the factory of MAKELSAN according to the direction to be made by the MAKELSAN head office. For malfunctions in the scope of guarantee, shipment fees are under the responsibility of MAKELSAN on the condition that products are delivered to the contracted freight company.
The device must be sent as packed in its original packaging as long as it is not desired by the service. Original packaging of devices should be preserved in order to use them for shipment of devices in terms of repairs to occur. Otherwise, no responsibility is assumed with regards to any troubles to be experienced.
All defective products to be delivered by hand or through freight are to meet the necessary shipment requirements. (Anti-static protective, bubble wrap or box etc.)It is essential that legible barcode serial number belonging to the product be on the product. Otherwise, it is not covered in the scope of the guarantee.
It is essential that products to be sent through freight definitely be together with delivery note, and that serial/model/malfunction details be written on delivery note to be sent (for example, breakdown report form), and that packaging content match with the products specified in the delivery note. Otherwise, freight is not accepted.
The use of theGuarantee Certificate, submitted together with products with MAKELSAN trademark,is permitted by the T.R. Ministry of Industry and Commerce and General Directorate of Protection of Competition with no……. in accordance with the law, with no. 4077, and the notification, with no. TRKGM-95/116-117, issued basing the aforementioned law. MAKELSAN acknowledges and undertakes to obey the liabilities determined by the laws and legislations.
7.2. CasesNotCoveredbytheGuarantee
Breakdowns resulting from the use of products contrary to the issues or the environment conditions (temperature, humidity etc.) specified in the user manual are not covered in the scope of guarantee.
Damages and breakdowns resulting from the use of software, hardware, interface, accessories or consumables apart from those used together with products or recommended ones; changing place, wrong and insufficient maintenance, calibration or use; its operation contrary to
![Page 29: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/29.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
29
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
environment specifications published for products; insufficiency of air installation; use of products in ambient having excessive humid or temperature; its operation in environment harmful for electrical circuits and abrasive; and accidents, impacts, electric, shipment, natural disasters, not limited to the ones listed above, are not covered in the scope of product guarantee.
In the general examination performed during the breakdown acceptance process, certain troubles causing products not to be covered in the scope of guarantee might not be understood. Provided that such faults come up in the detailed examination to be performed via technical service equipment, products are returned to customers.
Products not covered in the scope of guarantee can, on demand of customer, be treated in a fee-paying way within the bounds of possibilities of the authorized service. Products out of the scope of guarantee, repairs of which are not possible are returned to customers.
Damages and breakdowns resulting from treatments, internally or externally tampering, efforts to repair and spare part replacement of products, without approval of MAKELSAN, and those resulting from treatment of unauthorized service/dealer/person/establishment, are not covered in the scope of guarantee. Breakdown, cracks, scratches and wear, corrosion and dust to occur in time and by use in the outer surfaces of products (cabinet, cover, and front panel) are not covered in the scope of guarantee.
In the event that original serial numbers, guarantee labels and stamps on products are removed or distorted, products are not covered in the scope of guarantee. No guarantee is issued against the use of products for any other purpose, apart from those specified in introduction or manual of products.
Shelf lives of VRLA batteries are 6 months under the ambient temperature of 15 °C and 3
months under the ambient temperature of 25 °C.
It is compulsory that systems to be purchased be commissioned within 3 months.
![Page 30: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/30.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
30
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
CERTIFICATE OF GUARANTEE
MANUFACTURER COMPANY Certificate Approval Date : ‐‐/‐‐/‐‐‐‐
Certificate No :
TITLE : MAKELSAN MAKİNE KİMYA ELEKTRİK SAN. TİC. A.Ş.
ADDRESS : Deri Organize SanayiBölgesi 2.Yol I‐5 Parsel P.K. 34957
TELEPHONE : 0216 – 428 65 80
FAX : 0216 – 327 51 64
SIGNATURE AND STAMP OF
COMPANY AUTHORITY
OF THE PRODUCT
TYPE : _______________________________________________
TRADEMARK : _______________________________________________
MODEL : _______________________________________________
SERIAL NO / BANDEROLE : _______________________________________________
DELIVERY DATE AND PLACE : _______________________________________________
MAXIMUM REPAIR PERIOD : 20 business days
GUARANTEE PERIOD : _______________________________________________
VENDOR
TITLE : _______________________________________________
ADDRESS : _______________________________________________
TELEPHONE : _______________________________________________
FAX : _______________________________________________
INVOICE DATE / NO : _______________________________________________
DATE / SIGNATURE AND STAMP : _______________________________________________
CUSTOMER
TITLE / NAME : _______________________________________________
ADDRESS : _______________________________________________
SIGNATURE : _______________________________________________
UPS AUTHORIZED SERVICES
İstanbulDeri Organize
SanayiBölgesi
2. Yol I‐5 Parsel
34956 Tuzla/İstanbul
Tel: 0216 428 65 80
Fax: 0216 327 51 64
www.makelsan.com.tr
PZ‐FR‐07 (R2) Revision Date: 19.03.2014
![Page 31: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/31.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
31
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
CERTIFICATE OF GUARANTEE
1 – Guarantee period starts from the delivery date of the product and lasts………..years.
2 – The whole product, including all its parts are under the guarantee of our company.
3 – Provided that the product breaks down within the period of guarantee, the time passing
during the repair process is added to the guarantee time. Repair time of the product is …….
business days at most. This period starts from the date when the malfunction related to the
product is informed to the service station, if there exists no service station, to one of seller,
dealer, agency, representative, importer or one of manufacturer. Provided that the fault of
industrial product cannot be removed within 10 business days, manufacturer or importer is
obliged to assign another industrial product having similar features for the use of the consumer
until the faulty product has been repaired.
4 – Provided that the product breaks down due to materials and workmanship or assembly faults
within the period of guarantee, the product is repaired without claiming any charge for
workmanship, any price for spare part replacement or any fee under any name.
5 – The product will be replaced without any charge in the events;
‐ That passing over the product perpetuates due to the fact that the product repeats the
same malfunction more than twice or different malfunctions occur more than four times
in a year starting from the delivery date, on the condition of being in guarantee period;
‐ That maximum time required for the repairment of the product is exceeded;
‐ That, if there exists no service station, the repair of the malfunction is determined as
impossible through a report to be issued one of seller, dealer, agency, representative,
importer or manufacturer of the product respectively.
6 ‐ Malfunctions resulting from the use of the product contrary to the issues specified in the user
manual of the product are not covered in the scope of guarantee.
7 –For any trouble that may come up in terms of the Certificate of Guarantee, the Ministry of
Industry and Commerce, General Directorate of Protection of Consumer and Competition can be
applied.
NOTICE
8 – Under no circumstances shall the customer treat the product with the aim of repair, apart
from MAKELSAN authorized service personnel.
9 – Damages and results originating from the violation of the 8th Article shall be invoiced to the
customer.
The use of herein the certificate is permitted by the T.R. Ministry of Industry and
Commerce and General Directorate of Protection of Consumers and Competition in
accrordance with the Law on the Protection of Consumers, with no. 4077, and the
Notification Concerning the Application Principles of Guarantee Certificate, issued basing
the aforementioned law.
![Page 32: Powerpack Plus Serisi 1-3 kVA 0,8 Output Power Factor - · PDF fileThe Principle of the Product ... Read this chapter carefully before operating on the equipment. 1.1. ... DC/AC inverter](https://reader031.vdocuments.us/reader031/viewer/2022030414/5aa002827f8b9a89178d6ce4/html5/thumbnails/32.jpg)
POWERPACKPLUSSERIES1‐3KVAPOWERFACTOR0,8
32
AG‐SD‐69 Rev. No:1 Rev. Date:18.08.2014 Publish No:1
8. ContactInformation
www.makelsan.com.tr
Headquarter:İstanbulDeriOrganizeSanayiBölgesi2.YolI‐5Parsel34956Tuzla/İstanbul
Tel :02164286580
Fax :02163275164
E‐mail :[email protected]
İzmirOffice:HalkapınarMah.1348Sok.2AEKeremoğluİşMerkeziYenişehir–İzmir
Tel :02324694700
Fax :02324494700
E‐mail :[email protected]
AnkaraOffice:MustafaKemalMah.2157Sok.No:4/6Çankaya‐Ankara
Tel :03122198235/37
Fax :03122198236
E‐mail :[email protected]