Harvest the power of the sun
Maximum energy harvest
The Eaton Power Xpert Solar250 kW inverters are based onEatons mature PowerChainManagement solutions,which incorporate Eatonprogrammable logic controllers(PLCs), advanced variablefrequency drives and protectiverelays. Every critical componentinside the Power Xpert inverteris proven to be reliable basedon the known life cycles of high-volume industrial and electricalcontrol equipment.
Earliest startuplatestshutdown with DC excitationand zero load grid sync
Minimized offline nuisanceevents with superior faulttolerance of a utility-gradeelectric protection relay
At the heart of the Eaton PowerXpert Solar 250 kW inverteris the Eaton active front end(AFE) technology, which isproven to reliably operatein harsh environments with24-hours-a-day, 7-days-a-weekoperation cycles over decades.
Operations and maintenance
The Eaton Power Xpert Solar250 kW inverter is designed tooperate as consistently as thesun rises and sets. Insuringyour PV system investment, thePower Xpert is supported by aglobal service infrastructure andbacked by a company with morethan 100 years of performance.
AC/DC circuit terminationsaccessible by side and bottomgland plates with the largest
working volume in the industry
National support and serviceinfrastructure
Extended warranties andservice contracts availablefor long-term maintenance
The Eaton Power XpertSolar 250 kW inverter
is listed to UL1741 for three-phase ut ility
interact ive operation. Backed by a century
of experience with electrical power systems
and a global reputation for excellence.
The Eaton Power Xpert Solar 250 kW invertersconvert sunlight into clean alternating current,with an emphasis on:
Maximum energy harvest
System reliability
Enhanced operations and maintenance
High safety standards
Inverter re-combiner boxwith DC circuit breaker
Optional inverter re-combinebox with DC breakers to meNEC2011 requirementsfor safe DC disconnect,eliminating the need forexternal DC disconnects
DC breaker option eliminatethe need to replace DC fuseallowing cost and time savin(reducing operation andmaintenance costs)
Current sensing of eachDC input is available for arra
zone monitoring; DC inputcurrent is reported to invertcontroller, which makes itavailable via Modbus
DC breakers can be individuturned off, allowing isolationof a defective sub-array whilallowing other sub-arraysto operate
Features and options
UL 98 load break,service entrance rated400A AC breaker
100 kA surge protection Optional infrared inspection
ports for the AC and DCcabinet sections
Optional visual inspectionport in AC and DC cabinetsfor breaker and fuse status
Optional CEC-approvedsystem performance meter,2% accurate revenue testedto ANSI C-12
Factory configured inverterre-combiner box:
Fused input options:No fusing, 4 x 300A,8 x 150A, 6 x 225A,6 x 200A, 8 x 175A, 8 x 12
DC breaker input options:16 x 90A, 14 x 100A,12 x 125A, 8 x 150A,8 x 175A, 7 x 200A, 6 x 22
Power Xpert Solar250 kW inverter
-
8/11/2019 Power Xpert Solar 250 KW Inverter - Harvest the Power of the Sun
2/2
Eaton is a registered trademarkof Eaton Corporation.
All other trademarks are propertyof their respective owners.
Eaton CorporationElectrical Sector1111 Superior AvenueCleveland, OH 44114 USAEaton.com
2012 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. PA04010002E / Z12638September 2012
Specifications
Description Specification
AC OutputFactory Default
Maximum continuous output power 250 kW
Weighted efficiency (CEC) 96%
Maximum continuous output current 312A
Maximum branch over current protection 400A
Nominal operating voltage 3 480 Vac
Operating voltage range 423528 Vac
Nominal operating frequency 60 Hz
Operating frequency range 50.760.5 Hz
Tare loss 70W
Total harmonic distortion (THD) 0.99Utility connection Delta Three-wire (A, B, C)
Wye Four-wire (A, B, C, N)
DC Input
DC maximum input voltage 600 Vdc
DC maximum power point tracking range (MPPT) 300500 Vdc
DC operating range 300600 Vdc
DC input start 400 Vdc
DC operating current nominal 860A
Maximum DC ISC input 1340A
Factory configured PV array grounding Pos / Neg
Approximate Dimensions in Inches
Fork Lift Pockets
84.25(2140.0)
42.13(1070.1)
93.58(2376.9)
6.00(152.4)
30.00(762.0)
45.42(1153.7)
90.05(2287.3)
18.06(458.7)
X6 2.00 (50.8) Lifting Holes
Description Specification
Mechanical
Operating temperature range (without power foldback) 20 to 50C
Storage temperature range 30 to 70C
Enclosure rating UL Type 3R
Enclosure(s) construction Polyester powder coated
Relative humidity, non-condensing 0 to 95%
Inverter weight 4000 lbs (1814 kg)
Transformer weight 2850 lbs (1293 kg)
Inverter envelope dimensions in inches 94.0H x 93.0W x 46.0D
Transformer dimensions in inches 64.0H x 50.0W x 40.0D
Inverter and transformer mounting Pad mount (not freestanding)
Isolation transformer (external) Delta/deltaCooling Forced convection
Maximum altitude 3300 ft (1000m)
Air flow/inverter 48 m3(1700 cfm3)
Seismic rating successfully evaluated to Seismic qual ified to IBC/CBC
Certifications
UL 1741 2nd Ed., Jan. 2010
IEEE1547
400A AC breaker.
Factory default is delta three-wire; wye four-wire is field selectable.
Factory default is 400 Vdc.