  • 8/11/2019 Power Xpert Solar 250 KW Inverter - Harvest the Power of the Sun

    1/2

    Harvest the power of the sun

    Maximum energy harvest

    The Eaton Power Xpert Solar250 kW inverters are based onEatons mature PowerChainManagement solutions,which incorporate Eatonprogrammable logic controllers(PLCs), advanced variablefrequency drives and protectiverelays. Every critical componentinside the Power Xpert inverteris proven to be reliable basedon the known life cycles of high-volume industrial and electricalcontrol equipment.

    Earliest startuplatestshutdown with DC excitationand zero load grid sync

    Minimized offline nuisanceevents with superior faulttolerance of a utility-gradeelectric protection relay

    At the heart of the Eaton PowerXpert Solar 250 kW inverteris the Eaton active front end(AFE) technology, which isproven to reliably operatein harsh environments with24-hours-a-day, 7-days-a-weekoperation cycles over decades.

    Operations and maintenance

    The Eaton Power Xpert Solar250 kW inverter is designed tooperate as consistently as thesun rises and sets. Insuringyour PV system investment, thePower Xpert is supported by aglobal service infrastructure andbacked by a company with morethan 100 years of performance.

    AC/DC circuit terminationsaccessible by side and bottomgland plates with the largest

    working volume in the industry

    National support and serviceinfrastructure

    Extended warranties andservice contracts availablefor long-term maintenance

    The Eaton Power XpertSolar 250 kW inverter

    is listed to UL1741 for three-phase ut ility

    interact ive operation. Backed by a century

    of experience with electrical power systems

    and a global reputation for excellence.

    The Eaton Power Xpert Solar 250 kW invertersconvert sunlight into clean alternating current,with an emphasis on:

    Maximum energy harvest

    System reliability

    Enhanced operations and maintenance

    High safety standards

    Inverter re-combiner boxwith DC circuit breaker

    Optional inverter re-combinebox with DC breakers to meNEC2011 requirementsfor safe DC disconnect,eliminating the need forexternal DC disconnects

    DC breaker option eliminatethe need to replace DC fuseallowing cost and time savin(reducing operation andmaintenance costs)

    Current sensing of eachDC input is available for arra

    zone monitoring; DC inputcurrent is reported to invertcontroller, which makes itavailable via Modbus

    DC breakers can be individuturned off, allowing isolationof a defective sub-array whilallowing other sub-arraysto operate

    Features and options

    UL 98 load break,service entrance rated400A AC breaker

    100 kA surge protection Optional infrared inspection

    ports for the AC and DCcabinet sections

    Optional visual inspectionport in AC and DC cabinetsfor breaker and fuse status

    Optional CEC-approvedsystem performance meter,2% accurate revenue testedto ANSI C-12

    Factory configured inverterre-combiner box:

    Fused input options:No fusing, 4 x 300A,8 x 150A, 6 x 225A,6 x 200A, 8 x 175A, 8 x 12

    DC breaker input options:16 x 90A, 14 x 100A,12 x 125A, 8 x 150A,8 x 175A, 7 x 200A, 6 x 22

    Power Xpert Solar250 kW inverter

  • 8/11/2019 Power Xpert Solar 250 KW Inverter - Harvest the Power of the Sun

    2/2

    Eaton is a registered trademarkof Eaton Corporation.

    All other trademarks are propertyof their respective owners.

    Eaton CorporationElectrical Sector1111 Superior AvenueCleveland, OH 44114 USAEaton.com

    2012 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. PA04010002E / Z12638September 2012

    Specifications

    Description Specification

    AC OutputFactory Default

    Maximum continuous output power 250 kW

    Weighted efficiency (CEC) 96%

    Maximum continuous output current 312A

    Maximum branch over current protection 400A

    Nominal operating voltage 3 480 Vac

    Operating voltage range 423528 Vac

    Nominal operating frequency 60 Hz

    Operating frequency range 50.760.5 Hz

    Tare loss 70W

    Total harmonic distortion (THD) 0.99Utility connection Delta Three-wire (A, B, C)

    Wye Four-wire (A, B, C, N)

    DC Input

    DC maximum input voltage 600 Vdc

    DC maximum power point tracking range (MPPT) 300500 Vdc

    DC operating range 300600 Vdc

    DC input start 400 Vdc

    DC operating current nominal 860A

    Maximum DC ISC input 1340A

    Factory configured PV array grounding Pos / Neg

    Approximate Dimensions in Inches

    Fork Lift Pockets

    84.25(2140.0)

    42.13(1070.1)

    93.58(2376.9)

    6.00(152.4)

    30.00(762.0)

    45.42(1153.7)

    90.05(2287.3)

    18.06(458.7)

    X6 2.00 (50.8) Lifting Holes

    Description Specification

    Mechanical

    Operating temperature range (without power foldback) 20 to 50C

    Storage temperature range 30 to 70C

    Enclosure rating UL Type 3R

    Enclosure(s) construction Polyester powder coated

    Relative humidity, non-condensing 0 to 95%

    Inverter weight 4000 lbs (1814 kg)

    Transformer weight 2850 lbs (1293 kg)

    Inverter envelope dimensions in inches 94.0H x 93.0W x 46.0D

    Transformer dimensions in inches 64.0H x 50.0W x 40.0D

    Inverter and transformer mounting Pad mount (not freestanding)

    Isolation transformer (external) Delta/deltaCooling Forced convection

    Maximum altitude 3300 ft (1000m)

    Air flow/inverter 48 m3(1700 cfm3)

    Seismic rating successfully evaluated to Seismic qual ified to IBC/CBC

    Certifications

    UL 1741 2nd Ed., Jan. 2010

    IEEE1547

    400A AC breaker.

    Factory default is delta three-wire; wye four-wire is field selectable.

    Factory default is 400 Vdc.