power transformer 3

Upload: sherif-ahmed-moussa

Post on 30-May-2018

247 views

Category:

Documents


3 download

TRANSCRIPT

  • 8/14/2019 Power Transformer 3

    1/79

    11

    Power TransformerPower Transformer

    ByByDr. Tarek Saad AbdelDr. Tarek Saad Abdel--SalamSalam

  • 8/14/2019 Power Transformer 3

    2/79

    22

    PROTECTION OF TRANSFORMERSPROTECTION OF TRANSFORMERS

    LowLow--voltage circuit breakers can be used for thevoltage circuit breakers can be used for thetransformer protection required by NECtransformer protection required by NEC

    Section 450Section 450--3. Refer to this section for the specific3. Refer to this section for the specificprimary and secondary protection requirements forprimary and secondary protection requirements for

    transformers over 600 V nominal and equal to or lesstransformers over 600 V nominal and equal to or lessthan 600 V nominal. The protection discussed in thisthan 600 V nominal. The protection discussed in thissection of the NEC is intended to protect the transformersection of the NEC is intended to protect the transformeronly.only.

    Protection of the primary and secondary conductors mayProtection of the primary and secondary conductors maybe obtained by proper selection of cables.be obtained by proper selection of cables.

  • 8/14/2019 Power Transformer 3

    3/79

    33

    Application considerationsApplication considerations

    Considerations for the application of lowConsiderations for the application of low--voltagevoltagecircuit breakers for transformer protectioncircuit breakers for transformer protectioninclude the following:include the following:

    a) Will they clear the system for short circuitsa) Will they clear the system for short circuits

    within the transformer?within the transformer? b) Will they prevent the transformer fromb) Will they prevent the transformer from

    becoming overloaded beyond its ability?becoming overloaded beyond its ability?

    c) Will they protect the transformer fromc) Will they protect the transformer fromdamage during a throughdamage during a through--fault condition on thefault condition on theload side?load side?

  • 8/14/2019 Power Transformer 3

    4/79

    44

    d) Do they have adequate interrupting ratingsd) Do they have adequate interrupting ratingsfor faults at their loadfor faults at their load--side terminals?side terminals?

    e) Will they handle the transformer inrushe) Will they handle the transformer inrush

    current without nuisance tripping?current without nuisance tripping? f) Can they tolerate the current transients duringf) Can they tolerate the current transients during

    inrush and during other operating conditions?inrush and during other operating conditions?

    g) Do they provide conductor protection?g) Do they provide conductor protection?

    h) Is groundh) Is ground--fault protection provided (iffault protection provided (ifrequired)?required)?

    Application considerationsApplication considerations

  • 8/14/2019 Power Transformer 3

    5/79

    55

    Transformer w ith a primary rated over 600 VTransformer w ith a primary rated over 600 V

    When the transformer primary is over 600 V andWhen the transformer primary is over 600 V andthe secondary is 600 V or less, lowthe secondary is 600 V or less, low--voltagevoltagecircuit breakers might be used as the secondarycircuit breakers might be used as the secondarytransformer protection. The rating of thistransformer protection. The rating of this

    secondary protection must not exceed 125% ofsecondary protection must not exceed 125% ofthe transformer rated secondary current, or thethe transformer rated secondary current, or thenext higher standard rating or setting fornext higher standard rating or setting forunsupervised transformer applications per NECunsupervised transformer applications per NEC

    Section 450Section 450--3(a)(1); NEC Section 4503(a)(1); NEC Section 450--3(a)(2)3(a)(2)allows 250% of the transformer rated secondaryallows 250% of the transformer rated secondarycurrent forcurrent forsupervisedsupervisedinstallations.installations.

  • 8/14/2019 Power Transformer 3

    6/79

    66

    Transformer primary and secondary rated 600 V orTransformer primary and secondary rated 600 V orbelowbelow

    Primary protection onlyPrimary protection only The overload ratings or settings determined by theThe overload ratings or settings determined by the

    following paragraph do not necessarily providefollowing paragraph do not necessarily provide

    conductor protection. For example, NEC Section 240conductor protection. For example, NEC Section 240--

    3(i) states that transformer secondary conductors3(i) states that transformer secondary conductors

    (other than two(other than two--wire) are not considered to bewire) are not considered to be

    protected by the primary over current protection.protected by the primary over current protection.

    Before making the final selection of the circuitBefore making the final selection of the circuit--breaker rating, conductor protection must be verifiedbreaker rating, conductor protection must be verified

  • 8/14/2019 Power Transformer 3

    7/79

    77

    Primary protection onlyPrimary protection only NEC Section 450NEC Section 450--3(b)(1) states that if only primary protection is3(b)(1) states that if only primary protection is

    to be used for a transformer of 600 V or less, that protectionto be used for a transformer of 600 V or less, that protectionshall be an individual over current device on the primary side,shall be an individual over current device on the primary side,rated or set at not more than 125% of the rated primary currentrated or set at not more than 125% of the rated primary current

    of the transformer as shown in Figure 4of the transformer as shown in Figure 4--20. If the primary20. If the primarycurrent rating of the transformer is less than 9 A, the exceptiocurrent rating of the transformer is less than 9 A, the exceptionsnsallow the over current device to be rated up to, but no moreallow the over current device to be rated up to, but no morethan, 167% of the transformer primary current rating. If thethan, 167% of the transformer primary current rating. If theprimary current rating of the transformer is less than 2 A, theprimary current rating of the transformer is less than 2 A, the

    exceptions allow the over current device to be rated up to, butexceptions allow the over current device to be rated up to, butno more than, 300% of the transformer primary current rating.no more than, 300% of the transformer primary current rating.

    Transformer primary and secondary rated 600 V orTransformer primary and secondary rated 600 V orbelowbelow

  • 8/14/2019 Power Transformer 3

    8/79

    88

    Transformers w ith secondary protectionTransformers w ith secondary protection When the transformer has secondary protection, anWhen the transformer has secondary protection, an

    individual over current device is not required on theindividual over current device is not required on the

    primary side if:primary side if:

    a) The over current device on the secondary side isa) The over current device on the secondary side is

    rated or set at not more than 125% of therated or set at not more than 125% of the

    transformer secondary rating, andtransformer secondary rating, and

    b) The primary feeder over current device is rated orb) The primary feeder over current device is rated orset at not more than 250% of the transformerset at not more than 250% of the transformer

    primary current ratingprimary current rating

    Transformer primary and secondary rated 600 V orTransformer primary and secondary rated 600 V orbelowbelow

  • 8/14/2019 Power Transformer 3

    9/79

    99

    Other considerations for protecting transformersOther considerations for protecting transformers Selecting the current ratings is only part of theSelecting the current ratings is only part of the

    job of protecting the transformer. Transformerjob of protecting the transformer. Transformerdamage curves, current inrush data, overloaddamage curves, current inrush data, overload

    capabilities, and information on transientcapabilities, and information on transienttolerances can be obtained from thetolerances can be obtained from themanufacturers of the transformers and IEEEmanufacturers of the transformers and IEEEstandards. Refer to the IEEE C57 Collection andstandards. Refer to the IEEE C57 Collection and

    IEEE Std 242IEEE Std 242 --1986. This type of information1986. This type of informationw ill help the designer determine the proper tripw ill help the designer determine the proper tripunit settings.unit settings.

    PROTECTION OF TRANSFORMERSPROTECTION OF TRANSFORMERS

  • 8/14/2019 Power Transformer 3

    10/79

    1010

    Need for protectionNeed for protection

    Transformer failure may result in loss of service.Transformer failure may result in loss of service.However, prompt fault clearing, in addition toHowever, prompt fault clearing, in addition tominimizing the damage and cost of repairs,minimizing the damage and cost of repairs,usually minimizes system disturbance, theusually minimizes system disturbance, the

    magnitude of the service outage, and themagnitude of the service outage, and theduration of the outage. Prompt fault clearingduration of the outage. Prompt fault clearingusually prevents catastrophic damage. Properusually prevents catastrophic damage. Properprotection is, therefore, important forprotection is, therefore, important for

    transformers of all sizes, even though they aretransformers of all sizes, even though they areamong the simplest and most reliableamong the simplest and most reliablecomponents in the plantcomponents in the plants electrical system.s electrical system.

  • 8/14/2019 Power Transformer 3

    11/79

    1111

    Need for protectionNeed for protection

  • 8/14/2019 Power Transformer 3

    12/79

    1212

    Causes of FailureCauses of Failure

    a)a)WindingWindingbreakdownbreakdown, the most frequent cause, the most frequent causeof transformer failure. Reasons for this type ofof transformer failure. Reasons for this type of

    failure include insulation deterioration or defectsfailure include insulation deterioration or defects

    in manufacturing, overheating, mechanicalin manufacturing, overheating, mechanicalstress, vibration, and voltage surgesstress, vibration, and voltage surges

    b)b)TerminalTerminalboards and noboards and no--load tap changersload tap changers..

    Failures are attributed to improper assembly,Failures are attributed to improper assembly,damage during transportation, excessivedamage during transportation, excessive

    vibration, or inadequate design.vibration, or inadequate design.

  • 8/14/2019 Power Transformer 3

    13/79

    1313

    c)c)BushingBushingfailures.failures.CausesCauses include vandalism,include vandalism,contamination, aging, cracking, and animals.contamination, aging, cracking, and animals.

    d)d)LoadLoad--taptap--changerchangerfailures.failures.CausesCauses includeinclude

    mechanism malfunction, contact problems,mechanism malfunction, contact problems,insulating liquid contamination, vibration,insulating liquid contamination, vibration,

    improper assembly, and excessive stressesimproper assembly, and excessive stresses

    within the unit. Loadwithin the unit. Load--taptap--changing units arechanging units arenormally applied on utility systems rather thannormally applied on utility systems rather than

    on industrial systems.on industrial systems.

    Causes of FailureCauses of Failure

  • 8/14/2019 Power Transformer 3

    14/79

    1414

    e)e)MiscellaneousMiscellaneousfailures.failures.CausesCauses includeincludecore insulation breakdown, bushingcore insulation breakdown, bushing

    current transformer (CT) failure, liquidcurrent transformer (CT) failure, liquid

    leakage due to poor welds or tankleakage due to poor welds or tankdamage, shipping damage, and foreigndamage, shipping damage, and foreign

    materials left within the tank.materials left within the tank.

    Causes of FailureCauses of Failure

  • 8/14/2019 Power Transformer 3

    15/79

    1515

    Failure of other equipment within theFailure of other equipment within thetransformer protective devicetransformer protective devices zone ofs zone of

    protection could cause the loss of theprotection could cause the loss of the

    transformer to the system. This type of failuretransformer to the system. This type of failureincludes any equipment (e.g., cables, bus ducts,includes any equipment (e.g., cables, bus ducts,

    switches, instrument transformers, surgeswitches, instrument transformers, surge

    arresters, neutral grounding devices) betweenarresters, neutral grounding devices) between

    the next upstream protective device and thethe next upstream protective device and the

    next downstream device.next downstream device.

    Causes of FailureCauses of Failure

  • 8/14/2019 Power Transformer 3

    16/79

    1616

    Objectives in transformer protectionObjectives in transformer protection

    Protection is achieved by the proper combination ofProtection is achieved by the proper combination ofsystem design, physical layout, and protective devices assystem design, physical layout, and protective devices as

    required to:required to:

    a) Economically meet the requirements of thea) Economically meet the requirements of the

    application,application,

    ) Protect the electrical system from the effects of) Protect the electrical system from the effects of

    transformer failure,transformer failure,

    c) Protect the transformer from disturbances occurringc) Protect the transformer from disturbances occurringon the electrical system to which it is connected,on the electrical system to which it is connected,

  • 8/14/2019 Power Transformer 3

    17/79

    1717

    Objectives in transformer protectionObjectives in transformer protection

    d) Protect the transformer as much as possible fromd) Protect the transformer as much as possible fromincipient malfunction within the transformer itself, andincipient malfunction within the transformer itself, and

    e) Protect the transformer from physical conditions ine) Protect the transformer from physical conditions in

    the environment that may affect reliable performance.the environment that may affect reliable performance.

  • 8/14/2019 Power Transformer 3

    18/79

    1818

    Protection of different Types of transformersProtection of different Types of transformers

    Under the broad category of transformers, two types areUnder the broad category of transformers, two types arewidely used in industrial and commercial power systems:widely used in industrial and commercial power systems:

    liquid and dry.liquid and dry. Liquid transformers are constructed to have theLiquid transformers are constructed to have the

    essential element, the core and coils of the transformer,essential element, the core and coils of the transformer,contained in the liquidcontained in the liquid--filled enclosure. This liquid servesfilled enclosure. This liquid servesboth as an insulating medium and as a heatboth as an insulating medium and as a heat--transfertransfermedium.medium.

    The dry transformers are constructed to have the coreThe dry transformers are constructed to have the coreand coils surrounded by an atmosphere, which may beand coils surrounded by an atmosphere, which may bethe surrounding air, free to circulate from the outside tothe surrounding air, free to circulate from the outside tothe inside of the transformer enclosure. The dry coilsthe inside of the transformer enclosure. The dry coilsmay be conventional (with exposed, insulatedmay be conventional (with exposed, insulatedconductors) or encapsulated (with the coils completelyconductors) or encapsulated (with the coils completely

    vacuumvacuum--cast in an epoxy resin).cast in an epoxy resin).

  • 8/14/2019 Power Transformer 3

    19/79

    1919

    Preservation systemsPreservation systems

    Dry preservation systemsDry preservation systems

    Liquid preservation systemsLiquid preservation systems

  • 8/14/2019 Power Transformer 3

    20/79

    2020

    Dry preservation systemsDry preservation systems

    Dry preservation systems are used to ensure anDry preservation systems are used to ensure anadequate supply of clean ventilating air at an acceptableadequate supply of clean ventilating air at an acceptableambient temperature. Contamination of the insulatingambient temperature. Contamination of the insulatingducts within the transformer can lead to reducedducts within the transformer can lead to reducedinsulation strength and severe overheating. Theinsulation strength and severe overheating. Theprotection method most commonly used in commercialprotection method most commonly used in commercialapplications consists of a temperatureapplications consists of a temperature--indicating deviceindicating devicewith probes installed in the transformer winding ductswith probes installed in the transformer winding ductsand contacts to signal dangerously high temperature byand contacts to signal dangerously high temperature by

    visual and audible alarm. Figure 11visual and audible alarm. Figure 11--1 illustrates this1 illustrates thisfeature.feature.

  • 8/14/2019 Power Transformer 3

    21/79

    2121

    The following types of dry systems areThe following types of dry systems arecommonly used:commonly used:

    Open ventilatedOpen ventilated

    Filtered ventilatedFiltered ventilated

    Totally enclosed, nonTotally enclosed, non--ventilatedventilated

    Sealed airSealed air-- or gasor gas--filledfilled

    Dry preservation systemsDry preservation systems

  • 8/14/2019 Power Transformer 3

    22/79

    2222

    Dry preservation systemsDry preservation systems

  • 8/14/2019 Power Transformer 3

    23/79

    2323

    Liquid preservation systemsLiquid preservation systems

    Liquid preservation systems are used to preserve theLiquid preservation systems are used to preserve theamount of liquid and to prevent its contamination by theamount of liquid and to prevent its contamination by thesurrounding atmosphere that may introduce moisturesurrounding atmosphere that may introduce moistureand oxygen leading to reduced insulation strength andand oxygen leading to reduced insulation strength andto sludge formation in cooling ducts.to sludge formation in cooling ducts.

    The importance of maintaining the purity of insulating oilThe importance of maintaining the purity of insulating oilbecomes increasingly critical at higher voltages becausebecomes increasingly critical at higher voltages becauseof increased electrical stress on the insulating oil.of increased electrical stress on the insulating oil.

  • 8/14/2019 Power Transformer 3

    24/79

    2424

    Liquid preservation systemsLiquid preservation systems

    The sealed tank system is now used almost toThe sealed tank system is now used almost tothe total exclusion of other types in industrialthe total exclusion of other types in industrial

    and commercial applications. The followingand commercial applications. The following

    types of systems are commonly used:types of systems are commonly used: Sealed tankSealed tank

    PositivePositive--pressure inert gaspressure inert gas

    GasGas--oil sealoil seal

    Conservator tankConservator tank

  • 8/14/2019 Power Transformer 3

    25/79

    2525

    Sealed tankSealed tank

    The sealedThe sealed--tank design is most commonly used and istank design is most commonly used and is

    standard on most substation transformers. As the namestandard on most substation transformers. As the nameimplies, the transformer tank is sealed to isolate it fromimplies, the transformer tank is sealed to isolate it fromthe outside atmosphere.the outside atmosphere.

    A gas space equal to about oneA gas space equal to about one--tenth of the liquidtenth of the liquid

    volume is maintained above the liquid to allow forvolume is maintained above the liquid to allow forthermal expansion. This space may be purged of air andthermal expansion. This space may be purged of air andfilled with nitrogen.filled with nitrogen.

    A pressureA pressure--vacuum gauge and bleeder device may bevacuum gauge and bleeder device may befurnished on the tank to allow the internal pressure orfurnished on the tank to allow the internal pressure orvacuum to be monitored and any excessive staticvacuum to be monitored and any excessive staticpressure buildup to be relieved to avoid damage to thepressure buildup to be relieved to avoid damage to theenclosure and operation of the pressureenclosure and operation of the pressure--relief device.relief device.This system is the simplest and most maintenanceThis system is the simplest and most maintenance--freefree

    of all of the preservation systems.of all of the preservation systems.

  • 8/14/2019 Power Transformer 3

    26/79

    2626

    PositivePositive--pressure inert gaspressure inert gas

    The positiveThe positive--pressure inertpressure inertgas design shown in Figuregas design shown in Figure

    is similar to the sealedis similar to the sealed--tanktankdesign with the addition ofdesign with the addition ofa gas (usually nitrogen)a gas (usually nitrogen)pressurizing the assembly.pressurizing the assembly.This assembly provides aThis assembly provides a

    slight positive pressure inslight positive pressure inthe gas supply line tothe gas supply line toprevent air from enteringprevent air from enteringthe transformer duringthe transformer duringoperating mode oroperating mode or

    temperature changes.temperature changes.Transformers with primaryTransformers with primarywindings rated 69 kV andwindings rated 69 kV andabove and rated 7500above and rated 7500 kVAkVA

    and above typically areand above typically areequipped with this device.equipped with this device.

  • 8/14/2019 Power Transformer 3

    27/79

    2727

    GasGas--oil sealoil seal

    The gasThe gas--oil seal designoil seal design

    incorporates a captive gasincorporates a captive gasspace that isolates a secondspace that isolates a secondauxiliary oil tank from theauxiliary oil tank from themain transformer oil, asmain transformer oil, asshown in Figure. Theshown in Figure. The

    auxiliary oil tank is open toauxiliary oil tank is open tothe atmosphere andthe atmosphere andprovides room for thermalprovides room for thermalexpansion of the mainexpansion of the main

    transformer oil volume.transformer oil volume.

  • 8/14/2019 Power Transformer 3

    28/79

    2828

    Conservator tankConservator tank

    The conservator tank designThe conservator tank designshown in Figure does notshown in Figure does nothave a gas space above thehave a gas space above theoil in the main tank. Itoil in the main tank. Itincludes a second oil tankincludes a second oil tank

    above the main tank coverabove the main tank coverwith a gas space adequatewith a gas space adequateto absorb the thermalto absorb the thermalexpansion of the main tankexpansion of the main tankoil volume. The second tankoil volume. The second tank

    is connected to the mainis connected to the maintank by an oiltank by an oil--filled tube orfilled tube orpipe.pipe.

  • 8/14/2019 Power Transformer 3

    29/79

    2929

    Protective devices for liquid preservation systemsProtective devices for liquid preservation systems

    LiquidLiquid-- level gaugelevel gauge PressurePressure--vacuum gaugevacuum gauge

    PressurePressure--vacuum bleeder valvevacuum bleeder valve

    PressurePressure--relief devicerelief device

  • 8/14/2019 Power Transformer 3

    30/79

    3030

    Liquid-level gauge

  • 8/14/2019 Power Transformer 3

    31/79

    3131

    PressurePressure--vacuum gaugevacuum gaugePressurePressure--vacuum bleeder valvevacuum bleeder valve

  • 8/14/2019 Power Transformer 3

    32/79

    3232

    PressurePressure--relief devicerelief device

  • 8/14/2019 Power Transformer 3

    33/79

    3333

    Mechanical detection of faultsMechanical detection of faults

    Two methods of detecting transformer faultsTwo methods of detecting transformer faultsexist other than by electric measurements:exist other than by electric measurements:

    a) Accumulation of gases due to slowa) Accumulation of gases due to slow

    decomposition of the transformer insulation ordecomposition of the transformer insulation oroil. These relays can also detect heating due tooil. These relays can also detect heating due to

    highhigh--resistance joints or due to high eddyresistance joints or due to high eddy

    currents between laminations.currents between laminations.

    b) Increases in tank oil or gas pressures causedb) Increases in tank oil or gas pressures caused

    by internal transformer faults.by internal transformer faults.

  • 8/14/2019 Power Transformer 3

    34/79

    3434

    GasGas--accumulator relayaccumulator relay

    A gasA gas--accumulator relay, commonlyaccumulator relay, commonlyknown as the Buchholz relay, is applicableknown as the Buchholz relay, is applicable

    only to transformers equipped withonly to transformers equipped with

    conservator tanks and with no gas spaceconservator tanks and with no gas spaceinside the transformer tank.inside the transformer tank.

  • 8/14/2019 Power Transformer 3

    35/79

    3535

    GasGas--detector relaydetector relay

    The gasThe gas--detector relaydetector relay

    shown in Figure is ashown in Figure is a

    special device used tospecial device used to

    detect and indicate andetect and indicate an

    accumulation of gasaccumulation of gasfrom a transformerfrom a transformer

    with a conservatorwith a conservator

    tank, eithertank, either

    conventional or sealed.conventional or sealed.

  • 8/14/2019 Power Transformer 3

    36/79

    3636

    Static pressure relayStatic pressure relay

    The static pressure relay can be used on allThe static pressure relay can be used on alltypes of oiltypes of oil--immersed transformers. They areimmersed transformers. They are

    mounted on the tank wall under oil and respondmounted on the tank wall under oil and respond

    to the static or total pressure.to the static or total pressure.

  • 8/14/2019 Power Transformer 3

    37/79

    3737

    Sudden pressure relaysSudden pressure relays

    Sudden pressure relays areSudden pressure relays arenormally used to initiatenormally used to initiateisolation of the transformerisolation of the transformerfrom the electrical system andfrom the electrical system andto limit damage to the unitto limit damage to the unit

    when the transformer internalwhen the transformer internalpressure abruptly rises. Thepressure abruptly rises. Theabrupt pressure rise is due toabrupt pressure rise is due tothe vaporization of thethe vaporization of theinsulating liquid by an internalinsulating liquid by an internal

    fault, such as internal shortedfault, such as internal shortedturns, ground faults, orturns, ground faults, orwindingwinding--toto--winding faults.winding faults.

  • 8/14/2019 Power Transformer 3

    38/79

    3838

    Sudden oilSudden oil --pressure relaypressure relay

    The sudden oilThe sudden oil--pressure relay is applicable to allpressure relay is applicable to alloiloil--immersed transformers and is mounted onimmersed transformers and is mounted on

    the transformer tank wall below the minimumthe transformer tank wall below the minimum

    liquid level.liquid level.

  • 8/14/2019 Power Transformer 3

    39/79

    3939

    Sudden oilSudden oil --pressure relaypressure relay

  • 8/14/2019 Power Transformer 3

    40/79

    4040

    Sudden gasSudden gas--pressure relaypressure relay

    The sudden gasThe sudden gas--pressure relay is applicable topressure relay is applicable toall gasall gas--cushioned oilcushioned oil--immersed transformers andimmersed transformers and

    is mounted in the region of the gas space. Itis mounted in the region of the gas space. It

    consists of a pressureconsists of a pressure--actuated switch, housedactuated switch, housed

    in a hermetically sealed case and isolated fromin a hermetically sealed case and isolated from

    the transformer gas space except for a pressurethe transformer gas space except for a pressure--

    equalizing orificeequalizing orifice

  • 8/14/2019 Power Transformer 3

    41/79

    4141

    Sudden gas/ oilSudden gas/ oil --pressure relaypressure relay

    A more recent design of the relays is the suddenA more recent design of the relays is the suddengas/oilgas/oil--pressure relay, which utilizes twopressure relay, which utilizes two

    chambers, two control bellows, and a singlechambers, two control bellows, and a single

    sensing bellows. All three bellows have asensing bellows. All three bellows have a

    common interconnecting siliconecommon interconnecting silicone--oil passageoil passage

    with an orifice, and an ambientwith an orifice, and an ambient--temperaturetemperature--

    compensating assembly is inserted at thecompensating assembly is inserted at the

    entrance to one of the two control bellows.entrance to one of the two control bellows.

  • 8/14/2019 Power Transformer 3

    42/79

    4242

    Dissolved faultDissolved fault --gases detection devicegases detection device

    The dissolved faultThe dissolved fault--

    gases detectiongases detection

    device can be useddevice can be usedfor continuousfor continuous

    monitoring ofmonitoring of

    hydrogenhydrogen

  • 8/14/2019 Power Transformer 3

    43/79

    4343

    Thermal detection of abnormalitiesThermal detection of abnormalities

    Causes of transformer overheatingCauses of transformer overheating

    High ambient temperatureHigh ambient temperature

    Failure of cooling systemFailure of cooling system

    External fault not cleared promptlyExternal fault not cleared promptly

    OverloadOverload Abnormal system conditions, such as lowAbnormal system conditions, such as low

    frequency, high voltage, nonfrequency, high voltage, non --sinusoidal loadsinusoidal loadcurrent , or phasecurrent, or phase --voltage unbalance.voltage unbalance.

  • 8/14/2019 Power Transformer 3

    44/79

    4444

    Undesirable results of overheatingUndesirable results of overheating

    The consequences of overheating include theThe consequences of overheating include thefollowing:following: Overheating shortens the life of the transformerOverheating shortens the life of the transformer

    insulation in proportion to the duration of the highinsulation in proportion to the duration of the high

    temperature and in proportion to the degree of thetemperature and in proportion to the degree of thehigh temperature.high temperature.

    Severe over temperature may result in anSevere over temperature may result in animmediate insulation failure.immediate insulation failure.

    Severe over temperature may cause theSevere over temperature may cause thetransformer coolant to heat above its flashtransformer coolant to heat above its flashtemperature and result in fire.temperature and result in fire.

  • 8/14/2019 Power Transformer 3

    45/79

    4545

    Liquid temperature indicator (top oil)Liquid temperature indicator (top oil)

    The liquid temperature indicator measures theThe liquid temperature indicator measures the

    temperature of the insulating liquid at the top of thetemperature of the insulating liquid at the top of the

    transformer. Because the hottest liquid is less densetransformer. Because the hottest liquid is less dense

    and rises to the top of the tank, the temperature ofand rises to the top of the tank, the temperature of

    the liquid at the top partially reflects the temperaturethe liquid at the top partially reflects the temperature

    of the transformer windings and is related to theof the transformer windings and is related to theloading of the transformer.loading of the transformer.

  • 8/14/2019 Power Transformer 3

    46/79

    4646

    Thermal relaysThermal relays

    Thermal relays are used to give a more direct indicationThermal relays are used to give a more direct indicationof winding temperatures of either liquid or dryof winding temperatures of either liquid or drytransformers. A CT is mounted on one of the threetransformers. A CT is mounted on one of the threephases of the transformer bushing. It supplies currentphases of the transformer bushing. It supplies currentto the thermometer bulb heater coil, which contributesto the thermometer bulb heater coil, which contributesthe proper heat to closely simulate the transformer hotthe proper heat to closely simulate the transformer hot--spot temperaturespot temperature

  • 8/14/2019 Power Transformer 3

    47/79

    4747

    HotHot --spot temperature thermometersspot temperature thermometers HotHot--spot temperature equipment is similar to the thermal relayspot temperature equipment is similar to the thermal relay

    equipment on a transformer because it indicates the hottestequipment on a transformer because it indicates the hottest--spotspottemperature of the transformer. While the thermal relay works witemperature of the transformer. While the thermal relay works withthfluid expansion and a bourdon gauge, the hotfluid expansion and a bourdon gauge, the hot--spot temperaturespot temperatureequipment works electrically using a Wheatstone bridge method. Iequipment works electrically using a Wheatstone bridge method. Innother words, it measures the resistance of a resistance temperatother words, it measures the resistance of a resistance temperatureuredetector (RTD) that is responsive to transformer temperaturedetector (RTD) that is responsive to transformer temperaturechanges and increases with higher temperature.changes and increases with higher temperature.

  • 8/14/2019 Power Transformer 3

    48/79

    4848

    ForcedForced--air coolingair cooling

    Another means of protecting against overloads is toAnother means of protecting against overloads is toincrease the transformerincrease the transformers capacity by auxiliary cooling.s capacity by auxiliary cooling.ForcedForced--airair--cooling equipment is used to increase thecooling equipment is used to increase thecapacity of a transformer by 15% to 33% of base rating,capacity of a transformer by 15% to 33% of base rating,depending upon transformer size and design.depending upon transformer size and design.

  • 8/14/2019 Power Transformer 3

    49/79

    4949

    Fuses or over current relaysFuses or over current relays

    Other forms of transformer protection,Other forms of transformer protection,such as fuses or over current relays,such as fuses or over current relays,

    provide some degree of thermal protectionprovide some degree of thermal protection

    to the transformer.to the transformer.

  • 8/14/2019 Power Transformer 3

    50/79

    5050

    Over excitation protectionOver excitation protection

    OverOver--excitation may be of concern on directexcitation may be of concern on direct--connectedconnected

    generator unit transformers. Excessive excitation currentgenerator unit transformers. Excessive excitation currentleads directly to overheating of core and unleads directly to overheating of core and un--laminatedlaminatedmetal parts of a transformer.metal parts of a transformer.

    Such overheating in turn causes damage to adjacentSuch overheating in turn causes damage to adjacentinsulation and leads to ultimate failure.insulation and leads to ultimate failure.

  • 8/14/2019 Power Transformer 3

    51/79

    5151

    Nonlinear loadsNonlinear loads

    Nonlinear electrical loads may cause severeNonlinear electrical loads may cause severeoverheating even when the transformer isoverheating even when the transformer isoperating below rated capacity. This overheatingoperating below rated capacity. This overheatingmay cause failure of both the winding and themay cause failure of both the winding and the

    neutral conductor. Electronic equipment such asneutral conductor. Electronic equipment such ascomputers, printers, uninterruptible powercomputers, printers, uninterruptible powersupply (UPS) systems, variablesupply (UPS) systems, variable--speed motorspeed motordrives, and other rectified systems are nonlineardrives, and other rectified systems are nonlinearloads. Arc furnace and rectifier transformers alsoloads. Arc furnace and rectifier transformers alsoprovide power to nonlinear loads.provide power to nonlinear loads.

  • 8/14/2019 Power Transformer 3

    52/79

    5252

    The nonlinear load causes transformerThe nonlinear load causes transformeroverheating in three ways:overheating in three ways:

    HysteresisHysteresis

    Eddy currentsEddy currentsSkin effectSkin effect

    Nonlinear loadsNonlinear loads

  • 8/14/2019 Power Transformer 3

    53/79

    5353

    Overheating of neutral conductors fromOverheating of neutral conductors from

    nonlinear loads is due to the following:nonlinear loads is due to the following:ZeroZero--sequence and oddsequence and odd--order harmonicsorder harmonics

    Skin effectSkin effect

    Nonlinear loadsNonlinear loads

  • 8/14/2019 Power Transformer 3

    54/79

    5454

    Failures of transformers due to nonlinearFailures of transformers due to nonlinearloads can be prevented by deloads can be prevented by de--rating therating the

    transformer.transformer.

    Nonlinear loadsNonlinear loads

  • 8/14/2019 Power Transformer 3

    55/79

    5555

    Protecting the transformer from electricalProtecting the transformer from electrical

    disturbancesdisturbances

    Transformer failures arising from abusiveTransformer failures arising from abusiveoperating conditions are caused byoperating conditions are caused by

    Continuous overloadingContinuous overloading

    Short circuitsShort circuits Ground faultsGround faults

    Transient over voltagesTransient over voltages

  • 8/14/2019 Power Transformer 3

    56/79

    5656

    Overload protectionOverload protection

    An overload causes a rise in the temperature of theAn overload causes a rise in the temperature of the

    various transformer components. If the final temperaturevarious transformer components. If the final temperature

    is above the design temperature limit, deterioration ofis above the design temperature limit, deterioration of

    the insulation system occurs and causes a reduction inthe insulation system occurs and causes a reduction in

    the useful life of the transformerthe useful life of the transformer Protection against overloads consists of both loadProtection against overloads consists of both load

    limitation and overload detection. Loading on thelimitation and overload detection. Loading on the

    transformers may be limited by designing a systemtransformers may be limited by designing a system

    where the transformer capacity is greater than the totalwhere the transformer capacity is greater than the totalconnected load when a diversity in load usage isconnected load when a diversity in load usage is

    assumedassumed

  • 8/14/2019 Power Transformer 3

    57/79

    5757

    Over current relaysOver current relays

    Transformer overload protection may be provided byTransformer overload protection may be provided by

    relays. These relays are applied in conjunction withrelays. These relays are applied in conjunction with CTsCTs

    and a circuit breaker or circuit switcher, sized for theand a circuit breaker or circuit switcher, sized for themaximum continuous and interrupting duty requirementsmaximum continuous and interrupting duty requirements

    of the applicationof the application

  • 8/14/2019 Power Transformer 3

    58/79

    5858

    ShortShort

    --circuit current protectioncircuit current protection

    In addition to thermal damage from prolongedIn addition to thermal damage from prolonged

    overloads, transformers are also adversely affected byoverloads, transformers are also adversely affected byinternal or external shortinternal or external short--circuit conditions, which cancircuit conditions, which canresult in internal electromagnetic forces, temperatureresult in internal electromagnetic forces, temperaturerise, and arcrise, and arc--energy release.energy release.

    Protection of the transformer for both internal andProtection of the transformer for both internal andexternal faults should be as rapid as possible to keepexternal faults should be as rapid as possible to keepdamage to a minimum. This protection, however, maydamage to a minimum. This protection, however, maybe reduced by selectivebe reduced by selective--coordination system design andcoordination system design and

    operating procedure limitations.operating procedure limitations.

  • 8/14/2019 Power Transformer 3

    59/79

    5959

    TimeTime

    --current Characteristics (current Characteristics (

    TccsTccs

    ))

  • 8/14/2019 Power Transformer 3

    60/79

    6060

    Different types of protectionDifferent types of protection

    Over current relay protectionOver current relay protection Over current relays may be used to clear theOver current relays may be used to clear the

    transformer from the faulted bus or linetransformer from the faulted bus or line

    before the transformer is damaged. On somebefore the transformer is damaged. On somesmall transformers, over current relays maysmall transformers, over current relays may

    also protect for internal transformer faults. Onalso protect for internal transformer faults. On

    larger transformers, over current relays maylarger transformers, over current relays may

    be used to provide backup for differential orbe used to provide backup for differential or

    pressure relays.pressure relays.

  • 8/14/2019 Power Transformer 3

    61/79

    6161

    Different types of protectionDifferent types of protection

    Time over current relaysTime over current relays Over current relays applied on the primaryOver current relays applied on the primary

    side of a transformer provide protection forside of a transformer provide protection for

    transformer faults in the winding, and providetransformer faults in the winding, and providebackup protection for the transformer forbackup protection for the transformer for

    secondarysecondary--side faults.side faults.

  • 8/14/2019 Power Transformer 3

    62/79

    6262

    Different types of protectionDifferent types of protection

    Instantaneous over current relaysInstantaneous over current relays Phase instantaneous over current relaysPhase instantaneous over current relays

    provide shortprovide short--circuit protection to thecircuit protection to the

    transformers in addition to overloadtransformers in addition to overloadprotection. When used on the primary side,protection. When used on the primary side,

    they usually coordinate with secondarythey usually coordinate with secondary

    protective devices. Fast clearing of severeprotective devices. Fast clearing of severe

    internal faults can be obtainedinternal faults can be obtained

  • 8/14/2019 Power Transformer 3

    63/79

  • 8/14/2019 Power Transformer 3

    64/79

    6464

    Different types of protectionDifferent types of protection

    Phase differential relaysPhase differential relays Differential relaying compares the sum ofDifferential relaying compares the sum of

    currents entering the protected zone to thecurrents entering the protected zone to the

    sum of currents leaving the protected zone;sum of currents leaving the protected zone;these sums should be equal. If more than athese sums should be equal. If more than a

    certain amount or percentage of currentcertain amount or percentage of current

    enters than leaves the protected zone, a faultenters than leaves the protected zone, a fault

    is indicated in the protected zone; and theis indicated in the protected zone; and the

    relay operates to isolate the faulted zone.relay operates to isolate the faulted zone.

    Phase differential relaysPhase differential relays

  • 8/14/2019 Power Transformer 3

    65/79

    6565

    Phase differential relaysPhase differential relays

  • 8/14/2019 Power Transformer 3

    66/79

    6666

    y

  • 8/14/2019 Power Transformer 3

    67/79

    6767

    Phase differential relaysPhase differential relays

  • 8/14/2019 Power Transformer 3

    68/79

    6868

    Ground differential relaysGround differential relays

    Protection of the transformer by percentage differentialProtection of the transformer by percentage differential

    relays improves the overall effectiveness in detectingrelays improves the overall effectiveness in detectingphasephase--toto--phase internal faults. However, linephase internal faults. However, line--toto--groundgroundfaults in afaults in a wyewye winding may not be detected if thewinding may not be detected if thetransformer is lowtransformer is low--resistanceresistance--grounded where groundgrounded where ground

    fault current is limited to a low value below thefault current is limited to a low value below thedifferential relay pickup level.differential relay pickup level.

    Ground differential relaysGround differential relays

  • 8/14/2019 Power Transformer 3

    69/79

    6969

    Ground differential relaysGround differential relays

  • 8/14/2019 Power Transformer 3

    70/79

    7070

    Ground differential relaysGround differential relays

    Ground differential relaysGround differential relays

  • 8/14/2019 Power Transformer 3

    71/79

    7171

    Ground differential relaysGround differential relays

  • 8/14/2019 Power Transformer 3

    72/79

    7272

    Protection against over voltagesProtection against over voltages

    Transient over voltages produced by lightning,Transient over voltages produced by lightning,

    switching surges, switching of power factorswitching surges, switching of power factor

    correction capacitors, and other systemcorrection capacitors, and other system

    disturbances can cause transformer failures.disturbances can cause transformer failures.

    High voltage disturbances can be generated byHigh voltage disturbances can be generated bycertain types of loads and from the incomingcertain types of loads and from the incoming

    line. A common misconception is thatline. A common misconception is that

    underground services are isolated from theseunderground services are isolated from thesedisturbances.disturbances.

  • 8/14/2019 Power Transformer 3

    73/79

    7373

    Protection against over voltagesProtection against over voltages

    Surge arrestersSurge arresters

    Ordinarily, if the liquidOrdinarily, if the liquid--insulated transformer isinsulated transformer is

    supplied by enclosed conductors from thesupplied by enclosed conductors from the secondariessecondaries

    of transformers with adequate primary surgeof transformers with adequate primary surge

    protection, additional protection may not be required,protection, additional protection may not be required,depending on the system design. However, if thedepending on the system design. However, if the

    transformer primary or secondary is connected totransformer primary or secondary is connected to

    conductors that are exposed to lightning, theconductors that are exposed to lightning, the

    installation of surge arresters is necessaryinstallation of surge arresters is necessary

  • 8/14/2019 Power Transformer 3

    74/79

    7474

    Protection against over voltagesProtection against over voltages

    Surge capacitorsSurge capacitors

    Additional protection in the form of surgeAdditional protection in the form of surge

    capacitors located as closely as possible to thecapacitors located as closely as possible to the

    transformer terminals may also betransformer terminals may also be

    appropriate for all types of transformersappropriate for all types of transformers

    FerroresonanceFerroresonance

  • 8/14/2019 Power Transformer 3

    75/79

    7575

    FerroresonanceFerroresonance

    FerroresonanceFerroresonance

    is a phenomenon resultingis a phenomenon resulting

    in the development of a higher thanin the development of a higher than

    normal voltage in the windings of anormal voltage in the windings of a

    transformer. These overtransformer. These over--voltages mayvoltages mayresult in surge arrester operation, damageresult in surge arrester operation, damage

    to the transformer, and electrical shockto the transformer, and electrical shock

    hazard.hazard.

    FerroresonanceFerroresonance

  • 8/14/2019 Power Transformer 3

    76/79

    7676

    The following conditions combine to produceThe following conditions combine to produce

    ferroresonanceferroresonance:: a) No load on the transformera) No load on the transformer

    b) An open circuit on one of the primary terminals ofb) An open circuit on one of the primary terminals ofthe transformer and, at the same time, an energizedthe transformer and, at the same time, an energized

    terminal. In the case of threeterminal. In the case of three--phase transformers,phase transformers,either one or two of the three primary terminals mayeither one or two of the three primary terminals maybe disconnected.be disconnected.

    c) The location of the point of disconnection if it is notc) The location of the point of disconnection if it is notclose to the transformerclose to the transformer

    d) A voltage potential between the disconnectedd) A voltage potential between the disconnectedterminal conductor and groundterminal conductor and ground

    FerroresonanceFerroresonance

  • 8/14/2019 Power Transformer 3

    77/79

    7777

    Protection from the environmentProtection from the environment

  • 8/14/2019 Power Transformer 3

    78/79

    7878

    Undesirable conditions include:Undesirable conditions include:

    a) Average ambient temperatures above 30a) Average ambient temperatures above 30 C when theC when thetransformer is loaded at rated kilotransformer is loaded at rated kilo voltamperevoltampere or moreor more

    b) Corrosive agents, abrasive particulate matter, andb) Corrosive agents, abrasive particulate matter, andsurface contaminants derived from the surroundingsurface contaminants derived from the surroundingatmosphereatmosphere

    c) Conditions that can lead to moisture penetration or toc) Conditions that can lead to moisture penetration or tocondensation on windings and other internal electricalcondensation on windings and other internal electrical

    componentscomponents d) Submersion in water or mudd) Submersion in water or mud

    e) Obstruction to proper ventilation of liquid transformere) Obstruction to proper ventilation of liquid transformerradiators or, in the case of dry transformers, ventilatingradiators or, in the case of dry transformers, ventilating

    openingsopenings f) Exposure to damage from collision by vehiclesf) Exposure to damage from collision by vehicles

    g) Excessive vibrationg) Excessive vibration

    h) Exposure to vandalismh) Exposure to vandalism

    ConclusionConclusion

  • 8/14/2019 Power Transformer 3

    79/79

    7979

    Protection of todayProtection of todays larger and mores larger and moreexpensive transformers can be achievedexpensive transformers can be achievedby the proper selection and application ofby the proper selection and application ofprotective devices. Published applicationprotective devices. Published application

    guides covering transformers are readilyguides covering transformers are readilyavailable, for example, ANSI C37.91available, for example, ANSI C37.91--2000.2000.The system design engineer should relyThe system design engineer should rely

    heavily on sound engineering judgment toheavily on sound engineering judgment toachieve an adequate protection system.achieve an adequate protection system.