1
Power Systems Foundation for Supporting your
Critical Operations
Gary Farmer Curtis Engine & Equipment, Inc.
2
Agenda
Decide
Design
System Types
Construction
Prepare for Operations
Maintenance & Testing
Conclusion
Questions
3
Define
What is Critical to Operations? Everything is critical Everything is NOT mission critical to operations
Definition of Mission Critical
Wikipedia: any factor of a system (equipment, process, procedure, software, etc.) whose failure will result in the failure of business operations. That is, it is critical to the organization's "mission." NFPA: For reasons of public safety, emergency management, national security or business continuity. Mission critical is defined by you!
4
Critical Operations in Different Facilities Government
Communications Data Processing Data Storage Security Cybersecurity Weaponry
5
Critical Operations in Different Facilities Commercial
Processes Communications Data Processing Data Storage Security Cybersecurity
6
Critical Operations in Different Facilities Health Care
Patient Care HVAC Diagnostic Imaging Communications Data Processing Data Storage Security Cybersecurity
7
Critical Operations in Different Facilities Education
Communications Data Storage Security Cybersecurity
8
Critical Operations in Different Facilities Retail
Data Processing Data Storage Refrigeration (food & pharm) Security Cybersecurity
9
Design Consult Design Professionals
Architectural Firms Engineering Firms Energy Consultants Owner Representative Firms Equipment Vendors
10
Design Criteria Requirements (What Must Be Done):
Size, Fuel, Emissions, Permitting, Standards, Certification
Integration (Interaction with Environment):
Priorities, Trade-offs, Risk
Constraints (Restrictions):
Budget, Schedule, Scope of Work
11
Power System
Conventional Configuration:
1 Centralized Power Plant
2 Step Up Substation
3 Transmission
Network
4 Step Down
Substation
5 Delivery
Network
6 Load
12
Power Systems Conventional
Radial distribution Loop distribution Utility – Normal source Standby – Alternate source
Standby Single generation Parallel generation o Single connection o Iso-redundant system o Iso-parallel system
13
Uptime Institute Topology Tiers Tier 1
Non-redundant capacity components Single non-redundant distribution paths
Tier 2 Redundant capacity components Single non-redundant distribution paths
Tier 3 Redundant capacity components Multiple independent distribution paths
Tier 4 Redundant capacity components Multiple independent distribution paths Fault tolerant system
14
System Comparison
Standby Power Short-Term (t≤1 year)
Speculative
First Cost Driven
Design - Bid - Build
On-Site Power Long-Term (t≥10 years)
Calculated
Life Cycle Cost Driven
Design & Build
15
Non Traditional Power Systems
Distributed Energy:
More Efficient Use of Existing Assets
Replace Less Efficient Assets
Alternative to Additional Capacity
Energy Savings Offset Service Costs
Avoidance of Peak Demand Charges
16
Non Traditional Power Systems
Distributed Generation: Adding Generation Capacity near Load Avoid Transmission Bottlenecks Stand Alone or Grid Supporting Variety of Available Technologies System Design is Site Specific Suitable for CHP Application Adaptable to Support Load Changes Independent of Utility Grid Avoidance of Peak Demand Charges Interconnection Requirement Barriers
17
Non Traditional Power Systems
Demand Response:
Reduce Load for Set Time Period
Contracted Service upon Request
Alternative to Additional Capacity
Added Revenue from Existing Assets
Offset Costs of Additional Capacity
Communication is Key Enabler
Advanced Metering Infrastructure
18
Non Traditional Power Systems
Microgrid:
Combination of Complementary Power Sources
Multiple Generation Technologies
Multiple Fuel Types
Redundancy
Energy Storage as Backup
Independent of Any One Component
Connected, but Not Dependent on Utility Grid
Advanced Metering and Communications
Best Suited for Campus Wide Application
19
Operations
Preparation:
Staffing
Hardware
Software
Training
Political support
20
Maintenance & Testing
Regular Periodic Tasks:
Daily, Weekly, Monthly, Quarterly, & Anually
Visually Inspect & Record
Measure & Record
Test & Record
21
Maintenance & Testing
Diesel Generator SetMaintenance Items Visual Record Action Frequency
Battery SystemElectrolyte level X X Check Weekly
Charger and charge rate X X Inspect Weekly
Terminals clean and tight X Inspect/Check Weekly
Leakages and spillage X Inspect/Clean Weekly
Remove corrosion from case X Inspect/Clean Monthly
Specific gravity or state of charge X Test Monthly
Equalize charge X X Check Annually
Fuel SystemMain supply tank level X Check Weekly
Day tank level X Inspect/Check Weekly
Day tank float switch X Inspect/Test Weekly
Supply or transfer pump operation X Inspect/Test Weekly
Solenoid valve operation X Inspect/Test Weekly
Strainer, filter and/or dirt leg X Inspect/Drain/Change Weekly
Water in system X Check/Drain Weekly
Flexible hose and connectors X Inspect Weekly
Tank vents/overflow pipe blocked X Inspect/Replace Annually
Piping X Inspect Annually
Wiring in fuel system X Inspect Annually
Fuel in main tank X Test/Filter/Biocide Annually
Lubrication SystemOil level X X Inspect/Check Weekly
Lube oil heater X Check Weekly
Crankcase breather X Inspect/Clean/Replace Semiannual
Oil change X Replace Annually
Oil filter X Change Annually
Method of Checking and Action to Take
22
Maintenance & Testing
Diesel Generator SetMaintenance Items Visual Record Action Frequency
Cooling SystemCoolant level X X Inspect/Check WeeklyAdequate cooling water to heat
exchanger X Check Weekly
Adequate fresh air through radiator X Check Weekly
Water pump X Inspect/Check Weekly
Flexible water hoses and connections X Inspect Weekly
Jacket water heater Check Weekly
Fan and alternator belts X Inspect/Check Monthly
Antifreeze protection level X Test Semiannual
Antifreeze PH test X Test/Replace Annually
Rod out heat exchanger Clean Annually
Clean exterior of radiator Clean Annually
Inspect ductwork, clean louvers X Inspect/Check/Change Annually
Louver motor and controls X Inspect/Clean/Test Annually
Exhaust SystemLeakage X Inspect/Check Weekly
Drain condensate trap X Check Weekly
Insulation and fire hazards X Inspect Monthly
Flexible exhaust section X Inspect Semiannual
Excessive back pressure X Test Annually
Exhaust system hanger and supports X Inspect Annually
Method of Checking and Action to Take
23
Maintenance & Testing
Diesel Generator SetMaintenance Items Visual Record Action Frequency
EngineGeneral inspection X X Inspect Weekly
Service air cleaner X Inspect/Vacuum Semiannual
Governor oil level and linkage X Inspect Monthly
Governor oil X Change AnnuallyIgnition system - plugs, cap, rotor,
secondary wire insulation X
Inspect/Check/Replace/
Clean/Test AnnuallyChoke setting and carburetor
adjustment X Check SemiannualInjector pump and injectors for flow
rate, pressure, and/or spray pattern X Test Annually
Load test X Test Monthly
Valve clearance Test
Every 3 years or
500 hours
Torque bolts Test
Every 3 years or
500 hours
Generator EndBrush length, apprearance free to move
in holder X Inspect/Check/Clean Semiannual
Commutator and slip rings X Inspect/Clean Annually
Rotor and stator X Inspect/Clean Annually
Bearings X Inspect/Replace Annually
Bearing grease X Check/Replace Annually
Exciter X Inspect/Check/Clean Annually
Voltage regulator X Inspect/Check/Clean Annually
Measure and record resistance readings
of windings with insulation tester X Test Annually
Method of Checking and Action to Take
24
Maintenance & Testing
Diesel Generator SetMaintenance Items Visual Record Action Frequency
Electrical SystemGeneral inspection X Inspect Weekly
Circuit breakers, fuses X Inspect/Check/Clean Monthly
Wire chafing if subject to movement X Inspect/Check Monthly
Operation of safeties and alarms Check/Test Semiannual
Boxes, panels and cabinets Clean SemiannualTighten control and power wiring
connections X Check AnnuallyCalibration of voltage-sensing
relays/devices Check/Test Annually
Wire insulation breakdown X Test
Every 5 years or
500 hours
Automatic Transfer SwitchGeneral inspection X X Inspect Weekly
Exercise the system under load X Test Weekly
Automatic control system X Test Monthly
Cabinet exterior X Inspect/Clean Monthly
Tighten external components X Inspect/Check Monthly
External operating mechanism X Inspect/Clean/Lubricate Annually
Inspect interior of transfer switch X Inspect Annually
Tighten internal components X Inspect/Check AnnuallyLED indicators and remote control
systems operation X X Test Annually
Transfer switch main contacts X X Inspect/Clean/Replace Annually
Tighten wiring connections Check Annually
Wire insulation deterioration X Inspect/Check/Replace Annually
Method of Checking and Action to Take
25
Maintenance & Testing
Diesel Generator SetMaintenance Items Visual Record Action Frequency
General ConditionUnusual noises, vibrations, leakage,
temperatures or deterioration X X Inspect/Clean Weekly
Service room/surrounding area X Inspect/Clean WeeklyRestore system to automatic operation
condition X Inspect Weekly
Method of Checking and Action to Take
26
Adm. Ricover’s Principles of Safe Operation
Rising Standard of Quality
Highly Capable Operators Trained by Operators
Alert Bad News when it Happens
Respect the Danger
Constant and Rigorous Training
Repair, QC, Safety, and Technical Support must work together
Learn from Past Mistakes
27
Conclusion
One Size Fits One
You Define Mission Critical
Consult Design Professionals
Determine System Type
Prepare for Construction
Prepare for Operations
Prepare for Maintenance & Testing
28
Questions ?