![Page 1: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/1.jpg)
Power System Protection
Dr. Lionel R. Orama Exclusa, PEWeek 8
![Page 2: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/2.jpg)
Copyright L.R. Orama 2006 2
Distance Relays
• Mason– Chapter 4, pgs. 61-76
![Page 3: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/3.jpg)
Copyright L.R. Orama 2006 3
Objectives
• R-X Diagrams• Operating Principles of:
– Impedance– Admittance (Mho)– Reactance
• Memory Action
![Page 4: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/4.jpg)
Copyright L.R. Orama 2006 4
Distance Relays
• Respond to phasor ratio of input voltage & input current to relay (V/I)
• They are directional• They have high speed• Used to protect transmission lines• Usually induction cup design
![Page 5: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/5.jpg)
Copyright L.R. Orama 2006 5
Construction
![Page 6: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/6.jpg)
Copyright L.R. Orama 2006 6
R-X Diagram
• Can use impedance or R-X diagram to analyze relay operation
1. Plot relay characteristic
2. Plot impedance “seen” by the relay (Z relay)
![Page 7: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/7.jpg)
Copyright L.R. Orama 2006 7
![Page 8: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/8.jpg)
Copyright L.R. Orama 2006 8
![Page 9: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/9.jpg)
Copyright L.R. Orama 2006 9
![Page 10: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/10.jpg)
Copyright L.R. Orama 2006 10
![Page 11: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/11.jpg)
Copyright L.R. Orama 2006 11
![Page 12: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/12.jpg)
Copyright L.R. Orama 2006 12
Impedance Relay
![Page 13: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/13.jpg)
Copyright L.R. Orama 2006 13
Admittance (Mho) Relay
![Page 14: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/14.jpg)
Copyright L.R. Orama 2006 14
Offset Mho
![Page 15: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/15.jpg)
Copyright L.R. Orama 2006 15
Offset Mho
![Page 16: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/16.jpg)
Copyright L.R. Orama 2006 16
Angle Impedance Relay
Non-Directional
Not appropriate to work alone
![Page 17: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/17.jpg)
Copyright L.R. Orama 2006 17
Reactance Relay
Non-Directional
![Page 18: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/18.jpg)
Copyright L.R. Orama 2006 18
Distance Relays• Operating Time
– Induction Cup: High Speed
• Adjustments– Reach: Tapped
Transformer• Rises or lowers voltage on
restraining coil• Range of Z to cover down
the line
– Offset: Tapped Reactor• For offset Mho, adjust ZT
![Page 19: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/19.jpg)
Copyright L.R. Orama 2006 19
Application of Distance Relays to Transmission Line Protection
• Phase distance relays• Ground distance relays (will not be
covered)• Step distance relays
– Usually 3 zones
• Distance better than overcurrent– Faster– Easier coordination– Permit higher line loading
![Page 20: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/20.jpg)
Copyright L.R. Orama 2006 20
System Impedance on Relay Base
![Page 21: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/21.jpg)
Copyright L.R. Orama 2006 21
System Impedance on Relay Base
![Page 22: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/22.jpg)
Copyright L.R. Orama 2006 22
PT Connections-Phase Distance Relays
600577115
4.66
10115
115 3
→===
===
V
kV
V
VPTR
V
kV
V
VPTR
LGout
LGinLG
LLout
LLinLL
![Page 23: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/23.jpg)
Copyright L.R. Orama 2006 23
CT Connection to Op Coils
![Page 24: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/24.jpg)
Copyright L.R. Orama 2006 24
Impedances Detected by Phase Relays
3 Phase Fault
Phase-Phase Fault
Relay setting based on Positive Sequence Impedance (Z1)
![Page 25: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/25.jpg)
Copyright L.R. Orama 2006 25
Step Distance Relaying
Objectives• Zones of protection• Effect of arc resistance• Effect of infeed• Methods to reduce size of distance relay
characteristic
![Page 26: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/26.jpg)
Copyright L.R. Orama 2006 26
Zones of Protection-3 Zones
• 3 zones (Primary & Backup)Purpose: Provide high speed tripping for internal faults• Relay must be set to underreach• Does not cover entire line• Zone 1 settings:
– Reach:80-90%– Time: No time delay
Zone 1
![Page 27: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/27.jpg)
Copyright L.R. Orama 2006 27
Zones of Protection
Purpose: Cover remaining 10-20% of AB segment• Zone 2 must reach beyond B• Will detect faults on CD segment• Must have time delay• Zone 2 settings:
– Reach:120%– Time: 0.2-0.4 seconds
Zone 2
![Page 28: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/28.jpg)
Copyright L.R. Orama 2006 28
Zones of Protection
Purpose: Provides Backup protection for faults on adjacent line
• Do not set such that load can cause a trip• Zone 3 settings:
– Reach:120% of ZAB+ZCD
– Time: 0.4-1.0 seconds
Zone 3
Equivalent Relays at B and D looking on the other direction
![Page 29: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/29.jpg)
Copyright L.R. Orama 2006 29
Three Zones of Protection Using Mho Relays
• Advantage– Lots of fault coverage
• Disadvantage– Characteristic gets
close to ZLOAD
GCY - GE Mho
![Page 30: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/30.jpg)
Copyright L.R. Orama 2006 30
Relay Characteristic Vs Arc Resistance
• illustrates increase RF coverage with mho relay (GCY) & reactance relay (GCX)– O1 & M3 operate - Zone 1– O2 & M3 operate – Zone 2– M3 operate – Zone 3– M1 – Zone1 using mho
![Page 31: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/31.jpg)
Copyright L.R. Orama 2006 31
Zone 3 Setting with Infeed
![Page 32: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/32.jpg)
Copyright L.R. Orama 2006 32
Zone 3 Setting with Infeed
danger
![Page 33: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/33.jpg)
Copyright L.R. Orama 2006 33
Use of Blinders where Impedance may cause incorrect tripping
Zone 3 so big that ZLOAD gets inside of it
Angle Impedance relays to blind
![Page 34: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/34.jpg)
Copyright L.R. Orama 2006 34
Reverse Third ZoneZAB+ZCDIF/IA
![Page 35: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/35.jpg)
Copyright L.R. Orama 2006 35
Reverse Third Zone
Load
![Page 36: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/36.jpg)
Copyright L.R. Orama 2006 36
Admittance Relay Settings• Reach: Diameter of Mho
Circle– Maximum Z that makes
relay operate
![Page 37: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/37.jpg)
Copyright L.R. Orama 2006 37
Admittance Relay Settings
• t varies from 0.10 to 1.00 (t higher, smaller circle)• k is called Basic Minimum Reach is adjustable• Angle of maximum torque is adjustable• Offset is adjustable
![Page 38: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/38.jpg)
Copyright L.R. Orama 2006 38
Impedances Detected by all Relays During B-C Fault
B-C Relay
A-B Relay
C-A Relay
![Page 39: Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama Exclusa, PE ... System Impedance on Relay Base. ... Provides Backup protection for faults](https://reader036.vdocuments.us/reader036/viewer/2022081422/5b4f93a37f8b9a3e6e8c9a3c/html5/thumbnails/39.jpg)
Copyright L.R. Orama 2006 39
Impedances Detected by all Relays During B-C Fault