EE 369POWER SYSTEM ANALYSIS
Lecture 8Transformers, Per UnitTom Overbye and Ross Baldick
1
AnnouncementsFor lectures 8 to 10 read Chapter 3Homework 6 is 5.14, 5.23, 5.26, 5.27, 5.28,
5.33, 5.37, 5.43; due October 6.Tour of the UT power plant during class,
Tuesday, October 11. Meet Mr. Mack Andrews in the area between ACES and the power plant, adjacent to 24th Street.
Homework 7 is 3.1, 3.4, 3.8, 3.10, 3.14, 3.16, 3.19; due October 13.
Homework 8 is 3.21, 3.23, 3.28, 3.29, 3.38, 3.49, 3.60; due October 20. 2
AnnouncementsTour of ERCOT Met Center facility during class,
November 3. Mr. John Adams will be showing you around the
ERCOT facility, including the control room.If you a foreign national please email me your
nationality and your passport number.I will be sending a list of all attendees to ERCOT so
that they can prepare badges. You will need to get to the Met Center in your own
cars, but I will facilitate car-pooling for anyone who does not have a car.
3
Transformers Overview• Power systems are characterized by many different
voltage levels, ranging from 765 kV down to 220/110 volts.
• Transformers are used to transfer power between different voltage levels.
• The ability to inexpensively change voltage levels is a key advantage of ac systems over dc systems.
• In this section we’ll development models for the transformer and discuss various ways of connecting three phase transformers.
4
Ideal TransformerFirst we review the voltage/current relationships for an
ideal transformer– no real power losses– magnetic core has infinite permeability– no leakage flux
We’ll define the “primary” side of the transformer as the side that usually receives power from a line etc, and the secondary as the side that usually delivers power to a load etc:– primary is usually the side with the higher voltage, but may
be the low voltage side on a generator step-up transformer.
5
Ideal Transformer Relationships
1
1 1 2 2
1 21 1 2 2
1 2 1 1
1 2 2 2
Assume we have flux in magnetic material.
Then flux linking coil 1 having turns is:
, and similarly
,
= turns ratio
m
m m
m m
m
N
N N
d dd dv N v N
dt dt dt dtd v v V N
adt N N V N
Note that I2 and I2’ are in opposite directions
6
Current Relationships
'1 1 2 2
'1 1 2 2
'1 1 2 2
To get the current relationships use ampere's law
with path around core having total length :
mmf
Assuming uniform flux density in the core
having area ,
L
d N i N i
H L N i N i
B LN i N i
A
H L
'1 1 2 2
then B A
LN i N i
A
7
Current/Voltage Relationships'
1 1 2 2
'1 2 1 22 2'
1 2 12
1
2
1 2
1 2
If is infinite then 0 . Hence
1or , where
1Then: and:
0
10
N i N i
i N i Ni i
N i N ai
II a
aV V
I Ia
8
Impedance Transformation Example
•Example: Calculate the primary voltage and current for an impedance load Z on the secondary
21
21
2 2 / and substituting:
0
10
a VVVIZa
I V Z
21 2 1
21
1
1
primary referred value of
secondary load impedance
VV aV I
a ZV
a ZI
9
Real TransformersReal transformers
– have losses– have leakage flux– have finite permeability of magnetic core
• Real power losses– resistance in windings (I2 R)– core losses due to eddy currents and hysteresis
10
Transformer Core lossesEddy currents arise because of changing flux in core.Eddy currents are reduced by laminating the core
Hysteresis losses are proportional to area of BH curveand the frequency
These losses are reduced by using material with a “thin” BH curve
11
Effect of Leakage Flux
2
22
1 1 1
2 2 2
'1 1 1 2 2
11 1 1 1 1
1
''
2 2 2
Not all flux is within the transformer core
Assuming a linear magnetic medium we get
, including winding
resistance ,
l m
l m
l l l l
ml
l
N
N
L i L i
ddiv r i L N
dt dtr
div r i L
dt
2 2, including resistance .mdN rdt
12
Effect of Finite Core Permeability
m
1 1 2 2 m
m 21 2
1 1
1 m
Finite core permeability means a non-zero mmf
is required to maintain in the core
,
where is the reluctance.
This effect is usually modeled as a magnetizing current
N i N i R
R
R Ni i
N N
Ni i
2 m2 m
1 1
where ,
modeled by resistance and inductance.
Ri i
N N
13
Transformer Equivalent CircuitUsing the previous relationships, we can derive an equivalent circuit model for the real transformer
' 2 '2 2 1 2
' 2 '2 2 1 2
This model is further simplified by referring all
impedances to the primary side
e
e
r a r r r r
x a x x x x
14
Simplified Equivalent Circuit
15
Calculation of Model ParametersThe parameters of the model are determined
based upon: – nameplate data: gives the rated voltages and power– open circuit test: rated voltage is applied to primary
with secondary open; measure the primary current and losses (the test may also be done applying the voltage to the secondary, calculating the values, then referring the values back to the primary side).
– short circuit test: with secondary shorted, apply voltage to primary to get rated current to flow; measure voltage and losses. 16
Transformer Example
•Example: A single phase, 100 MVA, 200/80 kV transformer has the following test data:
–open circuit: 20 amps, with 10 kW losses–short circuit: 30 kV, with 500 kW losses
•Determine the model parameters.
17
Transformer Example, cont’d
2
2 2
2
100MVA 30 kV500 A, 60
200kV 500 A
500 kW 2 ,
Hence 60 2 60
200 (kV)4M
10 kW
200 kV10,000 10,000
20 A
sc e e
sc e sc e
e
c
e e m m
I R jX
P R I R
X
R
R jX jX X
From the short circuit test
From the open circuit test
18
Residential Distribution Transformers
Single phase transformers are commonly used in residential distribution systems. Most distributionsystems are 4 wire, with a multi-grounded, common neutral.
19
Per Unit CalculationsA key problem in analyzing power systems is the large
number of transformers. – It would be very difficult to continually have to refer
impedances to the different sides of the transformersThis problem is avoided by a normalization of all
variables.This normalization is known as per unit analysis.
actual quantityquantity in per unit
base value of quantity
20
Per Unit Conversion Procedure, 11. Pick a 1 VA base for the entire system, SB
2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts) 21
Per Unit Solution Procedure
1. Convert to per unit (p.u.) (many problems are already in per unit)
2. Solve3. Convert back to actual as necessary
22
Per Unit ExampleSolve for the current, load voltage and load power in the circuit shown below using per unit analysis with an SB of 100 MVA, and voltage bases of 8 kV, 80 kV and 16 kV, respectively.
Original Circuit23
Per Unit Example, cont’d2 2
2 2
2 2
8 (kV)0.64
100MVA
80 (kV)64
100MVA
16 (kV)2.56
100MVA
LeftB
MiddleB
RightB
Z
Z
Z
Same circuit, withvalues expressedin per unit.
24
Per Unit Example, cont’d
2*
1.0 00.22 30.8 p.u. (not amps)
3.91 2.327
1.0 0 0.22 30.8
p.u.
0.189 p.u.
1.0 0 0.22 30.8 30.8 p.u.
L
LL L L
G
Ij
V
VS V I
ZS
25
Per Unit Example, cont’dTo convert back to actual values just multiply the per unit values by their per unit base
Actual
Actual
Actual
Middle
ActualMiddle
0.859 30.8 16 kV 13.7 30.8 kV
0.189 0 100 MVA 18.9 0 MVA
0.22 30.8 100 MVA 22.0 30.8 MVA
100 MVA1250 Amps
80 kV
0.22 30.8 275 30.8
L
L
G
B
V
S
S
I
I
26
Three Phase Per Unit
1. Pick a 3 VA base for the entire system, 2. Pick a voltage base for each different voltage
level, VB,LL. Voltages are line to line. 3. Calculate the impedance base
Procedure is very similar to 1 except we use a 3 VA base, and use line to line voltage bases
3BS
2 2 2, , ,3 1 1
( 3 )
3B LL B LN B LN
BB B B
V V VZ
S S S
Exactly the same impedance bases as with single phase!27
Three Phase Per Unit, cont'd
4. Calculate the current base, IB
5. Convert actual values to per unit
3 1 13 1B B
, , ,
3
3 3 3B B B
B LL B LN B LN
S S SI I
V V V
Exactly the same current bases as with single phase!
28
Three Phase Per Unit Example•Solve for the current, load voltage and load power in the previous circuit, assuming:
–a 3 power base of 300 MVA, –and line to line voltage bases of 13.8 kV, 138 kV and 27.6 kV (square root of 3 larger than the 1 example voltages)–the generator is Y-connected so its line to line voltage is 13.8 kV.
Convert to per unitas before. Note the system is exactly the same!
29
3 Per Unit Example, cont'd
2*
1.0 00.22 30.8 p.u. (not amps)
3.91 2.327
1.0 0 0.22 30.8
p.u.
0.189 p.u.
1.0 0 0.22 30.8 30.8 p.u.
L
LL L L
G
Ij
V
VS V I
ZS
Again, analysis is exactly the same!30
3 Per Unit Example, cont'd
L
Actual
ActualL
ActualG
MiddleB
ActualMiddle
0.859 30.8 27.6 kV 23.8 30.8 kV
0.189 0 300 MVA 56.7 0 MVA
0.22 30.8 300 MVA 66.0 30.8 MVA
300 MVA125 (same cu0 Amps
3138 kV
0.22 30
rrent
8
!)
.
V
S
S
I
I
Amps 275 30.8
Differences appear when we convert back to actual values
31