power | no-break : sys 33, by sensys group

6
Mission Critical Applications INFINITE POWER UPS UNINTERRUPTIBLE POWER SUPPLY From 10 kVA to 300 kVA Sys 33 Full IGBT double conversion technology allowing it to provide extraordinary savings, while at the same time leading first class load protection UPS 3 PHASE IGBT Rectifier Design Double Conversion True On-Line-VFI Green Power Availability Reliability Efficiency GROUP

Upload: paulo-chong-santos

Post on 12-Aug-2015

53 views

Category:

Engineering


7 download

TRANSCRIPT

Page 1: POWER | NO-BREAK : SYS 33, by SENSYS Group

Mission Critical Applications

INFINITE POWER

UPSUNINTERRUPTIBLE POWER SUPPLY

From 10 kVA to 300 kVA

Sys 33

Full IGBT double conversion technology allowingit to provide extraordinary savings, while at the same

time leading first class load protection

UPS 3 PHASE

IGBT Rectifier DesignDouble Conversion

True On-Line-VFI Green Power AvailabilityReliabilityEfficiency

GROUP

Page 2: POWER | NO-BREAK : SYS 33, by SENSYS Group

02

Data Center

IT Rooms

Manufacture Line

Process Units

Hospital Operating Rooms

Medical Equipments

Magnetic Equipments

Laboratory Systems

Security Systems

Financial Systems

Transportation & Infrastructure

Television Systems

Broadcasting and Transmission

Equipment

Radio and Telecommunication

Lighting and Emergency

Call Centre

Applications

Our task is to be a global leader, both in technology and engineering, to provide innovative solutions and expertisein reliable power, precision cooling systems, embedded computing, integrated racks and enclosures, power switching and controls, renewable energies, emergency and security, monitoring, management and connectivity. To follow the needs of today’s business, SENSYS offers a complete portfolioof critical power products and services, from basic UPSto engineered power systems, and from basic batterymaintenance to comprehensive service contracts covering every aspect of your power quality.

Maximized to guarantee reliability and availability, provides the best power protection technology for modern mission criticalIT and electronic loads.

The SYS-33 series is a three phase unit UPS, VFIdouble-conversion, full IGBT design and DSP in inverter/rectifier that features high efficiency up to 94.3%.

In addition is designed with increased power factor correction PFC (>0.99) and low THD(i) (down to 3%).

With an industry-leading, the SYS-33 series delivers remarkably low total cost of ownership in terms of both system and operation cost.

Sys 3310 kVA to 300 kVA

Page 3: POWER | NO-BREAK : SYS 33, by SENSYS Group

• Capability to supply loads with capacitive PF – Output PF

• Operates in VFI mode (Voltage Frequency Independent) compliant

the maximum levels of power reliability for all mission-critical processes.

• Intelligent design provides easy maintenance and installation

• Fault tolerance with built-in maintenance and static bypass

• Multi language LCD display

• Wide input voltage range

• Battery management system (extends battery lifetime)

• Optional model with built-in galvanic isolation transformer

• High overload capacity to improve downstream discrimination

• Redundant auxiliary power and control circuit ensures higher reliability

• Easy integration with networking (TCP/IP-SNMP) and BMS systems

• Energy savings up to 94.3% - high efficiency in battery or normal mode even at low % of load for lower operation costs

• Green power design allows to work at maximum efficiency by offering a new benchmark according to the load requirement

• Eco Mode permits an overall efficiency of 97%

• Small footprint

• High input power factor (PF>0.99) and low harmonic distortion (THD down to 3 %), saving in installation costs

• Fully compatible with generator installation

• Evolution and redundancy N+1 guaranteed by on site Parallel Ready

• Ergonomic design to enable easy diagnostic

03

Lowest TCO - (total cost of ownership)

Flexibility and Availability Power

SYS-33 series is a transformerless UPS designed to help your business, making it the perfect solution for continuous availability, flexibility, serviceability and performance. This system, DSP microprocessor controlled, much faster than the standard microprocessor, is able to deliver 10kVA up to 300 kVA of power in different sizes to suit the marketrequirements.

Sys 3310 kVA to 300 kVA

Page 4: POWER | NO-BREAK : SYS 33, by SENSYS Group

04

Technical Specifications

Topology : true on-Line, double conversion, VFI (Voltage and Frequency Independent) - EN 62040-3Technology : full IGBT, DSP controlled, redundancy design, continuous operationConstruction : available 10 up to 300 kVAOperating modes : double conversion, automatic bypass, frequency converter and parallel operation

Output power rating (kVA)

Nominal active power (kW)

Dimensions (*)

Weight (kg)

Efficiency - AC/AC

Efficiency - Eco Mode

Standards

Input voltage

Input voltage range

Input frequency range

Input power factor

Input current harmonic distortion

Output voltage

Output frequency

Output Voltage Wave Form

Output voltage

Output voltage THD at linear load

Overload

Link DC Voltage

Operating Range

Interface standard

Optional interface acces

Emergency power off

Bypass

Parallel kit

Dual input connection

10 15 20 30 40 60

8 12 16 24 32 48

410 x 800 x 1100 550 x 900 x 1400

105 120 120 130 185 205

Up to 93.4 %

Up to 97 %

EN 62040-1 (safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)

380/220 , 400/230 , 415/240 (3 Phase, 4-wire plus ground) Vac

100% load ≈ 320Vac – 480Vac |50% load ≈ 210Vac – 480Vac |30% load ≈ 140Vac – 480Vac

50-60 Hz ± 10%

0.99

THD(i) down to 4% (CLEAN input)

380/220 , 400/230 , 415/240 (3 Phase, 4-wire plus ground) Vac

50-60 Hz ± 0.01% free running mode

Sine Wave

< 1%

< 3%

125% : 10minutes ; 150% : 1minute

± 372 Vdc

UPS: 0 ºC +40 ºC / Battery: 20-25 ºC

RS232, Smart Slot, RS485, Dry contacts, Generator port

SNMP card, Modbus card

Local and remote

Built-in static and manual bypass

Redundancy N+1 up to 4 units with parallel kit (optional)

Bypass and rectifier separated

(*) dimensions with casters

(optional)

Sys 3310 kVA to 300 kVA

Page 5: POWER | NO-BREAK : SYS 33, by SENSYS Group

05 (*) dimensions with casters

Technical Specifications

Topology : true on-Line, double conversion, VFI (Voltage and Frequency Independent) - EN 62040-3Technology : full IGBT, DSP controlled, redundancy design, continuous operationConstruction : available 10 up to 300 kVAOperating modes : double conversion, automatic bypass, frequency converter and parallel operation

Output power rating (kVA)

Nominal active power (kW)

Dimensions (*)

Weight (kg)

Standards

Input voltage

Input voltage range

Input frequency range

Input power factor

Input current harmonic distortion

Output voltage

Output frequency

Output Voltage Wave Form

Output voltage

Output voltage THD at linear load

Overload

Link DC Voltage

Operating Range

Interface standard

Optional interface acces

Emergency power off

Bypass

Parallel kit

Dual input connection

80 100 120 160 200 250 300

64 80 96 128 160 200 240

670 x 730 x 1630 850 x 780 x 1820

960 x 870 x 1860 1340 x 1080 x 1950

255 285 350 525 570 735 750

EN 62040-1 (safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)

100% load ≈ 320Vac – 480Vac |50% load ≈ 210Vac – 480Vac |30% load ≈ 140Vac – 480Vac

50-60 Hz ± 10%

0.99

THD(i) down to 3% (CLEAN input)

380/220 , 400/230 , 415/240 (3 Phase, 4-wire plus ground) Vac

50-60 Hz ± 0.01% free running mode

Sine Wave

< 1%

< 3%

125% : 10minutes ; 150% : 1minute

± 372 Vdc ± 360 Vdc

UPS: 0 ºC +40 ºC / Battery: 20-25 ºC

RS232, Smart Slot, RS485, Dry contacts, Generator port

SNMP card, Modbus card

Local and remote

Built-in static and manual bypass

Redundancy N+1 up to 4 units with parallel kit (optional)

Bypass and rectifier separated (optional)

Efficiency - AC/AC

Efficiency - Eco Mode

Up to 94.3 %

Up to 97 %

380/220 , 400/230 , 415/240 (3 Phase, 4-wire plus ground) Vac

Sys 3310 kVA to 300 kVA

Page 6: POWER | NO-BREAK : SYS 33, by SENSYS Group