DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES
Nexans AmerCable believes the information presented throughout this catalog to be reliable and current. All information is subject to change without notice. The information listed is approximate, and is presented only as a guide for product selection. We make no claims or warranties for the suitability of any product for any particular application.
DOWNSTREAM FACILITY CABLES
VFD Cables
Nexans AmerCable VFD Cables are speciallyengineered to provide 100% containment of EMIemissions and provide longer cable life in VFD applications.
Nexans AmerCable VFD cables feature symmetrical insulated groundconductors that reduce inducedvoltage imbalances and carrycommon mode noise back to the drive.
Nexans AmerCable’s high strandcount conductors and braid shielddesign is much more flexible, easier to install and more resistant tovibration than Type MC cable.
Available in 5 constructions.
See pages 16-20
CIR® (Crush & Impact Resistant)CIR is a next-generation cable designed to replaceolder-technology cables like Type MC. CIR has beensuccessfully used globally since 2002 for mission-critical equipment operating in harsh environments.
CIR passes the same crush and impact testingrequired by UL 2225 for Type MC-HL without theuse of external armoring.
CIR cables are GEXOL® insulated which provides alower dielectric constant, allowing longer VFDoutput cable lengths.
Made in America
Highly flexible, small bend radius,reduced tray fill and impervious towater and air.
UL Listed as Type TC-ER (Standard CIR) – suitable for avariety of uses, including those wheretray cables are not practical or cost-prohibitive.
UL Listed as Type TC-ER-HL (Arctic Grade CIR) – suitable for a variety of uses in Class 1, Div 1 andZone 1 environments including thosewhere tray cables are not practical orcost-prohibitive. (Cables up to 1” indiameter)
See pages 2-15
www.NexansAmerCable.comAmerCable® and GEXOL® are registered trademarks of AmerCable Incorporated.CORFLEX® is a registered trademark of Nexans
CORFLEX® Cables
CORFLEX cables are designed for reliable performance in a variety of oil and gasdownstream, industrial, commercial and utilityapplications which require an externally armored cable.
Nexans CORFLEX MC-HL and MV-105 or MC-HL cables can be installed in hazardous locations designated Class I, II & III,Divisions 1 & 2 as per NEC 2008 and NEC 2011(HL Rated).
See pages 32-45
RHH or RHW-2Cables
Nexans AmerCable’s 2000V DieselLocomotive Cable (DLO) is a singleconductor portable power cable suitable for use in applications needing great flexibility, excellentwearability and good flex life.
See pages 46-47
Type MMV (Medium Voltage) Power
Type MMV cables are designed for use as feedersor branch circuits in industrial facilities.
These cables utilize flexiblestranded conductors, braided shields and a braided armor (optional) which make them very suitable for applications involving repeated flexing and high vibration
These cables have a small minimum bending radius for easy installation.
See pages 22-31
2 www.nexansamercable.com • e-mail: [email protected]
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoplastic compoundmeeting UL 1309/CSA 245 and IEEE 1580.
ConductorSoft annealed flexiblestranded tinned copper perIEEE 1580 Table 11.
InsulationGEXOL® cross-linked flameretardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245.600V/IEC 1000V.
APPLICATIONDesigned and constructed to be a flexible alternativeto Type MC cable where user desires the added crushand impact protection.
FEATURESn MSHA approved (3 & 4 conductor cables))n Passes the same stringent crush and impact testingrequired by UL 2225 for Type MC-HL
n Gas & vapor tight – impervious to water and airn Smaller bend radius (up to 40% smaller) than Type MC
n Reduced tray fill (up to 35% less) compared to Type MC
n Considerably more flexible than Type MCn Reduced installation time and cost compared to Type MC
n Glands for this product cost up to 50% LESS than those for Type MC
37-102 CIR
STANDARD CIR® POWER CABLEUL LISTED AS TYPE TC-ERThree & Four Conductor + Ground • Gexol® Insulated • 0.6/1kV • MSHA Approved • Rated 90°C
Safer to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors
Standard CIR® Ratings & Approvalsn 90°C temperature ratingn UL Listed as Type TC-ER (E123629)n MSHA Approved (3 & 4 conductor cables)n UL Listed as Marine Shipboard Cable (E111461)n American Bureau of Shipping (ABS) n Flame Retardant – IEEE 1202n Suitable for use in Class I, Div 2 and Zone 2 environmentsn Sunlight resistantn Direct burial
SeeBend Radiuson Page 15
3Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Ampacities are based on Table 310.15 (B) (16) of the National Electrical Code (NEC) for conductors rated 90°C, in a multi-conductorcable, at an ambient temperature of 30°C. The 75°C column is provided for additional information. The ampacities shown apply to openruns of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is inaccordance with NEC Table 310.15 (B) (3) (a). The ampacities shown also apply to cables installed in cable tray in accordance with NECSection 392.80.
Conductor Size Grounding Nominal DC Resistance AC Resistance Inductive Voltage Drop AWG/ Number of Conductor Part No. Diameter Weight 90°C NEC 75°C NEC at 25°C at 90°C, 60Hz Reactance (Volts/Amp/ kcmil mm2 Conductors AWG/kcmil 37-102 (inches) (lbs/1000 ft.) Ampacity Ampacity Ampacity (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) 14 2.1 3 14 -508CIRG 0.500 161 15 15 2.91 3.64 0.04 5.069 14 2.1 4 14 -509CIRG 0.525 187 15 15 2.91 3.64 0.04 5.072 12 3.3 3 12 -516CIRG 0.537 210 20 20 1.83 2.28 0.03 3.195 12 3.3 4 12 -517CIRG 0.580 246 20 20 1.83 2.28 0.04 3.198 10 5.2 3 10 -308CIRG 0.580 277 30 30 1.15 1.44 0.03 2.028 10 5.2 4 10 -408CIRG 0.728 367 30 28 1.15 1.44 0.03 2.031 8 7.6 3 10 -309CIRG 0.760 431 55 50 0.708 0.885 0.034 1.261 8 7.6 4 10 -409CIRG 0.821 513 44 40 0.708 0.885 0.037 1.263 6 12.5 3 8 -310CIRG 0.860 585 75 65 0.445 0.556 0.032 0.803 6 12.5 4 8 -410CIRG 0.915 705 60 52 0.445 0.556 0.035 0.806 4 21 3 6 -312CIRG 0.944 774 95 85 0.300 0.376 0.029 0.550 4 21 4 6 -412CIRG 1.039 956 76 68 0.300 0.376 0.032 0.553 2 34 3 6 -314CIRG 1.094 1105 130 115 0.184 0.230 0.028 0.347 2 34 4 6 -414CIRG 1.203 1381 104 92 0.184 0.230 0.030 0.350 1/0 54 3 6 -316CIRG 1.331 1669 170 150 0.117 0.147 0.028 0.232 1/0 54 4 6 -416CIRG 1.475 2107 136 120 0.117 0.147 0.030 0.235 2/0 70 3 4 -317CIRG 1.445 2062 195 175 0.0929 0.1174 0.0270 0.190 2/0 70 4 4 -417CIRG 1.602 2585 156 140 0.0929 0.1174 0.0296 0.193 4/0 109 3 4 -319CIRG 1.769 3151 260 230 0.0585 0.0753 0.0261 0.131 4/0 109 4 4 -419CIRG 1.953 3972 208 184 0.0585 0.0753 0.0287 0.134 250 127 3 3 -330CIRG 1.925 3493 290 255 0.0488 0.0635 0.0263 0.115 250 127 4 3 -430CIRG 2.125 4510 232 204 0.0488 0.0635 0.0290 0.118 350 177 3 3 -331CIRG 2.171 4594 350 310 0.0344 0.0456 0.0256 0.090 350 177 4 3 -431CIRG 2.402 5900 280 248 0.0344 0.0456 0.0283 0.093 500 253 3 2 -333CIRG 2.521 6207 430 380 0.0251 0.0348 0.0258 0.075 500 253 4 2 -433CIRG 2.855 8178 344 304 0.0251 0.0348 0.0284 0.078 750 380 3 1 -334CIRG 3.081 9165 535 475 0.0166 0.0253 0.0252 0.061 750 380 4 1 -434CIRG 3.365 11883 428 380 0.0166 0.0253 0.0278 0.063
For Cable Color Codes andStranding Information
See page 14
4 www.nexansamercable.com • e-mail: [email protected]
37-102 CIR
STANDARD CIR® CONTROL CABLEUL LISTED AS TYPE TC-ERMulti-Conductor • Gexol® Insulated • 0.6/1kV • Rated 90°C
Gexol® and CIR® are registered trademarks of AmerCable Incorporated.
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoplastic compoundmeeting UL 1309/CSA 245 and IEEE 1580. Rated for directburial.
ConductorSoft annealed flexiblestranded tinned copper perIEEE 1580 Table 11.
InsulationGEXOL® cross-linked flameretardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. 600V/IEC 1000V.
Ampacities are based on Table 310.15 (B) (16) of the National Electrical Code (NEC) for conductors rated 90°C, in a multi-conductor cable, at an ambient temperature of 30°C. The 75°C column is provided for additional information. The ampacities shown apply to open runs of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is in accordance with NEC Table 310.15 (B) (3) (a). The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.80.
Conductor Size Nominal Weight DC Resistance AC Resistance Voltage Drop Number of Part No. Diameter (lbs/ 90°C NEC 75°C NEC at 25°C at 90°C, 60Hz (Volts/Amp/ AWG mm2 Conductors 37-102 (inches) 1000 ft.) Ampacity Ampacity (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) 14 2.1 3 -508CIR 0.490 147 15 15 2.91 3.64 5.069 14 2.1 4 -509CIR 0.535 174 15 15 2.91 3.64 5.072 14 2.1 5 -510CIR 0.565 206 15 15 2.91 3.64 5.072 14 2.1 7 -521CIR 0.602 249 15 14 2.91 3.64 5.072 14 2.1 9 -764CIR 0.796 289 15 14 2.91 3.64 5.072 14 2.1 12 -585CIR 0.840 426 12 10 3.00 3.75 5.224 14 2.1 19 -765CIR 0.955 677 12 10 3.00 3.75 5.224 14 2.1 37 -514CIR 1.315 1138 10 8 3.00 3.75 5.224 12 3.3 2 -515CIR 0.537 163 20 20 1.83 2.28 3.195 12 3.3 4 -517CIR 0.580 227 20 20 1.83 2.28 3.198 12 3.3 5 -560CIR 0.682 305 20 20 1.83 2.28 3.198 12 3.3 7 -712CIR 0.735 374 20 17 1.83 2.28 3.198 12 3.3 9 -766CIR 0.893 435 20 17 1.83 2.28 3.198 12 3.3 12 -750CIR 0.913 576 15 12 1.88 2.35 3.294 12 3.3 19 -767CIR 1.145 1007 15 12 1.88 2.35 3.294 12 3.3 37 -520CIR 1.448 1739 12 10 1.88 2.35 2.028 10 5.2 3 -308CIR 0.580 243 30 30 1.15 1.44 2.031 10 5.2 4 -408CIR 0.685 335 30 28 1.15 1.44 2.031 10 5.2 5 -561CIR 0.740 397 30 28 1.15 1.44 2.031 10 5.2 7 -591CIR 0.795 488 28 24 1.15 1.44 2.031 10 5.2 9 -768CIR 0.805 575 28 24 1.15 1.44 2.031 10 5.2 12 -762CIR 1.079 980 20 17 1.18 1.48 2.092
APPLICATIONDesigned and constructed to bea flexible alternative to Type MC cable where user desires the added crush and impact protection.
FEATURESn Passes the same stringent crush and impacttesting required by UL 2225 for Type MC-HL
n Gas & vapor tight – impervious to water & airn Smaller bend radius (up to 40% smaller) than Type MC
n Reduced tray fill (up to 35% less) compared to Type MC
n Considerably more flexible than Type MCn Reduced installation time and cost compared to Type MC
n Glands for this product cost up to 50% LESS than those for Type MC
For Cable Color Codes and Stranding
Informationsee page 14
Safer to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors
See Page 2for StandardCIR Ratings& Approvals
5Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Gexol® and CIR® are registered trademarksof AmerCable Incorporated.
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoplastic compoundmeeting UL 1309/CSA 245 and IEEE 1580.Rated for direct burial.
ConductorSoft annealed flexiblestranded tinned copper perIEEE 1580 Table 11.
InsulationGEXOL® cross-linked flameretardant polyolefin, meetingthe requirements for Type P ofIEEE 1580 and Type X110 ofUL 1309/CSA 245. 600V/IEC1000V.
Pairs/TriadsEach pair/triad is twisted with a bare tinned drain wire. Each pair/triad is shielded with polyester-backed aluminum foil tape toafford 100% coverage. Pairto pair, or triad to triad,isolation – plus overallshielding – is provided.
APPLICATIONDesigned and constructed to be a flexiblealternative to Type MC cable whereuser desires the added crush and impact protection.
FEATURESn Passes the same stringent crush and impacttesting required by UL 2225 for Type MC-HL
n Gas & vapor tight – impervious to water & airn Smaller bend radius (up to 40% smaller) than Type MC
n Reduced tray fill (up to 35% less) compared toType MC
n Considerably more flexible than Type MCn Reduced installation time and cost compared toType MC
n Glands for this product cost up to 50% LESSthan those for Type MC
Conductor Nominal DC Resistance Mutual Size Part No. Diameter Weight 20°C Capacitance Inductance AWG mm2 Pairs Triads 37-102 (inches) (lbs/1000 ft.) (ohms/1000 ft.) (nF/1000 ft.) (mH/1000 ft.) 16 1.3 1 – -610CIR 0.440 106 4.52 32 0.20 16 1.3 2 – -611CIR 0.700 279 4.52 32 0.20 16 1.3 4 – -613CIR 0.750 340 4.52 32 0.20 16 1.3 8 – -616CIR 1.048 702 4.52 32 0.20 16 1.3 12 – -618CIR 1.216 1062 4.52 32 0.20 16 1.3 24 – -699CIR 1.472 1560 4.52 32 0.20 16 1.3 – 1 -668CIR 0.470 128 4.52 32 0.20 16 1.3 – 4 -698CIR 0.930 453 4.52 32 0.20 16 1.3 – 8 -677CIR 1.130 825 4.52 32 0.20 16 1.3 – 12 -734CIR 1.395 1235 4.52 32 0.20
#16 Pairs / Triads
Capacitance – nF/1000 feet = 32Inductance – mH/1000 = 0.20Resistance – Ohms/1000 feet = 4.52 (@ 20°C)
VALUES:
For Cable Color Codes and Stranding InformationSee page 14
Safer to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors
See Page 2for StandardCIR Ratings& Approvals
See Bend Radiuson Page 15
37-102 CIR
STANDARD CIR® INSTRUMENTATIONCABLE UL LISTED AS TYPE TC-ERIndividually Shielded Pairs/Triads • Gexol® Insulated • 0.6/1kV • Rated 90°C
6 www.nexansamercable.com • e-mail: [email protected]
37-102 CIRVFD
CIR® (CRUSH & IMPACT RESISTANT) VFD POWERCABLE UL LISTED AS TYPE TC-ERThree Conductor • Gexol® Insulated • 2kV • Rated 90°C
APPLICATIONA flexible, braid and foil shielded, 2kV powercable specifically engineered for use in variablefrequency AC motor drive (VFD) applications.
FEATURESn Specially engineered cable design produces alonger cable life in VFD applications.
n Overall braid plus foil shield is engineered with 100% coverage and a surface transferimpedance <50 milliohms at 10MHz tocontain EMI.
n Symmetrical insulated ground conductorsreduce induced voltage imbalances and carrycommon mode noise back to the drive.
n High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
n Gexol’s lower dielectric constant (standard XLPEs,EPRs and other Type RHW insulation materialshave higher dielectric constants) reduces reflectedwave peak voltage magnitudes. This allows forlonger output cable distances and minimizes theeffect of high frequency noise induced into theplant ground system.
n 2kV insulation thickness is used to resist thepotential 2-3x reflected voltages experienced in600V VFD applications.
n Passes the same stringent crush and impacttesting required by UL 2225 for Type MC-HL
n Gas & vapor tight – impervious to waterand air
n Smaller bend radius (up to 40% smaller) than Type MC
n Reduced tray fill (up to 35% less) comparedto Type MC
n Considerably more flexible than Type MCn Reduced installation time and cost comparedto Type MC
n Glands for this product cost up to 50% LESSthan those for Type MC
Insulation (2kV)Gexol® cross-linked flame retardant polyolefin, meeting therequirements for Type RHW. Color: Gray with
printed phase I.D. (Black-Red-Blue)
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistantthermoplastic compound meetingUL 1277.
Power Conductors (x3)Soft annealed flexible stranded tinned copper per ASTM B-33.
Ground Conductors (x3)Soft annealed tinned copper per ASTM B-33 flexiblestranding with 600/1000V Gexol® insulation sized per UL 1277. Color: Green
ShieldOverall tinned copper braidplus aluminum/polyester tape providing 100% coverage.
Safe to HandleCIR® is a safe,
flexible alternative tometal-clad cables.
Gexol® and CIR® are registered trademarks of AmerCable Incorporated
CIR® VFD Ratings & Approvalsn 90°C temperature ratingn UL Listed as Type TC-ER (E123629) n Flame Retardant – IEEE 1202/FT-4n Sunlight resistantn Direct burial
Also available in Arctic Grade:Rated TC-ER-HL for cable diameters up to 1”
7Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Closest Equivalent Uninsulated Size Number IEEE 45 Metric Size ConductorAWG/kcmil of Strands Std. Size (mm2) Dia. (inches)
14121086421
1/02/03/04/0250262313350373444500535646750777
1919373761
133133209266342418532627646777888925
111012211332159118501924
46
101626416683
106133168212262262313373373444535535646777777
2.083.29 5.23 7.57
12.49 21.11 33.51 42.7954.45 70.01 85.57
108.91 125.84132.25159.06 178.23189.36227.23250.02272.68325.70378.82393.87
0.0740.093 0.113 0.1360.1750.2580.3240.361 0.4070.4610.510 0.5750.6280.6540.720 0.7590.7850.8600.8950.9411.0291.0701.132
NEC ampacities are based on Table 310.15(B)(16) of theNational Electrical Code (NEC) for conductors rate 90°C, ina multi-conductor cable, at an ambient temperature of 30°C. The 75°C column is provided for additional information. Theampacities shown apply to open runs of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is in accordance with NEC Table 310.15(B)(3)(a). The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.80.
37-102 CIR VFD • 2000 VOLTS • CRUSH & IMPACT RESISTANT
• Cable diameters are subject to a +/- 5% manufacturing tolerance• Ampacity In Free Air: Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table B.310.15(B)(2)(3)
• Ampacity In Cable Tray: Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table 310.15(B)(16)
• Ampacity In Raceway Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table B.310.15(B)(2)(1)
*3 Grounding Conductors – Green Insulated
CIR VFD Stranding Profile
DC Resist. AC Resist. Inductive Green Size Nominal Weight @ 25°C @ 90°C, 60 Hz Reactance Voltage Drop Insulated In Single InAWG/ Six Part No. Diameter (Lbs./ (Ohms/ (Ohms/ (Ohms/ (Volts/Amp/ Grounding* Free Air Tray Conduit kcmil mm2 37-102 Inches* 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) (3x) (AWG) 90°C 75°C 90°C 75°C 90°C 75°C
14 2.1 -508CIRVFD 0.768 297 2.892 3.616 0.041 5.047 18 15 13 15 13 15 13
12 3.3 -516CIRVFD 0.792 376 1.820 2.275 0.038 3.188 18 20 18 20 18 20 18
10 5.2 -308CIRVFD 0.888 492 1.132 1.416 0.036 1.996 14 30 27 30 27 30 27
8 7.6 -309CIRVFD 0.926 560 0.780 0.976 0.036 1.388 14 65 58 55 49 48 43
6 12.5 -310CIRVFD 1.051 826 0.445 0.556 0.034 0.805 12 87 77 75 67 65 58
4 21 -312CIRVFD 1.093 945 0.300 0.376 0.030 0.551 12 114 101 95 84 89 79
2 34 -314CIRVFD 1.225 1298 0.184 0.230 0.029 0.348 10 152 135 130 115 119 106
1 43 -315CIRVFD 1.340 1517 0.147 0.184 0.029 0.285 10 177 157 150 133 137 121
1/0 54 -316CIRVFD 1.447 1908 0.117 0.147 0.029 0.233 10 205 182 170 151 163 145
2/0 70 -317CIRVFD 1.566 2287 0.093 0.117 0.028 0.192 10 237 210 195 173 186 165
4/0 109 -319CIRVFD 1.874 3360 0.058 0.075 0.027 0.132 8 316 280 260 231 253 224
250 125 -330CIRVFD 1.970 3786 0.050 0.064 0.027 0.117 8 351 311 290 257 276 245
262 132 -320CIRVFD 2.031 4200 0.048 0.063 0.029 0.117 6 362 321 297 263 286 254
313 159 -321CIRVFD 2.130 4787 0.040 0.053 0.028 0.102 6 401 356 328 291 320 284
350 178 -331CIRVFD 2.280 5406 0.036 0.047 0.026 0.092 6 430 381 350 310 345 306
373 189 -322CIRVFD 2.257 5634 0.033 0.044 0.028 0.090 6 449 398 364 323 357 317
444 227 -323CIRVFD 2.400 6410 0.028 0.038 0.027 0.082 6 495 439 401 356 396 351
500 250 -333CIRVFD 2.595 6701 0.025 0.034 0.026 0.074 6 531 471 430 381 427 379
535 273 -324CIRVFD 2.705 7853 0.024 0.033 0.028 0.074 6 556 493 446 395 441 391
646 326 -326CIRVFD 2.898 9368 0.020 0.028 0.027 0.067 6 615 545 492 436 486 431
750 379 -334CIRVFD 3.020 10786 0.017 0.024 0.025 0.060 4 671 595 535 474 529 469
777 394 -327CIRVFD 3.102 11137 0.016 0.025 0.027 0.062 4 688 610 546 484 537 476
NEC Ampacities
8 www.nexansamercable.com • e-mail: [email protected]
CIR® Arctic Grade Ratings & Approvals
n 90°C temperature rating
n UL Listed as Marine Shipboard Cable (E111461)
n UL Listed as Type TC-ERn UL Listed as TC-ER-HL*n American Bureau of Shipping (ABS)
n Flame Retardant – IEEE 1202
n Suitable for use in Class I, Div 2 and Zone 2 environments
n Suitable for Class 1, Div 1 and Zone 1 environments*
*Cables up to 1” in diameter
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset compound meeting UL 1309/CSA 245 and IEEE 1580.
ConductorSoft annealed flexiblestranded tinned copper perIEEE 1580 Table 11.
InsulationGEXOL® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245.600V/IEC 1000V.
Gexol® and CIR® are registered trademarks of AmerCable Incorporated.
37-102 CIRGAG
ARCTIC GRADE CIR® POWER CABLETYPE TC-ER-HL*Three & Four Conductor + Ground • Gexol® Insulated • 0.6/1kV • Rated 90°C
Safer to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation ofconnectors
APPLICATIONDesigned and constructed to be a flexible alternative to Type MC cable where user desires crush and impact protection in arctic conditions.
FEATURESn Complies with the requirements for TC-ER-HL per UL 2225*
n Exceeds CSA cold bend / cold impact (-40°C / -35°C)
n Gas & vapor tight – impervious to water and airn Smaller bend radius (up to 40% smaller) than Type MC
n Reduced tray fill (up to 35% less) comparedto Type MC
n Considerably more flexible than Type MCn Reduced installation time and cost compared to Type MC
n Glands for this product cost up to 50% LESSthan those for Type MC
*cables up to 1” in diameter
Brittlepoint as perASTM D 746-07exceeds -65°C forJacket and -75°C for Insulation
See Bend Radiuson Page 15
9Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Ampacities are based on Table 310.16 of the National Electrical Code (NEC) for conductors rate 90°C, in a multi-conductor cable, at anambient temperature of 30°C. The 75°C column is provided for additional information. The ampacities shown apply to open runs of cable,installation in any approved raceway. Derating for more than three current carrying conductors within the cable is in accordance with NECTable 310.15 (B) (2) (a). The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.11.
Conductor Size Grounding Nominal DC Resistance AC Resistance Inductive Voltage Drop AWG/ Number of Conductor Part No. Diameter Weight 90°C NEC 75°C NEC at 25°C at 90°C, 60Hz Reactance (Volts/Amp/ kcmil mm2 Conductors AWG/kcmil 37-102* (inches) (lbs/1000 ft.) Ampacity Ampacity Ampacity (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) 14 2.1 3 14 -508CIRGAG 0.532 165 15 15 2.91 3.64 0.04 5.069 14 2.1 4 14 -509CIRGAG 0.572 195 15 15 2.91 3.64 0.04 5.072 12 3.3 3 12 -516CIRGAG 0.580 213 20 20 1.83 2.28 0.03 3.195 12 3.3 4 12 -517CIRGAG 0.700 288 20 20 1.83 2.28 0.04 3.198 10 5.2 3 10 -308CIRGAG 0.685 310 30 30 1.15 1.44 0.03 2.028 10 5.2 4 10 -408CIRGAG 0.740 371 30 28 1.15 1.44 0.03 2.031 8 7.6 3 10 -309CIRGAG 0.821 447 55 50 0.708 0.885 0.034 1.261 8 7.6 4 10 -409CIRGAG 0.888 536 44 40 0.708 0.885 0.037 1.263 6 12.5 3 8 -310CIRGAG 0.915 621 75 65 0.445 0.556 0.032 0.803 6 12.5 4 8 -410CIRGAG 1.100 780 60 52 0.445 0.556 0.035 0.806 4 21 3 6 -312CIRGAG 0.944 781 95 85 0.300 0.376 0.029 0.550 4 21 4 6 -412CIRGAG 1.037 964 76 68 0.300 0.376 0.032 0.553 2 34 3 6 -314CIRGAG 1.100 1082 130 115 0.184 0.230 0.028 0.347 2 34 4 6 -414CIRGAG 1.202 1351 104 92 0.184 0.230 0.030 0.350 1/0 54 3 6 -316CIRGAG 1.329 1665 170 150 0.117 0.147 0.028 0.232 1/0 54 4 6 -416CIRGAG 1.468 1954 136 120 0.117 0.147 0.030 0.235 2/0 70 3 4 -317CIRGAG 1.445 2042 195 175 0.0929 0.1174 0.0270 0.190 2/0 70 4 4 -417CIRGAG 1.600 2417 156 140 0.0929 0.1174 0.0296 0.193 4/0 109 3 4 -319CIRGAG 1.792 3106 260 230 0.0585 0.0753 0.0261 0.131 4/0 109 4 4 -419CIRGAG 1.948 3842 208 184 0.0585 0.0753 0.0287 0.134 250 127 3 3 -330CIRGAG 1.925 3683 290 255 0.0488 0.0635 0.0263 0.115 250 127 4 3 -430CIRGAG 2.106 4383 232 204 0.0488 0.0635 0.0290 0.118 350 177 3 3 -331CIRGAG 2.206 4448 350 310 0.0344 0.0456 0.0256 0.090 350 177 4 3 -431CIRGAG 2.440 6216 280 248 0.0344 0.0456 0.0283 0.093 500 253 3 2 -333CIRGAG 2.540 6115 430 380 0.0251 0.0348 0.0258 0.075 500 253 4 2 -433CIRGAG 2.872 8655 344 304 0.0251 0.0348 0.0284 0.078 750 380 3 1 -334CIRGAG 2.975 9042 535 475 0.0166 0.0253 0.0252 0.061 750 380 4 1 -434CIRGAG 3.353 11812 428 380 0.0166 0.0253 0.0278 0.063
Hawke Gland Types Type CIR
Industrial & Safe Area (IP68) 121 Increased Safety
501/421 “EExe” Explosion Proof 710 Class I, Div. 2 Class I, Zone 1 & 2 Flameproof 501/421 “EExd” Zone 1 & 2
Hawke Gland Types
For Cable Color Codesand Stranding Information
See page 14
10
37-102 CIRGAG
ARCTIC GRADE CIR® CONTROL CABLETYPE TC-ER-HL*Multi-Conductor • Gexol® Insulated • 0.6/1kV • Rated 90°C
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset compound meeting UL 1309/CSA 245 and IEEE 1580.
ConductorSoft annealed flexible stranded tinned copper per IEEE 1580 Table 11.
Ground
InsulationGEXOL® cross-linked flameretardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. 600V/IEC 1000V.
Ampacities are based on Table 310.16 of the National Electrical Code (NEC) for conductors rate 90°C, in amulti-conductor cable, at an ambient temperature of 30°C. The 75°C column is provided for additional information.The ampacities shown apply to open runs of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is in accordance with NEC Table 310.15 (B) (2) (a). The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.11.
See page 8 for Arctic CIR Ratings & Approvals
For Cable ColorCodes and StrandingInformation, seepage 12.
Safe to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation ofconnectors
APPLICATIONDesigned and constructed to be a flexible alternative toType MC cable where user desires crush and impactprotection in arctic conditions.
FEATURESn Complies with the requirements for TC-ER-HL per UL 2225*
n Exceeds CSA cold bend /cold impact (-40°C / -35°C)
n Gas & vapor tight – impervious to water & airn Smaller bend radius (up to 40% smaller) thanType MC
n Reduced tray fill (up to 35% less) compared to Type MC
n Considerably more flexible than Type MCn Reduced installation time and cost compared to Type MC
n Glands for this product cost up to 50% LESS than those for Type MC
Brittlepoint as perASTM D 746-07exceeds -65°C forJacket and -75°C for Insulation
Conductor Size Ground DC Resistance AC Resistance Voltage Drop Number of Part No. Diameter Weight 90°C NEC 75°C NEC at 25°C at 90°C, 60Hz (Volts/Amp/ AWG mm2 Conductors 37-102* Number AWG (inches) (lbs/1000 ft.) Ampacity Ampacity (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) 14 2.1 2 -507CIRGAG 1 14 0.500 137 15 15 2.91 3.64 5.069 14 2.1 3 -508CIRGAG 1 14 0.532 165 15 15 2.91 3.64 5.069 14 2.1 4 -509CIRGAG 1 14 0.572 195 15 15 2.91 3.64 5.072 14 2.1 5 -510CIRGAG 1 14 0.673 261 15 15 2.91 3.64 5.072 14 2.1 7 -521CIRGAG 1 14 0.800 345 15 14 2.91 3.64 5.072 14 2.1 9 -764CIRGAG 1 14 0.813 372 15 14 2.91 3.64 5.072 14 2.1 12 -585CIRGAG 1 14 0.850 447 12 10 3.00 3.75 5.224 14 2.1 19 -765CIRGAG 1 14 1.090 698 12 10 3.00 3.75 5.224 14 2.1 37 -514CIRGAG 1 14 1.455 1211 10 8 3.00 3.75 5.224 12 3.3 2 -515CIRGAG 1 12 0.539 175 20 20 1.83 2.28 3.195 12 3.3 3 -516CIRGAG 1 12 0.580 213 20 20 1.83 2.28 3.195 12 3.3 4 -517CIRGAG 1 12 0.700 288 20 20 1.83 2.28 3.198 12 3.3 5 -560CIRGAG 1 12 0.740 333 20 20 1.83 2.28 3.198 12 3.3 7 -712CIRGAG 1 12 0.865 442 20 17 1.83 2.28 3.198 12 3.3 9 -766CIRGAG 1 12 0.910 483 20 17 1.83 2.28 3.198 12 3.3 12 -750CIRGAG 1 12 0.935 578 15 12 1.88 2.35 3.294 12 3.3 19 -767CIRGAG 1 12 1.180 920 15 12 1.88 2.35 3.294 12 3.3 37 -520CIRGAG 1 12 1.500 1548 12 10 1.88 2.35 2.028 10 5.2 2 -553CIRGAG 1 10 0.582 229 30 30 1.15 2.35 2.028 10 5.2 3 -308CIRGAG 1 10 0.685 310 30 30 1.15 1.44 2.031 10 5.2 4 -408CIRGAG 1 10 0.740 371 30 28 1.15 1.44 2.031 10 5.2 5 -561CIRGAG 1 10 0.800 433 30 28 1.15 1.44 2.031 10 5.2 7 -591CIRGAG 1 10 0.930 569 28 24 1.15 1.44 2.031 10 5.2 9 -768CIRGAG 1 10 1.060 712 28 24 1.15 1.44 2.031 10 5.2 12 -762CIRGAG 1 10 1.135 868 20 17 1.18 1.48 2.092
*cables up to 1”in diameter)
11Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset compound meeting UL 1309/CSA 245 and IEEE 1580.
ConductorSoft annealed flexiblestranded tinned copper perIEEE 1580 Table 11.
InsulationGEXOL® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. 600V/IEC 1000V.
Pairs/TriadsEach pair/triad is twisted witha bare tinned drain wire.Each pair/triad is shielded with polyester-backed aluminum foil tape to afford 100% coverage. Pair to pair, or triad to triad, isolation – plus overall shielding – is provided.
Conductor Nominal DC Resistance Mutual Size Part No. Diameter Weight 20°C Capacitance Inductance AWG mm2 Pairs Triads 37-102* (inches) (lbs/1000 ft.) (ohms/1000 ft.) (nF/1000 ft.) (mH/1000 ft.) 16 1.3 1 – -610CIRAG 0.451 106 4.52 32 0.20 16 1.3 2 – -611CIRAG 0.725 279 4.52 32 0.20 16 1.3 4 – -613CIRAG 0.770 340 4.52 32 0.20 16 1.3 8 – -616CIRAG 1.075 702 4.52 32 0.20 16 1.3 12 – -618CIRAG 1.235 1062 4.52 32 0.20 16 1.3 24 – -699CIRAG 1.650 1560 4.52 32 0.20 16 1.3 – 1 -668CIRAG 0.470 128 4.52 32 0.20 16 1.3 – 4 -698CIRAG 0.960 453 4.52 32 0.20 16 1.3 – 8 -677CIRAG 1.200 825 4.52 32 0.20 16 1.3 – 12 -734CIRAG 1.395 1235 4.52 32 0.20
#16 Pairs / Triads
Capacitance – nF/1000 feet = 32
Inductance – mH/1000 = 0.20
Resistance – Ohms/1000 feet = 4.52 (@ 20°C)
VALUES:
See page 8 forArctic Grade CIR
Ratings &Approvals
For Cable Color Codes andStranding InformationSee page 14
Safer to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation ofconnectors
APPLICATIONDesigned and constructed to be a flexible alternative to Type MC cable where user desires crush and impact protection in arctic conditions.
FEATURESn Complies with the requirementsfor TC-ER-HL per UL 2225*
n Exceeds CSA cold bend / cold impact (-40°C / -35°C)
n Gas & vapor tight – impervious to water & airn Smaller bend radius (up to 40% smaller) than Type MC
n Reduced tray fill (up to 35% less) compared to Type MCn Considerably more flexible than Type MCn Reduced installation time and cost compared to Type MC
n Glands for this product cost up to 50% LESS than those for Type MC
*cables up to 1” in diameter
Brittlepoint as perASTM D 746-07exceeds -65°C forJacket and -75°C for Insulation
See Bend Radiuson Page 14
37-102 CIRAG
ARCTIC GRADE CIR®INSTRUMENTATION CABLETYPE TC-ER-HL*Individually Shielded Pairs/Triads • Gexol® Insulated • 0.6/1kV • Rated 90°C
12 www.nexansamercable.com • e-mail: [email protected]
37-102 CIRVFD
ARCTIC GRADE STANDARD CIR® TYPE VFDUL LISTED AS TYPE TC-ER-HL*Three Conductor • Gexol® Insulated • 2kV • Rated 90°C
APPLICATIONA flexible, braid and foil shielded, 2kV powercable specifically engineered for use in variablefrequency AC motor drive (VFD) applications.
FEATURES� Specially engineered cable design produces a longer cable life in VFD applications in severecold environments.
� Exceeds CSA cold bend/cold impact (-40°C/-35°F)� Brittlepoint as per ASTM D 7646-07 exceeds -65°C for Jacket and -75°C for insulation
� Overall braid and foil shield provides 100%coverage containing VFD EMI emissions.
� Symmetrical insulated ground conductors reduceinduced voltage imbalances and carry commonmode noise back to the drive.
� High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
� Gexol’s lower dielectric constant (standard XLPEs,EPRs and other Type RHW insulation materialshave higher dielectric constants) reduces reflectedwave peak voltage magnitudes. This allows forlonger output cable distances and minimizes theeffect of high frequency noise induced into theplant ground system.
� 2kV insulation thickness resists the repetitive 2x voltage spikes from 600V VFDs and reducesdrive over current trip problems due to cablecharging current.
� Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL
� Gas & vapor tight – impervious to water and air� Smaller bend radius (up to 40% smaller) than Type MC
� Reduced tray fill compared to Type MC� Considerably more flexible than Type MC� Reduced installation time and cost � Glands cost up to 50% less
Insulation (2kV)Gexol® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. Color: Gray with
printed phase I.D. (Black-Red-Blue)
JacketA black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset CPE meeting UL 1277.
Power Conductors (x3)Soft annealed flexible stranded tinned copper per UL 44.
Ground Conductors (x3)Soft annealed flexible stranded tinned copper per UL 44. Gexol® insulation sized per UL 1277.Color: Green
ShieldOverall tinned copper braid plus aluminum/polyestertape providing100% coverage.
CIR® Ratings & Approvals
n 90°C temperature rating
n UL Listed as Type TC-ER (E123629)n UL Listed as TC-ER-HL (cables up to 1” in diameter)n Flame Retardant – IEEE 1202
n Suitable for use in Class I, Div 2 and Zone 2 environments
n Suitable for Class 1, Div 1 and Zone 1 environments(cables up to 1” in diameter)
*Cables up to 1” in diameter
Safer to HandleCIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors
13Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Gexol® and CIR® are registered trademarks ofAmerCable Incorporated
Ampacities are based on Table 310.15(B)(16) of the National Electrical Code (NEC) for conductors rated 90°C, in a multi-conductorcable, at an ambient temperature of 30°C. The 75°C column is provided for additional information. The ampacities shown apply to openruns of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is inaccordance with NEC Table 310.15(B)(3)(a). The ampacities shown also apply to cables installed in cable tray in accordance with NECSection 392.80.
*Cable diameters are subject to a +/- 5% manufacturing tolerance
DC Resist. AC Resist. Inductive Green Size Nominal Weight @ 25°C @ 90°C, 60 Hz Reactance Voltage Drop Insulated In Single InAWG/ Size Part No. Diameter (Lbs./ (Ohms/ (Ohms/ (Ohms/ (Volts/Amp/ Grounding* Free Air Tray Conduit kcmil mm2 37-102 Inches* 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) (3x) (AWG) 90°C 75°C 90°C 75°C 90°C 75°C
14 2.1 -508CIRVFDA 0.742 283 2.892 3.616 0.041 5.047 18 15 13 15 13 15 13
12 3.3 -516CIRVFDA 0.815 378 1.820 2.275 0.038 3.188 18 20 18 20 18 20 18
10 5.2 -308CIRVFDA 0.871 473 1.132 1.416 0.036 1.996 14 30 27 30 27 30 27
8 7.6 -309CIRVFDA 0.893 553 0.780 0.976 0.036 1.388 14 65 58 55 49 48 43
6 12.5 -310CIRVFDA 1.093 797 0.445 0.556 0.034 0.805 12 87 77 75 67 65 58
4 21 -312CIRVFDA 1.225 929 0.300 0.376 0.030 0.551 12 114 101 95 84 89 79
2 34 -314CIRVFDA 1.341 1276 0.184 0.230 0.029 0.348 10 152 135 130 115 119 106
1 43 -315CIRVFDA 1.447 1576 0.147 0.184 0.029 0.285 10 177 157 150 133 137 121
1/0 54 -316CIRVFDA 1.566 2144 0.117 0.147 0.029 0.233 10 205 182 170 151 163 145
2/0 70 -317CIRVFDA 1.733 2144 0.093 0.117 0.028 0.192 10 237 210 195 173 186 165
4/0 109 -319CIRVFDA 1.874 3131 0.058 0.075 0.027 0.132 8 316 280 260 231 253 224
250 125 -330CIRVFDA 1.970 3955 0.050 0.064 0.027 0.117 8 351 311 290 257 276 245
262 132 -320CIRVFDA 2.031 3875 0.048 0.063 0.029 0.117 6 362 321 297 263 286 254
313 159 -321CIRVFDA 2.130 4709 0.040 0.053 0.028 0.102 6 401 356 328 291 320 284
350 178 -331CIRVFDA 2.240 4811 0.036 0.047 0.026 0.092 6 430 381 350 310 345 306
373 189 -322CIRVFDA 2.257 5209 0.033 0.044 0.028 0.090 6 449 398 364 323 357 317
444 227 -323CIRVFDA 2.400 6310 0.028 0.038 0.027 0.082 6 495 439 401 356 396 351
500 250 -333CIRVFDA 2.499 7114 0.025 0.034 0.026 0.074 6 531 471 430 381 427 379
535 273 -324CIRVFDA 2.705 7193 0.023 0.033 0.028 0.074 6 556 493 446 395 441 391
646 326 -326CIRVFDA 2.898 9217 0.020 0.028 0.027 0.067 6 615 545 492 436 486 431
750 379 -334CIRVFDA 3.020 10786 0.017 0.024 0.025 0.060 4 671 595 535 474 529 469
777 394 -327CIRVFDA 3.102 10340 0.016 0.025 0.027 0.062 4 688 610 546 484 537 476
NEC Ampacities
14 www.nexansamercable.com • e-mail: [email protected]
Power Cables 6 AWG and smaller = colored insulation 4 AWG and larger = print
Conductor # Color
1 Black
2 Red
3 Blue
4 Orange
Instrumentation Cables Pairs Black, White
Triads Black, White, Red
Pair / Triad numberprinted on conductors
Control CablesColored Insulation
Conductor #Base ColorTracer Color
1 Black –
2 Red –
3 Blue –
4 Orange –
5 Yellow –
6 Brown –
7 Red Black
8 Blue Black
9 Orange Black
10 Yellow Black
11 Brown Black
12 Black Red
13 Blue Red
14 Orange Red
15 Yellow Red
16 Brown Red
17 Black Blue
18 Red Blue
19 Orange Blue
20 Yellow Blue
21 Brown Blue
22 Black Orange
23 Red Orange
24 Blue Orange
25 Yellow Orange
26 Brown Orange
27 Black Yellow
28 Red Yellow
29 Blue Yellow
30 Orange Yellow
31 Brown Yellow
32 Black Brown
33 Red Brown
34 Blue Brown
35 Orange Brown
36 Yellow Brown
37 Black –
161412108642
1/02/04/0250350500750
19191937376113313326634253262788812211850
3461016264166106133212250350500750
1.322.083.295.237.5712.4921.1133.5154.4570.01108.91
127177253380
0.0560.0700.0880.1120.1340.1730.2570.3240.4090.4640.5790.6290.7590.8951.070
CIR Stranding Profiles
Size AWG/kcmilNo. ofStrands
Closest IEEE 45Standard Size
Equivalent MetricSize (mm2)
Uninsulated ConductorDia. (Inches)
15Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Data Basis: 1. Labor rate $35.00/hr.2. Labor time quotes based on long established Fluor Daniel Project Controls Standard Unit for Type TC and Type CWCMC cables for installation tray.
3. Identical installation for both productsusing a 100 ft. run basis.
4. Hawke A121 series glands used for CIR® cables andHawke N701 glands used for Type CWCMC cables.
5. MRO pricing is used for cables and glands.
AmerCable CIR® vs. Type CWCMC (MC-HL)Based on 100 ft. of cable, 2 glands and installation labor (cable & glands)
16 AWG 1 Shielded Pair . . . . . . . . . . . . . . . . . . . . . . CIR® Saves you 36%
14 AWG 3/C+G . . . . . . . . . . . . . . . . . . . . . . . . . . . .CIR® Saves you 37%
6 AWG 3/C+G . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CIR® Saves you 38%
4 AWG 3/C+G . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CIR® Saves you 33%
2/0 4/C+G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CIR® Saves you 10%
Glands for CIR Cables cost up to 50% LESS than those for Type MC
The True Cable Cost Comparison: Lower Total Installed Cost
Type CIR
IEEE 45 6X Diameter
NEC < 1" (25mm) 4X Diameter > 1" (25mm) < 2"(50mm) 5X Diameter > 2" (50mm) 6X Diameter
Bend Radius
16 www.nexansamercable.com • e-mail: [email protected]
37-102VFD
EXTRA FLEXIBLE VFD POWER CABLEGEXOL® INSULATEDThree Conductor • 2kV • Rated 90°C
APPLICATIONA flexible, braid and foil shielded, 2kV powercable specifically engineered for use in variablefrequency AC motor drive (VFD) applications.
FEATURESn Specially engineered cable design produces alonger cable life in VFD applications.
n Overall braid plus foil shield is engineered with 100% coverage and a surface transferimpedance <50 milliohms at 10MHz to contain EMI.
n Symmetrical insulated ground conductorsreduce induced voltage imbalances and carrycommon mode noise back to the drive.
n High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
n Gexol’s lower dielectric constant (standardXLPEs, EPRs and other Type RHW insulationmaterials have higher dielectric constants)reduces reflected wave peak voltagemagnitudes. This allows for longer outputcable distances and minimizes the effectof high frequency noise induced into the plantground system.
n 2kV insulation thickness is used to resist thepotential 2-3x reflected voltages experienced in 600V VFD applications.
n Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
n Flame retardant: IEC 332-3 Category A and IEEE 1202.
JacketA black, arctic grade, flameretardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1277.
Power Conductors (x3)Soft annealed flexible strandedtinned copper per IEEE 1580-2010 and UL 44.
ShieldOverall tinned copper braidplus aluminum/polyester tape providing 100% coverage.
Ratings & Approvalsn 90˚C Temperature Ratingn UL Listed as Type TC-ER (E123629) n Flame resistance: IEEE 1202/FT-4n Sunlight resistant
Ground Conductors (x3)Soft annealed flexiblestranded tinned copper perIEEE 1580 Table 11.Gexol® insulated andsized per UL 1277.Color: Green
Insulation (2kV)Gexol® cross-linked flameretardant polyolefin, meetingthe requirements for Type RHW.
Gexol® is a registered trademark of AmerCable Incorporated
17Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
37-102VFD • EXTRA FLEXIBLE VFD POWER CABLE • GEXOL® INSULATED
• Cable diameters are subject to a +/- 5% manufacturing tolerance• Ampacity In Free Air: Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table B.310.15(B)(2)(3)• Ampacity In Cable Tray: Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table 310.15(B)(16)• Ampacity In Raceway Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table B.310.15(B)(2)(1)*3 Grounding Conductors – Green Insulated
DC Resist. AC Resist. Inductive Green Size Nominal Weight @ 25°C @ 90°C, 60 Hz Reactance Voltage Drop Insulated In Single InAWG/ Size Part No. Diameter (Lbs./ (Ohms/ (Ohms/ (Ohms/ (Volts/Amp/ Grounding* Free Air Tray Conduit kcmil mm2 37-102 Inches* 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) (3x) (AWG) 90°C 75°C 90°C 75°C 90°C 75°C
4 21 -312VFD 1.100 925 0.300 0.376 0.030 0.551 12 114 101 95 84 89 79
2 34 -314VFD 1.235 1421 0.184 0.230 0.029 0.348 10 152 135 130 115 119 106
1 43 -315VFD 1.340 1517 0.147 0.184 0.029 0.285 10 177 157 150 133 137 121
1/0 54 -316VFD 1.450 1803 0.117 0.147 0.029 0.233 10 205 182 170 151 163 145
2/0 70 -317VFD 1.580 2120 0.093 0.117 0.028 0.192 10 237 210 195 173 186 165
4/0 109 -319VFD 1.900 3416 0.058 0.075 0.027 0.132 8 316 280 260 231 253 224
250 125 -330VFD 1.970 3955 0.050 0.064 0.027 0.117 8 351 311 290 257 276 245
262 132 -320VFD 2.050 4210 0.048 0.063 0.029 0.117 6 362 321 297 263 286 254
313 159 -321VFD 2.130 5105 0.040 0.053 0.028 0.102 6 401 356 328 291 320 284
350 178 -331VFD 2.260 5304 0.036 0.047 0.026 0.092 6 430 381 350 310 345 306
373 189 -322VFD 2.275 5521 0.033 0.044 0.028 0.090 6 449 398 364 323 357 317
444 227 -323VFD 2.425 6440 0.028 0.038 0.027 0.082 6 495 439 401 356 396 351
500 250 -333VFD 2.595 7272 0.025 0.034 0.026 0.074 6 531 471 430 381 427 379
535 273 -324VFD 2.643 7547 0.023 0.033 0.028 0.074 6 556 493 446 395 441 391
646 326 -326VFD 2.920 8916 0.020 0.028 0.027 0.067 6 615 545 492 436 486 431
750 379 -334VFD 3.020 10584 0.017 0.024 0.025 0.060 4 671 595 535 474 529 469
777 394 -327VFD 3.102 10671 0.016 0.025 0.027 0.062 4 688 610 546 484 537 476
NEC Ampacities
18 www.nexansamercable.com • e-mail: [email protected]
37-108VFD
FLEXIBLE TC-ERVFD POWER CABLEThree Conductor • 90°C • 1000V*
APPLICATIONA flexible, shielded power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications.
FEATURESn Specially engineered cable design produces a longer cable life in VFD applications.
n Overall shield provides 100% coverage containing VFD EMI emissions.
n Symmetrical ground conductors reduce inducedvoltage imbalances and carry common modenoise back to the drive.
n High strand count design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
n Meets crush and impact requirements for Type MC cable.
n AmerCable’s specially formulated insulationmaterial has a lower dielectric constant (standard XLPE and EPR insulation materials havehigher dielectric constants) which withstands reflected voltages. This allows for longeroutput cable distances and minimizes the effect of high frequency noise induced into the plant ground system.
n Permitted for Exposed Run (“ER”) use in accordance with the NEC.
n Permitted for use in Class I, Division 2 and Zone 2industrial hazardous locations per the NEC.
n Gas and vapor tight – impervious to water and air.
n Reduced tray fill (up to 35% less) than Type MC.
n Reduced installation time and cost compared to Type MC.
n Glands for this product cost up to 50% LESS than those for Type MC.
n Bend radius 12X O.D.
InsulationCross-linked, flexible, low dielectric constant compound rated 90°C.
Sizes larger than 4/0 AWG – individual conductors colored black with conductor number surface printed in contrasting ink.
Sizes 4/0 AWG and smaller – individually colored conductors – red, white,black.
JacketFlame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC). Colored black.
Power Conductors (x3)Soft annealed flexiblestranded tinned copperper ASTM B-33
SymmetricalGround Conductors (x3)Three symmetricallyplaced flexible stranded tinned copper conductors in directcontact with the shield.
Metallic ShieldSizes 8 AWG and Larger –Helically applied barecopper tape.
Sizes Smaller than8 AWG – tin-coatedcopper braid plusaluminum/polyester tape.
Both shielding systemsprovide 100% coverage.
TC-ER Ratings & Approvalsn UL Listed as Type TC-ER 600V
n UL Listed as 1000V flexible motor supply cable (up to 4/0 AWG)
n 90°C Temperature Rating
n FT-4 and IEEE 1202 flame ratingsn Sunlight resistantn Direct burial
*
*
19Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
• Cable diameters are subject to a +/- 5% manufacturing tolerance
• Ampacity In Free Air: Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table B.310.15(B)(2)(3)
• Ampacity In Cable Tray: Based on 90°C conductor temperature and 30°Cambient temperature per 2014 NEC Table 310.15(B)(16)
• Ampacity In Conduit: Based on 90°C conductor temperature and 30°C ambient temperature per 2014 NEC Table B.310.15(B)(2)(1)
37-108 VFD • FLEXIBLE TC-ER VFD • 1000 VOLTS
Equivalent Uninsulated Size Number Metric Size ConductorAWG/kcmil of Strands (mm2) Dia. (inches)
14121086421
1/02/04/0250262313350373444500535646750777
191937
133133259259259266323532627646777888925
111012211332159118501924
2.083.29 5.23 8.30
13.21 21.17
35 4350 66 95
125132150 178185240250273300379400
0.0740.093 0.113 0.1590.2010.2550.3210.3610.4130.4550.5840.6280.6540.7200.759 0.7850.8600.8950.9411.0291.1271.132
Stranding Profile
DC Resist. AC Resist. Inductive Green Size Nominal Weight @ 25°C @ 90°C, 60 Hz Reactance Voltage Drop Insulated In Single InAWG/ Size Part No. Diameter (Lbs./ (Ohms/ (Ohms/ (Ohms/ (Volts/Amp/ Grounding* Free Air Tray Conduit kcmil mm2 37-102 Inches* 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) 1000 Ft.) (3x) (AWG) 90°C 75°C 90°C 75°C 90°C 75°C
14 2.1 -508VFD 0.466 158 2.907 3.635 0.036 5.069 18 15 13 15 13 15 13
12 3.3 -516VFD 0.509 199 1.826 2.283 0.034 3.195 18 20 18 20 18 20 18
10 5.2 -308VFD 0.522 258 1.153 1.441 0.032 2.028 14 30 27 30 27 30 27
8 8.3 -309VFD 0.653 368 0.708 0.885 0.036 1.262 14 65 58 55 49 48 43
6 13.2 -310VFD 0.737 517 0.445 0.556 0.034 0.804 12 87 77 75 67 65 58
4 21 -312VFD 0.956 814 0.300 0.376 0.031 0.552 12 114 101 95 84 89 79
2 35 -314VFD 1.103 1178 0.184 0.230 0.030 0.349 10 152 135 130 115 119 106
1 43 -315VFD 1.221 1462 0.147 0.184 0.031 0.287 10 177 157 150 133 137 121
1/0 50 -316VFD 1.447 1714 0.117 0.147 0.030 0.235 10 205 182 170 151 163 145
2/0 66 -317VFD 1.538 1951 0.093 0.117 0.029 0.193 10 237 210 195 173 186 165
4/0 95 -319VFD 1.883 3102 0.058 0.075 0.028 0.133 8 316 280 260 231 253 224
250 126 -330VFD 1.930 3836 0.050 0.064 0.027 0.117 8 351 311 290 257 276 245
262 120 -320VFD 1.981 4338 0.048 0.063 0.026 0.114 6 362 321 297 263 286 254
313 150 -321VFD 2.082 4658 0.040 0.053 0.026 0.100 6 401 356 328 291 320 284
350 178 -331VFD 2.210 5141 0.036 0.047 0.026 0.092 6 430 381 350 310 345 306
373 185 -322VFD 2.334 5290 0.034 0.045 0.026 0.088 6 449 398 364 323 357 317
444 240 -323VFD 2.371 6177 0.028 0.039 0.026 0.079 6 495 439 401 356 396 351
500 250 -333VFD 2.545 6977 0.025 0.034 0.026 0.074 6 531 471 430 381 427 379
535 273 -324VFD 2.801 8044 0.024 0.033 0.025 0.071 6 556 493 446 395 441 391
646 300 -326VFD 2.893 9183 0.020 0.028 0.025 0.065 6 615 545 492 436 486 431
750 379 -334VFD 3.980 10051 0.017 0.024 0.025 0.060 4 671 595 535 474 529 469
777 400 -327VFD 3.165 10776 0.016 0.024 0.025 0.060 4 688 610 546 484 537 476
NEC Ampacities
CABLE SELECTION GUIDE FOR VFD APPLICATIONS
The circuit of a typical voltage source PWM drive is shown in Figure 1. Each part of the equipment is bondedto the safety earth system to ensure personnel safety if faults occur.
All parts have capacitance to ground shown by:
• CM for the motor windings.
• CC1 and CC2 for the power converter circuits.
• CT for the transformer’s secondarywinding to the transformers’ screen.
The IGBT switches are in constant operation at high frequency and this produces an inverter output voltage with a PWM wave shape as shown by the voltage V1(Figure 1).
This IGBT switches also cause a motor line to ground voltage V2 (Figure 1), normally called a common mode voltage.
The common mode voltages cause short high-frequency pulses of common modecurrent to flow in the safety earthcircuits, shown by currents I1 and I2 (Figure 1), unless the design includes cable features to stop this from happening.
It is essential that the common mode currents return to the inverter without causing EMC - EMI problems in other equipment, and this means that the common mode currents I1 and I2 must not flow in the safety earthing system.
For the motor, this is achieved by connecting a set of wires from the motor to the inverter that run withthe main power cables. These are called symmetrical grounding conductors, see Figure 2. These conductors have avery low impedance compared with the other return path via the safety earthing system.
The three symmetrical grounding conductors and overall shields are connected as shown in Figure 3. This 360° connection is essential.
The common mode currents I1 and I2 now flow in the symmetrical grounding conductors. This happens because the symmetricalgrounding conductors are close to the power conductors givinga low impedance route for the currents I1 and I2 compared withthe safety earthing system. As I1 and I2 flow near the power conductors this avoids creating external EMC - EMI problems.
F I G U R E 3
Figures 1 - 3 courtesy of Converteam
Manufactured by Nexans AmerCable • (870) 862-4919 • (800) 643-1516 • Fax (870) 862-961320
If symmetrical grounding conductors and an overall EMIshield are not used, EMC - EMI problems are very likely to occur.
For cables used with voltage source PWM drives, a number of features are required to ensure correct operation, avoid overheating and achieve longer service life.
The essential features of a mediumvoltage cable for PWM drives are :
• Insulation designed to withstandthe transients produced by the PWM
• Insulation with a dielectric constant no greater than 3.0 to minimize capacitance
• Voltage rating of 3x the operating voltage to prevent corona
• Three symmetrical grounding conductors. Some cables only have one grounding conductor. This is not acceptable as it produces circulating currents in the earth system
• Extremely fine strands to carry the harmonic currents without overheating (i.e. the inductance of fine stranded conductors is less than 7, 19, 37 strand conductors)
• Overall shield to stop the radiation of voltage EMI fields
• Correct termination at both ends
• Semi-conducting shield around each insulation layer (MMV only)
• Metallic layer around each semi-conducting shield to earth the semi-conducting shield(MMV only)
F I G U R E 2
www.nexansamercable.com • e-mail: [email protected] 21
Low-Smoke Halogen-Free and Fire Resistantconstructions available.
Contact your Nexans AmerCable rep.
22 www.nexansamercable.com • e-mail: [email protected]
37-105
TYPE MMV MEDIUM POWER CABLE (MV-105)Single Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 105°C APPLICATIONS
Nexans AmerCable medium voltagepower cables are recommended for use as feeder circuits, in electric utilitygenerating stations, for distributioncircuits, and for feeders or branchcircuits in industrial and commercialinstallations. Type MV cables may beinstalled in wet or dry locations,indoors or outdoors (exposed tosunlight), in any raceway orunderground duct, directly buried ifinstalled in a system with a groundingconductor in close proximity thatconforms with NEC Section250.4(A)(5), or messenger supported in industrial establishments and electric utilities.
FEATURESn These cables utilize flexible strandedconductors, braided shields and abraided armor (when armored) which make them very suitable forapplications involving repeated flexing and high vibration.
n These cables have a small minimumbending radius (6xOD forunarmored cables and 8xOD forarmored cables) for easy installation.
n Optional uninsulated groundingconductors sized per UL 1072.
n The increased flexibility of this cableallows for faster installation times.
Ratings & Approvals� UL Listed as Medium Voltage Cable (E116415)� Flame retardance: IEEE 1202 & IEC 60332� Sunlight Resistant� Cable Tray Use (Sizes 1/0 AWG and larger)� 105˚C Temperature Rating� Voltage Rating – 5kV to 15kV(25kV available on request)
Hawke Gland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-X Increased Safety
501/421 501/453/U “EExe” Explosion Proof 710 753 Class I, Div. 2 Class I, Div. 1 Class I, Zone 2 Class I, Zone 1 & 2 Flameproof 501/421 501/453/U “EExd” Zone 1 & 2 (2 liter or < enclosures) ICG 653/U (2 liter or > enclosures) Zone 1 & 2
Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1072.
Armor (optional)0.0126" bronze braid providing88% minimum coverage.
Sheath (optional)A black, arctic grade, flame retardant, oil, abrasion, chemical, and sunlight resistant thermosetting compound meeting UL 1072. Colored jackets for signifying different voltage levels is also available on special request (ie. yellow = 5kV, orange = 8kV and red = 15kV).
Metallic ShieldComposite shield consisting of0.0126" tinned copper braidedwith nylon providing 60%copper shielded coveragemeeting UL 1072. The nylon iscolored for easy phaseidentification (three conductor = black,blue, red) without the need toremove the shield to findan underlying colored tape.
Insulation ShieldSemi-conducting tape, with overlap, for fast and easy termination meeting UL 1072.
ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationExtruded thermosetting105°C Ethylene PropyleneRubber (EPR), meeting UL 1072.
JacketA black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1072. Colored jackets for signifying different voltage levels are also available on special request (ie. yellow = 5kV, orange = 8kV and red = 15kV).
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 23
Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
86421
1/02/03/04/0250262313350373444500535646750777
7.612.5213443547086
109126132159178189227250273326379394
-101MV-102MV-103MV-104MV-105MV-106MV-107MV-108MV-109MV-025MV-110MV-111MV-035MV-112MV-113MV-050MV-114MV-115MV-075MV-116MV
0.5870.6410.7230.7900.8240.9150.9911.0201.0871.1551.1671.2101.2901.3101.3691.4351.4501.5351.6151.632
205260349456522645797884
105312151266129316111683193521382248259830103066
1.2820.8220.5660.3610.2960.2450.2020.2780.1410.1300.1220.1080.1000.0950.0860.0810.0770.0700.0680.065
0.0540.0500.0440.0410.0400.0390.0380.0370.0350.0340.0340.0330.0330.0320.0320.0310.0310.0300.0300.030
93120160215250290330385445495509571615640715775807906
10001022
7499
130175205240275320375415427478515535596645672756835851
–––––218248289334371382428461480536581605680750767
0.7650.4360.2860.1750.1400.1110.0890.0700.0560.0480.0460.0380.0340.0320.0270.0240.0220.0190.0160.015
0.9570.5560.3760.2300.1840.1470.1170.0940.0750.0640.0630.0530.0470.0440.0380.0340.0330.0280.0240.025
SINGLE CONDUCTOR TYPE MMV MEDIUM VOLTAGE – 5KV, 100/133% INSULATION LEVEL
Ampacity
SINGLE CONDUCTOR TYPE MMV MEDIUM VOLTAGE – 8KV, 100% INSULATION LEVEL
Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0250262313350373444500535646750777
12.5213443547086
109126132159178189227250273326379394
-118MV-119MV-120MV-121MV-122MV-123MV-124MV-125MV-178MV-126MV-127MV-179MV-128MV-129MV-184MV-130MV-131MV-187MV-132MV
0.6870.7710.8740.9190.9751.0201.0691.1701.2051.2131.2831.3451.3501.4111.4901.4921.5831.6601.748
287392517594693809928
112812661282149516781720197722112298269130733246
0.8240.5670.3620.2980.2460.2030.1690.1420.0300.1230.1090.1010.0960.0870.0820.0780.0710.0690.066
0.0520.0460.0430.0420.0410.0390.0380.0360.0350.0350.0340.0340.0330.0330.0320.0320.0310.0310.030
125165215250290335385445495509567610634707765797905990
1011
100130170195225260300345380391437470487539580601668730743
––––
218251289334371382425458476530574598679743758
0.4360.2860.1750.1400.1110.0890.0700.0560.0480.0460.0380.0340.0320.0270.0240.0220.0190.0160.015
0.5560.3760.2300.1840.1470.1170.0940.0750.0640.0630.0530.0470.0440.0380.0340.0330.0280.0240.025
Ampacity
See page 25 forampacity notes.
24 www.nexansamercable.com • e-mail: [email protected]
SINGLE CONDUCTOR TYPE MMV MEDIUM VOLTAGE – 8KV, 133% INSULATION LEVEL
SINGLE CONDUCTOR TYPE MMV MEDIUM VOLTAGE – 15KV, 100% INSULATION LEVEL
37-105
TYPE MMV MEDIUM VOLTAGE CABLE (MV-105)Single Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 105°CAmpacity: Based on 105°C conductor temperature and 40°C ambient temperature
Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0250262313350373444500535646750777
12.5213443547086
109126132159178189227250273326379394
-134MV-135MV-136MV-137MV-138MV-139MV-140MV-141MV-125MV-142MV-143MV-189MV-144MV-145MV-190MV-146MV-147MV-191MV-148MV
0.7390.8230.9320.9711.0171.0731.1461.1911.2551.2651.3351.3851.3951.4611.5451.5891.6451.7731.790
321419570636725856992
115713201334155417261777204022852418267632453298
0.8260.5690.3650.3000.2470.2040.1710.1430.1340.1240.1100.1040.0970.0880.0830.0780.0720.0700.067
0.0540.0470.0450.0440.0420.0400.0390.0380.0370.0360.0350.0340.0340.0330.0330.0320.0320.0320.032
125165215250290335385445495509567610634707765797905990
1011
100130170195225260300345380391437470487539580601668730743
––––218251289334371382425458476530574598679743758
0.4360.2860.1750.1400.1110.0890.0700.0560.0480.0460.0380.0340.0320.0270.0240.0220.0190.0160.015
0.5560.3760.2300.1840.1470.1170.0940.0750.0640.0630.0530.0470.0450.0390.0340.0330.0280.0240.025
Ampacity
Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0250262313350373444500535646750777
3443547086
109126132159178189227250273326379394
-150MV-151MV-152MV-153MV-154MV-155MV-198MV-156MV-157MV-199MV-158MV-159MV-192MV-160MV-161MV-193MV-162MV
1.0041.0461.0931.1431.1921.2591.3451.3531.4001.4601.4701.5461.6101.6471.7401.8401.895
627705815925
1050123311661443162818191885217123722508282533473501
0.3690.3030.2510.2080.1740.1460.1370.1280.1130.1070.1000.0910.0870.0820.0750.0730.070
0.0490.0470.0450.0440.0420.0400.0400.0390.0380.0380.0370.0360.0360.0360.0350.0350.034
215250290335385445495509567610634707765797905990
1011
170195225260300345380391437539464580601668668730743
––
218251289334371382425458476530574598679743758
0.1750.1400.1110.0890.0700.0560.0480.0460.0380.0340.0320.0270.0240.0220.0190.0160.015
0.2300.1840.1470.1170.0940.0750.0640.0630.0530.0470.0440.0380.0340.0330.0280.0240.025
Ampacity
See page 25 forampacity notes.
25Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
SINGLE CONDUCTOR TYPE MMV MEDIUM VOLTAGE – 15KV, 133% INSULATION LEVEL
Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0250262313350373444500535646750777
3443547086
109126132159178189227250273326379394
-164MV-165MV-166MV-167MV-168MV-169MV-94MV
-170MV-171MV-195MV-172MV-173MV-196MV-174MV-175MV-197MV-176MV
1.0891.1251.1781.2301.2911.3571.4251.4341.4901.5451.5551.6151.7551.7551.8471.9451.969
701779886
10221162134011901535174319291977225025882675306835093608
0.3700.3050.2520.2090.1760.1480.1390.1290.1140.1080.1010.0930.0890.0840.0770.0740.071
0.0500.0490.0470.0450.0440.0420.0410.0400.0390.0390.0380.0380.0380.0370.0360.0360.035
215250290335385445495509567610634707765797905990
1011
170195225260300345380391437470487539580601668730743
––218251289334371382425458476530574598679743758
0.1750.1400.1110.0890.0700.0560.0480.0460.0380.0340.0320.0270.0240.0220.0190.0160.015
0.2300.1840.1470.1170.0940.0750.0640.0630.0530.0470.0440.0380.0340.0330.0280.0240.025
Ampacity
Notes:1) Ampacities in air are based on NEC 2014 Table 310.60(C)(69), Volts Ampacity column, for insulated singlecopper conductor isolated in air, maximum conductor temperature of 105°C, ambient air temperature of40°C.
2) Ampacities in Triangular Configuration are based on NEC 2014 Table 310.60(C)(67), Volts Ampacitycolumn, for insulated copper conductor cables isolated triplexed in air, maximum conductor temperature of105°C, ambient air temperature of 40°C.
3) Ampacities in cable tray are based on NEC 2014 Section 392.80(B)(2) and Table 310.60(C)(69), Ampacitycolumn, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
26 www.nexansamercable.com • e-mail: [email protected]
37-105
TYPE MMV MEDIUM POWER CABLE (MV-105)Three Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 105°C
APPLICATIONSNexans AmerCable medium voltagepower cables are recommended for use as feeder circuits, in electric utilitygenerating stations, for distributioncircuits, and for feeders or branchcircuits in industrial and commercialinstallations. Type MV cables may beinstalled in wet or dry locations,indoors or outdoors (exposed tosunlight), in any raceway orunderground duct, or messenger-supported in industrial establishmentsand electric utilities.Suitable for direct burial.*
FEATURESn These cables utilize flexible strandedconductors, braided shields and abraided armor (when armored) which make them very suitable forapplications involving repeated flexing and high vibration.
n These cables have a small minimumbending radius (6xOD forunarmored cables and 8xOD forarmored cables) for easy installation.
n Optional uninsulated groundingconductors sized per UL 1072.
n The increased flexibility of this cableallows for faster installation times.
Conductor ShieldA combination of semi-conducting tape andextruded thermosetting semi-conducting materialmeeting UL 1072.
Armor (optional)(Optional) 0.0126" bronze braid providing 88% minimum coverage.
JacketA black, arctic grade, flame retardant, oil, abrasion,chemical and sunlight resistant thermosettingcompound meeting UL 1072. Colored jackets forsignifying different voltage levels are also available onspecial request (ie. yellow = 5kV, orange = 8kV andred = 15kV).
Sheath (optional)A black, arctic grade, flame retardant, oil, abrasion,chemical, and sunlight resistant thermosettingcompound meeting UL 1072. Colored jackets forsignifying different voltage levels is also available onspecial request (ie. yellow = 5kV, orange = 8kV andred = 15kV).
Metallic ShieldComposite shield consisting of 0.0126" tinned copper braided with nylon providing 60% copper Shieldedcoverage meeting UL 1072. The nylon iscolored for easy phaseidentification (threeconductor = black, blue,red) without the need to remove the shield to find an underlying colored tape.
Insulation ShieldSemi-conducting tape, with overlap, for fastand easy termination meeting UL 1072.
ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationExtruded thermosetting105°C Ethylene PropyleneRubber (EPR), meeting UL 1072. Grounding Conductor (optional)
One uninsulated soft annealed flexible strandedtinned copper conductor per ASTM B 33 and sizedaccording to Table 21.1 of UL 1072.
Ratings & Approvals� UL Listed as Medium Voltage Cable (E116415)� Flame retardance: IEEE 1202 & IEC 60332� Sunlight Resistant� Cable Tray Use (Sizes 1/0 AWG and larger)� 105˚C Temperature Rating� Voltage Rating – 5kV to 15kV(25kV available on request)
Hawke Gland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-X Increased Safety
501/421 501/453/U “EExe” Explosion Proof 710 753 Class I, Div. 2 Class I, Div. 1 Class I, Zone 2 Class I, Zone 1 & 2 Flameproof 501/421 501/453/U “EExd” Zone 1 & 2 (2 liter or < enclosures) ICG 653/U (2 liter or > enclosures) Zone 1 & 2
*Cable with grounding conductor can be directly buried. Cable withoutgrounding conductor can be directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250.4(A)(5).
27Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Single Inductive Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
86421
1/02/03/04/0250262313350373444500535646750777
7.612.5213443547086
109126132159178189227250273326379394
-301MV-302MV-303MV-304MV-305MV-306MV-307MV-308MV-309MV-374MV-310MV-311MV-375MV-312MV-313MV-314MV-314MV-315MV-377MV-316MV
1.1761.2941.4691.6151.7461.8451.9962.0812.2222.3602.4102.4882.6402.6592.8923.0153.0503.2493.4003.458
722918
1252162019422257274431103714426344864599563458256946763180019274
1062510902
6688
115154180205240280320355365386409440456506545627685696
6384
109146171195228266304337347389418433481518537596651661
0.7650.4450.3000.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.0250.0230.0200.0170.016
0.9570.5560.3760.2300.1840.1460.1160.0920.0730.0620.0500.0450.0450.0420.0350.0310.0290.0240.0210.020
0.0480.0440.0390.0360.0350.0340.0330.0320.0310.0310.0300.0290.0290.0290.0280.0280.0280.0270.0270.027
1.2750.8150.5600.3560.2910.2390.1960.1630.1360.1270.1180.1040.0980.0920.0830.0790.0740.0670.0650.062
8666444332222111
1/01/01/02/0
THREECONDUCTORTYPE MMVMEDIUMVOLTAGE –5KV,100/133%INSULATIONLEVEL
Ampacity
THREECONDUCTORTYPE MMVMEDIUMVOLTAGE –8KV, 100%INSULATIONLEVEL
Single Inductive Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0250262313350373444500535646750777
12.5213443547086
109126132159178189227250273326379394
-317MV-318MV-319MV-320MV-321MV-322MV-323MV-324MV-378MV-325MV-326MV-379MV-327MV-328MV-380MV-329MV-330MV-381MV-331MV
1.3831.5741.7631.8611.9602.0772.1842.3372.4602.4932.6452.8252.8402.9813.1403.1563.3543.5053.583
10361378184021192442288033013943447145685318608962377150797582789660
1094311307
105135185210240275315360400411457490507559600620685745757
100128176200228261299342380390434466482531570589651708719
0.4450.3000.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.0250.0230.0200.0170.016
0.5560.3760.2300.1840.1460.1160.0920.0730.0620.0600.0500.0450.0420.0350.0310.0290.0240.0210.020
0.0460.0410.0380.0370.0360.0340.0330.0320.0320.0310.0300.0300.0300.0290.0290.0290.0280.0280.028
0.8180.5620.3570.2930.2410.1980.1650.1380.1290.1190.1050.0990.0930.0840.0800.0750.0680.0660.063
666444332222111
1/01/01/02/0
AmpacitySee page 29 forampacity notes
To order with Grounding Conductor, add G to Part Number
28 www.nexansamercable.com • e-mail: [email protected]
37-105
TYPE MMV MEDIUM VOLTAGE CABLE (MV-105)Three Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 105°CAmpacity: Based on 105°C conductor temperature and 40°C ambient temperature
THREECONDUCTORTYPE MMVMEDIUMVOLTAGE –8KV, 133%INSULATIONLEVEL
THREECONDUCTORTYPE MMVMEDIUMVOLTAGE –15KV, 100%INSULATIONLEVEL
Single Inductive Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0250262313350373444500535646
12.5213443547086
109126132159178189227250273326
-332MV-333MV-334MV-335MV-336MV-337MV-338MV-339MV-382MV-340MV-341MV-383MV-342MV-343MV-384MV-344MV-345MV
1.5041.7431.8891.9722.0712.1922.3032.4472.5712.6202.8192.9352.9553.0903.2553.3653.486
11661629207523012636308835244169471648545736636865377436830488699753
105135185210240275315360400411457490507559600620685
100128176200228261299342380390434466482531570589651
0.4450.3000.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.0250.0230.020
0.5560.3760.2300.1840.1460.1160.0920.0730.0620.0600.0500.0450.0420.0350.0310.0290.024
0.0480.0430.0400.0380.0370.0360.0350.0330.0330.0320.0320.0320.0310.0300.0300.0300.029
0.8200.5640.3590.2940.2420.1990.1660.1390.1300.1210.1060.1000.0940.0850.0810.0760.069
666444332322211
1/01/0
Ampacity
Single Inductive Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0250262313350373444500535
3443547086
109126132159178189227250273
-346MV-347MV-348MV-349MV-350MV-351MV-386MV-352MV-353MV-387MV-354MV-355MV-388MV-356MV
2.0432.1332.2352.3432.4492.5922.8202.8312.9583.0903.1053.2453.4003.491
23142599299233923838449045345449607867746977792887219248
185210240275315360400411457490507559600620
176200228261299342380390434466482531570589
0.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.0250.023
0.2300.1840.1460.1160.0920.0730.0620.0600.0500.0450.0420.0350.0310.029
0.0420.0400.0390.0370.0360.0350.0350.0340.0330.0330.0320.0310.0310.031
0.3610.2960.2440.2010.1680.1410.1320.1220.1070.1010.0950.0860.0820.077
6444332222111
1/0
Ampacity
Ordering Type MMV Medium VoltageCablesExample: • 3 conductor power cable • 15kV 100% • #2 AWG • Grounding Conductor
Nexans AmerCableType MMV Prefix
Specific CableNumber
(from charts)
Ground ConductorG – with groundBlank – no ground
37–105 – 346MV G
See page 27 forampacity notes
To order with Grounding Conductor, add G to Part Number
29Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
THREECONDUCTORTYPE MMVMEDIUMVOLTAGE –15KV, 133%INSULATIONLEVEL
Single Inductive Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0250262313350373444500535
3443547086
109126132159178189227250273
-357MV-358MV-359MV-360MV-361MV-362MV-391MV-363MV-364MV-392MV-365MV-366MV-393MV-367MV
2.2262.3042.4192.5292.6632.8673.0003.0333.1533.2653.2803.4233.5753.598
26552927332438094323513153635971660272587404840092599594
185210240275315360400411457490507559600620
176200228261299342380390434466482531570589
0.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.0250.023
0.2300.1840.1460.1160.0920.0730.0620.0600.0500.0450.0420.0350.0310.029
0.0440.0430.0410.0390.0380.0370.0360.0350.0340.0340.0340.0330.0330.033
0.3640.2990.2460.2030.1700.1420.1370.1240.1090.1030.0970.0880.0840.079
6444332222111
1/0
Ampacity
Closest Equivalent Uninsulated Size Number IEEE 45 Metric Size Conductor AWG/kcmil of Strands Std. Size (mm2) Dia. (inches)
86421
1/02/03/04/0250262313350373444500535646750777
1111
3761
133133209266342418532627646777888925
1110122113321591185019242745
1626416683
106133168212262262313373373444535535646777777
1111
7.57 12.49 21.11 33.51 41.94 53.3868.63 83.88
106.75 125.81129.63 155.91 178.19 185.61222.73 245.01 267.28 319.25371.22386.07561.94
0.134 0.173 0.257 0.324 0.3630.409 0.4640.5130.5790.629 0.6570.704 0.759 0.7650.8370.8950.9181.0101.0701.1071.375
MMV Stranding ProfileNotes:1) Ampacities in air are based on NEC2014 Table 310.60(C)(71), 2001-5000Volts Ampacity column, for insulated threeconductor copper cable isolated in air,maximum conductor temperature of105°C, ambient air temperature of 40°C.
2) Ampacities in cable tray are based onNEC 2014 Table 310.60(C)(75), 2001-5000 Volts Ampacity column, forinsulated three conductor copper cable inisolated conduit in air, maximumconductor temperature of 105°C, ambientair temperature of 40°C.
* Three conductor cables with 3 groundwires are also suitable for VFDapplications.
To order with Grounding Conductor, add G to Part Number
30 www.nexansamercable.com • e-mail: [email protected]
37-105VFD
TYPE MMV-VFDPOWER CABLE (MV-105)Three Conductor: 8kV –15kV • 133% Insulation Level • Rated 90°C
APPLICATIONSA flexible, braid and foil shielded,power cable specifically engineered for use in medium voltage variable frequency AC drive (VFD) applications.
FEATURESn Flexible stranded conductors andbraided shields. Suitable for applications involving repeated flexing and high vibration.
n Small minimum bending radius (8x OD) for easy installation.
n Insulation has a very low dielectricconstant. This allows for longeroutput cable distances andminimizes common mode current.
n Overall braid plus foil shield is engineered with 100% coverage anda surface transfer impedance <50milliohms at 10MHz to contain EMI.
n Symmetrical insulated ground conductors reduce induced voltageimbalances and carry common mode noise back to the drive.
n High strand count conductors andbraid shield design is much more flexible, easier to install and moreresistant to vibration than Type MC cable.
n Severe cold durability: exceeds CSA cold bend/cold impact (-40˚C/-35˚C).
Conductors (3)Soft annealed flexible strandedtinned copper per IEEE 1580 Table 11.
Conductor ShieldA combination of semi-conducting tape and extrudedthermosetting semi-conducting material meeting UL1072.
EMI ShieldOverall tinned copper braid plus aluminum/polyester tape provides 100% coverage.
JacketA black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1072. This jacket allows for isolation between the insulation shields and overall shield. Shields can then be terminated on opposite ends tominimize circulating currents.
Sheath (optional)A black, arctic grade, flame retardant, oil,abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1072.Colored jackets for signifying different voltage levels are also available on specialrequest (orange = 8kV and red = 15kV).
Insulation ShieldComposite shieldconsisting of 0.0126"tinned copper braidedwith nylon providing60% copper Shieldedcoverage meeting UL 1072. The nylon iscolored for easy phaseidentification (threeconductor = black,blue, red) without theneed to remove theshield to find anunderlying colored tape.
Insulation ShieldSemi-conducting layer meeting UL 1072.
InsulationExtruded thermosetting105°C EthylenePropylene Rubber (EPR),meeting UL 1072.
Symmetrical InsulatedGrounding Conductors (3)Soft annealed flexible stranded tinned copper conductor per IEEE 1580 Table 11. GexolInsulation sized per Table 23.2 of UL 1072.Color: Green
Ratings & Approvalsn UL Listed as Medium Voltage Cable (E116415)n Flame retardance: IEEE 1202 & IEC 60332n Sunlight Resistantn Cable Tray Use (Sizes 1/0 AWG and larger)n 105˚C Temperature Ratingn Voltage Rating – 5kV to 15kV (25kV available onrequest)
31Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
THREE CONDUCTOR TYPE MMV-VFD MEDIUM VOLTAGE8KV • 133% INSULATION LEVEL
Ampacity
Ampacity
THREE CONDUCTOR TYPE MMV-VFD MEDIUM VOLTAGE15KV • 133% INSULATION LEVEL
Ordering Type MMV-VFD Medium Voltage CablesExample: • 3 conductor MMV-VFD power cable • 15kV • #2 AWG
NexansAmerCable TypeMMV-VFD Prefix
Specific CableNumber (from
charts)
37–105 – 357VFDMVStranding Profile:See Page 29
Single Inductive Voltage Green Insulated Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop Grounding AWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (Ohms/ (Volts/Amp/ Conductor (3x) kcmil mm2 37-105 (Inches) 1000 Ft.) (Amps) (Amps) (Ohms/1000 Ft.) (Ohms/1000 Ft.) 1000 Ft.) 1000 Ft.) Size (AWG)
6421
1/02/03/04/0250262313350373444500535
12.5213443547086
109126132159178189227250273
-332VFDMV-333VFDMV-334VFDMV-335VFDMV-336VFDMV-337VFDMV-338VFDMV-339VFDMV-382VFDMV-340VFDMV-341VFDMV-383VFDMV-342VFDMV-343VFDMV-384VFDMV-344TVFDM
1430194523962728304335044148467552765423633170887147839290669746
1.5641.8021.9192.0282.1292.2482.3812.5322.6302.6802.8782.9903.0003.1633.3103.445
105135185210240275315360400411457490507559600620
100128176200228261299342380390434466482531570589
0.4450.3000.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.0250.023
0.5560.3760.2300.1840.1460.1160.0920.0730.0620.0600.0500.0450.0420.0350.0310.029
0.0480.0430.0400.0380.0370.0360.0350.0330.0330.0320.0320.0320.0310.0300.0300.030
0.8200.5640.3590.2940.2420.1990.1660.1390.1300.1210.1060.1000.0940.0850.0810.076
1010108886666664444
Single Inductive Voltage Green Insulated Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop Grounding AWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (Ohms/ (Volts/Amp/ Conductor (3x) kcmil mm2 37-105 (Inches) 1000 Ft.) (Amps) (Amps) (Ohms/1000 Ft.) (Ohms/1000 Ft.) 1000 Ft.) 1000 Ft.) Size (AWG)
21
1/02/03/04/0250262313350373444500
3443547086
109126132159178189227250
-357VFDMV-358VFDMV-359VFDMV-360VFDMV-361VFDMV-362VFDMV-391VFDMV-363VFDMV-364VFDMV-392VFDMV-365VFDMV-366VFDMV-393VFDMV
305333383830436651545738620166537360809285109223
10096
2.2842.3632.4782.6032.7932.9503.0583.1103.2383.3403.4153.4813.636
185210240275315360400411457490507559600
176200228261229342380390434466482531570
0.1840.1470.1170.0930.0740.0580.0500.0480.0400.0360.0330.0280.025
0.2300.1840.1460.1160.0920.0730.0620.0600.0500.0450.0420.0350.031
0.0440.0430.0410.0390.0380.0370.0360.0350.0340.0340.0340.0330.033
0.3640.2990.2460.2030.1700.1420.1330.1240.1090.1030.0970.0800.078
10888666666444
CORFLEX® is a registered trademark of Nexans
32 www.nexansamercable.com • e-mail: [email protected]
CORFLEX® MC-HL INSTRUMENTATION600V • PAIRS & TRIADS600V/1000V MARINE SHIPBOARD CABLERated 90°C • Single or Multiple Individually Shielded Pairs or Triads, Overall Cable Shield
Ratings & Approvals� 90˚C Temperature Rating� Meets UL 1309 and IEEE 1580 requirementsfor Marine Shipboard Cable
� Meets UL 1569 requirements for Type MC, Metal Clad cables
� Meets UL 2225 for Hazardous Locations� Designated Type MC as per NEC2008 and NEC 2011 Article 330
APPLICATIONCORFLEX® instrumentation cables minimize noise andsignal interference to enhance performance ininstrumentation, data flow, computer & data loggingapplications – especially in areas where high voltages orhigh currents are present.
FEATURES� UL listed as Marine Shipboard Cable (File E86139)600V/1000V
� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical trayfire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at210,000 BTU/hr, IEC 60332-3 category A fire test,IEEE 1202 and CSA FT4
� Cables are American Bureau of Shipping (ABS) listedas CWC MC Type MC
� Cables are marked “-40°C” and are suitable forhandling and installation down to -10°C (based on -40°C impactand bend tests per UL 1569)
� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugatedfor flexibility, prevents ingress of moisture, gases andliquids
� Aluminum armor resistance exceeds requirements ofthe NEC 2008 and NEC 2011 Article 250.178 forequipment grounding conductor
� Minimal noise and signal interference� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete
� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2008 and NEC 2011 (HL Rated)
BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter
ConductorBare, annealed copper conforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.
AssemblyPairs/triads are cabled in concentriclayers with interstices filled with suitablenon-hygroscopic fillers, as required. A binder tape of synthetic materialassembles the core in an essentiallyround configuration.
Conductor IDPairs: black/white &
number codedTriads: black/red/white &
number coded
ArmorContinuous corrugated andwelded, impervious aluminumsheath with no more than 0.2%trace copper providingcomplete protection againstliquid and gas ingress. Provides excellent mechanicalprotection, additionalelectrostatic shielding, andserves as an easy means forgrounding equipment.
InsulationFlame-retardant PVC, 15 milsnominal thickness, nylon jacket, 4mil nominal thickness. 90°C temperature rating, per UL Standard 66.
Insulation ShieldAluminum foil/polyester shieldhelically wrapped toprovide 100% coverage andtinned copper drain wire thatis two gauge sizes smallerthan the circuit conductors.These shields are electricallyisolated from each other.
Overall Cable ShieldAluminum foil/polyester shieldhelically wrapped to provide100% coverage. Tinned copperdrain wire that is the same sizeas the circuit conductors.
JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; low acid gas emission; limitedflame spread and excellentcorrosion resistance.
Inner JacketPolyvinyl chloride jacket, overcabled core as per UL1569,90°C temperature rating, withadditional resistance to flamespread. A rip cord is laidlongitudinally under thejacket to facilitate stripping.
33Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
NexansDesignNo.
654988654921654947654962665250662116
No.of
Pairs248121624
(inches)0.3190.3800.5170.6470.7311.016
(mils)404050505050
(inches)0.4050.4650.6210.7530.8371.124
(inches)0.5940.6330.8360.9761.1421.420
(mils)505050505050
(inches)0.6990.7350.9401.0801.2471.525
(lb/kft)2182573736218171427
Inner JacketThickness
Nominal DiameterOver Inner Jacket
Nominal DiameterOver Armor
Outer JacketThicknessPVC
(mils)151515151515
Nylon(mils)444444
Insulation Thickness Nominal DiameterOver Outer Jacket
Approx. NetCable Weight
Nominal DiameterOver Core
PAIRS WITH INDIVIDUAL AND OVERALL SHIELD • 600V – 18 AWG (7W)600V/1000V MARINE SHIPBOARD CABLE
PAIRS WITH INDIVIDUAL AND OVERALL SHIELD • 600V – 16 AWG (7W)600V/1000V MARINE SHIPBOARD CABLE
TRIADS WITH INDIVIDUAL AND OVERALL SHIELD • 600V – 16 AWG (7W)600V/1000V MARINE SHIPBOARD CABLE
ELECTRICAL PROPERTIES –PAIRS/TRIADS WITH INDIVIDUAL AND OVERALL CABLE SHIELD
Conductor Size(AWG)
DC Resistance(ohms/kft @ 20°C)
Conductor–Conductor(pf/ft)
Pairs
Capacitance
Triads
Conductor–Shield(pf/ft)
Conductor–Conductor(pf/ft)
Conductor–Shield(pf/ft)
1816
6.644.18
7486
148172
6387
156180
NexansDesignNo.
645390659052645291659078650796654889654905650788
No.of
Pairs124812162436
(inches)0.2090.4240.4820.6350.7970.8821.1241.312
(mils)4040505050505050
(inches)0.2930.4770.5330.6760.8350.9831.1261.370
(inches)0.4920.6390.7670.9261.1401.3201.4221.746
(mils)5050505050505060
(inches)0.6050.7440.8711.0301.2461.4311.5261.879
(lb/kft)157216375604862115114322121
Inner JacketThickness
Nominal DiameterOver Inner Jacket
Nominal DiameterOver Armor
Outer JacketThicknessPVC
(mils)1515151515151515
Nylon(mils)44444444
Insulation Thickness Nominal DiameterOver Outer Jacket
Approx. NetCable Weight
Nominal DiameterOver Core
NexansDesignNo.
654863644344670083670067
No.of
Triads14812
(inches)0.2250.4840.6800.820
(mils)40505050
(inches)0.3040.5870.7860.925
(inches)0.5070.7980.9981.212
(mils)50505050
(inches)0.6190.9001.1021.317
(lb/kft)1713004671007
Inner JacketThickness
Nominal DiameterOver Inner Jacket
Nominal DiameterOver Armor
Outer JacketThicknessPVC
(mils)15151515
Nylon(mils)4444
Insulation Thickness Nominal DiameterOver Outer Jacket
Approx. NetCable Weight
Nominal DiameterOver Core
34 www.nexansamercable.com • e-mail: [email protected]
CORFLEX® MC-HL ARMORED POWER & CONTROL600V • MULTI-CONDUCTOR600V/1000V MARINE SHIPBOARD CABLERated 90°C • Multi-Power Conductors with Bare Ground(s)
Ratings & Approvals� 90˚C Temperature Rating� Meets UL 1309 and IEEE 1580 requirementsfor Marine Shipboard Cable
� Meets UL 44, XHHW-2 600V conductors� Meets UL 1569 requirements for Type MC,Metal Clad cables
� Meets UL 2225 for Hazardous Locations (HL)� Dual certified IEEE 1580 and UL 1309 Type CWCMC
� Designated Type MC as per NEC 2008 andNEC 2011 Article 330
� Meets CSA C22.2 No. 123 for AluminumSheathed Cables
� Meets CSA C22.2 No. 174 for Hazardous Locations
APPLICATIONDesigned and constructed for the demandingenvironments of offshore drilling and petroleum facilities located throughout the world requiring a typeMC-HL cable.
FEATURES� UL listed as Marine Shipboard Cable (File E86139)600V/1000V
� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical trayfire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at210,000 BTU/hr, IEC 60332-3 category A fire test,IEEE 1202 and CSA FT4
� Cables are American Bureau of Shipping (ABS) listedas CWC MC Type MC
� Cables are marked “-40°C” and are suitable forhandling and installation down to -10°C (based on -40°C impact and bend tests per UL 1569)
� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugatedfor flexibility, prevents ingress of moisture, gases and liquids
� Aluminum armor resistance exceeds requirements ofthe NEC 2008 and NEC 2011 Article 250.178 forequipment grounding conductor
� Armor provides good EMI shielding so that CORFLEX can be used in certain instrumentation applications when adequately grounded
� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete
� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2008 and NEC 2011 (HL Rated)
BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter
ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.
AssemblyConductors are cabledin concentric layers withgrounding wire, intersticesare filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially roundconfiguration.
InsulationCross-linked polyethylenetype XHHW-2 per UL 44.
Grounding ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8. Meets or exceeds requirements of NECTable 250.122.
JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; low acid gas emission; limited flame spread andexcellent corrosion resistance.
ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.
CORFLEX® is a registered trademark of Nexans
Conductor IDMulti-conductor 14 AWG to 10 AWG: Method #1-E2 perICEA S-73-532
35Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
POWER & CONTROL • 600V600V/1000V MARINE SHIPBOARD CABLE
NexansDesignNo.
670155670142317677318345318352318360318378318386318394318402318410
670156670144317693318436318444318451318469318447318485318493318501
670157670146317719318527318535318543318550665148
23*45791215192537
23*45791215192537
23*45791237
(mils)3030303030303030303030
3030303030303030303030
3030303030303030
(inches)0.2730.3900.3360.3360.4170.4860.5610.6100.6690.7970.933
0.3450.3400.3850.4140.4780.5510.6390.6910.7600.8971.059
0.3610.4500.4490.4790.5560.6930.7451.227
(inches)0.4690.5550.5030.5320.6010.6450.7830.8110.9211.0051.218
0.5120.5550.5500.5990.6400.7770.8280.9360.9811.1901.374
0.5270.6200.6210.6410.7800.9370.9711.591
(mils)5050505050505050505050
5050505050505050505050
5050505050505060
Ω/kft2.55532.55532.55532.55532.55532.55532.55532.55532.55532.55532.5553
1.60821.60821.60821.60821.60821.60821.60821.60821.60821.60821.6082
1.01181.01181.01181.01181.01181.01181.01181.0118
InsulationThickness
NominalDiameterOver Core
NominalDiameter
Over ArmorJacket
Thickness(inches)0.5810.6600.6060.6350.7040.7480.8870.9151.0281.1111.323
0.6140.6600.6530.7020.7440.8810.9321.0391.0851.2951.478
0.6320.7250.7240.7430.8841.0401.0741.725
NominalDiameter
Over Jacket
DCResistance
20°C Ω/kft
2.60642.60642.60642.60642.60642.60642.60642.60642.60642.60642.6064
1.64041.64041.64041.64041.64041.64041.64041.64041.64041.64041.6404
1.03201.03201.03201.03201.03201.03201.03201.0320
DCResistance
25°C 60 Hz Ω/kft3.25833.25833.25833.25833.25833.25833.25833.25833.25833.25833.2583
2.05072.05072.05072.05072.05072.05072.05072.05072.05072.05072.0507
1.29021.29021.29021.29021.29021.29021.29021.2902
ACResistance
90°C Ω/kft@60Hz0.03760.03760.03760.04970.05450.05960.06410.06660.06940.07430.0787
0.03530.03530.03530.04750.05260.05740.06200.06440.06720.07190.0765
0.03320.03320.03320.04540.05070.05790.06010.0744
InductiveReactance
90°C Amps/kft2.94892.94892.94892.95422.95662.95852.96042.96152.96272.96492.9668
1.86101.86101.86101.86631.86851.87061.87261.87371.87491.87691.8789
1.17561.17561.17561.18091.18321.18641.18741.1936
VoltageDropVolts/
75°C15151515141410101098
2020202018181313131110
3030282825251814
90°C1515151515151313131110
2020202020201515151412
3030303028282016
(lb/kft)155200191212263307388443572691986
1852262392803384375026357439871365
2313123193644846307321984
Approx.Net CableWeightNo. of
Cond. kcmil14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)
12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)
10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)
ConductorSizeAWG/
AWG14(7w)3x18(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)14(7w)
12(7w)3x16(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)12(7w)
10(7w)3x14(7)10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)
GroundWireSize
Notes:1) Ampacities are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in raceway or direct buriedat 30°C ambient temperature and 90°C conductor temperature. The overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambienttemperature and number of conductors have been applied (NEC 2008 and NEC 2011 Article 240.4(D)). For correction factors fordifferent ambient temperatures and ampacities at different conductor temperatures, see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16). Ampacities for cables having more than three conductors have been derated per NEC 2008 Article 310.15(B)(2)(a)or NEC 2011 Article 310.15(B)(3)(a).
*Three conductor cables with 3 grounds are also suitable for VFD applications.
Ampacities(Note 1)
36 www.nexansamercable.com • e-mail: [email protected]
CORFLEX® MC-HL ARMORED COMPOSITE POWER & CONTROL • 600V • MULTI-CONDUCTOR600V/1000V MARINE SHIPBOARD CABLERated 90°C • 1 Bare Ground
Ratings & Approvals� 90˚C Temperature Rating� Meets UL 1309 and IEEE 1580 requirementsfor Marine Shipboard Cable
� Meets UL 44, XHHW-2 600V conductors� Meets UL 1569 requirements for Type MC,Metal Clad cables
� Meets UL 2225 for Hazardous Locations (HL)� Dual certified IEEE 1580 and UL 1309Type CWCMC
� Designated Type MC as per NEC 2008 andNEC 2011 Article 330
� Meets CSA C22.2 No. 123 for AluminumSheathed Cables
� Meets CSA C22.2 No. 174 for Hazardous Locations
APPLICATIONDesigned and constructed for the demandingenvironments of offshore drilling and petroleum facilitieslocated throughout the world requiring a type MC-HLcable.
FEATURES� UL listed as Marine Shipboard Cable (File E86139)600/1000V
� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical trayfire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at210,000 BTU/hr, IEC 60332-3 category A fire test,IEEE 1202 and CSA FT4
� Cables are American Bureau of Shipping (ABS) listedas CWC MC Type MC
� Cables are marked “-40°C” and are suitable forhandling and installation down to -10°C (based on -40°C impact and bend tests per UL 1569)
� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugatedfor flexibility, prevents ingress of moisture, gases and liquids
� Aluminum armor resistance exceeds requirements ofthe NEC 2008 and NEC 2011 Article 250.178 forequipment grounding conductor
� Armor provides good EMI shielding so that CORFLEXcan be used in certain instrumentation applicationswhen adequately grounded
� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete
� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2008 and NEC 2011 (HL Rated)
BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter
ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.
AssemblyConductors are cabledin concentric layers withgrounding wire, intersticesare filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially roundconfiguration.
InsulationCross-linked polyethylenetype XHHW-2 per UL 44.
Grounding ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.Meets or exceedsrequirements ofNEC Table 250.122.
JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; lowacid gas emission; limitedflame spread and excellentcorrosion resistance.
ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.
CORFLEX® is a registered trademark of Nexans
Conductor IDPower Conductors8 AWG and larger:Method #4 per ICEA S-73-532
Control Conductors14, 12 & 10 AWG:Method #1-E2 per ICEA S-73-532
37Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Notes:1) Ampacities are based on NEC 2011 Table 310.15(B)(16) for not more than three current-carrying conductors (where the 4th conductor is the neutral of a 3-phase, 4 wire system) in raceway, cable, or earth (direct buried), based on an ambient temperature of 30°C (86°F). Refer to Table 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F).
JacketThickness(mils)505050505050
505050505050
505050505050
505050505050
505050505050
75°C303030303030
505050505050
656565656565
858585858585
115115115115115115
90°C303030303030
555555555555
757575757575
959595959595
130130130130130130
ControlConductorsNo. x SizeAWG/kcmil
4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)
4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)
4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)
4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)
4x12(7w)3x12(7w)4x14(7w)3x14(7w)4x12(7w)4x14(7w)
NexansDesignNo.
199760665024665036665041665019665047
290783665025665037665042665020665048
290791665027665038665044665021665049
290809665028665039665045665022665050
654277665035665040665046665023665051
PowerConductorsNo. x SizeAWG/kcmil
3x10(7w)3x10(7w)3x10(7w)3x10(7w)4x10(7w)4x10(7w)
3x8(7w)3x8(7w)3x8(7w)3x8(7w)4x8(7w)4x8(7w)
3x6(7w)3x6(7w)3x6(7w)3x6(7w)4x6(7w)4x6(7w)
3x4(7w)3x4(7w)3x4(7w)3x4(7w)4x4(7w)4x4(7w)
3x2(7w)3x2(7w)3x2(7w)3x2(7w)4x2(7w)4x2(7w)
ControlInsulationThickness(mils)303030303030
303030303030
303030303030
303030303030
303030303030
PowerInsulationThickness(mils)303030303030
454545454545
454545454545
454545454545
454545454545
NominalDiameterOverArmor(in)
0.7720.7500.7540.6350.7820.777
0.9170.8000.8110.8000.9140.831
0.9750.9370.9410.9210.9580.938
1.1490.9640.9610.9871.0120.999
1.1681.1601.1281.1801.2141.214
NominalDiameterOverCore(in)
0.5400.4950.5100.4700.5600.550
0.6640.5900.6100.5910.6590.645
0.7500.6950.7000.6700.7250.695
0.8450.7350.7300.7700.8070.787
0.8700.8600.8200.8850.9270.927
NominalDiameterOverJacket(in)
0.8760.8540.8600.7380.8870.881
1.0260.9040.9150.9041.0240.935
1.0771.0411.0451.0281.0621.042
1.2541.0681.0651.0911.1171.103
1.2731.2651.2401.2851.3191.319
Ampacities(Note 1)
DCResist.
20C �/kft1.01181.01181.01181.01181.01181.0118
0.63610.63610.63610.63610.63610.6361
0.40020.40020.40020.40020.40020.4002
0.25160.25160.25160.25160.25160.2516
0.15740.15740.15740.15740.15740.1574
DCResist.
25C �/kft1.03201.03201.03201.03201.03201.0320
0.64880.64880.64880.64880.64880.6488
0.40820.40820.40820.40820.40820.4082
0.25660.25660.25660.25660.25660.2566
0.16050.16050.16050.16050.16050.1605
ACResist.
90C, 60 Hz�/kft
1.29021.29021.29021.29021.29021.2902
0.81110.81110.81110.81110.81110.8111
0.51040.51040.51040.51040.51040.5104
0.32090.32090.32090.32090.32090.3209
0.20090.20090.20090.20090.20090.2009
InductiveReactance90C, 60 Hz
�/kft0.03320.03320.03320.03320.03320.0332
0.03480.03480.03480.03480.03480.0348
0.03290.03290.03290.03290.03290.0329
0.03120.03120.03120.03120.03120.0312
0.02990.02990.02990.02990.02990.0299
VoltageDropVolts/
Amps/kft1.17561.17561.17561.17561.17561.1756
0.74520.74520.74520.74520.74520.7452
0.47370.47370.47370.47370.47370.4737
0.30250.30250.30250.30250.30250.3025
0.19380.19380.19380.19380.19380.1938
GroundWire SizeAWG
10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)
10(7w)10(7w)10(7w)10(7w)10(7w)10(7w)
8(7w)8(7w)8(7w)8(7w)8(7w)8(7w)
8(7w)8(7w)8(7w)8(7w)8(7w)8(7w)
6(7w)6(7w)6(7w)6(7w)6(7w)6(7w)
Approx.Net CableWeight(lbs/Kft)425396387340463428
565473478457630535
685665640641778749
926807799788993953
119811701165114614361401
COMPOSITE POWER & CONTROL • 600V600V/1000V MARINE SHIPBOARD CABLE
CORFLEX® MC-HL Power Cable • 600V600V/1000V Marine Shipboard CableRated 90°C • 3 and 4 Power Conductors with Ground(s)
Ratings & Approvals� 90˚C Temperature Rating� Meets UL 1309 and IEEE 1580 requirementsfor Marine Shipboard Cable
� Meets UL 44, XHHW-2 600V conductors� Meets UL 1569 requirements for Type MC,Metal Clad cables
� Meets UL 2225 for Hazardous Locations (HL)� Dual certified IEEE 1580 and UL 1309Type CWCMC
� Designated Types MC and MC-HL as per NEC2014 Articles 330, 501 and 505
� Meets CSA C22.2 No. 123 for AluminumSheathed Cables
� Meets CSA C22.2 No. 174 for Hazardous Locations
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleum facilities located throughout the world requiring a type MC-HL cable.
Features� UL listed as Marine Shipboard Cable (File E86139)600V/1000V
� UL listed as Type MC-HL, 600V (File E47409)� UL listed insulated conductors� Flame retardant: UL 1685 and IEEE 383 vertical trayfire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at210,000 BTU/hr, IEC 60332-3 category A fire test, IEEE1202 and CSA FT4
� Cables are marked “-40°C” and are suitable forhandling and installation down to -10°C (based on -40°C impactand bend tests per UL 1569)
� Temperature rating of 90°C dry and wet� 130°C emergency rating and 250°C short circuit rating� Continuous, impervious aluminum armor corrugated forflexibility, prevents ingress of moisture, gases and liquids
� Aluminum armor resistance exceeds requirements of theNEC 2014 Article 250.178 for equipment groundingconductor
� Excellent mechanical and physical properties� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete
� Three conductor cables have three symmetricalgrounding conductors suitable for PWM/VFD and othermodern AC drive/motor applications
� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2008 and NEC 2011 (HL Rated)
Bend Radius� Fixed position: 7X cable overall diameter� During pulling: 12X cable overall diameter
ConductorsBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.
AssemblyConductors are cabledin concentric layers withgrounding wire, intersticesare filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic materialassembles the core in an essentially roundconfiguration.
InsulationCross-linked polyethylenetype XHHW-2 per UL 44.
GroundingConductor(s)Bare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.Meets or exceedsrequirements of
JacketOverall black polyvinylchloride jacket per UL 1569,90°C temperature rating; low acid gas emission; limited flame spread and excellent corrosion resistance.
ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.
CORFLEX® is a registered trademark of Nexans
38 www.nexansamercable.com • e-mail: [email protected]
Conductor IDSizes 14 AWG to 2AWG:Method #1-E2 perICEA S-73-532
Sizes 1 AWG to 500kcmil: Method #4 perICEA S-73-532
39Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
NexansDesignNo.
670142317677670144317693670146317719670148317735670149317750670150317776670151317792670152698571670153317818670118317834670119660631670120317867670121670577670122317891670123317917
JacketThickness(mils)505050505050505050505050505050505050505060606060606060757575
75°C151520203030505065658585115115130130150150175175200200230230255255310310380380
90°C151520203030555575759595130130145145170170195195225225260260290290350350430430
Cond.SizeAWG/kcmil14(7w)14(7w)12(7w)12(7w)10(7w)10(7w)8(7w)8(7w)6(7w)6(7w)4(7w)4(7w)2(7w)2(7w)1(19w)1(19w)1/0(19w)1/0(19w)2/0(19w)2/0(19w)3/0(19w)3/0(19w)4/0(19w)4/0(19w)250(37w)250(37w)350(37w)350(37w)500(37w)500(37w)
No. ofCond.343434343434343434343434343434
InsulationThickness(mils)303030303030454545454545454555555555555555555555656565656565
NominalDiameterOverArmor(in)
0.5550.5030.5550.5490.6200.6200.7500.7950.8020.9300.9370.9951.1271.2141.2301.3611.3501.4271.4221.5981.6061.7301.7341.9361.9252.0122.0282.2302.3402.694
NominalDiameterOverCore(in)
0.3900.3360.3400.3960.4500.4500.5200.5850.6000.6800.7000.7820.8300.9270.9501.0411.0401.1341.1261.2381.2501.3561.3601.5001.4771.6531.6851.8891.9542.196
NominalDiameterOverJacket(in)
0.6600.6060.6600.6520.7250.7300.8380.9000.9051.0271.0391.0951.2321.3201.3201.4661.4731.5251.5101.7321.7391.8651.8672.0692.0582.1472.1622.3872.5042.861
Ampacities(Note 1)DC
Resist.20C �/kft2.55532.55531.60821.60821.01181.01180.63610.63610.40020.40020.25160.25160.15740.15740.12550.12550.09990.09990.07970.07910.06290.06270.04970.04970.04240.04240.03010.03010.02120.0212
DCResist.
25C �/kft2.60642.60641.64041.64041.03201.03200.64880.64880.40820.40820.25660.25660.16050.16050.12800.12800.10190.10190.08130.08060.06420.06400.05070.05070.04320.04320.03070.03070.02160.0216
ACResist.
90C, 60 Hz�/kft
3.25833.25832.05072.05071.29021.29020.81110.81110.51040.51040.32090.32090.20090.20090.16030.16030.12780.12780.10210.10110.08080.08040.06410.06410.05840.05840.03950.03950.02900.0282
InductiveReactance90C, 60 Hz
�/kft0.03760.03750.03530.03530.03320.03320.03480.03480.03290.03290.03120.03120.02990.02990.02880.02880.02810.02830.02800.02810.02750.02760.02710.02710.02630.02640.02630.02630.02500.0251
VoltageDropVolts/
Amps/kft2.94892.93071.86101.85101.17561.17580.74520.74720.47370.47370.30250.30240.19380.19380.15680.15670.12720.12690.10410.10330.08470.08440.06950.06940.06080.06070.04700.04680.03670.0363
GroundWire SizeAWG
3x18(7w)1x14(7w)3x16(7w)1x12(7w)3x14(7w)1x10(7w)3x14(7w)1x10(7w)3x12(7w)1x8(7w)3x12(7w)1x8(7w)3x10(7w)1x6(7w)3x10(7w)1x6(7w)3x10(7w)1x6(7w)3x10(7w)1x6(7w)3x8(7w)1x4(7w)3x8(7w)1x4(7w)3x8(7w)1x4(7w)3x6(7w)1x3(7w)3x6(7w)1x2(7w)
Approx.Net CableWeight(lbs/Kft)200191226245312320413465542675735892109713321330162815921922188223932400297529103605331641104375561760267892
POWER CABLE • 600V600V/1000V MARINE SHIPBOARD CABLE
Notes:1) Ampacities are based on NEC 2011 Table 310.15(B)(16) for not more than three current-carrying conductors (where the 4th conductor is theneutral of a 3-phase, 4 wire system) in raceway, cable, or earth (direct buried), based on an ambient temperature of 30°C (86°F). Refer toTable 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F).
2) Three conductor cables with 3 ground wires are also suitable for VFD applications.
CORFLEX® is a registered trademark of Nexans
40 www.nexansamercable.com • e-mail: [email protected]
CORFLEX® MV-105 OR MC-HL MEDIUM VOLTAGE5KV 133% INSULATION LEVEL8KV 100% INSULATION LEVELRated 105°C • 3 Conductors with 3 Bare Grounds
APPLICATIONDesigned and constructed for the demandingenvironments of offshore drilling and petroleum facilitieslocated throughout the world requiring a type MV-105 orMC-HL Medium Voltage cable.
FEATURES� UL listed as Marine Shipboard Cable (File E86139)� UL listed as Type MV-105 5kV and 8kV (File E66901)� Flame retardant: UL 1685 and IEEE 383 vertical trayfire tests at 70,000 BTU/hr, IEC 60332-3 category Afire test, IEEE 1202 and CSA FT4
� Cables are American Bureau of Shipping (ABS) listedas CWC MC Type MV/MC (Metal Clad, Medium Voltage)
� Cables are marked “-40°C” and are suitable forhandling and installation down to -10°C (based on -40°C impactand bend tests per UL 1569)
� Continuous, impervious aluminum armor corrugatedfor flexibility, prevents ingress of moisture, gases and liquids
� Aluminum armor resistance exceeds requirements ofthe NEC 2008 and NEC 2011 Article 250.178 forequipment grounding conductor
� Excellent mechanical and physical properties� Minimal noise and signal interference� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete
� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2008 and NEC 2011 (HL Rated)
� Three symmetrical grounding conductors for PWM/VFDand other modern AC drive/motor applications
� Phase identification: Color coded (black, red, blue)polyester ribbon laid longitudinally under the coppershield tape
BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter
InsulationEPR meets or exceeds electrical and physicalrequirements of UL 1072.
Conductor ShieldExtruded semiconductingconductor shield meetsor exceeds electrical andphysical requirementsof UL 1072.
Insulation ShieldNonmetallicExtruded semiconductinginsulation shield meetsor exceeds electricaland physical requirementsof UL 1072.
Metallic ShieldBare copper tape shieldhelically wrapped toprovide 100% coverage.
ConductorBare, annealed copperconforming to ASTM B3 and Class B Compactstranded in accordance with ASTM B496.
JacketOverall yellow polyvinylchloride jacket per UL 1072,90°C temperature rating; low acid gas emission; limitedflame spread and excellentcorrosion resistance.
ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.
Binder TapeSynthetic materialassembles the core inan essentially roundconfiguration.
Ratings & Approvals� 105˚C Temperature Rating� Meets UL 1309 and IEEE 1580 requirementsfor Marine Shipboard Cable
� Meets UL 1072 requirements for mediumvoltage power cables
� Meets UL 1569 requirements for Type MC, Metal Clad cables
� Meets UL 2225 for Hazardous Locations (MC-HL)� Designated Type MC as per NEC 2008 andNEC 2011 Article 330
� Insulation meets electrical and physical requirementsof ICEA S-93-639/NEMA WC 74 and UL 1072
� Designated Type MV-105 as per NEC 2008 andNEC 2011 Article 328
GroundingConductorsBare, annealed copperconforming to ASTM B3and Class B stranded inaccordance with ASTM B8.
41Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
5KV • 133% INSULATION LEVEL • EPR INSULATION: 90 MILS
NexansPartNo.
662776665017660072660648662186670667670669665029660075660076660349665014
JacketThickness(mils)506060606060606075758585
Cond.SizeAWG/kcmil6(7w)4(7w)2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)750(58w)1000(58w)
GroundWireSizeAWG3 x 103 x 103 x 103 x 83 x 83 x 83 x 63 x 63 x 63 x 43 x 43 x 4
NominalDiameterOver
Insulation(in)
0.4260.4700.5250.5560.5930.6340.7330.7860.8841.0451.1861.339
NominalDiameterOverArmor(in)
1.3721.5421.6311.7311.9051.9482.1032.2402.4592.7793.3663.505
NominalDiameterOverJacket(in)
1.4771.6781.7651.8642.0472.0812.2402.3872.6232.9463.5653.687
InAir
Note 1105135185210240275360400490600745860
CableTray
Note 292120165185215245320350430525635725
DirectBurialNote 3120155200225255290375410495590720810
DCResist.
20C �/kft0.40080.25200.15850.12600.09990.07920.04980.04220.03020.02110.01410.0106
DCResist.
25C �/kft0.40880.25700.16160.12850.10190.08080.05080.04310.03080.02150.01440.0108
ACResist.
90C, 60 Hz�/kft
0.51110.32130.20220.16070.12750.10120.06390.05430.03920.02810.01960.0159
InductiveReactance90C, 60 Hz
�/kft0.04600.04270.04000.03870.03740.03610.03380.03320.03120.03040.02920.0283
VoltageDropVolts/
Amps/kft0.48010.30780.19940.16160.13110.10690.07230.06340.04920.03860.03060.0266
AmpacitiesNominalDiameterOver
Core (in)1.0661.1621.2981.3681.4481.5341.7491.8652.0762.3352.7313.063
Approx.Net CableWeight(lbs/Kft)11021402177320922389268036734181536373231029212871
8KV • 100% INSULATION LEVEL • EPR INSULATION: 115 MILS
Notes:1) Ampacities in air are based on NEC 2011 Table 310.60(C)(71), 5001-35,000 Volts Ampacity column, for insulated three conductor coppercable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
2) Ampacities in cable tray are based on NEC 2011 Table 310.60(C)(75), 5001-35,000 Volts Ampacity column, for insulated three conductorcopper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
3) Ampacities for direct burial are based on NEC 2011 Table 310.60(C)(83), 5001-35,000 Volts Ampacity column, for insulatedthree conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperatureof 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.
* Three conductor cables with 3 ground wires are also suitable for VFD applications.
Notes:1) Ampacities in air are based on NEC 2011 Table 310.60(C)(71), 2001-5000 Volts Ampacity column, for insulated three conductorcopper cable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
2) Ampacities in cable tray are based on NEC 2011 Table 310.60(C)(75), 2001-5000 Volts Ampacity column, for insulated three conductor copper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
3) Ampacities for direct burial are based on NEC 2011 Table 310.60(C)(83), 2001-5000 Volts Ampacity column, for insulated three conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperatureof 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.
* Three conductor cables with 3 ground wires are also suitable for VFD applications.
NexansPartNo.
603837603838603839603840603841603842603843603844603845603846603847603848
JacketThickness(mils)505060606060606075758585
Cond.SizeAWG/kcmil6(7w)4(7w)2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)750(58w)1000(58w)
GroundWireSizeAWG3 x 103 x 103 x 103 x 83 x 83 x 83 x 63 x 63 x 63 x 43 x 43 x 4
NominalDiameterOver
Insulation(in)
0.3860.4300.4850.5170.5540.5940.6930.7470.8440.9651.1471.299
NominalDiameterOverArmor(in)
1.3111.3791.5641.6081.7041.8062.0042.1152.3502.6943.1943.464
NominalDiameterOverJacket(in)
1.4271.4841.6981.7411.8381.9392.1382.2492.5142.8603.3763.663
InAir
Note 188115154180205240320355440545685790
CableTray
Note 277100135155185210285315390475585660
DirectBurialNote 3115150190215245280360395475570700785
DCResist.
20C �/kft0.40080.25200.15850.12600.09990.07920.04980.04220.03020.02110.01410.0106
DCResist.
25C �/kft0.40880.25700.16160.12850.10190.08080.05080.04310.03080.02150.01440.0108
ACResist.
90C, 60 Hz�/kft
0.51110.32130.20220.16080.12750.10130.06400.05440.03930.02820.01990.0160
InductiveReactance90C, 60 Hz
�/kft0.04470.04090.03080.03680.03560.03450.03240.03190.03060.02940.02750.0283
VoltageDropVolts/
Amps/kft0.47920.30710.19860.19080.13030.10620.07170.06290.04870.03820.03030.0264
AmpacitiesNominalDiameterOver
Core (in)0.9811.0761.1951.2621.3451.4321.6461.7061.9732.2332.6282.958
Approx.Net CableWeight(lbs/Kft)1058123416231877216324733435389450817000983712951
CORFLEX® is a registered trademark of Nexans
42 www.nexansamercable.com • e-mail: [email protected]
CORFLEX® MV-105 OR MC-HL MEDIUM VOLTAGE15KV 100% INSULATION LEVEL & 133% INSULATION LEVELRated 105°C • 3 Conductors with 1 Bare Ground
Ratings & Approvals� 105˚C Temperature Rating� Meets UL 1309 and IEEE 1580 requirementsfor Marine Shipboard Cable
� Meets UL 1072 requirements for mediumvoltage power cables
� Meets UL 1569 requirements for Type MC, Metal Clad cables
� Meets UL 2225 for Hazardous Locations (MC-HL)� Designated Type MC as per NEC 2008 andNEC 2011 Article 330
� Insulation meets electrical and physical requirementsof ICEA S-93-639/NEMA WC 74 and UL 1072
� Designated Type MV-105 as per NEC 2008 andNEC 2011 Article 328
APPLICATIONDesigned and constructed for the demandingenvironments of offshore drilling and petroleum facilitieslocated throughout the world requiring a type MV-105 or MC-HL Medium Voltage cable.
FEATURES� UL listed as Marine Shipboard Cable (File E86139)� UL listed as Type MV-105 15 kV (File E66901)� Flame retardant: UL 1685 and IEEE 383 vertical trayfire tests at 70,000 BTU/hr, IEC 60332-3 category Afire test, IEEE 1202 and CSA FT4
� Cables are American Bureau of Shipping (ABS) listedas CWC MC Type MV/MC (Metal Clad, MediumVoltage)
� Cables are marked “-40°C” and are suitable forhandling and installation down to -10°C (based on -40°C impact and bend tests per UL 1569)
� Continuous, impervious aluminum armor corrugatedfor flexibility, prevents ingress of moisture, gases and liquids
� Aluminum armor resistance exceeds requirements ofthe NEC 2008 and NEC 2011 Article 250.178 forequipment grounding conductor
� Excellent mechanical and physical properties� Minimal noise and signal interference� Sunlight resistant jacket� Suitable for direct burial, use in cable tray and embedment in concrete
� Suitable for Class I, II and III, Divisions 1 & 2 as per NEC 2008 and NEC 2011 (HL Rated)
� Phase identification: Color coded (black, red, blue)polyester ribbon laid longitudinally under the coppershield tape
BEND RADIUS� Fixed position: 7 x cable overall diameter� During pulling: 12 x cable overall diameter
JacketOverall red polyvinylchloride jacket per UL 1072,90°C temperature rating; low acid gas emission; limitedflame spread and excellentcorrosion resistance.
InsulationEPR meets or exceeds electricaland physical requirements ofUL 1072.
Conductor ShieldExtruded semiconductingconductor shield meetsor exceeds electrical andphysical requirementsof UL 1072.
Metallic ShieldBare copper tape shieldhelically wrapped toprovide 100% coverage.
Binder TapeSynthetic materialassembles the core inan essentially roundconfiguration.
Insulation ShieldNonmetallicExtruded semiconductinginsulation shield meetsor exceeds electricaland physical requirementsof UL 1072.
ConductorBare, annealed copperconforming to ASTM B3 and Class B Compactstranded in accordance with ASTM B496.
ArmorContinuous corrugated and welded, imperviousaluminum sheath withno more than 0.2% tracecopper providing completeprotection against liquidand gas ingress. Providesexcellent mechanicalprotection, additionalelectrostatic shielding,and serves as an easymeans for groundingequipment.
Grounding ConductorBare, annealed copperconforming to ASTM B3 and Class B stranded inaccordance with ASTM B8.
43Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
15KV • 100% INSULATION LEVEL
15KV • 133% INSULATION LEVEL
NexansDesignNo.
664931664933664934664935664936664676664677664678664679
JacketThickness(mils)606060607575758585
InAir
Note 1185210240275360400490600745
CableTray
Note 2165185215245320350430525635
DirectBurialNote 3200225255290375410495590720
Cond.SizeAWG/kcmil2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)750(58w)
GroundWireSizeAWG644432211/0
NominalDiameterOver
Insulation(in)
0.6550.6790.7160.7560.8560.9101.0071.1281.310
NominalDiameterOverArmor(in)
1.9741.9962.0362.1542.4262.4902.7843.1853.480
NominalDiameterOverJacket(in)
2.1072.1292.1712.2892.5892.6532.9693.3673.671
AmpacitiesDC
Resist.20C �/kft0.15850.12600.09990.07920.04980.04220.03020.02110.0141
DCResist.
25C �/kft0.16160.12850.10190.08080.05080.04310.03080.02150.0144
ACResist.
90C, 60 Hz�/kft
0.20220.16070.12750.10120.06390.05430.03920.02800.0196
InductiveReactance90C, 60 Hz
�/kft0.04450.04280.04120.03980.03710.03630.03460.03300.0314
VoltageDropVolts/
Amps/kft0.20130.16330.13270.10850.07370.06470.05030.03960.0313
NominalDiameterOver
Core (in)1.5861.6311.7111.8002.0142.1312.3422.6072.999
Approx.Net CableWeight(lbs/Kft)2121236026302987407845995985778910716
Notes:1) Ampacities in air are based on NEC 2011 Table 310.60(C)(71), 5001-35,000 Volts Ampacity column, for insulated three conductor coppercable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
2) Ampacities in cable tray are based on NEC 2011 Table 310.60(C)(75), 5001-35,000 Volts Ampacity column, for insulated three conductorcopper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
3) Ampacities for direct burial applications are based on NEC 2011 Table 310.60(C)(83), 5001-35,000 Volts Ampacity column, for insulatedthree conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperature of 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.
NexansDesignNo.
665006665007665008665005665010665011665012665013
JacketThickness(mils)6060606075758585
InAir
Note 1185210240275360400490600
CableTray
Note 2165185215245320350430525
DirectBurialNote 3200225255290375410495590
Cond.SizeAWG/kcmil2(7w)1(18w)1/0(18w)2/0(18w)4/0(18w)250(36w)350(36w)500(36w)
GroundWireSizeAWG64443221
NominalDiameterOver
Insulation(in)
0.7350.7660.8030.8440.9430.9961.0941.215
NominalDiameterOverArmor(in)
2.0942.1772.2992.3622.6812.7683.1543.387
NominalDiameterOverJacket(in)
2.2352.3112.4422.4962.8532.9403.3363.575
AmpacitiesDC
Resist.20C �/kft0.15850.12600.09990.07920.04980.04220.03020.0211
DCResist.
25C �/kft0.16160.12850.10190.08080.05080.04310.03080.0215
ACResist.
90C, 60 Hz�/kft
0.20220.16070.12750.10120.06390.05430.03920.0280
InductiveReactance90C, 60 Hz
�/kft0.04680.04540.04370.04210.03910.03820.03630.0345
VoltageDropVolts/
Amps/kft0.20240.16440.13380.10950.07460.06550.05100.0402
NominalDiameterOver
Core (in)1.7401.8221.9021.9892.2032.3182.5282.792
Approx.Net CableWeight(lbs/Kft)22512616295632704546510663968209
Notes:1) Ampacities in air are based on NEC 2011 Table 310.60(C)(71), 5001-35,000 Volts Ampacity column, for insulated three conductor coppercable isolated in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
2) Ampacities in cable tray are based on NEC 2011 Table 310.60(C)(75), 5001-35,000 Volts Ampacity column, for insulated three conductorcopper cable in isolated conduit in air, maximum conductor temperature of 105°C, ambient air temperature of 40°C.
3) Ampacities for direct burial applications are based on NEC 2011 Table 310.60(C)(83), 5001-35,000 Volts Ampacity column, for insulatedthree conductor copper cable, directly buried, maximum conductor temperature of 105°C, ambient earth temperature of 20°C, 100 percent load factor, earth thermal resistivity of 90°C cm / W.
44 www.nexansamercable.com • e-mail: [email protected]
CORFLEX® PULLING INSTRUCTIONSCertain installations require thepulling of CORFLEX® into ducts ortrays. These installations requirecareful planning and execution. The following provides informationon how to calculate tensionsdeveloped during pulling andwhat precautions to take to prevent damage to the cable.
Pulling TensionThe maximum tension applied to acable is limited to prevent damageor distortion of cable componentswhich could reduce the life orreliability of the cable. The methodof pulling is significant in thatdifferent methods will resultin different stresses on critical cablecomponents for the same overalltension. Nexans AmerCablerecommends that CORFLEX MC-HLInstrumentation 600V cables arepulled by means of the aluminumsheath and jacket with a grip applied over the jacketed core,sheath and overall jacket. All otherCORFLEX cable types described in this catalog should be pulled by means of the conductors, aided with a grip over the outeraluminum sheath. The conductorsand the sheath must be pulledtogether. Maximum allowablepulling tensions for CORFLEX cablesshould never exceed the valuesshown in pulling tension table.
Calculating Pulling TensionsThe tension developed in anyStraight Section of duct iscalculated as:
T = L x W x f lbf whereL = section length (feet)W = cable weight per unit length
(lb/foot)f = coefficient of dynamic friction
The tension developed in any Bend is calculated as:T = T1 x efa lbf whereT1 = tension at bend entrance (lbf)e = base of natural logarithms
(2.71828)f = coefficient of dynamic frictiona = angle of bend (radians)or efa is given in the following tablefor common conditions:BendAngle f=0.15 f=0.30 f=0.35 f=0.40
30° 1.08 1.17 1.20 1.2345° 1.13 1.27 1.32 1.3760° 1.17 1.37 1.44 1.5290° 1.27 1.60 1.73 1.88
Coefficients of dynamic friction withlubricant are given in the followingtable for common duct and cablejacket materials. These coefficientscan be used for calculation oftensions.
CoefficientDuct Type Cable Jacket of Friction
PVC PVC 0.50PE PVC 0.30Fiber PVC 0.40
Asbestos Cement PVC 0.70
Considerations must be given toSide Wall Bearing Pressure (SWBP)when pulling CORFLEX through abend. The SWBP is calculated asfollows:
For CORFLEX, Nexans AmerCablerecommends a maximum SWBPof 500 pounds force/foot. Duringinstallation of the CORFLEX cable, itis recommended that the bend radiibe as noted in thecable descriptions.
Pulling in DuctIt is extremely important for thesuccess of any pull in duct to useapproved lubricants. Lubricants mustbe compatible with the cable jacketand duct material. Lubricating thepulling rope will decrease the tensionon the pulling equipment and moreimportantly will reduce the risk ofdamage to the inside of the ductwhich in turn can damage the cable.When designing the duct layout, it is suggested that the bends beconcentrated near the end fromwhich the cable is to be pulled. Thispractice will result in lower tensions.In some cases, the tensions resultingfrom alternative directions should be calculated.
Pulling in Trays & TrenchesFor the installation of CORFLEX intrays, rollers are normally used.Using well lubricated rollers and long radius sheaves at bends willresult in a lower coefficient of friction when compared to duct. A coefficient of friction of 0.15 canbe used when calculating pullingtension using rollers. For long pullswith bends it may be necessary toinstall assist pullers before the bends
to reduce the tension on thecable entering a bend andreducing the risk of damage from excessive SWBP.
The recommendations given aboveare intended to cover a wide varietyof pulling conditions. It is possible,under ideal conditions, and withexperienced supervision, to exceedthese limits.
For further guidance, see IEEE Paper84 T & D 365-3, orcontact Nexans AmerCable.
SWBP = Pulling Tension Cable at Bend Exit (lbf)Radius of Bend (feet)
45Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
CORFLEX® is a registered trademark of Nexans
CORFLEX® CONDUCTOR ID
Conductor Insulation Stripe Conductor Insulation Stripe
1st BLACK – 19th ORANGE Blue
2nd RED – 20th YELLOW Blue
3rd BLUE – 21st BROWN Blue
4th ORANGE – 22nd BLACK Orange
5th YELLOW – 23rd RED Orange
6th BROWN – 24th BLUE Orange
7th RED Black 25th YELLOW Orange
8th BLUE Black 26th BROWN Orange
9th ORANGE Black 27th BLACK Yellow
10th YELLOW Black 28th RED Yellow
11th BROWN Black 29th BLUE Yellow
12th BLACK Red 30th ORANGE Yellow
13th BLUE Red 31st BROWN Yellow
14th ORANGE Red 32nd BLACK Brown
15th YELLOW Red 33rd RED Brown
16th BROWN Red 34th BLUE Brown
17th BLACK Blue 35th ORANGE Brown
18th RED Blue 36th YELLOW Brown
Method #1-E2 per ICEA S-73-532
Method 4 of ICEA S-73-532
Conductor Printing Details Conductor Printing Details
1st “1-ONE-1” 5th “5-FIVE-5”
2nd “2-TWO-2” 6th “6-SIX-6”
3rd “3-THREE-3” 7th “7-SEVEN-7”
4th “4-FOUR-4” 8th “8-EIGHT-8”
46 www.nexansamercable.com • e-mail: [email protected]
37-XXX
TYPE RHH OR RHW-22000 VOLTS POWER & CONTROL • 90°CLimited Smoke (Sizes 2/0 and higher) • EP/CPE
APPLICATIONType RHH or RHW-2 2000 Volt Power andControl Cables are recommended for generalpower and control applications. These cablesmay be used in generating plants, substationsand industrial plants. Type RHH or RHW-2 maybe used up to 90°C in dry or wet locations. Thesecables may be installed in wet or dry locations,indoors or outdoors, in raceways, undergroundducts, cable tray (size 1/0 AWG and larger perNEC 392) or lashed to a messenger for aerialinstallation.
FEATURESn A two layer composite of flame retardant, oil and sunlight resistant ChlorinatedPolyethylene (CPE) outer layer and Ethylene-Propylene rubber (EPR) inner layer. The composite design provides significant diameter reductions compared to designs usingfull thickness jackets.
n Suitable for continuous operating temperatures of 90°C, wet or dry
n Rated RHH, RHW-2; 1/0 AWG and largerlisted and marked “for CT use”
n UL listed as Sunlight Resistant
n Insulation and jacket meet hazardous waste regulations, per Code of FederalRegulations 40 Section 261 (40CFR261) for characteristic lead content
n Flame Resistance: FT-4/IEEE1202 for sizes1/0 AWG and larger; UL VW-1
n Meets smoke release and other requirements of Vertical Cable Tray Test UL 1685 and is marked “ST-1” for 2/0 – 1111 kcmil
InsulationEthylene-Propylene rubber(EPR)
JacketFlame retardant, oil and sunlight resistant Chlorinated Polyethylene (CPE)
See belowfor jacket
color options(Special order)
ConductorBare, annealed copperconforming to ASTM B3and Class B stranded, inaccordance with ASTM B8
SeparatorSuitable separator tape provides easy stripping of insulation
Ratings & Approvals
n ICEA S-95-658/NEMA WC-70: Nonshielded Power Cables Rated 2000 Volts or Less for the Distribution ofElectrical Energy
n UL Standard 44: Thermoset Insulated Wires & Cables, Types RHH, RHW-2. UL VW-1
n UL Standard 1685: Vertical Tray Fire propagation and Smoke Release Test for Electrical and optical Fiber Cables. (UL,ST-1)
n MSHA P-184
n RoHS Compliant
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
37-XXX • TYPE RHH OR RHW-2 2000 VOLTS POWER AND CONTROL
TBD 14 7 0.045 0.015 0.213 31 35 TBD 12 7 0.045 0.015 0.232 41 40 TBD 10 7 0.045 0.015 0.261 58 55 TBD 8 7 0.055 0.030 0.336 94 80 TBD 6 7 0.055 0.030 0.373 131 105 TBD 4 7 0.055 0.030 0.42 188 140 TBD 2 7 0.055 0.030 0.478 275 190 TBD 1 19 0.065 0.045 0.567 359 220 TBD 1/0 19 0.065 0.045 0.606 435 260 TBD 2/0 19 0.065 0.045 0.651 532 300 TBD 3/0 19 0.065 0.045 0.701 652 350 TBD 4/0 19 0.065 0.045 0.757 802 405 TBD 250 37 0.075 0.065 0.866 972 455 TBD 350 37 0.075 0.065 0.966 1317 570 TBD 500 37 0.075 0.065 1.094 1819 700 TBD 750 61 0.090 0.065 1.309 2699 885*Ampacity – Calculated with at 90°C conductor
temperature and 30°C ambient air,per 2014 NEC Table 310.15(B)(17)
• Cable diameters are subject to +/-5%manufacturing tolerance
Approx.Weightlbs. per1,000 ft.
*Ampacity90°C
Part No.37-XXX-
SizeAWG/kcmil
MinimumWires perConductor
NominalInsulationThickness
in.
NominalJacket
Thickness in.
NominalOutside Diameter
in.
SAVETIME
SAVEMONEY
47
Order Your RHH or RHW-2 Cable with
Factory InstalledConnectors
WHAT CAN YOU EXPECT FROM NEXANSAMERCABLE?
■ High-Quality Cable with an Emphasis on Safety
■ On-Time Delivery
■ Professional Sales, Support and Service
■ Strategic Inventory Locations
■ Short Lead Times
4_16© 2016, AmerCable Incorporated
10633 West Little York • Building #1 • Suite #150 • Houston, TX 77041 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 • e-mail: [email protected]
www.nexansamercable.com
Nexans TrayCables
Cables for wet ordry locations incable trays,
raceways, open airor direct burial
NEXANS AMERCABLE’S DOWNSTREAM CABLE PRODUCTS
NexansInstrumentation
Cables300V & 600V Pairs
and Triads
CORFLEXType MC-HLCables
Industrial CIRCrush and ImpactResistant cableswithout external
armoring
Industrial VFDFoil shielded,power cables
engineered for usein variable
frequency AC driveapplications.
Available in severalconstructions
Nexans AmerCable is the leading global manufacturer of jacketed power, control and instrumentation cables for harsh industrial environments.
Nexans AmerCable is an ISO 9001 certifiedcable manufacturer that combines leading-edge technology, proven manufacturingtechniquesand high quality service to deliver the finestcable products available.
Our professional field engineering and customer supportteams work directly with customers or in partnership with a network of independent distributors to deliverproductivity enhancing cable solutions for downstream facilities.