power circuit breakers

31
1 1 Power Circuit Breakers Theory and Operation 2 Agenda Breaker fundamentals Types of Breakers – Ratings Design Tests Application & Operations Application Considerations Operation Considerations

Upload: mohammedsaadanihassani

Post on 13-Nov-2014

2.600 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: Power Circuit Breakers

1

1

Power Circuit Breakers

Theory and Operation

2

AgendaBreaker fundamentals– Types of Breakers– Ratings– Design Tests

Application & Operations– Application Considerations– Operation Considerations

Page 2: Power Circuit Breakers

2

3

Introduction

What does a breaker do?Circuit interruptionTypes of breakers

4

Power Circuit BreakersWaits for current zero to extinguish arc

Typical interrupting times 3-8 cycles

Attempts to prevent arc re-ignition (The interrupter must build up dielectric faster than the recovery voltage builds up)

Commutes plasma by removing energy which is in the form of heat

Page 3: Power Circuit Breakers

3

5

Power Circuit Breakers

The ability of the breaker to interrupt fault current is determined by two things:– the magnitude of the fault current– the magnitude and rate of rise of the voltage

across the contacts after the current goes out (both 60 hertz and transient voltages)

6

InterruptersArcing Contacts and medium (oil or gas) flow

Page 4: Power Circuit Breakers

4

7

Oil Interrupters:

I

Current zeros

Recoveryvoltage

t

Arc goes out

8

Types of Breakers:

OilAir blastAir magneticSF6 gasVacuumOthers

Page 5: Power Circuit Breakers

5

9

Circuit Breaker Year of Manufacture

0

20

40

60

80

100

120

140

1923

1949

1954

1959

1964

1969

1974

1979

1984

1989

1994

1999

Year

Num

ber airblast

vacuumairmagSF6OCB

10

Interrupting MediumsOil – Mineral oil is used to extinguish the arc and to

insulate the live parts to ground– Generally free breathing– May use a single tank or multiple tanks

Air Blast– Stored air is used to blow out the arc and cool

contacts– Very loud operation

Page 6: Power Circuit Breakers

6

11

InterruptersOil

12

InterruptersOil

Page 7: Power Circuit Breakers

7

13

Oil Breaker (Westinghouse 345G)

14

Oil Breaker(McGraw Edison CG38)

Page 8: Power Circuit Breakers

8

15

Interrupting Mediums

Air Magnetic – A magnetic field is place perpendicular to the

plane of the arc which drives the arc into insulating fins

– Sensitive to moisture– Compact

SF6 (Sulfur Hexa-flouride gas)– Multi-pressure or puffer operation– High speed

16

InterruptersAir Magnetic

Arcing Contacts

InsulatingFins

MagneticField

Page 9: Power Circuit Breakers

9

17

InterruptersSF6 Gas

18

Puffer Interrupter

Page 10: Power Circuit Breakers

10

19

Self-Blast Interrupter

20

Gas Breaker (ABB PM)

Page 11: Power Circuit Breakers

11

21

Gas Breaker (Westinghouse SP)

22

Gas Breaker (ABB PM)

Page 12: Power Circuit Breakers

12

23

Interrupting Mediums

Vacuum – Contacts incased in a sealed bottle which is under

vacuum– Compact

Others– Gas mixtures (N2, SF6 etc.)– Water– Solid State– Super-conductor???

24

Vacuum

Page 13: Power Circuit Breakers

13

25

Vacuum (GE PVDB-1)

26

Ratings

ContinuousInterruptingClose & latch – momentaryVoltage ratingsSwitching scenarios

Page 14: Power Circuit Breakers

14

27

Power Circuit Breaker Ratings

28

Power Circuit Breaker RatingsContinuous (load current)…typically 600,1200, 2000 or 3000 amperesANSI C37.04 Definition: The established limit of current in rms amps at rated frequency that it shall be required to carry continuously without exceeding temperature limits of its components.Select a breaker with a Continuous Current rating greater than the peak load current.

Page 15: Power Circuit Breakers

15

29

Power Circuit Breaker Ratings

30

Power Circuit Breaker Ratings

Interrupting Rating (fault current)…typically 20, 31.5, 40, or 63 kilo-amperesANSI C37.04 Definition: The highest value of the symmetrical component of the three-phase, short-circuit current in rms amps that the circuit breaker shall be required to interrupt at rated maximum voltage and on the standard operating duty.Select a breaker with a fault duty greater than the maximum available fault current.

Page 16: Power Circuit Breakers

16

31

Power Circuit Breaker Ratings

Cannot forget X/R!Standards assume X/R < 17.What do you do if X/R > 17?Delay opening.Increase kA interrupting requirements for the breaker.

32

Power Circuit Breaker Ratings

K Factor: Applies only to OCBs.Defined as the ratio of the rated maximum voltage to the lower limit of the range of operating voltage.The interrupting capabilities are inversely proportional to the operating voltage (i.e. a reduced voltage results in an increase in the current interrupting capability).Reference Engineering Manual Section 2 SI 4.0 –Application Guideline – AC High Voltage Circuit Breakers Based on Short Circuit Capability Criteria.

Page 17: Power Circuit Breakers

17

33

Power Circuit Breaker RatingsClose and Latch rating is expressed as a multiple of the rated short-circuit current.The maximum current for which the breaker will close and latch….stay closed.2.6 x rated short circuit current (Interrupting not Momentary).

34

Power Circuit Breaker RatingsRated Maximum Voltage is the highest rmsphase-to-phase voltage for which the circuit breaker is designed.The upper limit for operation.Typically 15kV, 84kV (25kV, 38kV, 46kV and 69kV), 145kV, 245kV, 362kV and 550kV

Page 18: Power Circuit Breakers

18

35

Power Circuit Breaker RatingsBasic Impulse Level (BIL) ,expressed in kV, is the maximum electrical impulse level (lightning strike) that the breaker can be exposed to and not flashover either internally or externally.Actual design BIL does not reflect the maximum impulse that can be generated because the magnitude of the impulse depends on the location of the strike.The designed BIL reflects the insulation coordination practices used in the design of electrical systems (Source: High Voltage Circuit Breakers: Design and Applications)

36

Power Circuit Breaker Ratings

A circuit breaker is a tie between two networks

Source Load

Source Load

TRV

Page 19: Power Circuit Breakers

19

37

Fault: faultV=0

TRV

v

t

Fault

i

Breaker opens

2 per unitTransient Recovery

Voltage

z

38

Power Circuit Breaker Ratings

The ability of the breaker to interrupt fault current is determined by the magnitude of the fault current and also by the rate of rise of the voltage across the breaker contacts as it opensTransient Recovery Voltage (TRV): is the transient voltage that appears across the contacts while interrupting a faulted circuit.

Page 20: Power Circuit Breakers

20

39

Transient Recovery Voltage:

t

V

TRVline = 1 - cos t/sqrtLC

Total TRV = bus - line

Initial Rate of rise Crest recovery

voltage

TRV

fault

TRVbus = 1 - cos t/sqrtLC

bus line

Time in hundreds of microseconds

40

Power Circuit Breaker Ratings

Standard C37.011 defines the TRV envelope that breakers must meet for rated current (Maximum TRV per standards is 2.4 per unit of rated breaker voltage)

Page 21: Power Circuit Breakers

21

41

42

Power Circuit Breaker Ratings

Some breakers were able to clear bus faults with no problem but were unable to interrupt faults a short distance out on the line even though the fault current was less than the bus fault. The cause of this becomes clear when the transient recovery voltage is analyzed for both scenarios:

Page 22: Power Circuit Breakers

22

43

Power Circuit Breaker Ratings

Short Line Fault: A fault that occurs a relatively short distance downstream from the circuit breaker on its load side.Also known as a kilometric fault since this is generally considered to be the critical distance for maximum severity of the recovery voltage. Allegheny specifies full nameplate interrupting for a 90% short line fault

44

Vbus

TRV= Vbus - Vline

TRV

Vbus Vline

Short Line Fault:

Vline

Page 23: Power Circuit Breakers

23

45

t

V

Fault i

Very steep rate of rise for TRV caused by the short length of the transmission line

TRV

46

t

V

Fault i

Adding shunt capacitance attenuates the rise

Page 24: Power Circuit Breakers

24

47

TRV= Vbus - Vline

TRV

Vbus Vline

Short Line Fault:Insert bushing shunt capacitance on line side

48

Bushing shunt capacitance

Page 25: Power Circuit Breakers

25

49

Power Circuit Breaker Ratings

50

Short Line Fault:– SF6 breakers up to 50 kA don’t require external

shunt bushing capacitors. – Most breakers rated at 63 kA require external

shunt bushing capacitors to meet Short Line Fault requirements of the standards.

– Mainly breakers above 100 kV.

Power Circuit Breaker Ratings

Page 26: Power Circuit Breakers

26

51

Power Circuit Breaker Ratings

1200pf, 3000pf and 12,000pf are typical values for external bushing capacitors.

52

Power Circuit Breaker Ratings

Operating Duty Cycle: A series of circuit breaker operations and time delays.Defined by ANSI as:O-15 SEC-CO-3 MIN.-CO.The first time delay can be reduced to 0.3 seconds for breakers designed for high-speed reclosing.0.3 seconds is the mechanical resetting time.

Page 27: Power Circuit Breakers

27

53

Power Circuit Breaker Ratings

A derating factor R is applied to OCBsbased on their reclosing duty.This does not apply to SF6 breakers.

54

Power Circuit Breaker Ratings

Asymmetrical Current Rating: Maximum RMS current, at rated frequency, including DC component against which the breaker is required to operate.Function of the system X/RStandards assume X/R of 17

Page 28: Power Circuit Breakers

28

55

Power Circuit Breaker Ratings

Momentary Rating:– Short time current rating– The current, equal to the rated symmetrical

short circuit current, that the breaker is required to carry for a specified time.

– Time = Allowable Tripping Delay

56

Application of Circuit Breakers

Page 29: Power Circuit Breakers

29

57

Switching Surges:

Z0= L/C

Voltage doubles when closing in on an open line = 2 P.U. at open line terminal

Assume that High Speed Re-closing traps a negative 1 P.U. charge on the line. Then when the breaker re-closes the maximum voltage at the open end can approach a maximum of 3.5 - 4.0 P.U. for multiple reflections depending on damping (R):

Trapped charge = -1.0 P.U.

3.5 P.U.

58

Breaker Applications

Closing resistors are used to reduce the switching surge created at the far end of a transmission line when it is energized– Once breaker is closed the resistor is

removed from the circuit.– Not designed to handle continuous load

current or fault current.– AP uses closing resistors on EHV breakers– Typical value: 400-450 ohms.

Page 30: Power Circuit Breakers

30

59

Closing resistors:

Z0= L/CRc

Rc

Z0 V0

Z0

(Rc + Z0)V0 = VS

bypass

VS

60

Z0 V0

Z0 (Rc + Z0)

V0R first close

V0B second close

Rc > Z0

V0R first close

V0B second close

Rc < Z0

Rc

V0R first close = V02 second close

Rc = Z0

2.0 P.U.

2.0 P.U.

2.0 P.U.Optimum closing resistor size = surge impedance

Closing resistors:

V0 = VS

Page 31: Power Circuit Breakers

31

61

Breaker Applications

Grading capacitors.– Applied on circuit breakers with more than one

gap per pole– Grading capacitors are applied across the

contacts of each interrupter to divide the recovery voltage during interruption

– Insures that the first gap to interrupt does not see the whole TRV

62

500kv PM breaker

Grading capacitors