power cable systems
TRANSCRIPT
-
7/26/2019 Power Cable Systems
1/35
KZ 3144
Power Cable systems
-
7/26/2019 Power Cable Systems
2/35
Introduction
A cable is defined as a single conductor or an assembly ofconductors covered by solid electrical insulation.
Cable specification generally starts with the conductor andprogress radically through the insulation and covering.
-
7/26/2019 Power Cable Systems
3/35
Introduction
The following is a typical list of specifications:
Number of conductors in cable
Conductor size and material
Insulation type
Shielding system
Outer finishes (sheath)
Insulation
Alternatively cables are specified by its ampacity, voltage,
frequency and other important system data
-
7/26/2019 Power Cable Systems
4/35
Cable construction
Conductors
The two conductor materials in common use are copper and
aluminum.
Copper is used for conductors of insulated cables primarily
for its desirable electrical and mechanical properties.
The use of aluminum is based mainly on its favorable
conductivity to weight ratio, availability and stable low cost.
-
7/26/2019 Power Cable Systems
5/35
Copper vs Aluminum
Copper-Advantages
Copper has a higher conductivity than aluminum.
It is more ductile (can be drawn out).
Copper has relatively high tensile strength (the greatest stress asubstance can bear along its length without tearing apart).
It can also be easily soldered.
Copper-Disadvantages
However, copper is more expensive and heavier than aluminum.
-
7/26/2019 Power Cable Systems
6/35
Copper vs Aluminum
Aluminum-Disadvantages
Compared to copper, aluminum has worse conductivity per unitvolume, but better conductivity per unit weight. In many cases, weightis more important than volume making aluminum the 'best' conductor
material for certain applications. For example, it is commonly used forlarge-scale power distribution conductors such as overhead powerlines.
Aluminum-Adantages
Although aluminum has only about 60 percent of the conductivity ofcopper, its lightness makes long spans possible.
Its relatively large diameter for a given conductivity reduces corona.
-
7/26/2019 Power Cable Systems
7/35
Cable construction
Classes of conductors
Conductors are classified as solid or standard. A solid conductor
is a single conductor of solid circular section.
A standard conductor is composed of a group of small
conductors in common contacts.
A standard conductor is used where the solid conductor is too
large and not flexible enough to be handled readily.
-
7/26/2019 Power Cable Systems
8/35
Cable construction
Conductor size Conductor sizes are ordinarily expresses by two different
numbering methods: the AWG and the circular mil.
The AWG conductor sizes are numbered from 30 to 1, then
continuing with 0, 00, 000, 0000.
Conductors larger than 4/0 AWG are designated in circular
mils.
A circular mil is defined as the area of a circle having a diameter
of 1/1000 of an inch.
-
7/26/2019 Power Cable Systems
9/35
Insulations
In general, current-carrying conductors must not beallowed to come in contact with one another, theirsupporting hardware, or personnel working nearthem.
To accomplish this, conductors are coated orwrapped with various materials, commonly knownas insulating materials.
Two fundamental properties of insulating areinsulation resistance and dielectric strength
-
7/26/2019 Power Cable Systems
10/35
Cable construction: Insulation
INSULATION RESISTANCE Insulation resistance is the resistance to current leakage through the insulation
materials. Insulation resistance can be measured with a megger withoutdamaging the insulation. Information so obtained is a useful guide in appraisingthe general condition of insulation. Clean, dry insulation having cracks or otherfaults may show a high value of insulation resistance but would not be suitablefor use.
DIELECTRIC STRENGTH
Dielectric strength is the ability of an insulator to withstand potentialdifference. It is usually expressed in terms of the voltage at which the insulationfails because of the electrostatic stress. Maximum dielectric strength values canbe measured only by raising the voltage of a TEST SAMPLE until the insulationbreaks down
-
7/26/2019 Power Cable Systems
11/35
Cable construction-: insulation
Insulations can be classified as solid, taped or special purposeinsulations. The following is a list of insulations commonly
used:
Thermosetting compounds (solid dielectric)
Thermoplastic compounds (solid dielectric)
Paper laminated tapes
Varnished cloth laminated tapes
Mineral inorganic insulation (solid dielectric granular)
-
7/26/2019 Power Cable Systems
12/35
Cable construction-: insulation
Insulations in general use for voltages above 2 KV:Thermosetting compounds (solid dielectric)
Cross linked polyethylene (XLP or XLPE)
Ethylene propylene rubber (EPR)
Styrene butadiene rubber (SBR) Silicon rubber, oil base rubber
Thermoplastic compounds (solid dielectric)
Polyethylene (natural)
Polyvinyl chloride (PVC)Paper laminated tapes
Varnished cloth laminated tapes
-
7/26/2019 Power Cable Systems
13/35
Cable construction-: Shielding
Insulation shielding is required for all non matallic, sheathed,single (> 2KV) and all metallic sheathed cables (> 5KV) :
Shielding confines the electric field of the cable to the insulationsurrounding the conductor by means of conducting or semi
conducting layer.
There are many purposes of shielding Confine the electric field within the cable Equalize the voltage stress within the insulation Protect cable from induced potentials Limit electromagnetic and electrostatic interference Reduce shock hazard
-
7/26/2019 Power Cable Systems
14/35
Cable construction-: Outer finishes
Cable outer coverings are used to protect the underlying cablecomponents from the environmental and installation conditionsassociated with intended service.
The choice of cable outer finishes for a particular application is
based on Electrical Thermal Mechnical considerations.
Combinations of metallic and non metallic finishes are usuallyrequired to provide the total protection needed for the installationand operation.
-
7/26/2019 Power Cable Systems
15/35
Cable Rating and Selection Criteria
The selection of power cables involves the consideration ofvarious electrical and environmental conditions including:
Quantity of power distributed
Degree of exposure to adverse mechanical and thermal stresses.
The selection of conductor size is based on the following criteria
Voltage rating
Load current criteria
Emergency overload criteria Voltage drop limitations
Fault current criteria.
-
7/26/2019 Power Cable Systems
16/35
Cable Selection: Voltage rating
The selection of power cables insulation (voltage) rating is basedon the phase to phase voltage of the system, system type(grounded or non grounded) and the time in which a ground faultis cleared by the protective equipment.
Ungrounded cable system must have greater insulation thicknessthan the cable used on a grounded system.
100% voltage rated cables are applicable to grounded system(clearing time 1 min).
133% voltage rated cable are applicable to ungrounded system(clearing time 1 hour)
-
7/26/2019 Power Cable Systems
17/35
Cable Selection: Load current criteria
The manufacturers ampacity recommendation should be used asload current criteria.
Ampacity tables indicates the minimum size conductor required.
Conservative engineering practice, future load growth, voltagedrop, short circuit consideration may requires the use of largerconductor
Other considerations to be honored in load current criteria are:
Skin and proximity effect
Ambient temperature
Surrounding medium
-
7/26/2019 Power Cable Systems
18/35
Cable Selection: Emergency overload
criteria
The nominal loading limits of insulated cables are determinedbased on many years of practical experience. These limits accountfor a rate of insulation deterioration that results in the useful lifeof cable system.
The life of cable insulation may be and the average thermalfailure rate almost doubles for each 5 to 15 degree increase innormal daily load temperature.
Maximum emergency overload temperatures for various types ofinsulation can be found in practical guides.
Operation at these emergency overload temperatures should notexceed 100 hours / year and such 100 hour period should notexceed five during the life of the cable.
-
7/26/2019 Power Cable Systems
19/35
Cable Selection: Voltage drop
The supply conductor, if not of sufficient size, will causeexcessive voltage drop in the circuit, and the drop will be in
direct preposion to the circuit length.
Proper starting and running of motors, lighting equipment,
and other loads having heavy inrush current must be
considered.
It is recommended that the steady state voltage drop in
distribution feeders be no more than 5%.
-
7/26/2019 Power Cable Systems
20/35
Cable Selection: Fault current criteria
Under short circuit conditions the temperature of the conductorrises rapidly then, due to the thermal characteristics of theinsulation,sheath, and surrounding materials, it cools off slowlyafter the short circuit is cleared.
A transient temperature limit for each type of insulation for shortcircuit duration not in excess of 10 sec has been established andmany times this criterion is used to determine mimimumconductor size.
IPCEA standard defines the maximum conductor temperaturelimits allowable under worst case fault condition.
-
7/26/2019 Power Cable Systems
21/35
This section will consider the following areas used in cable
selection:
Design current (Ib)
Rating of the protective device (In) Reference methods
Correction factors
Application of correction factors
Voltage drop
Shock protection
Thermal constraints
Diversity
-
7/26/2019 Power Cable Systems
22/35
To find the design current, you may need to use the
following equations:
Single phase supplies:
Uo=230 V
Three phase supplies:
Where PF is the power factor of the circuit concerned.
-
7/26/2019 Power Cable Systems
23/35
When you have worked out the design current (Ib), you
must next work out the current rating or setting (In) of the
protective device. The IEE wiring regulation says that
current rating (In) must be no less than the design current(Ib) of the circuit.
The reason for this is that the protective device must be
able to pass enough current for the circuit to operate atfull load, but without the protective device operating and
disconnecting the circuit.
-
7/26/2019 Power Cable Systems
24/35
You need to decide at this stage in the cable selection
process which method of installation to use. This will make
sure that the correct cable column is chosen in the later
stages of cable selection.
This choice is also important when you calculate
correction factors for thermal insulation.
-
7/26/2019 Power Cable Systems
25/35
Diagram
-
7/26/2019 Power Cable Systems
26/35
Ambient temperature
Grouping factors
Thermal insulation
BS 3036 fuse
Mineral insulated cable
-
7/26/2019 Power Cable Systems
27/35
This is the temperature of the surroundings of the cable.
When a cable carries current, it gives off heat.
Hotter the surroundings of the cable, the more difficult it is
for the cable to get rid of this heat. If the surrounding temperature is low, then the heat given off
could be easily let out and the cable could carry more current.
-
7/26/2019 Power Cable Systems
28/35
If a number of cables are run together and touching each other,they will all produce heat when they are carrying current-Separation necessary
If each cable is separated by a clearance to the next surface of atleast one cable diameter:- 'spaced' - correction factorimportant.
Where the horizontal clearance to the next cable is more than
2Dia then no correction factor is needed.
It is important that you apply these correction factors to thenumber of circuits or multicore cables that are grouped and notthe number of conductors.
-
7/26/2019 Power Cable Systems
29/35
Thermal insulation has the effect of wrapping a cable in a fur
coat on a hot summer's day. The heat produced when the cable
carries current cannot escape.
There are two ways; thermal insulation on one side of the cable
totally enclosed in thermal insulation
-
7/26/2019 Power Cable Systems
30/35
BS 3036 fuses
always use a factor of 0.725 when calculating current
carrying capacity.
Mineral insulated cable For bare cables (i.e. no PVC outer covering) exposed to
touch, the tabulated values should be multiplied by 0.9.
-
7/26/2019 Power Cable Systems
31/35
When the right correction factors have been applied, we then
know the effective current carrying capacity of the conductor
(Iz).
This value of current tabulated in Appendix 4 of BS 7671 is
given the symbol Itwhich must be greater than Iz. Hence:
-
7/26/2019 Power Cable Systems
32/35
-
7/26/2019 Power Cable Systems
33/35
the voltage drop between the origin of the installation
(usually the supply terminals) and the socket outlet or the
terminals of the current using equipment should not
exceed 4% of the supply voltage.
Voltage drop formula
-
7/26/2019 Power Cable Systems
34/35
-
7/26/2019 Power Cable Systems
35/35