PLC Connection Guide
TN527D
Communication settings between MicroLogix DF1 and PanelMaster
◎Revision Record
Revision Date Content Owner
TND527-E0
Page 2 of 10 www.cermate.com
Preface
This tech note introduces how to connect AB MicroLogix Series DF1 RS232 CPU Port
with PanelMaster HMI.
MicroLogix PLC
Channel 0 Channel 1
TND527-E0
Page 3 of 10 www.cermate.com
(1) PLC Parameter Setting:
(a) Executing Rockwell Software --- RSLinx tool to link with PLC(via DF1 RS232)
Step1: Connect with the program cable to Channel 0 and execute the “RSLinx” tool.
TND527-E0
Page 4 of 10 www.cermate.com
Step2: Executing the “Auto-Configure” function to link with Channel0 automatically.
Step3: Setting the communication format (Standard: 19200; 8, None, 1/ node address:0); Driver=DF1
Full Duplex及 Error Detection=CRC.
TND527-E0
Page 5 of 10 www.cermate.com
(a) When you wish to link with MicroLogix PLC, please follow below steps to create the devices that
you want to link with.
Step1: Executing the RSLogix 500 software and choose correct CPU type. With “OFFLINE” situation,
move the mouse to the device and press right button of the mouse. Select the “New Window”
to set the device range.
Step2: Select the ”Propertise” option.
TND527-E0
Page 6 of 10 www.cermate.com
Step3: Change the “Last” device name from B3:0 to B3:255.
Step4: When you press “OK” button to return Propertise window, you will see the range is created
from B3:0 to B3:255. Please remember to execute “Download…” function to write this range
setting to PLC.
TND527-E0
Page 7 of 10 www.cermate.com
(b) Cable Diagram:
HMI Side PLC Side
COM1 9-PIN Male
PV-Series
Serial Port 9-PIN Female
(DF1 RS232)
RXD + 2 3 TXD
TXD - 3 2 RXD
GND 5 5 SG
RTS 7 7 CTS
CTS 8 8 RTS
HMI Side PLC Side
COM2 9-PIN Female
PV-Series
Serial Port 9-PIN Female
(DF1 RS232)
RXD + 2 3 TXD
TXD - 3 2 RXD
GND 5 5 SG
RTS 7 7 CTS
CTS 8 8 RTS
TND527-E0
Page 8 of 10 www.cermate.com
(2) HMI Setting:
Select 【Direct Link [COM] 】&【Device/Server: Allen Bradley → MicroLogix 1000/1500】
Set the linking parameter same like PLC software setting.
TND527-E0
Page 9 of 10 www.cermate.com
(3) PLC Address
Bit Devices:
Word Devices:
~Thank You~
TND527-E0
Page 10 of 10 www.cermate.com
Technical Support Information
中國大陸 QQ專線 : 800014850 www.panelmaster.com.cn / www.cermate.com
資料下載專區 ftp:://mail.cermate.com + User name + Password (欲加入會員需要申請)
合作貼牌聯絡專線: China: 0910011916 / 86-13823788405 [email protected] Taiwan: 886-910011915 [email protected]
Worldwide: 886-910011914 [email protected]
Cermate Technologies (Shanghai) Inc. 屏通科技(上海)有限公司
Phone: +86-21-51758590~2 FAX : +86-21-51758589
E-mail: [email protected]
Shenzhen Cermate Technologies Inc. 屏通科技(深圳)有限公司
Phone: +86-755-83562179, FAX : +86-755-83562294
E-mail: [email protected]
Cermate Technologies Inc. (台湾) 屏通科技股份有限公司 7F-1, No. 168, Lien-Cheng Road, Chung-Ho City, Taipei, Taiwan 235 R.O.C.
Phone: 886-2-22437000 FAX : 886-2-22499933
E-mail: [email protected]