PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
ITER Central Interlock System:
Central Interlock Networks
Y. LIU Dec. 2014
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
Table of Topics
The demand for ITER CIN
The CIN Characteristics
The CIN Architecture
The CIN Infrastructure
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
The Demands for ITER CIN
The situations:Large area to cover, large scale to connect in:
About 40 PIS from 23 PBS involve in ITER interlock system,The PIS located in 13 different buildings.
Redundant CIS requires redundant networks to enhance the network availability.
Large amount data requires high performance networks.
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
CIN Characters
A total redundant ITER Interlock Network covers ITER buildings to connect Plant interlock systems.
Conventional TCP/IP networks is base on Gigabit Ethernet technology: Gigabit switch, fiber optic cables start and end at central/local interlock cubicles.
Network segment: two isolated sub-networks
• CIN-A: Connect operator station, engineer station and CIS modules (PLC, Fast controller, servers…) for administrative tasks (monitoring, archiving, engineering configuration…)
• CIN-P: Connect CIS modules (PLC, fast controller, supervisor module) and Plant Interlock System for process control, operations, timing propagation, diagnostics
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
VLAN technology used to segregate data to increase the CIN-P performance:
– VLAN for interlock slow architectures (PLCs)– VLAN for fast controllers– VLAN for hardwired architecture diagnostics data
Separated paths for backbone fiber cables.
CIN Characters
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
CIN Architecture
ArchivingServer
EngineeringServer
Supervision Module
CODACInterface
SPM CPM PPM
OperationStation
EngineerStation
PIS Slow PIS Fast
CIN-P
VLAN-1
VLAN-2
VLAN-3
CIN-A
DLIBs
VLAN-4
MCR
MSR
Buildings
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
3. CIN Infrastructure – Principals
MCR
Synchronization
BCR
CNP - CNP is a passive wall mounted
patch panel which is the physical termination point Interlock Networks.
- Network panels are installed at strategic locations close to the PIS cubicles
CIN Cubicle:
Network cubicles have interlock network
switches installed side and located in
rooms called CODAC hutch.MSR BSR
CNP
CIN CubicleIn CODAC Hutch
PIS slow PIS Fast
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
3. CIN Infrastructure – The Network coverage
CIN-P star point
23
99
CIN CubicleNetwork Panel (CNP)
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
Conclusions
CIN uses following measures to enhance the Network availability and performance:
Network redundancy
• Cable Segregation
• Data Segregation by VLAN technology.
• Network Segregation: CIN-A, CIN-P
All kinds of Segregation measures:
Gigabit technology
PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France PLC Based Interlock systems Workshop 4-5 December 2014 - ITER Organization Headquarters - St Paul-lez-Durance-France
Thank you...
ITER Central Interlock Networks