pip process industry practices

651
ENGINEERING STANDARD Nº BRASKEM REV. S/N 00 PROJECT CODE (PJ) N° PROJECTIONIST SHEET PJ-6000009 1 / 3 LOGISTIC CENTER PLANT AREA RJ60 RJ60-00 00000 PROJECT TITLE PETROCHEMICAL COMPLEX IN RIO DE JANEIRO - COMPERJ BOOK OF ENGINEERING STANDARDS PROCESS INDUSTRY PRACTICES (PIP) Rev Date Code Description Elaborate Verified Approved 00 April/03/2012 IN PRELIMINARY ISSUE FOR COMMENTS Code Issue PR Preliminary CO To Comment LE Released for Execution CC AS Built AC Accepted Certificate PC To Quote LD Released for Detail CS Canceled / Replaced IN Informative PP To Buy CP As Purchased CA Canceled

Upload: noxleek

Post on 01-Nov-2014

6.685 views

Category:

Documents


1.212 download

TRANSCRIPT

N BRASKEM

REV.

ENGINEERING STANDARDPROJECT CODE (PJ) N PROJECTIONIST

S/NSHEET

001/3

PJ-6000009LOGISTIC CENTER PLANT AREA

RJ60PROJECT TITLE

RJ60-00

00000

PETROCHEMICAL COMPLEX IN RIO DE JANEIRO - COMPERJ

BOOK OF ENGINEERING STANDARDS PROCESS INDUSTRY PRACTICES (PIP)

Rev 00

Date April/03/2012

Code IN

Description PRELIMINARY ISSUE FOR COMMENTS

Elaborate

Verified

Approved

Code Issue PR AC IN Preliminary Accepted Certificate Informative CO PC PP To Comment To Quote To Buy LE LD CP Released for Execution Released for Detail As Purchased CC CS CA AS Built Canceled / Replaced Canceled

N BRASKEM

REV.

ENGINEERING STANDARDSPROJECT CODE (PJ) N PROJECTIONIST

S/NSHEET

00 2/3

PJ-6000009LOGISTIC CENTER PLANT AREA

RJ60PROJECT TITLE

RJ60-00

00000

PETROCHEMICAL COMPLEX IN RIO DE JANEIRO - COMPERJ

INDEX PROCESS INDUSTRY PRACTICES (PIP)1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. ELSWC03D - Data Sheet for 600-Volt Power and Control Cable Specification ELSWC05 - 300-Volt Instrumentation Tray Cable Specification ELSWC05D - Data Sheet for 300-Volt Instrumentation Tray Cable Specification PCCGN002 - General Instrument Installation Criteria PCIEL000 - Instrumentation Electrical Installation Details PCSCP001 - Procurement of Control Panels PCSEL001 - Procurement of Instrumentation Junction Boxes PCCGN001 - General Instrumentation Design Basis PCFGN000 - Instrument Pipe Support Fabrication Details PCIGN100 - Instrument Pipe Support Installation Details PCIGN200 - General Instrument Purge Details PCIGN300 - General Instrument Accessory Details PCIEL000 - Instrumentation Electrical Installation Details PCIIA000 - Instrument Air Installation Details ELCGL01 - Electrical Design Criteria PCIDP100 - Differential Pressure Transmitter Installation Details PCIFL100 - Orifice Plate Installation Details PCILI100 - Level Transmitter Installation Details PCIPR100 - Pressure Transmitter Installation Details PCITE200 - RTD/Thermocouple Installation Details PNF0200 - Vents, Drains, and Instrument Connection Details PNSC0035 - Steam Tracing Specification PCCIP001 - Instrument Piping and Tubing Systems Criteria PCEIA001 - Instrument Air Systems Guidelines PCIIA000 - Instrument Air Installation Details PCCIA001 Instrument Air Systems Design Criteria PCSIP001 Instrument Tubing Material Specification PCCGN002 General Instrument Installation Criteria PCEPA001 - Process Analyzer System Engineering Guidelines . PCSPA001 - Process Analyzer Project Documentation Data Sheet Instructions .

N BRASKEM

REV.

ENGINEERING STANDARDSPROJECT CODE (PJ) N PROJECTIONIST

S/NSHEET

00 3/3

PJ-6000009LOGISTIC CENTER PLANT AREA

RJ60PROJECT TITLE

RJ60-00

00000

PETROCHEMICAL COMPLEX IN RIO DE JANEIRO - COMPERJ

31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41.

PCSPA01D - Process Analyzer Project Documentation Data Sheet . PCSPA002 - Process Analyzer System Data Sheet Instructions PCCIA001 - Instrument Air Systems Design Criteria PCCIP001 - Instrument Piping and Tubing Systems Criteria PCIIA000 - Instrument Air Installation Details PCSIP001 Instrument Piping and Tubing Systems Specifications PCIGN200 General Instrument Purge Details PCIGN300 General Instrument Accessory Details Page PCFEL000 Instrumentation Electrical Fabrication Details PCIEL000 Instrumentation Electrical Installation Details PCSPA02D . Process Analyzer System Data Sheet

COMPLETE REVISIONDecember 2007

Process Industry Practices Electrical

PIP ELCGL01 Electrical Design Criteria

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP.

PRINTING HISTORY November 2002 Issued December 2007 Complete Revision Not printed with State funds

COMPLETE REVISIONDecember 2007

Process Industry Practices Electrical

PIP ELCGL01 Electrical Design CriteriaTable of Contents 1. Introduction................................. 21.1 1.2 Purpose .......................................... 2 Scope ............................................. 2

2. References .................................. 22.1 2.2 Process Industry Practices............. 2 Industry Codes and Standards....... 3

3. Requirements.............................. 43.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 System Design ............................... 4 Electrical Area Classification .......... 7 Power Distribution .......................... 8 Motors........................................... 10 Motor Control................................ 11 Grounding..................................... 13 Lighting ......................................... 15 Power Receptacles, Feeder Breakers, and Convenience Outlets .......................................... 16 Wiring Methods ............................ 16 Power and Control Wiring ............ 19 Instrumentation............................. 20 Freeze Protection and Process Heat-Tracing Systems.................. 20 Cathodic Protection ...................... 21 Uninterruptible/Standby Power Supply........................................... 21 Skid-Mounted or Packaged Systems........................................ 21 Lightning Protection...................... 21

3.9 3.10 3.11 3.12 3.13 3.14 3.15 3.16

Process Industry Practices

Page 1 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

1.

Introduction1.1 Purpose This Practice provides general requirements and the basis for the design of an electrical system. 1.2 Scope This Practice describes the general design requirements for electrical systems. This Practice includes requirements for system components and typical configurations.

2.

ReferencesApplicable parts of the following Practices, industry codes and standards, and references shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 Process Industry Practices (PIP) PIP ELCGL01D - Data Sheet for Electrical Design Criteria PIP ELEHA01 - Engineering Procedure for Developing Electrical Area Classifications PIP ELEMT01 - Guidelines for Selecting IEEE and API Standards for AC Motors 250 HP (185kW) and Larger PIP ELIGD000 - Grounding Installation Details PIP ELIMT000 - Motor Installation Details PIP ELIMTN00 - Motor Installation Details - Nameplate Details PIP ELIMTS00 - Motor Installation Details - Stand PIP ELIMTT00 - Motor Installation Details - Motor Termination Detail 600 Volts PIP ELSAP01 - Design and Fabrication of Battery Chargers PIP ELSAP03 - Design and Fabrication of Online Ferroresonant Uninterruptible Power Supply System PIP ELSAP04 - Design and Fabrication of Online Pulse Width Modulated Uninterruptible Power Supply System PIP ELSAP11 - Design and Fabrication of Flooded-Cell Lead-Acid Batteries for Electrical Stations PIP ELSAP20 - Low-Voltage Automatic Transfer Switches PIP ELSBD01 - Design and Fabrication of Metal- Enclosed NonsegregatedPhase Bus Duct Assemblies PIP ELSGS01 - Design and Fabrication of High-Resistance Grounding System (600 Volts or Below) PIP ELSGS07 - Design and Fabrication of High Resistance Grounding System(1000 to 5000 Volts)

Page 2 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

PIP ELSGS11 - Design and Fabrication of Low Resistance Neutral Grounding Resistor 2.4 to 15kV PIP ELSMC11 - Medium-Voltage Motor Control Center Specification PIP ELSMC13 - Low-Voltage Circuit Breaker Motor Control Centers PIP ELSMC20 - Low-Voltage AC Adjustable Speed Drive Specification PIP ELSMT01 - AC Squirrel Cage Induction Motors (600 Volts and Below) Specification PIP ELSPS01 - Electrical Requirements for Packaged Equipment PIP ELSSG01 - Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PIP ELSSG02 - Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kV to 38 kV PIP ELSSG11 - Design and Fabrication of Electrical Power Center PIP ELSSG12 - Design and Fabrication of Outdoor Enclosures for Motor Controllers and Switchgear PIP ELSTR01 - Design and Fabrication of Liquid-Immersed Substation Power Transformers 34.5 kV and below, 750 kVA through 10,000 kVA PIP ELSWC03 - 600-Volt Power and Control Cable Specification PIP ELSWC05 - 300-Volt Instrumentation Tray Cable Specification PIP ELSWC06 - Nonshielded Power Cable Specification (2001 Volts and Above) PIP ELSWC07 - Shielded Power Cable Specification (5 to 46 kV) PIP ELTFT01 - Field Inspection and Testing of New Electrical Equipment PIP PCCEL001 - Instrumentation Electrical Requirements 2.2 Industry Codes and Standards American Petroleum Institute (API) API RP500 - Recommended Practice for Classification of Locations for Electrical Installations as Class I, Division 1 and Division 2 API RP505 - Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Zone 0, Zone 1, and Zone 2 API RP540 - Electrical Installations in Petroleum Processing Plants API RP2003 - Protection Against Ignitions Arising out of Static, Lightning, and Stray Currents American Society for Testing and Materials (ASTM) ASTM C94 - Standard Specification for Ready-Mixed Concrete Institute of Electrical and Electronic Engineers (IEEE) IEEE Std 80 - IEEE Guide for Safety in AC Substation Grounding

Process Industry Practices

Page 3 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

IEEE Std 141 - Recommended Practice for Electrical Power Distribution in Industrial Plants (IEEE Red Book) IEEE Std 142 - Recommended Practice for Grounding of Industrial and Commercial Power Systems IEEE Std 242 - Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems IEEE Std 515 - IEEE Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for Industrial Applications IEEE Std 519 - Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems IEEE Std 979 - IEEE Guide for Substation Fire Protection IEEE Std 980 - IEEE Guide for Containment and Control of Oil Spills in Substations IEEE Std 1584 - IEEE Guide for Performing Arc-Flash Hazard Calculations National Electrical Manufacturers Association (NEMA) NEMA VE1 - Metal Cable Tray Systems NEMA VE2 - Cable Tray Installation Guidelines National Fire Prevention Association (NFPA) NFPA 70 - National Electrical Code (NEC) NFPA 70E - Standard for Electrical Safety in the Workplace NFPA 77 - Recommended Practice on Static Electricity NFPA 496 - Standard for Purged and Pressurized Enclosures for Electrical Equipment NFPA 497 - Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installation in Chemical Process Areas NFPA 499 - Classification of Combustible Dust and of Hazardous (Classified) Locations for Electrical Installation in Chemical Process Areas NFPA 780 - Standard for the Installation of Lightning Protection Systems

3.

Requirements3.1 System Design 3.1.1 General 3.1.1.1 The complete electrical system shall be designed to enhance personnel safety and to minimize environmental exposure of the electrical equipment. 3.1.1.2 In addition, the electrical systems shall be designed for safe, continuous, and reliable service, equipment protection, ease of maintenance and operation, mechanical protection of equipment, interchangeability of equipment, and the addition of future loads.

Page 4 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.1.1.3 Equipment listed or labeled by a nationally recognized testing laboratory (NRTL) shall be used if available. 3.1.2 Electrical Codes All electrical systems and installations shall be in accordance with NFPA 70 (NEC) and NFPA 70E as applicable and any other applicable codes that are specified on the purchasers PIP ELCGL01D Data Sheet. 3.1.3 System Protection and Coordination 3.1.3.1 System protection and coordination shall be as in accordance with IEEE Std 242 - Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. 3.1.3.2 Electrical system studies shall be provided if specified on the purchasers PIP ELCGL01D Data Sheet. 3.1.3.3 When an incident energy study is specified, it shall be done in accordance with NFPA 70E or IEEE Std 1584 as specified on the purchasers PIP ELCGL01D Data Sheet. 3.1.3.4 Software program(s) as specified on the purchasers PIP ELCGL01D Data Sheet shall be used for any required studies. 3.1.3.5 Any files and libraries created in system studies shall be provided to the owner. Such files shall include paper files, electronic files, and native files required to run system studies. 3.1.3.6 System protective devices (e.g., relays, fuses, etc.) shall be selected and coordinated to ensure that the upstream-interrupting device nearest the point of fault (or overload) opens first and minimizes system disturbance. 3.1.4 Utility Interface Parameters Utility interface parameters shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.1.5 System Parameters 3.1.5.1 System voltage levels, motor horsepower range for each voltage level, and system grounding methods shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.1.5.2 Unless otherwise modified in accordance with Section 3.1.6, system voltages shall be within the tolerances specified in IEEE Std 141, Chapter 3. 3.1.6 Steady State Voltage 3.1.6.1 Voltage drop from the substation bus to the loads supplied from the substation shall not be greater than 5% total, typically split as 2% feeder and 3% branch circuit. 3.1.6.2 The rise in transformer secondary side no-load voltage shall not be greater than 8% above the nominal system voltage at the transformer secondary terminals.

Process Industry Practices

Page 5 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3.1.7

Motor-Starting Voltage Drop 3.1.7.1 Motor-starting conditions shall be evaluated based on system and process conditions that result in the minimum motor acceleration torque. 3.1.7.2 Acceleration studies shall be performed for motors and their driven loads when specified on the purchasers PIP ELCGL01D Data Sheet. Acceleration studies shall verify adequate motor acceleration torque and acceptable system voltage drops for specified system configurations and specified process conditions. 3.1.7.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, for motors of 600-volt rating, the system shall be designed to provide, as a minimum, 90% nominal system voltage at the substation bus during starting. 3.1.7.4 For motors of 600-volt rating, the system shall be designed to provide, as a minimum, 85% of nominal motor-rated terminal voltage at the motor terminals during starting. 3.1.7.5 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, for motors of 600-volt rating that cannot be started across the line, electronic soft starters shall be used. 3.1.7.6 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, for motors of >600-volt rating, the system shall be designed to provide, as a minimum, 85% nominal system voltage at the substation bus during starting. 3.1.7.7 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, for motors of >600-volt rating, the system shall be designed to provide, as a minimum, 80% of system nominal voltage at the motor terminals during starting. 3.1.7.8 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, for motors of >600-volt rating that cannot be started across the line because of system voltage drop requirements, a captive transformer shall be used.

3.1.8

Design Allowance 3.1.8.1 New electrical systems shall be designed with a minimum spare capacity as specified on the purchasers PIP ELCGL01D Data Sheet. Design allowances beyond the minimum requirements of the NEC shall be applied in sizing feeder circuits, transformers, panelboards, switchgear buses, and motor control center (MCC) buses to allow for future load growth. 3.1.8.2 Spare devices as specified on the purchasers PIP ELCGL01D Data Sheet shall be included with the following equipment: a. Medium-voltage (MV) switchgear, motor starters, and switch lineups b. Low-voltage (LV) switchgear c. LV MCC branch breakers, fused switches, and starters

Page 6 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.1.8.3 Equipped and unequipped spaces as specified on the purchasers PIP ELCGL01D Data Sheet shall be included in the following equipment: a. MV switchgear and motor starters b. LV switchgear 3.1.8.4 Future unit spaces as specified on the purchasers PIP ELCGL01D Data Sheet shall be included in LV MCCs. 3.1.8.5 Equipped spaces shall be furnished with all hardware, wiring, doors, and miscellaneous equipment, including current transformers and monitoring devices required to permit completion of the unit by the addition of only a circuit breaker or medium-voltage starter. 3.1.8.6 Equipped spaces shall be capable of being safely placed in service without shutdown of switchgear or motor control center lineup. 3.1.8.7 Unequipped spaces shall be provided with doors but with no other equipment for future use except the power stabs. 3.1.8.8 Unequipped spaces shall not be used for mounting control switches and other auxiliary equipment. 3.1.8.9 Power stabs (both line and load side) shall be provided with shutters or covers to prevent accidental contact with live parts when door is opened. 3.1.8.10 For MCCs, future unit spaces shall be provided with bus and blank doors. 3.1.9 Power Factor Power factor shall be corrected as specified on the purchasers PIP ELCGL01D Data Sheet. 3.1.10 Harmonics Power systems that include electronic switching devices shall be designed so that the total harmonic distortion is in accordance with IEEE Std 519. 3.1.11 Electrical Equipment Rooms 3.1.11.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, electrical equipment rooms or walk-in enclosures shall have a minimum of two doors at opposite ends of the room. 3.1.11.2 Doors shall be equipped with panic hardware and shall be self closing. 3.1.11.3 If specified on the purchasers PIP ELCGL01D Data Sheet, doors shall be lockable and equipped with night latch action (self locking). 3.2 Electrical Area Classification 3.2.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, electrical area classification shall be defined in accordance with

Process Industry Practices

Page 7 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

PIP ELEHA01. PIP ELEHA01 shall be used in conjunction with other standards that define the basis for area classification (e.g., NFPA 497, NFPA 499, API RP500, and API RP505). 3.2.2 3.2.3 3.2.4 3.3 The classification method, whether Division or Zone, shall be as specified on the purchasers PIP ELCGL01D Data Sheet. Preferably, all buildings containing only electrical equipment (e.g., electric rooms and control rooms) shall be located in unclassified areas. Electrical and control rooms located in classified areas shall be designed in accordance with NFPA 496 or as otherwise approved by the owner.

Power Distribution 3.3.1 System Configuration The power distribution system configuration shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.3.2 Utility Interface and Process Area Substations 3.3.2.1 Process area substations (the substation that serves the loads) shall be centrally located in the area where the loads to be served are situated. 3.3.2.2 Preferably, process area substations shall be located in unclassified areas. 3.3.2.3 Utility interface and process area substations shall be designed as specified on the purchasers PIP ELCGL01D Data Sheet. If specified on the purchasers PIP ELCGL01D Data Sheet, HVAC and pressurization systems shall be provided. 3.3.2.4 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, single-ended process area substations shall be designed for expansion in at least one direction. In this case, floor space shall be reserved for the addition of one or more vertical sections as specified on the purchasers PIP ELCGL01D Data Sheet. 3.3.2.5 If specified on the purchasers PIP ELCGL01D Data Sheet, design of single-ended substations shall allow for future conversion to doubleended (secondary selective) substations. 3.3.2.6 If specified on the purchasers PIP ELCGL01D Data Sheet, design of double-ended substations shall allow for future expansion. 3.3.3 Transformers 3.3.3.1 The system power transformers shall be selected as specified on the purchasers PIP ELCGL01D Data Sheet. 3.3.3.2 Transformers shall be sized in accordance with the designed operating load on the substation and the following: a. Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, liquid-filled transformers shall be sized based on their 55C rating. b. Dry type transformers shall be sized based on their 80C rating.

Page 8 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

c. If the forced-cooled rating is required for future load growth, provisions shall be made for the future addition of fans. 3.3.3.3 For double-ended substations or similar arrangements having more than one transformer serving interconnected buses, if one transformer is out of service, the remaining transformer(s) shall have sufficient capacity at the highest temperature rise ONAF rating to serve the maximum designed operating load on the substation. 3.3.3.4 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, liquid-filled transformers shall be filled with mineral-based dielectric oil. 3.3.3.5 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, system power transformers shall be located outdoors. a. Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, outdoor transformers shall be specified in accordance with PIP ELSTR01. 3.3.3.6 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, control power and lighting transformers shall be indoor, 80C rise with 220C insulation. 3.3.3.7 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, outdoor control power and lighting transformers shall be epoxy-encapsulated. 3.3.3.8 When specified on the purchasers PIP ELCGL01D Data Sheet, fire protection for mineral-oil-filled transformers shall be in accordance with IEEE Std 979-1994, Sections 1, 3, and 4. 3.3.3.9 When specified on the purchasers PIP ELCGL01D Data Sheet, containment and spill control for mineral-oil-filled transformers shall be in accordance with IEEE Std 980-1994, Sections 1, 2, 3, 4, 5.1, 5.4, 6, 7, 8.2.2.2, 8.3, and 8.4. 3.3.3.10 When specified on the purchasers PIP ELCGL01D Data Sheet, transformer differential protection shall be provided above the MVA level specified on the Data Sheet. 3.3.4 Metering, Monitoring, and Relaying 3.3.4.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, metering shall incorporate microprocessor-based multifunction devices. 3.3.4.2 If specified on the purchasers PIP ELCGL01D Data Sheet, metering and protective devices shall have digital communication capabilities. 3.3.4.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, protective relaying shall incorporate microprocessor-based multifunction devices.

Process Industry Practices

Page 9 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3.3.5

Switchgear 3.3.5.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, low-voltage switchgear shall be metal-enclosed drawout type in accordance with PIP ELSSG01. 3.3.5.2 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, medium-voltage switchgear shall be metal-clad drawout type in accordance with PIP ELSSG02. 3.3.5.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, switchgear-tripping voltages shall be 125-volt batterysupported DC. 3.3.5.4 If specified on the purchasers PIP ELCGL01D Data Sheet, switchgear shall be of arc-resistant construction. Voltage levels at which arc-resistant switchgear is required shall be indicated on the Data Sheet.

3.3.6

Batteries and Chargers 3.3.6.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, switchgear and substation batteries shall be lead-acid floodedcell type in accordance with PIP ELSAP11. 3.3.6.2 Unless otherwise specified on purchasers PIP ELCGL01D Data Sheet, switchgear and substation battery chargers shall be in accordance with PIP ELSAP01.

3.3.7

Switchgear Buildings and Enclosures Switchgear shall be housed as specified on the purchasers PIP ELCGL01D Data Sheet and in accordance with the following as applicable: a. In prefabricated buildings in accordance with PIP ELSSG11 b. In outdoor enclosures in accordance with PIP ELSSG12 c. In built-in-place buildings

3.3.8

Bus Duct Unless otherwise specified on purchasers PIP ELCGL01D Data Sheet, bus duct shall be in accordance with PIP ELSBD01.

3.3.9

Low-Voltage Automatic Transfer Switch Unless otherwise specified on purchasers PIP ELCGL01D Data Sheet, LV ATS shall be in accordance with PIP ELSAP20.

3.4

Motors 3.4.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, AC motors shall be specified in accordance with PIP ELSMT01 or PIP ELEMT01, and with the horsepower requirements and system supply voltages specified on the purchasers PIP ELCGL01D Data Sheet in accordance with Section 3.1.5 of this Practice. Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, motors shall be installed in accordance with PIP ELIMTG00,

3.4.2

Page 10 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

PIP ELIMTD00, PIP ELIMTN00, PIP ELIMTS00, and PIP ELIMTT00 installation details. 3.5 Motor Control 3.5.1 Single-Phase Motor Control 3.5.1.1 Controllers for single-phase motors should be manual motor starters with overload protection, located near the motors. 3.5.1.2 Manual starters shall be used only if the motor can restart automatically after a power failure without creating a safety problem. 3.5.1.3 Short-circuit protection shall be in accordance with the NEC. 3.5.1.4 Local magnetic starters may be provided if required for the application. 3.5.2 480-Volt Motor Control 3.5.2.1 MCCs shall be in accordance with PIP ELSMC13, or other, as specified on the purchasers PIP ELCGL01D Data Sheet. 3.5.2.2 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, MCCs located indoors shall be NEMA 1 gasketed. MCCs shall be located in accordance with the following: a. If possible and practical, MCCs shall be centrally located. b. MCCs shall preferably be located within an environmentally controlled, separate electrical equipment room. c. MCCs shall not be located in: (1) Classified areas (2) In areas exposed to corrosive chemicals, dust, or water (3) In areas subject to damage by moving equipment 3.5.2.3 If an MCC is to be located in a building or room within a Class I, Division 2 area, the building or room shall be purged and/or pressurized in accordance with NFPA 496 to permit the use of general purpose equipment. 3.5.2.4 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, if an MCC is to be located outdoors in a non-classified area, the MCC shall be provided with a NEMA 3R enclosure. 3.5.2.5 MCCs shall be supplied in front-only or back-to-back configurations as specified on the purchasers PIP ELCGL01D Data Sheet. 3.5.2.6 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, floor space shall be allocated for 20% potential MCC growth of the installed vertical sections. 3.5.2.7 If groups of individually enclosed motor starters are located outdoors, the starters shall be mounted on switchracks.

Process Industry Practices

Page 11 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3.5.2.8 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, individually enclosed motor starters located outdoors in nonclassified areas shall be provided with NEMA 4X enclosures. 3.5.2.9 Motor starters located in classified areas shall be as follows: a. Have explosion-proof enclosures b. Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, enclosures shall be bolted type. c. Explosion-proof starters shall be applied within the short-circuit rating of the starter assembly as listed by an NRTL. 3.5.2.10 Methodology of interfacing between the MCC and the control system shall be in accordance with other specifications furnished by the purchaser. 3.5.2.11 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, minimum starter size shall be NEMA Size 1. 3.5.2.12 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, motors shall be protected by ambient-compensated, bimetallic NEMA Class 20 motor overloads. 3.5.3 Low-Voltage Adjustable Speed Drives 3.5.3.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, low-voltage adjustable speed drives shall be in accordance with PIP ELSMC20. 3.5.3.2 Adjustable speed drives, motors, and associated equipment shall be designed as a coordinated system and in accordance with manufacturers recommendations. 3.5.4 Medium-Voltage Motor Control 3.5.4.1 For 2.3-kV and 4-kV motors, the horsepower ranges where circuit breakers shall be used as motor starters shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.5.4.2 If a contactor is to be used as motor starter, the controller shall be in accordance with the following: a. NEMA Class E2 fused b. Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, stationary type c. Have a separate isolation switch 3.5.4.3 Medium-voltage motors greater than 7.2 kV shall be controlled using 15-kV class or greater switchgear. 3.5.4.4 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, medium-voltage motor starters shall be provided in accordance with PIP ELSMC11. 3.5.4.5 A microprocessor-based motor protective relay as specified on the purchasers PIP ELCGL01D Data Sheet shall be provided for motor and motor circuit protection.

Page 12 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.5.4.6 Unless otherwise specified on purchasers PIP ELCGL01D Data Sheet, differential protection shall be provided for medium-voltage motors equal to or greater than 1500 hp. 3.6 Grounding Grounding shall be designed in accordance with IEEE Std 142 - Recommended Practice for Grounding of Industrial and Commercial Power Systems. 3.6.1 Substation 3.6.1.1 A substation shall be provided with a ground ring, grid or loop designed in accordance with IEEE Std 80 and the NEC. 3.6.1.2 Grid conductors shall be bare or covered stranded copper as specified on the purchasers PIP ELCGL01D Data Sheet and sized to accommodate the worst case fault condition. 3.6.1.3 If a substation fence is provided, the grid shall include a perimeter loop located 3 feet (0.9 m) outside the fence and bonded to the fence and gates. 3.6.2 System Grounding 3.6.2.1 Electrical systems shall be grounded and bonded in accordance with NEC Article 250. 3.6.2.2 System grounding shall be as specified on the purchasers PIP ELCGL01D Data Sheet. See Section 3.1.5 of this Practice. 3.6.2.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, 480-volt systems shall be wye-connected, high-resistance grounded using equipment in accordance with PIP ELSGS01. 3.6.2.4 Alarms from high-resistance grounding systems shall be connected to plant monitoring system. 3.6.2.5 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, medium-voltage motor control buses shall be low resistance grounded using NGRs in accordance with PIP ELSGS11. When medium-voltage motor control buses are specified to be highresistance grounded the grounding system shall be in accordance with PIP ELSGS07. 3.6.2.6 Unless specified otherwise on the purchasers PIP ELCGL01D Data Sheet, medium-voltage distribution systems that are derived from transformers shall be low-resistance grounded using transformer neutral grounding resistors in accordance with PIP ELSGS11. 3.6.3 Equipment Grounding 3.6.3.1 The path to ground from circuits, equipment, and enclosures shall be as follows: a. Permanent and continuous b. Have ample capacity to conduct any ground fault current likely to be imposed on it c. Of low impedance

Process Industry Practices

Page 13 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3.6.3.2 Equipment-grounding conductors shall be of the types permitted in NEC Article 250 and as specified on the purchasers PIP ELCGL01D Data Sheet. 3.6.3.3 Equipment-grounding conductors shall be connected to the grounding electrode at the service-supplied or separately derived system. 3.6.3.4 Ground fault current path continuity shall be maintained in circuits passing through non-metallic enclosures or raceways. 3.6.3.5 If specified on the purchasers PIP ELCGL01D Data Sheet or for motors rated 2300 volts and higher, motor frames shall also be bonded to one of the following: a. Adjacent building or structure steel b. Reinforcing mesh or bars in the concrete foundation c. Adequately sized bare, tin-coated or green-colored, covered copper conductor around the equipment foundation and connected to at least two ground rods or the ground grid 3.6.3.6 If specified on the purchasers PIP ELCGL01D Data Sheet, all 460-volt motors shall also be bonded by one of the methods mentioned in Section 3.6.3.5. 3.6.4 Plant Grounding System 3.6.4.1 The grounding system shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.6.4.2 If a ground loop system is specified on the purchasers PIP ELCGL01D Data Sheet, taps from the ground loop to all major equipment and structural steel shall be provided. 3.6.4.3 For facilities outside of plant ground grid, a grounding system shall be provided. Connection of the remote grounding system to the plant grounding system is recommended. 3.6.4.4 The plant grounding system impedance to earth shall not exceed 5 ohms. Results shall be obtained by methods in accordance with PIP ELTFT01. 3.6.4.5 Connections to the grounding system and the minimum depth of the buried grounding system shall be as specified on the purchasers PIP ELCGL01D Data Sheet or as detailed in PIP ELIGD000. 3.6.4.6 Instrument grounding shall be installed in accordance with PIP PCCEL001. 3.6.4.7 Cathodic protection systems in plants shall not be electrically isolated from the grounding system. Where bare underground cables are connected to cathodically protected systems, the cathodic protection current flow to the cable can be significantly reduced by use of tin-coated copper cable. If specified on the purchasers PIP ELCGL01D Data Sheet, tinned copper cable shall be installed.

Page 14 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.6.5

Static Electricity Grounding All equipment including tank trucks, tank cars, portable containers, marine craft, storage tanks, vessels, agitators, piping systems, etc., shall be protected against static electricity, lightning, and stray currents. See API RP2003, NFPA 77, and NFPA 780.

3.7

Lighting 3.7.1 3.7.2 3.7.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, illumination levels shall be in accordance with API RP540-2004, Table 4. Luminaire type and voltage rating for each area of the facility shall be as specified on the purchasers PIP ELCGL01D Data Sheet. Outdoor Lighting 3.7.3.1 Outdoor lighting shall be controlled automatically. 3.7.3.2 The preferred method for lighting control is photocell control, provided with time delay and other protection to negate the effect of lightning. The method of photocell control shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.7.3.3 For areas where plant flares, clouds of dust, and similar conditions can interfere with a photocell, an astronomical clock shall be used. Astronomical clocks shall be used if specified on the purchasers PIP ELCGL01D Data Sheet. 3.7.4 Emergency Lighting 3.7.4.1 If specified on the purchasers PIP ELCGL01D Data Sheet, emergency lighting shall provide minimal egress lighting in operating areas in the event of a power failure. If indicated on purchasers PIP ELCGL01D Data Sheet, include time delay off to allow for HID lighting restrike. 3.7.4.2 Emergency lighting shall be circuited and run separately from general lighting. 3.7.4.3 The type of emergency lighting shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.7.4.4 Battery-powered emergency lights shall be provided in the control room, substation buildings, and other locations as specified on the purchasers PIP ELCGL01D Data Sheet. 3.7.4.5 Exit signs shall be illuminated during the loss of normal lighting. 3.7.4.6 The loss of a luminaire or lighting circuit shall not leave any enclosed room containing power distribution or control equipment in darkness.

Process Industry Practices

Page 15 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3.8

Power Receptacles, Feeder Breakers, and Convenience Outlets 3.8.1 120-Volt Receptacles 3.8.1.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, 120-volt receptacles shall be located in process units so that equipment at grade can be reached with extension cords not longer than 50 feet. 3.8.1.2 All receptacles located in washdown areas or in other areas having wet atmospheric conditions shall be equipped with weatherproof covers and boxes. 3.8.1.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, all 120-volt receptacles located in non-classified areas shall be NEMA 5-20R. 3.8.1.4 If required by the NEC or specified on the purchasers PIP ELCGL01D Data Sheet, ground-fault circuit-interrupter (GFCI) protected receptacles shall be provided. 3.8.2 480-Volt Receptacles and Feeder Breakers 3.8.2.1 All 480-volt receptacles shall be three-phase, four-wire and shall be installed in convenient locations less than 100 feet from areas in which 480-volt power to portable equipment is required. 3.8.2.2 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, 480-volt receptacles shall be 60A. 3.8.2.3 All four-pole receptacles shall be of the same size and rating. 3.8.2.4 A maximum of four receptacles shall be connected to one feeder. 3.8.2.5 Feeder cable sizes shall be based on a demand factor of 0.5. 3.8.2.6 480-volt receptacles shall match the plug type specified on the purchasers PIP ELCGL01D Data Sheet. 3.8.2.7 480-volt receptacles and feeder breakers shall be applied within the short-circuit rating of the assembly as listed by an NRTL. 3.8.3 Specialty Receptacles Receptacles for use at voltages other than nominal 120 or 480 volts shall be selected in accordance with the application.

3.9

Wiring Methods 3.9.1 Cable Tray and Conduit Separation Requirements Spacing between different electrical and instrument cable trays or conduit systems shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.9.2 Cable Tray 3.9.2.1 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, cable tray shall be heavy-duty-rated NEMA 20C and NRTLlisted and labeled. Metallic tray shall be labeled as an equipmentgrounding conductor.

Page 16 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.9.2.2 The cable tray shall be secured with clips at every support. 3.9.2.3 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, cable tray shall be sized for a minimum of 20% spare capacity after the completion of project. 3.9.2.4 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, cable tray shall be of the ladder type with 9-inch rung spacing suitable for indoor or outdoor installations. 3.9.2.5 The cable tray shall have a minimum load safety factor of 1.5 based on the load capacity defined in accordance with NEMA VE1. 3.9.2.6 The cable tray shall also be capable of a 200-pound (90 kg) static load located at mid-span. 3.9.2.7 All bolts, nuts, and washers for cable tray systems shall be 316 stainless steel. 3.9.2.8 Expansion joints shall be provided as required by NEMA VE2-2006, Table 4-2, for long, straight tray runs. 3.9.2.9 Cable tray shall be installed to permit a minimum of 12 inches (0.3 m) of access above the top of each tray. 3.9.2.10 Installation of cables in cable trays shall be in accordance with the NEC. 3.9.2.11 Cable tray systems shall be installed above or to the side of process lines if possible and a minimum of 12 inches (0.3 m) from hot surfaces. 3.9.2.12 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, cable trays shall not have covers. 3.9.2.13 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, separate trays shall be provided for each voltage class of cables. 3.9.3 Aboveground Conduit and Fittings 3.9.3.1 Acceptable sizes, material, and construction of conduit systems shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.9.3.2 If specified on the purchasers PIP ELCGL01D Data Sheet, electrical metallic tubing (EMT) may be used in indoor unclassified locations (e.g., office buildings, administration buildings, guardhouses, change houses, etc.) if the EMT is not subject to vibration, corrosion, or physical damage.3.9.3.3 Flexible Conduit

1. Flexible conduit shall be liquid-tight, type UA for metal type, and suitable for the area classification where installed. 2. Flexible conduit shall be used to connect vibrating equipment to the conduit system.

Process Industry Practices

Page 17 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3. The length of flexible conduit shall not be greater than 6 feet (1.9 m). 3.9.3.4 All conduit connections to cabinets and junction boxes located outdoors or in washdown areas shall be made with factory hubs or weather-tight rigid conduit hubs. 3.9.3.5 Conduits shall not enter the top of cabinets or junction boxes located outdoors or in washdown areas. Bottom entry of cabinets or junction boxes is preferred. 3.9.3.6 Conduit drains shall be installed at the low point in all conduit systems and before entering electrical enclosures installed outdoors. 3.9.3.7 Drainage provisions shall be provided in the bottom of all pull boxes, junction boxes, control panels, etc., installed outdoors. 3.9.3.8 For long conduit runs, a method of support shall be provided that permits expansion and contraction. Expansion fittings, with bonding jumpers around the fittings, shall be installed as required. 3.9.3.9 For fireproofed structures, the design shall permit conduit supports to be installed before fireproofing and in such a manner that the conduit cannot become imbedded in fireproofing materials. 3.9.3.10 Conduit for corrosive areas shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.9.3.11 All coated conduit shall be coated on the outside and the inside. 3.9.4 Underground Conduit and Duct Banks 3.9.4.1 Underground conduit materials shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.9.4.2 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, stub-ups shall be made using rigid galvanized steel conduit elbows and galvanized fittings as required and shall include an insulated bushing on any exposed end of the conduit. 3.9.4.3 Minimum size of underground conduit shall be 1 inch (25.4 mm). Acceptable conduit sizes shall be as specified on the purchasers PIP ELCGL01D Data Sheet.3.9.4.4 Concrete Encasement

1. All conduit runs installed below grade (except in floor slabs) shall be encased in a minimum of 3 inches (76 mm) of concrete on all sides. 2. Concrete shall be 3000 psi (20.4 MPa) with a slump of 5 inches (127 mm) and shall be in accordance with ASTM C94. 3. The concrete shall be either colored throughout or colored at the top of the encasement. The coloring shall be a shade of red. 4. Reinforced concrete shall be used for all underground duct banks.

Page 18 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.9.4.5 The minimum spacing between conduits in underground duct banks shall be 1-1/2 inches (38 mm). 3.9.4.6 The minimum depth for all underground conduits, measured from grade to the top of the top conduit, shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.9.4.7 All horizontal bends in underground conduits shall be made using long radius sweeps. 3.9.4.8 For duct banks passing through manholes, the duct banks shall slope downward toward the manholes at a minimum slope of 3 inches (76 mm) per 100 feet (30.4 m). 3.9.4.9 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, a minimum 20% but not less than one spare conduit(s) shall be installed in all underground duct banks except for the following: a. Single or double conduit duct banks for street lighting b. Duct banks to individual, remotely located equipment 3.9.5 3.9.6 3.9.7 3.10 Installation of direct burial cable shall be as specified on the purchasers PIP ELCGL01D Data Sheet. Installation of overhead pole lines shall be as specified on the purchasers PIP ELCGL01D Data Sheet. Installation of messenger-supported cable shall be as specified on the purchasers PIP ELCGL01D Data Sheet.

Power and Control Wiring 3.10.1 Multiconductor cable shall be in accordance with PIP ELSWC06, PIP ELSWC07, and PIP ELSWC03. 3.10.2 Grounding conductor(s), sized in accordance with NEC, Article 250, shall be included in all multiconductor power cables. 3.10.3 All power/control wiring shall have copper conductors and construction as specified on the purchasers PIP ELCGL01D Data Sheet. 3.10.4 The minimum conductor size for power wiring shall be as follows: a. No. 12 AWG except for individual luminaire drops b. Conductors for individual luminaire drops may be No. 14 AWG 3.10.5 Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, the minimum conductor size for control in multiconductor cables shall be No. 14 AWG. 3.10.6 Composite power and control cable shall be permitted only as specified on the purchasers PIP ELCGL01D Data Sheet. 3.10.7 Bottom entry of cables into cabinets or junction boxes is preferred. Top entry of cables into cabinets or junction boxes located outdoors or in washdown areas shall not be permitted.

Process Industry Practices

Page 19 of 21

PIP ELCGL01 Electrical Design Criteria

COMPLETE REVISIONDecember 2007

3.10.8 Power cable termination methods shall be as specified on the purchasers PIP ELCGL01D Data Sheet. 3.10.9 If available, full ring compression lugs shall be used for CT secondary wiring and where vibration is anticipated. 3.10.10 If full ring compression lugs are not available, indent type lugs shall be used for power wiring. 3.11 Instrumentation Instrumentation design requirements shall be specified in accordance with PIP PCCEL001. 3.12 Freeze Protection and Process Heat-Tracing Systems 3.12.1 Freeze protection and process heat-tracing systems shall be designed in accordance with IEEE Std 515 and NFPA 70-2005 (NEC), Article 427. 3.12.2 Heat-tracing system components shall be provided as specified on the purchasers PIP ELCGL01D Data Sheet. 3.12.3 The heat-tracing systems shall include power transformers, electric heat trace control panels, electric heat cables, temperature sensors, temperature controllers, circuit breakers, enclosures, conduit, wire, insulation, and all necessary auxiliary equipment and controls. 3.12.4 Electric heat-tracing control panels, power transformers, and power distribution equipment shall be centrally located to minimize the lengths of heating power circuits in the area. 3.12.5 All tracing design shall use a minimum 25% safety factor in calculated heat input. Heat loss calculation shall be submitted to the purchaser for compliance verification. 3.12.6 Installation of heating cable, components, and controls shall begin after pressure testing of the pipeline and installation of all the instruments. 3.12.7 Thermal insulation shall be installed after the electrical installation and initial testing is complete. The heat tracing shall also be tested after thermal insulation is installed. 3.12.8 Heat tracing for pipes shall include all inline components. 3.12.9 All flanges, pumps, valves, devices, supports, and appurtenances shall be traced with appropriate additional lengths of heater cable as required to permit removal of the equipment without disconnecting and removing the heat tracing. 3.12.10 Heater cable design shall be suitable to deliver rated performance and service life if subjected to voltage variations from 90% to 110% of nominal distribution voltages. 3.12.11 Components of the electric heat-tracing systems shall be approved for the area classification in which they are installed. 3.12.12 Heating requirements and sectionalizing shall be in accordance with process requirements.

Page 20 of 21

Process Industry Practices

COMPLETE REVISIONDecember 2007

PIP ELCGL01 Electrical Design Criteria

3.12.13 Each heat-tracing circuit shall be equipped with a suitable device for isolation and installation of a lockout device. 3.13 Cathodic Protection If required, cathodic protection shall be in accordance with specifications separately furnished by the purchaser. 3.14 Uninterruptible/Standby Power Supply 3.14.1 Critical power supply systems shall be in accordance with the purchasers PIP ELCGL01D Data Sheet. 3.14.2 If specified on the purchasers PIP ELCGL01D Data Sheet, an uninterruptible power supply (UPS) shall be provided in accordance with the following: a. Sized to accommodate the process control loads and 20% spare capacity b. Shall have a dedicated battery and distribution panel c. A separate detailed specification shall be issued if required. d. Specification shall refer to PIP ELSAP03 and PIP ELSAP04. e. Unless specified otherwise on the purchasers PIP ELCGL01D Data Sheet, battery type shall be flooded cell in accordance with PIP ELSAP11. 3.14.3 If specified on the purchasers PIP ELCGL01D Data Sheet, standby power shall be provided by an alternate utility/plant feeder or a turbine-driven or diesel generator. Transfer switches shall be provided for critical loads not requiring uninterruptible power. 3.14.4 If a UPS is to be used on a high resistance grounded power system, the UPS vendor should be made aware of that fact in order to furnish a compatible UPS. 3.15 Skid-Mounted or Packaged Systems Unless otherwise specified on the purchasers PIP ELCGL01D Data Sheet, electrical requirements for skid-mounted or packaged systems shall be in accordance with PIP ELSPS01. 3.16 Lightning Protection 3.16.1 Tall or isolated structures and the high-voltage switchyard shall be protected against lightning in accordance with NFPA 780. 3.16.2 Down conductors from air terminals or lightning masts shall be connected to individual ground rods and to the plant grounding system.

Process Industry Practices

Page 21 of 21

COMPLETE REVISIONAugust 2010

Process Industry Practices Electrical

PIP ELSWC03 600-Volt Power and Control Cable Specification

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized Users client. PIPs copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice.

PRINTING HISTORY March 1999 Issued April 2005 Complete Revision August 2010 Complete Revision Not printed with State funds

COMPLETE REVISIONAugust 2010

Process Industry Practices Electrical

PIP ELSWC03 600-Volt Power and Control Cable SpecificationTable of Contents 1. Introduction................................. 21.1 Purpose ............................................ 2 1.2 Scope ............................................... 2

2. References .................................. 22.1 Process Industry Practices .............. 2 2.2 Industry Codes and Standards ........ 2

3. Definitions ................................... 2 4. Requirements.............................. 34.1 4.2 4.3 4.4 4.5 Fabrication ....................................... 3 Inspection and Testing ..................... 4 Shipping ........................................... 4 Documentation ................................. 5 Conflict Resolution ........................... 5

Process Industry Practices

Page 1 of 5

PIP ELSWC03 600-Volt Power and Control Cable Specification

COMPLETE REVISIONAugust 2010

1.

Introduction1.1 Purpose This Practice provides requirements for 600-volt-rated power and control tray cable (Type TC) and metal-clad (Type MC) cable. 1.2 Scope This Practice describes the minimum technical requirements for fabrication, inspection, testing, and shipping of insulated copper cable. This Practice covers 600-volt-rated multiple conductor power and control tray cable and metal-clad cable.

2.

ReferencesApplicable parts of the following Practices and industry codes and standards shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 2.2 Process Industry Practices (PIP) PIP ELSWC03D - Data Sheet for 600-Volt Power and Control Cable Industry Codes and Standards American Society for Testing Materials (ASTM) ASTM B8 - Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft Institute of Electrical and Electronics Engineers (IEEE) IEEE 1202 - IEEE Standard for Flame-Propagation Testing of Wire and Cable Insulated Cable Engineers Association (ICEA) ICEA S-73-532 (NEMA WC57) - Standard for Control, Thermocouple Extension, and Instrumentation Cables National Fire Protection Association (NFPA) NFPA 70 - National Electrical Code (NEC) Underwriters Laboratories (UL) UL 1277 - Standard for Electrical Power and Control Tray Cables with Optional Optical-Fiber Members UL 1569 - Standard for Metal-Clad Cables UL 2225 - Standard for Cables and Cable-Fittings for Use in Hazardous (Classified) Locations

3.

Definitionspurchaser: The party who awards the contract to the supplier. The purchaser may be the owner or the owners authorized agent.

Page 2 of 5

Process Industry Practices

COMPLETE REVISIONAugust 2010

PIP ELSWC03 600-Volt Power and Control Cable Specification

4.

Requirements4.1 Fabrication 4.1.1 General 4.1.1.1 Site conditions shall be in accordance with the purchasers PIP ELSWC03D Data Sheet. 4.1.1.2 All cable shall be in accordance with the requirements of the NEC. 4.1.1.3 The type of cable used in adjustable speed drive applications shall be specified on the purchasers PIP ELSWC03D Data Sheet. 4.1.1.4 For adjustable speed drive applications, a shield or metallic sheath shall be provided. 4.1.1.5 If specified on the purchasers PIP ELSWC03D Data Sheet, Type TC cable shall comply with the crush and impact requirements of Type MC cable and shall be identified for such use. 4.1.2 Conductor The conductor(s) shall be Class B stranded copper in accordance with ASTM B8. 4.1.3 Insulation 4.1.3.1 Insulation type shall be in accordance with the purchasers PIP ELSWC03D Data Sheet. 4.1.3.2 Unless otherwise specified on the purchasers PIP ELSWC03D Data Sheet, individual wire insulation shall be 600 volt, 75C (167F) (minimum) rated. Cable shall be suitable for installation in wet and dry locations. 4.1.3.3 Individual wires shall be color coded using ICEA S-73-532-2004 Appendix E, Method 1, and colors in accordance with ICEA S-73-532-2004 Table E-2 (without white and green). 4.1.3.4 If specified on the purchasers PIP ELSWC03D Data Sheet, for multiconductor power cable sizes 8 AWG and larger, wire identification shall be ICEA S-73-532-2004 Appendix E, Method 4 (numbered printing on single color insulation). 4.1.4 Ground Wire 4.1.4.1 Unless otherwise specified on the purchasers PIP ELSWC03D Data Sheet, a bare grounding conductor or conductors, sized in accordance with NEC-2008 Article 250.122 requirements, shall be provided in all cables. 4.1.4.2 For cable sizes 10 AWG and smaller, a green insulated conductor is acceptable as the grounding conductor. 4.1.4.3 For adjustable speed drive applications, three concentric grounding conductors shall be provided.

Process Industry Practices

Page 3 of 5

PIP ELSWC03 600-Volt Power and Control Cable Specification

COMPLETE REVISIONAugust 2010

4.1.5

Metallic Sheath 4.1.5.1 For Type MC cable, a metallic sheath shall be provided that is in accordance with UL 1569. 4.1.5.2 The metallic sheath shall be either continuous-welded, impervious, corrugated aluminum, aluminum interlocked armor, or galvanized steel interlocked armor in accordance with the purchasers PIP ELSWC03D Data Sheet. 4.1.5.3 If specified on the purchasers PIP ELSWC03D Data Sheet, the cable shall be labeled in accordance with the requirements of UL 2225 as MC-HL for use in Class I, Division 1 locations.

4.1.6

Outer Jacket 4.1.6.1 An outer, nonmetallic, flame-retardant jacket that is constructed of materials specified on the purchasers PIP ELSWC03D Data Sheet shall be applied over the completed cable assembly. 4.1.6.2 Unless otherwise specified on the purchasers PIP ELSWC03D Data Sheet, outer jacket color shall be manufacturers standard. 4.1.6.3 Outer jacket shall be oil-resistant and sunlight-resistant. Jacket shall be marked Sunlight-Resistant in accordance with UL 1277. 4.1.6.4 If specified on the purchasers PIP ELSWC03D Data Sheet, the cable shall be rated for direct burial.

4.1.7

Cable Identification The cable shall be marked and identified in accordance with NEC-2008 Article 310-11.

4.1.8

Cable Length Tolerance Unless otherwise specified on the purchasers PIP ELSWC03D Data Sheet, the length tolerance of each segment of cable shall be minus 0% to plus 5%.

4.2

Inspection and Testing 4.2.1 4.2.2 4.2.3 4.2.4 Factory inspection and testing shall be performed on Type TC cables in accordance with UL 1277. Factory inspection and testing shall be performed on Type MC cables in accordance with UL 1569. Type TC and MC cables shall also pass IEEE 1202 vertical tray flame tests. If specified on the purchasers PIP ELSWC03D Data Sheet, additional testing shall be performed as indicated. Cable reel type and lagging shall be in accordance with the purchasers PIP ELSWC03D Data Sheet. Minimum cable reel identification and marking for Type TC cables shall be in accordance with UL 1277.

4.3

Shipping 4.3.1 4.3.2

Page 4 of 5

Process Industry Practices

COMPLETE REVISIONAugust 2010

PIP ELSWC03 600-Volt Power and Control Cable Specification

4.3.3 4.3.4 4.4

Minimum cable reel identification and marking for Type MC cables shall be in accordance with UL 1569. Additional cable reel identification shall be in accordance with the purchasers PIP ELSWC03D Data Sheet.

Documentation The following information shall be provided with the quotation: a. Standard and maximum reel lengths b. Overall diameter over armor and outer jacket c. Diameter over cable assembly (not including armor and jacket) d. Cable weight per 1,000 ft (305 m) e. Maximum conductor continuous operating temperature f. Minimum bending radius g. Cable current-carrying capacity h. Maximum pulling tension and sidewall loading for each cable assembly i. j. Minimum cable-pulling temperature Descriptive literature (catalogs, etc.)

4.5

Conflict Resolution Any conflicts between the referenced documents shall be identified in writing to the purchaser for resolution. When resolving conflicts, the following order of precedence shall apply: a. Purchase order b. PIP ELSWC03D Data Sheet c. This Practice, PIP ELSWC03 d. Referenced standards

Process Industry Practices

Page 5 of 5

COMPLETE REVISIONAugust 2010

Process Industry Practices Electrical

PIP ELSWC03D Data Sheet for 600-Volt Power and Control Cable Specification

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized Users client. PIPs copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice.

PRINTING HISTORY March 1999 Issued April 2005 Complete Revision August 2010 Complete Revision Not printed with State funds

ASSOC. PIP ELSWC03

DATA SHEET

ELSWC03D-DPAGE 1 OF 1

600-VOLT POWER AND CONTROL CABLEISSUED FOR: FACILITY NAME/LOCATION: ITEM NAME: ITEM TAG NO.: SERVICE: UNIT: DWG NO.: DATA PROVIDED BY: APPLICABLE STATE AND LOCAL CODES: SITE CONDITIONS (4.1.1.1): ALTITUDE: AMBIENT TEMP.: MC APPLICATION: ADJUSTABLE SPEED DRIVE (4.1.1.4) CRUSH AND IMPACT RESISTANT TYPE TC CABLE (4.1.1.5) INSULATION (4.1.3): THHN/THWN XHHW - XLPE OTHER NEC TYPE : 75 C 90 C OTHER: CONDUCTOR COLOR CODING METHOD (4.1.3.3 & 4.1.3.4): ICEA METHOD 1 (WITHOUT WHITE AND GREEN) ICEA METHOD 4 (NUMBERED PRINTING ON SINGLE COLOR) OTHER: MULTICONDUCTOR CABLE GROUND CONDUCTOR (4.1.4): BARE COVERED OTHER: OTHER REQUIREMENTS: SIZED PER NEC-2008 250.122 XHHW - EPR CABLE LENGTH TOLERANCE (4.1.8): -0% TO +5% TESTING (4.2): ADDITIONAL REQUIREMENTS: CABLE REELS (4.3): RETURNABLE WOOD LAGGING ADDITIONAL REEL IDENTIFICATION MARKING (4.3.4): OTHER: OUTER JACKET COLOR: TC M (FT) MAX.: C MIN.: C METALLIC SHEATH CONSTRUCTION (4.1.5): CONTINUOUS CORRUGATED ALUMINUM INTERLOCKED ALUMINUM INTERLOCKED GALVANIZED STEEL OUTER JACKET (4.1.6): OUTER JACKET MATERIAL: PVC OTHER: PURCHASER SUPPLIER PURCHASER/LOCATION: JOB NO: PURCHASER ORDER NO.: SUPPLIER/LOCATION: SUPPLIER ORDER/SERIAL NOS.: PROPOSAL PURCHASE AS BUILT

AUGUST 2010

/

u SUPPLIER IF NOT BY PURCHASER

REFER TO PIP ELSWC03 FOR GENERAL REQUIREMENTS.

"MC-HL" LABELED

CABLE TYPE (4.1.1.2 & 4.1.1.3):

CPE

CSPE

MANUFACTURERS STANDARD OTHER:

DIRECT BURIAL RATING REQUIRED

NON-RETURNABLE

REEL ID

CABLE SIZE & CONDUCTORS (INDICATE GROUND AS REQUIRED)

LENGTH (FT)

REMARKS

NO.

DATE

REVISION DESCRIPTION

BY

APVD.

COMPLETE REVISIONAugust 2009

Process Industry Practices Electrical

PIP ELSWC05 300-Volt Instrumentation Tray Cable Specification

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP.

PRINTING HISTORY March 1999 Issued November 2004 Complete Revision June 2005 Editorial Revision August 2009 Complete Revision

Not printed with State funds

COMPLETE REVISIONAugust 2009

Process Industry Practices Electrical

PIP ELSWC05 300-Volt Instrumentation Tray Cable SpecificationTable of Contents 1. Introduction................................. 21.1 Purpose ............................................ 2 1.2 Scope ............................................... 2

2. References .................................. 22.1 Process Industry Practices .............. 2 2.2 Industry Codes and Standards ........ 2

3. Requirements.............................. 33.1 3.2 3.3 3.4 General ............................................ 3 Conductor......................................... 3 Insulation .......................................... 3 Conductor Twist, Shielding, and Fillers................................................ 4 3.5 Metallic Sheath ................................ 4 3.6 Outer Jacket ..................................... 4 3.7 Cable Identification .......................... 5 3.8 Cable Length Tolerance................... 5 3.9 Inspection and Testing ..................... 5 3.10 Shipping ........................................... 5 3.11 Documentation ................................. 5 3.12 Conflict Resolution ........................... 6

Process Industry Practices

Page 1 of 6

PIP ELSWC05 300-Volt Instrumentation Tray Cable Specification

COMPLETE REVISIONAugust 2009

1.

Introduction1.1 Purpose This Practice provides requirements for manufacturing and testing 300-volt-rated instrumentation tray cable (Type ITC). 1.2 Scope This Practice describes the technical requirements for manufacturing, inspection, testing, and shipping of insulated copper or thermocouple alloy conductor cable for 300-volt-rated multiple conductor instrumentation tray cable in single and multiple pair and triad construction. Pairs or triads may include individual shields and/or an overall shield. The following cable types are addressed by this Practice:TypeSPISCO SPTECO STISCO MPISCO MPTECI MPISCI MTISCO MTISCI

DescriptionSingle pair instrument signal cable (16 AWG minimum) with overall shield Single pair thermocouple extension cable (16 AWG minimum) with overall shield Single triad instrument signal cable (16 AWG minimum) with overall shield Multi-pair instrument signal cable (20 AWG minimum) with overall shield Multi-pair thermocouple extension cable (20 AWG minimum) with individual and overall shields Multi-pair instrument signal cable (20 AWG minimum) with individual and overall shields Multi-triad instrument signal cable (20 AWG minimum) with overall shield Multi-triad instrument signal cable (20 AWG minimum) with individual and overall shields

2.

ReferencesApplicable parts of the following Practices, industry codes and standards, and references shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 Process Industry Practices (PIP) PIP ELSWC05D - Data Sheet for 300-Volt Instrumentation Tray Cable 2.2 Industry Codes and Standards All cable shall be designed, manufactured, and tested in accordance with the applicable sections of the latest edition of the following standards: Instrument Society of America (ISA) ISA MC96.1 - Temperature Measurement Thermocouples

Page 2 of 6

Process Industry Practices

COMPLETE REVISIONAugust 2009

PIP ELSWC05 300-Volt Instrumentation Tray Cable Specification

National Fire Protection Association (NFPA) NFPA 70 - National Electrical Code (NEC) Underwriters Laboratories (UL) UL 2225 - Cables and Cable-Fittings for Use in Hazardous (Classified) Locations UL 2250 - Instrumentation Tray Cable

3.

Requirements3.1 General 3.1.1 3.1.2 3.1.3 Type ITC cable construction shall be in accordance with the requirements of NEC Article 727. Type ITC cable shall be suitable for outdoor installations. If specified on the purchasers PIP ELSWC05D Data Sheet, the cable shall be labeled as ITC-ER (open wire) in accordance with UL 2250-2006, paragraphs 32 and 33. If specified on the purchasers PIP ELSWC05D Data Sheet, the cable shall be labeled for use as direct burial in accordance with UL 2250-2006, paragraphs 30 and 32. If specified on the purchasers PIP ELSWC05D Data Sheet, the cable shall be labeled as ITC-HL in accordance with UL 2225 for use in Class I, Division 1 locations. Site conditions shall be as specified on the purchasers PIP ELSWC05D Data Sheet.

3.1.4

3.1.5

3.1.6 3.2

Conductor 3.2.1 3.2.2 3.2.3 All single and multi-pair and triad instrument wire shall have 7 strand, concentric bare copper, Class B conductors. All shield drain wires shall be 7 strand concentric tinned copper. Unless otherwise specified on the PIP ELSWC05D Data Sheet, all individual wires of the thermocouple extension cable shall have solid alloy conductors in accordance with ISA MC96.1. For vibrating thermocouple applications, thermocouple extension cable shall have stranded conductors.

3.3

Insulation 3.3.1 3.3.2 Individual wire insulation shall be as specified on the purchasers PIP ELSWC05D Data Sheet and shall be in accordance with UL 2250. Individual instrumentation wires shall be color coded. Unless otherwise indicated on the PIP ELSWC05D Data Sheet, twisted pairs shall be black and white; twisted triads shall be black, white, and red. Individual thermocouple wires shall be color coded in accordance with the ISA MC96.1 color code for the type of thermocouple specified.

3.3.3

Process Industry Practices

Page 3 of 6

PIP ELSWC05 300-Volt Instrumentation Tray Cable Specification

COMPLETE REVISIONAugust 2009

3.4

Conductor Twist, Shielding, and Fillers 3.4.1 The individual, color-coded wires shall be assembled as twisted pair or as twisted triad with individual pair or triad shielding to be as required by the cable type. Individual pair or triad shall consist of: 3.4.2.1 An aluminum/synthetic polymer-backed tape shield, helically applied over each pair or triad, with aluminum on the inside 3.4.2.2 A drain wire, the same size as the conductors in continuous contact with the shield 3.4.3 Multi-pair or multi-triad cables shall consist of: 3.4.3.1 Moisture and flame-resistant fillers as required to provide a round cable 3.4.3.2 An aluminum/synthetic polymer-backed tape overall shield, helically applied over all pairs or triads, with aluminum on the outside 3.4.3.3 A drain wire, the same size as the conductors in continuous contact with the shield 3.4.3.4 Individual shields, completely isolated from each other, if specified on the purchasers PIP ELSWC05D Data Sheet

3.4.2

3.5

Metallic Sheath 3.5.1 3.5.2 If metallic sheath is specified on the purchasers PIP ELSWC05D Data Sheet, the sheath shall be in accordance with requirements of UL 2250. The metallic sheath shall be either continuous welded impervious corrugated aluminum, aluminum interlocked armor, or galvanized steel interlocked armor as specified on the purchasers PIP ELSWC05D Data Sheet.

3.6

Outer Jacket 3.6.1 An outer protective jacket, constructed of materials specified on the purchasers PIP ELSWC05D Data Sheet, shall be applied over the completed cable assembly. Unless otherwise specified on the purchasers PIP ELSWC05D Data Sheet, outer jacket color shall be in accordance with the following table. Black Blue Red 3.6.3 3.6.4 For General Instrumentation and Thermocouple Extension Circuits For all Intrinsically Safe Circuits For Non-IS Emergency Shutdown Circuits

3.6.2

Outer jacket shall be moisture resistant, oil resistant, and sunlight resistant. Outer jacket shall be marked sunlight-resistant in accordance with UL 2250.

Page 4 of 6

Process Industry Practices

COMPLETE REVISIONAugust 2009

PIP ELSWC05 300-Volt Instrumentation Tray Cable Specification

3.6.5 3.7

For non-armored cable, a rip cord shall be provided under the jacket to facilitate jacket removal.

Cable Identification 3.7.1 3.7.2 Final cable assembly shall be in accordance with UL 2250 and shall have a UL Type ITC label. The cable shall be marked and identified in accordance with NEC-2008, Article 310-11.

3.8

Cable Length Tolerance The length of each segment of cable shall be the length specified on the purchasers PIP ELSWC05D Data Sheet minus 0% to plus 5%.

3.9

Inspection and Testing Factory inspection and testing shall be performed on all cables in accordance with UL 2250.

3.10

Shipping 3.10.1 Minimum cable reel identification and marking shall be in accordance with UL 2250. In addition, each reel shall include purchase order number, item number and reel number. 3.10.2 Cable reel identification tag number shall also be stenciled on both sides of reel with weather resistant paint. 3.10.3 Watertight seals shall be applied to ends of cables to prevent entrance of moisture during shipment or storage outdoors at jobsite. 3.10.4 Reels shall have protective wood lagging to prevent damage to finished cable.

3.11

Documentation 3.11.1 The following information shall be provided with quotations: a. Standard and maximum reel lengths b. Overall diameter over armor and outer jacket c. Diameter over cable assembly (not including armor and jacket) d. Cable weight per 1,000 ft (304.8 m) e. Minimum bending radius f. Maximum pulling tension and side wall loading for each cable assembly g. Minimum cable-pulling temperature h. Descriptive literature (catalogues, etc.)

Process Industry Practices

Page 5 of 6

PIP ELSWC05 300-Volt Instrumentation Tray Cable Specification

COMPLETE REVISIONAugust 2009

3.11.2 The following data, as a minimum, shall be supplied by the manufacturer for each type of cable supplied: a. Conductor - size, number, and overall conductor diameter (in inches) b. Overall diameters (in inches) of the following: 1) Insulation 2) Cable diameter over armor 3) Cable diameter over outer jacket c. Normal length of cable on reel (in feet) d. Minimum pulling tension, and bending radius (in inches and at what specific temperature) e. Approximate net and shipping weights (in pounds per 1,000 feet) 3.11.3 Documentation shall be identified by project, purchase order or contract number, and item number. 3.12 Conflict Resolution Any conflicts between the referenced documents shall be identified in writing to the purchaser for resolution. In general, when resolving conflicts, the following order of precedence shall apply: a. Purchase order b. PIP ELSWC05D Data Sheet c. This Practice, PIP ELSWC05 d. Other referenced specifications

Page 6 of 6

Process Industry Practices

COMPLETE REVISIONAugust 2009

Process Industry Practices Electrical

PIP ELSWC05D Electronic Entry Data Sheet for 300-Volt Instrumentation Tray Cable Specification

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP.

PRINTING HISTORY March 1999 Issued November 2004 Complete Revision August 2009 Complete Revision Not printed with State funds

ASSOC. PIP ELSWC05

DATA SHEET

ELSWC05D-DPAGE 1 OF 1 AUGUST 2009

300-VOLT INSTRUMENTATION TRAY CABLEISSUED FOR: FACILITY NAME/LOCATION: ITEM NAME: ITEM TAG NO.: SERVICE: UNIT: DWG. NO.: DATA PROVIDED BY: PURCHASER SUPPLIER PURCHASER/LOCATION: JOB NO: PURCHASER ORDER NO.: SUPPLIER/LOCATION: SUPPLIER ORDER/SERIAL NOS.: SUPPLIER IF NOT BY PURCHASER PROPOSAL PURCHASE AS BUILT

/

REFER TO PIP ELSWC05 FOR GENERAL REQUIREMENTS. APPLICABLE STATE AND LOCAL CODES: SITE CONDITIONS: ALTITUDE: AMBIENT TEMPERATURE: MAX: MARKINGS FOR USE (3.1.3, 3.1.4, 3.1.5): ITC-ER SOLID ALLOY INSULATION TYPE (3.3): PVC XLP FR-EPR OTHER: DIRECT BURIAL STRANDED ITC-HL THERMOCOUPLE EXTENSION CABLE (3.2.3): FT C MIN: C OUTER JACKET (3.6): OUTER JACKET MATERIAL: PVC CPE CSPE OTHER: MANUFACTURERS STANDARD OUTER JACKET COLOR: PER TABLE OTHER: CABLE LENGTH TOLERANCE (3.8): -0 TO +5% CABLE REELS (3.10): RETURNABLE WOOD LAGGING ADDITIONAL REEL MARKINGS: NON-RETURNABLE OTHER:

WIRE COLOR (3.3.2): TWISTED PAIR; BLACK AND WHITE TWISTED TRIADS; BLACK, WHITE AND RED OTHER: METALLIC SHEATH (3.5): REQUIRED CONTINUOUS CORRUGATED ALUMINUM NOT REQUIRED INTERLOCKED GALVANIZED STEEL

OTHER REQUIREMENTS:

REEL ID

CABLE TYPE

NO. PAIRS/ TRIADS

CONDUCTOR SIZE (AWG)

METALLIC SHEATH (Y/N)

LENGTH (FT)

REMARKS

SPISCO SPTECO STISCO MPISCO MPTECI MPISCI MTISCO MTISCI

1 1 1

SPISCO - SINGLE PAIR INSTRUMENT SIGNAL CABLE (OVERALL SHIELDED) SPTECO - SINGLE PAIR T/C EXTENSION CABLE (OVERALL SHIELDED) STISCO - SINGLE TRIAD INSTRUMENT SIGNAL CABLE (OVERALL SHIELDED) MPISCO - MULTI-PAIR INSTRUMENT SIGNAL CABLE (OVERALL SHIELDED) MPTECI - MULTI-PAIR T/C EXTENSION CABLE (INDIVIDUALLY AND OVERALL SHIELDED) MPISCI - MULTI-PAIR INSTRUMENT SIGNAL CABLE (INDIVIDUALLY AND OVERALL SHIELDED) MTISCO - MULTI-TRIAD INSTRUMENT SIGNAL CABLE (OVERALL SHIELDED) MTISCI - MULTI-TRIAD INSTRUMENT SIGNAL CABLE (INDIVIDUALLY AND OVERALL SHIELDED) NO. DATE REVISION DESCRIPTION BY APVD.

COMPLETE REVISIONAugust 2009

Process Industry Practices Process Control

PIP PCCEL001 Instrumentation Electrical Design Criteria

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP.

PRINTING HISTORY De