phs.pdf

Upload: cam

Post on 06-Jan-2016

18 views

Category:

Documents


0 download

TRANSCRIPT

  • 1

    Chapter 2

    Pumped Hydroelectric Storage

    Chi-Jen Yang

    Duke University, Durham, North Carolina 27708, USA. Tel. +1 919 9459075. E-mail

    address: [email protected]

    Contents

    Introduction

    Pros and Cons

    Historical Developments

    Prospects

    4.1 Revival of Conventional Pumped Hydroelectricity Storage

    4.2 Alternative and Novel Pumped Hydroelectricity Storage designs

    4.3 Retrofits of existing PHS and conventional hydropower stations

    References

    Abstract

    Pumped hydroelectric storage (PHS) is the most established technology for utility-scale

    electricity storage and has been commercially deployed since the 1890s. Since the 2000s,

    there have been revived interests in developing PHS facilities worldwide. Because most

    low-carbon electricity resources (for example, wind, solar, and nuclear) cannot flexibly

    adjust their output to match fluctuating power demands, there is an increasing need for

    bulk electricity storage due to increasing adoption of renewable energy. This chapter

    introduces the PHS technology, the pros and cons, its historical developments, and the

    prospect.

    Key Words:

    Pumped Hydroelectric Storage; Closed-loop; Pump-back; Peak Shaving

    1. Introduction:

    Pumped hydroelectric storage (PHS) is the most widely adopted utility-scale electricity

    storage technology. Furthermore, PHS provides the most mature and commercially

  • 2

    available solution to bulk electricity storage. It serves to stabilize the electricity grid

    through peak shaving, load balancing, frequency regulation, and reserve generation.

    Japan currently has the largest installed PHS capacity in the world [1], followed by China

    [2] and the United States [3]. China currently has the most aggressive plan to expand

    PHS installation, with 14 GW under construction and many more planned. China is

    expected to surpass Japan in installed PHS capacity by 2018. Table 1 shows the installed

    PHS capacities in major countries [2, 3, 4, 5].

    Table 1. Installed PHS capacities.

    Country

    Installed PHS Capacity

    /(MW)

    Japan 27 438

    China 21 545

    USA 20 858

    Italy 7 071

    Spain 6 889

    Germany 6 388

    France 5 894

    India 5072

    Austria 4 808

    Korea, South 4 700

    United Kingdom 2 828

    Switzerland 2 687

    Taiwan 2 608

    Australia 2 542

    Poland 1 745

    Portugal 1 592

    South Africa 1 580

    Thailand 1 391

    Belgium 1 307

    Russia 1 246

    Czech Republic 1 145

    Luxembourg 1 096

    Bulgaria 1 052

    Iran 1 040

    Slovakia 1 017

  • 3

    Argentina 974

    Norway 967

    Ukraine 905

    Lithuania 900

    Philippines 709

    Greece 699

    Serbia 614

    Morocco 465

    Ireland 292

    Croatia 282

    Slovenia 185

    Canada 174

    Romania 53

    Chile 31

    Brazil 20

    A PHS facility is typically equipped with pumps and generators connecting an upper and

    a lower reservoir (Figure 1). The pumps utilize relatively cheap electricity from the

    power grid during off-peak hours to move water from the lower reservoir to the upper

    one to store energy. During periods of high electricity demand (peak-hours), water is

    released from the upper reservoir to generate power at a higher price.

  • 4

    Figure 1. PHS Diagram.

    There are two main types of PHS facilities: (1) pure or off-stream PHS, which rely

    entirely on water that were previously pumped into an upper reservoir as the source of

    energy; (2) combined, hybrid, or pump-back PHS, which use both pumped water and

    natural stream flow water to generate power [4]. Off-stream PHS is sometimes also

    referred to as closed-loop systems. However, some may define closed-loop systems more

    strictly as being entirely isolated from natural ecosystems. The U.S. Federal Energy

    Regulatory Commission defines closed-loop pumped storage as projects that are not

    continuously connected to a naturally-flowing water feature [5].

    The efficiency of PHS varies quite significantly due to the long history of the technology

    and the long life of a facility. The round-trip efficiency (electricity generated divided by

    the electricity used to pump water) of facilities with older designs may be lower than

    60%, while a state-of-the-art PHS system may achieve over 80% efficiency.

  • 5

    2. Pros and Cons

    By storing electricity, PHS facilities can protect the power system from outages. Coupled

    with advanced power electronics, PHS systems can also reduce harmonic distortions, and

    eliminate voltage sags and surges. Among all kinds of power generators, those peak-load

    generators typically produce electricity at much higher costs than the base-load ones.

    PHS provides an alternative to peaking power by storing cheap base-load electricity and

    releasing it during peak hours.

    PHS facilities provide very large capacities of electricity, with low operation and

    maintenance cost, and high reliability. The levelized storage cost for electricity using

    PHS is usually much lower than other electricity storage technologies.

    There are several drawbacks to PHS technology. The deployment of PHS requires

    suitable terrains with significant elevation difference between the two reservoirs and

    significant amount of water resource. The construction of a PHS station typically takes

    many years, sometimes over a decade. Although the operation and maintenance cost is

    very low, there is a high upfront capital investment in civil construction, which can only

    be recouped over decades.

    Environmental impacts are also serious concerns and have caused many cancellations of

    proposed PHS projects. Conventional PHS construction sometimes involves damming a

    river to create a reservoir. Blocking natural water flows disrupt the aquatic ecosystem and

    the flooding of previously dry areas may destroy terrestrial wildlife habitats and

    significantly change the landscape. Pumping may also increase the water temperature and

    stir up sediments at the bottom of the reservoirs and deteriorate water quality. PHS

    operation may also trap and kill fish. There are technologies to mitigate the ecological

    impacts. Fish deterrent systems could be installed to minimize fish entrapment and

    reduce fish kill. The water intake and outlet could be designed to minimize the turbulence.

    An oxygen injection system could also compensate for the potential oxygen loss due to

    warming of the water because of pumping. In some cases, the PHS system may serve to

    stabilize water level and maintain water quality [6]. The potential impacts of PHS

    projects are site-specific and must be evaluated on a case-by-case basis. Governments

    usually require an environmental impact assessment before approving a PHS project.

    Most PHS facilities have good safety records. Nevertheless, the upper reservoir failure of

    Taum Sauk PHS station in the United States should be heeded as a reminder of its

    potential danger. On December 14, 2005, the upper reservoir of Taum Suak was

    overfilled, and the embankment was then overtopped and breached. The suddenly leased

    water washed away over one square kilometer of forest, uprooted all the trees and

    obliterated a house in its path. Although the Taum Sauk PHS station was later repaired

  • 6

    and brought back to operation in 2010, the reservoir failure incident should provide

    important lessons for future PHS design, construction and operation.

    3. Historical Development

    The earliest PHS in the world appeared in the Alpine regions of Switzerland, Austria, and

    Italy in the 1890s. The earliest designs use separate pump impellers and turbine

    generators. Since the 1950s, a single reversible pump-turbine has become the dominant

    design for PHS [7]. The development of PHS remained relatively slow until the 1960s,

    when utilities in many countries began to envision a dominant role for nuclear power.

    Many PHS facilities were intended to complement nuclear power in providing peaking

    power.

    In the 1990s, the development of PHS significantly declined in many countries. Many

    factors may have contributed to the decline. Low natural gas prices during this period

    make gas turbines more competitive in providing peaking power than PHS.

    The earliest PHS facilities were built in Italy and Switzerland in the 1890s [7]. Before the

    1950s, most of the PHS facilities were located in Europe. The United States completed its

    first PHS station in 1928. Japan built its first PHS in 1934 and China in 1968. Since the

    1950s, the adoption of PHS has gradually spread all over the world. As of 2014, the U.S.

    DOE Global Energy Storage Database recorded over three hundred operating PHS

    stations with total capacity of 142 GW in 41 countries [8].

    The design and site selection for PHS facilities are greatly influenced by national policies.

    Japan, China, and the United States have the largest PHS capacities in the world. Table 2,

    3, and 4 list the PHS facilities in Japan, China, and the United States. The distinctive

    policies and regulatory regimes for PHS in Japan, China, and the United States offer

    interesting contrasts and may reveal useful policy insights.

    The buildup of PHS capacities in Japan has been relatively steady over several decades.

    The Japanese power sector is mainly composed of vertically-integrated regional electric

    power utilities, which build, own and operate the PHS facilities. The vertically integrated

    power sector structure has provided a stable and predictable business environment that is

    favorable to the investments in PHS. The path of PHS development PHS in Japan is an

    epitome of PHS development worldwide. Before the early 1960s, PHS facilities were

    rare and small, mostly of hybrid design. The deployment started to accelerate since the

    1960s and continued throughout the 1990s. Since the 1970s, pure/off-stream PHS has

    become the dominant design, which is likely a result of increased concerns for ecological

    impacts of the hybrid systems. In addition to having the worlds largest PHS capacities, Japan is also the world leader in employing seawater PHS and variable-speed PHS.

  • 7

    Table 2 PHS stations in Japan.

    Plant Name

    (Japanese)

    Plant Name

    (English) Location Type

    Rating/

    (MW)

    Commission

    Year

    Ikejirigawa Nagano Prefecture Hybrid 2 1934 Omorikawa Kochi Prefecture Hybrid 12 1959 Morotsuka Miyazaki Prefecture Hybrid 50 1961 Hatakenagi No.1 Shizuoka Prefecture Hybrid 137 1962 Mio Nagano Prefecture Hybrid 36 1963 Ikehara Nara Prefecture Hybrid 350 1964 Ananaigawa Kochi Prefecture Hybrid 13 1964 Shiroyama Kanagawa Prefecture Pure 250 1965 Yagisawa Gunma Prefecture Hybrid 240 1965 Shinnaruhagawa Okayama Prefecture Hybrid 303 1968 Nagano Fukui Prefecture Hybrid 220 1968 Kagetaira Tokushima Prefecture Hybrid 47 1968 Azumi Nagano Prefecture Hybrid 623 1969 Takane No.1 Gifu Prefecture Hybrid 340 1969 Midono Nagano Prefecture Hybrid 245 1969 Kisen'yama Kyoto Pure 466 1970 Shintoyone Aichi Prefecture Hybrid 1 125 1972 Numappara Tochigi Prefecture Pure 675 1973 Okutataragi Hyogo Prefecture Pure 1 932 1974 Niikappu Hokkaido Hybrid 200 1974 Ohira Kumamoto Prefecture Pure 500 1975 Namwon Hiroshima Prefecture Pure 620 1976 Mazekawa No.1 Gifu Prefecture Hybrid 288 1976 Futai Dam Niigata Prefecture Pure 1 000 1978 Shin-Takasegawa Nagano Prefecture Hybrid 1 280 1979 Okuyoshino Nara Prefecture Pure 1 206 1980 Okuyahagi No.2 Aichi Prefecture Pure 780 1980 Okuyahagi No.1 Aichi Prefecture Pure 323 1980 Tamahara Gunma Prefecture Pure 1 200 1981 Motokawa Kochi Prefecture Pure 615 1982 Daini Numazawa Fukushima Prefecture Pure 460 1982 Takami Hokkaido Hybrid 200 1983

  • 8

    Matanoagawa Tottori Prefecture Pure 1 200 1986 Tenzan Saga Prefecture Pure 600 1986 Imaichi Tochigi Prefecture Pure 1 050 1988 Shimogo Fukushima Prefecture Pure 1 000 1988 Okawachi Hyogo Prefecture Pure 1 280 1992 Okumino Gifu Prefecture Pure 1 500 1994 Shiobara Tochigi Prefecture Pure 900 1994 Futai Dam No.2 Niigata Prefecture Pure 600 1996 Kazunogawa Yamanashi Prefecture Pure 1 200 1999

    Okinawa Seawater

    Pumped Hydro Okinawa Prefecture Pure 30 1999

    Kannagawa Gunma Prefecture Pure 940 2005 Omarugawa Miyazaki Prefecture Pure 1 200 2007 Shumarinai Hokkaido Hybrid 1 2013 Kyogoku Hokkaido Pure 200 2014

    China is a latecomer in the worldwide PHS deployment, but it is catching up quickly.

    With the largest PHS capacities planned and under construction, China will soon

    overtake Japan as the host of the largest PHS capacities in the world. Most of the PHS

    facilities in China are relative new, with large capacity and off-steam design.

    Chinas regulatory regime for PHS has been through great changes in the past two decades. Before 2004, most of the PHS facilities in China were built by local

    governments and local grid companies with diverse pricing models. In 2002, China

    restructured its power sector by separating them into 2 state-owned grid companies and 5

    power generation corporations. In 2004, the National Development and Reform

    Commission promulgated a regulation which specified that PHS stations are transmission

    facilities and should be constructed and managed by the grid companies, and that the

    construction and operation costs of PHS should be incorporated into the operation costs

    of the grid companies [9]. The decision to treat PHS as transmission facilities has

    contributed to the rapid expansion of PHS in China.

    Table 3 PHS stations in China.

    Plant Name

    (Chinese)

    Plant Name

    (English) Province Type

    Rating/

    (MW)

    Commission

    Year

  • 9

    Gangnan Hebei Hybrid 11 1968

    Miyun Beijing Hybrid 22 1975

    Panjiakou Hebei Hybrid 270 1992

    Cuntangkou Sichuan Pure 2 1992

    Guangzhou Phase 1 Guangdong Pure 1,200 1994

    Shisanling Beijing Pure 800 1997

    Yangzhuoyong Tibet Pure 90 1997

    Xikou Zhejiang Pure 80 1998

    Tianhuangping Zhejiang Pure 1 800 2000

    Guangzhou Phase 2 Guangdong Pure 1 200 2000

    Xianghongdian Anhui Hybrid 80 2000

    Tiantang Hubei Pure 70 2001

    Shahe Jiangsu Pure 100 2002

    Huilong Henan Pure 120 2005

    TONGBAI Zhejiang Pure 1 200 2006

    Hakusan Jilin Hybrid 300 2006

    Taian Shandong Pure 1 000 2007

    Langyashan Anhui Pure 600 2007

    Xilongchi Shanxi Pure 1 200 2008

    Yixing Jiangsu Pure 1 000 2008

    Zhanghewan Hebei Pure 1 000 2008

    Huizhou Guangdong Pure 2 400 2009

    Heimifeng Phase 1 Hunan Pure 1 200 2009

    Bailianhe Hubei Pure 1 200 2010

    Baoquan Henan Pure 1 200 2011

    Pushihe Liaoning Pure 1 200 2012

    Xiangshuijian Anhui Pure 1 000 2012

    Xianyou Fujian Pure 1 200 2013

  • 10

    Most of the PHS facilities in the United States were built in the 1970s and 1980s. Since

    the 1990s, the construction of PHS slowed down in the United States. Environmental

    concerns caused the cancellation of several PHS projects and significantly prolonged the

    permitting process. Power sector restructure also contributed to this slowdown. During

    the 1990s, the United States started to restructure the power sector by separating

    generation from transmission. The nature of energy storage falls into the gray area

    between generation and transmission [10]. Because the net electricity output of PHS

    operation is negative, a PHS facility usually cannot qualify as a power generator.

    Although their crucial load-balancing and ancillary services to the grid and reduces the

    needs for transmission upgrades, PHS facilities are not recognized as parts of the

    transmission infrastructure [11]. This confusion in business models has deterred the

    development of PHS in the United States.

    Table 4 PHS stations in the United States.

    Plant Name County State

    Type

    Rating/

    (MW)

    Commission

    Year

    Rocky River Litchfield CT Hybrid 31 1928

    Flatiron Larimer CO Hybrid 9 1954

    Hiwassee Dam Cherokee NC Hybrid 95 1956

    Lewiston Niagara Niagara NY Hybrid 240 1962

    Taum Sauk Reynolds MO Pure 408 1963

    Yards Creek Warren NJ Pure 453 1965

    Cabin Creek Clear Creek CO Pure 300 1967

    W R Gianelli Merced CA Pure 424 1967

    Muddy Run Lancaster PA Pure 1 072 1967

    ONeill Merced CA Pure 25 1968

    Thermalito Butte CA Hybrid 83 1968

    Edward C Hyatt Butte CA Hybrid 293 1968

    Salina Mayes OK Pure 288 1970

    FirstEnergy Seneca Warren PA Pure 469 1970

    Smith Mountain Franklin VA Hybrid 247 1970

    Mormon Flat Maricopa AZ Hybrid 54 1971

    Horse Mesa Maricopa AZ Hybrid 100 1972

    Degray Clark AR Hybrid 28 1972

    Northfield Mountain Franklin MA Pure 940 1973

    Ludington Mason MI Pure 1 979 1973

    Blenheim Gilboa Schoharie NY Pure 1 000 1973

    Jocassee Pickens SC Pure 612 1974

  • 11

    Bear Swamp Berkshire MA Pure 600 1974

    Castaic Los Angeles CA Hybrid 1 275 1976

    Carters Murray GA Hybrid 250 1977

    Fairfield Pumped Storage Fairfield SC Pure 511 1978

    Raccoon Mountain Hamilton TN Pure 1 714 1979

    Wallace Dam Hancock GA Hybrid 209 1980

    Grand Coulee Grant WA Hybrid 314 1980

    Harry Truman Benton MO Pure 161 1981

    Mount Elbert Lake CO Pure 200 1983

    Helms Pumped Storage Fresno CA Pure 1 053 1984

    Clarence Cannon Ralls MO Hybrid 31 1984

    Bath County Bath VA Pure 2 862 1985

    J S Eastwood Fresno CA Pure 200 1987

    Bad Creek Oconee SC Pure 1 065 1991

    Waddell Maricopa AZ Pure 40 1993

    North Hollywood Los Angeles CA Hybrid 5 1993

    Rocky Mountain Floyd GA Pure 848 1995

    Richard B Russell Elbert GA Hybrid 328 2002

    Lake Hodges San Diego CA Pure 42 2012

    The diverged paths of PHS development in Japan, China, and the United States have

    shown that the national regulatory and institutional environments have tremendous

    impacts on the deployment of PHS. PHS facilities are large facilities that require huge

    upfront capital investments, and the paybacks are spread over many decades. If a

    government wishes to facilitate the development of PHS, it needs to provide a stable and

    predictable regulatory environment, and a reasonable pricing scheme that allow the PHS

    facilities to be compensated for their services to the transmission grid.

    4. Prospects

    In recent years, due to increasing concern for global warming and the call to de-carbonize

    electricity, there has been increasing commercial interest in PHS [12]. Developers are

    actively pursuing new PHS projects around the world.

    4.1 Revival of conventional PHS

    More than 100 new PHS plants with about 74 GW capacities worldwide are expected to

    be in operation by 2020 [13]. China has the most aggressive plan. In 2014, the Chinese

    government announced its plan to more than quadruple its current PHS installations to a

    total capacity of 100 GW by 2025 [14]. Driven by the need to accommodating rapid

  • 12

    growth of intermittent renewable electricity, Europe is also witnessing a renaissance of

    PHS, particularly in Spain, Switzerland, and Austria, with 27 GW new PHS capacity

    expected by 2020 [15]. Although Japan already has the highest density of PHS

    installation in the world, Japanese power companies are continuing to develop more PHS

    plants. The United States is also experiencing a revival of PHS development. In 2014, the

    U.S. Federal Energy Regulatory Commission issued licenses to construct and operate two

    new PHS facilities (1.3 GW Eagle Mountain PHS and 400MW Iowa River PHS).

    Another application for construction and operation license (for the 1 GW Parker Noll

    PHS) is currently under review. In addition, there are over 40 proposed PHS projects

    currently conducting feasibility studies with issued preliminary permits. With the mature

    technology and high volume of commercial development activities, PHS will certainly

    remain the most dominant energy storage technology in the foreseeable future.

    4.2 Alternative and novel PHS designs

    Variable Speed PHS: Most existing PHS facilities are equipped with fixed-speed pump

    turbine. While those fixed-speed PHS facilities may provide economical bulk electricity

    storage, they can only provide frequency regulation during its generating mode, but not in

    pumping mode. With the increasing adoption of variable power sources such as wind and

    solar, there is an increasing demand for frequency regulation. New variable speed

    technology allows PHS facilities to regulate frequency at both pumping and generating

    modes. Japan has pioneered the variable-speed PHS technology and has successfully

    operated such systems at the Okawachi PHS station for over twenty years [16, 17].

    European countries are actively introducing variable speed PHS in recent years in order

    to accommodate more variable renewable electricity in their power portfolios [18].

    Seawater PHS: In addition to the worldwide revived interests in developing conventional

    PHS projects, many developers are also proposing new approaches. Japan has pioneered

    seawater PHS. The Okinawa seawater PHS station, which has commenced operation in

    1999, is the worlds first seawater PHS system [19]. The Okinawa PHS station uses the open sea as the lower reservoir together with a constructed upper reservoir at 150 meters

    above sea level. New seawater projects have been proposed in Ireland, Greece, Belgium,

    and the Netherlands [20, 21, 22, 23]. The energy islands concept proposed by the Dutch

    consulting company DNV KEMA has an unusual approach; they plan to use the open sea

    as the upper reservoir, and construct the lower reservoir by dredging and building a ring

    of dikes at a depth of 50 m below sea level.

    Underground PHS: Researchers since the 1970s [24], have proposed the possibility of

    utilizing underground caverns as lower reservoirs for PHS projects but so far none have

    been built [25]. The commercial interests in developing underground PHS have

    resurfaced in recent years in the United States. Several U.S. developers have received

  • 13

    preliminary permits to study the feasibility of building underground PHS facilities at their

    identified sites. A British company Quarry Battery is also working on developing

    underground PHS facilities with abandoned quarries [26].

    Compressed Air PHS: A promising innovative design (Figure 2) is to replace the upper

    reservoir in PHS with a pressurized water container [27]. The air within the pressure

    vessel becomes pressurized when water is pumped into the vessel. Instead of storing

    potential energy in elevated water, the proposed compressed air pumped hydro system

    stores the energy in compressed air. This innovative design could potentially free PHS

    from the geographic requirements and make it feasible at almost any location with

    flexible and scalable capacity. This concept is discussed in more detail in chapter 7.

    Figure 2. Diagram of compressed air PHS

    Undersea PHS: Another innovative concept (Figure 3) is to utilize the water pressure at

    the bottom of the sea to store electricity from off-shore wind turbines [28]. The system

    places submerged pressure vessels (hollow concrete tank) on the sea floor. It uses

    electricity to pump water out of the tank to store energy, and generate electricity when

    seawater is filling into the tank through the generator. This concept is further discussed in

    chapter 6.

  • 14

    Figure 3. Diagram of undersea PHS

    4.3 Retrofits of existing PHS and conventional hydropower stations

    Many existing PHS facilities were built many decades ago and therefore were equipped

    with outdated and inefficient technology. There is a significant potential in increasing

    PHS capacity simply by renovating and upgrading the existing PHS facilities. Upgrades

    to old PHS facilities typically include replacing outdated pumps/turbines, impellers, and

    control systems with new advanced equipment. Many existing PHS station may increase

    the capacity by 15% to 20% and efficiency by 5% to 10% [7]. In addition, many existing

    conventional hydropower stations could be re-engineered to add a lower reservoir and

    pump-back units to pump the water back to the upper reservoir during off-peak hours,

    and become combined PHS stations for use with intermittent energy from renewable

    sources such as wind turbines and solar panels.

    Although PHS may be an essential enabling technology for de-carbonizing electricity, the

    political will to mitigate carbon dioxide and to remove regulatory barriers for PHS is far

    from certain. The price of natural gas is also a key determinant in the future of PHS.

    Because PHS is essentially a peak-load technology, which competes directly with gas-

  • 15

    fired power, low natural gas price may render PHS uncompetitive. The vision of de-

    carbonizing electricity and how PHS fits into it, will likely vary from country to country.

    References

    [1] Electrical Japan. . http://agora.ex.nii.ac.jp/earthquake/201103-eastjapan/energy/electrical-

    japan/type/5.html.ja (accessed October 20, 2014)

    [2] W. Peng, D. Chen. Some considerations on the development of pumped hydroelectric

    storage power station in China (In Chinese: ). State Electricity Regulatory Commission, Peoples Republic of China. 2010. http://www.serc.gov.cn/jgyj/ztbg/201006/t20100621_13195.htm (assessed Nov. 24, 2010)

    [3] EIA. Electricity: Form EIA-860 detailed data 2012. Energy Information

    Administration, U.S. Department of Energy. Washington DC. 2012.

    http://www.eia.gov/electricity/data/eia860/

    [4] Army Corps. Engineering and design - hydropower. No. 1110-2-1701. Army Corps of

    Engineers, Department of the Army. Washington, DC. 1985.

    [5] U.S. Federal Energy Regulatory Commission.

    http://www.ferc.gov/industries/hydropower/gen-info/licensing/pump-storage.asp (accessed October 21, 2014)

    [6] C.-J. Yang, R. Jackson. Opportunities and barriers to pumped-hydro energy storage in

    the United States. Renewable and Sustainable Energy Reviews 15 (2011) 839844.

    [7] R. Baxter. Energy Storage: A Nontechnical Guide, PennWell, Tulsa, OK, 2006.

    [8] Available from: http://www.energystorageexchange.org/

    [9] M. Zeng, K. Zhang, D. Liu. Overall review of pumped-hydro energy storage in China:

    Status quo, operation mechanism and policy barriers. Renewable and Sustainable Energy

    Reviews 17 (2013) 3543.

    [10] APS Panel on Public Affairs Committee on Energy Environment. Challenges of

    Electricity Storage Technologies. American Physical Society, 2007.

    [11] FERC Encourages Transmission Grid Investment. Docket No. ER06-278-000.

    Federal Energy Regulatory Commission, Washington, DC; March 20, 2008.

  • 16

    [12] J.P. Deane, B.P. Gallachir, E.J. McKeogh. Techno-economic review of existing and new pumped hydro energy storage plant. Renewable and Sustainable Energy Reviews 14

    (2010) 12931302.

    [13] Ecoprog GmbH. 2013. The World Market for Pumped-Storage Power Plants. Kln,

    Germany.

    [14] Xinhuanet, 2014. http://news.xinhuanet.com/energy/2014-11/19/c_127223035.htm

    [15] M. Zuber. Renaissance for Pumped Storage in Europe, Hydro Review Worldwide 19

    (2011). http://www.hydroworld.com/articles/print/volume-19/issue-3/articles/new-

    development/renaissance-for-pumped-storage-in-europe.html

    [16] O. Nagura, M. Higuchi, K. Tani, T. Oyake. Hitachis adjustable-speed pumped-stroage system contributing to prevention of global warming. Hitachi Review 59 (2010)

    99105. [17] J.M.Henry, F. Maurer, J-L Drommi, T. Sautereau. Converting to variable speed at a

    pumped-storage plant. Hydro Review Worldwide 21 (2013).

    http://www.hydroworld.com/articles/print/volume-21/issue-5/articles/pumped-

    storage/converting-to-variable-speed-at-a-pumped-storage-plant.html

    [18] N. Lefebvre, M. Tabarin, O. Teller. A solution to intermittent renewable using

    pumped hydropower. Renewable Energy World, March/April 2015. 4957.

    [19] Available from: http://www.kankeiren.or.jp/kankyou/en/pdf/en108.pdf

    [20] E. McLean, D. Kearney. An evaluation of seawater pumped hydro storage for

    regulating the export of renewable energy to the national grid. Energy Procedia 46 (2014)

    152160. [21] D.A, Katsaprakakis, D.G. Christakis, I. Stefanakis, P. Spanos, N. Stefanakis. 2013.

    Technical details regarding the design, the construction and the operation of seawater

    pumped storage systems. Energy 55, 619630. [22] M. LaMonica. A manmade island to store wind energy. MIT Technology Review,

    February 5, 2013.

    [23] Available from: http://earthtechling.com/2013/01/energy-island-for-wind-power-

    storage-draws-belgiums-interest/

    [24] S.W. Tam, C.A. Blomquist, G.T. Kartsounes. Underground pumped hydro storagean overview. Energy Sources 4 (1979) 329351. [25] W.F. Pickard. 2012. The History, Present State, and Future Prospects of

    Underground Pumped Hydro for Massive Energy Storage. Proceedings of the IEEE 100,

    473483.

  • 17

    [26] Available from: http://www.quarrybatterycompany.com/

    [27] H. Wang, L.Wang, X. Wang, E. Yao. A Novel Pumped Hydro Combined with

    Compressed Air Energy Storage System. Energies 6 (2013) 15541567. [28] A.A. Slocum, G.E. Fennell, G. Dundar B.G. Hodder J.D.C. Meredith, M.A. Sager.

    Ocean renewable energy storage (ORES) system: analysis of an undersea energy storage

    concept. Proceedings of the IEEE 101 (2013) 906924.