Jay Johnson 24 June, 2011 Slide 1/18 Sandia National Laboratories is a multi-program laboratory managed and operated by Sandia Corporation, a wholly owned subsidiary of Lockheed Martin Corporation, for the U.S. Department of Energy's National Nuclear Security Administration under contract DE-AC04- 94AL85000. This work was funded by the US Department of Energy Solar Energy Technologies Program. Photovoltaic DC Arc Fault Detector Testing at Sandia National Laboratories Jay Johnson 1 , Birger Pahl 2 , Charles Luebke 2 , Tom Pier 2 , Theodore Miller 3 , Jason Strauch 1 , Scott Kuszmaul 1 , and Ward Bower 1 1 Sandia National Laboratories, Albuquerque, NM 2 Eaton Corporation, Milwaukee, WI 3 Eaton Corporation, Pittsburgh, PA

Upload: others

Post on 14-Oct-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 1/18

Sandia National Laboratories is a multi-program laboratory managed and operated by Sandia Corporation, a wholly owned subsidiary of Lockheed Martin Corporation, for the U.S. Department of Energy's National Nuclear Security Administration under contract DE-AC04-

94AL85000. This work was funded by the US Department of Energy Solar Energy Technologies Program.

Photovoltaic DC Arc Fault Detector Testing at Sandia National Laboratories

Jay Johnson1, Birger Pahl2, Charles Luebke2, Tom Pier2, Theodore Miller3, Jason Strauch1, Scott Kuszmaul1, and Ward Bower1

1 Sandia National Laboratories, Albuquerque, NM 2 Eaton Corporation, Milwaukee, WI3 Eaton Corporation, Pittsburgh, PA

Page 2: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 2/18

Presentation Outline

PV Arc Fault Background

Sandia National Labs Overview

Arc Fault Detection Challenges

Arc Fault Experiments• Inverter noise• Arcing noise• Arc vs baseline comparison on

multiple PV strings

Conclusions

Page 3: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 3/18

Sandia Contribution to PV Arc Fault Detection and Mitigation Requirements

Arc faults in PV systems cause fires.

Module damage modeling -80.0

-70.0

-60.0

-50.0

-40.0

-30.0

-20.0

-10.0

0.0

10.0

20.0

1.00E+00 1.00E+01 1.00E+02 1.00E+03 1.00E+04 1.00E+05 1.00E+06 1.00E+07

Mag

nitu

de (

dB)

Frequency (Hz)

Frequency Response for All Wire Orientations

Scan 1.1

Scan 1.2

Scan 1.3

Scan 2.1

Scan 2.2

Scan 2.3

Scan 3.1

Scan 3.2

Scan 3.3

Scan 4.1

Scan 4.2

Scan 4.3

Scan 2.1-2.3

Scan 1.1-1.3

Scan 3.1-3.3

Scan 4.1-4.3

RF Effects

2011 National Electrical Code ®

requires detection and interrupt of arc faults in PV systems.

Sandia Research: Arc modeling and electrical propagation studies.

Arc detection using frequency content of the PV string

Industry responds by creating PV AFCI devices.

Sandia research helps industry make better products.

Industry works with Sandia to test AFCIs.

Page 4: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 4/18

Why Test Arc Detection at Sandia National Laboratories?

Sandia National Labs is a resource for PV companies, technologies, and components.

• SNL has partnerships with inverter, module, BOS components, AFD, and AFCI manufacturers.

Distributed Energy Technologies Laboratory (DETL)

• Test bed for novel renewable energy technologies.

• Reconfigurable PV arrays with diverse portfolio of PV technologies: Different manufacturers, ages, and I-V

characteristics Range of connectors, DC disconnects, combiner

boxes, line lengths, and inverters. UL Subject 1699B does not cover all testing

cases or scenarios.• DETL can demonstrate AFCI robustness.

Distributed Energy Technologies Laboratory

Page 5: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 5/18

Arc Fault Detection Challenges

Some AFCIs use the AC frequency content of the string for detection Two challenges involved with arc detection using a remote arc fault detector:

1. Missed or delayed detection due to arc frequency attenuation in PV components (e.g., modules, connectors, bypass diodes)

2. Nuisance tripping due to noise from electromagnetic coupling (crosstalk), inverter switching, and radio frequency (RF) effects

“Pink” AC noise Modules/connectors change frequency content

RF phenomena, crosstalk noise, antenna effects

Inverter switching noise

Page 6: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 6/18

Arc Fault Experiments

Arc Fault Generator

Questions What is the influence of inverters on string noise? Are there frequency bands which are excited with an arc? Does crosstalk trip the AFCI? Do antenna effects and RF phenomenon influence detection? Does arc fault location change the arcing frequency content? Do DC/DC converters change the PV string AC spectrum?

DAQ System 10 MHz Current and Voltage

Time Series Data

PV String Testing Options at DETL

Basic Testing Setup

Page 7: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 7/18

Simulated Arc Fault

Page 8: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 8/18

String Noise Varies with Inverter Type, PV Module Technology, and Array Topology

120 Hz noise from the inverter compared to a

resistive load bank noise.

MPPT effect on current.

4 kW Inverter, 3 Strings of 2 540-W a-Si BIPV Modules

75 kW 3-phase Inverter, 8 Strings of 12 175-W a-Si Modules

3 kW Inverter, 4 Strings of 6 200-W c-Si Modules

20 kW 3-phase Inverter, 1 String of 21 90-W c-Si Modules

4.8 kW Inverter, 4 Strings of 6 175-W c-Si Modules

20 kW 3-phase Inverter, 1 String of 22 80-W c-Si Modules

Qualitative String Current Noise Comparison

Noi

se A

mpl

itude

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0Time (s)

Page 9: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 9/18

String Noise in Frequency Domain

Switching Frequency for Inverter

120 Hz Noise

Single-Sided Amplitude Spectrum of String Current

Cur

rent

Noi

se A

mpl

itude

(dB

)

Red line is the average of the current noise for

each decade.

101 102 103 104 105 106

Frequency (Hz)

-20

-40

-60

-80

-100

-120

-140

-160

-180

-200

Page 10: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 10/18

Testing Configurations

Baseline with an inverter.

Baseline without an inverter

Arc with an inverter.

Arc without an inverter

Page 11: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 11/18

DC String Current during an Arc Fault

Arcs, inverter

Arcs, load bankNo arcs, inverter

Arc fault begins at 0 sec.

No arcs, load bank

DC String Current vs Time

Strin

g C

urre

nt (A

)

Time (s)

3.8

4.0

3.6

2.4

3.4

3.2

3.0

2.8

2.6

0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.2 -0.1

Page 12: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 12/18

Arcs, inverter

Arcs, load bankNo arcs, inverter

No arcs, load bank

Arc fault begins at 0 sec.

DC String Voltage during an Arc Fault

DC String Voltage vs Time

Time (s)0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.2 -0.1

285

290

280

350

275

370

365

360

355

Strin

g Vo

ltage

(V)

Page 13: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 13/18

Arcs, inverter

No arcs, inverter

Arcs, load bank

No arcs, load bank

AC Arc Fault Frequencies on PV Strings

Single-Sided Amplitude Spectrum of String Current

Frequency (Hz)101 102 103 104 105 106

-140

-20

-40

-60

-80

-100

-120

-160

-180

-200

0

Cur

rent

Noi

se A

mpl

itude

(dB

)

Page 14: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 14/18

Binned Arc Current and Voltage Frequencies

Arcs, inverter

No arcs, inverter

Arcs, no inverter

No arcs, no inverter

String Current Spectrum (Binned)

Frequency (Hz)

Cur

rent

Noi

se A

mpl

itude

(dB

) What’s the best way to differentiate arcing and non-arcing strings?

101 102 103 104 105 106

-20

-40

-60

-80

-100

-120

-30

-50

-70

-90

-110

Page 15: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 15/18

Arc Fault Generation on Arrays

Baselines

Arc on String 3

Arc on String 2Arc on String 1

Same 3-phase inverter with 3 different strings:• 21 90-W c-Si modules, 22 80-W p-Si modules, 22 80-W c-Si modules

Single-Sided Amplitude Spectrum of String Current

Cur

rent

Noi

se A

mpl

itude

(dB

)

Hard to differentiate regionEasy to differentiate regionHard to differentiate region

101 102 103 104 105 106

-140

-20

-40

-60

-80

-100

-120

-160

-180

-200

Page 16: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 16/18

Conclusions

2011 NEC requires DC arc fault circuit protection on photovoltaic systems with dc source circuits, dc output circuits, or both, on or penetrating a building operating at a PV system maximum system voltage of 80 volts or greater.

Sandia National Laboratories provides an excellent testing facility for arc fault detectors and arc fault circuit interrupters because of the diversity of PV technologies.

Experimental work with Eaton has revealed some avenues for robust detection as well as some arc fault detection challenges.

• Arcing can excite certain frequency bands above the baseline (non-arcing) levels.

• Inverters generate a lot of baseline noise across the spectrum, but especially at 120 Hz, switching frequencies and harmonics.

Additional experimentation is recommended to further understand arcing phenomenon and signal propagation in a broad range of PV systems.

Page 17: Photovoltaic DC Arc Fault Detector Testing at Sandia ...€¦ · Jay Johnson 24 June, 2011 Slide 2/18 Presentation Outline PV Arc Fault Background Sandia National Labs Overview Arc

Jay Johnson 24 June, 2011 Slide 17/18

Acknowledgements

DETL Technicians• Armando Fresquez• Mike Montoya• Nelson Opell

Engineering Assistance• Sigfredo Gonzalez

US Department of Energy Solar Energy Technologies Program