phase sequence phase failure relay fk-04/04p, fk-14/14p

1
PHASE SEQUENCE PHASE FAILURE RELAY FK-04/04P, FK-14/14P, FKV-14/14P, FKV-03, FS-R FK-04/04P, FK-14/14P, FKV-14/14P, FKV-03 and FS-R phase failure relays are designed to avoid any failure of three phase motors (which works phase sequence) caused from network. FK-04P, FK-14P and FKV-14P types additionally avoids failure of motor caused thermal overload. FKV-14/14P Connection Diagram FK-14/14P Connection Diagram FK-04/04P Connection Diagram PTC 1 2 3 L1 N L2 L3 N 2A L1 L2 L3 Kontaktör M 3 ~ PTC FK-04P FKV-03 N 2A L1 L2 L3 L3 L2 N L1 1 2 3 M 3 ~ FKV-03 Connection Diagram Usage of Device and Working Principle Make the connections according to the diagram. Normal Operation (No Error): When the phases are at normal values and the phase sequence is correct, the relay gets activated and the OUT LED is on. Asymmetry Error: When any phase goes out of the normal range, the ERR LED flashes (at 2 second intervals), the OUT LED is off and the relay deactivated. Phase sequence reverse (Phase Sequence Error): The ERR LED lights steady, the OUT LED is off and the relay gets deactivated. PTC Errpr: In models with PTC, when the temperature of the motor exceeds the rated value, the ERR LED is flashes (at 1 second intervals), the OUT LED is off and the relay deactivates. When the temperature value returns to the nominal values, the relay gets activated again and the OUT LED lights up. Relay is Activated: 2 (COM) and 3 (NC) short circuit, 1 (NC) and 2 (COM) open circuit. Relay is De-activated: 2 (COM) and 1 (NC) short circuit, 3 (NC) and 2 (COM) open circuit. If the PTC function is will not to be used: If not using PTC in the FKV-14P, short the PTC (P) terminal to Neutral (N). If not using PTC in FK-04P and FK-14P, short the PTC ( ) terminals. FKV-03: There is no ERR LED on this device. In case of Asymmetry or Phase Sequence Errors, OUT LED goes out and the relay gets deactivated. PTC Maintenance Switch off the device and release from connections. Clean the trunk of device with a swab. Don’t use any conductor or chemical might damage the device. Make sure device works after cleaning. Warnings Please use the device according to the manual. Don’t use the device in wet. Include a switch and circuit breaker in the assembly. Put the switch and circuit breaker nearby the device, operator can reach easily. Mark the switch and circuit breaker as releasing connection for device. FKV-14/14P, FKV-03 Dimensions 23 mm 5,08 mm 90 mm 66 mm 45 mm 95 mm 35,5 mm 37 mm 60 mm 6,35 mm 90 mm 66 mm 44,8 mm 35,5 mm 37 mm 60 mm 35,4 mm FK-14/14P Dimensions 84,5 mm 80 mm 44 mm 7,62 mm 75 mm 35,5 mm 3,5 FK-04/04P, FS-R Dimensions Technical Specifications Operating Volt.(Un) 3 x 380V AC ve nötr : Operating Frequency 50/60 Hz. : Operating Power <6VA : Operating Temp. -20°C......+55°C : Tolerance ~%30 (FKV-03: ~%40) : Connection Type Terminal connection. : Weight Max. 110gr. : Contact 5A/250V AC (Resistive Load) : Mounting Assembled on the din rail. : Operating Altitude <2000m. : Cable Diameter 1.5mm² : Display OUT & ERR LEDs : PWR, OUT & ERR LEDs (FK-04/04P & FS-R) ON & OUT LEDs (FKV-03) Document No: DK-004-7 MADE IN TURKEY Contact: www.tense.com.tr [email protected] N 2A L1 L2 L3 Kontaktör L1 N L2 L3 1 2 3 M 3 ~ PTC PTC FK-14P FKV-14P N 2A L1 L2 L3 L3 L2 N L1 1 2 3 P M 3 ~ PTC General

Upload: others

Post on 08-Feb-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PHASE SEQUENCE PHASE FAILURE RELAY FK-04/04P, FK-14/14P

PHASE SEQUENCE PHASE FAILURE RELAY FK-04/04P, FK-14/14P, FKV-14/14P, FKV-03, FS-R

FK-04/04P, FK-14/14P, FKV-14/14P, FKV-03 and FS-R phase failure relays are designed to avoid any failure of three phase motors (which works phase

sequence) caused from network. FK-04P, FK-14P and FKV-14P types additionally avoids failure of motor caused thermal overload.

FKV-14/14P Connection DiagramFK-14/14P Connection DiagramFK-04/04P Connection Diagram

PTC1 2 3

L1N L2 L3

N

2A

L1

L2

L3

Ko

nta

ktö

r

M3 ~

PTCFK-04P FKV-03

N

2A

L1

L2

L3

L3L2N L1

1 2 3

M3 ~

FKV-03 Connection Diagram

Usage of Device and Working Principle

Make the connections according to the diagram.

Normal Operation (No Error): When the phases are at normal values and the phase sequence is correct, the relay gets activated and the OUT LED is on.

Asymmetry Error: When any phase goes out of the normal range, the ERR LED flashes (at 2 second intervals), the OUT LED is off and the relay deactivated.

Phase sequence reverse (Phase Sequence Error): The ERR LED lights steady, the OUT LED is off and the relay gets deactivated.

PTC Errpr: In models with PTC, when the temperature of the motor exceeds the rated value, the ERR LED is flashes (at 1 second intervals), the OUT LED is off

and the relay deactivates. When the temperature value returns to the nominal values, the relay gets activated again and the OUT LED lights up.

Relay is Activated: 2 (COM) and 3 (NC) short circuit, 1 (NC) and 2 (COM) open circuit.

Relay is De-activated: 2 (COM) and 1 (NC) short circuit, 3 (NC) and 2 (COM) open circuit.

If the PTC function is will not to be used: If not using PTC in the FKV-14P, short the PTC (P) terminal to Neutral (N).

If not using PTC in FK-04P and FK-14P, short the PTC ( ) terminals.

FKV-03: There is no ERR LED on this device. In case of Asymmetry or Phase Sequence Errors, OUT LED goes out and the relay gets deactivated.

PTC

Maintenance

Switch off the device and release from connections. Clean the trunk of device with a swab. Don’t use any conductor or chemical might damage the device.

Make sure device works after cleaning.

Warnings

Please use the device according to the manual.

Don’t use the device in wet. Include a switch and circuit breaker in the assembly.

Put the switch and circuit breaker nearby the device, operator can reach easily.

Mark the switch and circuit breaker as releasing connection for device.

FKV-14/14P, FKV-03 Dimensions

23 mm5,08 mm

90

mm

66

mm

45

mm

95

mm

35

,5 m

m

37 mm60 mm

6,35 mm

90

mm

66

mm

44

,8 m

m

35

,5 m

m

37 mm60 mm35,4 mm

FK-14/14P Dimensions

84,5 mm

80 mm

44 mm

7,62 mm

75

mm

35

,5 m

m

3,5

FK-04/04P, FS-R Dimensions

Technical Specifications

Operating Volt.(Un) 3 x 380V AC ve nötr:

Operating Frequency 50/60 Hz.:

Operating Power <6VA:

Operating Temp. -20°C......+55°C:

Tolerance ~%30 (FKV-03: ~%40) :

Connection Type Terminal connection.:

Weight Max. 110gr.:

Contact 5A/250V AC (Resistive Load):

Mounting Assembled on the din rail.:

Operating Altitude <2000m.:

Cable Diameter 1.5mm²:

Display OUT & ERR LEDs:

PWR, OUT & ERR LEDs (FK-04/04P & FS-R)

ON & OUT LEDs (FKV-03)

Do

cum

en

t N

o:

DK

-00

4-7

MADE IN TURKEYContact: www.tense.com.tr [email protected]

N

2A

L1

L2

L3

Ko

nta

ktö

r

L1N L2 L3

1 2 3

M3 ~

PTC

PTC

FK-14P FKV-14P

N

2A

L1

L2

L3

L3L2N L1

1 2 3 P

M3 ~

PTC

General