pg&e’s management of oil-filled electrical equipment (ofee) and other materials containing

26
1 PG&E’s Management of Oil-Filled Electrical Equipment (OFEE) and Other Materials Containing Polychlorinated Biphenyls (PCB)

Upload: joella

Post on 28-Jan-2016

23 views

Category:

Documents


0 download

DESCRIPTION

PG&E’s Management of Oil-Filled Electrical Equipment (OFEE) and Other Materials Containing Polychlorinated Biphenyls (PCB ). PCB’s in Oil Filled Electrical Equipment. Mineral Oil : to insulate, suppress corona and arcing and, as coolant PCB: as dielectric* fluid - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

1

PG&E’s Management ofOil-Filled Electrical Equipment

(OFEE) and Other Materials Containing

Polychlorinated Biphenyls (PCB)

Page 2: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

2

PCB’s in Oil Filled Electrical Equipment

•Mineral Oil : to insulate, suppress corona and arcing and, as coolant

•PCB: as dielectric* fluid

*electric insulating by polarization as opposed to electrical obstruction

Page 3: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

3

POLYCHLORINATED BIPHENYLS

Man-made organic chemicals, domestically manufactured beginning in 1929Used in many commercial applications

Insulating properties Stability Non-flammable

Page 4: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

4

Common Types of PCBsMineral Oil Dielectric Fluids:Mineral oil-filled electrical equipment may be contaminated from its origin of manufacture through servicing and/or rebuilding activitiesMust be assumed to contain 50-499 ppm while in use or in storage for reuse if:Manufactured prior to July 2, 1979PCB level is unknown

Page 5: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

5

Common Types of PCBs

Tar/Compound Dielectrics & Potting Agents:

•Non-liquid type of substance contaminated with PCBs (sometimes at very high levels) that may be found in electrical equipment– Bushings, old light ballasts, PTs, CTs are examples

that may be tar-filled

Page 6: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

6

Emerging PCB Issues: PCB in Schools (New York, Oregon, Massachusetts)

suspected at any location with pre-1979 light ballasts Leaking light ballasts

Caulking material Glazing material Paint

Page 7: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

7

Potential Health Effects: Probable Human Carcinogen Causes cancer Animals Non-cancer effects to the immune, reproductive,

endocrine systems

Page 8: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

8

PCB Regulations40 CFR Part 761 = The PCB Mega Rule

Subpart A §761.2 – PCB concentration assumptions for use

Subpart B §761.2 – Prohibitions & Exceptions

§761.3 – Use Authorizations

§761.35 – Storage for reuse

Subpart C §761.4 – Marking requirements

Page 9: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

9

PCB Prohibitions and Exceptions

No persons may use any PCB, or PCB Item regardless of concentration, in any manner other than in a totally enclosed manner within the United States unless authorized under §761.30

Page 10: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

10

PCB Regulatory Information

Page 11: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

11

Federal and State LevelsPCB in mineral oil (or in any material) :

Federal level TSCA: >50 ppm State level: 5-49 ppm

Page 12: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

12

Equipment that contains PCB’s

Page 13: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

13

Approximate number of PCB containing equipment

System Wide PGE has over 1,000,000 pieces of OFEE

Of those 1,000,000 Pieces approximately 33% are pre-1979

Of those Pieces approximately 3% contain PCB’s > 5 ppm

Page 14: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

14

Page 15: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

15

Page 16: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

16

Page 17: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

17

Page 18: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

18

Page 19: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

19

Page 20: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

20

Page 21: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

21

PGE Policy’s and Emergency Response

Page 22: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

22

PG&E Policy and ProceduresOur internal policy are reviewed on a regular basis to ensure that they meet the TSCA requirements.

Page 23: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

23Our policies contain information on the following topics: PCB Procedures:

Spill categories Degree of response / Emergency Guides Notification requirements Cleaning requirements / Safety Equipment Transportation and equipment re-use Documentation and certification requirements Personnel training 24-hour hotline to reach Environmental Professional

Page 24: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

24

PCB Waste Management Requirements

Page 25: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

25

Federal Requirements:TSCA – Class 1 TSCA permitted landfill – Waste Management Kettleman Hills – Not Accepting

RCRA Not regulated by RCRA

California 5ppm STLC, 50ppm TTLC

Soluble Threshold Limit Concentration (STLC) and Total Threshold Limit Concentration (TTLC) Regulatory Limits

Class 2 only if contaminating material is less than 50 ppm

Transformer Oil – if less than 50 ppm oil is recycled >50 oil is incinerated

Page 26: PG&E’s  Management of Oil-Filled Electrical Equipment (OFEE) and  Other Materials Containing

26

Summary PG&E started addressing the issue of

PCB in 1977 PCB procedures are based on Federal

and State regulations and they are reviewed or updated every year.

Personnel training conducted every two- years to all PG&E employees who might be assigned to handle PCB.