Preliminary Geotechnical InvestigationProposed Development
Highway 7Carleton Place, Ontario
Prepared For
Novatech Engineering Consultants
December 6, 2012
Report PG2793-1
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1
December 6, 2012 Page i
TABLE OF CONTENTS
PAGE
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 PROPOSED DEVELOPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.0 METHOD OF INVESTIGATION
3.1 Field Investigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.2 Field Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.3 Laboratory Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.0 OBSERVATIONS
4.1 Surface Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.2 Subsurface Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.3 Groundwater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.0 DISCUSSION
5.1 Geotechnical Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.2 Site Grading and Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.3 Foundation Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.4 Design for Earthquakes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.5 Basement Slab/Slab on Grade Construction . . . . . . . . . . . . . . . . . . . 9
5.6 Pavement Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6.0 DESIGN AND CONSTRUCTION PRECAUTIONS
6.1 Foundation Drainage and Backfill . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Protection of Footings Against Frost Action . . . . . . . . . . . . . . . . . . . 11
6.3 Excavation Side Slopes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.4 Groundwater Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.5 Winter Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.0 RECOMMENDATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.0 STATEMENT OF LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1
December 6, 2012 Page ii
APPENDICES
Appendix 1 Soil Profile and Test Data Sheets
Symbols and Terms
Appendix 2 Figure 1 - Key Plan
Drawing PG2793-1 - Test Hole Location Plan
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 1
1.0 INTRODUCTION
Paterson Group (Paterson) was commissioned by Novatech Engineering Consultants
to conduct a preliminary geotechnical investigation for the proposed development to
be located along Highway 7 and Highway 15 in the Town of Carleton Place, Ontario
(refer to Figure 1 - Key Plan in Appendix 2 of this report).
The objectives of the current investigation were to:
‘ determine the subsoil and groundwater conditions at this site by means of test
holes.
‘ to provide preliminary geotechnical recommendations for the design of the
proposed development including construction considerations which may affect
the design.
The following report has been prepared specifically and solely for the aforementioned
project which is described herein. It contains our findings and includes geotechnical
recommendations pertaining to the design and construction of the proposed
development as they are understood at the time of writing this report.
Investigating the presence or potential presence of contamination on the subject
property was not part of the scope of work of this present investigation.
2.0 PROPOSED DEVELOPMENT
It is understood that the proposed development will be a mix of Employment/Highway
commercial and residential buildings. There is a potential of two (2) school sites and
a recreational facility within the proposed development. It is further understood that the
commercial areas will be slab-on-grade construction or shallow foundations whereas
the residential areas will be conventional townhomes and single units with some walk
outs. There is a possibility that there will be some high density residential units along
the collectors an Highway 7.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 2
3.0 METHOD OF INVESTIGATION
3.1 Field Investigation
Field Program
The field program for the present investigation was carried out on October 22, 2012.
At that time, thirty-two (32) test pits were advanced to a maximum depth of 4.4 m. The
test pit locations were distributed in a manner to provide general coverage of the
subject site taking into consideration above ground features and below ground utilities.
The locations of the test pits are shown on Drawing PG2793-1 - Test Hole Location
Plan included in Appendix 2.
The test pits were put down using a rubber tired backhoe at selected locations. The
test pit procedure consisted of excavating to bedrock or the maximum reach of the
backhoe at the selected locations and sampling the overburden soils. All fieldwork was
conducted under the full-time supervision of Paterson personnel under the direction of
a senior engineer from the geotechnical division.
Sampling and In Situ Testing
Soil samples from the test pits were recovered from the side walls of the open
excavation and all soil samples were initially classified on site. The grab samples were
placed in sealed plastic bags. All samples were transported to our laboratory for further
examination and classification. The depths at which the grab samples were recovered
from the test pits are denoted as G on the Soil Profile and Test Data sheets presented
in Appendix 1.
The subsurface conditions observed in the boreholes were recorded in detail in the
field. The soil profiles are presented on the Soil Profile and Test Data sheets in
Appendix 1 of this report.
Groundwater
Groundwater infiltration levels were observed upon completion of the sampling
procedure at the test pit locations. Observed groundwater infiltration levels are noted
in the Soil Profile and Test Data sheets.
Sample Storage
All samples will be stored in the laboratory for a period of one month after issuance of
this report. They will then be discarded unless we are otherwise directed.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 3
3.2 Field Survey
The test hole locations were selected by Paterson and surveyed by Novatech. The
ground surface elevations at the test hole locations are understood to be referenced
to a geodetic datum. The locations and ground surface elevations of the test holes are
presented on Drawing PG2793-1 - Test Hole Location Plan in Appendix 2.
3.3 Laboratory Testing
The soil samples recovered from the subject site were examined in our laboratory to
review the results of the field logging.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 4
4.0 OBSERVATIONS
4.1 Surface Conditions
The site is predominantly undeveloped and grass covered with areas of mature trees
and brush. The east portion of the subject site is a low lying marsh area with some tree
cover. Some surface water was observed at the time of the field program.
4.2 Subsurface Profile
Generally, the soil profile at the test pit locations consists of topsoil/tilled agricultural
zone underlain by a brown silty clay layer and/or silty sand followed by shallow bedrock.
Practical refusal to excavation was encountered in the majority of the test pit locations
at depths varying between ground surface to 4.2 m. Specific details of the soil profile
at each test hole location are presented on the Soil Profile and Test Data sheets in
Appendix 1.
Based on available geological mapping, the subject site is located in an area where the
bedrock consists of interbedded sandstone and dolomite of the March formation with
an overburden thickness between 0 and 10 m.
4.3 Groundwater
Groundwater infiltration levels were measured in the open test holes. Our observations
at the time of excavation are presented in the Soil Profile and Test Data sheets in
Appendix 1. The majority of the test pits were noted to be dry upon completion.
Groundwater levels are subject to seasonal fluctuations. Therefore, groundwater levels
could vary at the time of construction.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 5
5.0 DISCUSSION
5.1 Geotechnical Assessment
From a geotechnical perspective, the subject site is adequate for the proposed
development. It is expected that the proposed buildings will be founded on
conventional shallow footings placed on an undisturbed, stiff silty clay or bedrock
bearing surface.
The above and other considerations are discussed in the following paragraphs.
5.2 Site Grading and Preparation
Stripping Depth
Topsoil and deleterious fill, such as those containing organic materials, should be
stripped from under any buildings and other settlement sensitive structures.
Bedrock Removal
Bedrock removal can be accomplished by hoe ramming where only a small quantity of
the bedrock needs to be removed. Sound bedrock may be removed by line drilling and
controlled blasting and/or hoe ramming.
Prior to considering blasting operations, the blasting effects on the existing services,
buildings and other structures should be addressed. A pre-blast or pre-construction
survey of the existing structures located in proximity of the blasting operations should
be carried out prior to commencing site activities. The extent of the survey should be
determined by the blasting consultant and should be sufficient to respond to any
inquiries/claims related to the blasting operations.
As a general guideline, peak particle velocities (measured at the structures) should not
exceed 25 mm per second during the blasting program to reduce the risks of damage
to the existing structures.
The blasting operations should be planned and conducted under the supervision of a
licensed professional engineer who is also an experienced blasting consultant.
Excavation side slopes in sound bedrock can be carried out using almost vertical side
walls. A minimum 1 m horizontal ledge, should be left between the bottom of the
overburden excavation and the top of the bedrock surface to provide an area to allow
for potential sloughing.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 6
Vibration Considerations
Construction operations are also the cause of vibrations, and possibly, sources of
nuisance to the community. Therefore, means to reduce the vibration levels as much
as possible should be incorporated in the construction operations to maintain, as much
as possible, a cooperative environment with the residents.
The following construction equipments could be the source of vibrations: piling rig, hoe
ram, compactor, dozer, crane, truck traffic, etc. The construction of the shoring system
using soldier piles or sheet piling will require the use of these equipments. Vibrations,
whether it is caused by blasting operations or by construction operations, could be the
cause of the source of detrimental vibrations on the adjoining buildings and structures.
Therefore, it is recommended that all vibrations be limited.
Two parameters are used to determine the permissible vibrations, namely, the
maximum peak particle velocity and the frequency. For low frequency vibrations, the
maximum allowable peak particle velocity is less than that for high frequency vibrations.
As a guideline, the peak particle velocity should be less than 15 mm/s between
frequencies of 4 to 12 Hz, and 50 mm/s above a frequency of 40 Hz (interpolate
between 12 and 40 Hz). It should be noted that these guidelines are for today’s
construction standards. Considering that these guidelines are above perceptible human
level and, in some cases, could be very disturbing to some people, it is recommended
that a pre-construction survey be completed to minimize the risks of claims during or
following the construction of the proposed buildings.
Fill Placement
Fill used for grading beneath the proposed buildings, unless otherwise specified, should
consist of clean imported granular fill, such as Ontario Provincial Standard
Specifications (OPSS) Granular A or Granular B Type II. The fill should be tested and
approved prior to delivery to the site. It should be placed in lifts no greater than
300 mm thick and compacted using suitable compaction equipment for the lift
thickness. Fill placed beneath the building areas should be compacted to at least 98%
of its standard Proctor maximum dry density (SPMDD).
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 7
Non-specified existing fill along with site-excavated soil can be used as general
landscaping fill where settlement of the ground surface is of minor concern. These
materials should be spread in thin lifts and at least compacted by the tracks of the
spreading equipment to minimize voids. If these materials are to be used to build up
the subgrade level for areas to be paved, they should be compacted in thin lifts to a
minimum density of 95% of their respective SPMDD. Non-specified existing fill and site-
excavated soils are not suitable for use as backfill against foundation walls, unless used
in conjunction with a geocomposite drainage membrane, such as Miradrain G100N or
Delta Drain 6000.
5.3 Foundation Design
Shallow Foundation
Footings placed on a clean, surface sounded bedrock surface can be designed using
a factored bearing resistance value at ultimate limit states (ULS) of 1,500 kPa,
incorporating a geotechnical resistance factor of 0.5, and a bearing resistance value at
serviceability limit states (SLS) of 500 kPa. The settlement associated with the bearing
resistance value at SLS is expected to be negligible.
A clean, surface-sounded bedrock bearing surface should be free of loose materials,
and have no near surface seams, voids, fissures or open joints which can be detected
from surface sounding with a rock hammer.
Footings, up to 3 m wide, placed on an undisturbed, stiff silty clay surface can be
designed using a bearing resistance value at SLS of 100 kPa and a factored bearing
resistance value at ULS of 200 kPa. Footings designed using the bearing resistance
value at SLS given above will be subjected to potential post construction total and
differential settlements of 25 and 20 mm, respectively.
A geotechnical resistance factor of 0.5 was applied to the above noted bearing
resistance value at ULS. The bearing resistance value at SLS will be subjected to
potential post-construction total and differential settlements of 25 and 20 mm,
respectively. A permissible grade raise restriction of 2 m is recommended for proposed
buildings where footings are placed directly over a stiff silty clay subgrade.
An undisturbed soil bearing surface consists of a surface from which all topsoil and
deleterious materials, such as loose, frozen or disturbed soil, whether in situ or not,
have been removed, in the dry, prior to the placement of concrete for footings.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 8
Where a building is founded partly on bedrock and partly on soil bearing media, it is
recommended to decrease the bearing resistance value at SLS by 25% for the footings
placed on soil bearing media to reduce the potential long term total and differential
settlements. Also, at the soil/bedrock and bedrock/soil transitions, it is recommended
that the upper 0.5 m of the bedrock be removed for a minimum length of 2 m (on the
bedrock side) and replaced with nominally compacted OPSS Granular A or Granular B
Type II material. The width of the sub-excavation should be at least the proposed
footing width plus 0.5 m. Steel reinforcement, extending at least 3 m beyond both sides
of the 2 m long transition, should be placed in the top part of the footings and
foundation walls.
The suitability of grade raises in excess of 1.5 m should be evaluated where silty clay
is encountered below the footing level. There will be essentially no grade raise
restrictions for areas of the site underlain by granular soils and/or bedrock.
Lateral Support
The bearing medium under footing-supported structures is required to be provided with
adequate lateral support. Adequate lateral support is provided to a silty clay bearing
medium when a plane extending down and out from the bottom edge of the footing, at
a minimum of 1.5H:1V. Near vertical (1H:6V) slopes can be used for unfractured
bedrock bearing media; a 1H:1V slope can be used for fractured bedrock.
5.4 Design for Earthquakes
The site class for seismic site response can be taken as Class C for foundations placed
on the bedrock surface. Reference should be made to the latest revision of the 2006
Ontario Building Code for a full discussion of the earthquake design requirements. A
higher site class, such as Class A or B may be applicable for the proposed
development. However, the higher site classes have to be confirmed by site specific
shear wave velocity testing. Soils underlying the subject site are not susceptible to
liquefaction.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 9
5.5 Basement Slab/Slab-on-Grade Construction
With the removal of all topsoil and fill, containing deleterious materials, within the
footprint of the proposed buildings, the native soil will be considered an acceptable
subgrade surface on which to commence backfilling for floor slab construction. OPSS
Granular B Type II, with a maximum particle size of 50 mm, are recommended for
backfilling below the floor slabs. It is recommended that the upper 200 mm of sub-slab
fill consist of OPSS Granular A crushed stone material for slab on grade construction.
It is recommended that the upper 200 mm of sub-slab fill consist of 19 mm clear
crushed stone material for basement slab. All backfill material within the footprint of the
proposed buildings should be placed in maximum 300 mm thick loose layers and
compacted to at least 98% of its SPMDD.
5.6 Pavement Structure
For design purposes, the pavement structure presented in the following tables could be
used for the design of car only parking areas, truck parking areas and local roadways.
Table 1 - Recommended Pavement Structure - Car Only Parking Areas/Driveways
Thickness
(mm)Material Description
50 Wear Course - HL-3 or Superpave 12.5 Asphaltic Concrete
150 BASE - OPSS Granular A Crushed Stone
300 SUBBASE - OPSS Granular B Type II
SUBGRADE - Either in situ soils or OPSS Granular B Type I or II material placed over in situ soil
Table 2 - Recommended Pavement Structure
Local Roadways and Heavy Truck Parking Areas
Thickness
(mm)Material Description
40 Wear Course - HL-3 or Superpave 12.5 Asphaltic Concrete
50 Binder Course - HL-8 or Superpave 19.0 Asphaltic Concrete
150 BASE - OPSS Granular A Crushed Stone
400 SUBBASE - OPSS Granular B Type II
SUBGRADE - Either in situ soils or OPSS Granular B Type I or II material placed over in situ soil
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 10
Table 3 - Recommended Pavement Structure - Arterial Roadways
Thickness
(mm)Material Description
40 Wear Course - HL-3 or Superpave 12.5 Asphaltic Concrete
50 Binder Course - HL-8 or Superpave 19.0 Asphaltic Concrete
50 Binder Course - HL-8 or Superpave 19.0 Asphaltic Concrete
150 BASE - OPSS Granular A Crushed Stone
600 SUBBASE - OPSS Granular B Type II
SUBGRADE - Either in situ soils or OPSS Granular B Type I or II material placed over in situ soil
Minimum Performance Graded (PG) 58-34 asphalt cement should be used for this
project.
If soft spots develop in the subgrade during compaction or due to construction traffic,
the affected areas should be excavated and replaced with OPSS Granular B Type I or
II material.
The pavement granular base and subbase should be placed in maximum 300 mm thick
lifts and compacted to a minimum of 100% of the material’s SPMDD using suitable
vibratory equipment.
Pavement Structure Drainage
Satisfactory performance of the pavement structure is largely dependent on keeping the
contact zone between the subgrade material and the base stone in a dry condition.
Failure to provide adequate drainage under conditions of heavy wheel loading can
result in the fine subgrade soil being pumped into the voids in the stone subbase,
thereby reducing the load bearing capacity.
Where silty clay is encountered at subgrade level, consideration should be given to
installing subdrains during the pavement construction. These drains should extend in
four orthogonal directions (minimum 3 m length) at a catch basin structure or
longitudinally when placed along a curb. The clear stone surrounding the drainage lines
or the pipe, should be wrapped with suitable filter cloth. The subdrain inverts should be
approximately 300 mm below subgrade level. The subgrade surface should be shaped
to promote water flow to the drainage lines.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 11
6.0 DESIGN AND CONSTRUCTION PRECAUTIONS
6.1 Foundation Drainage and Backfill
It is recommended that a perimeter foundation drainage system be provided for the
proposed structures. The system should consist of a 100 to 150 mm diameter
perforated corrugated plastic pipe, surrounded on all sides by 150 mm of 10 mm clear
crushed stone, placed at the footing level around the exterior perimeter of the structure.
The pipe should have a positive outlet, such as a gravity connection to the storm sewer.
Backfill against the exterior sides of the foundation walls should consist of free-draining
non frost susceptible granular materials. The greater part of the site excavated
materials will be frost susceptible and, as such, are not recommended for re-use as
backfill against the foundation walls, unless used in conjunction with a drainage
geocomposite, such as Miradrain G100N or Delta Drain 6000, connected to the
perimeter foundation drainage system. Otherwise, imported granular materials, such
as clean sand or OPSS Granular B Type I granular material, should otherwise be used
for this purpose.
6.2 Protection of Footings Against Frost Action
Perimeter footings of heated structures are required to be insulated against the
deleterious effect of frost action. A minimum of 1.5 m thick soil cover (or equivalent)
should be provided in this regard.
Exterior unheated footings, such as those for isolated exterior piers, are more prone to
deleterious movement associated with frost action than the exterior walls of the
structure proper and require additional protection, such as soil cover of 2.1 m or a
combination of soil cover and foundation insulation.
For footings founded directly on sound bedrock where insufficient soil cover is available,
rigid insulation can be used to make up the shortfall. Also, if the bedrock is considered
to be non-frost susceptible, the suggested insulation can be omitted. Non-frost
susceptible bedrock requires confirmation of no significant soil bearing seams within the
potential frost penetration depth. This confirmation is carried out using probeholes
which are verified by geotechnical personnel.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 12
6.3 Excavation Side Slopes
The side slopes of excavations in the soil and fill overburden materials should either be
cut back at acceptable slopes or should be retained by shoring systems from the start
of the excavation until the structure is backfilled. It is assumed that sufficient room will
be available for the greater part of the excavations to be undertaken by open-cut
methods (i.e. unsupported excavations).
The excavation side slopes above the groundwater level extending to a maximum depth
of 3 m should be cut back at 1H:1V or flatter. The flatter slope is required for
excavation below groundwater level. The subsoil at this site is considered to be mainly
a Type 2 and 3 soil according to the Occupational Health and Safety Act and
Regulations for Construction Projects.
Excavated soil should not be stockpiled directly at the top of excavations and heavy
equipment should be kept away from the excavation sides.
Slopes in excess of 3 m in height should be periodically inspected by the geotechnical
consultant in order to detect if the slopes are exhibiting signs of distress.
It is recommended that a trench box be used at all times to protect personnel working
in trenches with steep or vertical sides. It is expected that services will be installed by
“cut and cover” methods and excavations will not be left open for extended periods of
time.
6.4 Groundwater Control
The contractor should be prepared to direct water away from all bearing surfaces and
subgrades, regardless of the source, to prevent disturbance to the founding medium.
It is anticipated that pumping from open sumps will be sufficient to control the
groundwater influx through the sides of the excavations.
Pumping of more than 50,000 L/day to an off site receptor requires a temporary Ontario
Ministry of Environment (MOE) permit to take water (PTTW). At least 3 to 4 months
should be allowed for completion of the application and issuance of the permit by the
MOE.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 13
6.5 Winter Construction
Precautions must be taken if winter construction is considered for this project. The
subsoil conditions at this site consist of frost susceptible materials. In the presence of
water and freezing conditions, ice could form within the soil mass. Heaving and
settlement upon thawing could occur.
In the event of construction during below zero temperatures, the founding stratum
should be protected from freezing temperatures by the use of straw, propane heaters
and tarpaulins or other suitable means. In this regard, the base of the excavations
should be insulated from sub-zero temperatures immediately upon exposure and until
such time as heat is adequately supplied to the building and the footings are protected
with sufficient soil cover to prevent freezing at founding level.
Trench excavations and pavement construction are also difficult activities to complete
during freezing conditions without introducing frost in the subgrade or in the excavation
walls and bottoms. Precautions should be taken if such activities are to be carried out
during freezing conditions.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 14
7.0 RECOMMENDATIONS
It is a requirement for the foundation design data provided herein to be applicable that
a materials testing and observation services program including the following aspects be
performed by the geotechnical consultant.
‘ A detailed geotechnical investigation should be completed, once details of the
proposed development are determined.
‘ Observation of all bearing surfaces prior to the placement of concrete.
‘ Sampling and testing of the concrete and fill materials used.
‘ Periodic observation of the condition of unsupported excavation side slopes in
excess of 3 m in height, if applicable.
‘ Observation of all subgrades prior to backfilling
‘ Field density tests to determine the level of compaction achieved.
‘ Sampling and testing of the bituminous concrete including mix design reviews.
A report confirming that these works have been conducted in general accordance with
our recommendations could be issued, upon request, following the completion of a
satisfactory materials testing and observation program by the geotechnical consultant.
paterson Preliminary Geotechnical InvestigationOttawa Kingston North Bay Proposed Development
Highway 7 - Carleton Place
Report: PG2793-1December 6, 2012 Page 15
8.0 STATEMENT OF LIMITATIONS
The recommendations made in this report are in accordance with our present
understanding of the project. The client should be aware that any information
pertaining to soils and all test hole logs are furnished as a matter of general information
only and test hole descriptions or logs are not to be interpreted as descriptive of
conditions at locations other than those of the test holes.
The present report applies only to the project described in this document. Use of this
report for purposes other than those described herein or by person(s) other than
Novatech Engineering Consultants or their agent(s) is not authorized without review by
this firm for the applicability of our recommendations to the altered use of the report.
Paterson Group Inc.
Michael Beaudoin, B.Eng.
David J. Gilbert, P.Eng.
Report Distribution:
‘ Novatech Engineering (3 copies)
‘ Paterson Group (1 copy)
APPENDIX 1
SOIL PROFILE AND TEST DATA SHEETS
SYMBOLS AND TERMS
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
GROUND SURFACE0
DEPTHSAMPLE
1G
0.50
Brown SILTY CLAY with sand, tracetopsoil
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.50m depth
(TP dry upon completion)
patersongroup
50 mm Dia. Cone
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Remoulded
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Consulting
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
or RQD
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
127.58
TP 1BORINGS BY
Undisturbed
ELEV.
NUMBER
Carleton Place, Ontario
Co
nstr
uctio
n
October 22, 2012
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.25TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.25m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
128.01
TP 2
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
RECOVERY
STRATA PLOT
0
DEPTHSAMPLE
% Water Content %
0.30
0.63
TOPSOIL
Brown SILTY CLAY with sand
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.63m depth
(TP dry upon completion)
Remoulded
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
patersongroupProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
GROUND SURFACE
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Undisturbed
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
127.61
NUMBER
ELEV.
October 22, 2012 TP 3
or RQD
Co
nstr
uctio
n
Carleton Place, Ontario
TYPE
RECOVERY
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
20 40 60 80 100
DATE
%
STRATA PLOT
0
1
DEPTH
GROUND SURFACE
1G
0.15
1.58
TOPSOIL
Brown SILTY CLAY with sand
End of Test Pit
Practical shovel refusal on inferredbedrock at 1.58m depth
(Water infiltration at 1.5m depth)
N VALUE
SAMPLE
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical InvestigationProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
ELEV.
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
TP 4
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
October 22, 2012
Carleton Place, Ontario
128.27
127.27
NUMBER
Co
nstr
uctio
n
or RQD
Undisturbed
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
RECOVERY
STRATA PLOT
0
1
DEPTHSAMPLE
% Water Content %
0.20
1.67
TOPSOIL
Brown SILTY CLAY with sand
End of Test Pit
Practical shovel refusal on inferredbedrock at 1.67m depth
(TP dry upon completion)
Remoulded
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
patersongroupProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
GROUND SURFACE
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Undisturbed
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
128.95
127.95
NUMBER
ELEV.
October 22, 2012 TP 5
or RQD
Co
nstr
uctio
n
Carleton Place, Ontario
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
20 40 60 80 100
STRATA PLOT
0
SAMPLE
GROUND SURFACE
patersongroup
1G
0.15
0.70
TOPSOIL
Brown SILTY SAND with clay
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.70m depth
(TP dry upon completion)
RECOVERY
N VALUE
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
Proposed Residential Development - Highway 7
DEPTH
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
NUMBER
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
129.79
TP 6
ELEV.
October 22, 2012
Undisturbed
Co
nstr
uctio
n
or RQD
Carleton Place, Ontario
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
GROUND SURFACE0
DEPTHSAMPLE
1G0.43
TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.43m depth
(TP dry upon completion)
patersongroup
50 mm Dia. Cone
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Remoulded
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Consulting
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
or RQD
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
129.58
TP 7BORINGS BY
Undisturbed
ELEV.
NUMBER
Carleton Place, Ontario
Co
nstr
uctio
n
October 22, 2012
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
20 40 60 80 100
STRATA PLOT
0
1
SAMPLE
GROUND SURFACE
patersongroup
1G
0.17
1.47
TOPSOIL
Brown SILTY SAND with clay
End of Test Pit
Practical shovel refusal on inferredbedrock at 1.47m depth
(TP dry upon completion)
RECOVERY
N VALUE
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
Proposed Residential Development - Highway 7
DEPTH
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
NUMBER
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
130.55
129.55
TP 8
ELEV.
October 22, 2012
Undisturbed
Co
nstr
uctio
n
or RQD
Carleton Place, Ontario
TYPE
RECOVERY
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
20 40 60 80 100
DATE
%
STRATA PLOT
0
1
2
3
DEPTH
GROUND SURFACE
1G
0.23
3.64
TOPSOIL
Brown to grey SILTY SAND withclay
End of Test Pit
Practical shovel refusal on inferredbedrock at 3.64m depth
(Water infiltration at 2.9m depth)
N VALUE
SAMPLE
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical InvestigationProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
ELEV.
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
TP 9
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
October 22, 2012
Carleton Place, Ontario
129.18
128.18
127.18
126.18
NUMBER
Co
nstr
uctio
n
or RQD
Undisturbed
TYPE
RECOVERY
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
20 40 60 80 100
DATE
%
STRATA PLOT
0
1
2
3
4
DEPTH
GROUND SURFACE
1G
0.35
4.19
TOPSOIL
Brown to grey SILTY CLAY withsand
End of Test Pit
Practical shovel refusal on inferredbedrock at 4.19m depth
(Water infiltration at 3.5m depth)
N VALUE
SAMPLE
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical InvestigationProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
ELEV.
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
TP10
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
October 22, 2012
Carleton Place, Ontario
128.16
127.16
126.16
125.16
124.16
NUMBER
Co
nstr
uctio
n
or RQD
Undisturbed
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
STRATA PLOT
DEPTHSAMPLE
Consulting
(m)
BEDROCK SURFACE
Preliminary Geotechnical Investigationpatersongroup
Remoulded
Water Content %
DATE
20 40 60 80 100
N VALUE
RECOVERY
50 mm Dia. Cone
FILE NO.
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
TP11
NUMBER
Undisturbed
or RQD
BORINGS BY
Carleton Place, Ontario
October 22, 2012
ELEV.
GROUND SURFACE
Co
nstr
uctio
n
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
50 mm Dia. Cone
0
1
2
DEPTHSAMPLE
2.24
Brown SILTY CLAY with sand
End of Test Pit
Practical shovel refusal on inferredbedrock at 2.24m depth
(Water infiltration at 1.8m depth)
patersongroup
Remoulded
Consulting
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Water Content %
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
130.15
129.15
128.15
TP12
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.04TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.04m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
137.82
TP13
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
GROUND SURFACE0
DEPTHSAMPLE
1G0.28TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.28m depth
(TP dry upon completion)
patersongroup
50 mm Dia. Cone
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Remoulded
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Consulting
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
or RQD
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
133.03
TP14BORINGS BY
Undisturbed
ELEV.
NUMBER
Carleton Place, Ontario
Co
nstr
uctio
n
October 22, 2012
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
20 40 60 80 100
STRATA PLOT
0
SAMPLE
GROUND SURFACE
patersongroup
1G
0.12
0.59
TOPSOIL
Brown SILTY CLAY, trace sand
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.59m depth
(TP dry upon completion)
RECOVERY
N VALUE
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
Proposed Residential Development - Highway 7
DEPTH
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
NUMBER
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
130.68
TP15
ELEV.
October 22, 2012
Undisturbed
Co
nstr
uctio
n
or RQD
Carleton Place, Ontario
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.43
TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.43m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
131.65
TP16
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
GROUND SURFACE0
DEPTHSAMPLE
1G0.42
TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.42m depth
(TP dry upon completion)
patersongroup
50 mm Dia. Cone
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Remoulded
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Consulting
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
or RQD
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
134.17
TP17BORINGS BY
Undisturbed
ELEV.
NUMBER
Carleton Place, Ontario
Co
nstr
uctio
n
October 22, 2012
20 40 60 80 100
N VALUE
RECOVERY
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
SAMPLE
Preliminary Geotechnical Investigation
TYPE
%
STRATA PLOT
GROUND SURFACE
1G
0.23
0.50
1.48
TOPSOIL
Brown SILTY SAND
Grey SILTY SAND with clay
End of Test Pit
Practical shovel refusal on inferredbedrock at 1.48m depth
(TP dry upon completion)
DATE
patersongroup
Remoulded
Water Content %
DEPTH
Proposed Residential Development - Highway 7
0
1
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
ELEV.
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
132.25
131.25
TP18October 22, 2012
Carleton Place, Ontario
NUMBER
Co
nstr
uctio
n
or RQD
Undisturbed
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
RECOVERY
TYPE
N VALUE
STRATA PLOT
0
1
DEPTHSAMPLE
patersongroup
0.15
1.60
TOPSOIL
Brown to grey SILTY SAND, traceclay and gravel
End of Test Pit
Practical shovel refusal on inferredbedrock at 1.60m depth
(Water infiltration at 1.0m depth)
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
Proposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
ELEV.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Undisturbed
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
135.41
134.41
NUMBER
October 22, 2012
Carleton Place, Ontario
TP19
GROUND SURFACE
Co
nstr
uctio
n
or RQD
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
20 40 60 80 100
STRATA PLOT
0
SAMPLE
GROUND SURFACE
patersongroup
1G
0.11
0.43
TOPSOIL
Brown SILTY SAND with clay
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.43m depth
(TP dry upon completion)RECOVERY
N VALUE
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
Proposed Residential Development - Highway 7
DEPTH
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
NUMBER
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
135.24
TP20
ELEV.
October 22, 2012
Undisturbed
Co
nstr
uctio
n
or RQD
Carleton Place, Ontario
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
RECOVERY
STRATA PLOT
0
DEPTHSAMPLE
% Water Content %
0.15
0.49
TOPSOIL
Brown SILTY SAND with clay
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.49m depth
(TP dry upon completion)
Remoulded
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
patersongroupProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
GROUND SURFACE
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Undisturbed
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
135.50
NUMBER
ELEV.
October 22, 2012 TP21
or RQD
Co
nstr
uctio
n
Carleton Place, Ontario
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
20 40 60 80 100
STRATA PLOT
0
SAMPLE
GROUND SURFACE
patersongroup
1G
0.23
0.98
TOPSOIL
Brown SILTY SAND with clay
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.98m depth
(TP dry upon completion)
RECOVERY
N VALUE
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
Proposed Residential Development - Highway 7
DEPTH
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
NUMBER
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
135.76
TP22
ELEV.
October 22, 2012
Undisturbed
Co
nstr
uctio
n
or RQD
Carleton Place, Ontario
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.38
TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.38m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
135.71
TP23
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
GROUND SURFACE0
DEPTHSAMPLE
1G0.22
TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.22m depth
(TP dry upon completion)
patersongroup
50 mm Dia. Cone
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Remoulded
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Consulting
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
or RQD
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
138.56
TP24BORINGS BY
Undisturbed
ELEV.
NUMBER
Carleton Place, Ontario
Co
nstr
uctio
n
October 22, 2012
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.27TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.27m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
139.04
TP25
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.24TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.24m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
138.00
TP26
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
Consulting
STRATA PLOT
50 mm Dia. Cone
0
DEPTHSAMPLE
0.04TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.04m depth
(TP dry upon completion)
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY (m)
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
136.63
TP27
NUMBER
or RQD
GROUND SURFACE
Co
nstr
uctio
n
Carleton Place, Ontario
October 22, 2012
ELEV.
Undisturbed
STRATA PLOT
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
%
GROUND SURFACE0
DEPTHSAMPLE
1G0.22TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.22m depth
(TP dry upon completion)
patersongroup
50 mm Dia. Cone
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
RECOVERY
Remoulded
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
Pen. Resist. Blows/0.3m
Consulting
Proposed Residential Development - Highway 7
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
ter
HOLE NO.
or RQD
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
136.42
TP28BORINGS BY
Undisturbed
ELEV.
NUMBER
Carleton Place, Ontario
Co
nstr
uctio
n
October 22, 2012
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
RECOVERY
STRATA PLOT
0
DEPTHSAMPLE
% Water Content %
0.07
0.43
TOPSOIL
Brown SILTY SAND
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.43m depth
(TP dry upon completion)
Remoulded
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
patersongroupProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
GROUND SURFACE
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Undisturbed
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
137.79
NUMBER
ELEV.
October 22, 2012 TP29
or RQD
Co
nstr
uctio
n
Carleton Place, Ontario
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
TYPE
20 40 60 80 100
STRATA PLOT
0
SAMPLE
GROUND SURFACE
patersongroup
1G0.20
0.53
FILL: Gravel with clay
TOPSOIL
End of Test Pit
Practical shovel refusal on inferredbedrock at 0.53m depth
(TP dry upon completion)
RECOVERY
N VALUE
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
Proposed Residential Development - Highway 7
DEPTH
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
NUMBER
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
137.43
TP30
ELEV.
October 22, 2012
Undisturbed
Co
nstr
uctio
n
or RQD
Carleton Place, Ontario
TYPE
RECOVERY
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
20 40 60 80 100
DATE
%
STRATA PLOT
0
1
2
3
DEPTH
GROUND SURFACE
1G
0.20
3.98
FILL: Gravel
Very stiff, brown SILTY CLAY withsand
- stiff and grey by 2.5m depth
End of Test Pit
(Water infiltration at 3.0m depth)
N VALUE
SAMPLE
patersongroup
Remoulded
Water Content %
Preliminary Geotechnical InvestigationProposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
ELEV.
HOLE NO.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
TP31
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
October 22, 2012
Carleton Place, Ontario
128.48
127.48
126.48
125.48
NUMBER
Co
nstr
uctio
n
or RQD
Undisturbed
%
50 mm Dia. Cone
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
RECOVERY
TYPE
N VALUE
STRATA PLOT
0
1
2
3
4
DEPTHSAMPLE
patersongroup
3.95
4.43
Brown SILTY CLAY with sand
- grey by 2.2m depth
Grey SILTY SAND with clay andgravel
End of Test Pit
(Water infiltration at 2.5m depth)
Remoulded
Water Content %
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
Proposed Residential Development - Highway 7
BORINGS BY
REMARKS
Ground surface elevations provided by Novatech Engineering Consultants Ltd.
Backhoe
HOLE NO.
ELEV.
Engineers
20 40 60 80
PG2793
(m)
SOIL PROFILE AND TEST DATA
DATUM
Pie
zo
me
terPen. Resist. Blows/0.3m
Undisturbed
Consulting
(m)
FILE NO.
Shear Strength (kPa)
SOIL DESCRIPTION
127.77
126.77
125.77
124.77
123.77
NUMBER
October 22, 2012
Carleton Place, Ontario
TP32
GROUND SURFACE
Co
nstr
uctio
n
or RQD
0
1
2
3
DEPTHSAMPLE
ELEV.
TP 1
NUMBER
Undisturbed
or RQD
GROUND SURFACE
Carleton Place, Ontario
Soft, brown SILTY CLAY withsand
1
2
3
G
G
G
0.91
1.96
Constr
uction
%
TYPE
3.81
Possible FILL: Brown siltyclay with topsoil, peat andwood
End of Test Pit
Stiff to very stiff, grey SILTYCLAY
STRATA PLOT
(m)
BORINGS BY Hydraulic Shovel
Consulting
(m)
Engineers
PG2618REMARKS
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
31 January 2012
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
Proposed Development - McNeely Avenue
DATUM
RECOVERY
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
0
1
DEPTHSAMPLE
Carleton Place, Ontario
ELEV.
TP 2
NUMBER
Undisturbed
or RQD
GROUND SURFACE
End of Test Pit
Practical refusal to excavation@ 1.93m depth
(TP dry upon completion)
1
2
G
G
0.15
0.56
1.93
TOPSOIL
GLACIAL TILL: Loose tocompact, grey silty sand withclay, gravel and cobbles
TYPE
%
STRATA PLOT
Brown SILTY SAND, traceclay
(m)
REMARKS
Constr
uction
Consulting
(m)
Engineers
PG2618
BORINGS BY
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
20 40 60 80 100
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel DATE
N VALUE
RECOVERY
Proposed Development - McNeely Avenue
DATUM
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
0
1
2
DEPTHSAMPLE
Carleton Place, Ontario
ELEV.
TP 3
NUMBER
Undisturbed
or RQD
GROUND SURFACE
End of Test Pit
Practical refusal to excavation@ 2.51m depth
(TP dry upon completion)
1
2
G
G
1.09
1.35
2.51
TOPSOIL
GLACIAL TILL: Compact,brown silty sand with clay,gravel and cobbles
TYPE
%
STRATA PLOT
Compact, dark brown SILTYSAND with clay
(m)
REMARKS
Constr
uction
Consulting
(m)
Engineers
PG2618
BORINGS BY
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
20 40 60 80 100
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel DATE
N VALUE
RECOVERY
Proposed Development - McNeely Avenue
DATUM
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
0
1
2
DEPTHSAMPLE
Carleton Place, Ontario
ELEV.
TP 4
NUMBER
Undisturbed
or RQD
GROUND SURFACE
End of Test Pit
Practical refusal to excavation@ 2.31m depth
(TP dry upon completion)
1
2
G
G
0.20
0.51
2.31
TOPSOIL
GLACIAL TILL: Compact,grey silty sand with clay, graveland cobbles
TYPE
%
STRATA PLOT
Brown SILTY SAND
(m)
REMARKS
Constr
uction
Consulting
(m)
Engineers
PG2618
BORINGS BY
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
20 40 60 80 100
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel DATE
N VALUE
RECOVERY
Proposed Development - McNeely Avenue
DATUM
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
0
1
2
DEPTHSAMPLE
Carleton Place, Ontario
ELEV.
TP 5
NUMBER
Undisturbed
or RQD
GROUND SURFACE
End of Test Pit
Practical refusal to excavation@ 2.34m depth
(TP dry upon completion)
1
2
G
G
0.20
0.41
2.34
TOPSOIL
GLACIAL TILL: Loose tocompact, grey silty sand withgravel and cobbles
TYPE
%
STRATA PLOT
Loose, brown SILTY SAND,trace clay
(m)
REMARKS
Constr
uction
Consulting
(m)
Engineers
PG2618
BORINGS BY
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
20 40 60 80 100
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel DATE
N VALUE
RECOVERY
Proposed Development - McNeely Avenue
DATUM
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
0
1
DEPTHSAMPLE
Carleton Place, Ontario
ELEV.
TP 6
NUMBER
Undisturbed
or RQD
GROUND SURFACE
End of Test Pit
Practical refusal to excavation@ 1.40m depth
(TP dry upon completion)
1
2
G
G
0.30
0.74
1.40
TOPSOIL
GLACIAL TILL: Loose tocompact, grey-brown silty sandwith clay, gravel and cobbles
TYPE
%
STRATA PLOT
Brown SILTY CLAY, tracesand
(m)
REMARKS
Constr
uction
Consulting
(m)
Engineers
PG2618
BORINGS BY
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
20 40 60 80 100
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel DATE
N VALUE
RECOVERY
Proposed Development - McNeely Avenue
DATUM
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
NUMBER
Carleton Place, Ontario
ELEV.SAMPLE
TP 7
DEPTH
Undisturbed
or RQD
Constr
uction
GROUND SURFACE
1G
0.25
0.53
TOPSOIL
Brown SILTY CLAY withsand and gravel
End of Test Pit
Practical refusal to excavation@ 0.53m depth
(Groundwater infiltration atbottom of test pit)
31 January 2012
TYPE
%
STRATA PLOT
0
SOIL PROFILE AND TEST DATA
Hydraulic Shovel
Consulting
(m)
Engineers
20 40 60 80
BORINGS BY
(m)
REMARKS
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
PG2618FILE NO.
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
Shear Strength (kPa)
RECOVERY
DATUM
SOIL DESCRIPTION
Proposed Development - McNeely Avenue
HOLE NO.
Pen. Resist. Blows/0.3m
ELEV.DEPTHSAMPLE
Carleton Place, Ontario
TP 8
NUMBER
Undisturbed
or RQD
Constr
uction
GROUND SURFACE
1
2
G
G
0.23
2.31
TOPSOIL
GLACIAL TILL: Loose tocompact, brown silty sand withclay, gravel and cobbles
End of Test Pit
Practical refusal to excavation@ 2.31m depth
(Groundwater infiltration @0.9m depth)
0
1
2
TYPE
%
STRATA PLOT
SOIL PROFILE AND TEST DATA
REMARKS
Consulting
(m)
Engineers
20 40 60 80
(m)
BORINGS BY
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
PG2618
N VALUE
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel
20 40 60 80 100
RECOVERY
DATUM
DATE
FILE NO.
Proposed Development - McNeely Avenue
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
NUMBER
Carleton Place, Ontario
ELEV.SAMPLE
TP 9
DEPTH
Undisturbed
or RQD
Constr
uction
GROUND SURFACE
1G
0.18
0.97
TOPSOIL
GLACIAL TILL: Loose tocompact, brown silty sand withgravel and cobbles
End of Test Pit
Practical refusal to excavation@ 0.97m depth
(Groundwater infiltration atbottom of test pit)
31 January 2012
TYPE
%
STRATA PLOT
0
SOIL PROFILE AND TEST DATA
Hydraulic Shovel
Consulting
(m)
Engineers
20 40 60 80
BORINGS BY
(m)
REMARKS
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
PG2618FILE NO.
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
Shear Strength (kPa)
RECOVERY
DATUM
SOIL DESCRIPTION
Proposed Development - McNeely Avenue
HOLE NO.
Pen. Resist. Blows/0.3m
0
1
DEPTHSAMPLE
Carleton Place, Ontario
ELEV.
TP10
NUMBER
Undisturbed
or RQD
GROUND SURFACE
End of Test Pit
Practical refusal to excavation@ 1.55m depth
1
2
G
G
0.23
0.69
1.55
TOPSOIL
GLACIAL TILL: Loose tocompact, grey silty sand withclay, gravel and cobbles
TYPE
%
STRATA PLOT
Grey-brown SILTY CLAYwith sand
(m)
REMARKS
Constr
uction
Consulting
(m)
Engineers
PG2618
BORINGS BY
SOIL PROFILE AND TEST DATA
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
20 40 60 80
20 40 60 80 100
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel DATE
N VALUE
RECOVERY
Proposed Development - McNeely Avenue
DATUM
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
FILE NO.
NUMBER
Carleton Place, Ontario
ELEV.SAMPLE
TP11
DEPTH
Undisturbed
or RQD
Constr
uction
GROUND SURFACE
1G
2.31
3.12
Possible FILL: Mixture of siltyclay, sand, cobbles andboulders
GLACIAL TILL: Compact,grey-brown silty sand with clay,gravel and cobbles
End of Test Pit
Practical refusal to excavation@ 3.12m depth
(TP dry upon completion)
31 January 2012
TYPE
%
STRATA PLOT
0
1
2
3
SOIL PROFILE AND TEST DATA
Hydraulic Shovel
Consulting
(m)
Engineers
20 40 60 80
BORINGS BY
(m)
REMARKS
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
PG2618FILE NO.
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
Shear Strength (kPa)
RECOVERY
DATUM
SOIL DESCRIPTION
Proposed Development - McNeely Avenue
HOLE NO.
Pen. Resist. Blows/0.3m
NUMBER
Carleton Place, Ontario
ELEV.SAMPLE
TP12
DEPTH
Undisturbed
or RQD
Constr
uction
GROUND SURFACE
1G
1.52
2.41
Possible FILL: Sitly sand withgravel, topsoil and wood
GLACIAL TILL: Compact,brown silty clay with sand,gravel and cobbles
End of Test Pit
Practical refusal to excavation@ 2.41m depth
(TP dry upon completion)
31 January 2012
TYPE
%
STRATA PLOT
0
1
2
SOIL PROFILE AND TEST DATA
Hydraulic Shovel
Consulting
(m)
Engineers
20 40 60 80
BORINGS BY
(m)
REMARKS
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
PG2618FILE NO.
Preliminary Geotechnical Investigation
DATE
20 40 60 80 100
N VALUE
Shear Strength (kPa)
RECOVERY
DATUM
SOIL DESCRIPTION
Proposed Development - McNeely Avenue
HOLE NO.
Pen. Resist. Blows/0.3m
ELEV.DEPTHSAMPLE
Carleton Place, Ontario
TP13
NUMBER
Undisturbed
or RQD
Constr
uction
GROUND SURFACE
1
2
G
G
1.52
4.30
Possible FILL: Topsoil, peatand wood
Firm to stiff, grey SILTYCLAY
End of Test Pit
Practical refusal to excavation@ 4.30m depth
(Groundwater infiltration @1.1m depth)
0
1
2
3
4
TYPE
%
STRATA PLOT
SOIL PROFILE AND TEST DATA
REMARKS
Consulting
(m)
Engineers
20 40 60 80
(m)
BORINGS BY
50 mm Dia. Cone
Pie
zom
ete
r
154 Colonnade Road South, Ottawa, Ontario K2E 7J5
patersongroup
Remoulded
Water Content %
PG2618
N VALUE
31 January 2012
Preliminary Geotechnical Investigation
Hydraulic Shovel
20 40 60 80 100
RECOVERY
DATUM
DATE
FILE NO.
Proposed Development - McNeely Avenue
HOLE NO.
Pen. Resist. Blows/0.3m
SOIL DESCRIPTION
Shear Strength (kPa)
SYMBOLS AND TERMS
SOIL DESCRIPTION Behavioural properties, such as structure and strength, take precedence over particle gradation in
describing soils. Terminology describing soil structure are as follows:
Desiccated - having visible signs of weathering by oxidation of clay
minerals, shrinkage cracks, etc.
Fissured - having cracks, and hence a blocky structure.
Varved - composed of regular alternating layers of silt and clay.
Stratified - composed of alternating layers of different soil types, e.g. silt
and sand or silt and clay.
Well-Graded - Having wide range in grain sizes and substantial amounts of
all intermediate particle sizes (see Grain Size Distribution).
Uniformly-Graded - Predominantly of one grain size (see Grain Size Distribution).
The standard terminology to describe the strength of cohesionless soils is the relative density, usually
inferred from the results of the Standard Penetration Test (SPT) ‘N’ value. The SPT N value is the
number of blows of a 63.5 kg hammer, falling 760 mm, required to drive a 51 mm O.D. split spoon
sampler 300 mm into the soil after an initial penetration of 150 mm.
Relative Density ‘N’ Value Relative Density %
Very Loose <4 <15
Loose 4-10 15-35
Compact 10-30 35-65
Dense 30-50 65-85
Very Dense >50 >85
The standard terminology to describe the strength of cohesive soils is the consistency, which is based on
the undisturbed undrained shear strength as measured by the in situ or laboratory vane tests,
penetrometer tests, unconfined compression tests, or occasionally by Standard Penetration Tests.
Consistency Undrained Shear Strength (kPa) ‘N’ Value
Very Soft <12 <2
Soft 12-25 2-4
Firm 25-50 4-8
Stiff
Very Stiff
50-100
100-200
8-15
15-30
Hard >200 >30
SYMBOLS AND TERMS (continued)
SOIL DESCRIPTION (continued) Cohesive soils can also be classified according to their “sensitivity”. The sensitivity is the ratio between
the undisturbed undrained shear strength and the remoulded undrained shear strength of the soil.
Terminology used for describing soil strata based upon texture, or the proportion of individual particle
sizes present is provided on the Textural Soil Classification Chart at the end of this information package.
ROCK DESCRIPTION The structural description of the bedrock mass is based on the Rock Quality Designation (RQD).
The RQD classification is based on a modified core recovery percentage in which all pieces of sound core
over 100 mm long are counted as recovery. The smaller pieces are considered to be a result of closely-
spaced discontinuities (resulting from shearing, jointing, faulting, or weathering) in the rock mass and are
not counted. RQD is ideally determined from NXL size core. However, it can be used on smaller core
sizes, such as BX, if the bulk of the fractures caused by drilling stresses (called “mechanical breaks”) are
easily distinguishable from the normal in situ fractures.
RQD % ROCK QUALITY
90-100 Excellent, intact, very sound
75-90 Good, massive, moderately jointed or sound
50-75 Fair, blocky and seamy, fractured
25-50 Poor, shattered and very seamy or blocky, severely fractured
0-25 Very poor, crushed, very severely fractured
SAMPLE TYPES
SS - Split spoon sample (obtained in conjunction with the performing of the Standard
Penetration Test (SPT))
TW - Thin wall tube or Shelby tube
PS - Piston sample
AU - Auger sample or bulk sample
WS - Wash sample
RC - Rock core sample (Core bit size AXT, BXL, etc.). Rock core samples are
obtained with the use of standard diamond drilling bits.
SYMBOLS AND TERMS (continued)
GRAIN SIZE DISTRIBUTION
MC% - Natural moisture content or water content of sample, %
LL - Liquid Limit, % (water content above which soil behaves as a liquid)
PL - Plastic limit, % (water content above which soil behaves plastically)
PI - Plasticity index, % (difference between LL and PL)
Dxx - Grain size which xx% of the soil, by weight, is of finer grain sizes
These grain size descriptions are not used below 0.075 mm grain size
D10 - Grain size at which 10% of the soil is finer (effective grain size)
D60 - Grain size at which 60% of the soil is finer
Cc - Concavity coefficient = (D30)2 / (D10 x D60)
Cu - Uniformity coefficient = D60 / D10
Cc and Cu are used to assess the grading of sands and gravels:
Well-graded gravels have: 1 < Cc < 3 and Cu > 4
Well-graded sands have: 1 < Cc < 3 and Cu > 6
Sands and gravels not meeting the above requirements are poorly-graded or uniformly-graded.
Cc and Cu are not applicable for the description of soils with more than 10% silt and clay
(more than 10% finer than 0.075 mm or the #200 sieve)
CONSOLIDATION TEST
p’o - Present effective overburden pressure at sample depth
p’c - Preconsolidation pressure of (maximum past pressure on) sample
Ccr - Recompression index (in effect at pressures below p’c)
Cc - Compression index (in effect at pressures above p’c)
OC Ratio Overconsolidaton ratio = p’c / p’o
Void Ratio Initial sample void ratio = volume of voids / volume of solids
Wo - Initial water content (at start of consolidation test)
PERMEABILITY TEST
k - Coefficient of permeability or hydraulic conductivity is a measure of the ability of
water to flow through the sample. The value of k is measured at a specified unit
weight for (remoulded) cohesionless soil samples, because its value will vary
with the unit weight or density of the sample during the test.
APPENDIX 2
FIGURE 1 - KEY PLAN
DRAWING PG2793-1 - TEST HOLE LOCATION PLAN
FIGURE 1
KEY PLAN
SITE