performance of condenser and effect of vacuum in 120mw thermal power plant.ppt (1)
TRANSCRIPT
![Page 1: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/1.jpg)
PERFORMANCE OF CONDENSER AND EFFECT OF VACUUM IN 120 MW THERMAL POWER PLANT
Department of mechanical engineering
Gandhiji Institute of science and technologyApproved by AICTE, New Delhi , Affiliated to JNTU,
KAKINADAGattu- Bhimavaram (P) , Vatsai(M), Krishna Dist., A.P-
521175
![Page 2: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/2.jpg)
UNDER GUIDE BY : HEAD OF DEPARTMENT:
SHAIK MOULALI M.Tech K. PRADEEP KUMAR M.TECH
Asst. Professor Asst. Professor
PRESENTED BY :
UJJAWAL KUMAR SHARMA 13JF1A0344
SAURAV RANJAN 13JF1A0338
CHANDAN KUMAR 13JF1A0307
A. SUDHEER KUMAR 14JF5A0306
A. SURESH KUMAR 14JF1A0307
U. NAGARAJU 14JF1A0304
![Page 3: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/3.jpg)
CONTENTS
Abstract
Introduction
Various Method For Condenser Cleaning For Improvement Of Its Performance
Condenser performance
Results And Graphs
Conclusion
![Page 4: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/4.jpg)
Abstract
The purpose of present project is to analyze the performance of condenser at 120 MW thermal power
plant and comparison made with the partial loads of 116
MW and 110 MW. It is used as the guidance for the scheduling maintenance outages on the basis of performance trades.
Here an attempt is made on various factors like vacuum systems, circulating water system, that effect on the actual performance of condenser.
The whole project carried out at 120 MW thermal station in unit no.7 at KTPS, Paloncha ,Kothaguddem.
![Page 5: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/5.jpg)
INTRODUCTION
About Thermal Power Plant
About APGENCO
About KTPS
Condenser
Circulating Water System
Cooling Tower
![Page 6: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/6.jpg)
Plant layout
![Page 7: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/7.jpg)
CONDENSATE SYSTEM
Condenser Types of condenser
1) Direct contact
![Page 8: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/8.jpg)
Surface contact
![Page 9: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/9.jpg)
Constructional feature
Air leakage in condenser
Location of air leakage
Disadvantages of detecting air leakage in condenser
Circulating water leakages
Effect of cooling water leakage into the condensate
Initial indication of a tube leak
Air extraction system
![Page 10: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/10.jpg)
Various Methods for Condenser Cleaning For Improvement Of Its Performance
Cleaning With Wire Brushes And Rods
1.Nylon Brush Type
2.Steel Brush Type
3.Sponge Ball Type
Bullet cleaning
Chemical cleaning during shutting down
Condenser on load tube cleaning system (OLTC system)
![Page 11: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/11.jpg)
PERFORMANCE CALCULATIONS
AT LAOD 116 MW:
Main steam flow =348 tons
Main steam Temperature = 537 oC
Main steam Pressure =132kg/cm2
CW inlet temperature =29 oC
CW outlet temperature =39 oC
LP turbine exhaust steam temp. = 48 oC
Condenser Vacuum =0.91 bar
Efficiency of condenser =52.6 %
Vacuum Efficiency = 95.56 %
![Page 12: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/12.jpg)
AT LOAD 110 MW
Main steam flow = 335 tons
Main steam temperature =535 oC
Main steam pressure = 125kg/cm2
CW inlet temperature = 34 oC
CW outlet Temperature = 43 oC
LP turbine Exhaust temperature = 52 oC
Condenser Vacuum =0.88 bar
Efficiency of condenser = 50 %
Vacuum Efficiency = 98.2 %
![Page 13: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/13.jpg)
Results And Graphs
The various parameters in the performance are noted and their relations are plotted :
1.Load vs vacuum
2.cooling water vs vacuum
![Page 14: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/14.jpg)
![Page 15: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/15.jpg)
3.Latent heat vs cooling water flow rate
![Page 16: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/16.jpg)
4. Vacuum vs cooling water outlet
![Page 17: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/17.jpg)
CONCLUSION
the parameter like condenser duty, vacuum efficiency, clean lines factor, cooling water flow, latent heat and performance of condenser and effect of vacuum are analyzed.
the efficiency of the condenser is reduced at reduced loads.
The main problem in condenser functioning is fouling and corrosion compared to other parameters like tube leakage and air leakage.
![Page 18: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/18.jpg)
Sponge balls cleaning method is the best method for increasing the condenser efficiency.
vacuum in the condenser effects its performance.
![Page 19: Performance of condenser and effect of vacuum in 120MW thermal power plant.ppt (1)](https://reader035.vdocuments.us/reader035/viewer/2022081815/5a6745a17f8b9ab12b8b4a29/html5/thumbnails/19.jpg)
Latent heat vs vacuum