    The Performance of CFRP Strengthening During a Real Fire

    Tim Stratford

    Jian-fei ChenMartin Gillie

    The University of Edinburgh

    The Performance ofCFRP Strengthening

    During a Real Fire

  • 8/13/2019 Performance of CFRP Under Real Fire

    2/48

    The Performance of CFRP Strengthening During a Real Fire

    BackgroundCarbon fibre reinforced polymer

    (CFRP) strengthening

  • 8/13/2019 Performance of CFRP Under Real Fire

    3/48

    The Performance of CFRP Strengthening During a Real Fire

    Background

    Example applications of Carbon Fibre ReinforcedPolymer (CFRP) strengthening systems

  • 8/13/2019 Performance of CFRP Under Real Fire

    4/48The Performance of CFRP Strengthening During a Real Fire

    Background

    Concrete substrate

    Bonding adhesive

    Carbon fibre

    (preformed plate or wet lay-up)

    Finish (coating resin etc)

    Tg

    = 65 - 100C

  • 8/13/2019 Performance of CFRP Under Real Fire

    5/48The Performance of CFRP Strengthening During a Real Fire

    Background

    Preformed CFRP plate

    Tg of resin 250C (?)

    Bonding adhesive

    Tg 65 to 100C (?)

  • 8/13/2019 Performance of CFRP Under Real Fire

    6/48The Performance of CFRP Strengthening During a Real Fire

    Concrete Society Technical Report 55:

    Fire protection.

    Regulations may require the application of an

    over-coat layer, which has been tested on the

    fully-cured composite system

    Unless a rigorous analysis is undertaken it is

    sensible to neglect the strengthening from FRPin fire situations.

    Background

  • 8/13/2019 Performance of CFRP Under Real Fire

    7/48The Performance of CFRP Strengthening During a Real Fire

    Background

  • 8/13/2019 Performance of CFRP Under Real Fire

    8/48The Performance of CFRP Strengthening During a Real Fire

    Structural alterations

    FRP carrying permanent load, and must carry load during fire

    Background

    Fire protection?

  • 8/13/2019 Performance of CFRP Under Real Fire

    9/48The Performance of CFRP Strengthening During a Real Fire

    Background

    Dalmarnock compartment fire tests

    Unique opportunity to assess CFRP

    Strengthening in a Real Fire

  • 8/13/2019 Performance of CFRP Under Real Fire

    10/48The Performance of CFRP Strengthening During a Real Fire

    Installation of

    Strengthening

  • 8/13/2019 Performance of CFRP Under Real Fire

    11/48The Performance of CFRP Strengthening During a Real Fire

    I t ll ti

  • 8/13/2019 Performance of CFRP Under Real Fire

    12/48

    The Performance of CFRP Strengthening During a Real Fire

    InstallationWINDOW

    FRP plate 11180

    1360

    1560

    1940

    2190

    2420

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    Intumescent

    Intumescent

    Unprotected

    Unprotected

    Gypsum Board

    Gypsum Board

    x

    y

    I t ll ti

  • 8/13/2019 Performance of CFRP Under Real Fire

    13/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation

    PLATES NSM

    Intumescent

    Un

    protected

    Gyproc

    In

    tumescent

    U

    nprotected

    G

    yproc

    I t ll ti FRP Pl t

  • 8/13/2019 Performance of CFRP Under Real Fire

    14/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation FRP Plates

    I t ll ti FRP Pl t

  • 8/13/2019 Performance of CFRP Under Real Fire

    15/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation FRP Plates

    Medium Modulus (MM) CFRP plate, 100x1.2mm.

    2-part ambient cure epoxy adhesive.

    Installation FRP Plates

  • 8/13/2019 Performance of CFRP Under Real Fire

    16/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation FRP Plates

    Installation FRP Plates

  • 8/13/2019 Performance of CFRP Under Real Fire

    17/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation FRP Plates

    Installation NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    18/48

    The Performance of CFRP Strengthening During a Real Fire

    Near-surface mounted FRP strengthening:

    bonded into a groove cut into the concrete soffit

    Industry perception: better fire performance.

    Installation NSM FRP

    Installation NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    19/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation NSM FRP

    Installation NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    20/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation NSM FRP

    Installation NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    21/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation NSM FRP

    Installation NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    22/48

    The Performance of CFRP Strengthening During a Real Fire

    Installation NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    23/48

    The Performance of CFRP Strengthening During a Real Fire

    Gypsum board

    2 layers of 12mm board+ intumescent sealer

    (Designed system)

  • 8/13/2019 Performance of CFRP Under Real Fire

    24/48

    The Performance of CFRP Strengthening During a Real Fire

    Experimental Setup

    Strain gauges, Thermocouples

    WINDOWy

    Experimental Setup

  • 8/13/2019 Performance of CFRP Under Real Fire

    25/48

    The Performance of CFRP Strengthening During a Real Fire

    1180

    7Pt 7Mt

    5Pt*

    4Pt

    3Pt

    6Pt

    5Mt

    6Mt

    4Mt

    3Mt

    2Pt 2Mt

    1360

    1560

    1940

    2190

    2420

    x

    7Nt

    6Nt*

    4Nt

    4Qt*

    4Rt

    3Nt

    5Nt

    2Nt

    FRP plate 1

    FRP NSM 1

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    Experimental Setup

    Thermocouples

    in FRP bondline

    WINDOWy

    Experimental Setup

  • 8/13/2019 Performance of CFRP Under Real Fire

    26/48

    The Performance of CFRP Strengthening During a Real Fire

    FRP plate 11180

    750 750

    7P 7M

    5P

    4P

    3P

    6P

    5M

    6M

    4M

    3M

    2P 2M

    1360

    1560

    1940

    2190

    2420

    FRP NSM 1

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    x

    7N

    (Dead Gauge)

    4N

    3N

    5N

    2N

    Experimental Setup

    Strain gauges on FRP

    plates (bonded side)

  • 8/13/2019 Performance of CFRP Under Real Fire

    27/48

    The Performance of CFRP Strengthening During a Real Fire

    Other instrumentation:

    -gauges on top of slab

    -gauges on top of slab

    -gauges againstadjoining wall

    Thermocouples throughslab depth

    Thermocouples within

    compartment (gas phase)

  • 8/13/2019 Performance of CFRP Under Real Fire

    28/48

    The Performance of CFRP Strengthening During a Real Fire

    Results

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    29/48

    The Performance of CFRP Strengthening During a Real Fire

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    30/48

    The Performance of CFRP Strengthening During a Real Fire

    Gas-phase temperatures

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    0 5 10 15 20

    Time (mins)

    Temperatu

    re(C)

    TC-12-2

    TC-14-2

    TC-17-2

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    31/48

    The Performance of CFRP Strengthening During a Real Fire

    ResultsUnprotected FRP Plate

  • 8/13/2019 Performance of CFRP Under Real Fire

    32/48

    The Performance of CFRP Strengthening During a Real Fire

    Fibres on floor (resin burnt off)

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    ResultsIntumescent + FRP Plate

  • 8/13/2019 Performance of CFRP Under Real Fire

    33/48

    The Performance of CFRP Strengthening During a Real Fire

    Mostly debonded.Resin mostly burnt off.

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    ResultsGypsum board + FRP Plate

  • 8/13/2019 Performance of CFRP Under Real Fire

    34/48

    The Performance of CFRP Strengthening During a Real Fire

    Gypsum board intact.Plate and adhesive visually sound.

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    ResultsUnprotected NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    35/48

    The Performance of CFRP Strengthening During a Real Fire

    Bonding adhesive burnt awayfrom beneath and to sides,

    leaving fibre in FRP exposed.

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    ResultsIntumescent + NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    36/48

    The Performance of CFRP Strengthening During a Real Fire

    Intumescent layer intact;FRP and adhesive in place.

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    ResultsGypsum board + NSM FRP

  • 8/13/2019 Performance of CFRP Under Real Fire

    37/48

    The Performance of CFRP Strengthening During a Real Fire

    Gypsum board sound.FRP and adhesive visually sound.

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    38/48

    The Performance of CFRP Strengthening During a Real Fire

    FRP Plates Bondline Temperatures

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    0 10 20 30 40 50 60

    Time (mins)

    Temperat

    ure(C)

    Unprotected

    Intumescent

    Gypsum Board

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    39/48

    The Performance of CFRP Strengthening During a Real Fire

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

    NSM FRP Bondline Temperatures

    0

    50

    100

    150

    200

    250

    300

    350

    0 10 20 30 40 50 60

    Time (mins)

    Temperat

    ure(C)

    Unprotected

    Intumescent

    Gypsum Board

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    40/48

    The Performance of CFRP Strengthening During a Real Fire

    NSM FRP Bondline Temperatures

    0

    50

    100

    150

    200

    250

    300

    350

    0 10 20 30 40 50 60

    Time (mins)

    Temperature(C)

    Unprotected

    Intumescent

    Gypsum Board

    FRP Plates Bondline Temperatures

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    0 10 20 30 40 50 60

    Time (mins)

    Tempera

    ture(C)

    Unprotected

    Intumescent

    Gypsum Board

    Temperatures >> Tg in all tests.

  • 8/13/2019 Performance of CFRP Under Real Fire

    41/48

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    42/48

    The Performance of CFRP Strengthening During a Real Fire

    NSM Plates - Central Strain Gauge Readings

    0

    500

    1000

    1500

    2000

    2500

    3000

    3500

    4000

    4500

    5000

    0 10 20 30 40 50 60

    Time (min)

    Strain(strain)

    Unprotected

    Intumescent

    Gypsum Board

    WINDOW

    FRP plate 1

    FRP NSM

    FRP plate 2

    FRP NSM 2

    FRP plate 3

    FRP NSM 3

  • 8/13/2019 Performance of CFRP Under Real Fire

    43/48

    Results

  • 8/13/2019 Performance of CFRP Under Real Fire

    44/48

    The Performance of CFRP Strengthening During a Real Fire

    NSM Plates - Central Strain Gauge Readings

    0

    500

    1000

    1500

    2000

    2500

    3000

    3500

    4000

    4500

    5000

    0 10 20 30 40 50 60

    Time (min)

    Strain(strain)

    Unprotected

    Intumescent

    Gypsum Board

    NSM Plates - End Strain Gauge Readings

    -500

    0

    500

    1000

    1500

    2000

    2500

    3000

    3500

    0 10 20 30 40 50 60

    Time (min)

    Strain(strain)

    Unprotected

    Intumescent

    Gypsum Board

    Strains indication of catastrophic failureNB: - Corrected for temperature effects using T.C. data.

    - All strains are the result of thermal effects: no applied load.

  • 8/13/2019 Performance of CFRP Under Real Fire

    45/48

    The Performance of CFRP Strengthening During a Real Fire

    Ongoing work and

    Conclusions

    Ongoing Work

  • 8/13/2019 Performance of CFRP Under Real Fire

    46/48

    The Performance of CFRP Strengthening During a Real Fire

    Further analysis of complete strain and

    thermal dataset

    Characterisation of properties of materials used

    Modelling of composite strengthened slab

    (thermal strains in concrete)

    Thermal analysis

    Conclusions

  • 8/13/2019 Performance of CFRP Under Real Fire

    47/48

    The Performance of CFRP Strengthening During a Real Fire

    During a real fire, the glass transition temperature

    of the adhesive is exceeded.

    Gypsum board can be used to insulate the FRP,

    but further research is required before it can

    be reliably designed

    The integrity of NSM strengthening is superior

    to plate FRP strengthening during a fire.