Performance Measurements on Performance Measurements on Power Line Carrier Data Power Line Carrier Data Transmissions in Indoor Office Transmissions in Indoor Office Environments Environments University "Stefan cel Mare" Suceava - Romania Faculty of Electrical Engineering and Computer Science COCA Eugen, Ph.D. POTORAC Dan Alin, Ph.D.

Upload: jamel-waldie

Post on 31-Mar-2015

217 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

Performance Measurements on Power Performance Measurements on Power Line Carrier Data Transmissions in Line Carrier Data Transmissions in

Indoor Office EnvironmentsIndoor Office Environments

University "Stefan cel Mare" Suceava - Romania

Faculty of Electrical Engineering and Computer Science

COCA Eugen, Ph.D.POTORAC Dan Alin, Ph.D.

Page 2: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

22

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

› Introduction

› Data communications over power lines

› Field measurements results

› Conclusions

Page 3: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

33

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

PLC = Data over Power Lines

1950 - Data transmission on high voltage power lines

75 to 9600 bps

Page 4: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

44

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Radio link

Low Speed PLC

Leased Line

No Communication

Page 5: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

55

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Radio link

Low Speed PLC

Leased Line

No Communication

Page 6: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

66

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Radio link

Low Speed PLC

Leased Line

High Speed PLC

Page 7: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

77

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Data valid on 03/2005

Low voltage solution providers

Page 8: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

88

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Data valid on 03/2005

Low voltage solution providers

Very high speed transmission tests announcedlate 2005 in Germany and Spain (100Mbps)

Page 9: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

99

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Network topology used for our field tests

Field measurements results

Power

Devices

Load 1

Load 2

Distance

Page 10: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1010

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Network topology used for our field tests

Field measurements results

Power

Devices

Load 1

Load 2

Distance

Page 11: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1111

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Network topology used for our field tests

Field measurements results

Power

Devices

Load 1

Load 2

Distance

Page 12: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1212

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Network topology used for our field tests

Field measurements results

Power

Devices

Load 1

Load 2

Distance

Page 13: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1313

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Network topology used for our field tests

Field measurements results

Power

Devices

Load 1

Load 2

Distance

Page 14: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1414

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Network topology used for our field tests

Field measurements results

Power

Devices

Load 1

Load 2

Distance

Page 15: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1515

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Test configuration - Low distance~ 50m

Page 16: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1616

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Reply from 192.168.100.103 : bytes=32 time=16ms TTL=62Reply from 192.168.100.103 : bytes=32 time<10ms TTL=62Reply from 192.168.100.103 : bytes=32 time=15ms TTL=62Reply from 192.168.100.103 : bytes=32 time<10ms TTL=62Ping statistics for 192.168.100.103 :Packets: Sent = 393, Received = 392, Lost = 1 (0% loss),Approximate round trip times in mili-seconds:Minimum = 0ms, Maximum = 23ms, Average = 6ms

Low distance - Excellent transmission quality~ 50m

Page 17: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1717

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Reply from 192.168.100.103 : bytes=32 time=126ms TTL=62Reply from 192.168.100.103 : bytes=32 time=18ms TTL=62Reply from 192.168.100.103 : bytes=32 time=156ms TTL=62Reply from 192.168.100.103 : bytes=32 time=118ms TTL=62Ping statistics for 192.168.100.103 :Packets: Sent = 1567, Received = 1504, Lost = 63 (4% loss),Approximate round trip times in milli-seconds:Minimum = 0ms, Maximum = 328ms, Average = 124ms

Long distance - Poor transmission quality~ 350m

Page 18: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

1818

Performance Measurements on Power Line Carrier Data Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office EnvironmentsTransmissions in Indoor Office Environments

ECUMICT 2006

Conclusions

› Good performances for Web and Email services

› Energy supply blackout VoIP problems (no 112)

› EMC related problems (shortwave interferences)

› Future investigation and filed tests

Page 19: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

Web: Web: www.ecoca.roE-mail: [email protected]: [email protected]

PLC partnershipsPLC partnershipsthrough our Research Centerthrough our Research Center

- Real world tests on low voltage power networks- Real world tests on low voltage power networks

- EMC related measurements in customer installations- EMC related measurements in customer installations

- Worst conditions test- Worst conditions test

SiSCON.usv.ro

Page 20: Performance Measurements on Power Line Carrier Data Transmissions in Indoor Office Environments University "Stefan cel Mare" Suceava - Romania Faculty

Thank you !Thank you !

Q u e s t i o n s ?Q u e s t i o n s ?