  • Perfect climate for travelling

    Ventilation and fire protection technology at airports Comfort and safety for passengers

  • The art of handling airTROX understands the art of competently handling air like no other company.

    Since its foundation in 1951, TROX has been developing sophisticated

    components and efficient systems for ventilation and air conditioning as well

    as for fire and smoke protection. Dedicated research has made TROX a leader

    of innovation in these fields.

    Perfect systems from a single source.The level of interaction between technical building services can make or break

    the whole system. This is why TROX offers everything from a single source.

    Air handling unit and ventilation components complement each other perfectly.

    This results in maximum energy efficiency while the coordination effort during

    the design and installation stages for a project is reduced to a minimum.

    The perfect system for each building.Working closely with its customers, TROX develops specific systems that take

    the relevant criteria for each building into account and meet the requirements

    of its occupants. This close cooperation leads to sustainable solutions that

    help to increase people's well-being and to protect life and the environment.

    2

  • Perfect climate for travelling

    Airports are huge complexes with many and diverse requirements on ventilation

    and air conditioning. They are 'places of public assembly' and hence subject

    to safety regulations that ensure sufficient fresh air by mechanical ventilation

    and air conditioning systems. In the event of a fire, such systems also aid in

    the mechanical smoke extract in order to keep escape routes free from smoke.

    Air conditioning system solutions for the entire complex. As a system supplier, TROX offers the broadest spectrum of ventilation and

    air conditioning components, from air handling units, fire dampers and tunnel

    dampers to air terminal devices and air-water systems, and to control components

    and systems, providing specialist consultants with a multitude of options for

    complete airport solutions. Today, and in fact more than ever before, the focal

    point of air conditioning system design is energy efficiency. TROX has long been

    committed to the development of adaptable high-efficiency system solutions

    that help not only to save resources but also to reduce operating costs.

    The highest safety standards due to innovative fire protection and smoke extract technology. TROX has always provided important input to innovative solutions and been at the

    forefront of developing and enhancing fire and smoke protection as well as control

    systems, which are immensely important particularly at airports. Fire tests to

    determine the fire protection classification of building products for ventilation and

    air conditioning systems in accordance with national and international standards

    are regularly carried out in the TROX International Center for Fire Protection (ICB),

    which is the most modern of its kind.

    Perfect air conditioning for airports:

    • comprehensive and integrated with the central BMS

    • adaptable and efficient

    • reliable and safe

    Palma de Mallorca, Spain Hamburg, Germany Madrid, Spain

    3

  • At home in the world's top airports

    Whatever your destination, chances are that TROX is already there. In many

    airports around the world, TROX products ensure well-being and safety for staff

    and passengers alike: with German engineering at its best!

    TROX components and systems are installed at airports on all five continents.

    Whether international transport hubs such as New York JFK, Frankfurt, Singapore

    or Dubai, or domestic airports in other countries such as Australia, Ireland, Poland,

    Switzerland, Hungary, Austria, Greece or Brazil: Ventilation and air conditioning

    components and, even more importantly, innovative and proven fire protection

    and smoke control technology from TROX can be found at numerous airports all over

    the world. TROX has also developed individual solutions. The jet nozzles at Madrid

    Barajas, for example, blend in perfectly with the terminal's characteristic architecture

    by star architects Rogers and Estudio Lamela.

    This application brochure is dedicated to the most critical ventilation and air

    conditioning issues that airports face these days. The main focus is on airport

    terminal ventilation, control, and fire and smoke protection. The requirements

    on air in the office buildings, restaurants, and shops at an airport are no

    different from those of other buildings where people go for work or leisure.

    Frankfurt/Main, Germany

    Integration: TROX jet nozzles in the check-in area blend in nicely with the architecture.

    Madrid, Spain

    4

  • 5

  • Cosmopolitan air

    The load requirements in an airport terminal vary. As a consequence, flexible

    air conditioning is in demand, creating a complex challenge for designers and

    specialist consultants. Most terminal buildings are unusually high and comprise

    diverse functional areas as well as stationary workplaces to which the comfort

    criteria for workplaces as stipulated in regulations and directives apply. It is

    therefore possible to create a so-called micro climate in the area where the

    ground staff works – a micro climate with its own air supply and individual

    heating or cooling systems.

    6

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    1617

    1819

  • Other aspects that need attention are related to the specific use of an airport

    terminal. Load requirements fluctuate and may be extreme – throughout a day

    but also depending on the season. High levels of comfort for passengers and staff

    can only be achieved with unconventional air handling concepts. The various

    concepts as well as the most critical parameters are given on the following pages.

    7

    X-CUBE air handling units

    Active chilled beams

    Jet nozzles

    Floor diffusers

    Ceiling diffusers

    Decentralised ventilation systems

    Control units and systems

    X-FANS EC roof fans

    X-FANS jet ventilation systems

    Fire dampers

    X-FANS impulse jet fans

    Tunnel dampers

    X-FANS axial fans

    Smoke extract dampers

    TROXNETCOM

    X-FANS smoke exhaust fans for roof installation

    External weather louvres

    Filters

    Sound attenuators

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    9

    12

    13

    14

    15

    TROX components, units and systems in an airport:

  • Typical values of the most critical parameters in selected airport areas

    Specific area m²/person ≥ 3 ≥ 5 ≥ 5 ≥ 3 ≥ 2 ≥ 1.5 ≥ 7 ≥ 2 ≥ 10 ≥ 2 Based on EN 15251

    Fresh air flow rate in m³/(h m²) 10 - 12 6 6 10 - 12 18 - 20 20 7 15 60 - 80 p.p . 6 15 10 6 EN 15251

    Fresh air flow rate in l/(s m²) 3 - 4 2 2 3 - 4 5 - 6 6 2 4 16 - 22 p.p . 2 4 3 2 EN 15251

    Design values for room temperature [°C]

    Typical minimum room temperature when heating (winter) 20 20 20 20 20 18 20 20 20 20 EN 15251

    Typical maximum room temperature when cooling (summer) 26 26 26 26 26 25 26 - 26 26 EN 15251

    Sound pressure level, typical range [dB(A)]

    Standard design value 45 45 45 45 45 45 45 40 55 40 35 45 45 45 EN 15251

    Air handling and transport

    Air handling units • • • • • • • • • • • • • • •

    Ventilation fans • • • Centrifugal, axial, duct, wall and roof fans

    Filters • • • • • • • • • • •

    Sound attenuators • • • • • • • • • • • •

    Control systems

    Volume flow controllers • • • • • •

    Control of AHUs • • • • • • • • • • •

    Ventilation systems

    All-air system - mixed flow (p. 12) • • • • • • • • • • • •

    All-air system - displacement flow (p. 14) • • • • • • • •

    Air-water systems (p. 16) • • • • • • • •

    Smoke extract / fire protection / smoke control

    Smoke dilution and extract • • • • • • • • Engineering principles

    Creation of layers and smoke extract • • • • • • • • • • DIN 18232, part 2 (natural systems) and part 5 (mechanical systems)

    Smoke exhaust with jet ventilation system • • VDI 2053 Engineering principles

    Pressurisation systems • • EN 12101, part 6

    Components for smoke control and fire protection systems

    TROXNETCOM with AS-i or LON Modbus • • • • • • • • • • • • •

    Smoke exhaust fans • • • • • • • • Extract air systems • • • • •F600, F400, F300, F200**

    Axial, roof, centrifugal, wall fans

    Smoke extract dampers • • • • • • • • • • • • EN 12101, part 8

    Fire dampers • • • • • • • • • • • • EN 15650

    Smoke detectors • • • • • • • • • • • • •

    Duct smoke detectors • • • • • • • • • • • •

    * For information on dampers please refer to the 'Safety first' section of this brochure. ** Installation in the fire zone, outside of the fire zone, or in a ventilated room; EN 12101, part 3.

    Depa

    rtur

    e ha

    ll

    Chec

    k-in

    cou

    nter

    s

    Serv

    ice

    coun

    ters

    Wai

    ting

    area

    s

    Loun

    ges

    Secu

    rity

    (b

    agga

    ge c

    heck

    )

    Bars

    , caf

    é,

    bis

    tro,

    rest

    aura

    nt

    Shop

    s

    Design criteria Terminal Shops and restaurants

    8

  • Typical values of the most critical parameters in selected airport areas

    Specific area m²/person ≥ 3 ≥ 5 ≥ 5 ≥ 3 ≥ 2 ≥ 1.5 ≥ 7 ≥ 2 ≥ 10 ≥ 2 Based on EN 15251

    Fresh air flow rate in m³/(h m²) 10 - 12 6 6 10 - 12 18 - 20 20 7 15 60 - 80 p.p . 6 15 10 6 EN 15251

    Fresh air flow rate in l/(s m²) 3 - 4 2 2 3 - 4 5 - 6 6 2 4 16 - 22 p.p . 2 4 3 2 EN 15251

    Design values for room temperature [°C]

    Typical minimum room temperature when heating (winter) 20 20 20 20 20 18 20 20 20 20 EN 15251

    Typical maximum room temperature when cooling (summer) 26 26 26 26 26 25 26 - 26 26 EN 15251

    Sound pressure level, typical range [dB(A)]

    Standard design value 45 45 45 45 45 45 45 40 55 40 35 45 45 45 EN 15251

    Air handling and transport

    Air handling units • • • • • • • • • • • • • • •

    Ventilation fans • • • Centrifugal, axial, duct, wall and roof fans

    Filters • • • • • • • • • • •

    Sound attenuators • • • • • • • • • • • •

    Control systems

    Volume flow controllers • • • • • •

    Control of AHUs • • • • • • • • • • •

    Ventilation systems

    All-air system - mixed flow (p. 12) • • • • • • • • • • • •

    All-air system - displacement flow (p. 14) • • • • • • • •

    Air-water systems (p. 16) • • • • • • • •

    Smoke extract / fire protection / smoke control

    Smoke dilution and extract • • • • • • • • Engineering principles

    Creation of layers and smoke extract • • • • • • • • • • DIN 18232, part 2 (natural systems) and part 5 (mechanical systems)

    Smoke exhaust with jet ventilation system • • VDI 2053 Engineering principles

    Pressurisation systems • • EN 12101, part 6

    Components for smoke control and fire protection systems

    TROXNETCOM with AS-i or LON Modbus • • • • • • • • • • • • •

    Smoke exhaust fans • • • • • • • • Extract air systems • • • • •F600, F400, F300, F200**

    Axial, roof, centrifugal, wall fans

    Smoke extract dampers • • • • • • • • • • • • EN 12101, part 8

    Fire dampers • • • • • • • • • • • • EN 15650

    Smoke detectors • • • • • • • • • • • • •

    Duct smoke detectors • • • • • • • • • • • •

    * For information on dampers please refer to the 'Safety first' section of this brochure. ** Installation in the fire zone, outside of the fire zone, or in a ventilated room; EN 12101, part 3.

    Loun

    ges

    Kitc

    hen

    (e

    xtra

    ct a

    ir)

    Offic

    es

    Unde

    rgro

    und

    ca

    r par

    k

    Stai

    rwel

    ls

    Met

    ro s

    tatio

    n

    Esca

    pe t

    unne

    ls

    Conf

    eren

    ce a

    nd

    mee

    ting

    room

    s

    Toile

    ts

    (ex

    trac

    t ai

    r)

    Shops and restaurants Administration Other

    Note

    9

  • 10

    Departure hall at Düsseldorf International airport, Germany, with jet nozzles, VDW air terminal devices and X-FANS smoke exhaust fans.

    Not shown: large number of fire dampers. As a special feature, the fire dampers are equipped with smoke detectors and spring return actuators.

    Ready for take-off

  • Ready for take-off

    Airports have their own aerodynamics.

    Airport terminals constitute probably the most challenging task for specialist consultants.

    On the following pages we describe some alternative approaches and deal with the vital role

    of intelligent control systems and of safe fire protection and smoke extract technology.

    11

  • Airport air All-air system: mixed flow

    Good air quality in a terminal building can be achieved only with a sufficient

    fresh air flow rate that is based on the number of occupants. With a classic all-air

    system one would need a specific supply air flow rate of 6.0 to 20.0 m³/(h m²).

    The required temperature is generally provided by the supply air. In the highest

    areas of the departure and arrival halls, air is usually supplied with either

    actuator-driven or self-powered jet nozzles.

    In functional areas with a clear height of up to 6.0 m, fresh air is supplied with

    adjustable swirl diffusers or other ceiling diffusers. Mixed flow ventilation means

    that supply air and room air mix evenly such that a uniform temperature and air

    distribution is quickly achieved. Sophisticated air terminal devices with specific

    blade contours ensure that high airflow velocities and temperature differences

    are quickly reduced.

    Variant: Mixed flow ventilation with jet nozzlesOccupied zone: airflow velocity near the ground - Sitting areas and workstations < 0.2 m/s

    - Free jet entry area (should not be used for workstations) < 0.5 m/s

    Supply air temperature – mixed flow 16 to 18   °C

    Proportional cooling capacity in case of mixed flow up to 80 W/m²

    The adjustable TJN jet nozzles are made of high-grade polymer and allow for adapting the supply air flow to different conditions. The enhanced jet nozzles

    are acoustically optimised and more energy-efficient than similiar products since

    the actuator is fitted on the outside and does not lead to any additional pressure

    drop.

    VDL swirl diffusers are suitable for large volume flow rate ranges and can be adjusted mechanically or manually. Blade adjustment allows for optimum

    ventilation (purging) of the occupied zone while high comfort requirements

    are met at the same time.

    The stand-alone LON-WA TDC module is used for the control of adjustable air terminal devices independent of the temperature; it can be integrated

    with a central BMS easily and flexibly.

    AIRNAMIC swirl diffusers are fitted with innovative air distribution elements that combine an extremely quiet air discharge with the optimum swirl. The most

    demanding comfort requirements can thus be met, even with very high volume

    flow rates.

    PASSCLEAN ceiling diffusers are ideal for departure halls with their high passenger volumes. With PASSCLEAN diffusers, contamination of the ceiling

    is avoided in spite of the high secondary air induction.

    For more solutions and products please visit www.trox-airport-air.com

    Hamburg, Germany

    VDL swirl diffusers 70 – 1225 l/s

    237 – 5040 m³/h Ø 315 – 800 mm

    TJN jet nozzles 20 – 1000 l/s

    72 – 3600 m³/h Ø 160 - 400 mm

    PASSCLEAN ceiling diffusers 111 – 222 l/s

    400 – 800 m³/h Ø 600 mm

    800, 825 mm

    For rooms of standard height:AIRNAMIC swirl diffusers

    40 – 385 l/s 144 – 1386 m³/h

    Ø 400 and 600 mm 300, 600, 625 mm

    12

  • 13

  • 14

  • Airport air All-air system: displacement flow

    Displacement flow systems may be combined with mixed flow systems; they can

    also be used for situations where small or medium air volumes are required and

    where only smaller heat loads (e.g. from people or equipment) must be dissipated.

    If necessary, additional passive cooling systems may be used.

    Displacement flow systems are ideal in places where maximum comfort is required,

    e.g. for the airport staff. Low airflow velocities help to keep workplaces free from

    turbulence while ensuring high room air quality.

    Variant: Displacement flow combined with large area heating and cooling systems, e.g. chilled ceilings Airflow velocity - Occupied zone, sitting areas and workstations < 0.2 m/s

    - Near zone of displacement flow diffusers (within 5 m) < 0.5 m/s

    Supply air temperature with displacement flow ventilation 20 to 22 °C

    Proportional cooling capacity by supply air 20 to 40 W/m²

    Extract air temperature near the roof up to 32 °C

    TROX displacement flow diffusers are available for many different installation

    situations and in a multitude of forms and appealing designs; they can be

    aesthetically integrated into existing architectural designs. In fact, special

    designs have been produced for several airports.

    Displacement flow ventilation requires that the supply air temperature is lower

    than the room temperature. Displacement flow diffusers, which should be installed

    as close to the floor as possible, supply air to the room such that a supply air pool

    is created. The convection from people and other heat sources causes the air in

    this supply air pool to rise. The extract air is then removed above the occupied

    zone, ideally near the roof.

    The QL displacement flow diffusers with their special air distribution nozzles are characterised by an excellent, uniform velocity profile and a smaller near zone.

    For more solutions and products please visit www.trox-airport-air.com

    Madrid BarajasExample of combined displacement flow and mixed flow systems (jet nozzles)

    QL-WR displacement flow diffuser, circular, without duct covering

    10 – 430 l/s 36 – 1545 m³/h

    Ø 200 – 630 mm H: 600 – 2000 mm

    QL-WV displacement flow diffuser for wall installation, 90° construction for corners, without duct covering

    10 – 411 l/s 36 – 1481 m³/h

    B: 190 – 450 mm H: 600 – 1500 mm

    15

  • Airport air Air-water systems

    More and more air-water systems are employed today since the heating and cooling

    capacity of these systems can be provided independent of the required fresh air

    flow rate. Various types can be distinguished:

    • large-area heating and cooling systems, e.g. chilled ceilings,

    combined with displacement flow systems

    • passive chilled beams combined with mixed flow systems

    • active chilled beams

    Air-water systems have the advantage that the thermal energy is very efficiently

    transported by water – rather than by air. This means that less energy is required

    to provide the same heating or cooling capacity. In the airport areas with offices,

    shops and restaurants, thermal loads are ideally dissipated by water side heating

    and cooling systems.

    Air-water systems are suitable for the ventilation of functional areas with an

    average required fresh air volume of up to 12 m³/(h m²). For areas with a very high

    occupancy, such as security, an additional system can provide up to 20 m³/(h m²).

    The DID 632 active chilled beam offers comfortable ventilation and air conditioning for rooms with a high heat load. The aerodynamic properties of ceiling diffusers in

    combination with the energy-efficient dissipation of heat loads using water make

    active chilled beams the perfect solution for sustainable architectural concepts.

    PKV passive chilled beams (no supply air) are used to dissipate high interior heat loads, thereby fully achieving the energy benefits of dissipating loads with

    water.

    TROX air-water systems allow for the space-saving integration of additional components such as lighting, smoke detectors, loudspeakers or sprinklers. Air-water

    systems may be designed as canopies, for example, to accentuate a building's

    architecture, or blend in inconspicuously with the ceiling construction. All systems

    can be integrated with the central BMS.

    For more solutions and products please visit www.trox-airport-air.com London Heathrow

    DID 632 active chilled beamsPrimary air:

    6 – 85 l/s 22 – 306 m³/h

    L: 900 and 3000 mm B: 593, 598, 618 and 623 mm H: 210 mmCooling capacity up to 2450 WHeating capacity up to 2970 W

    PKV passive chilled beamsRectangular

    L: 900 – 3000 mm B: 180 – 600 mm H: 110 – 300 mmCooling capacity up to 1400 W

    16

  • 17

  • Safety first

    18

  • Safety first Effective fire protection saves lives.

    Ventilation and smoke extract technology are crucial factors for the safety of an airport terminal.

    Fire professionals will find it reassuring that they can obtain functioning fire protection and

    smoke extract systems from a single source. From smoke detectors and control components to fire

    and smoke extract dampers and to smoke exhaust fans: TROX system components complement

    each other, can be interconnected, and are easy to integrate with the central BMS.

    19

  • 20

  • Fire prevention

    Airports are complex buildings. Huge quantities of air are supplied to and extracted

    from an airport terminal. In the event of a fire, adjacent areas such as shopping

    zones must be closed off from the departure hall. Underground car parks present,

    due to their low ceiling, a particular challenge for smoke extract systems. Following

    the devastating fire at Düsseldorf airport in 1996, airports all over the world have

    examined and modernised their smoke control and smoke exhaust systems. Düsseldorf

    International is today one of the most modern and safe airports with regard to fire and

    smoke protection.

    The prime objectives of fire and smoke protection are as follows:

    • Ensure the safety of people

    • Support the firefighters in extinguishing the fire and in rescuing people

    • Ensure the safety of buildings and equipment (keep disruption of operations

    to a minimum)

    For these objectives to be achieved, modern smoke extract management

    for complex buildings must fulfil a multitude of tasks:

    • A fire must be detected, and an alarm emitted, at an early stage – even if

    the temperature remains comparatively low, e.g. in case of a smouldering fire.

    • The smoke extract system must be automatically triggered at an early stage

    to give the people in a building sufficient time to escape.

    • Spread of the fire and transmission of smoke to adjacent occupied zones

    must be prevented, e.g. by a mechanical smoke exhaust system.

    • Positive pressure must be maintained in corridors, stairwells, and escape

    and rescue routes; pressurisation systems must be installed.

    • Escape routes must allow passengers and staff to safely escape as quickly

    as possible.

    • In the event of a fire, elevators must be made to stop only on floors where

    no smoke has been detected.

    For more solutions and products please visit www.trox-airport-air.comFrankfurt/Main, Germany

    21

    A mechanical smoke exhaust system ensures a smoke-free layer with a height of at least 2.50 m, extending the time available for escape; this is essential for large indoor spaces such as departure halls, atria, or conference rooms.

  • Fire protection: tested, CE-certified and with building inspectorate approval

    Large airports offer many applications for TROX smoke extract systems. Our smoke

    extract components and systems are the basis for effective smoke extract management.

    With such safety-relevant systems, components from a single source are the best

    solution for critical interfaces.

    Our fire dampers and smoke extract dampers as well as the X-FANS smoke exhaust

    fans have been certified to EN standards and approved by the building inspectorate

    in Germany for many applications. TROX engineers are experts in their fields and

    always apply the latest findings from both TROX fire tests and tests by independent

    testing institutes to the design; as members of standardisation committees they

    also provide valuable input to these bodies.

    Intelligence inside. TROX fire engineering products.

    Fire dampers must close at a certain temperature or when smoke is detected. They effectively close off adjacent fire compartments and prevent the spread

    of fire and smoke.

    TROXNETCOM communication systems for AS-i or LON, and with Modbus or BACnet interface, ensure the seamless integration of TROX fire protection and

    smoke extract components with central building management systems. In airports,

    which are frequented by many passengers with restricted mobility, complete system

    solutions for fire protection are indispensable. They ensure that a fire is detected

    at an early stage and prevented from spreading; they also ensure the smooth

    escape of people and the evacuation of buildings. TROXNETCOM offers solutions

    that are SIL2-certified and provide overall safety even in case of a malfunction.

    TROX smoke detectors of Types RM-O-VS-D-LON/RM-O-3-D detect smoke in ducts at an early stage and independent of the temperature, and they release the fire

    dampers such that they close. The detectors are fitted with comprehensive

    self-monitoring functions (contamination, airflow, electronics) and require

    maintenance only once per year.

    Frankfurt/Main, GermanyFor more solutions and products please visit www.trox-airport-air.com

    RM-O-VS-D smoke detector• Bus-enabled version as an option • Airflow velocity: 1 to 20 m/s

    TROXNETCOM• Digital monitoring and triggering

    of fire protection and smoke control equipment

    • Highest safety standards to EN 61508 (VDMA 24200-1) tested by TUEV, Germany

    • Easy installation and integration with central BMS

    • Integral maintenance function

    22

    FK-EU/FKS-EU fire dampersRectangular B: 200 – 1500 mmH: 100 – 800 mm Classification to EN 13501-3: EI 90 (ve, ho i o) S

    FKRS-EU/FKR-EU fire dampersCircular B: 200 – 800 mmH: 100 – 200 mmClassification to EN 13501-3: EI 90 (ve, ho i o) S

  • 23

  • Infrared sensors and emitters on the walls of the Düsseldorf airport departure hall – at 5 m from the ground and with a distance of less than one metre from each other – detect smoke immediately

    and trigger an alarm. The axial fans under the ceiling start working at once to extract the smoke.

    24

  • Smoke is in the airX-FANS smoke exhaust systems

    In complex buildings, such as departure halls, smouldering fires can easily have

    devastating effects if they are not immediately detected. Mechanical smoke

    exhaust systems can provide a higher level of safety than other systems. They

    create smoke-free layers along the escape and rescue routes and therefore allow

    people in the building to escape by themselves. Smoke exhaust fans remove

    smoke gases, thus preventing smoke from spreading uncontrollably and supporting

    the firefighters in extinguishing the fire.

    Mechanical pressurised smoke exhaust systems remove not only smoke but also

    dissipate the heat, thus preventing a dangerous flash over. The required air

    transfer dampers open at the same time.

    Requirements of a pressurisation system.Keeping the layer with smoke gases separate from the smoke-free layer requires

    a delicate combination of supply and extract air; the following conditions must

    be met in particular:

    • At the boundary between the smoke gas layer and the smoke-free layer, only minimal

    horizontal and vertical airflows at low velocities should be present, if at all.

    • Supply air openings must be adequately sized and be installed at the right

    distance from each other. They must open automatically before the smoke exhaust

    fans are switched on.

    • Supply air must be discharged into the smoke compartment considerably below

    the layer with smoke gas, ideally with no or very little impulse, and at a low

    velocity (

  • Smoke exhaust in underground car parks Danger lurks below the surface

    Cars catching fire in underground car parks are more common than one should

    think. A car catching fire in a car park under an airport terminal poses

    a particularly high safety risk. The real danger, however, are the highly

    poisonous smoke gases.

    Smoke extract via the ductwork. The first and foremost task of extract air systems is removing the exhaust fumes

    through extract air ducts while fresh air is led into the garage via ventilation

    ducts or other openings such as the access slope. The heart of such a system

    is a two-stage axial fan. In the event of a fire, the second axial fan for smoke

    exhaust is automatically switched on.

    The smoke gases rise towards the ceiling from where they are removed through

    duct systems. Creating different layers is usually not possible in underground

    car parks because of the lack of height.

    Keeping spaces smoke-free with a jet ventilation system (JVS).Jet ventilation systems are an alternative to conventional smoke exhaust

    systems. When in ventilation mode, the combined effect of radiation and

    induction of the jet ventilation fan ensures a particularly efficient mixing

    of air, the removal of CO gases and hence fresh air in the underground car park.

    The volume flows calculated for the car park are created by fans installed in

    the central shafts and are directed towards the outside; dedicated extract air

    and smoke extract ducts are not required.

    In the event of a fire, the smoke gas temperature increases, and the gases rise

    towards the ceiling, where they spread. If smoke is detected, the fans, which are

    installed in the extract air ducts, are switched on and remove the smoke from

    under the ceiling. At the beginning, a layer is created which is nearly free from

    smoke. Escape and rescue routes are hence easy to recognise and allow people

    to leave the building.

    The jet ventilation fans are only switched on after about three to five minutes.

    By that time, the people will have left the underground car park via the short

    escape routes. The jet ventilation fans dissolve the smoke layers in the previously

    selected areas, and 'dead corners' are being cleared. The firefighters can now

    locate and eventually extinguish the fire without being obstructed.

    The jet ventilation system allows for large fire compartments so that underground

    car parks can be designed accordingly – open, spacious, and pleasant. Users will

    welcome the additional ease of orientation, feel better, feel safer – and are

    indeed safer in such a garage.

    Jet ventilation fans are used for the ventilation and smoke exhaust in underground car parks.

    For more solutions and products please visit www.trox-airport-air.com

    26

    X-FANS smoke exhaust fans remove the smoke gases from the individual fire compartments in the garage. Customers have a choice of different constructions for various temperature ranges, depending on the garage layout.

    Smoke Volume flow rate Temperature exhaust fans up to (m3/h)

    Roof fans 55,000 600 °C 400 °C 300 °C 200 °C

    Axial fans 265,000 600 °C 400 °C 300 °C 200 °C

    Centrifugal fans 160,000 600 °C 400 °C

    Wall fans 55,000 600 °C 400 °C 300 °C 200 °C

    Construction and performance of X-FANS smoke exhaust fans

  • 27

  • Düsseldorf, Germany

    Roger and clear

    28

  • Roger and clear Intelligent systems ensure quiet, clean and efficient air supply.

    The functional areas of an airport are usually divided into different 'control zones'. Volume flow controllers react to the air quality and adapt the volume flow rate for every zone separately and based on demand, while frequency converters control the fan speed, again based on demand. This saves valuable energy and reduces the 'air transport cost' considerably.

    X-CUBE air handling units are extremely variable and adaptable to different control strategies and room conditions.

    29

  • Air management: handling and conditioning airflows

    For an airport with its different buildings and areas, air handling units have to be

    highly variable and provide utmost adaptability to each control strategy. Flexibility

    with regard to the installation is an advantage since the units have to be adapted

    to different locations and conditions.

    The air around an airport terminal is, as expected, highly contaminated, mainly

    by unburnt kerosene. This is why effective filtering is mandatory, as are hygiene

    and ease of cleaning.

    TROX X-CUBE air handling units are very versatile. They can be individually configured and are hence suitable for a wide spectrum of applications. More than

    70 construction variants can handle volume flow rates of 1200 to 86,000 m³/h at

    an airflow velocity of 2 m/s. X-CUBE units are available as supply or extract air

    units or as a combination of both. Depending on the installation location, they can

    be arranged side by side or on top of each other. The cubes are also available for

    outside installation on roofs, and thanks to the lifting eyes at the top they can

    be easily moved and lifted with a crane. This simplifies installation and reduces

    the installation time considerably.

    The duplex powder coating (corrosion protection class C4) and the stainless steel

    condensate drip tray, which is sloped on all sides, ensure optimum corrosion

    protection. Ease of operation and cleaning are further advantages. As an option,

    the X-CUBE units can be fitted with high-efficiency activated carbon filters for the

    separation of kerosene mist. Heat recovery systems and EC fans ensure high energy

    efficiency. The units are available with an integral measurement and control system

    upon request. And last but not least, they can of course be integrated with various

    building management systems.

    TROX TLT X-FANS ventilation fans can be perfectly adapted to diverse ventilation requirements. Whether large or small airflows – or even extract air from commercial

    kitchens –, TROX TLT offers a suitable fan. Just go to the configurator software at

    www.trox-tlt.com.

    For more solutions and products please visit www.trox-airport-air.com X-CUBE air handling unit

    X-CUBE air handling unit

    The wide spectrum of TROX TLT ventilation fans suits the most diverse locations and applications.

    Extensive filter programme – certified by Eurovent.

    To find the best suitable fan, go to the configurator at www.trox-tlt.com

    30

    Ventilation fans Max. motor rating [kW] Max. volume flow rate [m3/h] Max. pressure [Pa]

    Axial fans 280 400,000 4000

    Centrifugal fans 130 200,000 4000

    Roof fans 30 55,000 2300

    Duct fans 12 12,000 1200

    X-FANS ventilation fans and performance

    A+Energieeffizienzklasse

    Raumlufttechnische GeräteHerstellerverband e.V.

    nach RLT-Richtlinie 01

  • 31

  • 32

  • For more solutions and products please visit www.trox-airport-air.com

    33

    Air management: control strategies

    The functional areas of an airport are usually divided into different 'control zones'.

    Volume flow controllers react to the air quality and adapt the volume flow rate

    for every zone separately and based on demand, while frequency converters control

    the fan speed, again based on demand. This saves valuable energy and reduces

    the 'air transport cost' considerably.

    The control strategy of the air handling unit for the base load of an airport depends

    on an adjustment of the volume flow rate in relation to the air quality. With an

    air-water system the temperature is controlled separately by water side systems.

    Only for peak loads is volume flow control included in the overall control of the

    room temperature.

    Intelligent TROX control systems ensure that all TROX air conditioning components,

    including the air handling unit, complement each other perfectly. Components,

    units and systems from a single source reduce the design and coordination effort

    considerably.

    VARYCONTROL VAV terminal units such as TVR/TVT are fitted with electronic controllers. Customers have a choice of many different control components to suit

    each situation, be it for integration with the central BMS or to safely shut off fire

    compartments (power off to close). The temperature and/or quality of the room air

    can be individually adjusted by changing the supply air flow rate. The system only

    supplies the amount of air required, which saves energy.

    VAV terminal unitsTVR, circular V: 10 – 1680 l/s V: 36 – 6048 m³/h ∆p: 20 – 1500 Pa Ø 100 – 400 mm

    TVT, square, rectangular V: 45 – 10,100 l/s V: 162 – 36,360 m³/h ∆p: 20 – 1000 Pa B: 200 – 1000 mm H: 100 – 1000 mm

    TROXNETCOM• Easy commissioning and

    integration with the central BMS• Integral maintenance function

    Frankfurt/Main, Germany

  • TROX GmbH

    Heinrich-Trox-Platz

    47504 Neukirchen-Vluyn, Germany

    Phone +49 (0) 2845 2020

    Fax +49 (0) 2845 202265

    www.troxtechnik.com

    [email protected] AL/0

    2/20

    14/t

    rave

    l clim

    ate/

    DE/e

    n •

    Subj

    ect

    to c

    hang

    e •

    All r

    ight

    s re

    serv

    ed •

    © T

    ROX

    GmbH

    02/

    2014

    Wherever you touch down, chances are

    that TROX is already there. TROX provides a

    comfortable indoor climate and ensures

    safety in the most important airports of the

    world. Our list of reference projects covers

    airports from A as in Amsterdam to Z as in

    Zurich.

    AMS – Amsterdam

    ATH – Athens

    BER – Berlin

    BCN – Barcelona

    BIO – Bilbao

    BUD – Budapest

    DRS – Dresden

    FRA – Frankfurt/Main

    HAM – Hamburg

    HKG – Hong Kong

    LHR – London

    LUX – Luxemburg

    MAD – Madrid

    MUC – Munich

    JFK – New York

    PMI – Palma de Mallorca

    GUG – Rio de Janeiro

    WAW – Warsaw

    ZRH – Zurich