KFU8-FSSP-1.D-Y Frequency voltage converter (10 kHz version) FACTORY AUTOMATION MANUAL

Upload: others

Post on 10-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • KFU8-FSSP-1.D-YFrequency voltage converter(10 kHz version)

    FACTORY AUTOMATION

    MANUAL

  • 2046792 2008-11

    KFU8-DW-1.D

    With regard to the supply of products, the current issue of the following doc-ument is applicable: The General Terms of Delivery for Products and Servic-

    es of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie

    (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship"

  • KFU8-DW-1.D046792 2008-11

    1 Introduction ............................................ 5

    2 Declaration of Conformity ..................... 7

    3 Safety ...................................................... 83.1 Symbols relevant to safety .......................................... 8

    3.2 Intended use ................................................................. 8

    3.3 General safety instructions ......................................... 9

    4 Product description ............................. 104.1 Device description...................................................... 10

    5 Operation .............................................. 125.1 Operating mode.......................................................... 12

    5.2 Setup mode................................................................. 14

    6 Appendix............................................... 22

    3

  • KFU8-DW-1.D

    046792 2008-11

    6.1 Technical data .............................................................22

    6.2 Terminal assignment ..................................................25

    6.3 Dimensions, operating and display devices.............26

    6.4 Connection diagram ...................................................27

    6.5 Functional description................................................28

    4

  • KFU8-FSSP-1.D-YIntroduction

    046792 2008-11

    KFU8-FSSP-1.D-Y

    1 Introduction

    Congratulations

    You have chosen a device manufactured by Pepperl+Fuchs. Pepperl+Fuchs develops, produces and distributes electronic sensors and interface modules for the market of automation technology on a worldwide scale.

    Before you install this device and put it into operation, please read the operating instructions thoroughly. The instructions and notes contained in this operating manual will guide you step-by-step through the installation and commissioning to ensure the trouble-free usage of this product. This is useful to you, because with this you:

    • support the safe operation of the device• can utilize the device’s entire range of functions• reduce faulty operation and the associated errors• reduce costs from downtime and incidental repairs• increase the effectiveness and operating efficiency of your plant.

    Store this operating manual somewhere safe in order to have it available for future work on the device.

    Directly after opening the packaging, please ensure that the device is intact and that the package is complete.

    5

  • KFU8-FSSP-1.D-YIntroduction

    046792 2008-11

    Symbols used

    The following symbols are used in this manual:

    Handling instructions

    This symbol denotes handling instructions.

    Contact

    If you have any questions about the device, its functions, or accessories, please contact us at:

    Pepperl+Fuchs GmbHLilienthalstraße 20068307 MannheimTelephone: +49 621 776-1111Fax: +49 621 776-271111E-Mail: [email protected]

    NOTE!

    This symbol brings important information to your attention.

    6

  • 7

    KFU8-FSSP-1.D-YDeclaration of Conformity

    046792 2008-11

    2 Declaration of Conformity

    This product has been developed and manufactured in accordance with applicable European standards and directives.

    The manufacturer of this product, Pepperl+Fuchs GmbH, in D-68307 Mannheim, Germany, has a certified quality management system in accordance with ISO 9001.

    NOTE!

    A Declaration of Conformity can be requested from the manufacturer.

    ISO9001

    KFU8-FSSP-1.D-Y

  • KFU8-FSSP-1.D-YSafety

    KFU8-FSSP-1.D-Y

    046792 2008-11

    3 Safety

    3.1 Symbols relevant to safety

    3.2 Intended use

    The KFU8* series comprises a range of devices used to display and monitor periodic signals. The devices can be used as a control cabinet module or for field applications. Use wiring designed specially for the devices.

    Danger!This symbol indicates a warning about a possible danger.

    In the event the warning is ignored, the consequences may range from personal injury to death.

    Warning!This symbol indicates a warning about a possible fault or danger.

    In the event the warning is ignored, the consequences may course personal injury or heaviest property damage.

    Caution!This symbol warns of a possible fault.

    Failure to observe the instructions given in this warning may result in the devices and any connected facilities or systems develop a fault or fail completely.

    8

  • KFU8-FSSP-1.D-YSafety

    046792 2008-11

    3.3 General safety instructions

    Installation and commissioning of all devices must be performed by a trained professional only.

    Always operate the device as described in these instructions to ensure that the device and connected systems function correctly. The protection of operating personnel and plant is only guaranteed if the device is operated in accordance with its intended use.

    The devices have been designed in protection category IP 20 in accordance with IEC 60529/EN 60529 and are suitable for use in environments of contamination level 2. If used in environments with a higher level of contamination the devices must be protected accordingly.

    When packing the device for storage or transport, use materials that will protect the device from bumps and impacts and protect against moisture. The original packaging provides the best protection. Also take into account the permitted ambient conditions.

    The operating company bears responsibility for observing locally applicable safety regulations.

    Independent interventions and separate modifications are dangerous and will void the warranty and exclude the manufacturer from any liability. If serious faults occur, stop using the device. Secure the device against inadvertent operation. In the event of repairs, send the device to Pepperl+Fuchs.

    9

  • KFU8-FSSP-1.D-YProduct description

    KFU8-FSSP-1.D-Y

    046792 2008-11

    4 Product description

    4.1 Device description

    The frequency voltage/current converter KFU8-FSSP-1.D-Y is a device for displaying and monitoring periodical signals which occur in almost all areas of process automation, i.e. from general frequencies to specific speeds.

    The input signals are evaluated and converted into a frequency or speed by a powerful -controller in accordance with the cycle method. The -controller calculates a voltage value proportional to the input frequency and produces it with a digital/analog converter in accordance with the selected limit value of the measurement range.

    You can select either of the following analog signals:

    • 0 V ... 10 V• 2 V ... 10 V

    The pulse output produces the input frequency which is subdivided by the adjustable factor of 1 ... 9999.

    Furthermore, in applications involving slow processes, where sensors deliver multiple pulses per revolution, it is possible to automatically operate with the actual speed of the drive by specifying the number of pulses per revolution.

    NOTE!

    Close attention was paid to the special case of speed measurement during the development of the device. The indicators and inputs can therefore occur in Hz or in rpm.

    10

  • KFU8-FSSP-1.D-YProduct description

    046792 2008-11

    The input or output signal is displayed on a 7-segment LED display on the front of the device. The display has 4 digits and up to 3 decimal places. The parameterization is performed using the 4 buttons below the display.

    The frequency voltage/current converter is supplied with 24 VDC.

    NOTE!

    All currently available two, three or four-wire proximity switches and incremental rotary encoders are acceptable as sensors.

    11

  • KFU8-FSSP-1.D-YOperation

    KFU8-FSSP-1.D-Y

    046792 2008-11

    5 Operation

    5.1 Operating mode

    Signal frequency

    The frequency voltage/current converter processes input signals of 0.001 Hz ... 9999 Hz or speeds of 0.02 rpm ... 9999 rpm. Signals not having a duty rate of 1:1 must have a minimum pulse pause or pulse duration of 40 s in order to be detected with certainty behind the input filter.

    Measurement underrange, message

    This message appears when no input signal is recognized.

    Measurement overrange, message

    The preset display and measurement range was exceeded.

    NOTE!

    Select a wider measurement range.

    12

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Very low signal frequencies, displayed value is not valid,

    message

    During the measurement of very low signal frequencies, the measuring system has detected that the signal has fallen below the last computed frequency. The time between the last two signal edges has already elapsed. The device is now waiting for the next positive signal edge in order to compute the next measured value. Here, 'XXX' represents the positions of the first three digits of the last measured value.

    Self test, message

    When the power supply is switched on, the device performs a self test. The message appears when it is established that there is an error, for example during the check summation of the EEPROM data; in this state, the output relay behaves as if there has been a power failure. The error message can be cleared by switching the supply voltage off and on again.

    Error message

    NOTE!

    If, when switching on again, the error message appears, then the factory presets were loaded.

    13

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    1. Enter the parameters again.

    2. Switch the device off and back on again.

    The normal function of the output relay is restored.

    5.2 Setup mode

    view Figure 6.2 on page 29

    Transition operating mode setup mode

    Starting setup mode

    Press the "Mode" and "+" buttons at the same time.

    The display shows the parameters in text form.

    Transition setup mode operating mode

    Exiting setup mode

    Press the "Enter" and "+" buttons at the same time.

    The parameters are stored in an EEPROM in a non-volatile manner.

    NOTE!

    You can modify the parameters in the parameter value display (flashing digits). The parameters come into effect temporarily until the operating voltage is interrupted.

    14

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Button functions for the parameter display

    Button functions for the parameter value display (one digit flashes)

    Function selection

    (factory preset: Rotational speed measurement in rpm)

    2 measurement functions are available:

    1. Frequency measurement in Hz (parameter value = 0)

    The established cycle duration of the input signal is converted into a frequency

    in Hz through the formation of a reciprocal value.

    Range: 0.001 Hz ... 9999 Hz

    "+" Switch to next parameter.

    "-" Switch to previous parameter.

    "Mode" Switch modes of parameter display.

    "Enter" and "+"

    Closes parameter editor and stores all parameters in the EEPROM.

    "+" Increase the value of the flashing digit.

    "-" Decrease the value of the flashing digit.

    "Mode" Move flashing digit.

    "Enter" and "+"

    Transfer from parameter value display to parameter display.

    15

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    2. Rotational speed measurement in rpm (parameter value = 1)

    The signal frequency calculated from the cycle duration is multiplied by 60 and

    displayed in rpm.

    Range: 0.02 rpm ... 9999 rpm

    Pulse divider

    (factory preset: 1 pulse/revolution)

    Applications involving slow processes are frequently equipped with sensors which provide several pulses per revolution. In the rotational speed measuring function, the device undertakes the conversion to the actual value of rpm by inputting the numerical value (of pulses/revolution), i.e. both the indication and the input of the measurement range end value are obtained from the actual rate of rotation of the drive.

    Range: 1 ... 1200

    NOTE!

    The pulse separator is only active for rotational speed measurement.

    16

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Measurement range full scale reading

    (factory preset: 9999)

    In frequency measurement, the set value is measured in Hz or in speed measurement it is measured rpm (depending on Function selection) it determines the frequency or speed at the analog output of the maximum voltage of 10 V.

    Range: see display and measurement range.

    Teaching in

    Press the "Mode" button only and then press "Enter".

    The frequency or speed of the current pending input signal are taught in.

    Analog output

    (factory preset: 0 V ... 10 V)

    Selection of the analog output signal.

    Parameter value Analog output

    0 0 V ... 10 V

    1 2 V ... 10 V

    17

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Display function

    (factory preset: frequency or speed)

    The display shows the determined frequency or speed in Hz and rpm (depending on Function selection) or the output voltage in V.

    Display rate

    (factory preset: 0.33 s)

    In order to ensure good readability of the display, the time taken to indicate the current measured value in the display can be selected between 0.01 s and 2.5 s.

    Display function Function selection Analog output Display

    0 0 - Frequency in Hz

    1 - Rotational speed in rpm

    1 - 0 Voltage in V

    - 1 Voltage in V

    NOTE!

    The display rate influences neither the time required to calculate the measured value nor the switching characteristics of the output relay.

    18

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Division factor for the pulse output

    If the division factors is set to 1, the pulse output goes to high level approx. 25 s after the positive slope of the input signal and to low level approx. 50 s after the negative slope.

    Figure 5.1: Division factor 1

    With division factors greater than 1, the pulse output goes to high level approx. 50 s after the first positive input signal slope.

    For even division factors the output level goes approx. 50 s after the ‘division factor’/2 period to low level for the following periods.

    approx. 25 μs approx. 50 μs

    19

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Figure 5.2: Division factor 4

    For uneven division factors the output level goes approx. 50 s after the (‘division factor’-1)/2 period to low level for the following periods.

    Figure 5.3: Division factor 5

    Range: 1 ... 9999

    approx. 50 μs approx. 50 μs

    Example:division factor = 4

    output level high:4/2 = 2 periods

    2 periods

    4 periods

    approx. 50 μs approx. 50 μs

    Example:division factor = 5

    output level high:(5-1)/2 = 2 periods

    2 periods

    5 periods

    20

  • KFU8-FSSP-1.D-YOperation

    046792 2008-11

    Software version number

    NOTE!

    You can only read out the version number of the software.

    21

  • KFU8-FSSP-1.D-YAppendix

    KFU8-FSSP-1.D-Y

    046792 2008-11

    6 Appendix

    6.1 Technical data

    Power supply

    Rated voltage 20,4 ... 27.6 VDC

    Power consumption < 5 W

    Display/controls

    Type 4-digit 7-segment display, red, 7 mm digit height

    Display area: 0,002 ... 9999 Hz or 0.01... 9999 rpm

    Parameter assignment Keypad menu guidance

    Input

    Connection Terminals 7+, 13- sensor supply Terminals 14, 15 npn/pnp input (galvanically isolated)

    Connectable sensor types Two, three or four-wire proximity switches and incremental rotary encoders

    Sensor supply voltage Rated voltage – 1.5 V not stabilized; 30 mA short-circuit proof

    Switching point high: 16 ... 30 VDC; max.10 mA; Ri 3 klow: 0 ... 6 V DC

    22

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    Output

    Analog voltage output 0 ... 10 VDC; 2 ... 10 VDC; 30 mA max.; resolution: 12 mV; Ri 330 (Term. 5+, 6-)

    Digital incrementing (Ub -3 V), 20 mA, short-circuit proof (Terminals 1-, 2+) with frequency division Fin /1 ... Fin /9999

    Transfer characteristics

    Input frequency 10000 Hz, pulse pause/duration: 40 s

    Deviation 0.2 % of the end value

    Changing interval 10 ms (internal processing time)

    Ambient conditions

    Ambient temperature -25 ... 50 °C (248 ... 323 K)

    Storage temperature -40 ... 85 °C (233 ... 358 K)

    Relative humidity max. 80 %, non-condensing

    Altitude 0 - 2000 m

    Operating conditions The device is for indoor use only

    Conformity

    Electromagnetic compatibility EN 50081-2, EN 50082-2

    23

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    Mechanical data

    Degree of protection IP20

    Connection Coded, removable terminals, core cross-section: 0.34 ... 2.5 mm2

    Design Modular terminal housing in Makrolon, system KF

    Mounting Snap-on to 35 mm DIN mounting rail according to DIN EN50022 or screw fixing by means of extendable latches in 90 mm grid

    24

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    6.2 Terminal assignment

    Term. 1: Sensor power supplyGND

    Term. 10: Not connected

    Term. 2: Pulse output Term. 11: Power supply 24 VDC, L +

    Term. 3: Not connected Term. 12: Power supply 24 VDC, L -

    Term. 4: Not connected Term. 13: Sensor power supplyGND

    Term. 5: Analog output U +

    Term. 14: PNP, NPN input- (cathode)

    Term. 6: Analog output U -

    Term. 15: PNP, NPN input+ (anode)

    Term. 7: Sensor power supply+ 24 VDC

    Term. 16: Not connected

    Term. 8: Not connected Term. 17: Not connected

    Term. 9: Not connected Term. 18: Not connected

    25

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    6.3 Dimensions, operating and display devices

    Mode

    Output DrehzahlwächterSpeed monitor

    Enter

    +

    1 2 3 4 5 6

    13 14 15 16 17 187 8 9 10 11 12

    PEPPERL+FUCHS GERMANY

    Control keys

    7-segment-display

    107

    93

    115

    "Mode" and "+": Start parameter editor

    "+": Advance to next parameter selection or increase the value of the flashing digit

    "-": Advance to next parameter selection or decrease the value of the flashing digit

    "Mode": Display parameter value (right digit flashes) or shift the flashing digit to the left

    "Enter": Exit parameter value display, the device now operates temporarily with the altered parameter.

    "Enter" and "+": Exit parameter editor, the parameters are now stored in the EEPROM in a non-volatile manner.

    26

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    6.4 Connection diagram

    Figure 6.1: Connection diagram

    L+

    L–

    L+

    L–

    L+

    L–

    L+

    L–

    L+

    L–

    9

    8

    7

    15

    14

    13

    11

    12

    16

    18

    17

    DC

    DC

    D

    A

    5I+ / U+

    I–

    U–

    4

    6

    2

    1

    3

    10

    V

    Ri ≥ 330 W

    13, 14157

    13147, 15

    13, 14157

    13147, 15

    Power supply 24 V DC

    Sensor power supply 24 V

    Encoder,push-pull

    Encoder,push-pull

    DC-3-wiresensor, PNP

    DC-3-wiresensor, NPN

    Galvanicallyisolated input forPNP- and NPN-output circuits

    Sensor powersupply GND

    Sensor powersupply GND

    Pulse output

    Not connected

    Not connected

    Not connected

    Not connected

    Not connected

    Not connected

    Not connected

    27

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    6.5 Functional description

    MODE

    MODE

    MODE

    ENTER

    EN

    TE

    R

    ENTER

    MODE

    ENTER

    MODE

    ENTER

    MODE

    + +

    ++

    + –

    + –

    + –

    + –

    +

    +

    Operating mode

    Function selection: X=0: Frequency measurement 0.002 Hz...9999 Hz X=1: Speed measurement 0.01 min-1...9999 min-1

    Factory set: X = 1

    Signal divider: Number of signals per rotation (is ignored during frequency measurement) 1 ≤ XXXX ≤ 1200, Factory set: XXXX = 1

    Measurement range final value: Frequency or speed, by which 10 V or 20 mA are applied to the analog output.0 ≤ XXXX ≤ 9999, Factory set: XXXX = 9999 Teach in of the current frequency or speed value as a measurement range final value by pressing the "MODE" button and then the "ENTER" button.

    Display and measurement range:0 ≤ X ≤ 3 at frequency measurement 0 ≤ X ≤ 2 at speed measurement Factory set: X = 0

    X Frequency Speed [Hz] [min-1] 0000 0 ... 9999 000.1 0 ... 999.9 00.02 0 ... 99.99 0.003 0 ... 9.999 –

    28

  • KFU8-FSSP-1.D-YAppendix

    046792 2008-11

    Figure 6.2: Graphic function description

    MODE

    ENTER

    MODE

    ENTER+ –

    MODE

    ENTER+ –

    MODE

    ENTER+ –

    MODE

    ENTER+ –

    ENTER

    Software-version number:Can only be read.

    Division factor for pulse output: 1 ≤ XXXX ≤ 9999Factory set: XXXX = 1

    Display: X=0: Frequency or speedX=1: Voltage display or current display Factory set: X = 0

    Display rate:0.01 s ≤ X.XX ≤ 2.5 sFactory set: X.XX = 0.33 s

    X Analog output0 0 V ... 10 V1 2 V ... 10 V2 0 mA ... 20 mA3 4 mA ... 20 mA Factory set: X = 0

    29

  • 30046792 2008-11

    KFU8-FSSP-1.D-Y

  • 31

    KFU8-FSSP-1.D-Y

    046792 2008-11

  • FACTORY AUTOMATION – SENSING YOUR NEEDS

    Subject to modificationsCopyright PEPPERL+FUCHS • Printed in Germany

    www.pepperl-fuchs.com

    Worldwide HeadquartersPepperl+Fuchs GmbH68307 Mannheim · GermanyTel. +49 621 776-0E-Mail: [email protected]

    USA HeadquartersPepperl+Fuchs Inc.Twinsburg, Ohio 44087 · USATel. +1 330 4253555E-Mail: [email protected]

    Asia Pacific HeadquartersPepperl+Fuchs Pte Ltd.Company Registration No. 199003130ESingapur 139942Tel. +65 67799091E-Mail: [email protected]

    TDOCT0628B_ENG / 04679211/2008

    1 Introduction 52 Declaration of Conformity 73 Safety 83.1 Symbols relevant to safety 83.2 Intended use 83.3 General safety instructions 9

    4 Product description 104.1 Device description 10

    5 Operation 125.1 Operating mode 125.2 Setup mode 14

    6 Appendix 226.1 Technical data 226.2 Terminal assignment 256.3 Dimensions, operating and display devices 266.4 Connection diagram 276.5 Functional description 28

    1 IntroductionCongratulationsSymbols usedHandling instructionsContact

    2 Declaration of Conformity3 Safety3.1 Symbols relevant to safety3.2 Intended use3.3 General safety instructions

    4 Product description4.1 Device description

    5 Operation5.1 Operating modeSignal frequencyMeasurement underrange, messageMeasurement overrange, messageVery low signal frequencies, displayed value is not valid, messageSelf test, messageError message1. Enter the parameters again.2. Switch the device off and back on again.

    5.2 Setup modeTransition operating mode Æ setup modeStarting setup modeTransition setup mode Æ operating modeExiting setup modeButton functions for the parameter displayButton functions for the parameter value display (one digit flashes)Function selectionPulse dividerMeasurement range full scale readingTeaching inAnalog outputDisplay functionDisplay rateDivision factor for the pulse outputSoftware version number

    6 Appendix6.1 Technical data6.2 Terminal assignment6.3 Dimensions, operating and display devices6.4 Connection diagram6.5 Functional description