battery-free solution
for your UPS system
How it works
A carbon fiber cylinder linked to a shaft with a motor-generator is fully
magnetically levitated, spinning in a vacuum. In an outage, the motor-
generator uses inertia to create the energy needed by the UPS’s DC bus.
Typical continuous power quality solution
TM
TM
Reliable UPS energy storage
Batteries and reliability
There’s a better way
Bridging the gap
Power quality/reliability systems need
energy storage to ensure protected
loads always get clean power. But any
UPS operator will tell you that batteries
are the weakest link in the chain. They:
● Fail unpredictably
Require precise temperature control
Need reinforced floor space,and lots of it
Endanger personnel with hazmats
●Require frequent and costly maintenance
Need total replacement every 2 - 4 years●
●
●
●
The Pentadyne energy storage system
is vastly more reliable and cost efficient
while it eliminates lead-acid battery
hazards, maintenance, environmental
impact and that “cross-your-fingers”
approach to power certainty.
This carbon-fiber-flywheel technology
connects with leading brands of UPS
systems – just like a battery cabinet –
but without the dangers, repetitive
costs and poor reliability issues.
Flywheels cover the time gap between
an outage and the UPS generator com-
ing online; they also ensure continuous
power during brief utility disturbances.
Utility feed
ATS
Back-up genset
In a power outage, an automatic transfer switch
(ATS) commands the back-up generator to start.
During this time, the UPS ensures continuous power to the
protected load via batteries or a flywheel. These energy
storage devices power the protected loads until the
utility line returns to normal or the back-up genset takes over.
Motor-generatorstator
Axialelectromagnet
Patentedmolecular
vacuum sleeve
2-inchthick steel
housing
Synchronousreluctance
motor-generator
Lower radialelectromagnet
Carbon fibercompositeflywheel cylinder
Lower vacuumchamber
Upper vacuumchamber Upper radial
electromagnet
Makes batteries more reliable...
...Or eliminates batteries altogether
The Pentadyne clean energy system can operate in parallel with batteries
as the first line of defense against power quality disturbances.
During a power interruption, the UPS first draws current from the
flywheel; the batteries are isolated. The flywheel delivers continuous
power to ride through brief events (99% of all outages last <10 seconds,
according to EPRI) or until the backup generator is online.
Unless there is a need for energy storage redundancy,most facilities use
flywheels alone to achieve a real-world-proven 10x reliability improve-
ment without all the hazmats,costs,and risks of battery banks.
without all the maintenance and costs of lead-acid batteries
“Batteries are the primary field failure problem
with UPS systems” – Electric Power Research Institute (EPRI)
Key features and benefits
Real-world-proven: >10x the reliability of lead-acid batteries
Vastly lower lifecycle costs than batteries and other flywheels
An environmentally responsible solution to UPS energy storage
½ the footprint of VRLAs, and ¼ the weight
Runs near silently within a wide temperature range: no HVAC
Less standby draw than batteries; 1/10th that of other flywheels
No special flooring needs, rolls into place and installs in 1-2 hrs.
UPS Protectedload
Flywheel Optional batteries
About Pentadyne Power Corporation
Pentadyne is one of the world's leading manufacturers of flywheel energy storagesystems used for energy recycling applications and to replace hundreds of lead-acidbatteries used with large-scale UPS systems.Award-winning flywheels made by thisInc. 500 listed company deliver an order of magnitude greater reliability thanbatteries, have near-zero maintenance needs, and have a footprint and lifecycle costless than half that of batteries. Using 90% less power than other flywheels, thissustainable, environmentally responsible system is sold by several of the world'sleading UPS manufacturers. A well-financed, ISO-9001-certified private company –named aTechnology Pioneer by theWorld Economic Federation – Pentadyne designsand manufactures its products in LosAngeles.
“10-yr”VRLA batteries
access
FW FW
access
VRLA VRLA
Footprint comparisonThe floorspace needed byVRLA battery cabinets for a 400-kVA UPS –
including code-mandated access space – is nearly twice that of a similar
capacity pair of flywheels (green). Compared to a one megawatt set of
wet cells,the flywheel footprint is nearly 80% smaller (orange).
wet cell batteries
wet cell batteries
access
access
access access
Pentadyne GTX
access
FW FW FW FW FW
Reliability Each cycle degrades reliability
Unknown state of charge
Recharge takes minutes/hours
Narrow temperature range
Frequent service & downtime
Dropped loads:<30k hrs
Very low“float”energy needs
Expensive HVAC needs
Very frequent maintenance
Large footprint
Floor loading issues
Replacement every 2-4 yrs
Acid spills, gases
Speculative monitoring option
dangerous
Unaffected by cycling
Always known state of charge
Symmetrical recharge (secs.)
Broad temperature range
Brief service every 2 yrs
Dropped loads:>350k hrs
Even lower float energy needs
No HVAC needs
Very infrequent maintenance
Small footprint
No floor loading issues
>20-year design life
Built-in real-time monitoring
No hazmats,gases or fire risks
Costs
VRLA
Flywheels cost more than VRLA batteries, but eliminate battery maintenance andstring replacements, paying for themselves by shortly after what would be the firstbattery string replacement interval.
TM
20750 Lassen Street • Chatsworth, CA 91311 • pentadyne.com • 818.350.0370
Protected
load
Utility
Optional
Gen
Soft start
Controlpanel
Sp
eed
Sen
so
rs
Tem
peratu
re
Sen
so
rs
Po
sit
ion
Sen
so
rs
Power conversion module controller (PCMC)
Motor-generator controlsDC monitoring
To
UPS
battery
input
Magneticlevitation module
(MLM)
Flywheelmodule
IGBT power convertor
Versatile Interface:
Remote Monitoring,
Diagnostics & Control
TM
Powerconversionmodule
Motor-generatorfilter
Versatileinterface(opt.)
Userinterface
Magneticlevitation
module
Flywheel module
UL®UL®
Data collectionmodule (opt.)
Disconnectswitch
© 2009 Pentadyne Power Corp.Pentadyne products are made in the USA.
Specifications subject to change without notice.
UPSrating*
Flywheelcabinets
50% loadduration
80% loadduration
1000 kVA750 kVA625 kVA
500 kVA400 kVA300 kVA250 kVA225 kVA200 kVA150 kVA120 kVA
100 kVA80 kVA
433
22211111
11
23 sec.23 sec.28 sec.
23 sec.29 sec.39 sec.23 sec.26 sec.29 sec.39 sec.48 sec.
59 sec.75 sec.
12 sec.12 sec.16 sec.
12 sec.17 sec.24 sec.12 sec.15 sec.17 sec.24 sec.31 sec.
37 sec.46 sec.
Runtimes for UPS systems loaded at 50%and 80% (fractional seconds rounded down).
Lightly loaded systems can use fewercabinets,then add more as load grows.
Runtimes
* UL-certification requirements have an upper limit of 600Vdc
Specs
DC input/output voltage
Continuous output power
Recharging timeDC rippleDC output voltage regulationStandby draw/heat dissipationWeightDimensions D xW x HOperating sound levelOperating temperature range
Cabling access
Service access
Adjustable: 350 to 850*Vdc
200 kW nom., 225 kW max.
<15 sec. (DC source dependent)
<2%±1% steady state0.25 kW / 850 BTU/hr1,300 pounds (590 kg)
33x25x71 in (83x63x180 cm)
45 dBA @ 1 meter-4°F to 122°F (-20°C to 50°C)
Top or sideOnly front access required
* Assumes a 540 Vdc bus, 0.9 pf and 95% inverter efficiency.Includes switchgear & cable losses; excludes rectifier walk-in.