pe7214/pe7216/pe7324/pe7328 · 4 description: 100-240v 16a 0u 14-outlet pdu function: 14-outlet...
TRANSCRIPT
As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco
PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7214 / PE7216 / PE7324
/PE7328 eco PDUs are intelligent PDUs that contain 14, 16, 24, or 28 AC outlets and are available in various IEC
socket configurations.
NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data
center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well
as the ability to monitor the center's health environment via sensors.
NRGence eco PDUs offer remote power control combined with real-time power measurement – allowing you to
control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet
level, depending on the model, from practically any location via a TCP/IP connection.
NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors (eco PDU
Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an
intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power
status of the equipment connected to it.
With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable,
and most cost effective way to remotely manage power access for multiple computer installations and allocate
power resources in the most efficient way possible.
1
ECO PDUPE7214/PE7216/PE7324/PE7328
2
Connections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity,IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensors forracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V20A0U14-OutletPDUFunction: 14-OutletMetering,
0-OutletSwitchingControl&1-BankMetering
InputPowerPlug: NEMA6-20P
PowerCapacity: 4.2kW
SocketConfiguration:
IEC60320C19(2)
IEC60320C13(12)
Features
ECO PDUPE7214B
3
Optional AccessoriesEnvironment Sensors
PartNo. Sensor
EA1140 Temperature
EA1240 Temperature/Humidity
EA1340 DifferentialPressure/Temperature
Cable Holders
PartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door Sensors
PartNo. Sensor
EA1440 PhotoDoorSensor
EA1441 InductiveProximityDoorSensor
EA1442 ReedDoorSensor
• Lok-U-PlugInstallation
Model PE7214BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 20AMax;16A(ULde-rated)InputFrequency 50-60HzInputConnection 1xNEMA6-20PInputPower 4160VA(Max)3328VA(ULde-rated)
OutletTypeTotal:12xIEC320C13+2xIEC320C19Bank1:Outlet1–14;12xC13+2xC19
NominalOutputVoltage 100–240VAC
MaximumOutputCurrent(Outlet)
C13:15A(Max)12A(ULde-rated)C19:20A(Max)16A(ULde-rated)
MaximumOutputCurrent(Bank) 20A(Max)16A(ULde-rated)
MaximumOutputCurrent(Total) 20A(Max)16A(ULde-rated)
Breakers 1x20ANon-Fusebreaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracy
VoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 91x6.6x4.4cmShippingDimensions(HxWxD)
100x19x17cm
Weight/ShippingWeight 2.7/3.8kg
PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C
Humidity(Operating&Storage)
0–80%RH,Non-Condensing
ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification ByRequest
PackageContents1. PE7214B2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord
Specifications
RackMountKit
2X-018G
SidePanelMountKit(2X-018G)
Mounting Kit
4
Description: 100-240V16A0U14-OutletPDUFunction: 14-OutletMetering,
0-OutletSwitchingControl&1-BankMetering
InputPowerPlug: IEC60320C20
PowerCapacity: 3.7kW
SocketConfiguration:
IEC60320C19(2)
IEC60320C13(12)
FeaturesConnections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity,IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensors forracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
ECO PDUPE7214G
5
Optional AccessoriesEnvironment Sensors
PartNo. Sensor
EA1140 Temperature
EA1240 Temperature/Humidity
EA1340 DifferentialPressure/Temperature
Cable Holders
PartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door Sensors
PartNo. Sensor
EA1440 PhotoDoorSensor
EA1441 InductiveProximityDoorSensor
EA1442 ReedDoorSensor
• Lok-U-PlugInstallation
Model PE7214GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 16AMaxInputFrequency 50-60HzInputConnection 1xIEC60320C20InputPower 3680VA(Max)
OutletTypeTotal:12xIEC320C13+2xIEC320C19Bank1:Outlet1–14;12xC13+2xC19
NominalOutputVoltage 100–240VAC
MaximumOutputCurrent(Outlet)
C13:10A(Max)C19:16A(Max)
MaximumOutputCurrent(Bank) 16A(Max)
MaximumOutputCurrent(Total) 16A(Max)
Breakers 1x16ANon-Fusebreaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracy
VoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 91x6.6x4.4cmShippingDimensions(HxWxD)
100x19x17cm
Weight/ShippingWeight 2.7/3.8kg
PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to40˚C/-20to60˚C
Humidity(Operating&Storage)
0–80%RH,Non-Condensing
ComplianceEMCVerification CE,OthersbyRequestSafetyVerification CE-LVD,OthersbyRequest
PackageContents1. PE7214G2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord
Specifications
RackMountKit
2X-018G
SidePanelMountKit(2X-018G)
Mounting Kit
Connections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V20A0U16-OutletPDUFunction: 16-OutletMetering,
0-OutletSwitchingControl&1-BankMetering
InputPowerPlug: NEMA6-20P
PowerCapacity: 4.2kW
SocketConfiguration:
IEC60320C19(2)
IEC60320C13(14)
Features
6
ECO PDUPE7216B
• Lok-U-PlugInstallation
Model PE7216BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 20AMax;16A(ULde-rated)InputFrequency 50-60HzInputConnection 1xNEMA6-20PInputPower 4160VA(Max)3328VA(ULde-rated)
OutletTypeTotal:14xIEC320C13+2xIEC320C19Ban1-1:Outlet1–8;7xC13+1xC19Bank1-2:Outlet9–16;7xC13+1xC19
NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)
C13:15A(Max)12A(ULde-rated)C19:20A(Max)16A(ULde-rated)
MaximumOutputCurrent(Bank) 20A(Max)16A(ULde-rated)
MaximumOutputCurrent(Total) 20A(Max)16A(ULde-rated)
Breakers 1x20ANon-Fusebreaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 132.5x6.6x4.4cmShippingDimensions(HxWxD)
142x16x17cm
Weight/ShippingWeight 3.7/7.7kg
PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C
Humidity(Operating&Storage)
0–80%RH,Non-Condensing
ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification TUV-CB,OthersbyRequest
PackageContents1. PE7216B2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord
7
Optional AccessoriesSpecifications
Environment Sensors
PartNo. Sensor
EA1140 Temperature
EA1240 Temperature/Humidity
EA1340 DifferentialPressure/Temperature
Cable Holders
PartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door Sensors
PartNo. Sensor
EA1440 PhotoDoorSensor
EA1441 InductiveProximityDoorSensor
EA1442 ReedDoorSensor
RackMountKit
2X-018G
SidePanelMountKit(2X-018G)
Mounting Kit
Connections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V16A0U16-OutletPDUFunction: 16-OutletMetering,
0-Outlet Switching Control &1-BankMetering
InputPowerPlug: IEC60320C20
PowerCapacity: 3.7kW
SocketConfiguration:
IEC60320C19(2)
IEC60320C13(14)
Features
8
ECO PDUPE7216G
• Lok-U-PlugInstallation
Model PE7216GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 16AMaxInputFrequency 50-60HzInputConnection 1xIEC60320C20InputPower 3680VA(Max)
OutletTypeTotal:14xIEC320C13+2xIEC320C19Bank1-1:Outlet1–8;7xC13+1xC19Bank1-2:Outlet9–16;7xC13+1xC19
NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)
C13:10A(Max)C19:16A(Max),TUVDe-rated15A(Max)
MaximumOutputCurrent(Bank) 16A(Max),TUVDe-rated15A(Max)
MaximumOutputCurrent(Total) 16A(Max).TUVDe-rated15A(Max)
Breakers 1x16ANon-Fusebreaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 132.5x6.6x4.4cmShippingDimensions(HxWxD)
142x16x17cm
Weight/ShippingWeight 3.7/7.7kg
PowerCordLength 3mEnvironmentalTemperature(Operating/Storage) 0to40˚C/-20to60˚C
Humidity(Operating&Storage)
0–80%RH,Non-Condensing
ComplianceEMCVerification CE,OthersbyRequestSafetyVerification TUV-CB,CE-LVD,OthersbyRequest
PackageContents1. PE7216G2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)5. PowerCord
9
Optional AccessoriesSpecificationsEnvironment Sensors
PartNo. Sensor
EA1140 Temperature
EA1240 Temperature/Humidity
EA1340 DifferentialPressure/Temperature
Cable Holders
PartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door Sensors
PartNo. Sensor
EA1440 PhotoDoorSensor
EA1441 InductiveProximityDoorSensor
EA1442 ReedDoorSensor
RackMountKit
2X-018G
SidePanelMountKit(2X-018G)
Mounting Kit
Connections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V30A0U24-OutletPDUFunction: 24-OutletMetering,
0-Outlet Switching Control &2-BankMetering
InputPowerPlug: NEMAL6-30P
PowerCapacity: 6.2kW
SocketConfiguration:
IEC60320C19(3)
IEC60320C13(21)
Features
10
ECO PDUPE7324B
Model PE7324BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 30AMax;24A(ULde-rated)InputFrequency 50-60HzInputConnection NEMAL6-30PInputPower 6240VA(Max)4992VA(ULde-rated)
OutletType
Total:21xIEC320C13+3xIEC320C19Bank1-1:Outlet1–8;7xC13+1xC19Bank1-2:Outlet9–16;7xC13+1xC19Bank2:Outlet17–24;7xC13+1xC19
NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)
C13:15A(Max)12A(ULde-rated)C19:15A(Max)12A(ULde-rated)
MaximumOutputCurrent(Bank) 15A(Max)12A(ULde-rated)
MaximumOutputCurrent(Total) 30A(Max)24A(ULde-rated)
Breakers 2x16AUL489Breaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 177.5x6.6x4.4cmShippingDimensions(HxWxD)
189x21x17cm
Weight/ShippingWeight 6.5/10.5kg
PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C
Humidity(Operating&Storage)
0–80%RH,Non-Condensing
ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification TUV-CB,OthersbyRequest
PackageContents1. PE7324B2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)
11
Optional AccessoriesSpecificationsEnvironment Sensors
PartNo. SensorEA1140 TemperatureEA1240 Temperature/HumidityEA1340 DifferentialPressure/Temperature
Cable HoldersPartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door SensorsPartNo. Sensor
EA1440 PhotoDoorSensorEA1441 InductiveProximityDoorSensorEA1442 ReedDoorSensor
• Lok-U-PlugInstallation
• Side Mount Installation
• Side Panel Double Mount Installation
• Button Mount Installation
SlideRailKit(2X-016G)
SidePanelDoubleMountKit(2X-019G)
ButtonMountKit(2X-017G)
SidePanelMountKit(2X-018G)
Mounting Kit
2X-018G
RackMountKit
Connections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V32A0U24-OutletPDUFunction: 24-OutletMetering,
0-OutletSwitchControl&2-BankMetering
InputPowerPlug: IEC6030932A
PowerCapacity: 7.4kW
SocketConfiguration:
IEC60320C19(3)
IEC60320C13(21)
Features
12
ECO PDUPE7324G
• Lok-U-PlugInstallation
Model PE7324GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent
32AMax
InputFrequency 50-60HzInputConnection IEC6030932AInputPower 7360VA(Max)
OutletType
Total:21xIEC320C13+3xIEC320C19
Bank1-1:Outlet1–8;7xC13+1xC19
Bank1-2:Outlet9–16;7xC13+1xC19
Bank2:Outlet17–24;7xC13+1xC19NominalOutputVoltage
100–240VAC
MaximumOutputCurrent(Outlet)
C13:10A(Max)
C19:16A(Max),TUVDe-rated15A(Max)MaximumOutputCurrent(Bank)
16A(Max),TUVDe-rated15A(Max)
MaximumOutputCurrent(Total)
32A(Max),TUVDe-rated30A(Max)
Breakers 2x16AUL489Breaker
MeteringPerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort
4
MeteringAccuracy
VoltageRange:100VAC~250VAC+/-1%
PowerRange:100W~5000W+/-2%
CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%MechanicalDimension(HxWxD) 177.5x6.6x4.4cmShippingDimensions
(HxWxD)189x21x17cm
Weight/ShippingWeight
6.2/10.2kg
PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage)
0to40˚C/-20to60˚C
Humidity
(Operating&Storage)0–80%RH,Non-Condensing
ComplianceEMCVerification CE,OthersbyRequestSafetyVerification TUV-CB,CE-LVD,OthersbyRequest
PackageContents1. PE7324G2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)
13
Optional AccessoriesSpecifications
Environment SensorsPartNo. Sensor
EA1140 TemperatureEA1240 Temperature/HumidityEA1340 DifferentialPressure/Temperature
Cable HoldersPartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door SensorsPartNo. Sensor
EA1440 PhotoDoorSensorEA1441 InductiveProximityDoorSensorEA1442 ReedDoorSensor
• Side Mount Installation
• Side Panel Double Mount Installation
• Button Mount Installation
SlideRailKit(2X-016G)
SidePanelDoubleMountKit(2X-019G)
ButtonMountKit(2X-017G)
SidePanelMountKit(2X-018G)
Mounting Kit
2X-018G
RackMountKit
Connections•Support10/100MbitEthernetInterface•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V30A0U28-OutletPDUFunction: 28-OutletMetering,
0-Outlet Switching Control &2-BankMetering
InputPowerPlug: NEMAL6-30P
PowerCapacity: 6.2kW
SocketConfiguration:
IEC60320C19(4)
IEC60320C13(24)
Features
14
ECO PDUPE7328B
• Lok-U-PlugInstallation
Optional Accessories
Model PE7328BElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 30AMax;24A(ULde-rated)InputFrequency 50-60HzInputConnection NEMAL6-30PInputPower 6240VA(Max)4992VA(ULde-rated)
OutletTypeTotal:24xIEC320C13+4xIEC320C19Bank1:Outlet1–14;12xC13+2xC19Bank2:Outlet15–28;12xC13+2xC19
NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)
C13:15A(Max)12A(ULde-rated)C19:15A(Max)12A(ULde-rated)
MaximumOutputCurrent(Bank) 15A(Max)12A(ULde-rated)
MaximumOutputCurrent(Total) 30A(Max)24A(ULde-rated)
Breakers 2x16AUL489Breaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 135.9x6.6x4.4cmShippingDimensions(HxWxD)
142x16x17cm
Weight/ShippingWeight 4.1/7.9kg
PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage) 0to50˚C/-20to60˚C
Humidity(Operating&Storage) 0–80%RH,Non-Condensing
ComplianceEMCVerification FCCPart15ClassA,OthersbyRequestSafetyVerification TUV-CB,OthersbyRequest
PackageContents1. PE7328BPDU2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)
Specifications
15
Environment Sensors
PartNo. Sensor
EA1140 Temperature
EA1240 Temperature/Humidity
EA1340 DifferentialPressure/Temperature
Cable Holders
PartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door Sensors
PartNo. Sensor
EA1440 PhotoDoorSensor
EA1441 InductiveProximityDoorSensor
EA1442 ReedDoorSensor
SidePanelDoubleMountKit(2X-019G)
SidePanelMountKit(2X-018G)
• Side Mount Installation
2X-018G
Mounting Kit
RackMountKit
• Side Panel Double Mount Installation
Connections•Support10/100MbitEthernetInterface
•SupportTCP/IP,UDP,HTTP,HTTPS,SSL,DHCP,SMTP,NTP,DNS,AutoSense,Ping,SNMPV1,V2&V3,Telnet
•Support2-levelaccount/passwordsecurity, IP/MACfilter,128bitSSL,RADIUS
•Support:ecoSensors,Browser(IE,Firefox,Chrome,Safari)
Metering•PDUandoutletlevelpowermeteringandmonitoring
•Environmentmonitoring–supportsexternaltemperature/temperature&humiditysensorsforracktemperatureandhumiditymonitoring
•Current,voltage,power,powerdissipation,temperature,andhumiditymeteringandthresholdlevelsetting
•Supportdoorsensor
OutletSwitchControl•AlwaysOn
Description: 100-240V32A0U28-OutletPDUFunction: 28-OutletMetering,
0-OutletSwitchControl&2-BankMetering
InputPowerPlug: IEC6030932A
PowerCapacity: 7.4kW
SocketConfiguration:
IEC60320C19(4)
IEC60320C13(24)
Features
16
ECO PDUPE7328G
• Lok-U-PlugInstallation
Optional Accessories
Model PE7328GElectricalNominalInputVoltage 100–240VACMaximumInputCurrent 32AMaxInputFrequency 50-60HzInputConnection IEC6030932AInputPower 7360VA(Max)
OutletTypeTotal:24xIEC320C13+4xIEC320C19Bank1:Outlet1–14;12xC13+2xC19Bank2:Outlet15–28;12xC13+2xC19
NominalOutputVoltage 100–240VACMaximumOutputCurrent(Outlet)
C13:10A(Max)C19:16A(Max),TUVDe-rated15A(Max)
MaximumOutputCurrent(Bank) 16A(Max)
MaximumOutputCurrent(Total) 32A(Max)
Breakers 2x16AUL489Breaker
Metering PerOutletLevelCurrent,Voltage,VA,PF,KWhMonitoring
OutletSwitch NoneEnvironmentSensorPort 4
MeteringAccuracyVoltageRange:100VAC~250VAC+/-1%PowerRange:100W~5000W+/-2%CurrentRange:0.1A~1A+/-0.1A,1A~20A+/-1%
MechanicalDimension(HxWxD) 135.9x6.6x4.4cmShippingDimensions(HxWxD)
142x16x17cm
Weight/ShippingWeight 4.1/7.9kg
PowerCordLength 1.6mEnvironmentalTemperature(Operating/Storage) 0to40˚C/-20to60˚C
Humidity(Operating&Storage)
0–80%RH,Non-Condensing
ComplianceEMCVerification CE,OthersbyRequestSafetyVerification TUV-CB,CE-LVD,OthersbyRequest
PackageContents1. PE7328GPDU2. StandardRackMountKit3. QuickStartGuide4. CD-ROM(Manual,ecoSensorsSoftware)
Specifications
ATEN International Co., Ltd. 3F., No.125, Sec. 2, Datong Rd., Sijhih District., New Taipei City 221, TaiwanPhone: 886-2-8692-6789 Fax: 886-2-8692-6767 www.aten.com E-mail: [email protected]
© Copyright 2017 ATEN® International Co., Ltd.ATEN and the ATEN logo are trademarks of ATEN International Co., Ltd. All rights reserved. All other trademarks are the property of their respective owners.
17
Environment SensorsPartNo. Sensor
EA1140 TemperatureEA1240 Temperature/Humidity
EA1340 DifferentialPressure/Temperature
Cable HoldersPartNo. Description
2X-EA07 Lok-U-PlugCableHolder(10pcsperpack)PatentPending!
2X-EA08 Lok-U-PlugInstallationTool(4pcsperpack)
Door SensorsPartNo. Sensor
EA1440 PhotoDoorSensor
EA1441 InductiveProximityDoorSensor
EA1442 ReedDoorSensor
SidePanelDoubleMountKit(2X-019G)
SidePanelMountKit(2X-018G)
• Side Mount Installation
2X-018G
Mounting Kit
RackMountKit
• Side Panel Double Mount Installation
Publish Date: 04/2017 V4.0