SPD ELECTRICAL SYSTEMS —Actron™ Circuit Breakers
Photo courtesy Litton Ingalls Shipbuilding
Photo courtesy U.S. Navy
Photo courtesy U.S. Navy
Registered by UL to ISO 9001
L-3 Communications/SPD Electrical Systems13500 Roosevelt BoulevardPhiladelphia, PA 19116Phone: 215.677.4900Fax: 215.677.1504www.L-3com.com /SPDES.html
L-3 COMMUNICAT I O NS/SPD TECHNOLOGIEST h e P o w e r i s H e r e™
The L-3/SPD Technologies companies cometogether to form the only fully integrated,full-line provider of ruggedized, reliable andcost-effective electrical power systems andservices to navy vessels around the world, as well as the most demanding commercialpower users from the inner city to outerspace. The L-3/SPD Technologies companiesand brands are:
SPD Electrical SystemsCreating the future in circuit-breaker design,engineering, manufacturing and testing for theworld’s most demanding applications.
■ Electronic Design (EDI) — control and monitoring systems for military and commercial marine applications
SPD SwitchgearThe most reliable line of electrical power c o n t rol and distribution products for commerc i a l ,industrial and military applications.
Power ParagonSpecialists in power-conversion technology and advanced power systems for mission-criticalapplications worldwide including:
■ Power Systems Group■ Power Switching & Conversion Systems■ Power Magnetics■ EuroAtlas■ JovyAtlas
HenschelDesign, engineering, manufacturing and integration of machinery control, monitoring andcommunication systems.
PacOrdMultifaceted DoD services, installation and integration of shipboard combat systems worldwide.
Actron is a trademark of L-3 Communications/SPD Electrical Systems.This document has been released into the public domain in accordance with U.S. International Traffic in Arms Regulations (ITAR), 22 CFR 120.© Copyright 2001, L-3 Communications/SPD Technologies. All rights reserved. Qty:5M 3/01 Printed in U.S.A.
components with state-of-the-art
materials to effectively solve system-
coordination problems in virtually all
harsh-environment applications. Actron
circuit breakers are engineered to offer
the highest value at affordable prices.
Actron circuit breakers comply with
specification MIL-C-17361 or MIL-C-17587.
L-3/SPD Electrical Systems also conducts
extensive Quality Assurance Programs
which adhere to MIL-Q-9858A and
MIL-I-45208A, as well as to the highest
internal, proprietary quality-control
standards in the industry. Each
manufacturing facility has advanced
computer design systems and computer-
controlled manufacturing processes.
No one in the industry can match
L-3/SPD Electrical Systems’ engineering
experience and know-how.
After rigorous audits, SPD
Electrical Systems has earned the
prestigious ISO 9001 certification for
the manufacture, testing and factory
servicing of air and molded-case circuit
breakers and accessories for use in
military, commercial and nuclear
applications. This is an assurance that
L-3/SPD quality-management systems
are among the very best in the world.
Actron Circuit Breakers — From 15 Amperes to 4,000 Amperes
With over a hundred years of
experience dating back to Henry Cutter’s
first “inverse time element” circuit
breaker in the late nineteenth century,
L-3 Communications/SPD Electrical
Systems is the world’s leading supplier
of innovative shock-hardened circuit
breakers and switchgear for military and
industrial applications.
The Actron line of technically superior,
electronically controlled MIL-SPEC circuit
breakers combines miniature electronic
Advanced features and commerc i a l - o ff-the-shelf (COTS)technology for significantly reduced logistics costs.
Smaller and lighter universal air circuit bre a k e r s .
E l e c t ronically controlled MIL-SPEC circuit breakers for harsh-environment applications.
C o n t e n t s
MOLDED-CASE CIRCUIT BREAKERSAQB HIGHLIGHTS PAGE 2A Q B - A 1 0 2 3AQB-A102 FUSED 3A Q B - A 2 5 2 4A Q B - L F 2 5 2 4A Q B - A 4 0 2 5A Q B - L F 4 0 2 5A Q B - A 8 0 2 6A Q B - A 1 6 0 4 7
AIR CIRCUIT BREAKERSACB HIGHLIGHTS 1 2A C B - 1 6 0 6 H R C 1 3A C B - 2 0 1 0 H R C 1 4A C B - 4 0 1 0 H R 1 5
D I M E N S I O N SA Q B - A 1 0 2 8AQB-A102 FUSED 8A Q B - A 2 5 2 8A Q B - L F 2 5 2 8A Q B - A 4 0 2 9A Q B - L F 4 0 2 9A Q B - A 8 0 2 9A Q B - A 1 6 0 4 9AQB TIME-CURRENTCURVES & ACCESSORIES 1 0AQB ORDERING DATA 1 1
D I M E N S I O N SA C B - 1 6 0 6 H R C 1 6A C B - 2 0 1 0 H R C 1 6A C B - 4 0 1 0 H R 1 6ACB TIME-CURRENTC U R V E S 1 6
—
—
Photo courtesy U.S. Navy
Photo courtesy U.S. Navy
Actron Circuit BreakerAQB-A102 & Fused AQB-A102
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
MULTIPLES OF 100 AMPERE FRAME RATING3X 4X 6X 8X 10X 12X 15X 20X 30X 40X
300 400 600 800 1000 1200 1500 2000 3000 4000
* A fuse unit is required for the fused AQB-A102.NOTE: Fused AQB-A102 available for 60HZ applications only.
CATALOG NUMBERS
ADJUSTABLE CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)15 25 50 75 100
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
ADJUSTABLE SHORT-TIME PICKUPSETTINGS IN AMPERES 60HZ & 400HZ
2X 3X 4X 6X 8X 10X 15X
15 30 45 60 90 120 150 22525 50 75 100 150 200 250 37550 100 150 200 300 400 500 75075 150 225 300 450 600 750 1125
100 200 300 400 600 800 1000 1500
CONTINUOUSCURRENTSETTING
AQB-A102 &Fused AQB-A102
Advanced COTS (commercial-off-the-shelf) TechnologyActron circuit breakers are based on leadingcommercial circuit breaker technologies.
Advanced FeaturesActron circuit breaker features allow increasedautomation and reduced manning throughlocal and remote state monitoring of circuitbreaker parameters.
Among the many new features are RMSSensing, Rating Plugs, Adjustable Short-TimeDelay Trip, Adjustable Instantaneous Settingsup to 50 times the frame rating, Ground FaultDetection, Real-Time State Monitoring,Bidirectional Communications and ControlFunctions and more.
Universal Circuit Breaker ApplicationEach Actron circuit breaker can be used forthe complete range of continuous currentsettings of that frame size.
Significantly Reduced Logistics CostsThe universal application of the Actroncircuit breakers reduces parts inventory andmaintenance, which lowers logistics costs.
Interchangeability withExisting Circuit BreakersActron circuit breakers meet the form, fitand function requirements of existing circuitbreakers in the Navy fleet.
Enhanced FeaturesThe electronic design of the Actron circuitbreakers allows for higher endurance ratingfor the shunt trip and undervoltage features,as much as four times to six times higher thanolder and competitive models.
■
■
■
■
■
■
TM
■
■
■
■
Increased AdjustableInstantaneous SettingsActron circuit breakers have adjustableinstantaneous settings as high as 50 times theframe rating, providing increased selectivity,flexibility and reduced cost.
Significantly Increased CoordinationThe Actron series represents a whole newgeneration of “smart,” tough, reliable circuitbreakers that have won the United StatesNavy’s QPL approval rating. In fact, the Navy’sown analysis conducted on surface combatantsshows that electronic circuit breakers achievea 70% increase in electrical coordination overolder and competitive models.
More Automation, Reduced ManningActron circuit breakers have microprocessorsthat automatically and continuously monitora host of current parameters. This providesthe capability for on-board automation andreduces manpower requirements and costs.
Less Hardware, Lower CostsIn the past, Navy circuit breakers used eitherthermal magnetic or electromechanical tripunits for overcurrent protection. By integratingelectronic overcurrent protection in the Actroncircuit breakers, L-3/SPD Electrical Systemseliminates the need for costly trip units. Everyframe size has all-continuous current settingsincluded and requires only a change in theswitch settings or rating plug. This providessimplified ordering, application versatility,reduced parts inventory and reducedmaintenance resulting in manpower savings.
Time-Current Characteristics refer to page 10.• Accessories refer to page 10.Installation Dimensions refer to page 8.
DESCRIPTION SUFFIX NO.
1a & 1b Auxiliary Switch 102a & 2b Auxiliary Switch 20115VAC 60HZ Shunt Trip 00S00115VAC 400HZ Shunt Trip 00S00450VAC 60HZ Shunt Trip 00S00120VDC Shunt Trip 00S00250VDC Shunt Trip 00S00
AUXILIARY FEATURES
2 3
ITEM A102 & FUSED A102*AQB Circuit Breaker (60HZ and 400HZ) ETN 2860NQB Circuit Breaker ETN 2862Single Mounting Base, Front-Connected ETN 2766Single Mounting Base, Rear-Connected ETN 2767Double Mounting Base, Front-Connected ETN 2768Double Mounting Base, Rear-Connected ETN 2769Fuse Unit Mounting Base, Front-Connected ETN 2786Fuse Unit Mounting Base, Rear-Connected ETN 2787Fuse Unit 15-100A (Fused AQB-A102 only)* ETN 2791
Actron Molded-CaseCircuit Breakers Offer:
4 5
Time-Current Characteristics refer to page 10.• Accessories refer to page 10. • Installation Dimensions refer to page 8.Time-Current Characteristics refer to page 10.• Accessories refer to page 10.Installation Dimensions refer to page 9.
CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)250 300 350 400
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
2X 3X 4X 6X 8X 10X 15X
250 500 750 1000 1500 2000 2500 3750300 600 900 1200 1800 2400 3000 4500350 700 1050 1400 2100 2800 3500 5250400 800 1200 1600 2400 3200 4000 6000
CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)250 300 350 400
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS IN AMPERES 60HZ
2X 3X 4X 6X 8X 10X 15X
250 500 750 1000 1500 2000 2500 3750300 600 900 1200 1800 2400 3000 4500350 700 1050 1400 2100 2800 3500 5250400 800 1200 1600 2400 3200 4000 6000
CONTINUOUSCURRENTSETTING
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
MULTIPLES OF 400 AMPERE FRAME RATING3X 4X 6X 8X 10X 12X 15X 20X 30X* 40X*
1200 1600 2400 3200 4000 4800 6000 8000 12000 16000
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
CONTINUOUSCURRENTSETTING
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ
MULTIPLES OF 400 AMPERE FRAME RATING3X 4X 6X 8X 10X 12X 15X 20X 30X 40X
1200 1600 2400 3200 4000 4800 6000 8000 12000 16000
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
DESCRIPTION SUFFIX NO.
1a & 1b Auxiliary Switch, Left Pole 102a & 2b Auxiliary Switch, Left Pole 203a & 3b Auxiliary Switch, Left Pole 3028VDC Shunt Trip 00S30120VDC Shunt Trip 00S32250VDC Shunt Trip 00S33115VAC Shunt Trip 00S31450VAC Shunt Trip 00S3633VDC Undervoltage 00U03120VDC Undervoltage 00U02250VDC Undervoltage 00U05115VAC Undervoltage 00U01450VAC Undervoltage 00U06
Actron Circuit BreakerAQB-A252 & AQB-LF252
Current-Limiting Fuse (three fuses required per circuit breaker) 1 Fuse ETN 7750
Current-Limiting Fuse Unit Assembly Housing, 3 Fuses CLFA252
AQB-LF252
State Monitoring provides monitoringof functions described on page 10.
AUXILIARY FEATURES
DESCRIPTION SUFFIX NO.
1a & 1b Auxiliary Switch, Left Pole 102a & 2b Auxiliary Switch, Left Pole 203a & 3b Auxiliary Switch, Left Pole 3028VDC Shunt Trip 00S30120VDC Shunt Trip 00S32250VDC Shunt Trip 00S33115VAC Shunt Trip 00S31450VAC Shunt Trip 00S3633VDC Undervoltage 00U03120VDC Undervoltage 00U02250VDC Undervoltage 00U05115VAC Undervoltage 00U01450VAC Undervoltage 00U06
AUXILIARY FEATURES
Current-Limiting Fuse (three fuses required per circuit breaker) 1 Fuse ETN 6796A
Current-Limiting Fuse Unit Assembly Housing, 3 Fuses CLFA402
AQB-LF402
State Monitoring provides monitoringof functions described on page 10.
Actron Circuit BreakerAQB-A402 & AQB-LF402
CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)125 150 175 225 250
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS IN AMPERES 60HZ
2X 3X 4X 6X 8X 10X 15X
125 250 375 500 750 1000 1250 1875150 300 450 600 900 1200 1500 2250175 350 525 700 1050 1400 1750 2625225 450 675 900 1350 1800 2250 3375250 500 750 1000 1500 2000 2500 3750
CONTINUOUSCURRENTSETTING
AQB-LF252
CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)100 125 150 160 175 225 250
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
2X 3X 4X 6X 8X 10X 15X
100 200 300 400 600 800 1000 1500125 250 375 500 750 1000 1250 1875150 300 450 600 900 1200 1500 2250160 320 480 640 960 1280 1600 2400175 350 525 700 1050 1400 1750 2625225 450 675 900 1350 1800 2250 3375250 500 750 1000 1500 2000 2500 3750
CONTINUOUSCURRENTSETTING
AQB-A252
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
MULTIPLES OF 250 AMPERE FRAME RATING3X 4X 6X 8X 10X 15X 20X 30X 40X* 50X*
750 1000 1500 2000 2500 3750 5000 7500 10000 12500
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ
MULTIPLES OF 250 AMPERE FRAME RATING3X 4X 6X 8X 10X 15X 20X 30X 40X 50X
750 1000 1500 2000 2500 3750 5000 7500 10000 12500
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
AQB-LF402
AQB-A402
Enhanced Circuit Breakers are Equipped with State Monitoring Features.Standard Circuit Breakers have no State Monitoring Features.
Enhanced Circuit Breakers are Equipped with State Monitoring Features.Standard Circuit Breakers have no State Monitoring Features.
*APPLICABLE FOR 60HZ ONLY.
*APPLICABLE FOR 60HZ ONLY.
CONTINUOUS AQB-A252 AQB-A252 AQB-LF252 REPLACEMENTCURRENT SETTING ENHANCED STANDARD ENHANCED STANDARD RATING PLUG(IN AMPERES) 60Hz 400Hz 60Hz 400Hz 60Hz 60Hz A252 LF252
– ETN 3100 ETN 3130 ETN 3150 ETN 3180 ETN 3200 ETN 3250 – –100 ETN 3101 ETN 3131 ETN 3151 ETN 3181 – – ERP2 100 –125 ETN 3102 ETN 3132 ETN 3152 ETN 3182 ETN 3201 ETN 3251 ERP2 125 ERP2 125150 ETN 3103 ETN 3133 ETN 3153 ETN 3183 ETN 3202 ETN 3252 ERP2 150 ERP2 150160 ETN 3104 ETN 3134 ETN 3154 ETN 3184 – – ERP2 160 –175 ETN 3105 ETN 3135 ETN 3155 ETN 3185 ETN 3203 ETN 3253 ERP2 175 ERP2 175225 ETN 3106 ETN 3136 ETN 3156 ETN 3186 ETN 3204 ETN 3254 ERP2 225 ERP2 225250 ETN 3107 ETN 3137 ETN 3157 ETN 3187 ETN 3205 ETN 3255 ERP2 250 ERP2 250
ITEM AQB-A252 AQB-LF252
NQBCircuit Breaker ETN 3199 –Motor Operator – 115VAC, 60HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3197 ETN 3297Motor Operator – 115VAC, 400HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3198 –Motor Operator – 115VAC, 60HZ, 120VDC ETN 5988 ETN 3296Motor Operator – 115VAC, 400HZ ETN 5827 –Switchboard Mounting Block (two required per circuit breaker) ETN 5314 ETN 5314
CONTINUOUS AQB-A402 AQB-A402 AQB-LF402 REPLACEMENTCURRENT SETTING ENHANCED STANDARD ENHANCED STANDARD RATING PLUG(IN AMPERES) 60Hz 400Hz 60Hz 400Hz 60Hz 60Hz A402 LF402
– ETN 3300 ETN 3330 ETN 3350 ETN 3380 ETN 3400 ETN 3450 – –250 ETN 3301 ETN 3331 ETN 3351 ETN 3381 ETN 3401 ETN 3451 ERP4 250 ERP4 250300 ETN 3302 ETN 3332 ETN 3352 ETN 3382 ETN 3402 ETN 3452 ERP4 300 ERP4 300350 ETN 3303 ETN 3333 ETN 3353 ETN 3383 ETN 3403 ETN 3453 ERP4 350 ERP4 350400 ETN 3304 ETN 3334 ETN 3354 ETN 3384 ETN 3404 ETN 3454 ERP4 400 ERP4 400
ITEM AQB-A402 AQB-LF402
NQBCircuit Breaker ETN 3399 –Motor Operator – 115VAC, 60HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3397 ETN 3497Motor Operator – 115VAC, 400HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3398 –Motor Operator – 115VAC, 60HZ, 120VDC ETN 6798 ETN 6797Motor Operator – 115VAC, 400HZ ETN 6810 ETN 6960Switchboard Mounting Block (two required per circuit breaker) ETN 6743 ETN 6743
6 7
Actron Circuit BreakerAQB-A802
Actron Circuit BreakerAQB-A1604
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
2X 3X 4X 6X 8X 10X
400 800 1200 1600 2400 3200 4000500 1000 1500 2000 3000 4000 5000600 1200 1800 2400 3600 4800 6000700 1400 2100 2800 4200 5600 7000800 1600 2400 3200 4800 6400 8000
CONTINUOUSCURRENTSETTING
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ
MULTIPLES OF 1600 AMPERE FRAME RATING3X 4X 5X 6X 8X 10X 12X 15X
4800 6400 8000 9600 12800 16000 19200 24000
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS IN AMPERES 60HZ
2X 3X 4X 6X 8X 10X
600 1200 1800 2400 3600 4800 6000800 1600 2400 3200 4800 6400 8000
1000 2000 3000 4000 6000 8000 100001200 2400 3600 4800 7200 9600 120001400 2800 4200 5600 8400 11200 140001600 3200 4800 6400 9600 12800 16000
CONTINUOUSCURRENTSETTING
CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)600 800 1000 1200 1400 1600
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS IN AMPERES 60HZ & 400HZ
MULTIPLES OF 800 AMPERE FRAME RATING3X 4X 5X 6X 8X 10X 12X* 15X* 20X* 30X*
2400 3200 4000 4800 6400 8000 9600 12000 16000 24000
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
CONTINUOUS CURRENT SETTINGS (CCS) (IN AMPERES)400 500 600 700 800
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .025 – .0552 .065 – .0953 .105 – .135
Time-Current Characteristics refer to page 10.• Accessories refer to page 10. • Installation Dimensions refer to page 9.Time-Current Characteristics refer to page 10.• Accessories refer to page 10.Installation Dimensions refer to page 9.
AQB-A802AQB-A1604
State Monitoring providesmonitoring of the following functions:■ Ground Fault ■ Type & Phase of Last Trip■ Phase Current ■ Current Data Logging■ Bidirectional Communication■ Remote Opening & Closing of Circuit Breaker
State Monitoring providesmonitoring of the following functions:■ Ground Fault ■ Type & Phase of Last Trip■ Phase Current ■ Current Data Logging■ Bidirectional Communication■ Remote Opening & Closing of Circuit Breaker
DESCRIPTION SUFFIX NO.
1a & 1b Auxiliary Switch, Left Pole 102a & 2b Auxiliary Switch, Left Pole 203a & 3b Auxiliary Switch, Left Pole 3028VDC Shunt Trip 00S30120VDC Shunt Trip 00S32250VDC Shunt Trip 00S33115VAC Shunt Trip 00S31450VAC Shunt Trip 00S3633VDC Undervoltage 00U03120VDC Undervoltage 00U02250VDC Undervoltage 00U05115VAC Undervoltage 00U01450VAC Undervoltage 00U06
AUXILIARY FEATURESDESCRIPTION SUFFIX NO.
1a & 1b Auxiliary Switch, Left Pole 102a & 2b Auxiliary Switch, Left Pole 203a & 3b Auxiliary Switch, Left Pole 3028VDC Shunt Trip 00S30120VDC Shunt Trip 00S32250VDC Shunt Trip 00S33115VAC Shunt Trip 00S31450VAC Shunt Trip 00S3633VDC Undervoltage 00U03120VDC Undervoltage 00U02250VDC Undervoltage 00U05115VAC Undervoltage 00U01450VAC Undervoltage 00U06
AUXILIARY FEATURES
*APPLICABLE FOR 60HZ ONLY.
Enhanced Circuit Breakers are Equipped with State Monitoring Features.Standard Circuit Breakers have no State Monitoring Features.
Enhanced Circuit Breakers are Equipped with State Monitoring Features.Standard Circuit Breakers have no State Monitoring Features.
ITEM AQB-A802
NQBCircuit Breaker ETN 3599Motor Operator – 115VAC, 60HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3597Motor Operator – 115VAC, 400HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3598Motor Operator – 115VAC, 60HZ, 120VDC ETN 3596Switchboard Mounting Block (two required per circuit breaker) ETN 8221
CONTINUOUS AQB-A802 AQB-A802 REPLACEMENTCURRENT SETTING ENHANCED STANDARD RATING PLUG(IN AMPERES) 60Hz 400Hz 60Hz 400Hz A802
– ETN 3500 ETN 3530 ETN 3550 ETN 3580 –400 ETN 3501 ETN 3531 ETN 3551 ETN 3581 ERP8 400500 ETN 3502 ETN 3532 ETN 3552 ETN 3582 ERP8 500600 ETN 3503 ETN 3533 ETN 3553 ETN 3583 ERP8 600700 ETN 3504 ETN 3534 ETN 3554 ETN 3584 ERP8 700800 ETN 3505 ETN 3535 ETN 3555 ETN 3585 ERP8 800
CONTINUOUS AQB-A1604 AQB-A1604 REPLACEMENTCURRENT SETTING ENHANCED STANDARD RATING PLUG(IN AMPERES) 60Hz 60Hz A1604
– ETN 3600 ETN 3650 –600 ETN 3601 ETN 3651 ERP16 600800 ETN 3602 ETN 3652 ERP16 800
1000 ETN 3603 ETN 3653 ERP16 10001200 ETN 3604 ETN 3654 ERP16 12001400 ETN 3605 ETN 3655 ERP16 14001600 ETN 3606 ETN 3656 ERP16 1600
ITEM AQB-A1604
NQBCircuit Breaker ETN 3699Motor Operator – 115VAC, 60HZ, 120VDC for Circuit Breaker with State Monitoring ETN 3697Motor Operator – 115VAC, 60HZ, 120VDC ETN 9770Motor Operator – 450VAC, 60HZ ETN 9709Switchboard Mounting Base (one required per circuit breaker) ETN 9750
8 9
Weights & Dimensions
FusedAQB-A102
MOUNTING BASE DIMENSIONSDESCRIPTION A B C LBSSINGLE BASE, FRONT CONNECTED 4 1/8 6 1/2 1 3/8 2.40SINGLE BASE, REAR CONNECTED 4 1/8 6 1/2 3 7/8 3.20DOUBLE BASE, FRONT CONNECTED 4 1/8 14 1 3/8 4.60DOUBLE BASE, REAR CONNECTED 4 1/8 14 3 7/8 5.40CIRCUIT BREAKER 6.00
AQB-A102
AQB-LF252AQB-A252
MOUNTING BASE DIMENSIONSDESCRIPTION A B C LBSSINGLE BASE, FRONT CONNECTED 4 1/8 10 1 3/8 5.40SINGLE BASE, REAR CONNECTED 4 1/8 10 3 7/8 6.20DOUBLE BASE, FRONT CONNECTED 4 1/8 20 1 3/8 10.60DOUBLE BASE, REAR CONNECTED 4 1/8 20 3 7/8 11.40CIRCUIT BREAKER 6.00
NET WEIGHTS LBSCIRCUIT BREAKER (WITH 3 FUSES) 31.44CURRENT-LIMITING FUSE UNIT 8.30MOUNTING BLOCK 2.50MOTOR OPERATOR 25.00
NET WEIGHTS LBSCIRCUIT BREAKER 21.56MOUNTING BLOCK 2.50MOTOR OPERATOR 25.00
4 1/8
6 1/2
4 5/16
A
B
C
4 7/89
11
4 21/32
4 7/8
9
6 13/16
12
4 21/32
6 13/16
4 1/8
B
4 5/16
A
B
C
MOUNTING BASE
MOUNTING BASE
PLAN VIEW OFMOUNTING BLOCK &
CIRCUIT BREAKER
PLAN VIEW OFMOUNTING BLOCK &
CIRCUIT BREAKER
Dimensions are in inches.
AQB-LF402AQB-A402
AQB-A1604AQB-A802NET WEIGHTS LBSCIRCUIT BREAKER 65.00MOUNTING BASE 34.00MOTOR OPERATOR 25.00
NET WEIGHTS LBSCIRCUIT BREAKER 72.00MOUNTING BLOCK 11.00MOTOR OPERATOR 25.00
9
15 1/2
5 1/16
4 7/8
5 1/16
9
22
5 1/2
6 13/16
5 1/2
9 4 3/4
16 1/2
5 3/8
4 3/4
9
9
17 15/16
4 7/8
6 3/16
6 3/16
PLAN VIEW OFMOUNTING BLOCK &
CIRCUIT BREAKERPLAN VIEW OF MOUNTING BLOCK &
CIRCUIT BREAKER
NET WEIGHTS LBSCIRCUIT BREAKER 32.94MOUNTING BLOCK 6.00MOTOR OPERATOR 25.00
PLAN VIEW OFMOUNTING BLOCK &
CIRCUIT BREAKER
NET WEIGHTS LBSCIRCUIT BREAKER 44.75CURRENT-LIMITING FUSE UNIT 8.50MOUNTING BLOCK 6.00MOTOR OPERATOR 25.00
PLAN VIEW OFMOUNTING BLOCK &
CIRCUIT BREAKER
Weights & Dimensions
Dimensions are in inches.
10 11
SHUNT TRIP UNDERVOLTAGE TRIP28 VDC S30 33 VDC U03120 VDC S32 120 VDC U02250 VDC S33 250 VDC U05115 VAC S31 115 VAC U01450 VAC S36 450 VAC U06
POSITION 1 2 3 4 5 6 7 8 9 10 11 12 13 14
CATALOG NO. E T N 3 1 5 1 1 0 S 3 0
Ordering Data — Actron AQBsSee page 10 for possible feature combinations.
AQB-A/LF252 through AQB-A1604
Positions 1 through 7 Circuit breaker catalog number from pages 1 through 7. If a circuit breakerwith no features is being ordered, fill only these positions.
Positions 8 and 9 Number of auxiliary switches (1a & 1b contacts per switch) available forcustomer use. Available options are as follows:
Positions 10 through 12 Indicates if a shunt trip or undervoltage trip is required. Available options are as follows.
Position 13 Indicates if lugs or connectors are required. Available options are:
( Z)-Line and load side lugs instead of tulip clips.(X )-Load side lugs only instead of tulip clips.(C )-Connector required on feature leads.
Position 14 Indicates if lugs are required when a connector is specified in position 13.Available options are the same as (Z ) and (X ) above.
AQB-A/LF252 through AQB-A1604
POSITION 1 2 3 4 5 6 7 8 9 10 11 12
CATALOG NO. E T N 2 8 6 0 1 0 S 0 0
AQB-A102 and Fused AQB-A102
NUMBER POSITION 8 and 9
OF SWITCHES STANDARD SWITCH SWITCH WIRED IN PARALLEL* ALL LEADS WIRED OUT0 00 00 001 10 40 70 (2a & 2b)2 20 50 80 (4a & 4b)3 30 60** 90 (6a & 6b)**
AQB-A102 and Fused AQB-A102
Positions 1 through 7 Basic circuit breaker catalog number. If a circuitbreaker with no features is being ordered, fill onlythese positions.
Positions 8 and 9 Number of auxiliary (a & b) contacts available forcustomer use. Available options are 0, 1, 2.
Positions 10 through 12 Indicates if a shunt trip is required. Available optionis (S ) for shunt trip. The shunt trip voltage rating isuniversal for the following ratings:115VAC 60HZ & 400HZ, 450VAC 60HZ,120VDC & 250VDC.
AQB TIME-CURRENTCHARACTERISTICS
CURVE
DESCRIPTION AQB-A102 AQB-A252 AQB-LF252 AQB-A402 AQB-LF402 AQB-A802 AQB-A1604
Handle-Locking Device ETN 4304 ETN 4305 ETN 4305 ETN 4305 ETN 4305 ETN 8218 ETN 9717Handle Shield ETN 2785Extension Handle ETN 9000 ETN 9000Cable Adapter-800AMP ETN 9752Cable Adapter-1600AMP ETN 9753Current-Limiting Fuse-1 ETN 7750 ETN 6796AElectronic AQB Test Set 117602K01 117602K01 117602K01 117602K01 117602K01 117602K01
AQB ACCESSORIES
INTERRUPTING NO. OFFRAME VOLTAGE AMPERE CAPACITY NO. OF PROTECTEDSIZE RATING RATINGS (ASYM, AMPS) POLES POLES
AQB-A102 500VAC, 60HZ 15-100 15,000 3 3500VAC, 400HZ 15-100 10,000 3 3
AQB-A102 FUSED 500VAC, 60HZ 15-100 100,000 3 3NQB-A102 500VAC, 60 & 400HZ 100 – 3 –AQB-A252 500VAC, 60HZ 100-250 20,000 3 3
500VAC, 400HZ 100-250 10,000 3 3NQB-A252 500VAC, 60 & 400HZ 250 – 3 –AQB-LF252 500VAC, 60HZ 125-250 100,000 3 3AQB-A402 500VAC, 60HZ 250-400 30,000 3 3
500VAC, 400HZ 250-400 10,000 3 3NQB-A402 500VAC, 60 & 400HZ 400 – 3 –AQB-LF402 500VAC, 60HZ 250-400 100,000 3 3AQB-A802 500VAC, 60HZ 400-800 50,000 3 3
500VAC, 400HZ 400-800 10,000 3 3NQB-A802 500VAC, 60 & 400HZ 800 – 3 –AQB-A1604 500VAC, 60HZ 600-1600 75,000 3 3NQB-A1604 500VAC, 60HZ 1600 – 3 –
ACTRON AQB RATINGS
AQB-A/LF252 THROUGH AQB-A1604
AUXILIARY SHUNT CATALOGSWITCHES TRIP UNDERVOLTAGE NUMBERS
0 0 0 ETN xxxx1 0 0 ETN xxxx102 0 0 ETN xxxx203 0 0 ETN xxxx300 1 0 ETN xxxx00Sxx1 1 0 ETN xxxx10Sxx2 1 0 ETN xxxx20Sxx0 0 1 ETN xxxx00Uxx1 0 1 ETN xxxx10Uxx2 0 1 ETN xxxx20Uxx3 0 1 ETN xxxx30Uxx
NOTES: xxxx – Basic Catalog Numberxx – Auxiliary Feature Suffix Number
SHORT-TIME DELAYPICKUP SETTINGS
(2X – 15X)
FUSECHARACTERISTICS
SHORT-TIMEDELAY
SETTINGS
CURRENT IN MULTIPLES OF CONTINUOUS CURRENT SETTINGS
LONG-TIME DELAY
BAND NO. 3BAND NO. 2
BAND NO. 1
AQB-A102
AUXILIARY SHUNT CATALOGSWITCHES TRIP UNDERVOLTAGE NUMBERS
0 0 0 ETN xxxx1 0 0 ETN xxxx102 0 0 ETN xxxx200 1 0 ETN xxxx00S001 1 0 ETN xxxx10S00
FEATURE COMBINATIONS
STATE MONITORING PROVIDES MONITORINGOF THE FOLLOWING FUNCTIONS:
■ Ground Fault■ Type & Phase of Last Trip■ Phase Current■ Current Data Logging■ Bidirectional Communication■ Remote Opening & Closing of Circuit Breaker
NUMBER POSITION 8 and 9
OF SWITCHES STANDARD SWITCH0 001 102 20
* For low voltage, low current applications ** Not available on enhanced version, or when a shunt trip is required
Positions 10 through 12: Location for 3-character shunt trip or undervoltage trip suffix.A “00” in positions 8 and 9 indicates that additional auxiliary switches are not required.However, an internal “a” contact is automatically provided to be externally wired toshunt trip coils. Caution should be exercised when specifying both auxiliary switchesand shunt trip or undervoltage trip features since not all combinations are feasible.
SHUNT TRIP SUFFIX NO.
115VAC 60HZ Shunt Trip S00115VAC 400HZ Shunt Trip S00450VAC 60HZ Shunt Trip S00120VDC Shunt Trip S00250VDC Shunt Trip S00
12 13
Charging Motor Protection ✓ *Electrical Closing Mechanism ✓ *Cell Switch ✓
Hold Close ✓ ✓
Indicating Light ✓
Lockout ✓ ✓ *Mechanical Position Indicator ✓
Secondary Disconnects (Qty. = 24) ✓
Operations Counter ✓
Overcurrent Protection ✓ ✓
Undervoltage Protection ✓ ✓ *Shunt Trip ✓ ✓ *Trip On Power Up ✓ ✓ *Fault Closing Discrimination ✓
Ground Fault Current Detection ✓
Actron Circuit BreakerACB-1606HRC
* Control voltage available at 120VAC and 450VAC.
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .080 – .1202 .160 – .2403 .240 – .360
Field ControlFeatures Standard Option Selectable Voltage
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS
MULTIPLES OF 1600 AMPERE FRAME RATING3X 5X 6X 8X 10X 12X 15X 18X 20X
4800 8000 9600 12800 16000 19200 24000 28800 32000
ADJUSTABLE RATINGS & CONTINUOUS CURRENT SETTINGS (CCS)600 800 1000 1200 1400 1600
ADJUSTABLE LONG-TIME DELAY PICKUP SETTINGS(IN MULTIPLES OF CONTINUOUS CURRENT SETTING)
1.5X 2.0X 2.5X
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS(IN MULTIPLES OF CONTINUOUS CURRENT SETTING)
2X 2.5X 3X 4X 5X 6X 7X 8X
ACB-1606HRC
The ACB-1606HRC is half the size of existing 1600 Ampere ACB’s.Time-Current Characteristics refer to page 16. • Installation Dimensions refer to page 16.
State Monitoring provides monitoring of the following functions:■ Ground Fault ■ Type & Phase of Last Trip ■ Phase Current■ Current Data Logging ■ Bidirectional Communication■ Remote Opening & Closing of Circuit Breaker
Advanced COTS (commercial-off-the-shelf) TechnologyActron circuit breakers are based on GroupeSchneider’s Masterpact circuit breaker, theleading air circuit breaker in the world.
Advanced FeaturesActron circuit breaker features allow increasedautomation and reduced manning throughlocal and remote state monitoring of circuitbreaker parameters.Among the many new standard features areRMS Sensing, Ground Fault Detection, Real-TimeState Monitoring, Bidirectional Communications,Control Functions, Undervoltage Dropout,Undervoltage Lockout, Power-Up Trip, ChargingMotor Protection and more.
Universal Circuit Breaker ApplicationEach Actron circuit breaker has continuouscurrent settings and standard features included,and requires only a change in switch settingsto reconfigure the circuit breaker.
Significantly Reduced Logistics CostsThe universal application of the Actroncircuit breakers reduces parts inventory andmaintenance, which lowers logistics costs.
Smaller and Lighter Air Circuit BreakersActron circuit breakers are as much as one-halfof the size and weight of existing air circuitbreakers. That means reduced size and weightfor switchgear as well!
Interchangeability withExisting Circuit BreakersActron circuit breakers can meet the form, fitand function requirements of existing circuitbreakers in the Navy fleet through the useof the Actron retrofit kit.
■
■
■
■
■
■
■
■
■
Significantly Increased CoordinationThe Actron series represents a whole newgeneration of “smart,” tough, reliable circuitbreakers that have won the United StatesNavy’s QPL approval rating. In fact, the Navy’sown analysis conducted on surface combatantsshows that electronic circuit breakers achievea 70% increase in electrical coordination overolder and competitive models.
More Automation, Reduced ManningActron circuit breakers have microprocessorsthat automatically and continuously monitora host of current parameters. This providesthe capability for on-board automation andreduces manpower requirements and costs.
Less Hardware, Lower CostsIn the past, Navy circuit breakers used electro-mechanical trip units for overcurrent protection.By integrating electronic overcurrent protectionin the Actron circuit breakers, L-3/SPD ElectricalSystems eliminates the need for costly overcurrentassemblies. With the flexibility provided by theActron circuit breaker, this provides simplifiedordering, application versatility, reduced partsinventory, and reduced maintenance resultingin manpower savings.
TM
Ratings of Circuit Breakers and AttachmentsRated Continuous Current (Amperes) 1600Rated Maximum Voltage (60 HZ) 500V ACMaximum Interrupting Rating – Rated Symmetrical Short Circuit Current (Amperes) 85,000 ACRated Short-Time Current (Amperes) 85,000Rated Short-Time Current (Duration) (Seconds) 0.50Maximum Weight – Breaker (LBS) 205Maximum Weight – Cradle (LBS) 278Number of Poles 3Number of Protected Poles 3Auxiliary Switches – No. of Contacts 8
Actron Air CircuitBreakers Offer:
14 15
Actron Circuit BreakerACB-4010HR
Charging Motor Protection ✓ *Electrical Closing Mechanism ✓ *Cell Switch ✓
Hold Close ✓ ✓
Indicating Light ✓
Lockout ✓ ✓ *Mechanical Position Indicator ✓
Secondary Disconnects (Qty. = 30) ✓
Operations Counter ✓
Overcurrent Protection ✓ ✓
Undervoltage Protection ✓ ✓ *Shunt Trip ✓ ✓ *Trip On Power Up ✓ ✓ *Fault Closing Discrimination ✓
Ground Fault Current Detection ✓
* Control voltage available at 120VAC and 450VAC.
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .065 – .1302 .130 – .2403 .240 – .3404 .360 - .5005 .500 - .900
Field ControlFeatures Standard Option Selectable Voltage
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS
MULTIPLES OF 4000 AMPERE FRAME RATING3X 5X 6X 8X 10X 12X 15X 17X 20X
12000 20000 24000 32000 40000 48000 60000 68000 80000
ADJUSTABLE RATINGS & CONTINUOUS CURRENT SETTINGS (CCS)2000 2400 2800 3200 4000
ADJUSTABLE LONG-TIME DELAY PICKUP SETTINGS(IN MULTIPLES OF CONTINUOUS CURRENT SETTING)
1.5X 2.0X 2.5X
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS(IN MULTIPLES OF CONTINUOUS CURRENT SETTING)2X 2.5X 3X 4X 5X
ACB-4010HR
Ratings of Circuit Breakers and AttachmentsRated Continuous Current (Amperes) 2000Rated Maximum Voltage (60 HZ) 500V ACMaximum Interrupting Rating – Rated Symmetrical Short Circuit Current (Amperes) 85,000 ACRated Short-Time Current (Amperes) 85,000Rated Short-Time Current (Duration) (Seconds) 0.50Maximum Weight – Breaker (LBS) 205Maximum Weight – Cradle (LBS) 278Number of Poles 3Number of Protected Poles 3Auxiliary Switches – No. of Contacts 8
Actron Circuit BreakerACB-2010HRC
Charging Motor Protection ✓ *Electrical Closing Mechanism ✓ *Cell Switch ✓
Hold Close ✓ ✓
Indicating Light ✓
Lockout ✓ ✓ *Mechanical Position Indicator ✓
Secondary Disconnects (Qty. = 24) ✓
Operations Counter ✓
Overcurrent Protection ✓ ✓
Undervoltage Protection ✓ ✓ *Shunt Trip ✓ ✓ *Trip On Power Up ✓ ✓ *Fault Closing Discrimination ✓
Ground Fault Current Detection ✓
* Control voltage available at 120VAC and 450VAC.
ADJUSTABLE SHORT-TIMEDELAY SETTING
SHORT-TIME DELAYDELAY BAND (SECONDS)
1 .065 – .1302 .130 – .2403 .240 – .3404 .360 - .500
Field ControlFeatures Standard Option Selectable Voltage
ADJUSTABLE INSTANTANEOUS PICKUP SETTINGS
MULTIPLES OF 2000 AMPERE FRAME RATING3X 5X 6X 8X 10X 12X 15X 18X 20X
6000 10000 12000 16000 20000 24000 30000 36000 40000
ADJUSTABLE RATINGS & CONTINUOUS CURRENT SETTINGS (CCS)800 1000 1200 1400 1600 2000
ADJUSTABLE LONG-TIME DELAY PICKUP SETTINGS(IN MULTIPLES OF CONTINUOUS CURRENT SETTING)
1.5X 2.0X 2.5X
ADJUSTABLE SHORT-TIME DELAY PICKUP SETTINGS(IN MULTIPLES OF CONTINUOUS CURRENT SETTING)2X 2.5X 3X 4X 5X
ACB-2010HRC
The ACB-2010HRC is half the size of existing 2000 Ampere ACB’s.Time-Current Characteristics refer to page 16. • Installation Dimensions refer to page 16.
State Monitoring provides monitoring of the following functions:■ Ground Fault ■ Type & Phase of Last Trip ■ Phase Current■ Current Data Logging ■ Bidirectional Communication■ Remote Opening & Closing of Circuit Breaker
State Monitoring provides monitoring of the following functions:■ Ground Fault ■ Type & Phase of Last Trip ■ Phase Current■ Current Data Logging ■ Bidirectional Communication■ Remote Opening & Closing of Circuit Breaker
The ACB-4010HR is half the size of existing 4000 Ampere ACB’s.Time-Current Characteristics refer to page 16. • Installation Dimensions refer to page 16.
Ratings of Circuit Breakers and AttachmentsRated Continuous Current (Amperes) 4000Rated Maximum Voltage (60 HZ) 500V ACMaximum Interrupting Rating – Rated Symmetrical Short Circuit Current (Amperes) 85,000 ACRated Short-Time Current (Amperes) 85,000Rated Short-Time Current (Duration) (Seconds) 0.75Maximum Weight – Breaker (LBS) 360Maximum Weight – Cradle (LBS) 410Number of Poles 3Number of Protected Poles 3Auxiliary Switches – No. of Contacts 12
16 17
ACB-1606HRC& ACB-2010HRC
20.63
17.94
16.2824.72
21.63
32.94
16.28
24.72
ACB Dimensions
Dimensions are in inches.
STATE MONITORING PROVIDESMONITORING OF THE FOLLOWING FUNCTIONS:
■ Ground Fault ■ Type & Phase of Last Trip ■ Phase Current ■ Current Data Logging■ Bidirectional Communication ■ Remote Opening & Closing of Circuit Breaker
ACB-4010HR
ACB TIME-CURRENT CHARACTERISTICS CURVES
ACB-1606HRC ACB-2010HRC ACB-4010HR
LONG-TIME PICKUP SETTINGSMULTIPLES OF CONTINUOUS
CURRENT SETTINGS1.5 2.0 2.5
SHORT-TIME DELAYS (SECONDS)BAND NO. 1 BAND NO. 2 BAND NO. 3.080 –.120 .160 –.240 .240 –.360
SHORT-TIME DELAYS (SECONDS)BAND NO. 1 BAND NO. 2 BAND NO. 3 BAND NO. 4 BAND NO. 5.065 –.130 .130 –.240 .240 –.340 .360 –.500 .500 –.900
SHORT-TIME DELAYS (SECONDS)BAND NO. 1 BAND NO. 2 BAND NO. 3 BAND NO. 4.065 –.130 .130 –.240 .240 –.340 .360 –.500
SHORT-TIME PICKUP SETTINGSMULTIPLES OF CONTINUOUS
CURRENT SETTINGS2.0 2.5 3.0 4.0 5.0 6.0 7.0 8.0
SHORT-TIME PICKUP SETTINGSMULTIPLES OF CONTINUOUS
CURRENT SETTINGS2.0 2.5 3.0 4.0 5.0
SHORT-TIME PICKUP SETTINGSMULTIPLES OF CONTINUOUS
CURRENT SETTINGS2.0 2.5 3.0 4.0 5.0
LONG-TIME PICKUP SETTINGSMULTIPLES OF CONTINUOUS
CURRENT SETTINGS1.5 2.0 2.5
LONG-TIME PICKUP SETTINGSMULTIPLES OF CONTINUOUS
CURRENT SETTINGS1.5 2.0 2.5
2.08.0
2.0 2.05.0
5.0
BAND NO. 1
BAND NO. 2
BAND NO. 3
BAND NO. 1
BAND NO. 2
BAND NO. 3
BAND NO. 4
BAND NO. 1
BAND NO. 2
BAND NO. 3
BAND NO. 5
BAND NO. 4
Notes: