IM-WMJ-1208(0)L-YORKPart No.: R08019032669
INSTALLATION MANUALWALL MOUNTED
SPLIT TYPE AIR CONDITIONER(J Series)
INSTALLATION MANUAL
1
Eng
lish
OUTLINE AND DIMENSIONS
Indoor Unit [WMJ Series]
ATHE MARK SHOWS PIPING DIRECTION
LEFTREAR
TOP VIEW
REARRIGHT
B
BOTTOM
LOUVER FRONT GRILLEFIXED SCREWS(INSIDE)
BOTTOM
FRONT VIEW
SIGNAL RECEIVER
INDOOR UNIT ON/OFF SWITCH
ROOM TEMPERATURE THERMISTOR (INSIDE)
B
NAMEPLATE
TERMINALBLOCKWITHEARTHTERMINAL
C
SIDE VIEW
Recommended mountingplate retention spots(5 spots in all)
D
Use tape measure as shown.Position the end of a tapemeasure at
BG
All dimensions are in mm / (in)
HJ L
MA
K
F
I
G
F
E
Through the wallhole Ø 65mm
Drain hoseposition
Gas pipe endLiquid pipe end
INSTALLATIONPLATE
Dimension A B C D E F G H I J K L M
WM10/15J 800 288 206 166 184 42 46 55 56 154 182 263 52(31.5) (11.3) (8.1) (6.5) (7.2) (1.7) (1.8) (2.1) (2.2) (6.1) (7.2) (10.4) (2.0)
2
Outdoor Unit [SLC Series]
K
BAll dimensions are in mm / (in)
Dimension A B C D E F G H I J K L M N O
SL09C 600 475 245 418 177 35 93 81 83 55 398 101 97 17 22(23.6) (18.7) (9.6) (16.4) (6.9) (1.3) (3.6) (3.1) (3.2) (2.2) (15.6) (3.9) (3.8) (0.6) (0.8)
SL15C 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18(27.5) (20.5) (9.8) (19.1) (6.8) (1.4) (3.7) (3.6) (3.3) (2.6) (17.3) (5.1) (4.3) (0.5) (0.7)
L L
CN
N
M
30 (1.2
)
A
DO
3(0
.1)
19 (0.7
)
65 (2.6
)80 (3.1
)
C
G H
I J
EF
3
Eng
lish
SAFETY PRECAUTIONS
This manual provides the procedures of installation to ensure a safe and good standardof operation for the air conditioner unit.Special adjustment may be necessary to suit local requirements.Before using your air conditioner, please read this instruction manual carefully andkeep it for future reference.
INSTALLATION MANUAL
! CAUTIONPlease take note of the following importantpoints when installing.• Do not install the unit where leakage of
flammable gas may occur.If gas leaks and accumulates around theunit, it may cause fire ignition.
• Ensure that drainage piping is connectedproperly.
If the drainage piping is not connectedproperly, it may cause water leakagewhich will dampen the furniture.
• Do not overcharge the unit.This unit is factory pre-charged.Overcharge will cause over-current ordamage to the compressor.
• Ensure that the unit’s panel is closed afterservice or installation.
Unsecured panels will cause the unitto operate noisily.
• Sharp edges and coil surfaces are potentiallocations which may cause injury hazards.Avoid from being in contact with theseplaces.
• Before turning off the power supply, set theremote controller’s ON/OFF switch to the“OFF” position to prevent the nuisancetripping of the unit. If this is not done, theunit’s fans will start turning automaticallywhen power resumes, posing a hazard toservice personnel or the user.
• Do not operate any heating apparatus tooclose to the air conditioner unit. This maycause the plastic panel to melt or deform as aresult of the excessive heat.
• Ensure the color of wires of the outdoorunit and the terminal markings are sameto the indoors respectively.
• IMPORTANT : DO NOT INSTALL ORUSE THE AIR CONDITIONER UNIT INA LAUNDRY ROOM.
• Don’t use joined and twisted wires forincoming power supply.
! WARNING• Installation and maintenance should be
performed by qualified persons who are familiarwith local code and regulation, and experiencedwith this type of appliance.
• All field wiring must be installed in accordancewith the national wiring regulation.
• Ensure that the rated voltage of the unitcorresponds to that of the name plate beforecommencing wiring work according to thewiring diagram.
• The unit must be GROUNDED to preventpossible hazard due to insulation failure.
• All electrical wiring must not touch therefrigerant piping, or any moving parts of thefan motors.
• Confirm that the unit has been switched OFFbefore installing or servicing the unit.
• Disconnect from the main power supplybefore servicing the air conditioner unit.
• DO NOT pull out the power cord when thepower is ON. This may cause serious electricalshocks which may result in fire hazards.
• Keep the indoor and outdoor units, power cableand transmission wiring, at least 1m from TVsand radios, to prevent distorted pictures andstatic. {Depending on the type and source ofthe electrical waves, static may be heard evenwhen more than 1m away}.
4
INSTALLATION DIAGRAM
INSTALLATION OF THE OUTDOOR UNIT
The outdoor unit must be installed in such a way,so as to prevent short circuit of the hot dischargedair or obstruction to the smooth air flow. Pleasefollow the installation clearances shown in thefigure. Select the coolest possible place whereintake air temperature is not greater than theoutside air temperature (maximum 45°C).
Indoor Unit
Front panel
Outdoor Unit
50mm or more from walls(on both sides)
30mm or more from ceiling Caulk pipehole gapwith putty.
Cut thermal insulationpipe to an appropriatelength and wrap it withtape, making sure that nogap is left in the insulationpipe’s cut line.
Wrap the insulation pipe withthe finishing tape from bottomto top.
M4 x 12LAir filter
Air filterAir-Purifying Filterwith bacteriostaticvirustatic function
Filter frame
Tab
Air-Purifying Filter with bacteriostaticvirustatic function (2)
Service lid
����� Opening service lidService lid is opening/closing type.
����� Opening method1) Remove the service lid
screws.2) Pull out the service lid
diagonally down in thedirection of the arrow.
3) Pull down.
Dimension A B C
Minimum Distance, 300 300 500mm (in) (11.8) (11.8) (19.7)
Installation clearances
Obs
tacl
e
Ret
urn
air
Serv
ice
acce
ss
Obs
tacl
e
Obs
tacl
e
Ret
urn
air
Dis
char
ge a
ir
A
B C
Note: If there is any obstacle higher than 2m, orif there is any obstruction at the upper part of theunit, please allow more space than the figureindicated in the above table.
250mm from wall
5
Eng
lish
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a wayso as to prevent short circuit of the cooldischarged air with the hot return air. Pleasefollow the installation clearance shown in thefigure. Do not place the indoor unit where therecould be direct sunlight shining on it. Also, thislocation must be suitable for piping and drainage,and be away from doors or windows.
Air flow(Indoor)
Routing Of PipingRemove the screw holding the front panel.
12 4
5
63
Piping Routing
min
. 30
(Spa
ce f
or p
erfo
rman
ce)
Required space
All dimensions are in mm
min. 50
(Space formaintenance)
min. 50
(Space formaintenance)
The refrigerant piping can be routed to the unitin a number of ways (left or right from the backof the unit), by using the cut-out holes on thecasing of the unit (see figure). Bend the pipescarefully to the required position in order to alignit with the holes. For the side and bottom out,hold the bottom of the piping and then positionit to the required direction (see figure). Thecondensation drain hose can be taped to thepipes.
Right-Side, Right-Back or Right-BottomPiping
Right-back piping
Bind coolant pipeand drain hosetogether withinsulating tape.
Right-bottompiping
Remove pipe port cover herefor right-bottom piping
Right-sidepiping
Remove pipe port coverhere for right-side piping
Remove pipe port cover herefor left-bottom piping
Remove pipeport cover herefor left-sidepiping
Left-backpiping
Left-sidepiping
Left-bottom piping
Left-Side, Left-Back or Left-BottomPiping
6
Mounting Installation PlateEnsure that the wall is strong enough to withstandthe weight of the unit. Otherwise, it is necessaryto reinforce the wall with plates, beams or pillars.Use the level gauge for horizontal mounting, andfix it with 5 suitable screws.In case the rear piping draws out, drill a hole65mm in diameter with a cone drill, slightlylower on the outside wall (see figure).
Recommended Mounting PlateRetention Spots And Dimensions
How To Attach The Indoor UnitHook the claws of the bottom frame to themounting plate.
How To Remove The Indoor UnitPush up the marked area (at the lower part of thefront grille) to release the claws.
Mounting plate
Mounting platefixing screw
Inside Outside
Throughthe wallholeØ 65mm
Drainhoseposition
Recommended mountingplate retention spots(5 spots in all)
Use tape measure as shown.Position the end of a tape measureat
Gas pipe endLiquid pipe end
166 184
181.7 55.554.5 153.8 263 51.9800
45.9
42.2
288
42.2
45.9
Hole with cone drill
All dimensions are in mm
CaulkingWall embeddedpipe (Fieldsupply)
Wall hole cover(Field supply)
Wall embedded pipe(Field supply)
Ø 65
Mount The Unit Onto The InstallationPlateHook the indoor unit onto the upper portion ofthe installation plate (Engage the two hooks atthe rear top of the indoor unit with the upperedge of the installation plate). Ensure that thehooks are properly seated on the installation plateby moving it to the left and right.
Mountingplate
Clip
Mark(rear side)
Bottom frameFront grille
Mountingplate
Interconnectingwires
Hang indoor unit’s hook here.
Wire guide
When strippingthe ends ofinterconnectingwires in advance,bind right endsof wires withinsulating tape.
Water Drainage PipingThe indoor drain pipe must be in a downwardgradient for smooth drainage. Avoid situationsthat are likely to cause water to leak.
Enddippedintowater
Waterleaking
Waterleaking
Waterleaking
Wrong Wrong Wrong
Drain
Water Drainage
Waterretention
Correct
7
Eng
lish
REFRIGERANT PIPINGPiping Length & ElevationIf the pipe is too long, both the capacity andreliability of the unit will drop. As the numberof bends increases, resistance to the flow ofrefrigerant system increases, thus loweringcooling capacity. As a result, the compressor maybecome defective. Always choose the shortestpath and follow the recommendations astabulated below:
Outdoor Unit
Indoor Unit
ModelMin. allowable length (L)Max. allowable length (L)Max. allowable height (H)Gas pipeLiquid pipe
10 15
3m
15m
10m
O.D. 9.5mm O.D. 12.7mm
O.D. 6.4mm
L H
*Be sure to add the proper amount of additionalrefrigerant. Failure to do so may result inreduced performance.
Remark: The refrigerant pre-charged in theoutdoor unit is for piping length up to7.5 m.
Piping Works• Do not use contaminated or damaged copper
tubing. Do not remove plastic, rubber plugsand brass nuts from the valves, fittings, tubingsand coils until you are ready to connect suctionor liquid line into valves or fittings.
• If any brazing work is required, ensure thatthe nitrogen gas is passed through coil andjoints while the brazing work is being done.This will eliminate soot formation on theinside walls of the copper tubings.
• Cut the connection pipe with a pipe cutter.• Remove burrs from cut edges of the pipes with
remover.Hold the end of the pipe downwards to preventmetal chips from entering the pipe.
• Insert the flare nuts, mounted on theconnection parts of both the indoor unit andoutdoor unit onto the copper pipes.
• Flare the pipe with extra length above theflaring tool as shown in the table.
• The flared edge must be even and not crackedor scratched.
Ø Tube, D A (mm)Inch mm Imperial Rigid1/4" 6.35 1.3 0.73/8" 9.52 1.6 1.01/2" 12.70 1.9 1.35/8" 15.88 2.2 1.73/4" 19.05 2.5 2.0
Cutting copper tube
1/4t
Remove burr
Copper tubeSwaging block
8
Piping Connection To The Units• Align the center of the piping and tighten the
flare nut sufficiently with fingers.• Finally, tighten the flare nut with the torque
wrench until the wrench clicks.
Pipe Size mm / (in) Torque Nm / (ft - lb)6.35 (1/4) 18 (13.3)9.53 (3/8) 42 (31.0)12.7 (1/2) 55 (40.6)15.88 (5/8) 65 (48.0)19.05 (3/4) 78 (57.6) Torque wrench
Spanar
Flared tubeFlare joint
Flare nutIndoor piping
ELECTRICAL WIRING CONNECTION
IMPORTANT: * The figures shown in the table are for information purpose only. They shouldbe checked and selected to comply with the local/national codes ofregulations. This is also subject to the type of installation and conductorsused.
** The appropriate voltage range should be checked with label data on the unit.
COMP
N2
COMP
N
N1
L
E
OutdoorUnit
TerminalBlock
IndoorUnit
TerminalBlock
There must be a double pole switchwith a minimum 3mm contact gap andfuse/circuit breaker as recommendedin the fixed installation circuit.
!
Power Supply Cable
Cooling Unit (single phase)
Model WM10/15J
Voltage range** 220V-240V / 1Ph
/ 50Hz + !
Power supply cable size* mm2 1.5Number of wire 3
Interconnection cable size* mm2 1.5Number of wire 3
Recommended fuse A 15
9
Eng
lish
VACUUMING AND CHARGING
Purging The Piping And The Indoor UnitExcept for the outdoor unit which is pre-chargedwith refrigerant, the indoor unit and therefrigerant connection pipes must be air-purgedbecause the air containing moisture that remainsin the refrigerant cycle may cause malfunctionof the compressor.• Remove the caps from the valve and the
service port.• Connect the center of the charging gauge to
the vacuum pump.• Connect the charging gauge to the service
port of the 3-way valve.• Start the vacuum pump. Evacuate for
approximately 30 minutes. The evacuationtime varies with different vacuum pumpcapacity. Confirm that the charging gaugeneedle has moved towards -760mmHg.
Caution• If the gauge needle does not move to
-760mmHg, be sure to check for gas leaks(using the refrigerant detector) at flare typeconnection of the indoor and outdoor unitand repair the leak before proceeding to thenext step.
Service port Outdoor unit 3 ways valve
Flare nutRefrigerant piping
Allen key
• Close the valve of the charging gauge andstop the vacuum pump.
• On the outdoor unit, open the suction valve(3 way) and liquid valve (2 way) (in anti-clockwise direction) with 4mm key forhexagon sacked screw.
• All wires must be firmly connected.• All wires must not touch the refrigerant piping, compressor or any moving parts of the fan
motor.• The connecting wires between the indoor and the outdoor unit must be clamped on the wire
clamps.• The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum
requirement.
10
Charge OperationThis operation must be done by using a gascylinder and a precise weighing machine. Theadditional charge is topped-up into the outdoorunit using the suction valve via the service port.• Remove the service port cap.• Connect the low pressure side of the charging
gauge to the suction service port center ofthe cylinder tank and close the high pressureside of the gauge. Purge the air from theservice hose.
• Start the air conditioner unit.• Open the gas cylinder and low pressure
charging valve.• When the required refrigerant quantity is
pumped into the unit, close the low pressureside and the gas cylinder valve.
• Disconnect the service hose from serviceport. Put back the service port cap.
Suctionvalve
Discharge valve
Indoor Unit Outdoor UnitLiquid side
Gas side
Vacuumpump
Open
Close
Close
CloseHi
Low
Open
Open
Suctionvalve
Discharge valveIndoor Unit Outdoor UnitLiquid side
Gas side
Checkvalve
Close
Hi
Low
Additional ChargeThe refrigerant is pre-charged in the outdoor unit.If the piping length is less than 7.5m, thenadditional charge after vacuuming is notnecessary. If the piping length is more than 7.5m,then use the additional charge valve as indicatedin the table.
Additional refrigerant charge [g] peradditional 1m length as tabulated
Indoor WM10/15JOutdoor SL09/15CAdditional charge [g/m] 16
Example:
WM10J & SL09C with 12m piping length,additional piping length is 4.5m. Thus,Additional charge = 4.5[m] x 16[g/m]
= 72.0[g]
INDICATOR LIGHTS
IR Signal ReceiverWhen an infrared remote control operating signalhas been transmitted, the signal receiver on theindoor unit will respond as below to confirmacceptance of the signal transmission.
ON to OFF 1 Long BeepOFF to ON
2 Short Beep Pump down/Cool force onOthers 1 Short Beep
Cooling UnitThe table shows the LED indicator lights for theair conditioner unit under normal operation andfault conditions.The LED indicator lights are located at the right-bottom of the air conditioner unit.
IR Receiver
LED Indicator Lights for Cooling Unit
IR Receiver
ON/OFF
CoolTimerSleepON/OFF switch
11
Eng
lish
LED Indicator Lights : Normal Operation And Fault Conditions For CoolingUnit
Normal Operation / Action ErrorFault Indication Code
Cool mode – –
Auto mode in Cooling operation – –
Timer on – –
Sleep mode on – –
Fan mode on – –
Dry mode on – –
Room air sensor contact
Loose / ShortCall your dealer Blink E1
Outdoor coil sensor open Call your dealer Blink E3
Indoor coil sensor open Call your dealer Blink E2
Compressor overload /
Indoor coil sensor short / Call your dealer Blink E4
outdoor coil sensor short
Defrost operation – –
Gas leak Call your dealer Blink E5
Hardware error (tact switch pin short) Call your dealer Blink E8
No feedback from indoor fan Call your dealer Blink E9
EEPROM error Call your dealer Blink EE5 times
1 time
COOL(GREEN)
Green
Red
1 time
3 times
3 times
4 times
2 times
6 times
Green
ON ON or OFF Blinking
Note: The unit will not detect sensor missing when the compressor is ON.
1 2 N 1 2 N
500ms 500ms
500ms 500ms
3 seconds
ONOFF
ONOFF
Blink N times
Blink continuously
12
AIR CONDITIONER UNIT OPERATION
Dry Mode• When the air humidity is high, the unit can
operate in dry mode. Press <MODE> buttonand choose <DRY>.
• If the room temperature is 2°C/3.6°F higherthan the set temperature, the air conditionerwill operate under cooling mode until itreaches within the 2°C/3.6°F range ofdifference compared to the set temperaturebefore it converts to dry mode.
• If the room temperature is within the 2°C/3.6°F range of difference compared to theset temperature, it will directly operate underdry mode.
• The unit will operate at LOW speed underdry mode.
Air Flow Control• For more effective air circulation, you can
manually adjust the air discharge grille tothe left or right.
• During cool mode operation and dry modeoperation, do not direct the air dischargelouver downwards for too long. If operatingcontinues in this way, condensation mayoccur on the louver, thus resulting indrippings.
Frost Prevention• When the air filter is dirty, the evaporating
temperature will decrease and eventuallycause frosting.
• If the evaporating temperature reaches-1°C/33.8°F, the unit will trip.
Fan Speed And Rated Cooling Capacity• The rated cooling capacity is provided at the
high fan speed.• The cooling capacity is lower when the unit
is operating at MEDIUM and LOW fanspeed.
Notes On Flaps And Louvers Angles• When “SWING button” is selected, the flaps
swinging range depends on the operationmode. (See the figure.)
ATTENTION• Always use a remote controller to adjust the
flaps angle. If you attempt to move it forciblywith hand when it is swinging, themechanism may be broken.
• Be careful when adjusting the louvers. Insidethe air outlet, a fan is rotating at a high speed.
In COOL, DRY and FAN mode
When stopoperation
Upper limit 50˚
Lower limit 70˚
OPERATING RANGE
Cooling Unit
Temperature Ts °C / °F Th °C / °F
Minimum indoor temperature 19.0 / 66.2 14.0 / 57.2
Maximum indoor temperature 32.0 / 89.6 23.0 / 73.4
Minimum outdoor temperature 19.4 / 66.9 –
Maximum outdoor temperature 46.0 / 114.8 –
Ts: Dry bulb temperature. Th: Wet bulb temperature.
13
Eng
lish
AIR FILTER
1. Open the front panel.• Hold the panel at the recesses on the main
unit (2 recesses on right and left sides) andlift it until it stops.
2. Pull out the air filters.• Push a little upwards the tab at the center
of each air filter, then pull it down.
3. Take off the Bio filter withbacteriostatic, virustatic functions.• Hold the recessed parts of the frame and
unhook the four claws.
4. Clean or replace each filter.See figure.• When shaking off remaining water, do not
wring the filter.
5. Set the air filter and Bio filter withbacteriostatic, virustatic functions asthey were and close the front panel.• Insert claws of the filters into slots of the
front panel. Close the front panel slowly andpush the panel at the 3 points. (1 on eachside and 1 in the middle.)
• The air filter and Bio filter withbacteriostatic, virustatic functions have asymmetrical form in the horizontaldirection.
FRONT
Recess onmain unit
Filter frame
Tab
Air filter
Bio filter withbacteriostatic,virustatic functions
Titanium Apatit Filter (Bio Filter)Attached Concept Air filter
Heat exchanger
Bio filter attached partTitanium apatit filter
Installation Procedure for Bio filterBio filter packs in ahermetically-sealed bag.
Take it outat the time of installation.
Slip the filter in between filter frameand Titanium apatite filter.
Titanium apatite filter
Bio filter
Filter frame
14
! CAUTION• Storage, handling and disposal methods.
• The lifetime of this Bio filter is about a year after opening.
• In case you do not use this Bio filter right away, please don’t place the Bio filter inany place where it will be subjected to direct sunlight, high temperatures and/or highhumidity.
• There can be slight differences between Bio filter color because of the manufacturingreasons, there is no effect on the unit performance.
• Please open this bag right before you use it. Bio filter should remain unopened andsealed in its packaging until right before usage. (It may cause performancedeterioration or quality change.)
• To avoid danger of suffocation and any unexpected accident, please dispose theplastic bag immediately after you remove the Bio filter. Keep out of reach of babiesand children.
• If you keep this Bio filter for a long time, please keep it unopened and store in a coolplace avoiding direct sunlight.
• Please dispose the old Bio filter as nonflammable garbage after use.
• Operation with dirty filters:
(1) cannot deodorize the air. (3) results in poor cooling.
(2) cannot clean the air. (4) may cause odour.
• To order Bio filter, contact the service shop where you bought the air conditioner.
15
Eng
lish
SERVICE AND MAINTENANCE
Service Parts
Indoor airfilter
Indoor unit
Maintenance Procedures
1. Remove any dust adhering to the filter by using avacuum cleaner or wash in lukewarm water (below40°C/104°F) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it backonto the unit.
3. Do not use gasoline, volatile substances or chemicalsto clean the filter.
1. Clean any dirt or dust on the grille or panel by wipingit with a soft cloth soaked in lukewarm water (below40°C/104°F) and a neutral detergent solution.
2. Do not use gasoline, volatile substances or chemicalsto clean the indoor unit.
Period
At least onceevery 2 weeks.More frequently ifnecessary.
At least onceevery 2 weeks.More frequently ifnecessary.
AUTO RANDOM RE-START FUNCTION
If there is a power cut when the unit is operating, it will automatically resume the same operatingmode when the power is restored.
1. Open the front panel.• Hold the panel at the recesses on the main
unit (2 recesses on right and left sides) andlift it until it stops.
2. Remove the front panel.• While lifting the front panel further, slide
it to the right and pull it to the front side.The left rotating shaft is detached. Slide theright rotating shaft to the left and pull it tothe front side to remove it.
3. Attach the front panel.• Align the right and left rotating shafts of
the front panel with the grooves and pushthem all the way in.
• Gently close the front panel. (Push bothends and the center on the front panel.)
Rotating shaft
Recess onmain unit
! CAUTION• Don’t touch the metal parts of the indoor unit. It may cause an injury.• When removing or attaching the front panel, support the panel securely with hand to
prevent it from falling.• For cleansing, do not use hot water above 40°C, benzine, gasoline, thinner, nor other
volatile oils, polishing compound, scrubbing brushes, nor other hand stuff.• After cleaning, make sure that the front panel is securely fixed.
16
When The Unit Is Not To Be Used For An Extended Long Period Of Time
Operate the unit for2 hours with thefollowing setting.
Operating mode : coolTemperature : 30°C/86°F
Remove the power plug.If you are using anindependent electriccircuit for your unit,cut off the circuit.Remove the batteries inthe remote control.
If any malfunction of the air conditioner unit is noted, immediately switch off the powersupply to the unit. Check the following fault conditions and causes for some simpletroubleshooting tips.
Causes / Action
- Protection against frequent starting. Waitfor 3 to 4 minutes for the compressor tostart operating.
- Power failure, or the fuse need to bereplaced.
- The power plug is disconnected.- It is possible that your delay timer has
been set incorrectly.- If the fault persist after all these
verifications, please contact the airconditioner unit installer.
- The air filter is dirty.- The doors or windows are open.- The air suction and discharge are clogged.- The regulated temperature is not high
enough.
- Odours may be caused by cigarettes,smoke particles, perfume etc. which mighthave adhered onto the coil.
- This is caused by air humidity after anextended long period of operation.
- The set temperature is too low, increasethe temperature setting and operate theunit at high fan speed.
- Switch off unit and call dealer.
- Refrigerant fluid flowing into theevaporator coil.
Fault
1. The compressor does not operate3 minutes after the air conditioner unitis started.
2. The air conditioner unit does notoperate.
3. The air flow is too low.
4. Discharge air flow has bad odour.
5. Condensation on the front air grille ofthe indoor unit.
6. Water flowing out from the airconditioner unit.
7. Hissing air flow sound from the airconditioner unit during operation.
If the fault persists, please call your local dealer / serviceman.
TROUBLESHOOTING
OYL MANUFACTURING COMPANY SDN. BHD.
LOT 60334, PERSIARAN BUKIT RAHMAN PUTRA 3, TAMAN PERINDUSTRIAN RAHMAN PUTRA, 47000 SUNGAIBULOH, SELANGOR DARUL EHSAN, MALAYSIA.
• The manufacturer reserves the right to revise any of the specification and design contain herein at any time without priornotification.