Page 1: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

The A/C management system that offers powerful functions, yet still gives simple navigation for any user.

Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems.PCN0411B

The interface for connecting VRV to BACnet® or LONWORKS® protocols

DAIKIN is the first manufacturer (Vendor ID53: Nov 15, 1999) whose VRV System has been officially approved as BACnet® compatible equipment.Catalog information is as of July 2007.BACnet® is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).LONWORKS®, LON® and LonTalk® are registered tradmarks of Echelon Corporation.Ethernet is a registered trademark of Xerox Corporation.

DCS601C51Communication capabilities via a Web browser further expand air conditioning control possibilities.

Using interface

1. Onc e a month, adjus t the c loc k of the interfac e.

2. Daikin’ s unique P.P.D. s ys tem es timates the power c ons umption of eac h individual indoor unit bas ed on data c ommunic ated from indoor units and c ompared to the power c ons umption of an air c onditioning ins tallation with a s tandard s etup. Note that P.P.D. is not a “ gauge” adapted to the

methods of meas uring power c ons umption in eac h c ountry. All c ountries differ in the ways tenant billing s ys tems are implemented depending on their res pec tive legal s ys tems . Data obtained by P.P.D. is for referenc e only and s hould not be us ed for offic ial financ ial trans ac tions .

3. J MT (J oint Matc hing Tes t) is normally required before projec t exec ution.

DAM602B51 B52

E v o l u t i o n

* RoHS DirectiveThe RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

All rights reservedPrinted in Japan 07/07/003 AD.HP.SWc

DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan

Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/

Specifications, designs and other content appearing in this brochure are current as of July 2007 but subject to change without notice.

ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.

About ISO 14001

ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at the plant.

About ISO 9001

JMI-0107 JQA-1452

Page 2: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

Connect VRV to your BMS via BACnet® or LONWORKS®-

using Daikin's integrated control system solutions.Typical BACnet® application

Dedicated interfaces make Daikin air conditionersfreely compatible with open networks

Local C ontroller

OutdoorUnit

Daikin's A/C infras truc ture

B MS

BuildingControlNetwork

IndoorUnit

R emote C ontroller

HR V

DMS502B51

BA

Cn

et® /E

the

rne

t

( Interfac e for us e in B AC net® )

S ecurityFire AlarmP ower S upplyFacility

E levator P ump Lighting, etc

Typical LONWORKS® application

Local C ontroller

OutdoorUnit

Daikin's A/C infras truc ture

B MS

IndoorUnit

R emote C ontroller

HR V

C ompatible with B AC net® and L ONW OR K S

®, the two leading open network c omunic ation protoc ols ,

the interfac es offered by Daikin provide a s eamles s c onnec tion between VR V and your B MS .

Air conditioning control systems can be realized with little equipment and lower costs.

Simple, direct connections make setup quick and easy.

Dedicated interfaces enhance VRV control.

Providing flexible control and monitoring capabilitythat features linked operation with other systems.

Units can be added freely and easily to expand the number of control points.

Other systems such as those for fire and crime prevention can be easily interlocked with Daikin's unit.

Air conditioning control systems can be realised with little equipment and lower costs.

Simple, direct connections make setup quick and easy.

Dedicated interfaces enhance VRV control.

Providing flexible control and monitoring capabilitythat features linked operation with other systems.

Units can be added freely and easily to expand the number of control points.

Other systems such as those for fire and crime prevention can be easily interlocked with Daikin's unit.

RLonTalk

Eth

ern

et

(TC

/IP

)

LonP oint LonP ointS ecurityS ystem

Fire Alarm S ystem

RLonTalk

1 2

Daikin air conditioning and control systemshelp you set up an open network.

Daikin air conditioning and control systemshelp you set up an open network.

Open network

S ecurity

Fire Alarm P ower S upplyFacility

D-B AC SInterfac e Unit

E levator P ump Lighting, etc

BACnet® BACnet® LONWORKS®LONWORKS®

Open network

BuildingControlNetwork

DMS504B51

B MS

P C

( Interfac e for us e in L ONW OR K S ® )

Page 3: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

Connect VRV to your BMS via BACnet® or LONWORKS®-

using Daikin's integrated control system solutions.Typical BACnet® application

Dedicated interfaces make Daikin air conditionersfreely compatible with open networks

Local C ontroller

OutdoorUnit

Daikin's A/C infras truc ture

B MS

BuildingControlNetwork

IndoorUnit

R emote C ontroller

HR V

DMS502B51

BA

Cn

et® /E

the

rne

t

( Interfac e for us e in B AC net® )

S ecurityFire AlarmP ower S upplyFacility

E levator P ump Lighting, etc

Typical LONWORKS® application

Local C ontroller

OutdoorUnit

Daikin's A/C infras truc ture

B MS

IndoorUnit

R emote C ontroller

HR V

C ompatible with B AC net® and L ONW OR K S

®, the two leading open network c omunic ation protoc ols ,

the interfac es offered by Daikin provide a s eamles s c onnec tion between VR V and your B MS .

Air conditioning control systems can be realized with little equipment and lower costs.

Simple, direct connections make setup quick and easy.

Dedicated interfaces enhance VRV control.

Providing flexible control and monitoring capabilitythat features linked operation with other systems.

Units can be added freely and easily to expand the number of control points.

Other systems such as those for fire and crime prevention can be easily interlocked with Daikin's unit.

Air conditioning control systems can be realised with little equipment and lower costs.

Simple, direct connections make setup quick and easy.

Dedicated interfaces enhance VRV control.

Providing flexible control and monitoring capabilitythat features linked operation with other systems.

Units can be added freely and easily to expand the number of control points.

Other systems such as those for fire and crime prevention can be easily interlocked with Daikin's unit.

RLonTalk

Eth

ern

et

(TC

/IP

)

LonP oint LonP ointS ecurityS ystem

Fire Alarm S ystem

RLonTalk

1 2

Daikin air conditioning and control systemshelp you set up an open network.

Daikin air conditioning and control systemshelp you set up an open network.

Open network

S ecurity

Fire Alarm P ower S upplyFacility

D-B AC SInterfac e Unit

E levator P ump Lighting, etc

BACnet® BACnet® LONWORKS®LONWORKS®

Open network

BuildingControlNetwork

DMS504B51

B MS

P C

( Interfac e for us e in L ONW OR K S ® )

Page 4: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

Monitors ON/OFF s tatus of the res pective air conditioners .

Monitors whether air conditioners are operating normally and, if not, s ends out an alarm s ign.

Dis plays error code s pecified by the res pective manufacturer if an abnormality occurs in the s ys tem.

Monitors s tatus of cooling, heating and ventilation operation.

Monitors room temperature and dis plays the actual room temperature.

C hecks the limit of filters in us e and monitors if there is a neces s ity to replace the filters .

Monitors whether the thermos tat in the air conditioner is operating properly.

Monitors whether compres s ors in outdoor units that are connected to the indoor units are operating

properly.

Monitors whether fans in the air conditioners are operating properly.

Monitors whether heaters in the air conditioners are operating properly.

Total electric power (number of indoor units ) as an object of accumulator.

S tarts and s tops the res pective air conditioners and monitors control res ults .

S ets the operation mode (cooling, heating, ventilation or auto mode) and monitors the s etting res ults .

S ets room temperatures of the res pective air conditioners and monitors the s etting res ults .

C hecks whether there is a us e limit for the res pective filters and then res ets the s ign as neces s ary.

S ets the permis s ion/rejection function of remote controllers in order not to allow operation control, s uch

as ON/OFF, operation mode and room temperature, from the remote controllers .

S ets the control permis s ion/rejection function of centralis ed devices (i.e. , air conditioners in a s ub group

addres s ) connected on the D -NET.

S ets the airflow rate and monitors the s etting res ults .

S ets the air direction and monitors the s etting res ults .

ON/OFF Status

Alarm Sign

Error Code

Operation Mode

Room Temperature

Filter Limit

Thermostat Status

Compressor Status

Indoor Fan Status

Heater Operation Status

PPD data

ON/OFF Operation

Operation Mode Setting

Room Temperature Setting

Filter Limit and Reset

Remote Control Operation Rejection

Sub Group Address Control Operation Rejection

Airflow Rate Setting Operation

Air Direction Setting Operation

System Forced OFF Setting Rejection

Forced Thermostat OFF Setting

Energy Efficiency Setting

Function Description

Mo

nito

rin

gO

per

atio

n,

Set

ting

an

d

Mo

nito

rin

g

Seamless connection between and BACnet® open network protocol.

DMS502B51

C onformance C lass - 3 Data Link Layer Option - B AC net/IP

Analog Input Analog Value B inary Input B inary Output

B inary Value M ultis tate Input M ultis tate OutputM onitor C ommand Alarm

FunctionalityObjects

Hardware model name

Max. number indoor units

Max. number outdoor units

B MS

DMS502B51

128

20

DMS502B51+DAM411B51 (Optional D expansion kit)

256 per gateway

40 per gateway

Local P rocurement

R ated power s upply

R ated power c ons umption

P ower s upply fluc tuation

Operable temperature range

S torage temperature range

Operable ambient humidity

Ins ulation res is tanc e

Ins tallation

Dimens ions (W x H x D)

Weight

Model name

Item

Transmiss ion

Des c ription

DMS 502B 51(Interfac e for us e in B AC net® )

B AC net®/IP

C onformanc e C las s 3 (AS HR AE 135- 1995)

B - AS C (AS HR AE 135- 2001)

S ingle phas e AC 100 to 240 ±10% at 50/60 Hz

Maximum 20 W

±10% of the rated value

– 10°C to 50°C

– 15°C to 60°C

0 to 98% (No c ondens ation)

50 MΩ or more by DC 500 megohmmeter

E nc los ed in elec tric al panel

275 x 263 x 81.5 (mm)

3.0 kg

Optional D expans ion kit

Item

DIII B oard

Model name

D L ines

DAM411B51

2

Digita l input port

Imbedded in DMS 502B 51

Optional board(DAM412B 51) is required.

Di (Forced off)

Di(kwh meter connection for P P D)

4

12

DMS502B51 SpecificationDaikin's interface unit for B AC net® communicates with B AC net® c lients via B AC net® over an ethernet.

This unit provides information for VR V through B AC net® s ervices .

The items to monitor and control air conditioners from B AC net® communication and des criptions of each item are lis ted below.

Specifications of Communication

Monitoring and control of A/C

Series and components

Specifications

Functions of operating system version 3.0 (Providing interface from BACnet® to VRV.)

COV(Change of value)With the new O.S . a change of object can be automatically read by

the B MS without having to cons tantly s can regularly for any change.

Property array index (Reading of objects)

This is used for objects such as the S chedule Object that use the Property

Array included in the device object. The reason why this is sometimes re-

quired is so that registration of objects can be done automatically and man-

ual input is not necessary.

The "Object_List" of the device can be read automatically with this index,

there by reducing engineering time of programming the indoor units into the Segmented requestsThis function trans mits two or more packets s eparately, when the

amount of data exceeds one packet s ize.

If there are a large number of indoor units the res pons e is in the

"read property reques t" and the return data are s egmented.

ISO 16484-5S upports B AC net/IP in accordance with IS O16484-5 (B uilding automa-

tion and control s ys tems . Data communication protocol) for B AC net.

Note: Does not s upport IEEE802.3 protocol for B AC net.

Product description

To achieve a s eamles s connection between both the B MS and Daikin's B AC net interfaces , it is crucial that you contact us prior to any project cons ideration.For a detailed lis t of B MS and compatibility s pecifications pleas e contact your local dis tributor.

Note:

3 4

Typical BACnet® application

Local C ontroller

OutdoorUnit

Maximum of 10 outdoor units

Maximum of 64 groups

Daikin's A/C infras truc ture

B MS

BuildingControlNetwork

IndoorUnit

R emote C ontroller

HR V

DMS502B51

BA

Cn

et® /E

the

rne

t

F ire alarm S ecurity P ower S upply Facility E levator P ump Lighting, etc

BACnet® is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

RoHS compliantW e have been making efforts to fac ilitate the trans ition to R oHS

Direc tive c omplianc e.

PPD dataVR V PPD (power proportional dis tribution) data can be trans mitted by

B AC net communication for the B MS s ys tem.

*Optional Di board (DAM412B 51) is required for the PPD s ys tem.

BTL CertificationHigh reliability product with B TL certification, the s ymbol of high quality.

*B TL(B AC net Tes ting Laboratory) was es tablis hed by B AC net International to s upport

compliance tes ting and interoperability tes ting activities .

*R efer to the back cover for details of the R oHS Directive.

NE W

Page 5: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

Monitors ON/OFF s tatus of the res pective air conditioners .

Monitors whether air conditioners are operating normally and, if not, s ends out an alarm s ign.

Dis plays error code s pecified by the res pective manufacturer if an abnormality occurs in the s ys tem.

Monitors s tatus of cooling, heating and ventilation operation.

Monitors room temperature and dis plays the actual room temperature.

C hecks the limit of filters in us e and monitors if there is a neces s ity to replace the filters .

Monitors whether the thermos tat in the air conditioner is operating properly.

Monitors whether compres s ors in outdoor units that are connected to the indoor units are operating

properly.

Monitors whether fans in the air conditioners are operating properly.

Monitors whether heaters in the air conditioners are operating properly.

Total electric power (number of indoor units ) as an object of accumulator.

S tarts and s tops the res pective air conditioners and monitors control res ults .

S ets the operation mode (cooling, heating, ventilation or auto mode) and monitors the s etting res ults .

S ets room temperatures of the res pective air conditioners and monitors the s etting res ults .

C hecks whether there is a us e limit for the res pective filters and then res ets the s ign as neces s ary.

S ets the permis s ion/rejection function of remote controllers in order not to allow operation control, s uch

as ON/OFF, operation mode and room temperature, from the remote controllers .

S ets the control permis s ion/rejection function of centralis ed devices (i.e. , air conditioners in a s ub group

addres s ) connected on the D -NET.

S ets the airflow rate and monitors the s etting res ults .

S ets the air direction and monitors the s etting res ults .

ON/OFF Status

Alarm Sign

Error Code

Operation Mode

Room Temperature

Filter Limit

Thermostat Status

Compressor Status

Indoor Fan Status

Heater Operation Status

PPD data

ON/OFF Operation

Operation Mode Setting

Room Temperature Setting

Filter Limit and Reset

Remote Control Operation Rejection

Sub Group Address Control Operation Rejection

Airflow Rate Setting Operation

Air Direction Setting Operation

System Forced OFF Setting Rejection

Forced Thermostat OFF Setting

Energy Efficiency Setting

Function Description

Mo

nito

rin

gO

per

atio

n,

Set

ting

an

d

Mo

nito

rin

g

Seamless connection between and BACnet® open network protocol.

DMS502B51

C onformance C lass - 3 Data Link Layer Option - B AC net/IP

Analog Input Analog Value B inary Input B inary Output

B inary Value M ultis tate Input M ultis tate OutputM onitor C ommand Alarm

FunctionalityObjects

Hardware model name

Max. number indoor units

Max. number outdoor units

B MS

DMS502B51

128

20

DMS502B51+DAM411B51 (Optional D expansion kit)

256 per gateway

40 per gateway

Local P rocurement

R ated power s upply

R ated power c ons umption

P ower s upply fluc tuation

Operable temperature range

S torage temperature range

Operable ambient humidity

Ins ulation res is tanc e

Ins tallation

Dimens ions (W x H x D)

Weight

Model name

Item

Transmiss ion

Des c ription

DMS 502B 51(Interfac e for us e in B AC net® )

B AC net®/IP

C onformanc e C las s 3 (AS HR AE 135- 1995)

B - AS C (AS HR AE 135- 2001)

S ingle phas e AC 100 to 240 ±10% at 50/60 Hz

Maximum 20 W

±10% of the rated value

– 10°C to 50°C

– 15°C to 60°C

0 to 98% (No c ondens ation)

50 MΩ or more by DC 500 megohmmeter

E nc los ed in elec tric al panel

275 x 263 x 81.5 (mm)

3.0 kg

Optional D expans ion kit

Item

DIII B oard

Model name

D L ines

DAM411B51

2

Digita l input port

Imbedded in DMS 502B 51

Optional board(DAM412B 51) is required.

Di (Forced off)

Di(kwh meter connection for P P D)

4

12

DMS502B51 SpecificationDaikin's interface unit for B AC net® communicates with B AC net® c lients via B AC net® over an ethernet.

This unit provides information for VR V through B AC net® s ervices .

The items to monitor and control air conditioners from B AC net® communication and des criptions of each item are lis ted below.

Specifications of Communication

Monitoring and control of A/C

Series and components

Specifications

Functions of operating system version 3.0 (Providing interface from BACnet® to VRV.)

COV(Change of value)With the new O.S . a change of object can be automatically read by

the B MS without having to cons tantly s can regularly for any change.

Property array index (Reading of objects)

This is used for objects such as the S chedule Object that use the Property

Array included in the device object. The reason why this is sometimes re-

quired is so that registration of objects can be done automatically and man-

ual input is not necessary.

The "Object_List" of the device can be read automatically with this index,

there by reducing engineering time of programming the indoor units into the Segmented requestsThis function trans mits two or more packets s eparately, when the

amount of data exceeds one packet s ize.

If there are a large number of indoor units the res pons e is in the

"read property reques t" and the return data are s egmented.

ISO 16484-5S upports B AC net/IP in accordance with IS O16484-5 (B uilding automa-

tion and control s ys tems . Data communication protocol) for B AC net.

Note: Does not s upport IEEE802.3 protocol for B AC net.

Product description

To achieve a s eamles s connection between both the B MS and Daikin's B AC net interfaces , it is crucial that you contact us prior to any project cons ideration.For a detailed lis t of B MS and compatibility s pecifications pleas e contact your local dis tributor.

Note:

3 4

Typical BACnet® application

Local C ontroller

OutdoorUnit

Maximum of 10 outdoor units

Maximum of 64 groups

Daikin's A/C infras truc ture

B MS

BuildingControlNetwork

IndoorUnit

R emote C ontroller

HR V

DMS502B51

BA

Cn

et® /E

the

rne

t

F ire alarm S ecurity P ower S upply Facility E levator P ump Lighting, etc

BACnet® is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

RoHS compliantW e have been making efforts to fac ilitate the trans ition to R oHS

Direc tive c omplianc e.

PPD dataVR V PPD (power proportional dis tribution) data can be trans mitted by

B AC net communication for the B MS s ys tem.

*Optional Di board (DAM412B 51) is required for the PPD s ys tem.

BTL CertificationHigh reliability product with B TL certification, the s ymbol of high quality.

*B TL(B AC net Tes ting Laboratory) was es tablis hed by B AC net International to s upport

compliance tes ting and interoperability tes ting activities .

*R efer to the back cover for details of the R oHS Directive.

NE W

Page 6: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

Remote Control Operation Mode Setting Rejection Report

Remote Control Temperature Setting Operation Rejection Report

System Forced OFF Setting Report

Sub Group Address Control Operation Rejection Setting Report

A/C Communication Status Report

Monitor items

Network parameter chart

This product features objects for a group of 64 indoor units. As shown below, the object name and the last "nn" in the "nv Name" correspond with the DIII-NET location

Indoor Unit Location S etting Address A/C Object nv Name (E xample)

1-00 - 1-15 AC_01 - AC_16 nviOnOff_01 - nviOnOff_16

2-00 - 2-15 AC_17 - AC_32 nviOnOff_17 - nviOnOff_32

3-00 - 3-15 AC_33 - AC_48 nviOnOff_33 - nviOnOff_48

4-00 - 4-15 AC_49 - AC_64 NviOnOff_49 - nviOnOff_64

G E NE R AL (objec t id = 65)

nviSystemOffSNVT_switch

nvoSystemOffSNVT_switch

nviRejLCSNVT_switch

nvoRejLCSNVT_switch

Configuration Propertiesnc49 Send Heartbeat nc52 Minimum Send Time nc64 Send on Delta Temperaturenc111 Delay Start Up nc20 Range Maximum

AC _nn (objec t id = 1- 64)

nviOnOff_nnSNVT_switch

nviHeatCool_nnSNVT_hvac_mode

nviSetpoint_nnSNVT_temp_p

nviFanSpeed_nnSNVT_switch

nviFSReset_nnSNVT_switch

nviRejOnOff_nnSNVT_switch

nviRejMode_nnSNVT_switch

nviRejSetpoint_nnSNVT_switch

nviThermoOff_nnSNVT_switch

nvoOnOff_nnSNVT_switch

nvoHeatCool_nnSNVT_hvac_mode

nvoSetpoint_nnSNVT_temp_p

nvoSpaceTemp_nnSNVT_temp_p

nvoFanSpeed_nnSNVT_switch

nvoFiltersign_nnSNVT_switch

nvoFailure_nnSNVT_switch

nvoErrStatus_nnSNVT_count

nvoThermo_nnSNVT_switch

nvoRejOnOff_nnSNVT_switch

nvoRejMode_nnSNVT_switch

nvoRejSetpoint_nnSNVT_switch

nvoHvacExist_nnSNVT_switch

nvoThermoOff_nnSNVT_switch

Each item controlled or monitored by the control and monitoring function is s ubject to a variety of res trictions that are not des cribed here due to s pace limitations . For details , contact your DAIKIN dis tributor.

ON/OFF Command

Operation Mode Setting

Temperature Setting

Airflow Rate Setting

Filter Sign Reset

Forced Thermostat OFF Setting

Remote ON/OFF Control Rejection

Remote Operation Mode Control Rejection

Remote Temperature Setting Control Rejection

System Forced OFF Setting

Sub Group Address Control Rejection Setting

C ontrol items

ON/OFF Status Report

Operation Mode Status Report

Temperature Setting Report

Room Temperature Report

Airflow Rate Setting Report

Filter Sign Report

Error Status Report

Error Code Report

Thermostat Status Report

Forced Thermostat OFF Setting Status Report

Remote ON/OFF Operation Rejection Report

Product description

P rotocol: LonTalk®

Transmiss ion speed: 78 kbpsTopology: Free topologyTransmiss ion medium: Twist pair

DMS504B51 Specification

Network parametersIn parameter names, 'nn' refers to air-conditioning unit numbers 01

to 64. For 'NV' with 'nn' attached, a total of 64 NV has been pre-

pared (one for each object).

Control and monitor fauction

Specifications

Des c ription

DMS 504B 51 (Interfac e for us e in LONWOR K S® )

LONWOR K S®

F T- X1 (F ree topology 78 kbps )

S ingle phas e AC 100 to 240 V 50/60 Hz

Maximum 5 W

Us e no voltage c ontac t ( F orc ed off ) minimum applic ation load DC 16 V and 10 mA

- 10 to +50°C

- 20 to +60°C

0 to 95% ( No c ondens ation )

50 MΩ or more by DC 500 megohmmeter

E nc los ed in elec tric al panel

168 x 260 x 50 (mm)

1.5 kg

Item

Model name

Transmiss ion

R ated power s upply

R ated power c ons umption

C ontac t input

Operable temperature range

S torage temperature range

Operable ambient humidity

Ins ulation res is tanc e

Ins tallation

Dimens ions (W x H x D)

Weight

Air C onditioner Objec ts

Facilitating the network integration of and LONWORKS

®

DMS504B51

5 6

Typical LONWORKS® application

OutdoorUnit

Maximum of 10 outdoor units

Maximum of 64 groups

Daikin's A/C infras truc ture

Local C ontroller

B MS

BuildingControlNetwork

IndoorUnit

R emote C ontroller

HR V

DMS504B51

Eth

ern

et

(TC

P/I

P)

LonTalk®

LonTalk®

LonP oint LonP ointS ecurityS ystem

Fire Alarm S ystem

Open network integrationA gateway for connection to LONWOR KS

® network equipment

and building control s ys tem. LONWOR KS

® networks are recognis ed worldwide as the de fac-

to s tandard in the building control indus try. S ys tems are available for acces s control, energy manage-ment, fire/life, HVAC , lighting, and more.

Reduction in engineering and cost of wiringThe open protocol s pecification gives local s ys tem integrators complete des ign freedom. Plus , the ability to combine individual items of equipment into a LONWOR KS

® network reduces the engineering time and cos ts

required for wiring.

Connectable to up to 64 groupsThis unit can be connected to up to 64 groups . (This figure depends on the number of control and monitoring functions us ed.) Pleas e cons ult your Daikin repres entative for details .

RoHS-compliant hardware

LONWORKS®, LON® and LonTalk® are registered tradmarks of Echelon Corporation.

We have been making efforts to facilitate the trans ition to R oHS Directive compliance.

*R efer to the back cover for details of the R oHS Directive.

D - NE T C ommon Objec ts

Page 7: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

Remote Control Operation Mode Setting Rejection Report

Remote Control Temperature Setting Operation Rejection Report

System Forced OFF Setting Report

Sub Group Address Control Operation Rejection Setting Report

A/C Communication Status Report

Monitor items

Network parameter chart

This product features objects for a group of 64 indoor units. As shown below, the object name and the last "nn" in the "nv Name" correspond with the DIII-NET location

Indoor Unit Location S etting Address A/C Object nv Name (E xample)

1-00 - 1-15 AC_01 - AC_16 nviOnOff_01 - nviOnOff_16

2-00 - 2-15 AC_17 - AC_32 nviOnOff_17 - nviOnOff_32

3-00 - 3-15 AC_33 - AC_48 nviOnOff_33 - nviOnOff_48

4-00 - 4-15 AC_49 - AC_64 NviOnOff_49 - nviOnOff_64

G E NE R AL (objec t id = 65)

nviSystemOffSNVT_switch

nvoSystemOffSNVT_switch

nviRejLCSNVT_switch

nvoRejLCSNVT_switch

Configuration Propertiesnc49 Send Heartbeat nc52 Minimum Send Time nc64 Send on Delta Temperaturenc111 Delay Start Up nc20 Range Maximum

AC _nn (objec t id = 1- 64)

nviOnOff_nnSNVT_switch

nviHeatCool_nnSNVT_hvac_mode

nviSetpoint_nnSNVT_temp_p

nviFanSpeed_nnSNVT_switch

nviFSReset_nnSNVT_switch

nviRejOnOff_nnSNVT_switch

nviRejMode_nnSNVT_switch

nviRejSetpoint_nnSNVT_switch

nviThermoOff_nnSNVT_switch

nvoOnOff_nnSNVT_switch

nvoHeatCool_nnSNVT_hvac_mode

nvoSetpoint_nnSNVT_temp_p

nvoSpaceTemp_nnSNVT_temp_p

nvoFanSpeed_nnSNVT_switch

nvoFiltersign_nnSNVT_switch

nvoFailure_nnSNVT_switch

nvoErrStatus_nnSNVT_count

nvoThermo_nnSNVT_switch

nvoRejOnOff_nnSNVT_switch

nvoRejMode_nnSNVT_switch

nvoRejSetpoint_nnSNVT_switch

nvoHvacExist_nnSNVT_switch

nvoThermoOff_nnSNVT_switch

Each item controlled or monitored by the control and monitoring function is s ubject to a variety of res trictions that are not des cribed here due to s pace limitations . For details , contact your DAIKIN dis tributor.

ON/OFF Command

Operation Mode Setting

Temperature Setting

Airflow Rate Setting

Filter Sign Reset

Forced Thermostat OFF Setting

Remote ON/OFF Control Rejection

Remote Operation Mode Control Rejection

Remote Temperature Setting Control Rejection

System Forced OFF Setting

Sub Group Address Control Rejection Setting

C ontrol items

ON/OFF Status Report

Operation Mode Status Report

Temperature Setting Report

Room Temperature Report

Airflow Rate Setting Report

Filter Sign Report

Error Status Report

Error Code Report

Thermostat Status Report

Forced Thermostat OFF Setting Status Report

Remote ON/OFF Operation Rejection Report

Product description

P rotocol: LonTalk®

Transmiss ion speed: 78 kbpsTopology: Free topologyTransmiss ion medium: Twist pair

DMS504B51 Specification

Network parametersIn parameter names, 'nn' refers to air-conditioning unit numbers 01

to 64. For 'NV' with 'nn' attached, a total of 64 NV has been pre-

pared (one for each object).

Control and monitor fauction

Specifications

Des c ription

DMS 504B 51 (Interfac e for us e in LONWOR K S® )

LONWOR K S®

F T- X1 (F ree topology 78 kbps )

S ingle phas e AC 100 to 240 V 50/60 Hz

Maximum 5 W

Us e no voltage c ontac t ( F orc ed off ) minimum applic ation load DC 16 V and 10 mA

- 10 to +50°C

- 20 to +60°C

0 to 95% ( No c ondens ation )

50 MΩ or more by DC 500 megohmmeter

E nc los ed in elec tric al panel

168 x 260 x 50 (mm)

1.5 kg

Item

Model name

Transmiss ion

R ated power s upply

R ated power c ons umption

C ontac t input

Operable temperature range

S torage temperature range

Operable ambient humidity

Ins ulation res is tanc e

Ins tallation

Dimens ions (W x H x D)

Weight

Air C onditioner Objec ts

Facilitating the network integration of and LONWORKS

®

DMS504B51

5 6

Typical LONWORKS® application

OutdoorUnit

Maximum of 10 outdoor units

Maximum of 64 groups

Daikin's A/C infras truc ture

Local C ontroller

B MS

BuildingControlNetwork

IndoorUnit

R emote C ontroller

HR V

DMS504B51

Eth

ern

et

(TC

P/I

P)

LonTalk®

LonTalk®

LonP oint LonP ointS ecurityS ystem

Fire Alarm S ystem

Open network integrationA gateway for connection to LONWOR KS

® network equipment

and building control s ys tem. LONWOR KS

® networks are recognis ed worldwide as the de fac-

to s tandard in the building control indus try. S ys tems are available for acces s control, energy manage-ment, fire/life, HVAC , lighting, and more.

Reduction in engineering and cost of wiringThe open protocol s pecification gives local s ys tem integrators complete des ign freedom. Plus , the ability to combine individual items of equipment into a LONWOR KS

® network reduces the engineering time and cos ts

required for wiring.

Connectable to up to 64 groupsThis unit can be connected to up to 64 groups . (This figure depends on the number of control and monitoring functions us ed.) Pleas e cons ult your Daikin repres entative for details .

RoHS-compliant hardware

LONWORKS®, LON® and LonTalk® are registered tradmarks of Echelon Corporation.

We have been making efforts to facilitate the trans ition to R oHS Directive compliance.

*R efer to the back cover for details of the R oHS Directive.

D - NE T C ommon Objec ts

Page 8: PCN0411B - Daikin · Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems. PCN0411B ... Monitoring and control of A/C Series

The A/C management system that offers powerful functions, yet still gives simple navigation for any user.

Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems.PCN0411B

The interface for connecting VRV to BACnet® or LONWORKS® protocols

DAIKIN is the first manufacturer (Vendor ID53: Nov 15, 1999) whose VRV System has been officially approved as BACnet® compatible equipment.Catalog information is as of July 2007.BACnet® is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).LONWORKS®, LON® and LonTalk® are registered tradmarks of Echelon Corporation.Ethernet is a registered trademark of Xerox Corporation.

DCS601C51Communication capabilities via a Web browser further expand air conditioning control possibilities.

Using interface

1. Onc e a month, adjus t the c loc k of the interfac e.

2. Daikin’ s unique P.P.D. s ys tem es timates the power c ons umption of eac h individual indoor unit bas ed on data c ommunic ated from indoor units and c ompared to the power c ons umption of an air c onditioning ins tallation with a s tandard s etup. Note that P.P.D. is not a “ gauge” adapted to the

methods of meas uring power c ons umption in eac h c ountry. All c ountries differ in the ways tenant billing s ys tems are implemented depending on their res pec tive legal s ys tems . Data obtained by P.P.D. is for referenc e only and s hould not be us ed for offic ial financ ial trans ac tions .

3. J MT (J oint Matc hing Tes t) is normally required before projec t exec ution.

DAM602B51 B52

E v o l u t i o n

* RoHS DirectiveThe RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

All rights reservedPrinted in Japan 07/07/003 AD.HP.SWc

DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan

Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/

Specifications, designs and other content appearing in this brochure are current as of July 2007 but subject to change without notice.

ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.

About ISO 14001

ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at the plant.

About ISO 9001

JMI-0107 JQA-1452