passive house design (pedro rico lópez)
DESCRIPTION
Project of Passive House in DenmarkTRANSCRIPT
PASSIVE HOUSE
Group: 19
Miguel SalgadoPedro RicoAdam Marko
1. INTRODUCTION LOCATION
Galgehøj, 8700 Horsens Plot 33
2. DESIGN A/V FACTOR
NUMBER OF FLOORS 2
A (GROSS FLOOR AREA) 154m2
A (BUILDING ENVELOPE) 420m2
V (GROSS ENVELOPE) 539m3
A/V 0,78m2/m3
2. DESIGN AREAS
Ground floor
2. DESIGN AREAS
1st floor
2. DESIGN DIMENSIONS
Ground floor
2. DESIGN DIMENSIONS
1st floor
2. DESIGN U-VALUES
Assembly No. Building assembly description Interior insulation?
1 External Wall
Heat transfer resistance [m²K/W] interior Rsi : 0,13exterior Rse : 0,04
Area section 1l [W/(mK)] Area section 2 (optional)
l [W/(mK)] Area section 3 (optional)l [W/(mK)] Thickness [mm]
1. Brick 0,600 108
2. Insulation 0,032 350
3. Finish layer 0,250 10
4.
5.
6.
7.
8.Percentage of Sec. 2 Percentage of Sec. 3 Total
46,8 cm
U-Value: 0,088 W/(m²K)
2. DESIGN U-VALUES
Assembly No. Building assembly description Interior insulation?
2 Roof
Heat transfer resistance [m²K/W] interior Rsi : 0,26
exterior Rse : 0,04
Area section 1 l [W/(mK)] Area section 2 (optional) l [W/(mK)] Area section 3 (optional) l [W/(mK)] Thickness [mm]
1. Tile 1,000 20
2. Mortar 0,100 100
3. Insulation 0,034 400
4. Mortar 0,100 50
5. Concrete 1,600 200
6.
7.
8.Percentage of Sec. 2 Percentage of Sec. 3 Total
77,0 cm
U-Value: 0,073 W/(m²K)
2. DESIGN U-VALUES
Assembly No. Building assembly description Interior insulation?
3 Ground Floor supporter floor
Heat transfer resistance [m²K/W] interior Rsi : 0,17
exterior Rse: 0,00
Area section 1l [W/(mK)] Area section 2 (optional)
l [W/(mK)] Area section 3 (optional)l [W/(mK)] Thickness [mm]
1. Parquet 0,200 20
2. concrete 1,600 100
3. Hard insulation 0,037 350
4. Light clincker 0,085 250
5. Light clincker 0,102 75
6.
7.
8.Percentage of Sec. 2 Percentage of Sec. 3 Total
79,5 cm
U-Value: 0,074 W/(m²K)
2. DESIGN ORIENTATION AND WINDOWS
WINDOWS
NORTH 9,5%
EAST 22,1%
SOUTH 44,9%
WEST 23,5%
2. DESIGN ORIENTATION AND WINDOWS
Glazing.
Frame
2. DESIGN SHADINGS
2. DESIGN ELEVATIONS (SOUTH)
2. DESIGN ELEVATIONS (EAST)
2. DESIGN ELEVATIONS (WEST)
2. DESIGN ELEVATIONS (NORTH)
2. DESIGN SECTIONS (A-A’)
A’
A
B’B
2. DESIGN SECTIONS (B-B’)
A’
A
B’B
2. DESIGN DETAILS
Wall-Window
2. DESIGN DETAILS
Roof-Wall
Air thingt layer
3. INSTALATIONS VENTILATION
Passive House Standard
Supply air:30m3/h/person * 4 person = 120m3/h
Extract air:
1 Kitchen: 60 m3/h3 Bathrooms: 40 m3/h * 3 = 120 m3/h2 Storage room: 40 m3/h
Total= 220 m3/h
Minimun ari change of 0,3/h:
0,3/h*144 m2*2,5= 108 m3/h
3. INSTALATIONS VENTILATION
INNOAIR 300 DC (max. 300 m³/h bei 100 Pa.)
3. INSTALATIONS VENTILATION (SUPPLY)
Room No qbasic
(l/s)qbasic
(m3/s)Ʃq dimensioning
(m3/s)Type (M, B, C)
Velocity(m/s)
Duct dimension (calculated) (m)
Final duct dimension (mm)
Living room
12,5 0,0125 0,0125 C 2,5 75 75
Dinnigroom
12,5 0,0125 0,0125 C 2,5 75 75
Branch1
25 0,0250 0,0250 B 3,5 90 90
Room 1 11,2 0,0112 0,0112 C 2,5 75 75
Room2
11,2 0,0112 0,0112 C 2,5 75 75
Branch2
22,4 0,024 0,024 B 3,5 100 100
Room3
17 0,017 0,017 C 2,5 100 100
Branch3
39,4 0,0394 0,0394 B 3,5 125 125
Main 64,4 0,0644 0,0644 M 4 150 150
3. INSTALATIONS VENTILATION (EXTRACTION)
Room No qbasic
(l/s)qbasic
(m3/s)Ʃq dimensioning
(m3/s)Type (M, B, C)
Velocity(m/s)
Duct dimension (calculated) (m)
Final duct dimension (mm)
Kitchen 20 0,020 0,020 C 2,5 90 90
Bathroom1
15 0,015 0,015 C 2,5 75 75
Branch1
35 0,0350 0,0350 B 3,5 110 110
Storage1
10 0,01 0,01 C 2,5 75 75
Brach2
45 0,045 0,045 B 3,5 125 125
Bathroom2
15 0,015 0,015 C 2,5 75 75
Storage2
10 0,01 0,01 C 2,5 75 75
Bathroom3
15 0,015 0,015 C 2,5 75 75
Brach3
40 0,04 0,04 B 3,5 125 125
Main 85 0,085 0,085 M 4 175 175
3. INSTALATIONS VENTILATION (PLANS)
Ground floor
Suppy
Extract
3. INSTALATIONS VENTILATION (PLANS)
1st floor
Suppy
Extract
3. INSTALATIONS VENTILATION
Suppy
Extract
3. INSTALATIONS DOMESTIC HOT WATER
Ground floor
3. INSTALATIONS DOMESTIC HOT WATER
1st floor
3. INSTALATIONS DOMESTIC HOT WATER
4. CONCLUSIONS VERIFICATION
THATS ALL!!THANKS!!