© Horizon Power Corporation Part 2 – Reference – Drawing Register Number Description R1 Pole Bolt Details R2-1 Bonding, Intermediate R2-2 Running disc angle 11, 22 and 33 kV – 3 Phase Superposition R3-1 Insulators R3-2 Insulator Ties R3-3 Armour Rods R4 Insulator Pin and Bolt Details R5-1 Eyebolt Details R5-2 Eyebolt, Conductor Terminations R6 Earthing R7-1 Cable cleat – Guard and Pole Top Switch – Anti Climbing Guard Detail R7-2 Service Cable Cleat, Guard Fixing Details R8-1 ABC Taps for Transformer, and Cable Termination R8-2 Lugs and Connectors, Transformer and Cable R8-3 PG Clamps Installation Instruction R8-4 Lugs and Connectors, Insulation Piercing Clamps R10-1 Dropout Fuse Mounting, Details R10-2 Dropout Fuse Mounting, Boric Acid and Fault Tamer Details R11 Flowline Fuse Mounting and Service Termination R11-1 LV Supply to Pole-Mounted Equipment R12-1 Transformer LV, Isolation Details R12-2 Transformer LV, Isolation Details R12-3 Transformer LV, Isolation Details

Upload: trankhuong

Post on 24-Mar-2018

223 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

© Horizon Power Corporation

Part 2 – Reference – Drawing Register

Number Description

R1 Pole Bolt Details

R2-1 Bonding, Intermediate

R2-2 Running disc angle 11, 22 and 33 kV – 3 Phase Superposition

R3-1 Insulators

R3-2 Insulator Ties

R3-3 Armour Rods

R4 Insulator Pin and Bolt Details

R5-1 Eyebolt Details

R5-2 Eyebolt, Conductor Terminations

R6 Earthing

R7-1 Cable cleat – Guard and Pole Top Switch – Anti Climbing Guard Detail

R7-2 Service Cable Cleat, Guard Fixing Details

R8-1 ABC Taps for Transformer, and Cable Termination

R8-2 Lugs and Connectors, Transformer and Cable

R8-3 PG Clamps Installation Instruction

R8-4 Lugs and Connectors, Insulation Piercing Clamps

R10-1 Dropout Fuse Mounting, Details

R10-2 Dropout Fuse Mounting, Boric Acid and Fault Tamer Details

R11 Flowline Fuse Mounting and Service Termination

R11-1 LV Supply to Pole-Mounted Equipment

R12-1 Transformer LV, Isolation Details

R12-2 Transformer LV, Isolation Details

R12-3 Transformer LV, Isolation Details

Page 2: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

© Horizon Power Corporation

Number Description

R13-1 Pole Embedment Depth, Danger Plate

R13-2 Steel Distribution Pole Belling of Base C and D Areas

R14-1 Ground Stay

R14-2 Outrigger Stay, HV and LV Tee Off

R14-3 Outrigger Stay, HV or LV Termination only, HV and LV Intermediate only

R14-4 Outrigger Stay, Running Disc Angle, 12.5 m Pole

R14-5 Aerial Stay

R14-6 Outrigger Stay Pole

R14-7 Double Ground Stay for Running Disc Angle with Underslung or Overhead Earth Wire

R16 Screw In Anchor, Flow Chart

R17 Transformer Kiosk (Non MPS), 160-1000 kVA Installation Guide

R18 Transformer Kiosk (MPS), 160-630 kVA Installation Guide

R19-1 Kiosk, 25-50 kVA Spud Transformer Installation Guide

R19-2 Transformer Kiosk (MPS) 63 kVA (HUB2 on a culvert) Installation Guide

R20-1 Schneider RM6 Outdoor Switchgear – 4 Way Installation Guide

R20-2 Schneider RM6 Outdoor Switchgear – 4 Way Installation Guide

R20-3 Schneider RM6 Extensible Switchgear Installation Guide

R21 Transformer Kiosk (Non MPS), 160-315-630-1000 kVA, Cable Arrangements

R22 MPS Substation, Up to 630 kVA

R24 LV Switchgear Kiosk, General Arrangement

R26-1 Street Light Cutout, Single Phase Supply

R26-2 Street Light Cutout, Single Phase Supply for Class II Luminaries

Page 3: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

© Horizon Power Corporation

Number Description

R26-3 Street Light Cutout Connection Arrangement for Electrical Attachment

R27 Fusing Arrangement for Street Light Columns

R29 25kVA Padmount Trfr 240V Street Feeder/Consumer Mains Terminal Block

R30 25kVA Padmount Trfr 480V Street Feeder/Consumer Mains Terminal Block

R31 Mini Pillar Additional Neutral

R32 Mini Pillar Terminal Block

R33 Mini Pillar XLPE Working End

R35 Mini Pillar SPUDS 240V

R36 Nulec PMB Control Box Connection Detail

R37 Nulec PMB Solar Connection Detail (WITHDRAWN)

R38 Overhead Fault Indicator Solar Connection Detail

R39 Installer Identification Tag

R40 Installation of Above Ground Cable Marker

R42 Earth Bonding of Meter Guard

R50 Sample Operational Label

R51 Placement of Duct Beneath Road Crossings

R52 Cable and Duct Placement on Truncations

R53 Cross Section Details of Cable Easement

R54 Placement of Duct Beneath Open Drain

R55 Cable Trench Layout (Green Field Site) Two Layers (1 Tx and 5 LV Cables)

Page 4: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

POLE BOLT

DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R1

200

'A'

ROUND WASHER

76 x 76 x 5 SQUARE WASHER

COIL SPRING M14 TO M24

51 x 51 x 3 SQUARE WASHER

POLE SIDE

CUT EXCESS THREAD TO WITHIN 10mm OF NUT

DIMENSION A

PB1 = 300mm

PB2 = 400mm

PB3 = 550mm

DIAMETER OF POLE BOLTS

12mm 16mm 20mm

12mm 16mm 20mm

12mm 16mm 20mm

BOLT DIMENSIONS

Page 5: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

BONDING

INTERMEDIATE

REVISION DATE

DRAWING No.

B JUNE 2011

R2-1

100

PURPOSES

HOLE FOR EARTHING

50mm OF M12 THREADED

FOR EARTHING PURPOSES

50mm OF M12 THREADED HOLE

Page 6: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

RUNNING DISC ANGLE

11kV, 22kV & 33kV (3 PHASE)

PHASE SUPERPOSITION

REVISION DATE

DRAWING No.

C MARCH 14

R2-2

VIEWED FROM THIS END

RIGHT-HAND ANGLE WHEN

ON TOP

WHITE PHASE

VIEWED FROM THIS END

LEFT-HAND ANGLE WHEN

IN ALL CASES MARK THE PHASE COLOURS ON THE VERTICAL/ANGLE STRAIN POLES.1.

NOTES:

Page 7: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

INSULATORS

REVISION DATE

DRAWING No.

B JUNE 2011

R3-1

STRAIN INSULATOR

RUNNING DISC ANGLE

INTERMEDIATE TERMINATION

20mm BAND-IT STRAP TYPE

TERMINATION INTERMEDIATE

TO 20 DEG

ANGLE UP

OR ANGLE 20-45 DEG

INLINE STRAIN

POST INSULATOR

HIGH POLLUTION

HIGH VOLTAGE (33,22,11,6.6kV)

LOW VOLTAGE

SWITCH WIRE AND RUNNING EARTH

Page 8: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

INSULATOR TIES

REVISION DATE

DRAWING No.

C JUNE 2011

R3-2

H) TURN ENDS OF TIE DOWN AGAINST THE CONDUCTOR.

G) THREE TURNS.

F) ONE OPEN TURN.

E) FIVE TURNS.

D) ONE OPEN TURN.

AND AROUND CONDUCTOR FOR SIX TURNS.

C) CROSS TIE AT THE BACK OF INSULATOR AND CONTINUE UNDER

AND AROUND CONDUCTOR FOR ONE TURN.

B) CROSS TIE AT THE FRONT OF INSULATOR AND CONTINUE UNDER

CONDUCTOR FOR ONE TURN.

A) TAKE HALF TURN AROUND INSULATOR, UNDER AND AROUND

HALVE TIE. START WITH MIDDLE OF TIE AT BACK OF INSULATOR.

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS FOR HV & LV

TOP TIE

HIGH VOLTAGE

SIDE TIE

HIGH VOLTASGE

TOP TIE

LOW VOLTAGE

TOP TIE

95 & 150 mm2 ABC

CENTRE OF INSULATOR

BARE ABC 300mm OVER

300

L) TURN ENDS OF TIE DOWN AGAINST CONDUCTOR.

K) THREE TURNS.

J) ONE OPEN TURN.

H) FIVE TURNS.

G) ONE OPEN TURN.

F) TAKE FIVE TURNS AROUND CONDUCTOR.

CARRYING EACH END TO BOTTOM OF CONDUCTOR.

E) PASS ENDS OVER AND ACROSS IN FRONT OF INSULATOR

D) TAKE ONE TURN AROUND CONDUCTOR ON EACH SIDE OF INSULATOR

BOTTOM OF CONDUCTOR ON EACH SIDE.

C) CROSS ENDS AROUND BACK OF INSULATOR AND RETURN TO

EACH SIDE OF INSULATOR.

B) TAKE ONE AND HALF TURNS AROUND CONDUCTOR ON

CONDUCTOR ON EACH SIDE.

A) TAKE HALF TURN AROUND INSULATOR AND UNDER

HALVE TIE. START WITH MIDDLE OF TIE AT BACK OF INSULATOR.

SIDE TIE

HIGH VOLTAGE

Page 9: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

ARMOUR RODS

REVISION DATE

DRAWING No.

B JUNE 2011

R3-3

ARMOUR ROD

ARMOUR RODS ARE TO BE USED ON ALL BAYS OVER 80m (WAS 100 m.)

Page 10: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

INSULATOR PIN AND BOLT DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R4

HV INSULATOR BOLT

LV INSULATOR PIN

190

80

100

260

160

503

50mm SQUARE WASHER

M16 HEX. NUT

M16 THREAD

'B' HEAD, LEAD

TO SPINDLE

40 mm SQUARE WASHER WELDEDWASHER

75 mm SQUARE

COIL SPRING

SPRING WASHER75 x 75 x 5 WASHER

24mm THREAD

(WOOD CROSSARM)

(STEEL CROSSARM)

Page 11: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

EYEBOLT DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R5-1

POLE

POLE

20mm EYEBOLT FOR STAY

16mm EYEBOLT FOR CROSSARM

AND RUNNING DISC ANGLE

16mm EYEBOLT FOR CENTRE PHASE

ROPE THIMBLE

CROSSARM

HELICAL TERMINATION

AGAINST POLE OR WASHER

EYE RETURN TO BE HARD

(N/A FOR STEEL POLES)

76 x 76 x 5 SQUARE WASHER

Page 12: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CONDUCTOR TERMINATIONS

REVISION DATE

DRAWING No.

C MARCH 14

R5-2

CLEVIS THIMBLE

ALUMINIUM

CLEVIS THIMBLE

MALLEABLE CAST IRON

TERMINATION

HELICAL

STEEL CONDUCTOR (SCAC)

OR

ALUMINIUM CONDUCTOR (AAC & AAAC)

COPPER CONDUCTOR (CU)

OR

STEEL CONDUCTOR (SCGZ)

TERMINATION

HELICAL

TERMINATION

HELICAL

FOR PTS ARRANGEMENT

SUPPLIED WITH PTS

STRAP AND CLAMPS

Page 13: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

R7 - STANDARD CABLE GUARD

EARTH MAT

MAT

EARTH

600 SQ.

R6

450

ROADSIDE

MINIM

UM

HEIG

HT

ROD GUIDE

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

EARTHING

REVISION DATE

DRAWING No.

C JUNE 2011

R6

SPEAR

EARTH

2070

720

450

150

EARTHWIREEARTH ROD

20

MINIM

UM

CLAMP

TO POLE

30 OHMS

R = LESS THAN

SECURED WITH BAND-IT STRAPS

(POSITION TO SUIT)

3 EXTRA ROD GUIDES REQUIRED

EARTH PIT

EARTH ROD

SEE NOTE 1

BAND-IT STRAPS TO SUIT EQUIPMENT

SEE NOTE 2

STRAP 150 ABOVE G.L.

FIRST 12mm BANDIT

STEEL POLE

100 ABOVE G.L.

EARTH POINT M.E.N.

COMBINED

INDIVIDUAL

<1 ohm

<30 ohm

EARTH

WITH OVERHEAD

ISOLATED H.V.

OVERHEAD EARTH

WITH NO

ISOLATED H.V.

<30 ohm <30 ohm

<10 ohm <30 ohm

INSTALLED EARTHING RESISTANCE REQUIREMENTSTABLE

RESISTANCE

REFER EARTHING

SEE NOTE 3

BAND-IT STRAPS FOR EARTHING

SPACE APPROXIMATELY 500mm APART

TO FIX EQUIPMENT DOWN EARTHS TO POLE. TO BE

3. 12mm WIDE BAND-IT STRAPS FITTED WITH SADDLES

FRAME

BOND THE OPERATING HANDLE TO THE HANDLE

2. AN APPROVED EARTHING BRAID MUST BE FITTED TO

GUARDS.

BRACKET. 12mm WIDE BAND-IT STRAPS ON CABLE

POLE ROD GUIDES AND LV ANGLE INSULATOR

1. 20mm WIDE BAND-IT STRAPS ON RAYCHEM BRACKET,

Page 14: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE CLEAT / GUARD AND

POLE TOP SWITCH

ANTI CLIMBING GUARD DETAIL

REVISION DATE

DRAWING No.

C MARCH 14

R7-1

CA

BLE CLE

AT SP

ACIN

G

SEE NOTE 2

SURGE ARRESTOR

BI-LUG PLATE

EARTH SCREEN

XLPE TYPE

STRAP

12mm BAND-IT

EARTH POINT

SEE NOTE 3

SWITCH

TO POLE TOP

1500

740

2000

1500

1500

2070

150

ROD GUIDE

NOTE 4

CONNECTION.

AS HIGH UP AS POSSIBLE TO THE SIDE OF THE

POLE AND PROPERTY BOUNDARY) THEN ROLLED

BE INSTALLED ON THE FOOTPATH SIDE (BETWEEN

- FOR POLE TOP SWITCH POLES THE CABLE MUST

CONNECTION.

AND PROPERTY BOUNDARY) UP TO THE

POLE ON THE FOOTPATH SIDE (BETWEEN POLE

THEN THE CABLE MUST BE ROLLED AROUND THE

ON THE OPPOSITE SIDE OF THE INSTALLED CABLE,

- IF THE CONNECTION POINT AT THE POLE TOP IS

SIDE. (BETWEEN POLE AND PROPERTY BOUNDARY)

CABLES MAY BE INSTALLED ON THE FOOTPATH

- SHOULD POINT ABOVE BE IMPRACTICAL, THE

TRAFFIC.

OPPOSITE SIDE OF THE POLE TO ONCOMING

- ALL CABLES SHALL BE INSTALLED ON THE

FOR THE CABLE INSTALLATION.

URD CABLES ON THEM THE FOLLOWING WILL APPLY

IN ALL SECTIONS WHERE POLES ARE DRAWN WITH 5.

STRAPS MIN 2 REQUIRED.

ANTICLIMBING GUARD SECURED WITH 12mm BANDIT 4.

BETWEEN F.G.L. AND GUARD SHALL BE MAINTAINED.

MINIMUM OF 2 REQUIRED. MINIMUM GAP POSSIBLE

CABLE GUARD SECURED WITH 12mm BANDIT STRAPS 3.

STRAPS MINIMUM OF 2 REQUIRED.

CABLE CLEATS SECURED WITH 12mm BANDIT 2.

FOR NTEC'S BAND STRAP OVER ONLY 1 CHANNEL.1.

NOTES:

Page 15: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTE:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

SERVICE CABLE CLEAT / GUARD

FIXING DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R7-2

150

150

150

150

SHRINK GLOVE

SHRINK GLOVE

TOP BAND-IT STRAP

FIRST BAND-IT STRAP

SEE NOTE 1

1000mm MAX SPACING

EQUI-SPACED BETWEEN

MINIMUM OF 3 BAND-IT STRAPS

EQUI-SPACED

3 BAND-IT STRAPS

4m CONDUIT

AS POSSIBLE TO THE SIDE OF THE CONNECTION.

AND PROPERTY BOUNDARY) THEN ROLLED AS HIGH UP

INSTALLED ON THE FOOTPATH SIDE (BETWEEN POLE

- FOR POLE TOP SWITCH POLES THE CABLE MUST BE

BOUNDARY) UP TO THE CONNECTION.

THE FOOTPATH SIDE (BETWEEN POLE AND PROPERTY

THE CABLE MUST BE ROLLED AROUND THE POLE ON

THE OPPOSITE SIDE OF THE INSTALLED CABLE, THEN

- IF THE CONNECTION POINT AT THE POLE TOP IS ON

(BETWEEN POLE AND PROPERTY BOUNDARY)

MAY BE INSTALLED ON THE FOOTPATH SIDE.

- SHOULD POINT ABOVE BE IMPRACTICAL, THE CABLES

SIDE OF THE POLE TO ONCOMING TRAFFIC.

- ALL CABLES SHALL BE INSTALLED ON THE OPPOSITE

FOR THE CABLE INSTALLATION.

URD CABLES ON THEM THE FOLLOWING WILL APPLY

2. IN ALL SECTIONS WHERE POLES ARE DRAWN WITH

SHALL BE MAINTAINED.

MINIMUM GAP POSSIBLE BETWEEN F.G.L. AND GUARD

MINIMUM OF 2 REQUIRED.

1. CABLE GUARD SECURED WITH 12mm BANDIT STRAPS

150

Page 16: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

ABC TAPS FOR TRANSFORMER

AND CABLE TERMINATION

REVISION DATE

DRAWING No.

B JUNE 2011

R8-1

INSULATED CRIMP

95 ABC

95 ABC

P.G CLAMP

TO D.O.F.

C. DROPOUT FUSE TO CABLE SURGE ARRESTORS

B. DROPOUT FUSE TO TRANSFORMER WITH SURGE ARRESTER

A. LINE TAPS TO DROPOUT FUSE or CABLE SURGE ARRESTOR

WITH 12mm HOLE

INSULATED LUG

SURGE ARRESTOR END

WITH 12mm HOLE

INSULATED LUG

CONDUCTIVE GREASE

CONTACT AFTER APPLY

ENSURE GOOD ELECTRICAL

PAINT CLEANED OFF TOSEE NOTE 2

D.O.F. END

WITH 12mm HOLE

INSULATED LUG

TO INSULATOR

HALF CLAMP

TINNED BRASS

SURGE ARRESTOR END

WITH 12mm HOLE

INSULATED LUG

D.O.F. END

WITH 12mm HOLE

INSULATED LUG

NOTE:

3. ALTERNATIVELY USE "C" FROM D.O.F. TO TRANSFORMER OR TRANSFORMER TO SURGE ARRESTOR

2. REMOVE INSULATION FOR BRASS HALF CLAMP AND MOISTURE DRAIN (20mm)

SEE R8/2 FOR PG CLAMP APPLICATION

INSULATION MUST BE REMOVED BEHIND THE INSULATED LUG TO ALLOW MOISTURE TO DRAIN.

1. WHERE THE INSULATED SPLICE CRIMP IS NOT USED FOR TRANSFORMER OR LINE TAPS A 20mm LENGTH OF

CLAMPS

SPLICE TO SUIT MAINS USING PG

CONNECT COPPER OR ALUMINIUM

SEE NOTE 1

SEE NOTE 2

Page 17: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

LUGS AND CONNECTORS

TRANSFORMER AND CABLE

REVISION DATE

DRAWING No.

D JUNE 2011

R8-2

UTIL

UX

FT94

AAustralia

20-23.5

mm dia.

38-283

AL

HE

X

DIE

O.D. 35.0

mma.

AA

C,

AA

AC

CRIMP MARK

EARTH PHASE

BRAID

(CABLE CONNECTIONS)

Q TYPE LUG

CABLE CRIMP

LUG BI-METAL

TRANSFORMER & EARTH LUGS ABC TO AERIAL

S/S BOLT & NUT

12 DIAMETER

S/S FLAT WASHER

S/S SPRING WASHER

ABC LUG

Page 18: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

PG CLAMPS

INSTALLATION INSTRUCTION

REVISION DATE

DRAWING No.

D JUNE 2011

R8-3

INCLUDING Cu DOWN EARTH JOINS

UP TO 70mm sq COPPER CONDUCTOR

SMALL COPPER PG CLAMP FOR

ALUMINIUM OR COPPER

ALUMINIUM

STOCK No. PG 0002

IMMEDIATELY APPLY ALUMINIUM JOINTING COMPOUND.

WIRE BRUSH SURFACE OF CONDUCTOR AND JAWS OF CLAMP. THEN

THE COPPER

IF COPPER TO ALUMINIUM THEN ALUMINIUM CONDUCTOR TO BE ABOVE

FIT CLAMP AND TIGHTEN BOLTS SECURELY.

STEP 1

PARALLEL GROOVE CLAMPS

STEP 2

STEP 3

REUSE OF PG CLAMPS

TO EXCLUDE ALL MOISTURE - STOCK No K10020

INADEQUATE, THEN APPLY 510 DENSO TAPE OVER GREASE AND JOINT

IN EXTREMELY CORROSIVE ENVIRONMENTS WHERE THIS HAS PROVEN

USE SHELL MP2 - STOCK No PG0125.

APPLY GREASE TO COVER ALL PARTS OF JOINT.

(TYPICALLY WITHIN 5 Kms OF COAST)

IN AREAS OF HIGH POLLUTION

ENVIRONMENTAL PROTECTION AT THE INTERFACE

APPLY CONTACT PROTECTION GREASE TO REINSTATE

CONDITION

THOROUGHLY CLEANED TO BRING THE SURFACE BACK TO "AS NEW"

CONTACT GROOVES OF THE PG CONDUCTOR INTERFACE MUST BE

HEAVY FAULT CONDITIONS AND EXCESSIVE CORROSION

DO NOT REUSE PG CLAMPS WHICH HAVE BEEN SUBJECTED TO

Page 19: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

LUGS AND CONNECTORS

INSULATION PIERCING CLAMPS

REVISION DATE

DRAWING No.

B JUNE 2011

R8-4

LV MAINS IPC - ABC TO ABC

ABC TO SERVICE 95/35 & 150/35

Page 20: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

DROPOUT FUSE MOUNTING

DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R10-1

STANDOFF INSULATOR

HIGH POLLUTION NORMAL POLLUTION

DROPOUT FUSE FITTED TO TERMINATION POLE TOP SWITCH WITH CABLE

NOMINATED HIGH FAULT CURRENT AREAS

HIGH POLUTION ALL AREAS EXCEPT METRO 11kV

NORMAL POLLUTION INCLUDING 11kV AREAS

11kV METRO ONLY,NOMINATED LOCATIONS

BRACKET FOR ANGLE

HOLES IN OFFSET CROSSARM

M12 BOLTS THROUGH PREDRILLED

HOLES IN OFFSET CROSSARM

M12 BOLTS THROUGH PREDRILLED

HOLES IN OFFSET CROSSARM

M12 BOLTS THROUGH PREDRILLED

THROUGH INSULATOR

2 M12 BOLTS

ANGLE BRACKET

M16 BOLTS THROUGH ANGLE

HOLES IN OFFSET CROSSARM

M12 BOLTS THROUGH PREDRILLED

22kV ONLY

FAULT TAMER

STRAIN EYE OF PTS

M16 BOLT

M12 BOLT

M16 BOLT

M12 BOLT

ANGLE BRACKET

OF PTS

STRAIN EYE

M16 BOLT

ANGLE BRACKET

Page 21: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

DROPOUT FUSE MOUNTING

BORIC ACID AND FAULT TAMER

DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R10-2

RADII

XARM MOUNTED

XARM TYPES

POLE MOUNTED

STANDARD MOUNTING

XARM TYPES

STANDARD DOF's UP TO 33kV

FIRE RISK AREAS AND HIGHER FAULT RATINGS

BORIC ACID FUSES FOR

260

1146

SWING CLEARANCE

FOR FITTING & BARREL

ON EXISTING STRUCTURES

POSSIBLE MOUNTING VARIATIONS

Page 22: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

3/05/2017 1:26:11 PM ___H:\00 - Temp - 00\HP\AB\R11\R11.dgn___GIS900526___mleroux

Page 23: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

LV SUPPLY

TO POLE MOUNTED EQUIPMENT

REVISION DATE

DRAWING No.

A 27-03-15

R11-1

LV UNDERGROUND CONNECTION SIDE VIEW

LV TRANSFORMER CONNECTION SIDE VIEW

U23-1

CB (5 AMP)

LV ABC CONNECTION SIDE VIEW

R8-4

ABC IPC

R12-2

LV AERIAL CONNECTION SIDE VIEW

R-11

INTO CLAMP

BEFORE PUTTING

DOUBLED OVER

MUST BE

CB (5 AMP)

CB (5 AMP)

CB (5 AMP)

Page 24: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

TRANSFORMER LV

ISOLATION DETAILS

REVISION DATE

DRAWING No.

D MARCH 14

R12-1

NEUTRAL

NEUTRAL

100 AND 200kVA TO BARE CONDUCTOR

25 AND 63kVA TO BARE CONDUCTOR

ABC LUGS

ABC HARNESS 95sqmm

BOLTED TO HARNESS BRACKET

ABC SUSPENSION CLAMPS

TO ABC

LENGTH AND CRIMPED

ABC SPLICE CUT TO

COPPER DOWN EARTH

70sqmm PVC COVERED

QUICK LUGS TO DOWN EARTH

AND PUT INTO PG CLAMP

ABC SPLICE CRIMPED TO ABC

ABC LUGS

BOLTED TO HARNESS BRACKET

ABC SUSPENSION CLAMPS

AND PUT INTO PG CLAMP

ABC SPLICE CRIMPED TO ABC

QUICK LUGS TO DOWN EARTH

COPPER DOWN EARTH

70sqmm PVC COVEREDABC HARNESS 150sqmm FOR 200kVA

ABC HARNESS 95sqmm FOR 100kVA

ABC LUG CRIMPED TO ABC

TO INSULATOR PIN

400AMP LV ISOLATOR BOLTED

100 AMP FUSE HOLDER

Page 25: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

TRANSFORMER LV

ISOLATION DETAILS

REVISION DATE

DRAWING No.

D MARCH 14

R12-2

5000

a2

a1

a3

a4

1000

BOTTOM OF FUSE SWITCH

SINGLE PHASE 10 AND 25kVA

100 and 200kVA TO ABC

FOR 200kVA

150sqmm ABC

PFISTERE FUSE UNIT

95sqmm ABC FOR

KRONE - FOR 200kVA

100kVA AND BELOW

PFISTERE - FOR

315kVA TO ABC

FOR OPTIONS

REFER TO R12 SHEET 3

NEUTRAL

SERVICE

16sqmm TAP

100 AMP FUSE HOLDER

25sqmm PVC COVERED COPPER

TERMINAL BLOCK

POINT

TO EARTH

EARTH

DOWN

NOTES:

CABLE CLEARANCE CANNOT BE OBTAINED

1. ALTERNATIVE POSITION FOR BRACKET IF

BRACKET

TOP OF

SEE NOTE 1

DOWN EARTH

QUICK LUGS TO 25sqmm

ER

TO RUNNING EARTH

Page 26: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

TRANSFORMER LV

ISOLATION DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

R12-3

N

OPTION 1

OPTION 2

OPTION 3

OPTION 4

SHOWN FOR CLARITY

1 PHASE ONLY

SINGLE LINE REPRESENTATION

PG

GS0062

LV AERIAL

SUPPLY

FROM TX

FUSES

KRONE

SUPPLY

FROM TX

GS0062

LV AERIALPG PG

GS0062

LV AERIALPG

FUSES

KRONE

N

FUSES

KRONE

SUPPLY

FROM TX

PGLV AERIAL

FUSES

KRONE

Page 27: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

POLE EMBEDMENT DEPTH

AND DANGER PLATE

REVISION DATE

DRAWING No.

B JUNE 2011

R13-1

WHEN SUPPLIED FOR FITTING

DANGER PLATE LOCATION

1400

E

PL

G.L.

EXAMPLE 9.5m POLE

POLE LENGTH EMBEDMENT DEPTH

9.5m 1.55m

1.70m

1.85m

2.00m

11.0m

12.5m

14.0m

NOTE:

PL = POLE LENGTH

TO BE DETERMINED BY DESIGNER

FOR CYCLONIC AREAS BURIAL DEPTH

E = EMBEDMENT DEPTH

POLE BURIAL DEPTHS

= 1.55m

= (15.5) / 10

= (9.5 + 6.0) / 10

E = (PL + 6.0) / 10

Page 28: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

STEEL DISTRIBUTION POLE

BELLING OF BASE

C AND D AREAS

REVISION DATE

DRAWING No.

B JUNE 2011

R13-2

G.L.

600 TO 900

600

100

CONCRETE BASE

SA

ND

Y

SOIL

S

UP

TO 14

000

BU

RIA

L

DEP

TH

TO

BE

DET

ER

MIN

ED

BY

EN

GIN

EER

(MARK ON FACE)

GROUND LINE INDICATOR

NOTE:

APPROPRIATELY PRODDED TO REMOVE TRAPPED AIR POCKETS

1 PART OF WATER

3 PARTS OF 20mm AGGREGATE

2 PART OF CLEAN SAND

1 PART OF CEMENT

THE REQUIRED MEASURE IS:

WITH NO ADDITIVES REQUIRED

20mm AGGREGATE, SLUMP OF 80mm, CONCRETE GRADE OF N20

CONCRETE MIXED ON SITE WILL HAVE

MASS FOR EACH BASE PLATE WILL BE APPROXIMATELY 60Kg

CONCRETE DIA. FOR SANDY SOILS 600mm

SLEEVE AROUND THE COLUMN FOR THE FULL BURIAL DEPTH.

COLUMNS SHALL BE SUPPORTED WITH A N20 CONCRETE

FOR CYCLONIC AREAS (AS1170.2-CAT2-REGION "D") 6.5M

FEATURE

ABSORBENT

IMPACT

9.5M, 11M & 12.5M POLES 219, 1 x 48 CHS GRADE 350

Page 29: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTE:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

GROUND STAY

REVISION DATE

DRAWING No.

A JUNE 2011

R14-1

ROPE GRIP

ROPE THIMBLE TERMINATION

HELICAL

3000

ROPE THIMBLE

TERMINATION

HELICAL

TERMINATION

HELICALINSULATOR

GROUND LEVEL

R5

AND COVERED IN INSULATING MATERIAL

L.V. MAINS MUST BE CONSTRUCTED ON A 2100mm CROSSARM

1. IF THE STAY WIRE PASSES THROUGH L.V. MAINS THEN THE

A

BC

a

b

c

90

(DEGREES)

ANGLE a

(DEGREES)

ANGLE b

60

(DEGREES)

ANGLE c

30

90

90

45

30

45

60

B

(LENGTH)

C=

Bx1.73

(LENGTH)

A=

Bx0.57

Bx2

Bx1.41

Bx1.15

(TENSION)

C

SUM OF LINE LOAD x 1.41

INSTALLATION ANGLES AND TENSIONS OF STAYS

C = LENGTH OF STAY WIRE

B = HEIGHT OF STAY ATTACHMENT ABOVE GROUND

A = POSITION OF STAY ROD FROM BASE OF POLE

PVC CONDUIT

25mm UV STABILISED

19/2.00

19/2.00

(SEE FLOW CHART - R16)

GROUNDSCREW

SUM OF LINE LOAD x 1.15

SUM OF LINE LOAD x 2

Page 30: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

OUTRIGGER STAY

HV AND LV TEE-OFF

REVISION DATE

DRAWING No.

B MARCH 14

R14-2

ROPE GRIP

ROPE THIMBLE TERMINATION

HELICAL

ROPE THIMBLE

TERMINATION

HELICAL

TERMINATION

HELICAL

INSULATOR

GROUND LEVEL

R5

PVC CONDUIT

25mm UV STABILISED

3600

ROPE THIMBLE

157

4950

2700

TERMINATION

HELICAL

(SEE FLOW CHART - R16)

GROUNDSCREW

19/2.00

19/2.0

0

2700

(MINIM

UM)

EQUIPMENT (NOTE 2)

BANDIT STRAPS TO SUIT

32mm WIDE BANDIT STRAP ON OUTRIGGER.2.

AND COVERED IN INSULATING MATERIAL

CONSTRUCTED ON A 2100mm CROSSARM

MAINS THEN THE L.V. MAINS MUST BE

IF THE STAY WIRE PASSES THROUGH L.V. 1.

NOTES:

Page 31: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

OUTRIGGER STAY

HV OR LV TERMINATION ONLY

HV AND LV INTERMEDIATE ONLY

REVISION DATE

DRAWING No.

B MARCH 14

R14-3

ROPE GRIP

ROPE THIMBLE TERMINATION

HELICAL

ROPE THIMBLE

TERMINATION

HELICAL

TERMINATION

HELICAL

INSULATOR

GROUND LEVEL

R5

PVC CONDUIT

25mm UV STABILISED

ROPE THIMBLE

2700

TERMINATION

HELICAL

(SEE FLOW CHART - R16)

GROUNDSCREW

19/2.00

19/2.0

0

2700

(MINIM

UM)

4400

HV

3000 L

V

3600

EQUIPMENT. (NOTE 2)

BANDIT STRAP TO SUIT

32mm WIDE BANDIT STRAPS ON OUTRIGGER.2.

AND COVERED IN INSULATING MATERIAL

CONSTRUCTED ON A 2100mm CROSSARM

MAINS THEN THE L.V. MAINS MUST BE

IF THE STAY WIRE PASSES THROUGH L.V. 1.

NOTES:

Page 32: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

OUTRIGGER STAY

RUNNING DISC ANGLE

12.5m POLE

REVISION DATE

DRAWING No.

B MARCH 14

R14-4

ROPE GRIP

ROPE THIMBLE TERMINATION

HELICAL

ROPE THIMBLE

TERMINATION

HELICAL

TERMINATION

HELICAL

INSULATOR

GROUND LEVEL

PVC CONDUIT

25mm UV STABILISED

ROPE THIMBLE

2700

TERMINATION

HELICAL

(SEE FLOW CHART - R16)

GROUNDSCREW

19/2.0

0

2700

(MINIM

UM)

4950

410

0

19/2.00

R5 (NOTE 2)

EQUIPMENT (NOTE 3)

BANDIT STRAPS TO SUIT

RIGGER.

32mm WIRE BANDIT STRAPS ON OUT3.

LOCATIONS.

STANDARD H6 FOR STAY EYEBOLT

REFER TO RDA CONSTRUCTION 2.

MATERIAL.

CROSSARM AND COVERED IN INSULATING

BE CONSTRUCTED ON A 2100mm

L.V. MAINS THEN THE L.V. MAINS MUST

IF THE STAY WIRE PASSES THROUGH 1.

NOTES:

Page 33: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

AERIAL STAY

REVISION DATE

DRAWING No.

A JUNE 2011

R14-5

TERMINATION

HELICAL

INSULATOR

R5

ROPE THIMBLE

3000

TERMINATION

HELICAL

ROPE THIMBLETERMINATION

HELICAL

19/2.00 19/2.00

OVER CONDUCTOR AT BOTH ENDS.

POLE. STAY MAY REQUIRE TWO INSULATORS IF

STAY INSULATOR/S MUST BE FITTED 3.0m FROM 1.

NOTES:

Page 34: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

OUTRIGGER STAY POLE

REVISION DATE

DRAWING No.

A JUNE 2011

R14-6

ROPE GRIP

ROPE THIMBLE TERMINATION

HELICAL

ROPE THIMBLE

TERMINATION

HELICAL

TERMINATION

HELICAL

INSULATOR

GROUND LEVEL

R5

PVC CONDUIT

25mm UV STABILISED

ROPE THIMBLE

2700

TERMINATION

HELICAL

(SEE FLOW CHART - R16)

GROUNDSCREW

19/2.00

19/2.0

0

2700

(MINIM

UM)

xx

xx

TERMINATION

HELICAL

3000

INSULATOR

19/2.00

THIMBLE

ROPE

Page 35: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

DOUBLE GROUND STAY FOR

RUNNING DISC ANGLE WITH UNDERSLUNG

OR OVERHEAD EARTH WIRE

REVISION DATE

DRAWING No.

A JUNE 2011

R14-7

(SEE FLOW CHART - R16)

GROUNDSCREW

3000

3000

GROUND LEVEL

PVC CONDUIT

25mm UV STABILISED

ROPE GRIP

TERMINATION

HELICAL

ROPE THIMBLE

19/2.00

TERMINATION

HELICALINSULATOR

19/2.00

TERMINATION

HELICAL

ROPE THIMBLE

A

BC

a

b

c

90

(DEGREES)

ANGLE a

(DEGREES)

ANGLE b

60

(DEGREES)

ANGLE c

30

90

90

45

30

45

60

B

(LENGTH)

C=

Bx1.73

(LENGTH)

A=

Bx0.57

Bx2

Bx1.41

Bx1.15

(TENSION)

C

SUM OF LINE LOAD x 1.41

INSTALLATION ANGLES AND TENSIONS OF STAYS

C = LENGTH OF STAY WIRE

B = HEIGHT OF STAY ATTACHMENT ABOVE GROUND

A = POSITION OF STAY ROD FROM BASE OF POLE

19/2.00

19/2.00

NOTE:

SUM OF LINE LOAD x 1.15

SUM OF LINE LOAD x 2

FOR STAYS EYEBOLT LOCATIONS.

2. REFER TO RDA CONSTRUCTION STANDARD H7

AND COVERED IN INSULATING MATERIAL

CONSTRUCTED ON A 2100mm CROSSARM

MAINS THEN THE L.V. MAINS MUST BE

1. IF THE STAY WIRE PASSES THROUGH L.V.

R5 (NOTE 2)

Page 36: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

SCREW IN ANCHOR

FLOW CHART

REVISION DATE

DRAWING No.

B JUNE 2011

R16

REMAINS EXPOSED

UNTIL 300mm OF ROD

ATTEMPT TO DRIVE ANCHOR

LOAD WITH 4 PINSREMAINS EXPOSED

UNTIL 300mm OF ROD

ATTEMPT TO DRIVE ANCHOR

FIT EXTENSION ROD

EXPOSED

300mm OF ROD

WITH MORE THAN

BEFORE REACHING

PINS SHEAR

NO

PINS SHEAR YES

SCREW ANCHOR

TRY 300mm

START AGAIN

200mm SCREW ANCHOR

TOO SOFT FOR

CONDITIONS

SOIL

NO

REMAINS EXPOSED

UNTIL 300mm OF ROD

ATTEMPT TO DRIVE ANCHOR

LOAD WITH 10 PINS

YES

STALLS

AUGER MOTOR

OR

PINS SHEAR

YES

NO

NO

FITTED

ALREADY BEEN

EXTENSION ROD

HAS AN

YES

REMAINS EXPOSED

UNTIL 100mm OF ROD

ATTEMPT TO DRIVE ANCHOR

REMOVE 6 PINS

THAN 300mm

EXPOSED LESS

LENGTH OF ROD

IS

PINS SHEAR NO

ACHIEVED

INSTALLATION

ANCHOR

SATISFACTORY

FINISH

YES

YES

SCREW ANCHOR

200mm

START USE

Page 37: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

23/08/2016 9:08:55 AM ___pw:\\OCA-PW-701.ghdnet.internal:PWV8iSS4ProdHP\Documents\Projects\61\31539 NIS Business Urgent Works\08_0 DRAFTING\8_3 DRAWINGS\R17.dgn___GIS900526___mleroux

Page 38: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

23/08/2016 9:13:39 AM ___pw:\\OCA-PW-701.ghdnet.internal:PWV8iSS4ProdHP\Documents\Projects\61\31539 NIS Business Urgent Works\08_0 DRAFTING\8_3 DRAWINGS\R18.dgn___GIS900526___mleroux

Page 39: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

23/08/2016 9:15:26 AM ___pw:\\OCA-PW-701.ghdnet.internal:PWV8iSS4ProdHP\Documents\Projects\61\31539 NIS Business Urgent Works\08_0 DRAFTING\8_3 DRAWINGS\R19-1.dgn___GIS900526___mleroux

Page 40: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

TRANSFORMER KIOSK (MPS)

63kVA (HUB2 ON A CULVERT)

INSTALLATION GUIDE

REVISION DATE

DRAWING No.

C MARCH 14

R19-2

A8

A8

B8

B8

C8

C8

LV

NOT TO SCALENOT TO SCALE

VOID FILLCOMPACTED BACKFILL

COMPACTED & LEVELLED SUBGRADE

FGL

FRONT VIEWSIDE VIEW

FGL

CABLE ENTRY

OVERHANG LIMITED TO

LV CABLE ACCESS CULVERT

BASE

577

1000

FI4.4

REFER TO

TYPICAL

LIMIT OF EXCAVATION500 500500500

600

NOTES:

DSM - 4 - 02

DSM - 3 - 26

DSM - 3 - 01 SHEETS 1&2

SITE DESIGN & INSTALLATION DETAILS ETC. REFER TO

FOR OTHER INFORMATION ON

EQUIPMENT WEIGHTNOTE:

LV

LV

MV

MV

MVLV

CONNECTIONS

FUTURE MPS

TRANSFORMER

WHEN CONNECTION IS MADE TO 63kVA

ALLOW FOR FUTURE MPS INSTALLATION

CABLE LENGTH AND ALIGNMENT TO

LIFTING POINTS

MV CABLE ACCESS

MV

THIS DRAWING TO BE READ IN CONJUNCTION WITH THE SUBSTATION INSTALLATION REQUIREMENTS - HPC-9DJ-23-0001-2012

63kVA = 720kgTRANSFORMERS:

BASE = 384kg

CROWN = 948kgBOX CULVERT:

63kVA CONNECTIONS

�»¿

Page 41: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

23/08/2016 9:38:47 AM ___pw:\\OCA-PW-701.ghdnet.internal:PWV8iSS4ProdHP\Documents\Projects\61\31539 NIS Business Urgent Works\08_0 DRAFTING\8_3 DRAWINGS\R20-1.dgn___GIS900526___mleroux

Page 42: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

23/08/2016 9:39:54 AM ___pw:\\OCA-PW-701.ghdnet.internal:PWV8iSS4ProdHP\Documents\Projects\61\31539 NIS Business Urgent Works\08_0 DRAFTING\8_3 DRAWINGS\R20-2.dgn___GIS900526___mleroux

Page 43: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

23/08/2016 9:41:19 AM ___pw:\\OCA-PW-701.ghdnet.internal:PWV8iSS4ProdHP\Documents\Projects\61\31539 NIS Business Urgent Works\08_0 DRAFTING\8_3 DRAWINGS\R20-3.dgn___GIS900526___mleroux

Page 44: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

TRANSFORMER KIOSK (NON MPS)

160/315/630/1000 kVA

CABLE ARRANGEMENTS

REVISION DATE

DRAWING No.

C 02/04/14

R21

N R W B

LV LV

LV LV

MANUFACTURER

TO BUSHING BY

EXTENSION PALM FITTED

N R W B

315 AND 630kVA 33kV TRANSFORMER

18 DIAMETER HOLE

120

30

50

1130

1030

1100

1200

1230

1200

1130

1320

1250

6.6/11kV & 22kV TRANSFORMER LV

315 AND 630kVA

33kV TRANSFORMER LV

315, 630kVA

6.6/11kV, 22 & 33kV TRANSFORMER LV

1000kVA

6.6/11kV AND 22kV TRANSFORMER

1000kVA

6.6/11kV AND 22kV TRANSFORMER

315 AND 630kVA

1000kVA 33kV TRANSFORMER

AND NUMBER OF 1 X 630mm� PER PHASE.

CUSTOMER LV CABLES CONNECTED TO A SOLE USE 160 kVA TRANSFORMER CAN BE A MAXIMUM SIZE 5.

MAXIMUM SIZE AND NUMBER OF 2 X 630mm� PER PHASE.

CUSTOMER LV CABLES CONNECTED TO A SOLE USE 315 AND 630kVA TRANSFORMER CAN BE A 4.

AND NUMBER OF 3 X 630 sq mm PER PHASE.

CUSTOMER LV CABLES CONNECTED TO A SOLE USE 1000kVA TRANSFORMER CAN BE A MAXIMUM SIZE 3.

PER PHASE AND 1 PER NEUTRAL.

ALL LV CABLES INSTALLED FOR NON MPS DISTRICT SUBSTATION ARRANGEMENTS TO BE 630mm� Al, 2 2.

BUSHINGS.

SLACK FOR POSSIBLE 1000kVA TRANSFORMER UPGRADE SEE ABOVE FOR HEIGHTS OF LV AND MV

MV AND LV CABLES INSTALLED FOR 315 AND 630kVA NON MPS TRANSFORMERS MUST ALLOW 500 mm 1.

NOTES:

MV

MV MV

MV

Page 45: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

MPS SUBSTATION

UP TO 630 kVA

REVISION DATE

DRAWING No.

B JUNE 2011

R22

1 2 3 4 5

(REF R25)

CABLE TO FUSE SWITCH

630 AMP COVER WITH 600 AMP LINKS - OPTIONAL

5 x 400 AMP COVERS SUPPLIED WITH MPS

1200 AMP ARRANGEMENT - OPTIONAL

600 AMP LINKS

2 X 630 COVERS FIXED TOGETHER WITH

600

HEATSHRINK

BW

R

STRIP

N

R

W

B

NOTES:

630 kVA

2. CABLE SUPPLIED WITH MPS TRANSFORMER RANGE - 160, 315 AND

INCLUDING 630 AMP BASES.

1. MPS COMES COMPLETE WITH TRANSFORMER AND 5 x LV SWITCHES

Page 46: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

LV SWITCHGEAR

KIOSK

GENERAL ARRANGEMENT

REVISION DATE

DRAWING No.

C MARCH 14

R24

LV KIOSK TYPE 1 - FEEDER PILLAR

LV KIOSK TYPE 2 - DISTRICT SUBSTATION

LV KIOSK TYPE 3 - DISTRICT SUBSTATION

IN 2HR FIRE RATED SUBSTATION

IN 2HR FIRE RATED SUBSTATION

RECESSED IN WALL FREESTANDING

FREESTANDING

FREESTANDING

1000

1025

1500

1025

1400

900

FGL FGL

FGL

FGL

THIS AREA TO BE

FREE OF FOOTINGS

DIMENSIONS SHOWN

RECESS BUILT TO

400 DEEP400 DEEP

(500 x 200 x 25 THICK)

CONCRETE SLABS

SUBSTATION

FLOOR OF

400 DEEP

1m DEEP TRENCH

1m DEEP TRENCH

THRU REINFORCED SECTIONS

DRILL 4-HOLES 12 DIAMETER

1300

1025

1600

(500 x 200 x 25 THICK)

CONCRETE SLABS

220010

25

1600

THRU REINFORCED SECTIONS

DRILL 6-HOLES 12 DIAMETER

SUBSTATION

FLOOR OF

APPROXIMATE MAXIMUM WEIGHT WITH 5 FUSEWAYS AND 2 DISCONNECTORS = 240kg2.

RAWLNUTS AND 4 x 10mm BOLTS x 75 LONG.

KIOSK BOLTED TO SUBSTATION WALL ABOVE THE TRENCH WITH 4 x 10mm 1.

NOTES:

(500 x 200 x 25 THICK)

CONCRETE SLABS

400 DEEP

APPROXIMATE MAXIMUM WEIGHT WITH 5 FUSEWAYS AND 2 DISCONNECTORS = 350kg2.

RAWLNUTS AND 6 x 10mm BOLTS x 75 LONG.

KIOSK BOLTED TO SUBSTATION WALL ABOVE THE TRENCH WITH 6 x 10mm 1.

NOTES:

APPROXIMATE MAXIMUM WEIGHT WITH 6 FUSEWAYS = 160kg.2.

TO BE RECESSED IN THE WALL.

THE CUSTOMER IS RESPONSIBLE FOR THE INSTALLATION OF THE HP SUPPLIED FEEDER PILLAR, 1.

NOTES:

Page 47: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

STREET LIGHT CUTOUT

SINGLE PHASE SUPPLY

REVISION DATE

DRAWING No.

C MARCH 14

R26-1

N E

SUPERSEDED TYPE 1 REQUIREMENTS

PLUG

E

A N A N

E

LOOPED SERVICE SUPPLYSINGLE SERVICE SUPPLY

ENAA N E

TYPE 2

CAT No. 8DE 54715-04

CUTOUT

STREET LIGHTING SERVICE

GEC HENLEY

TO MOUNTING BRACKET FROM EARTH BLOCKS

CONNECT 6mm EARTH WIRE (EE1364)

TO BE 6mm Cu PVC INSULATED.

LOOP BETWEEN NEUTRAL AND EARTH BLOCKS

THESE LINKS MUST BE INSTALLED.

'WITH THE MEN LOOP INSTALLED' & 'EARTH LEAD TO MOUNTING BRACKET'

TO THE NUMBER OF THIS TYPE STILL IN USE TYPE 1 MUST BE CONNECTED AS SHOWN

BY THE TYPE 2 CUTOUT WITH A COMMON EARTH/NEUTRAL TERMINAL HOWEVER, DUE

THIS CUTOUT, WITH SEPARATE EARTH/NEUTRAL TERMINALS, WAS SUPERSEDED

NOTE:

FRONT COVER TYPE 2

VIEW ON INSIDE OF

OR FUSE

LINK

TO EACH LUMINAIRE

A DOUBLE INSULATED CABLE

TO EACH LUMINAIRE

A DOUBLE INSULATED CABLE

UNIT

TO ENTER

(SHEATHING)

INSULATION

DOUBLE

UNIT

TO ENTER

(SHEATHING)

INSULATION

DOUBLE

USING M4 SCREW

MOUNTING BRACKET

FIX TO

BLOCK(MEN)

EARTH/NEUTRAL

OR TAPE

WITH HEAT SHRINK

TO BE INSULATED

EARTH/NEUTRALOR TAPE

WITH HEAT SHRINK

TO BE INSULATED

EARTH/NEUTRAL

WOUND NEUTRAL SCREEN CABLE

INSULATED, RED CORE INSULATION, HELICAL

10mm (EE1420) OR 16mm (EE1421) XLPE

SUPERSEDED TYPE 2 UNIT SEE R26/2 FOR REPLACEMENT

SCREW.

LUG AND M6

TERMINAL

USING

BRACKET

TO MOUNTING

EARTH WIRE

CONNECT

M6 SCREW.

BRACKET USING TERMINAL LUG AND

CONNECT EARTH WIRE TO MOUNTING

Page 48: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

STREET LIGHT CUTOUT

SINGLE PHASE SUPPLY

FOR CLASS II LUMINIARES

REVISION DATE

DRAWING No.

C MARCH 14

R26-2

A N NE E

A

N

A

VIEW ON INSIDE OF FRONT COVER

SINGLE PHASE LOOPED SERVICESINGLE PHASE

STOCK No: HZ0128

A N E A N E A N E

TO EACH LUMINAIRE

A DOUBLE INSULATED CABLE

WOUND NEUTRAL SCREEN CABLE

INSULATED, RED CORE INSULATION, HELICAL

10mm (EE1420) OR 16mm (EE1421) XLPE

PLATE AND SCREWS

BRACKET USING

FIX TO MOUNTING

PLATE AND SCREWS

BRACKET USING

FIX TO MOUNTING

A A A

LED INSTALLATIONS.

GF1300) MUST BE INSTALLED FOR

LST 10A FUSE (STOCK CODE: 1.

NOTE:

LST 10A FUSE

N

WITHDRAW

N

REFER TO R26

-3

Page 49: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

STREET LIGHT CUTOUT

SINGLE PHASE SUPPLY

FOR LUMINIARES

REVISION DATE

DRAWING No.

A APRIL 14

R26-3

A N NE E

A

N

A

VIEW ON INSIDE OF FRONT COVER

STOCK No: HZ0128

A N E A N E A N E

TO EACH LUMINAIRE

A DOUBLE INSULATED CABLE

WOUND NEUTRAL SCREEN CABLE

INSULATED, RED CORE INSULATION, HELICAL

10mm (EE1420) OR 16mm (EE1421) XLPE

PLATE AND SCREWS

BRACKET USING

FIX TO MOUNTING

PLATE AND SCREWS

BRACKET USING

FIX TO MOUNTING

A A A

LST 10A FUSE

N

SUPPLY FUSE 32A

SINGLE PHASE

SUPPLY FUSE 32A

SINGLE PHASE LOOPED SERVICE

NOTE 4

NOTE 3

NOTE 2

WIRE (EE1364) LOOP.

MEN BRIDGE OR 6mm EARTH 4.

FROM EARTH TERMINAL.

(EE1364) TO MOUNTING BRACKET

CONNECT 6mm EARTH WIRE 3.

SCREW (AB2820).

TERMINAL LUG (FL0163) AND M6

MOUNTING BRACKET USING

CONNECT EARTH WIRE TO 2.

ALL INSTALLATIONS.

GF1300) MUST BE INSTALLED FOR

LST 10A FUSE (STOCK CODE: 1.

NOTE:

NOTE 4

NOTE 3

NOTE 2

Page 50: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

FUSING ARRANGEMENTS FOR

STREET LIGHT COLUMNS

REVISION DATE

DRAWING No.

B JUNE 2011

R27

FROM A LOOPED SERVICE

FROM A MINI PILLAR

TO OTHER STREET LIG

HTS

G.L.

TERMINATING BLOCKS

NOTES FOR PILLAR CONNECTIONS.

G.L.

G.L. G.L.

BEYOND SECOND NUT.

SCREW THREAD PROTRUDING

CUTOFF ANY PORTION OF

2 C0RE 10sqmm

CABLE (EE1420)

R26

(W/LINK)

R26

(W/FUSE)

STREET LIG

HT OR PIL

LA

R.

SUPPLY FRO

M PREVIO

US

STREET LIGHT FUSE

HOLDER (SEE NOTE 2)

FITTED ON OPPOSITE

SIDE OF TERMINALS

BY FITTING TERMINAL

FIXING SCREW AS

SHOWN.

USE WITH 10A NIT TYPE FUSE (GF0915)

2. GEC REDSPOT TYPE RS20H FUSE HOLDER (GF0121),

WITHIN THE DEVELOPMENT.

1. DISTRIBUTE LIGHTING LOAD ACROSS THE PHASES

ALSO REFER TO DETAILS IN DRG R26 SERIES

MOUNTING

BOARD

MINI

PILLAR

TOP VIEW

Page 51: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

DISTRIBUTION CONSTRUCTION

STANDARDS

OPERATIONS

REFERENCE DRAWING

25kVA PADMOUNT Tx LV DISTR. BOARD

240V STREET FEEDER/CONSUMER MAINS

TERMINAL BLOCK

REVISION DATE

DRAWING No.

C FEB 2013

R29

RED

BLACK

RED

WHITE

70 mm sq GREEN/ YELLOW

TO TRANSFORMER HV EARTH BAR

MAXIMUM 5 CABLES

MAXIMUM 35mm� Cu XLPE 3C LV

FROM

FUSE HOLDER

FROM

TRANSFORMER

BUSHING (a2)

M.E.N.

SCREEN

BLUE

LUG SEPERATE

USE COMMON BOLT

RED

WHITE

NEUTRAL

EARTH

PERSPEX COVER

BLACK HEAT SHRINK OR

TAPE OVER SCREEN AND

BLUE PHASE

NOTES:

1. SEE R35 FOR MINI PILLAR ARRANGEMENT.

2. SETUP FOR A 12.7kV OR 19.1kV 25kVA 240/480V TRANSFORMER

240V CONFIGURATION SHOWN, SEE R30 FOR 480V CONFIGURATION.

Page 52: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

DISTRIBUTION CONSTRUCTION

STANDARDS

OPERATIONS

REFERENCE DRAWING

25kVA PADMOUNT Tx LV DISTR. BOARD

480V STREET FEEDER/CONSUMER MAINS

TERMINAL BLOCK

REVISION DATE

DRAWING No.

B FEB 2013

R30

RED

BLACK

RED

WHITE

70 mm sq GREEN/ YELLOW

TO TRANSFORMER HV EARTH BAR

MAXIMUM 5 CABLES

MAXIMUM 35mm� Cu XLPE 3C LV

FROM

FUSE HOLDER

FROM

TRANSFORMER

BUSHING (a2)

M.E.N.

SCREEN

BLUE

LUG SEPERATE

USE COMMON BOLT

RED

WHITE

NEUTRAL

EARTH

PERSPEX COVER

BLACK HEAT SHRINK OR

TAPE OVER SCREEN AND

BLUE PHASE

NOTES:

WHITE

1. SEE R35A FOR MINI PILLAR ARRANGEMENT.

2. SETUP FOR A 12.7kV OR 19.1kV 25kVA 240/480V TRANSFORMER

480V CONFIGURATION SHOWN. SEE R29 FOR 240V CONFIGURATION.

Page 53: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

MINI PILLAR

ADDITIONAL NEUTRAL

FITTING REQUIREMENTS

REVISION DATE

DRAWING No.

B JUNE 2011

R31

N

VIEW FROM BACK OF BOARD

STOCK No. HC1299

R W B N

COVER

CONNECTION LINK

STOCK No HC1299

ADDITIONAL M.E.N LINK

TERMINAL

EARTH WIRE

TO OLD

NEUTRAL

M.E.N LINK

EXISTING

EARTH ROD

TO EXISTING

EARTH WIRE

THE ADDITIONAL LINK.

5. THEN CONNECT EXTRA NEUTRALS TO

THE ADDITIONAL M.E.N LINK.

AND BOTTOM CENTRE TERMINAL IN

EARTH TERMINAL IN EXISTING LINK

CONDUCTOR (BLACK) BETWEEN OLD

4. CONNECT A 25/35MM NEUTRAL

THE ADDITIONAL LINK.

TO BOTTOM R/HAND TERMINAL OF

3. CONNECT REMOVED EARTH CABLE END

TO CONFIRM NO POTENTIAL DIFFERENCE.

M.E.N LINK AND REMOVED CABLE END

FROM M.E.N LINK AND TEST BETWEEN

REMOVE EARTH STAKE CONDUCTOR

2. USING INSULATED GLOVES AND TOOLS

PANEL BEHIND EXISTING M.E.N LINK.

1. FIX EXTRA NEUTRAL LINK TO BACK OF

INSTALLATION PROCEDURE:

NOTES:

1. IF POTENTIAL EXISTS BETWEEN CUT ENDS NOTIFY HORIZON POWER.

ON BACK

CONDUCTOR TO LOOP TO M.E.N.

ADDITIONAL 25/35mm BLACK

BOARD

MOUNTING

Page 54: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

MINI / UNIVERSAL PILLAR

TERMINATION BLOCK

REVISION DATE

DRAWING No.

B JUNE 2011

R32

R W B N

VIEW FROM STREET

VIEW FROM SIDE

NEUTRAL

STREET LIGHT

TERMINAL BLOCKS

COVER

BOARD

MOUNTING

(TO EARTH ROD)

EARTH

CROSSING

TO ROAD

CROSSING

TO ROAD

M.E.N. LINK

TO STREET LIGHT/S

FROM TEE JOINT

25mm� SERVICE

CONNECTION LINKS

RED SPOT FUSE

TO STREET LIGHT

LIGHT FUSE

SUPPLY TO STREET

WHERE REQUIRED

STREET LIGHT FUSE

Page 55: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

MINI PILLAR

XLPE WORKING END

REVISION DATE

DRAWING No.

B JUNE 2011

R33

NEUTRAL BLOCK

SPLIT SCREEN

G.L. BA

CK 300

mm

CA

BLE T

O

BE S

TRIP

PE

D

200

160

120

HEATSHRINK

XLPE

(GLOVE)

PVC POULTICE AREA

NOTES:

1. MINI PILLAR ENCLOSED WORKING END, LID OF PILLAR TO BE PAINTED WHITE

Page 56: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

SPUDS MINI PILLAR

240V SUPPLY FROM R29

ARRANGEMENT

REVISION DATE

DRAWING No.

B JUNE 2011

R35

R W B N

ACTIVE NEUTRAL

HEATSHRINK

TAPE

GL

SEE R29

OVER BLUE PHASE

BLACK HEATSHRINK

R W B N

EARTH ROD

240V OUT

240V IN

240V 1 PHASE SUPPLY ARRANGEMENT

PROPERTY

ROAD

N

ACTIVE

1 PHASE CUSTOMER

ACTIVE

N

1 PHASE CUSTOMER

NOTES:

1. MAXIMUM CABLE SIZE 35mm�

Page 57: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

NULEC N-SERIES RECLOSER CONTROL BOX

CONNECTION DETAIL

REVISION DATE

DRAWING No.

D MARCH 14

R36

1 2 3 4 5 6 7

A

ANTENNA

EQUIPMENT

P1 P2

240V SUPPLY

MCB

BATTERY

SURGE ARRESTOR

BEHIND THE EQUIPMENT PANEL

TO ALLOW SUPPLY CABLE TO BE RUN

FIXING POINTS TO BE LOOSENED

MODEM

RADIO

LEAD

PATCH

EARTH

CONTROL CABLE

CORRUGATED CONDUIT

GLAND

SUPPLY CABLE

LV MAINS

MOUNT SURGE ARRESTOR

MODULAR DIN RAIL

REARE

20mm LV MAINS ENTRY M10 EARTH STUD

MAINS ENTRY

20mm LV

FRONT

16mm SPARE

(TO SWITCHGEAR)

CONTROL CABLE ENTRY

TOP VIEW

PATCH LEAD

INSTALLATION DETAIL

ANTENNA SURGE ARRESTOR

"O" RING

RETAINING NUT

COAXIAL CABLE

CONDUIT

1 2 3 4 5 6 7

AN

E

EN

L

BETWEEN TERMINALS 6 & 7

REMOVE MCB AND FIT LINK

E

AN

E

E

N E

SUPPLY

240V AC

ARRESTOR

SURGE

USING NAMEPLATE FIXING

RADIO MODEM TO BE FITTED

LIVE

NEUTRAL

NOTE 2

PVC 240V

2C+E 2.5sqmm

STUD

EARTH

SUPPLY CABLE

LV MAINS

FOR ARRESTOR

OF VERMIN PROOFING

DRILL OUT CORNER

EA

RT

H

- POLE MOUNTED RECLOSER/ISOLATOR

REFER TO DISTRIBUTION COMMISSIONING TEST SHEET2.

LEAD IS REQUIRED FOR THE SURGE ARRESTOR.

FOR DOUBLE SKIN OR PAINTED ENCLOSURES AN EARTH 1.

NOTES:

Page 58: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

2/09/2016 11:30:38 AM ___H:\00 - Temp - 00\HP\AB\R37_B.dgn___GIS900526___mleroux

Page 59: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

OVERHEAD FAULT INDICATOR

SOLAR CONNECTION

REVISION DATE

DRAWING No.

B JUNE 2011

R38

20W SOLAR PANEL

++- -

-

+

TX

BATTERY SPACE

TRANSFORMER

(IC)

RADIO MODEM

+-

PHOTOVOLTAIC CONTROLLER

CHARGING DISCONNECT

LOAD

6.0A LOAD

6.5A SOLAR

12 VOLTS

SELECT

FLOODED

OR

SEALED

+ + +- - - BATTERY

FLOODED

WIRE FOR

JUMPER

REMOVE

TEMP. SENSE

3

1 6 53 24

SOLAR BATTERY LOAD

MORNINGSTAR

SUNSAVER-6

CHARGER

uP CONTROLLED

NOTE 3

NOTE 1

NOTE 2

NOTE 4 & 5

SOLAR CONTROLLER

BATTERY

RTU

RADIO MODEM

ENCLOSURE

BATTERY

MODEM

NOTES:

(TOP VIEW)

CONTROLLER

SOLAR

NOTE 6

NOTE 7

REQUIRES LARGER VERSION OF ENCLOSURE

8. CONSTRUCTION USING 2 x 7Ah BATTERIES

7. LINK REQUIRED FOR SEALED LEAD ACID BATTERY.

LOAD DISCONNECT.

6. DO NOT USE LOAD TERMINALS FOR CONTROLLERS WITH

OR REGULATOR.

5. FOR 2 x 10W SOLAR PANELS REQUIRED AT SOLAR PANEL

4. SOLAR PANEL MAY BE PROVIDED WITH FLEXIBLE CABLE TAIL.

3. PROVIDE LOOP AT BATTERY AND SOLAR TERMINALS.

2. REMOVE TRANSFORMER CONNECTION.

1. REMOVE BATTERY AND TAILS. (ALLOW FOR RETERMINATING)

Page 60: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

INSTALLER IDENTIFICATION TAG

REVISION DATE

DRAWING No.

B JUNE 2011

R39

X X X X XX M M Y Y

STAINLESS STEEL TAG 80 x 20 x 0.5

ADJACENT THE JOINT/TERMINATION

USE SCREEN WIRE TO FIX TAG TO CABLE

PAY OR CONTRACTOR NUMBER

eg 03.08

(MONTH, YEAR)

DATE OF INSTALLATION

2. ONE TAG IS REQUIRED WHERE A 3 PHASE SET IS INSTALLED

1. INSTALLER TO MARK TAG AS DETAILED WITH SUITABLE PUNCH SET

NOTES:

Page 61: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

INSTALLATION OF

ABOVE GROUND CABLE MARKER

REVISION DATE

DRAWING No.

B JUNE 2011

R40

DIAL 1100BEFORE YOU DIG

DANGER

THE VICINITY

CABLES IN

ELECTRICAL

UNDERGROUND

DIAL 1100BEFORE YOU DIG

DANGER

THE VICINITY

CABLES IN

ELECTRICAL

UNDERGROUND

EQ

UIP

ME

NT P

RO

TECTIO

N

1200CA

BLES IN

VICINIT

Y

1000

1600

FRONT VIEW BACK VIEW

STOCK CODE CR0327

INSTALLATION TOOL

STOCK CODE CR 0328

REMOVAL TOOL

DANGER LABEL

NOTES:

1. REMOVAL TOOL TO BE ORDERED FROM SUPPLIER AS NEEDED

Page 62: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

EARTH BONDING OF METER GUARD

REVISION DATE

DRAWING No.

C MARCH 14

R42

ELECTROCARD METER

DISPLAY

SETTINGS

CREDIT

EMERGENCY

INSERT CARD STRIPE ON TOP

SERIAL NUMBER

212

170

WASHER

STAR

NUT

2 NUTS

WASHERS

2 FLAT

FLAT WASHER

BOLT

BOLT

97

METER BOARD

METER COVER

METER

FIXING POINT

REMOVED AROUND

PAINT TO BE

SEE NOTE 4

CRIMP LUG

SPLAYED

1, 2, 3 & 4

SEE NOTES

STOCK No. JW0152 (COVER)

6 DIAMETER x 20 LG GHH BOLT, FLAT WASHER AND NUT AS SHOWN.

GHH BOLT, 1 STAR WASHER, 2 FLAT WASHERS & 2 NUTS AS SHOWN. REMAINING FIXINGS TO BE DONE WITH

SPLAYED LUG TO BE SECURED TO EARTH COVER ON REAR OF METER BOARD WITH 6 DIAMETER x 20 LG 4.

EARTH WIRE TO BE FITTED BY LICENSED ELECTRICIAN3.

ALL METER GUARDS ARE TO BE BONDED TO CONSUMERS METAL ENCLOSURE EARTHING POINT OR M.E.N.2.

BOND EARTH WIRE TO BE SAME AS INCOMING SUPPLY NEUTRAL.1.

NOTES:

Page 63: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

SAMPLE OPERATIONAL LABEL

REVISION DATE

DRAWING No.

A 21/08/15

R50

LABEL SPECIFICATIONS

EQUIPMENT IS OPERATIONAL

TREAT AS ENERGISED

DANGER!!

- DO NOT ENERGISE

- DANGER : OTHER END NOT TERMINATED

OTHER TAGS AVAILABLE:�

FRONT DOOR OF SUBSTATION.

MOUNTED IN PROMINENT POSITION ON EQUIPMENT E.G. SIDE OF MINI AND UNIVERSAL PILLAR OR �

"DANGER" TO APPEAR IN RED, OTHER TEXT IN BLACK.�

DIMENSIONS : 100mm (WIDTH) x 80mm (DEPTH).�

ALUMINIUM, SELF ADHESIVE, WEATHERPROOF.�

Page 64: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

KERB LINE

CABLE

PROTECT CABLES BETWEEN EDGE OF ALIGNMENT AND END OF CONDUIT WITH PROTECTION SLABS

RO

AD

WA

Y

RO

AD

WA

Y

CONDUIT INSTALLATION REQUIREMENTS FOR HV & LV CABLES

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

PLACEMENT OF DUCT

BENEATH ROAD CROSSINGS

REVISION DATE

DRAWING No.

A 21/08/15

R51

BOUNDARY LINE

PROPERTY

PAST KERB1.0m MIN

CABLE

POWER ALIGNMENTUNDERGROUND

POWER ALIGNMENTUNDERGROUND

CONDUIT INSTALLATION REQUIREMENTS FOR SERVICE & STREET LIGHT CABLES

CONDUIT SHALL BE INSTALLED TO EDGE OF CABLE ALIGNMENT

KERB LINE

CABLE

RO

AD

WA

Y

RO

AD

WA

Y

BOUNDARY LINE

PROPERTYCABLE

POWER ALIGNMENTUNDERGROUND

POWER ALIGNMENTUNDERGROUND

PAST KERB1.0m MIN

MANUAL FOR SPECIFIC REQUIREMENTS.

REFER TO HORIZON POWER UNDERGROUND CABLE INSTALLATION 1.

Page 65: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE AND DUCT PLACEMENTS

ON TRUNCATIONS

REVISION DATE

DRAWING No.

A 21/08/15

R52

ROADWAY

ROADWAY

ROADWAY

ROADWAY

500

NOTE:

PROPERTY BOUNDARY

PROPERTY BOUNDARY

0-500mm ALIGNMENT

HORIZON POWER

CARRIAGEWAY

EDGE OF

DUCT

500

THE DUCT SHALL BE INSTALLED FROM EDGE TO EDGE OF THE CABLE ALIGNMENT.

0-500mm ALIGNMENT

HORIZON POWER

Page 66: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

T

3 & 4)

(NOTES

1000

MARKER TAPE

500

(NOTES 3 & 4)

T

EASEMENT

CONDUIT NOMINAL DIAMETER, WHICHEVER IS SMALLER.

ENCASEMENT THICKNESS "T" SHALL BE AT MOST 150mm OR 200% OF THE LARGEST 4.

CONDUIT NOMINAL DIAMETER, WHICHEVER IS GREATER.

ENCASEMENT THICKNESS "T" SHALL BE AT LEAST 75mm OR 75% OF THE LARGEST 3.

CONDUITS SHALL BE CENTRED IN EASEMENT.2.

(AS DEFINED BY AS/NZS 3000 WIRING RULES), CONCRETE ENCASEMENT IS NOT REQUIRED.

WHERE DUCT IS HEAVY DUTY AND MEETS THE RQUIREMENT OF CATEGORY A 1.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CROSS SECTION DETAILS OF CABLE EASEMENT

REVISION DATE

DRAWING No.

A 21/08/15

R53

(INDICATIVE)2 x �100 DUCTS

Page 67: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

PLACEMENT OF DUCT BENEATH

OPEN DRAIN

REVISION DATE

DRAWING No.

A 21/08/15

R54

PUBLIC OPEN SPACE

OPEN DRAIN

PUBLIC OPEN SPACE

CABLE

ROADWAY

ROADWAY

4 & 5)

(NOTES

(NOTES 4 & 5)

DUCT

CONCRETE ENCASEMENT DETAIL

LOT

T

T

LOT

CROSSES OPEN DRAINS

DUCT WHERE CABLE

POWER ALIGNMENTUNDERGROUND

DIAMETER, WHICHEVER IS SMALLER.

ENCASEMENT THICKNESS "T" SHALL BE AT MOST 150mm OR 200% OF THE LARGEST CONDUIT NOMINAL 5.

DIAMETER, WHICHEVER IS GREATER.

ENCASEMENT THICKNESS "T" SHALL BE AT LEAST 75mm OR 75% OF THE LARGEST CONDUIT NOMINAL 4.

900mm AND 1500mm AND DUCTS SHALL EXTEND 1500mm BEYOND EXTENT OF WATER COURSE EACH SIDE.

WHERE DIRECTIONAL DRILLING IS USED, CONCRETE ENCASEMENT IS NOT REQUIRED, DEPTH SHALL BE BETWEEN3.

DUCTS SHALL EXTEND TO THE PROPERTY BOUNDARY EITHER SIDE OF THE WATER COURSE OR OPEN DRAIN.2.

WATER COURSE OR OPEN DRAIN.

DUCTS SHALL BE CONCRETE ENCASED AND HAVE A MINIMUM COVER OF 850mm BELOW THE BOTTOM OF 1.

Page 68: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE TRENCH LAYOUT

GREEN FIELD SITE

TWO LAYERS (1 Tx AND 5 LV CABLES)

REVISION DATE

DRAWING No.

A 24/08/15

R55

DEPTH OF COVER.

CABLE ALIGNMENT SHALL BE INCREASED AS REQUIRED SO THAT THE CABLE JOINTS ALSO HAVE THE NECESSARY

THE MINIMUM DEPTH OF COVER OF CABLES SHALL BE 850mm. THE DEPTH OF COVER OF CABLES IN A NOMINAL 6.

LAYOUT OF HV CABLES SHALL START FROM THE ROAD SIDE OF THE TRENCH.5.

LV CABLE JOINTS SHALL BE INSTALLED AT STAGGERED LOCATIONS.4.

LV CABLE JOINTS SHALL BE INSTALLED ABOVE OTHER LV CABLES. 3.

LV CABLE JOINTS ARE APPROXIMATELY �170mm. 2.

LV CABLES SHALL BE ON THE TOP LAYER WITH THIS LAYER CONSISTING OF A MAXIMUM OF 5 LV CABLES.1.

LV CABLE

35mm� OR 50mm� HV CABLE (TRANSFORMER)

CABLE TRENCH

ROAD RESERVE

500

425

850

25

25 25

200

150

MARKER TAPE LEVEL

25

HV CABLE (TRANSFORMER)

100

PROPERTY BOUNDARY

BEDDING

Page 69: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

LV CABLE

35mm� OR 50mm� HV CABLE (TRANSFORMER)

CABLE TRENCH

ROAD RESERVEPROPERTY BOUNDARY

500

425

850

200

150

MARKER TAPE LEVEL

100

HV CABLE (FEEDER)

25

HV CABLE (FEEDER)

SERVICE CABLES.

INCLUDING STREET LIGHT AND

TRANSFORMER AND LV CABLES

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE TRENCH LAYOUT

GREEN FIELD SITE TWO LAYERS (1 HV FEEDER, 1 Tx & LV CABLES)

REVISION DATE

DRAWING No.

A 24/08/15

R56

DEPTH OF COVER.

CABLE ALIGNMENT SHALL BE INCREASED AS REQUIRED SO THAT THE CABLE JOINTS ALSO HAVE THE NECESSARY

THE MINIMUM DEPTH OF COVER OF CABLES SHALL BE 850mm. THE DEPTH OF COVER OF CABLES IN A NOMINAL 6.

LAYOUT OF HV CABLES SHALL START FROM THE ROAD SIDE OF THE TRENCH.5.

LV CABLE JOINTS SHALL BE INSTALLED AT STAGGERED LOCATIONS.4.

LV CABLE JOINTS SHALL BE INSTALLED ABOVE OTHER LV CABLES. 3.

LV CABLE JOINTS ARE APPROXIMATELY �170mm. 2.

AND 1 X 35mm� HV CABLE.

LV CABLES SHALL BE ON THE TOP LAYER WITH THIS LAYER CONSISTING OF NO MORE THAN 2 LV CABLES 1.

BEDDING

Page 70: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

LV CABLE

35mm� OR 50mm� HV CABLE (TRANSFORMER)

CABLE TRENCH

ROAD RESERVE

500

425

850

200

150

MARKER TAPE LEVEL

100

HV CABLE (FEEDER)

25

100

SERVICE CABLES.

STREET LIGHT AND

LV CABLES INCLUDING

TRANSFORMER CABLE

HV FEEDER CABLE AND

DEPTH OF COVER.

CABLE ALIGNMENT SHALL BE INCREASED AS REQUIRED SO THAT THE CABLE JOINTS ALSO HAVE THE NECESSARY

THE MINIMUM DEPTH OF COVER OF CABLES SHALL BE 850mm. THE DEPTH OF COVER OF CABLES IN A NOMINAL 5.

IF THE 35mm� HV CABLE IS NOT ON THE BOTTOM LAYER IT SHALL BE NEAREST TO THE ROADSIDE.4.

LAYOUT OF THE HV CABLES SHALL START FROM THE ROAD SIDE OF THE TRENCH. 3.

LV CABLE JOINTS ARE APPROXIMATELY �170mm. 2.

LV CABLES SHALL BE ON THE TOP LAYER WITH THIS LAYER CONSISTING OF NO MORE THAN 2 LV CABLES.1.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE TRENCH LAYOUT

GREEN FIELD SITE TWO LAYERS (1 HV FEEDER, 1 Tx & 2 LV CABLES)

REVISION DATE

DRAWING No.

A 24/08/15

R57

PROPERTY BOUNDARY

BEDDING

Page 71: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE TRENCH LAYOUT

GREEN FIELD SITE

ONE LAYER (1 Tx AND 3 LV CABLES)

REVISION DATE

DRAWING No.

A 24/08/15

R58

LV CABLE

35mm� OR 50mm� HV CABLE (TRANSFORMER)

CABLE TRENCH

ROAD RESERVE

500

425

850

150

MARKER TAPE LEVEL

100

25

25

AND SERVICE CABLES

INCLUDING STREET LIGHT

TRANSFORMER AND LV CABLES

DEPTH OF COVER.

CABLE ALIGNMENT SHALL BE INCREASED AS REQUIRED SO THAT THE CABLE JOINTS ALSO HAVE THE NECESSARY

THE MINIMUM DEPTH OF COVER OF CABLES SHALL BE 850mm. THE DEPTH OF COVER OF CABLES IN A NOMINAL 6.

LAYOUT OF HV CABLES SHALL START FROM THE ROAD SIDE OF THE TRENCH.5.

LV CABLE JOINTS SHALL BE INSTALLED AT STAGGERED LOCATIONS.4.

LV CABLE JOINTS SHALL BE INSTALLED ABOVE OTHER LV CABLES. 3.

LV CABLE JOINTS ARE APPROXIMATELY �170mm. 2.

1 X 35mm� HV CABLE CAN BE INSTALLED.

FOR A ONE LAYER CABLE TRENCH NO MORE THAN 4 X 185mm� OR 3 X 240mm� LV CABLES AND 1.

PROPERTY BOUNDARY

BEDDING

Page 72: Part 2 – Reference – Drawing Register - Horizon Power · PDF fileMPS Substation, Up to 630kVA . R24 . ... Street Light Cutout Connection Arrangement for Electrical Attachment

NOTES:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

REFERENCE DRAWING

CABLE TRENCH LAYOUT

GREEN FIELD SITE

ONE LAYER (1 HV FEEDER AND LV CABLES)

REVISION DATE

DRAWING No.

A 24/08/15

R59

LV CABLE

CABLE TRENCH

ROAD RESERVE

500

425

850

150

MARKER TAPE LEVEL

100

HV CABLE (FEEDER)

SERVICE CABLES

STREET LIGHT AND

CABLES INCLUDING

HV FEEDER AND LV

PROPERTY BOUNDARY

BEDDING

DEPTH OF COVER.

CABLE ALIGNMENT SHALL BE INCREASED AS REQUIRED SO THAT THE CABLE JOINTS ALSO HAVE THE NECESSARY

THE MINIMUM DEPTH OF COVER OF CABLES SHALL BE 850mm. THE DEPTH OF COVER OF CABLES IN A NOMINAL 5.

LAYOUT OF HV CABLES SHALL START FROM THE ROAD SIDE OF THE TRENCH.4.

LV CABLE JOINTS SHALL BE INSTALLED AT STAGGERED LOCATIONS.3.

LV CABLE JOINTS SHALL BE INSTALLED ABOVE OTHER LV CABLES. 2.

LV CABLE JOINTS ARE APPROXIMATELY �170mm. 1.