panel designator...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m...

98

Upload: others

Post on 31-Aug-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf
Page 2: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

Site

PARKWAY OFF CENTRAL9436 ULYSSES STREET NEBLAINE, MN 55434

SYSTEM SEQUENCE OF OPERATIONS

PROJECT DIRECTORY

Installer

BERD ELECTRIC3308 SOUTHWAY DRIVEST. CLOUD, MN 56301-9513

Tyco SimplexGrinnell District - 337

5400 NATHAN LANE, SUITE 100PLYMOUTH, MN 55442PHONE: 763-367-5000FAX: 763-367-5002SERVICE: 763-367-5001

OCCUPANCY TYPE(S): SPRINKLER PROTECTION:

APPLICABLE CODES & STANDARDS

ABBREVIATIONS LEGEND

END OF LINE

EXPLOSION PROOF

EMERGENCY POWER OFFFIRE ALARM CONTROL PANELFIRE ALARM TERMINAL CABINETFURNISHED BY OTHERSFIRE COMMAND CENTER

EOL =

XP =

EPO =FACP =FATC =FBO =FCC =

EXISTING TO REMAINCEILING MOUNTEDABOVE CEILING

WEATHERPROOF

RELOCATED DEVICE

DETECTOR

(eg. 15CD) CANDELA

ANNUNCIATORALARM

EXISTING DEVICE TO BE RELOCATED

REMOVE EXISTING AND REPLACE W/NEW

EXISTING TO REMOVE AND COVER

ABOVE FINISHED FLOOR

CALIFORNIA BUILDING CODE

CALIFORNIA STATE FIRE MARSHAL

AUTHORITY HAVING JURISDICTION

BUILDING MANAGEMENT SYSTEM

DATA GATHERING PANEL

RC

=ALM

CBC =

DET =CSFM =

CD =

ANN =BMS =

=DGP

RD =

RR =WP =

=

RL =

=AFFAHJ =

C =E =

AC = ==

=

====

==

=

=

=

==

=

=

=

==

==

===

=

=W/

TYPUON

VTWFW

VCC

TRBL

MAX

NIC

NTS

SMKSLC

NPU

SCC

TACSUPV

MINN/ANAC

NECNDU

NFPA

HT

FSD

HVAC

UNLESS OTHERWISE NOTEDVOICE COMMAND CENTER

WITH

VALVE TAMPERWATER FLOW(eg. 1/2W) WATT

TROUBLE

TYPICAL

MAXIMUM

NOTIFICATION APPLIANCE CIRCUIT EXTENDER

SIGNALING LINE CIRCUIT

NATIONAL ELECTRICAL CODE

NETWORK PROCESSING UNIT

NETWORK DISPLAY UNIT

STATUS COMMAND CENTER

NATIONAL FIRE PROTECTION ASSOCIATION

TRUEALERT ADDRESSABLE CONTROLLER

NOT IN CONTRACT

NOT TO SCALE

SUPERVISORYSMOKE

NOT APPLICABLEMINIMUM

HEATING, VENTILATION, & AIR CONDITIONING

FIRE SMOKE DAMPER

HEIGHT

=W/O WITH OUT

FIRE ALARM ANNUNCIATORFAA =FIRE ALARM TRANSPONDERFTR =

=TS TAMPER SWITCH

=IMS INFORMATION MANAGEMENT SYSTEM

=PAP PRE-ACTION PANEL

HIGH HUMIDITYH =

SIMPLEXGRINNELL CONTACTS

GENERAL NOTES

LEGENDSDRAWING INDEX

DEVICE TAG LEGEND

1:T2:A2:1-1(E1:1)

PANEL DESIGNATOR:· FA: = FACP (NON-NETWORK)· #: = NODE NUMBER· T#: = TRANSPONDER NUMBER· #:T# = NODE:TRANSPONDER NUMBER· N#: = NAC EXTENDER NUMBERCIRCUIT DESIGNATOR:· A#:# = EPS NUMBER:EPS CHANNEL NUMBER· D# = DOOR HOLDER CIRCUIT NUMBER· F# = FIRE PHONE CIRCUIT· H# = AUDIBLE (HORN) CIRCUIT NUMBER· M# = IDNET LOOP NUMBER· P# = POWER CIRCUIT NUMBER· S# = SPEAKER CIRCUIT NUMBER· V# = VISUAL CIRCUIT NUMBER· Z# = ZONE NUMBER

BRANCH / ISOLATED LOOP DESIGNATOR:· (L#) = IDNET ISOLATED LOOP NUMBER· (#) = IDNAC BRANCH NUMBER· (E#:#) = ENHANCED POWER REPEATER NUMBER:BRANCH NUMBER

DEVICE NUMBER

R-2 Residential Group BUILDING ISFULLYSPRINKLED

FIRE ALARM SYSTEM

PARKWAY OFF CENTRAL

PHONE:

Sales Representative

Jon [email protected]

320-237-9020

PHONE:

Project Manager

Nancy [email protected]

763-367-5027

PHONE:

Drawings Prepared By

Dennis [email protected]

320-237-9011

PHONE:

Drawings Reviewed By

Gaston [email protected]

763-367-5038

JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTEDCODE. CHECK WITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS.

1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS IS TO BE DETERMINED IN THE FIELD BY THEINSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.

2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THECONTRACTOR SHALL CONTACT SIMPLEXGRINNELL IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE.

3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THERELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORDDRAWINGS.

4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION.5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED

MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER)SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.

6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO SIMPLEXGRINNELL NO LATER THAN 7 DAYS AFTER FINALTEST.

7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER.8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE.9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO

DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER.10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY

BEING PERFORMED.11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE

INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES. REFER TO 'APPLICABLE CODES &STANDARDS' FOR SPECIFIC CODE REFERENCES.

12. ALL WIRING SHALL BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES.13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH APPLICABLE

ELECTRICAL CODE SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE.14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP.15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATING MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE

FPLR.16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS.17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOORS SHALL BE INSTALLED IN ACCORDANCE APPLICABLE ELECTRICAL CODES, WHERE

APPLICABLE.18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.22. MAINTAIN MAXIMUM CONDUIT FILL RATIO AS PER APPLICABLE ELECTRICAL CODES REQUIREMENTS.23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY; HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS

MEET CURRENT STANDARDS AND CODES. SIMPLEXGRINNELL MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS.

FACP

FAA

F

S

WF

VS

AIM

AOM

DH

QTYSYMBOL

DESCRIPTION MODEL

BOX

CODE

WIRE

TYPE

BRAND

FIRE ALARM SYMBOL LEGEND

FBOWATERFLOW SWITCH

BY OTHERS4

ZBY OTHERS

MFG4100ES FIRE ALARM CONTROL PANEL, 120 VAC 4100-93111 SIMPLEX

1FINDIVIDUAL ADDRESSABLE MODULE

4090-900112

MZ

SIMPLEX

DOOR HOLDERBY OTHERS

8BY

OTHERS

6DSERIAL LCD ANNUCIATOR

4603-91011

BP

SIMPLEX

1AADDRESSABLE STROBE, WALL MOUNT, WHITE, FIRE, CLEARLENS

49VO-WWF18

A4A

SIMPLEX

4APHOTOELECTRIC SMOKE SENSOR WITH STANDARD BASE

4098-9792 BASE4098-9714 HEAD

29M

4KSIMPLEX

4GSINGLE ACTION MANUAL PULL STATION

4099-90041

M1E

SIMPLEX

4AADDRESSABLE MULTI-CANDELA HORN/STROBE, WHITE,FIRE, CLEAR LENS

49AV-WWF70

A1B

SIMPLEX

FBOTAMPER SWITCH

BY OTHERS8

ZBY OTHERS

4HRELAY IAM

4090-900214

MR

SIMPLEX

4" SQ. BOX 1 1/2" DEEP4A

4" SQ. BOX 1 1/2" DEEP W/ COVER4B

SINGLE GANG BOX 2" DEEP1B

SINGLE GANG BOX 2 1/8" DEEP1C

FOR ADDITIONAL BACK BOX OPTIONS, REFER TO THE XX-700 SERIES DRAWINGS OR PRODUCT DATA SHEETS ANDINSTALLATION INSTRUCTIONS.

4" SQ. BOX 1 1/2" DEEP W/ 1 1/2" EXT. RING4C

SINGLE GANG BOX 2 1/8" DEEP W/COVER1D

CODE BOX SPECIFICATIONS CODE BOX SPECIFICATIONS

4" SQ. BOX 2 1/8" DEEP4D

SINGLE GANG BOX 2 1/2" DEEP1E

4" SQ. BOX 2 1/8" DEEP W/ COVER4E

SINGLE GANG BOX 2 1/2" DEEP W/COVER1F

4" SQ. BOX 2 1/8" DEEP W/ 1 1/2" EXT. RING4F

SINGLE GANG BOX 2 3/4" DEEP1G

4" SQ. BOX 2 1/8" DEEP W/ SINGLE GANG COVER4G

SINGLE GANG BOX 3 1/2" DEEP1H

4" SQ. BOX 2 1/8" DEEP W/ TWO GANG COVER4H

DOUBLE GANG BOX 2" DEEP2A

4" SQ. BOX 2 1/2" DEEP4J

TWO GANG BOX 2 1/2" DEEP2B

4" OCT. BOX 1 1/2" DEEP4K

TWO GANG BOX 2 3/4" DEEP2C

4" OCT. BOX 1 1/2" DEEP W/ 1 1/2" EXT. RING4L

HANDY BOX 1 1/2" DEEPHB

4 11/16" SQ. BOX 2 1/8" DEEP4M

6 SINGLE GANG BOXES 3 1/2" DEEP6A

4 11/16" SQ. BOX 1 1/2" DEEP W/ 1 1/2" EXT. RING4N

6 GANG BOX 6B

4 11/16" SQ. BOX 2 1/8" DEEP W/ 1 1/2" EXT. RING4P

FURNISHED BY OTHERSFBO

SINGLE GANG BOX 1 1/2" DEEP1A

SUPPLIED BY MANUFACTURERMFG

MOUNTS TO DUCTWORKMDW

MOUNTS IN BOX BEHIND DETECTORMBD

WALL MOUNTWM

DESK TOP MOUNTDT

NO BACKBOX REQUIREDNR

3.5" WIDE SNAP TRACK W/MOUNTING SCREWSTRM

4APHOTOELECTRIC SMOKE SENSOR WITH SOUNDER BASE

4098-9772 BASE4098-9714 HEAD

461M

4K VSIMPLEXS

SB

MFG4009 IDNET NAC EXTENDER PANEL, BEIGE, 120 VAC 4009-92018

VSIMPLEXNAC#

MAX CONDUCTOR AREACONDUIT SIZE CONDUIT SIZE

ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION.THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THEABOVE REQUIREMENTS. RECOMMENDED CABLE MANUFACTURERS AND MODEL NUMBERS ARE AVAILABLE UPON REQUEST.

1/2"3/4"1"

0.12 SQ INCH *0.21 SQ INCH *0.34 SQ INCH *

1-1/4"1-1/2"

2"

0.60 SQ INCH *0.82 SQ INCH *1.34 SQ INCH *

NOTES

*40% FILL PER N.E.C.SUBSCRIPT "u": UNSHIELDED CABLES MIXED WITH SHIELDEDCABLES OF SAME CIRCUIT DESIGNATION.

MAX CONDUCTOR AREA

**OUTDOOR AERIAL CABLE REQUIRES MESSENGER

THHN / TFFN FPLPFPLR

CIRCUIT DESCRIPTION

ACCEPTABLE CABLE TYPES

CONSTRUCTION GAUGE CIRCUIT PROPERTIES

OUTDOOR

FIRE ALARM WIRE LIST

14 AWG XA ADDRESSABLE NOTIFICATION UTP SOLID X60pf/ft. MAX CAPACITANCE; 3

twists/ft. RECOMMENDED

18 AWG XB RUI+ COMMUNICATION UTP SOLID X60pf/ft. MAX CAPACITANCE; 3

twists/ft. RECOMMENDED

14 AWG X XD DOOR HOLDER TP SOLID X

18 AWG X XK REMOTE TEST SWITCH/LED (2) 2 COND. SOLID X

18 AWG XM IDNET UTP SOLID X

14 AWG X XP POWER 2 COND. SOLID X

14 AWG X XR RELAY 2 COND. SOLID X

16 AWG XS AUDIO UTP SOLID X30pf/ft. MAX CAPACITANCE

RECOMMENDED

18 AWG X XZ ZONE (IDC) 2 COND. SOLID X

14 AWG X XV VISUAL SIGNAL 2 COND. SOLID X

SCOPE OF WORK

PROVIDE AND INSTALL A NEW AUTOMATIC AND MANUAL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS.

ALL WIRING TO BE CLASS B NOTIFICATION APPLIANCE CIRCUITS, INITIATING DEVICE CIRCUITS, AND SIGNALING LINE CIRCUITS.

AUTOMATIC FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION. THESUPERVISING STATION SHALL BE LISTED AS EITHER UUFX OR UUJS UNDERWRITERS LABORATORY OR SHALL MEET THE REQUIREMENTS OF FACTORY MUTUALRESEARCH APPROVAL STANDARD 3011. SUPERVISION OF SYSTEM AND LEASED TELEPHONE LINES SHALL BE ARRANGED BY THE OWNER.

DESIGN STATEMENT

THIS PROJECT'S DESIGN IS BASED ON THE ENGINEERED PLANS AND SPECIFICATIONS PREPARED BY: AMCON CONSTRUCTION COMPANY

ARCHITECTURAL PLANS DATED: 2/18/16

MECHANICAL PLANS DATED: -

ELECTRICAL PLANS DATED: -

SPECIFICATIONS DATED: -

ADDENDUM DATED: -

International Fire Code (IFC), 2012 Edition w/ 2015 MN State Amendments

National Electric Code, 2014 Edition (MN State Building Code, MN Rules Chapter 1315)

ASME A17.1/CSA B44-2010; ASME A17.3-2011; ASME A17.5-2011 (MN MN Rules, Chapter 1307)

TM

Safer. Smarter. Tyco.

SimplexGrinnell

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-0

00.d

wg

9/13

/201

6 9:

51:4

8 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-000

COVER SHEET

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

ACTU

ATE A

UDIBL

E TRO

UBLE S

IGNA

L

ACTU

ATE A

UDIBL

E SUPE

RVISO

RY SI

GNAL

ACTU

ATE C

OMMON TR

OUBLE S

IGNA

L IND

ICAT

OR

ACTU

ATE A

UDIBL

E ALA

RM SI

GNAL

SYSTEM INPUTS

ACTU

ATE C

OMMON AL

ARM SI

GNAL I

NDIC

ATOR

SYST

EM O

UTPUTS

TRAN

SMIT

SUPV

. SIG

NAL T

O SUPE

RVISI

NG ST

ATIO

N

REMARKS

CONTROL UNIT ANNUNCIATION NOTIFICATION FIRE SAFETY CONTROL

ACTU

ATE C

OMMON SU

PERV

ISORY

SIGNA

L IND

ICAT

OR

ACTU

ATE A

PPRO

PRIA

TE LO

CATI

ON IN

DICA

TOR

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC

TRAN

SMIT

ALA

RM SI

GNAL T

O SUPE

RVISI

NG ST

ATIO

N

TRAN

SMIT

TRO

UBLE S

IGNA

L TO SU

PERV

ISING

STAT

ION

AD

123456789101112131415161718192021222324252627282930

AE AF AG

31

AH32

AI AJ

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ1234567891011121314151617181920212223242526272829303132

SMOKE SENSOR/DETECTORSMOKE/HEAT SENSOR W/ SOUNDER BASEMANUAL PULL STATION

ELEVATOR MECH. ROOM HEAT DETECTORELEVATOR MECH. ROOM SMOKE DETECTOR

ELEVATOR SHAFT SMOKE DETECTOR

MAIN FLR. ELEV. LOBBY SMOKE DETECTORELEVATOR LOBBY SMOKE DETECTORS (EXC. MAIN FLR.)

ELEVATOR SHAFT HEAT DETECTOR

ELEVATOR POWER MONITOR

MAIN

FLOOR

ELEV

ATOR

RECA

LL

ALTE

RNAT

E FLO

OR EL

EVAT

OR RE

CALL

RELE

ASE E

LEVA

TOR

FIRE D

OORSEL

EVAT

OR SH

UNT T

RIP

ELEV

ATOR

HAT FL

ASH

WATERFLOW SWITCHTAMPER SWITCHPOST INDICATOR VALVE SWITCHFIRE ALARM AC POWER FAILUREFIRE ALARM SYSTEM LOW BATTERY

CLASS B NOTIFICATION CIRCUIT (NAC) - SHORTOPEN CIRCUIT OR GROUND FAULT

ACTU

ATE A

LL VIS

IBLE E

VACU

ATION S

IGNALS

ACTU

ATE A

LL AU

DIBLE

EVAC

UATION S

IGNALS

REMOTE

LY D

ISPLA

Y AC

TIVE

STAT

US

DISP

LAY

CHAN

GE OF S

TATU

S

DRAWING INDEX

DWG# DESCRIPTION

General Information (FA-000 Series)

FA-000 COVER SHEETFloorplans (FA-100 Series)

FA-101 GARAGE DEVICE PLACEMENT PLAN

FA-102 1ST FLOOR DEVICE PLACEMENT PLAN

FA-103 2ND FLOOR DEVICE PLACEMENT PLAN

FA-104 3RD FLOOR DEVICE PLACEMENT PLAN

FA-105 4TH FLOOR DEVICE PLACEMENT PLANRisers (FA-200 Series)

FA-201 RISER DIAGRAM

FA-202 RISER DIAGRAMPanel Details (FA-500 Series)

FA-501 PANEL LAYOUTCalculations (FA-600 Series)

FA-601 CALCULATIONS AND SCHEDULES

FA-602 CALCULATIONS AND SCHEDULES

FA-603 CALCULATIONS AND SCHEDULES

FA-604 CALCULATIONS AND SCHEDULESTypical Details (FA-700 Series)

FA-701 WIRING TYPICALS

s:\1-current projects\7555-parkway off central\Fire\FA-000.dwg, FA-000 COVER SHEET, 9/13/2016 9:51:47 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 3: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

GENERAL NOTES

2-WAY COMMUNICATIONS SYSTEM

PARKWAY OFF CENTRAL

1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS IS TO BE DETERMINED IN THE FIELD BY THEINSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.

2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THECONTRACTOR SHALL CONTACT SIMPLEXGRINNELL IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE.

3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THERELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORDDRAWINGS.

4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION.5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED

MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER)SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.

6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO SIMPLEXGRINNELL NO LATER THAN 7 DAYS AFTER FINALTEST.

7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER.8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE.9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO

DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER.10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY

BEING PERFORMED.11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE

INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES. REFER TO 'APPLICABLE CODES &STANDARDS' FOR SPECIFIC CODE REFERENCES.

12. ALL WIRING SHALL BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES.13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH APPLICABLE

ELECTRICAL CODE SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE.14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP.15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATING MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE

FPLR.16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS.17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOORS SHALL BE INSTALLED IN ACCORDANCE APPLICABLE ELECTRICAL CODES, WHERE

APPLICABLE.18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.22. MAINTAIN MAXIMUM CONDUIT FILL RATIO AS PER APPLICABLE ELECTRICAL CODES REQUIREMENTS.23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY; HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS

MEET CURRENT STANDARDS AND CODES. SIMPLEXGRINNELL MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS.

TM

Safer. Smarter. Tyco.

SimplexGrinnell

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-0

00.d

wg

9/13

/201

6 9:

51:4

9 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-001

2-WAY COVER SHEET

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

LEGENDS

QTYSYMBOL

DESCRIPTION MODEL

BOX

CODE

WIRE

TYPE

BRAND

2-WAY COMM. SYMBOL LEGEND

MFGRESCUE ASSISTANCE ANNUNCIATOR, 5 ZONE 2500-105PSS1 RATH

MFGCALL BOX, FLUSH MOUNTW/ SIGN 7044

2100-958SR10 RATH

2WAYM

2WAY

FOR ADDITIONAL BACK BOX OPTIONS, REFER TO THE XX-700 SERIES DRAWINGS OR PRODUCT DATA SHEETS ANDINSTALLATION INSTRUCTIONS.

CODE BOX SPECIFICATIONS CODE BOX SPECIFICATIONS

FURNISHED BY OTHERSFBO SUPPLIED BY MANUFACTURERMFG

MFGPOWER SUPPLY

2500-PWR241 RATH2WPS

MAX CONDUCTOR AREACONDUIT SIZE CONDUIT SIZE

ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION.THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR SELECTING AND INSTALLING CABLE MANUFACTURER AND MODEL THAT MEETS OR EXCEEDS THEABOVE REQUIREMENTS. RECOMMENDED CABLE MANUFACTURERS AND MODEL NUMBERS ARE AVAILABLE UPON REQUEST.

1/2"3/4"1"

0.12 SQ INCH *0.21 SQ INCH *0.34 SQ INCH *

1-1/4"1-1/2"

2"

0.60 SQ INCH *0.82 SQ INCH *1.34 SQ INCH *

NOTES

*40% FILL PER N.E.C.SUBSCRIPT "u": UNSHIELDED CABLES MIXED WITH SHIELDEDCABLES OF SAME CIRCUIT DESIGNATION.

MAX CONDUCTOR AREA

**OUTDOOR AERIAL CABLE REQUIRES MESSENGER

THHN / TFFN FPLPCM

CIRCUIT DESCRIPTION

ACCEPTABLE CABLE TYPES

CONSTRUCTION GAUGE CIRCUIT PROPERTIES

OUTDOOR

2-WAY COMM. WIRE LIST

18 AWG X XP POWER 2 COND. SOLID 500 FT MAX. DISTANCE

22 AWG X XR CALL BOXES/RESCUE STATIONTO BASE STATION

(2) 2 COND. SOLID 500 FT MAX. DISTANCE

CAT 3 XT TELEPHONE UTP SOLID 300 FT MAX. DISTANCE

ABBREVIATIONS LEGEND

END OF LINE

EXPLOSION PROOF

EMERGENCY POWER OFFFIRE ALARM CONTROL PANELFIRE ALARM TERMINAL CABINETFURNISHED BY OTHERSFIRE COMMAND CENTER

EOL =

XP =

EPO =FACP =FATC =FBO =FCC =

EXISTING TO REMAINCEILING MOUNTEDABOVE CEILING

WEATHERPROOF

RELOCATED DEVICE

DETECTOR

(eg. 15CD) CANDELA

ANNUNCIATORALARM

EXISTING DEVICE TO BE RELOCATED

REMOVE EXISTING AND REPLACE W/NEW

EXISTING TO REMOVE AND COVER

ABOVE FINISHED FLOOR

CALIFORNIA BUILDING CODE

CALIFORNIA STATE FIRE MARSHAL

AUTHORITY HAVING JURISDICTION

BUILDING MANAGEMENT SYSTEM

DATA GATHERING PANEL

RC

=ALM

CBC =

DET =CSFM =

CD =

ANN =BMS =

=DGP

RD =

RR =WP =

=

RL =

=AFFAHJ =

C =E =

AC = ==

=

====

==

=

=

=

==

=

=

=

==

==

===

=

=W/

TYPUON

VTWFW

VCC

TRBL

MAX

NIC

NTS

SMKSLC

NPU

SCC

TACSUPV

MINN/ANAC

NECNDU

NFPA

HT

FSD

HVAC

UNLESS OTHERWISE NOTEDVOICE COMMAND CENTER

WITH

VALVE TAMPERWATER FLOW(eg. 1/2W) WATT

TROUBLE

TYPICAL

MAXIMUM

NOTIFICATION APPLIANCE CIRCUIT EXTENDER

SIGNALING LINE CIRCUIT

NATIONAL ELECTRICAL CODE

NETWORK PROCESSING UNIT

NETWORK DISPLAY UNIT

STATUS COMMAND CENTER

NATIONAL FIRE PROTECTION ASSOCIATION

TRUEALERT ADDRESSABLE CONTROLLER

NOT IN CONTRACT

NOT TO SCALE

SUPERVISORYSMOKE

NOT APPLICABLEMINIMUM

HEATING, VENTILATION, & AIR CONDITIONING

FIRE SMOKE DAMPER

HEIGHT

=W/O WITH OUT

FIRE ALARM ANNUNCIATORFAA =FIRE ALARM TRANSPONDERFTR =

=TS TAMPER SWITCH

=IMS INFORMATION MANAGEMENT SYSTEM

=PAP PRE-ACTION PANEL

HIGH HUMIDITYH =

SCALE: NTS

TYPICAL WIRING

SCALE: NTS

RISER DIAGRAM

120 VOLT AC

FA-101 FA-101

FA-102 FA-102

2WAYMT LOCATE NEXT TO FAA IN VEST. 005

FA-103 FA-103

2WAYP,R

FA-104 FA-104

2WAYP,R

8P,8R

4P,4R

2WPSM

11P

NOTE: HOMERUN POWERTO POWER SUPPLY ASSHOWN IN DETAIL.

FA-105 FA-105

2WAYP,R

2WAYP,RP,R

2WAY

P,R2WAY

2P,2R

6P,6R

P,R2WAY

P,R2WAY

2WAYP,RP,R

2WAYLOCATE IN ELEVATOR LOBBY (TYPICAL)

s:\1-current projects\7555-parkway off central\Fire\FA-000.dwg, FA-001 2-WAY COVER SHEET, 9/13/2016 9:51:48 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 4: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

WF AIM M1-8

VS

AIM M1-9WF

AIM M1-10WF

AIM M1-11WF

AIM M1-12

AIM M1-13VS

VS AIM M1-18

AIM M1-19VS

VS AIM M1-16

AIM M1-17VS

VS AIM M1-14

AIM M1-15VS

75

A1:1-5(1)

75

A1:1-4(1)

75

A1:1-3(1)

75A1:1-1(1)

75

A1:1-2(1)

75A1:1-6(2)

75A1:1-7(2)

75A1:1-8(2)

75A1:1-9(2)

75A1:1-10(2)

75A1:1-11(2)

75

A1:1-16(2)

75

A1:1-15(2)

75

A1:1-14(2)

75

A1:1-13(2)

75A1:1-12(2)

S

M1-20

S

M1-2

S M1-21

AOMPRI

M1-22AOM

ALTM1-23

AOMFIREHAT

M1-24

S M1-4

AOMPRI

M1-5AOM

ALTM1-6

AOMFIREHAT

M1-7

2WAY

2WAY

2WAY M

FACP

FAA

1

1

1

F

M1-3

S

M1-1

AA

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

GENERAL NOTES:

1. ALL CEILINGS ARE ASSUMED TO BE 10' A.F.F., SMOOTH CONSTRUCTION UNLESS NOTEDOTHERWISE.2. ALL NOTIFICATION APPLIANCE CANDELA INTENSITY PLUGS SHALL RETAIN THEIR FACTORYSETTING OF "FACP" UNLESS OTHERWISE DIRECTED BY THE AUTHORITY HAVING JURISDICTION.3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON' FOR NAC CIRCUITSUPERVISION.

KEYNOTES:

VERIFY EXACT LOCATION IN FIELD.1

(IN FEET)0

SCALE:

PLANNORTH

1/16" = 1'-0"8 16 32

GARAGE DEVICE PLACEMENT PLAN

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-1

01.d

wg

9/13

/201

6 9:

51:5

3 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-101

GARAGE DEVICE

PLACEMENT PLAN

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-101.dwg, FA-101 GARAGE DEVICE PLACEMENT PLAN, 9/13/2016 9:51:52 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
110
AutoCAD SHX Text
POOL EQUIP.
AutoCAD SHX Text
113
AutoCAD SHX Text
MECH
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
001
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
001
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
001
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
002
AutoCAD SHX Text
STAIR "A"
AutoCAD SHX Text
003
AutoCAD SHX Text
TRASH/RECYCLE #1
AutoCAD SHX Text
007
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
009
AutoCAD SHX Text
ELEV EQUIP
AutoCAD SHX Text
006
AutoCAD SHX Text
STAIR "C"
AutoCAD SHX Text
004
AutoCAD SHX Text
STAIR "B"
AutoCAD SHX Text
005
AutoCAD SHX Text
VEST.
AutoCAD SHX Text
008
AutoCAD SHX Text
ELEV #1
AutoCAD SHX Text
010
AutoCAD SHX Text
MECH
AutoCAD SHX Text
012
AutoCAD SHX Text
STAIR "D"
AutoCAD SHX Text
015
AutoCAD SHX Text
ELEV #2
AutoCAD SHX Text
014
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
016
AutoCAD SHX Text
TRASH/RECYCLE #2
AutoCAD SHX Text
017
AutoCAD SHX Text
ELEV. EQUIP
AutoCAD SHX Text
018
AutoCAD SHX Text
STAIR "E"
Page 5: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

15

A1:2-4(1)

15

A1:2-3(1)

15

A1:2-2(1)

15A1:2-12(1)

30A1:2-11(1)

75A1:2-6(1)

15A1:2-1(1)

15A1:2-7(1)

15A1:2-8(1)

15A1:2-9(1)

15A1:2-10(1)

15A1:2-13(1)

185A1:2-14(1)

15A1:2-23(1)

185

A1:2-24(1)

15A1:2-15(2)

15A1:2-16(2)

15A1:2-17(2)

15A1:2-19(2)

15A1:2-18(2)

15

A1:2-21(2)

15

A1:2-20(2)

15

A1:2-22(2)

S

M1-80

S

M1-34

2WAY

2WAY

SSB

M1-57

N1:H2-12

SSB

M1-45

N1:H1-11

SSB

M1-55

N1:H2-10

SSB

M1-54

N1:H2-9

SSB

M1-43

N1:H1-9

SSB

M1-52

N1:H2-7

SSB

M1-51

N1:H2-6

SSB

M1-41

N1:H1-7

SSB

M1-40

N1:H1-6

SSB

M1-38

N1:H1-4

SSB

M1-37

N1:H1-3

SSB

M1-48

N1:H2-3

SSB

M1-47

N1:H2-2

SSB

M1-46

N1:H2-1 SSB

M1-35

N1:H1-1

SSB

M1-56N1:H2-11

SSB

M1-44

N1:H1-10

SSB

M1-53

N1:H2-8

SSB

M1-42

N1:H1-8

SSB

M1-50

N1:H2-5

SSB

M1-49N1:H2-4

SSB

M1-39

N1:H1-5

SSB

M1-36

N1:H1-2

SSB

M1-98

N1:H4-1

SSB

M1-100

N1:H4-3S

SB

M1-99

N1:H4-2

SSB

M1-101

N1:H4-4 SSB

M1-102

N1:H4-5

SSB

M1-103

N1:H4-6

SSB

M1-104

N1:H4-7

SSB

M1-105

N1:H4-8

SSB

M1-106

N1:H4-9S

SB

M1-107

N1:H4-10S

SB

M1-109

H3-2

SSB

M1-108

H3-1

SSB

M1-110

H3-3

SSB

M1-111

H3-4S

SB

M1-113

H3-6SSB

M1-112

H3-5

SSB

M1-114

H3-7

SSB

M1-115

H3-8

SSB

M1-116

H3-9S

SB

M1-117

H3-10

SSB

M1-118

N2:H4-13

SSB

M1-119

N2:H4-12

SSB

M1-120

N2:H4-11 SSB

M1-121

N2:H4-10

SSB

M1-122

N2:H4-9

SSB

M1-124

N2:H4-7S

SB

M1-123

N2:H4-8

SSB

M1-125

N2:H4-6

SSB

M1-127

N2:H4-4

SSB

M1-128

N2:H4-3

SSB

M1-126

N2:H4-5

SSB

M1-59

N1:H3-2

SSB

M1-60

N1:H3-3S

SB

M1-62

N1:H3-5

SSB

M1-63

N1:H3-6

SSB

M1-64

N1:H3-7

SSB

M1-58

N1:H3-1

SSB

M1-61

N1:H3-4

SSB

M1-65

N1:H3-8S

SB

M1-66

N1:H3-9S

SB

M1-67

N2:H3-13

SSB

M1-69

N2:H3-11

SSB

M1-68

N2:H3-12 SSB

M1-70

N2:H3-10

SSB

M1-72

N2:H3-8

SSB

M1-71

N2:H3-9S

SB

M1-73

N2:H3-7S

SB

M1-75

N2:H3-5

SSB

M1-76

N2:H3-4

SSB

M1-74

N2:H3-6S

SB

M1-77

N2:H3-3 SSB

M1-78

N2:H3-2

SSB

M1-79

N2:H3-1

SSB

M1-130

N2:H4-1

SSB

M1-129

N2:H4-2

SSB

M1-132

N2:H2-2

SSB

M1-133

N2:H2-3

SSB

M1-131

N2:H2-1

SSB

M1-134

N2:H2-4

SSB

M1-135

N2:H2-5

SSB

M1-86

N2:H1-3

SSB

M1-84

N2:H1-1

SSB

M1-85

N2:H1-2

SSB

M1-88

N2:H1-5

SSB

M1-87

N2:H1-4

SSB

M1-136

N2:H2-6

SSB

M1-137

N2:H2-7

SSB

M1-138

N2:H2-8

SSB

M1-139

N2:H2-9

SSB

M1-140

N2:H2-10

SSB

M1-141

N2:H2-11

SSB

M1-89

N2:H1-6

SSB

M1-91

N2:H1-8

SSB

M1-90

N2:H1-7

SSB

M1-92

N2:H1-9

SSB

M1-93

N2:H1-10

SSB

M1-94

N2:H1-11

SSB

M1-142

N2:H2-12

SSB

M1-143

N2:H2-13

SSB

M1-144

N2:H2-14

SSB

M1-145

N2:H2-15S

SB

M1-97

N2:H1-14

SSB

M1-95

N2:H1-12 SSB

M1-96

N2:H1-13

D1-12DH

D1-11DH

NAC2M1-83

S M1-82

NAC1 M1-31

S M1-32

15

A1:2-5(1)

AOMDAMPER CONTROL

M1-811

AOMDAMPER CONTROL

M1-331

N1:H110KN1:H2

10K

N1:H310K

N1:H410K

H310K

N2:H110K

N2:H210K

N2:H310K

N2:H410K

AA

V V

VV

V

S

M1-146

S

M1-147

VV

V

V

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

GENERAL NOTES:

1. ALL CEILINGS ARE ASSUMED TO BE 10' A.F.F., SMOOTH CONSTRUCTION UNLESS NOTEDOTHERWISE.2. ALL NOTIFICATION APPLIANCE CANDELA INTENSITY PLUGS SHALL RETAIN THEIR FACTORYSETTING OF "FACP" UNLESS OTHERWISE DIRECTED BY THE AUTHORITY HAVING JURISDICTION.3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON' FOR NAC CIRCUITSUPERVISION.

KEYNOTES:

VERIFY EXACT LOCATION IN FIELD.1

(IN FEET)0

SCALE:

PLANNORTH

1/16" = 1'-0"8 16 32

1ST FLOOR DEVICE PLACEMENT PLAN

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-1

02.d

wg

9/13

/201

6 9:

51:5

8 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-102

1ST FLOOR DEVICE

PLACEMENT PLAN

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-102.dwg, FA-102 1ST FLOOR DEVICE PLACEMENT PLAN, 9/13/2016 9:51:56 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

AutoCAD SHX Text
UNIT 142
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 143
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 141
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 140
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 139
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 138
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 137
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 136
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 135
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 134
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 133
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 132
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 131
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 130
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 129
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 128
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 126
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 127
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 125
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 124
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 123
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 122
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 121
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 119
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 120
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 117
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 118
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 116
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 115
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 114
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 113
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 112
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 111
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 110
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 109
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 108
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 107
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 106
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 105
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 104
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 103
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 102
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 101
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 100
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
144
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
144
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
144
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
RA
AutoCAD SHX Text
PLENM
AutoCAD SHX Text
RA
AutoCAD SHX Text
PLENM
AutoCAD SHX Text
RA
AutoCAD SHX Text
PLENM
AutoCAD SHX Text
RA
AutoCAD SHX Text
PLENM
AutoCAD SHX Text
146
AutoCAD SHX Text
GROUP FITNESS
AutoCAD SHX Text
147
AutoCAD SHX Text
FITNESS CENTER
AutoCAD SHX Text
150
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
149
AutoCAD SHX Text
MEN
AutoCAD SHX Text
148
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
152
AutoCAD SHX Text
THEATRE
AutoCAD SHX Text
153
AutoCAD SHX Text
COMMUNITY ROOM
AutoCAD SHX Text
154
AutoCAD SHX Text
MAIL ROOM
AutoCAD SHX Text
160
AutoCAD SHX Text
CONF. ROOM
AutoCAD SHX Text
161
AutoCAD SHX Text
WORK ROOM
AutoCAD SHX Text
165
AutoCAD SHX Text
ELECT ROOM
AutoCAD SHX Text
158
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
162
AutoCAD SHX Text
RECEPT
AutoCAD SHX Text
163
AutoCAD SHX Text
OFFICE #1
AutoCAD SHX Text
164
AutoCAD SHX Text
OFFICE #2
AutoCAD SHX Text
155
AutoCAD SHX Text
MECH. ROOM
AutoCAD SHX Text
156
AutoCAD SHX Text
STAIR "B"
AutoCAD SHX Text
159
AutoCAD SHX Text
STAIR "C"
AutoCAD SHX Text
157
AutoCAD SHX Text
ELEV #1
AutoCAD SHX Text
166
AutoCAD SHX Text
ELEV #2
AutoCAD SHX Text
170
AutoCAD SHX Text
ELECT/MECH
AutoCAD SHX Text
168
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
167
AutoCAD SHX Text
ELEV LOBBY
AutoCAD SHX Text
169
AutoCAD SHX Text
TRASH #2
Page 6: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

A A

V

VV

V

V

V

V

V

V

15

A1:3-4(1)

15

A1:3-3(1)

15

A1:3-2(1)

15A1:3-1(1)

15

A1:3-11(1)

185

A1:3-10(1)

15A1:3-6(1)

15A1:3-12(2)

15A1:3-13(2)

15A1:3-15(2)

15A1:3-14(2)

15A1:3-17(1)

15A1:3-16(1)

15A1:3-18(1)S

M2-54(L1)

SM3-4

2WAY

2WAY

SSB

M2-13(L1)

N3:H1-12

SSB

M2-12(L1)

N3:H1-11

SSB

M2-15(L1)

N3:H1-14

SSB

M2-28(L1)

N3:H2-13

SSB

M2-10(L1)

N3:H1-9

SSB

M2-26(L1)

N3:H2-11

SSB

M2-25(L1)

N3:H2-10

SSB

M2-8(L1)

N3:H1-7

SSB

M2-7(L1)

N3:H1-6

SSB

M2-5(L1)

N3:H1-4

SSB

M2-4(L1)

N3:H1-3

SSB

M2-22(L1)

N3:H2-7

SSB

M2-21(L1)N3:H2-6

SSB

M2-2(L1)

N3:H1-1

SSB

M2-14(L1)

N3:H1-13

SSB

M2-11(L1)

N3:H1-10

SSB

M2-27(L1)N3:H2-12

SSB

M2-9(L1)

N3:H1-8

SSB

M2-24(L1)

N3:H2-9

SSB

M2-23(L1)N3:H2-8

SSB

M2-6(L1)

N3:H1-5

SSB

M2-3(L1)

N3:H1-2

SSB

M2-75(L1)

N3:H4-5

SSB

M2-77(L1)

N3:H4-7S

SB

M2-76(L1)

N3:H4-6

SSB

M2-78(L1)

N3:H4-8 SSB

M2-79(L1)

N3:H4-9

SSB

M2-80(L1)

N3:H4-10

SSB

M2-81(L1)

N3:H4-11

SSB

M2-82(L1)

N3:H4-12 SSB

M2-83(L1)

N3:H4-13S

SB

M2-84(L1)

H4-1S

SB

M2-86(L1)

H4-3

SSB

M2-85(L1)

H4-2

SSB

M2-87(L1)

H4-4

SSB

M2-88(L1)

H4-5S

SB

M2-90(L1)

H4-7SSB

M2-89(L1)

H4-6

SSB

M2-91(L1)

H4-8

SSB

M2-92(L1)

H4-9

SSB

M2-93(L1)

N4:H4-15S

SB

M2-94(L1)

N4:H4-14

SSB

M2-95(L1)

N4:H4-13

SSB

M2-96(L1)

N4:H4-12

SSB

M2-97(L1)

N4:H4-11 SSB

M2-98(L1)

N4:H4-10

SSB

M2-99(L1)

N4:H4-9S

SB

M2-101(L1)

N4:H4-7S

SB

M2-100(L1)

N4:H4-8

SSB

M2-102(L1)

N4:H4-6

SSB

M2-104(L1)

N4:H4-4

SSB

M2-105(L1)

N4:H4-3

SSB

M2-103(L1)

N4:H4-5

SSB

M2-33(L1)

N3:H3-5

SSB

M2-34(L1)

N3:H3-6

SSB

M2-36(L1)

N3:H3-8

SSBM2-37(L1)

N3:H3-9

SSB

M2-38(L1)

N3:H3-10

SSB

M2-32(L1)

N3:H3-4

SSB

M2-35(L1)N3:H3-7

SSB

M2-39(L1)

N3:H3-11S

SB

M2-40(L1)

N3:H3-12S

SB

M2-41(L1)

N4:H3-13

SSB

M2-43(L1)

N4:H3-11

SSB

M2-42(L1)

N4:H3-12 SSB

M2-44(L1)

N4:H3-10

SSB

M2-46(L1)

N4:H3-8

SSB

M2-45(L1)

N4:H3-9S

SB

M2-47(L1)

N4:H3-7S

SB

M2-49(L1)

N4:H3-5

SSB

M2-50(L1)

N4:H3-4

SSB

M2-48(L1)

N4:H3-6S

SB

M2-51(L1)

N4:H3-3 SSB

M2-52(L1)

N4:H3-2

SSB

M2-53(L1)

N4:H3-1

SSB

M2-107(L1)

N4:H4-1

SSB

M2-106(L1)

N4:H4-2

SSB

M2-109(L1)

N4:H2-2

SSB

M2-110(L1)

N4:H2-3

SSB

M2-108(L1)

N4:H2-1

SSB

M2-111(L1)

N4:H2-4

SSB

M2-112(L1)

N4:H2-5

SSB

M2-59(L1)

N4:H1-3

SSB

M2-57(L1)

N4:H1-1

SSB

M2-58(L1)

N4:H1-2

SSB

M2-61(L1)

N4:H1-5

SSB

M2-60(L1)

N4:H1-4

SSB

M2-113(L1)

N4:H2-6

SSB

M2-114(L1)N4:H2-7

SSB

M2-115(L1)

N4:H2-8

SSB

M2-116(L1)

N4:H2-9

SSB

M2-117(L1)

N4:H2-10

SSB

M2-118(L1)N4:H2-11

SSB

M2-62(L1)

N4:H1-6

SSB

M2-64(L1)

N4:H1-8

SSB

M2-63(L1)N4:H1-7

SSB

M2-65(L1)

N4:H1-9

SSB

M2-66(L1)

N4:H1-10

SSB

M2-67(L1)

N4:H1-11

SSB

M2-119(L1)

N4:H2-12

SSB

M2-120(L1)

N4:H2-13

SSB

M2-121(L1)

N4:H2-14

SSB

M2-122(L1)

N4:H2-15S

SB

M2-70(L1)

N4:H1-14

SSB

M2-68(L1)

N4:H1-12

SSB

M2-69(L1)N4:H1-13

15A1:3-5(1)

SSB

M2-19(L1)

N3:H2-4

SSB

M2-20(L1)

N3:H2-5

SSB

M2-18(L1)

N3:H2-3

SSB

M2-17(L1)

N3:H2-2

SSB

M2-16(L1)N3:H2-1

SSB

M2-71(L1)

N3:H4-1

SSB

M2-73(L1)

N3:H4-3

SSB

M2-72(L1)

N3:H4-2

SSB

M2-74(L1)

N3:H4-4

SSB

M2-31(L1)

N3:H3-3

SSB

M2-29(L1)

N3:H3-1

SSB

M2-30(L1)

N3:H3-2

15A1:3-7(1)

185A1:3-9(1) 185

A1:3-8(1)

D1-22DH

D1-21DH

15A1:3-19(1)

185A1:3-20(1)

185A1:3-21(1)

15

A1:3-22(1)

NAC4 M2-56(L1)

S

M2-55(L1)

NAC3

M3-2

S

M3-1

AOMDAMPER CONTROL

M2-123(L1)1AOM

DAMPER CONTROL

M3-31

N3:H110K

N3:H210K

N3:H310K

N3:H410K

N4:H310K

H410K

N4:H410K

N4:H210KN4:H1

10K

S

M2-1(L1)

SM2-124(L1)

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

GENERAL NOTES:

1. ALL CEILINGS ARE ASSUMED TO BE 10' A.F.F., SMOOTH CONSTRUCTION UNLESS NOTEDOTHERWISE.2. ALL NOTIFICATION APPLIANCE CANDELA INTENSITY PLUGS SHALL RETAIN THEIR FACTORYSETTING OF "FACP" UNLESS OTHERWISE DIRECTED BY THE AUTHORITY HAVING JURISDICTION.3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON' FOR NAC CIRCUITSUPERVISION.

KEYNOTES:

VERIFY EXACT LOCATION IN FIELD.1

(IN FEET)0

SCALE:

PLANNORTH

1/16" = 1'-0"8 16 32

2ND FLOOR DEVICE PLACEMENT PLAN

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-1

03.d

wg

9/13

/201

6 9:

52:0

4 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-103

2ND FLOOR DEVICE

PLACEMENT PLAN

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-103.dwg, FA-103 2ND FLOOR DEVICE PLACEMENT PLAN, 9/13/2016 9:52:02 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UNIT 234
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 232
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 231
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 230
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 229
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 228
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 226
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 227
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 225
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 224
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 223
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 222
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 221
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 219
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 220
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 217
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 218
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 216
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 215
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 214
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 213
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 212
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 211
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 210
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 209
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 208
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 207
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 206
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 205
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 204
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 203
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 202
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 201
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 200
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 235
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 236
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 237
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 239
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 238
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 241
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 240
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 242
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 244
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 243
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 245
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 246
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 247
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 248
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 233
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
244
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
244
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
244
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
253
AutoCAD SHX Text
MECH
AutoCAD SHX Text
254
AutoCAD SHX Text
STAIR "B"
AutoCAD SHX Text
257
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
259
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
258
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
256
AutoCAD SHX Text
FLOOR LOBBY
AutoCAD SHX Text
255
AutoCAD SHX Text
ELEV #1
AutoCAD SHX Text
260
AutoCAD SHX Text
ELEV LOBBY
AutoCAD SHX Text
262
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
261
AutoCAD SHX Text
ELEV #2
AutoCAD SHX Text
264
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
263
AutoCAD SHX Text
TRASH ROOM
Page 7: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

A

A

A

V

VV

V

V

15

A1:1-21(3)

15

A1:1-20(3)

15

A1:1-19(3)

15A1:1-18(3)

15A1:1-22(3)

15A1:1-23(3)

15A1:1-24(3)

15

A1:1-26(3)

15A1:1-25(3)

15

A1:1-28(3)

15

A1:1-27(3)

15

A1:1-30(3)

SM2-178(L2)

S

M3-14

2WAY

2WAY

SSB

M2-137(L2)

N5:H1-12

SSB

M2-136(L2)

N5:H1-11

SSB

M2-139(L2)

N5:H1-14

SSB

M2-152(L2)

N5:H2-13

SSB

M2-134(L2)

N5:H1-9

SSB

M2-150(L2)

N5:H2-11

SSB

M2-149(L2)

N5:H2-10

SSB

M2-132(L2)

N5:H1-7

SSB

M2-131(L2)

N5:H1-6

SSB

M2-129(L2)

N5:H1-4

SSB

M2-128(L2)

N5:H1-3

SSB

M2-146(L2)

N5:H2-7

SSB

M2-145(L2)N5:H2-6

SSB

M2-126(L2)

N5:H1-1

SSB

M2-138(L2)N5:H1-13

SSB

M2-135(L2)

N5:H1-10

SSB

M2-151(L2)N5:H2-12

SSB

M2-133(L2)

N5:H1-8

SSB

M2-148(L2)

N5:H2-9

SSB

M2-147(L2)N5:H2-8

SSB

M2-130(L2)

N5:H1-5

SSB

M2-127(L2)

N5:H1-2

SSB

M2-199(L2)

N5:H4-5

SSB

M2-201(L2)

N5:H4-7S

SB

M2-200(L2)

N5:H4-6

SSB

M2-202(L2)

N5:H4-8 SSB

M2-203(L2)

N5:H4-9

SSB

M2-204(L2)

N5:H4-10

SSB

M2-205(L2)

N5:H4-11

SSB

M2-206(L2)

N5:H4-12 SSB

M2-207(L2)

N5:H4-13S

SB

M2-208(L2)

H9-1S

SB

M2-210(L2)

H9-3

SSB

M2-209(L2)

H9-2

SSB

M2-211(L2)

H9-4

SSB

M2-212(L2)

H9-5S

SB

M2-214(L2)

H9-7SSB

M2-213(L2)

H9-6

SSB

M2-215(L2)

H9-8

SSB

M2-216(L2)

H9-9

SSB

M2-217(L2)

N6:H4-15S

SB

M2-218(L2)

N6:H4-14

SSB

M2-219(L2)

N6:H4-13

SSB

M2-220(L2)

N6:H4-12

SSB

M2-221(L2)

N6:H4-11S

SB

M2-222(L2)

N6:H4-10

SSB

M2-223(L2)

N6:H4-9S

SB

M2-225(L2)

N6:H4-7S

SB

M2-224(L2)

N6:H4-8

SSB

M2-226(L2)

N6:H4-6

SSB

M2-228(L2)

N6:H4-4

SSB

M2-229(L2)

N6:H4-3

SSB

M2-227(L2)

N6:H4-5

SSB

M2-157(L2)

N5:H3-5

SSB

M2-158(L2)

N5:H3-6S

SB

M2-160(L2)

N5:H3-8

SSB

M2-161(L2)

N5:H3-9

SSB

M2-162(L2)

N5:H3-10

SSB

M2-156(L2)

N5:H3-4

SSB

M2-159(L2)

N5:H3-7

SSB

M2-163(L2)

N5:H3-11S

SB

M2-164(L2)

N5:H3-12S

SB

M2-165(L2)

N6:H3-13

SSB

M2-167(L2)

N6:H3-11

SSB

M2-166(L2)

N6:H3-12 SSB

M2-168(L2)

N6:H3-10

SSB

M2-170(L2)

N6:H3-8

SSB

M2-169(L2)

N6:H3-9S

SB

M2-171(L2)

N6:H3-7S

SB

M2-173(L2)

N6:H3-5

SSB

M2-174(L2)

N6:H3-4

SSB

M2-172(L2)

N6:H3-6S

SB

M2-175(L2)

N6:H3-3 SSB

M2-176(L2)

N6:H3-2

SSB

M2-177(L2)

N6:H3-1

SSB

M2-232(L2)

N6:H4-1

SSB

M2-231(L2)

N6:H4-2

SSB

M2-234(L2)

N6:H2-2

SSB

M2-235(L2)

N6:H2-3

SSB

M2-233(L2)

N6:H2-1

SSB

M2-236(L2)

N6:H2-4

SSB

M2-237(L2)

N6:H2-5

SSB

M2-183(L2)

N6:H1-3

SSB

M2-181(L2)

N6:H1-1

SSB

M2-182(L2)

N6:H1-2

SSB

M2-185(L2)

N6:H1-5

SSB

M2-184(L2)

N6:H1-4

SSB

M2-238(L2)

N6:H2-6

SSB

M2-239(L2)

N6:H2-7

SSB

M2-240(L2)

N6:H2-8

SSB

M2-241(L2)

N6:H2-9

SSB

M2-242(L2)

N6:H2-10

SSB

M2-243(L2)

N6:H2-11

SSB

M2-186(L2)

N6:H1-6

SSB

M2-188(L2)

N6:H1-8

SSB

M2-187(L2)

N6:H1-7

SSB

M2-189(L2)

N6:H1-9

SSB

M2-190(L2)

N6:H1-10

SSB

M2-191(L2)N6:H1-11

SSB

M2-244(L2)

N6:H2-12

SSB

M2-245(L2)

N6:H2-13

SSB

M2-246(L2)

N6:H2-14

SSB

M2-247(L2)

N6:H2-15S

SB

M2-194(L2)

N6:H1-14

SSB

M2-192(L2)

N6:H1-12

SSB

M2-193(L2)N6:H1-13

15A1:1-29(3)

SSB

M2-143(L2)

N5:H2-4

SSB

M2-144(L2)

N5:H2-5

SSB

M2-142(L2)

N5:H2-3

SSB

M2-141(L2)

N5:H2-2

SSB

M2-140(L2)N5:H2-1

SSB

M2-195(L2)

N5:H4-1

SSB

M2-197(L2)

N5:H4-3

SSB

M2-196(L2)

N5:H4-2

SSB

M2-198(L2)

N5:H4-4

SSB

M2-155(L2)

N5:H3-3

SSB

M2-153(L2)

N5:H3-1

SSB

M2-154(L2)

N5:H3-2

D1-32DH

D1-31DH

NAC6 M2-180(L2)

S

M2-179(L2)

NAC5

M3-12S

M3-11

AOMDAMPER CONTROL

M2-230(L2)1AOM

DAMPER CONTROL

M3-131 S

M2-248(L2)

SM2-249(L2)

TAP1

N5:H110K

N5:H210K

N5:H310K

N5:H410K

H910K

N6:H410K

N6:H310K

N6:H110K

N6:H210K

JB

V

V

V

V

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

GENERAL NOTES:

1. ALL CEILINGS ARE ASSUMED TO BE 10' A.F.F., SMOOTH CONSTRUCTION UNLESS NOTEDOTHERWISE.2. ALL NOTIFICATION APPLIANCE CANDELA INTENSITY PLUGS SHALL RETAIN THEIR FACTORYSETTING OF "FACP" UNLESS OTHERWISE DIRECTED BY THE AUTHORITY HAVING JURISDICTION.3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON' FOR NAC CIRCUITSUPERVISION.

KEYNOTES:

VERIFY EXACT LOCATION IN FIELD.1

(IN FEET)0

SCALE:

PLANNORTH

1/16" = 1'-0"8 16 32

3RD FLOOR DEVICE PLACEMENT PLAN

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-1

04.d

wg

9/13

/201

6 9:

52:0

9 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-104

3RD FLOOR DEVICE

PLACEMENT PLAN

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-104.dwg, FA-104 3RD FLOOR DEVICE PLACEMENT PLAN, 9/13/2016 9:52:07 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UNIT 334
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 332
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 331
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 330
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 329
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 328
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 326
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 327
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 325
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 324
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 323
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 322
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 321
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 319
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 320
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 317
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 318
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 316
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 315
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 314
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 313
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 312
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 311
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 310
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 309
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 308
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 307
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 306
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 305
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 304
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 303
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 302
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 301
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 300
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 335
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 336
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 337
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 339
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 338
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 341
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 340
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 342
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 344
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 343
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 345
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 346
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 347
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 348
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 333
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
344
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
344
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
344
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
353
AutoCAD SHX Text
MECH
AutoCAD SHX Text
354
AutoCAD SHX Text
STAIR "B"
AutoCAD SHX Text
359
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
358
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
356
AutoCAD SHX Text
FLOOR LOBBY
AutoCAD SHX Text
355
AutoCAD SHX Text
ELEV #1
AutoCAD SHX Text
360
AutoCAD SHX Text
ELEV LOBBY
AutoCAD SHX Text
362
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
361
AutoCAD SHX Text
ELEV #2
AutoCAD SHX Text
364
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
363
AutoCAD SHX Text
TRASH ROOM
Page 8: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

VV

V

V

AA

A

V

V

V

V

V

15

A1:2-29(3)

15

A1:2-28(3)

15A1:2-27(3)

15A1:2-26(3)

15A1:2-31(3)

15A1:2-32(3)

15A1:2-33(3)

15A1:2-35(3)

15A1:2-34(3)

15

A1:2-37(3)

15

A1:2-36(3)

15

A1:2-38(3)

S

M3-77

S

M3-24

2WAY

2WAY

SSB

M3-36

N7:H1-12

SSB

M3-35

N7:H1-11

SSB

M3-38

N7:H1-14

SSB

M3-51

N7:H2-13

SSB

M3-33

N7:H1-9

SSB

M3-49

N7:H2-11

SSB

M3-48

N7:H2-10S

SB

M3-31

N7:H1-7

SSB

M3-30

N7:H1-6

SSB

M3-28

N7:H1-4

SSB

M3-27

N7:H1-3

SSB

M3-45

N7:H2-7

SSB

M3-44N7:H2-6

SSB

M3-25

N7:H1-1

SSB

M3-37

N7:H1-13

SSB

M3-34

N7:H1-10

SSB

M3-50

N7:H2-12

SSB

M3-32N7:H1-8

SSB

M3-47

N7:H2-9

SSB

M3-46

N7:H2-8

SSB

M3-29

N7:H1-5

SSB

M3-26

N7:H1-2

SSB

M3-98

N7:H4-5

SSB

M3-100

N7:H4-7S

SB

M3-99

N7:H4-6

SSB

M3-101

N7:H4-8 SSB

M3-102

N7:H4-9

SSB

M3-103

N7:H4-10

SSB

M3-104

N7:H4-11

SSB

M3-105

N7:H4-12 SSB

M3-106

N7:H4-13S

SB

M3-107

H10-1S

SB

M3-109

H10-3

SSB

M3-108

H10-2

SSB

M3-110

H10-4

SSB

M3-111

H10-5S

SB

M3-113

H10-7SSB

M3-112

H10-6

SSB

M3-114

H10-8

SSB

M3-115

H10-9

SSB

M3-116

N8:H4-15S

SB

M3-117

N8:H4-14

SSB

M3-118

N8:H4-13

SSB

M3-119

N8:H4-12

SSB

M3-120

N8:H4-11S

SB

M3-121

N8:H4-10

SSB

M3-122

N8:H4-9S

SB

M3-124

N8:H4-7S

SB

M3-123

N8:H4-8

SSB

M3-125

N8:H4-6

SSB

M3-127

N8:H4-4

SSB

M3-128

N8:H4-3

SSB

M3-126

N8:H4-5

SSB

M3-56

N7:H3-5S

SB

M3-57

N7:H3-6S

SB

M3-59

N7:H3-8

SSB

M3-60

N7:H3-9

SSB

M3-61

N7:H3-10

SSB

M3-55

N7:H3-4

SSB

M3-58

N7:H3-7

SSB

M3-62

N7:H3-11S

SB

M3-63

N7:H3-12S

SB

M3-64

N8:H3-13

SSB

M3-66

N8:H3-11

SSB

M3-65

N8:H3-12 SSB

M3-67

N8:H3-10

SSB

M3-69

N8:H3-8

SSB

M3-68

N8:H3-9S

SB

M3-70

N8:H3-7S

SB

M3-72

N8:H3-5

SSB

M3-73

N8:H3-4

SSB

M3-71

N8:H3-6S

SB

M3-74

N8:H3-3 SSB

M3-75

N8:H3-2

SSB

M3-76

N8:H3-1S

SB

M3-130

N8:H4-1

SSB

M3-129

N8:H4-2

SSB

M3-133

N8:H2-2

SSB

M3-134

N8:H2-3

SSB

M3-132N8:H2-1

SSB

M3-135N8:H2-4

SSB

M3-136

N8:H2-5

SSB

M3-82

N8:H1-3

SSB

M3-80

N8:H1-1

SSB

M3-81

N8:H1-2

SSB

M3-84

N8:H1-5

SSB

M3-83

N8:H1-4

SSB

M3-137

N8:H2-6

SSB

M3-138

N8:H2-7

SSB

M3-139

N8:H2-8

SSB

M3-140

N8:H2-9

SSB

M3-141

N8:H2-10

SSB

M3-142

N8:H2-11

SSB

M3-85

N8:H1-6

SSB

M3-87

N8:H1-8

SSB

M3-86

N8:H1-7

SSB

M3-88

N8:H1-9

SSB

M3-89

N8:H1-10

SSB

M3-90

N8:H1-11

SSB

M3-143

N8:H2-12

SSB

M3-144

N8:H2-13

SSB

M3-145

N8:H2-14

SSB

M3-146

N8:H2-15S

SB

M3-93

N8:H1-14

SSB

M3-91

N8:H1-12

SSB

M3-92N8:H1-13

15A1:2-30(3)

SSB

M3-42

N7:H2-4

SSB

M3-43

N7:H2-5

SSB

M3-41

N7:H2-3

SSB

M3-40

N7:H2-2

SSB

M3-39

N7:H2-1

SSB

M3-94

N7:H4-1

SSB

M3-96

N7:H4-3

SSB

M3-95

N7:H4-2

SSB

M3-97

N7:H4-4

SSB

M3-54

N7:H3-3

SSB

M3-52

N7:H3-1

SSB

M3-53

N7:H3-2

D1-42DH

D1-41DH

NAC8M3-79

S

M3-78

NAC7M3-22

SM3-21

N8:H110K

N8:H210K

N8:H310K

N8:H410K

N7:H310K

N7:H110K

N7:H210K

N7:H410K

AOMDAMPER CONTROL

M3-231 AOM

DAMPER CONTROL

M3-1311

H1010K

S

M3-147

S

M3-148

TAP1JB

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

GENERAL NOTES:

1. ALL CEILINGS ARE ASSUMED TO BE 10' A.F.F., SMOOTH CONSTRUCTION UNLESS NOTEDOTHERWISE.2. ALL NOTIFICATION APPLIANCE CANDELA INTENSITY PLUGS SHALL RETAIN THEIR FACTORYSETTING OF "FACP" UNLESS OTHERWISE DIRECTED BY THE AUTHORITY HAVING JURISDICTION.3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON' FOR NAC CIRCUITSUPERVISION.

KEYNOTES:

VERIFY EXACT LOCATION IN FIELD.1

(IN FEET)0

SCALE:

PLANNORTH

1/16" = 1'-0"8 16 32

4TH FLOOR DEVICE PLACEMENT PLAN

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-1

05.d

wg

9/13

/201

6 9:

52:1

5 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-105

4TH FLOOR DEVICE

PLACEMENT PLAN

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-105.dwg, FA-105 4TH FLOOR DEVICE PLACEMENT PLAN, 9/13/2016 9:52:13 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UNIT 434
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 432
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 431
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 430
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 429
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 428
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 426
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 427
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 425
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 424
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 423
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 422
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 421
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 419
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 420
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 417
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 418
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 416
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 415
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 414
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 413
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 412
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 411
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 410
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 409
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 408
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 407
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 406
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 405
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 404
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 403
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 402
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 401
AutoCAD SHX Text
3 BEDROOM
AutoCAD SHX Text
UNIT 400
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 435
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 436
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 437
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 439
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 438
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 441
AutoCAD SHX Text
STUDIO
AutoCAD SHX Text
UNIT 440
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 442
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 444
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 443
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 445
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 446
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 447
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
UNIT 448
AutoCAD SHX Text
1 BEDROOM
AutoCAD SHX Text
UNIT 433
AutoCAD SHX Text
2 BEDROOM
AutoCAD SHX Text
444
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
444
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
444
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
453
AutoCAD SHX Text
MECH
AutoCAD SHX Text
454
AutoCAD SHX Text
STAIR "B"
AutoCAD SHX Text
459
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
458
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
456
AutoCAD SHX Text
FLOOR LOBBY
AutoCAD SHX Text
455
AutoCAD SHX Text
ELEV #1
AutoCAD SHX Text
460
AutoCAD SHX Text
ELEV LOBBY
AutoCAD SHX Text
462
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
461
AutoCAD SHX Text
ELEV #2
AutoCAD SHX Text
464
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
463
AutoCAD SHX Text
TRASH ROOM
Page 9: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Doo

r -

D1

Doo

r -

D1

DD

IDN

et -

M1

IDN

et -

M2(

L1)

IDN

et -

M3 ID

Net

- M

1M

M

M

M

NAC

- A

1:1(

2)

NAC

- A

1:1(

1)

Hor

n -

H3

Hor

n -

N1:

H1

Hor

n -

N1:

H2

Hor

n -

N1:

H3

Hor

n -

N1:

H4

Hor

n -

N2:

H1

Hor

n -

N2:

H2

Hor

n -

N2:

H3

Hor

n -

N2:

H4

NAC

- A

1:2(

1)

NAC

- A

1:2(

2)

Hor

n -

N3:

H1

Hor

n -

N3:

H2

Hor

n -

N3:

H3

Hor

n -

N3:

H4

Hor

n -

N4:

H1

Hor

n -

N4:

H2

Hor

n -

N4:

H3

Hor

n -

N4:

H4

NAC

- A

1:3(

1)

NAC

- A

1:3(

2)

41

00

ES

LOCA

TED

IN M

ECH

010. .

FA

CP

2 PA

IR T

ELCO

RJ-3

1X J

ACK

SUPP

LIED

BY

ECTO

TEL

EPH

ON

EM

OU

NTI

NG

BO

ARD

TO T

ELEP

HO

NE

MO

UN

TIN

G B

OAR

D

2 PA

IR T

ELCO

RJ-3

1X J

ACK

SUPP

LIED

BY

EC

LIN

E 2

LIN

E 1

14' R

J45

CABL

E (2

080-

9047

) SU

PPLI

EDW

ITH

PAN

EL

14' R

J45

CABL

E (2

080-

9047

) SU

PPLI

EDW

ITH

PAN

EL

120

VOLT

AC

Hor

n -

H3

AA

V

A

V

A

VV

V

V

VV

V

V

Hor

n -

H4

VV

VV

VV

VV

AA

V

Hor

n -

H4

FA-1

01FA

-101

S

M1-1

MEC

H 010

S

M1-2

LOBB

Y 00

7

F

M1-3

STAI

R "C

" 006

S

M1-4

ELEV

EQUIP

009

AOM

PRI M1-

5

ELEV

EQUIP

009R

TO ELEVCONTROLLER

AOM

ALT M1-

6

ELEV

EQUIP

009R

TO ELEVCONTROLLER

AOM

FIREH

AT M1-7

ELEV

EQUIP

009R

TO ELEVCONTROLLER

AIM

M1-8

MEC

H 113

WF

Z

6.8K

AIM

M1-9

MEC

H 113

WF

Z

6.8K

AIM

M1-10

MEC

H 113

WF

Z

6.8K

AIM

M1-11

MEC

H 113

WF

Z

6.8K

AIM

M1-12

MEC

H 113

VS

Z

6.8K

AIM

M1-13

MEC

H 113

VS

Z

6.8K

AIM

M1-14

MEC

H 113

VS

Z

6.8K

AIM

M1-15

MEC

H 113

VS

Z

6.8K

AIM

M1-16

MEC

H 113

VS

Z

6.8K

AIM

M1-17

MEC

H 113

VS

Z

6.8K

AIM

M1-18

MEC

H 113

VS

Z

6.8K

AIM

M1-19

MEC

H 113

VS

Z

6.8K

S

M1-20

LOBB

Y 01

4

S

M1-21

ELEV

. EQUIP

017

AOM

PRI M1-

22

ELEV

. EQUIP

017R

TO ELEVCONTROLLER

AOM

ALT M1-

23

ELEV

. EQUIP

017R

TO ELEVCONTROLLER

AOM

FIREH

AT M1-24

ELEV

. EQUIP

017R

TO ELEVCONTROLLER

75

A1:1

-6(2

)

GAR

AGE 0

01

75

A1:1

-7(2

)

GAR

AGE 0

01

75

A1:1

-8(2

)

GAR

AGE 0

01

75

A1:1

-9(2

)

GAR

AGE 0

01

75

A1:1

-10(

2)

GAR

AGE 0

01

75

A1:1

-11(

2)

GAR

AGE 0

01

75

A1:1

-12(

2)

GAR

AGE 0

01

75

A1:1

-13(

2)

GAR

AGE 0

01

75

A1:1

-14(

2)

GAR

AGE 0

01

75

A1:1

-15(

2)

GAR

AGE 0

01

75

A1:1

-16(

2)

GAR

AGE 0

01

75

A1:1

-1(1

)

GAR

AGE 0

01

75

A1:1

-2(1

)

GAR

AGE 0

01

75

A1:1

-3(1

)

GAR

AGE 0

01

75

A1:1

-4(1

)

GAR

AGE 0

01

75

A1:1

-5(1

)

GAR

AGE 0

01

FA-1

02FA

-102

D1-

11DH

D1-

12DH

NAC

1

M1-31

ELEC

T RO

OM 165

S

M1-32

ELEC

T RO

OM 165

AOM

DAMPE

R CO

NTROL M1-

33

BY

CONF

. ROOM 16

0R

TO WESTDAMPERCONTROL

S

M1-34

LOBB

Y 15

8

SSB

M1-35

2 BE

DROOM U

NIT

136

N1:H1-

1

SSB

M1-36

2 BE

DROOM U

NIT

136

N1:H1-

2

SSB

M1-37

2 BE

DROOM U

NIT

136

N1:H1-

3

SSB

M1-38

2 BE

DROOM U

NIT

138

N1:H1-

4

SSB

M1-39

2 BE

DROOM U

NIT

138

N1:H1-

5

SSB

M1-40

2 BE

DROOM U

NIT

138

N1:H1-

6

SSB

M1-41

2 BE

DROOM U

NIT

140

N1:H1-

7

SSB

M1-42

2 BE

DROOM U

NIT

140

N1:H

1-8

SSB

M1-43

2 BE

DROOM U

NIT

140

N1:H

1-9

SSB

M1-44

1 BE

DROOM U

NIT

143

N1:H

1-10

SSB

M1-45

1 BE

DROOM U

NIT

143

N1:H

1-11

SSB

M1-46

STUDI

O UNI

T 13

4

N1:H

2-1

SSB

M1-47

STUDI

O UNI

T 13

5

N1:H

2-2

SSB

M1-48

1 BE

DROOM U

NIT

137

N1:H

2-3

SSB

M1-49

1 BE

DROOM U

NIT 13

7

N1:H

2-4

SSB

M1-50

1 BE

DROOM U

NIT

139

N1:H

2-5

SSB

M1-51

1 BE

DROOM U

NIT

139

N1:H

2-6

SSB

M1-52

2 BE

DROOM U

NIT

141

N1:H

2-7

SSB

M1-53

2 BE

DROOM U

NIT 14

1

N1:H

2-8

SSB

M1-54

2 BE

DROOM U

NIT 14

1

N1:H

2-9

SSB

M1-55

2 BE

DROOM U

NIT

142

N1:H

2-10

SSB

M1-56

2 BE

DROOM U

NIT

142

N1:H

2-11

SSB

M1-57

2 BE

DROOM U

NIT

142

N1:H

2-12

SSB

M1-58

1 BE

DROOM U

NIT

131

N1:H3-

1

SSB

M1-59

1 BE

DROOM U

NIT

131

N1:H

3-2

SSB

M1-60

3 BE

DROOM U

NIT

129

N1:H

3-3

SSB

M1-61

3 BE

DROOM U

NIT

129

N1:H

3-4

SSB

M1-62

3 BE

DROOM U

NIT

129

N1:H3-

5

SSB

M1-63

3 BE

DROOM U

NIT

129

N1:H3-

6

SSB

M1-64

2 BE

DROOM U

NIT

126

N1:H3-

7

SSB

M1-65

2 BE

DROOM U

NIT

126

N1:H3-

8

SSB

M1-66

2 BE

DROOM U

NIT

126

N1:H3-

9

SSB

M1-67

2 BE

DROOM U

NIT

124

N2:H

3-13

SSB

M1-68

2 BE

DROOM U

NIT

124

N2:H

3-12

SSB

M1-69

2 BE

DROOM U

NIT

124

N2:H

3-11

SSB

M1-70

2 BE

DROOM U

NIT

121

N2:H

3-10

SSB

M1-71

2 BE

DROOM U

NIT

121

N2:H

3-9

SSB

M1-72

2 BE

DROOM U

NIT

121

N2:H

3-8

SSB

M1-73

2 BE

DROOM U

NIT

119

N2:H

3-7

SSB

M1-74

2 BE

DROOM U

NIT 11

9

N2:H

3-6

SSB

M1-75

2 BE

DROOM U

NIT 11

9

N2:H

3-5

SSB

M1-76

2 BE

DROOM U

NIT

117

N2:H

3-4

SSB

M1-77

2 BE

DROOM U

NIT

117

N2:H

3-3

SSB

M1-78

2 BE

DROOM U

NIT

117

N2:H

3-2

SSB

M1-79

STUDI

O UNI

T 11

5

N2:H

3-1

S

M1-80

ELEV

LOBB

Y 16

7

AOM

DAMPE

R CO

NTROL M1-81

BY

STORA

GE 168R

TO EASTDAMPERCONTROL

S

M1-82

ELEC

T/MEC

H 170

NAC

2

M1-83

ELEC

T/MEC

H 170

SSB

M1-84

2 BE

DROOM U

NIT

110

N2:H

1-1

SSB

M1-85

2 BE

DROOM U

NIT

110

N2:H

1-2

SSB

M1-86

2 BE

DROOM U

NIT

110

N2:H

1-3

SSB

M1-87

1 BE

DROOM U

NIT

108

N2:H

1-4

SSB

M1-88

1 BE

DROOM U

NIT

108

N2:H

1-5

SSB

M1-89

2 BE

DROOM U

NIT

106

N2:H

1-6

SSB

M1-90

2 BE

DROOM U

NIT

106

N2:H

1-7

SSB

M1-91

2 BE

DROOM U

NIT

106

N2:H

1-8

SSB

M1-92

1 BE

DROOM U

NIT

104

N2:H

1-9

SSB

M1-93

1 BE

DROOM U

NIT

104

N2:H

1-10

SSB

M1-94

STUDI

O UNI

T 10

2

N2:H

1-11

SSB

M1-95

2 BE

DROOM U

NIT

100

N2:H

1-12

SSB

M1-96

2 BE

DROOM U

NIT

100

N2:H

1-13

SSB

M1-97

2 BE

DROOM U

NIT

100

N2:H

1-14

SSB

M1-98

2 BE

DROOM U

NIT

133

N1:H

4-1

SSB

M1-99

2 BE

DROOM U

NIT

133

N1:H

4-2

SSB

M1-10

0

2 BE

DROOM U

NIT

133

N1:H

4-3

SSB

M1-10

1

1 BE

DROOM U

NIT

132

N1:H

4-4

SSB

M1-10

2

1 BE

DROOM U

NIT 13

2

N1:H

4-5

SSB

M1-10

3

1 BE

DROOM U

NIT

130

N1:H

4-6

SSB

M1-10

4

1 BE

DROOM U

NIT

130

N1:H

4-7

SSB

M1-10

5

1 BE

DROOM U

NIT

128

N1:H

4-8

SSB

M1-10

6

1 BE

DROOM U

NIT

128

N1:H

4-9

SSB

M1-10

7

STUDI

O UNI

T 12

7

N1:H

4-10

SSB

M1-10

8

2 BE

DROOM U

NIT

125

H3-1

SSB

M1-10

9

2 BE

DROOM U

NIT

125

H3-2

SSB

M1-11

0

2 BE

DROOM U

NIT

125

H3-3

SSB

M1-11

1

2 BE

DROOM U

NIT

123

H3-4

SSB

M1-11

2

2 BE

DROOM U

NIT

123

H3-5

SSB

M1-11

3

2 BE

DROOM U

NIT

123

H3-6

SSB

M1-11

4

1 BE

DROOM U

NIT 12

2H3-

7

SSB

M1-11

5 1

BEDR

OOM UNIT

122

H3-8

SSB

M1-11

6

1 BE

DROOM U

NIT 12

0

H3-9

SSB

M1-11

7

1 BE

DROOM U

NIT 12

0

H3-10

SSB

M1-11

8

1 BE

DROOM U

NIT 11

8

N2:H

4-13

SSB

M1-11

9

1 BE

DROOM U

NIT 11

8

N2:H

4-12

SSB

M1-12

0

1 BE

DROOM U

NIT 11

6

N2:H

4-11

SSB

M1-12

1

1 BE

DROOM U

NIT

116

N2:H

4-10

SSB

M1-12

2

2 BE

DROOM U

NIT 11

4

N2:H4-

9

SSB

M1-12

3

2 BE

DROOM U

NIT

114

N2:H4-

8

SSB

M1-12

4

2 BE

DROOM U

NIT

114

N2:H4-

7

SSB

M1-12

5

3 BE

DROOM U

NIT

113

N2:H4-

6

SSB

M1-12

6

3 BE

DROOM U

NIT

113

N2:H4-

5

SSB

M1-12

7

3 BE

DROOM U

NIT

113

N2:H4-

4S

SB

M1-12

8

3 BE

DROOM U

NIT

113

N2:H4-

3

SSB

M1-12

9

1 BE

DROOM U

NIT

112

N2:H

4-2

SSB

M1-13

0

1 BE

DROOM U

NIT

112

N2:H

4-1

SSB

M1-13

1

1 BE

DROOM U

NIT

111

N2:H2-

1

SSB

M1-13

2

1 BE

DROOM U

NIT

111

N2:H

2-2

SSB

M1-13

3

2 BE

DROOM U

NIT

109

N2:H

2-3

SSB

M1-13

4

2 BE

DROOM U

NIT

109

N2:H

2-4

SSB

M1-13

5

2 BE

DROOM U

NIT

109

N2:H2-

5

SSB

M1-13

6

1 BE

DROOM U

NIT 10

7

N2:H2-

6

SSB

M1-13

7

1 BE

DROOM U

NIT

107

N2:H2-

7

SSB

M1-13

8

1 BE

DROOM U

NIT

105

N2:H2-

8

SSB

M1-13

9

1 BE

DROOM U

NIT

105

N2:H2-

9

SSB

M1-14

0

1 BE

DROOM U

NIT

103

N2:H

2-10

SSB

M1-14

1

1 BE

DROOM U

NIT

103

N2:H

2-11

SSB

M1-14

2

3 BE

DROOM U

NIT

101

N2:H

2-12

SSB

M1-14

3

3 BE

DROOM U

NIT

101

N2:H

2-13

SSB

M1-14

4

3 BE

DROOM U

NIT

101

N2:H

2-14

SSB

M1-14

5

3 BE

DROOM U

NIT

101

N2:H

2-15

S

M1-14

6

CORR

IDOR

144

S

M1-14

7

CORR

IDOR

144

15

A1:2

-1(1

)

CORR

IDOR

144

15

A1:2

-2(1

)

CORR

IDOR

144

15

A1:2

-3(1

)

CORR

IDOR

144

15

A1:2

-4(1

)

CORR

IDOR

144

15

A1:2

-5(1

)

CONF.

ROOM 16

0

75

A1:2

-6(1

)

COMMUNI

TY R

OOM 153

15

A1:2

-7(1

)

THEA

TRE 1

52

15

A1:2

-8(1

)

WOMEN

148

15

A1:2

-9(1

)

MEN

149

15

A1:2

-10(

1)

SHOWER

150

30

A1:2

-11(

1)

FITN

ESS C

ENTE

R 14

7

15

A1:2

-12(

1)

GRO

UP FIT

NESS 1

46

15

A1:2

-13(

1)

STUDI

O UNI

T 13

5

185

A1:2

-14(

1)

STUDI

O UNI

T 13

5

15

A1:2

-23(

1)

1 BE

DROOM U

NIT

128

185

A1:2

-24(

1)

1 BE

DROOM U

NIT

128

15

A1:2

-15(

2)

CORR

IDOR

144

15

A1:2

-16(

2)

CORR

IDOR

144

15

A1:2

-17(

2)

CORR

IDOR

144

15

A1:2

-18(

2)

CORR

IDOR

144

15

A1:2

-19(

2)

CORR

IDOR

144

15

A1:2

-20(

2)

CORR

IDOR

144

15

A1:2

-21(

2)

CORR

IDOR

144

15

A1:2

-22(

2)

STORA

GE 168

FA-1

03FA

-103

D1-

21DH

D1-

22DH

S

M2-1(

L1)

CORR

IDOR

244

SSB

M2-2(

L1)

2 BE

DROOM U

NIT

240

N3:H

1-1

SSB

M2-3(

L1)

2 BE

DROOM U

NIT

240

N3:H

1-2

SSB

M2-4(

L1)

2 BE

DROOM U

NIT

240

N3:H

1-3

SSB

M2-5(

L1)

2 BE

DROOM U

NIT

243

N3:H

1-4

SSB

M2-6(

L1)

2 BE

DROOM U

NIT

243

N3:H

1-5

SSB

M2-7(

L1)

2 BE

DROOM U

NIT 24

3

N3:H

1-6

SSB

M2-8(

L1)

2 BE

DROOM U

NIT

245

N3:H

1-7

SSB

M2-9(

L1)

2 BE

DROOM U

NIT

245

N3:H

1-8

SSB

M2-10

(L1)

2 BE

DROOM U

NIT

245

N3:H

1-9

SSB

M2-11

(L1)

1 BE

DROOM U

NIT

248

N3:H

1-10

SSB

M2-12

(L1)

1 BE

DROOM U

NIT

248

N3:H

1-11

SSB

M2-13

(L1)

2 BE

DROOM U

NIT

247

N3:H

1-12

SSB

M2-14

(L1)

2 BE

DROOM U

NIT 24

7

N3:H

1-13

SSB

M2-15

(L1)

2 BE

DROOM U

NIT 24

7

N3:H

1-14

SSB

M2-16

(L1)

STUDI

O UNI

T 23

7

N3:H

2-1

SSB

M2-17

(L1)

1 BE

DROOM U

NIT

238

N3:H

2-2

SSB

M2-18

(L1)

1 BE

DROOM U

NIT

238

N3:H

2-3

SSB

M2-19

(L1)

1 BE

DROOM U

NIT

239

N3:H

2-4

SSB

M2-20

(L1)

1 BE

DROOM U

NIT

239

N3:H

2-5

SSB

M2-21

(L1)

STUDI

O UNI

T 24

1

N3:H

2-6

SSB

M2-22

(L1)

1 BE

DROOM U

NIT 24

2

N3:H

2-7

SSB

M2-23

(L1)

1 BE

DROOM U

NIT 24

2

N3:H

2-8

SSB

M2-24

(L1)

1 BE

DROOM U

NIT

244

N3:H

2-9

SSB

M2-25

(L1)

1 BE

DROOM U

NIT

244

N3:H

2-10

SSB

M2-26

(L1)

2 BE

DROOM U

NIT

246

N3:H

2-11

SSB

M2-27

(L1)

2 BE

DROOM U

NIT

246

N3:H

2-12

SSB

M2-28

(L1)

2 BE

DROOM U

NIT

246

N3:H

2-13

SSB

M2-29

(L1)

2 BE

DROOM U

NIT

233

N3:H3-

1

SSB

M2-30

(L1)

2 BE

DROOM U

NIT

233

N3:H3-

2

SSB

M2-31

(L1)

2 BE

DROOM U

NIT

233

N3:H

3-3

SSB

M2-32

(L1)

1 BE

DROOM U

NIT

231

N3:H

3-4

SSB

M2-33

(L1)

1 BE

DROOM U

NIT

231

N3:H

3-5

SSB

M2-34

(L1)

3 BE

DROOM U

NIT

229

N3:H3-

6

SSB

M2-35

(L1)

3 BE

DROOM U

NIT

229

N3:H3-

7

SSB

M2-36

(L1)

3 BE

DROOM U

NIT

229

N3:H3-

8

SSB

M2-37

(L1)

3 BE

DROOM U

NIT 22

9

N3:H3-

9

SSB

M2-38

(L1)

2 BE

DROOM U

NIT

226

N3:H

3-10

SSB

M2-39

(L1)

2 BE

DROOM U

NIT

226

N3:H

3-11

SSB

M2-40

(L1)

2 BE

DROOM U

NIT 22

6

N3:H

3-12

SSB

M2-41

(L1)

2 BE

DROOM U

NIT

224

N4:H

3-13

SSB

M2-42

(L1)

2 BE

DROOM U

NIT

224

N4:H3-

12

SSB

M2-43

(L1)

2 BE

DROOM U

NIT

224

N4:H

3-11

SSB

M2-44

(L1)

2 BE

DROOM U

NIT

221

N4:H

3-10

SSB

M2-45

(L1)

2 BE

DROOM U

NIT

221

N4:H

3-9

SSB

M2-46

(L1)

2 BE

DROOM U

NIT

221

N4:H

3-8

SSB

M2-47

(L1)

2 BE

DROOM U

NIT

219

N4:H

3-7

SSB

M2-48

(L1)

2 BE

DROOM U

NIT

219

N4:H

3-6

SSB

M2-49

(L1)

2 BE

DROOM U

NIT 21

9

N4:H

3-5

SSB

M2-50

(L1)

2 BE

DROOM U

NIT

217

N4:H

3-4

SSB

M2-51

(L1)

2 BE

DROOM U

NIT

217

N4:H

3-3

SSB

M2-52

(L1)

2 BE

DROOM U

NIT

217

N4:H

3-2

SSB

M2-53

(L1)

STUDI

O UNI

T 21

5

N4:H

3-1

S

M2-54

(L1)

ELEV

LOBB

Y 26

0

S

M2-55

(L1)

ELEC

T 26

4

NAC

4

M2-56

(L1)

ELEC

T 26

4

SSB

M2-57

(L1)

2 BE

DROOM U

NIT 21

0

N4:H

1-1

SSB

M2-58

(L1)

2 BE

DROOM U

NIT

210

N4:H

1-2

SSB

M2-59

(L1)

2 BE

DROOM U

NIT

210

N4:H

1-3

SSB

M2-60

(L1)

1 BE

DROOM U

NIT 20

8

N4:H

1-4

SSB

M2-61

(L1)

1 BE

DROOM U

NIT

208

N4:H

1-5

SSB

M2-62

(L1)

2 BE

DROOM U

NIT

206

N4:H

1-6

SSB

M2-63

(L1)

2 BE

DROOM U

NIT

206

N4:H

1-7

SSB

M2-64

(L1)

2 BE

DROOM U

NIT

206

N4:H

1-8

SSB

M2-65

(L1)

1 BE

DROOM U

NIT

204

N4:H

1-9

SSB

M2-66

(L1)

1 BE

DROOM U

NIT

204

N4:H

1-10

SSB

M2-67

(L1)

STUDI

O UNI

T 20

2

N4:H

1-11

SSB

M2-68

(L1)

2 BE

DROOM U

NIT

200

N4:H

1-12

SSB

M2-69

(L1)

2 BE

DROOM U

NIT

200

N4:H

1-13

SSB

M2-70

(L1)

2 BE

DROOM U

NIT

200

N4:H

1-14

SSB

M2-71

(L1)

2 BE

DROOM U

NIT

236

N3:H

4-1

SSB

M2-72

(L1)

2 BE

DROOM U

NIT

236

N3:H

4-2

SSB

M2-73

(L1)

2 BE

DROOM U

NIT

236

N3:H

4-3

SSB

M2-74

(L1)

STUDI

O UNI

T 23

5

N3:H

4-4

SSB

M2-75

(L1)

2 BE

DROOM U

NIT 23

4

N3:H

4-5

SSB

M2-76

(L1)

2 BE

DROOM U

NIT 23

4

N3:H

4-6

SSB

M2-77

(L1)

2 BE

DROOM U

NIT

234

N3:H

4-7

SSB

M2-78

(L1)

1 BE

DROOM U

NIT 23

2

N3:H

4-8

SSB

M2-79

(L1)

1 BE

DROOM U

NIT

232

N3:H

4-9

SSB

M2-80

(L1)

1 BE

DROOM U

NIT 23

0

N3:H

4-10

SSB

M2-81

(L1)

1 BE

DROOM U

NIT 23

0

N3:H

4-11

SSB

M2-82

(L1)

1 BE

DROOM U

NIT

228

N3:H

4-12

SSB

M2-83

(L1)

1 BE

DROOM U

NIT

228

N3:H

4-13

SSB

M2-84

(L1)

STUDI

O UNI

T 22

7H4-

1

SSB

M2-85

(L1)

2 BE

DROOM U

NIT

225

H4-2

SSB

M2-86

(L1)

2 BE

DROOM U

NIT

225

H4-3

SSB

M2-87

(L1)

2 BE

DROOM U

NIT

225

H4-4

SSB

M2-88

(L1)

2 BE

DROOM U

NIT

223

H4-5

SSB

M2-89

(L1)

2 BE

DROOM U

NIT

223

H4-6

SSB

M2-90

(L1)

2 BE

DROOM U

NIT

223

H4-7

SSB

M2-91

(L1)

1 BE

DROOM U

NIT

222

H4-8

SSB

M2-92

(L1)

1 BE

DROOM U

NIT

222

H4-9

SSB

M2-93

(L1)

1 BE

DROOM U

NIT 22

0

N4:H

4-15

SSB

M2-94

(L1)

1 BE

DROOM U

NIT

220

N4:H4-

14

SSB

M2-95

(L1)

1 BE

DROOM U

NIT

218

N4:H

4-13

SSB

M2-96

(L1)

1 BE

DROOM U

NIT

218

N4:H

4-12

SSB

M2-97

(L1)

1 BE

DROOM U

NIT

216

N4:H

4-11

SSB

M2-98

(L1)

1 BE

DROOM U

NIT

216

N4:H

4-10

SSB

M2-99

(L1)

2 BE

DROOM U

NIT

214

N4:H

4-9

SSB

M2-10

0(L1

)

2 BE

DROOM U

NIT

214

N4:H

4-8

SSB

M2-10

1(L1

)

2 BE

DROOM U

NIT

214

N4:H

4-7

SSB

M2-10

2(L1

)

3 BE

DROOM U

NIT 21

3

N4:H

4-6

SSB

M2-10

3(L1

)

3 BE

DROOM U

NIT

213

N4:H

4-5

SSB

M2-10

4(L1

)

3 BE

DROOM U

NIT

213

N4:H

4-4

SSB

M2-10

5(L1

)

3 BE

DROOM U

NIT

213

N4:H

4-3

SSB

M2-10

6(L1

)

1 BE

DROOM U

NIT

212

N4:H

4-2

SSB

M2-10

7(L1

)

1 BE

DROOM U

NIT

212

N4:H

4-1

SSB

M2-10

8(L1

)

1 BE

DROOM U

NIT

211

N4:H2-

1

SSB

M2-10

9(L1

)

1 BE

DROOM U

NIT

211

N4:H2-

2

SSB

M2-11

0(L1

)

2 BE

DROOM U

NIT

209

N4:H

2-3

SSB

M2-11

1(L1

)

2 BE

DROOM U

NIT

209

N4:H

2-4

SSB

M2-11

2(L1

)

2 BE

DROOM U

NIT

209

N4:H

2-5

SSB

M2-11

3(L1

)

1 BE

DROOM U

NIT 20

7

N4:H2-

6

SSB

M2-11

4(L1

)

1 BE

DROOM U

NIT 20

7

N4:H2-

7

SSB

M2-11

5(L1

)

1 BE

DROOM U

NIT

205

N4:H2-

8

SSB

M2-11

6(L1

)

1 BE

DROOM U

NIT

205

N4:H2-

9

SSB

M2-11

7(L1

)

1 BE

DROOM U

NIT

203

N4:H

2-10

SSB

M2-11

8(L1

)

1 BE

DROOM U

NIT

203

N4:H

2-11

SSB

M2-11

9(L1

)

3 BE

DROOM U

NIT

201

N4:H

2-12

SSB

M2-12

0(L1

)

3 BE

DROOM U

NIT

201

N4:H

2-13

SSB

M2-12

1(L1

)

3 BE

DROOM U

NIT

201

N4:H

2-14

SSB

M2-12

2(L1

)

3 BE

DROOM U

NIT

201

N4:H

2-15

AOM

DAMPE

R CO

NTRO

L

M2-12

3(L1

)

CORR

IDOR

244R

TO DAMPERCONTROL

S

M2-12

4(L1

)

CORR

IDOR

244

S

M3-1

ELEC

T 25

9

NAC

3

M3-2

ELEC

T 25

9

AOM

DAMPE

R CO

NTROL M3-

3

CORR

IDOR

244R

TO DAMPERCONTROL

S

M3-4

FLOOR

LOBB

Y 25

6

15

A1:3

-1(1

)

CORR

IDOR

244

15

A1:3

-2(1

)

CORR

IDOR

244

15

A1:3

-3(1

)

CORR

IDOR

244

15

A1:3

-4(1

)

CORR

IDOR

244

15

A1:3

-5(1

)

STORA

GE 258

15

A1:3

-6(1

)

CORR

IDOR

244

15

A1:3

-7(1

)

3 BE

DROOM U

NIT

229

185

A1:3

-8(1

)

3 BE

DROOM U

NIT

229

185

A1:3

-9(1

)

3 BE

DROOM U

NIT

229

185

A1:3

-10(

1)

3 BE

DROOM U

NIT

229

15

A1:3

-11(

1)

3 BE

DROOM U

NIT

229

15

A1:3

-16(

1)

CORR

IDOR

244

15

A1:3

-17(

1)

CORR

IDOR

244

15

A1:3

-18(

1)

STORA

GE 262

15

A1:3

-19(

1)

2 BE

DROOM U

NIT

210

185

A1:3

-20(

1)

2 BE

DROOM U

NIT

210

185

A1:3

-21(

1)

2 BE

DROOM U

NIT

210

15

A1:3

-22(

1)

2 BE

DROOM U

NIT

210

15

A1:3

-12(

2)

CORR

IDOR

244

15

A1:3

-13(

2)

CORR

IDOR

244

15

A1:3

-14(

2)

CORR

IDOR

244

15

A1:3

-15(

2)

CORR

IDOR

244

FA-1

04FA

-104

N1:

H1

10K

N1:

H2

10K

N1:

H3

10K

N1:

H4

10K

N2:

H1

10K

N2:

H2

10K

N2:

H3

10K

N2:

H4

10K

H3

10K

N3:

H1

10K

N3:

H2

10K

N3:

H3

10K

N3:

H4

10K

N4:

H1

10K

N4:

H2

10K

N4:

H3

10K

N4:

H4

10K

H4

10K

2A,D

,2M

,2V

2A,D

,2M

,2V

4A,D

,3M

,3V

4A,D

,3M

,3V

6A,D

,4M

,4V

6A,D

,4M

,4V

FAA

VEST

. 00

5B P

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

RISER NOTES:

1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE SYSTEMARCHITECTURE IN BUILDING CROSS SECTION. IT IS NOT INTENDEDTO REPRESENT ACTUAL WIRE RUNS, PANEL CONFIGURATIONS ORPENETRATIONS. REFER TO FLOOR PLANS AND PANEL DETAILS FORCIRCUIT ROUTING AND CONFIGURATION INFORMATION.

2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL CODES.REFER TO 'APPLICABLE CODES & STANDARDS' ON SHEET FA-000 FORSPECIFIC CODE REFERENCES.

3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON'FOR NAC CIRCUIT SUPERVISION.

SCALE: NTS

RISER DIAGRAM

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-2

01.d

wg

9/13

/201

6 9:

52:2

0 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-201

RISER DIAGRAM

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-201.dwg, FA-201 RISER DIAGRAM, 9/13/2016 9:52:19 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 10: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Doo

r -

D1

DDD

oor

- D

1

IDN

et -

M2(

L2)

IDN

et -

M3

M

M

MID

Net

- M

3

NAC

- A

1:2(

3)

Hor

n -

H10

Hor

n -

H9

Hor

n -

N5:

H1

Hor

n -

N5:

H2

Hor

n -

N5:

H3

Hor

n -

N5:

H4

Hor

n -

N6:

H1

Hor

n -

N6:

H2

Hor

n -

N6:

H3

Hor

n -

N6:

H4

NAC

- A

1:1(

3)

Hor

n -

N7:

H1

Hor

n -

N7:

H2

Hor

n -

N7:

H3

Hor

n -

N7:

H4

Hor

n -

N8:

H1

Hor

n -

N8:

H2

Hor

n -

N8:

H3

Hor

n -

N8:

H4

VV

VV

VV

VV

VV

VV

VH

orn

- H

9

V

Hor

n -

H10

A A

VV

VV

AAAA

V

V

FA-1

04FA

-104

D1-

31DH

D1-

32DH

SSB

M2-12

6(L2

)

2 BE

DROOM U

NIT

340

N5:H

1-1

SSB

M2-12

7(L2

)

2 BE

DROOM U

NIT

340

N5:H1-

2

SSB

M2-12

8(L2

)

2 BE

DROOM U

NIT

340

N5:H

1-3

SSB

M2-12

9(L2

)

2 BE

DROOM U

NIT 34

3

N5:H1-

4

SSB

M2-13

0(L2

)

2 BE

DROOM U

NIT

343

N5:H

1-5

SSB

M2-13

1(L2

)

2 BE

DROOM U

NIT 34

3

N5:H

1-6

SSB

M2-13

2(L2

)

2 BE

DROOM U

NIT 34

5

N5:H1-

7

SSB

M2-13

3(L2

)

2 BE

DROOM U

NIT

345

N5:H

1-8

SSB

M2-13

4(L2

)

2 BE

DROOM U

NIT 34

5

N5:H1-

9

SSB

M2-13

5(L2

)

1 BE

DROOM U

NIT

348

N5:H

1-10

SSB

M2-13

6(L2

)

1 BE

DROOM U

NIT

348

N5:H

1-11

SSB

M2-13

7(L2

)

2 BE

DROOM U

NIT

347

N5:H

1-12

SSB

M2-13

8(L2

)

2 BE

DROOM U

NIT 34

7

N5:H1-

13

SSB

M2-13

9(L2

)

2 BED

ROOM U

NIT

347

N5:H

1-14

SSB

M2-14

0(L2

)

STUDI

O UNI

T 33

7

N5:H

2-1

SSB

M2-14

1(L2

)

1 BE

DROOM U

NIT

338

N5:H

2-2

SSB

M2-14

2(L2

)

1 BE

DROOM U

NIT 33

8

N5:H

2-3

SSB

M2-14

3(L2

)

1 BE

DROOM U

NIT

339

N5:H

2-4

SSB

M2-14

4(L2

)

1 BE

DROOM U

NIT

339

N5:H

2-5

SSB

M2-14

5(L2

)

STUDI

O UNI

T 34

1

N5:H

2-6

SSB

M2-14

6(L2

)

1 BE

DROOM U

NIT 34

2

N5:H

2-7

SSB

M2-14

7(L2

)

1 BE

DROOM U

NIT

342

N5:H

2-8

SSB

M2-14

8(L2

)

1 BE

DROOM U

NIT

344

N5:H

2-9

SSB

M2-14

9(L2

)

1 BE

DROOM U

NIT

344

N5:H

2-10

SSB

M2-15

0(L2

)

2 BE

DROOM U

NIT

346

N5:H2-

11

SSB

M2-15

1(L2

)

2 BE

DROOM U

NIT 34

6

N5:H

2-12

SSB

M2-15

2(L2

)

2 BE

DROOM U

NIT

346

N5:H

2-13

SSB

M2-15

3(L2

)

2 BE

DROOM U

NIT

333

N5:H

3-1

SSB

M2-15

4(L2

)

2 BE

DROOM U

NIT

333

N5:H3-

2

SSB

M2-15

5(L2

)

2 BE

DROOM U

NIT

333

N5:H

3-3

SSB

M2-15

6(L2

)

1 BE

DROOM U

NIT

331

N5:H

3-4

SSB

M2-15

7(L2

)

1 BE

DROOM U

NIT

331

N5:H3-

5

SSB

M2-15

8(L2

)

3 BE

DROOM U

NIT 32

9

N5:H

3-6

SSB

M2-15

9(L2

)

3 BE

DROOM U

NIT

329

N5:H3-

7

SSB

M2-16

0(L2

)

3 BE

DROOM U

NIT 32

9

N5:H

3-8

SSB

M2-16

1(L2

)

3 BE

DROOM U

NIT

329

N5:H3-

9

SSB

M2-16

2(L2

)

2 BE

DROOM U

NIT 32

6

N5:H

3-10

SSB

M2-16

3(L2

)

2 BE

DROOM U

NIT

326

N5:H3-

11

SSB

M2-16

4(L2

)

2 BE

DROOM U

NIT 32

6

N5:H

3-12

SSB

M2-16

5(L2

)

2 BE

DROOM U

NIT

324

N6:H

3-13

SSB

M2-16

6(L2

)

2 BE

DROOM U

NIT 32

4

N6:H3-

12

SSB

M2-16

7(L2

)

2 BE

DROOM U

NIT

324

N6:H

3-11

SSB

M2-16

8(L2

)

2 BE

DROOM U

NIT

321

N6:H

3-10

SSB

M2-16

9(L2

)

2 BE

DROOM U

NIT

321

N6:H3-

9

SSB

M2-17

0(L2

)

2 BE

DROOM U

NIT

321

N6:H

3-8

SSB

M2-17

1(L2

)

2 BE

DROOM U

NIT

319

N6:H3-

7

SSB

M2-17

2(L2

)

2 BE

DROOM U

NIT 31

9

N6:H

3-6

SSB

M2-17

3(L2

)

2 BE

DROOM U

NIT

319

N6:H3-

5

SSB

M2-17

4(L2

)

2 BE

DROOM U

NIT

317

N6:H

3-4

SSB

M2-17

5(L2

)

2 BE

DROOM U

NIT 31

7

N6:H3-

3

SSB

M2-17

6(L2

)

2 BE

DROOM U

NIT

317

N6:H3-

2

SSB

M2-17

7(L2

)

STUDI

O UNI

T 31

5

N6:H

3-1

S

M2-17

8(L2

)

ELEV

LOBB

Y 36

0

S

M2-17

9(L2

)

ELEC

T 36

4

NAC

6

M2-18

0(L2

)

ELEC

T 36

4

SSB

M2-18

1(L2

)

2 BE

DROOM U

NIT

310

N6:H

1-1

SSB

M2-18

2(L2

)

2 BE

DROOM U

NIT

310

N6:H

1-2

SSB

M2-18

3(L2

)

2 BE

DROOM U

NIT

310

N6:H

1-3

SSB

M2-18

4(L2

)

1 BE

DROOM U

NIT

308

N6:H

1-4

SSB

M2-18

5(L2

)

1 BE

DROOM U

NIT 30

8

N6:H

1-5

SSB

M2-18

6(L2

)

2 BE

DROOM U

NIT

306

N6:H

1-6

SSB

M2-18

7(L2

)

2 BE

DROOM U

NIT 30

6

N6:H

1-7

SSB

M2-18

8(L2

)

2 BE

DROOM U

NIT

306

N6:H

1-8

SSB

M2-18

9(L2

)

1 BE

DROOM U

NIT 30

4

N6:H

1-9

SSB

M2-19

0(L2

)

1 BE

DROOM U

NIT

304

N6:H

1-10

SSB

M2-19

1(L2

)

STUDI

O UNIT

302

N6:H1-

11

SSB

M2-19

2(L2

)

2 BE

DROOM U

NIT

300

N6:H

1-12

SSB

M2-19

3(L2

)

2 BE

DROOM U

NIT

300

N6:H

1-13

SSB

M2-19

4(L2

)

2 BE

DROOM U

NIT

300

N6:H

1-14

SSB

M2-19

5(L2

)

2 BE

DROOM U

NIT

336

N5:H

4-1

SSB

M2-19

6(L2

)

2 BE

DROOM U

NIT

336

N5:H4-

2

SSB

M2-19

7(L2

)

2 BE

DROOM U

NIT

336

N5:H

4-3

SSB

M2-19

8(L2

)

STUDI

O UNI

T 33

5

N5:H

4-4

SSB

M2-19

9(L2

)

2 BE

DROOM U

NIT

334

N5:H4-

5

SSB

M2-20

0(L2

)

2 BE

DROOM U

NIT 33

4

N5:H

4-6

SSB

M2-20

1(L2

)

2 BE

DROOM U

NIT

334

N5:H4-

7

SSB

M2-20

2(L2

)

1 BE

DROOM U

NIT

332

N5:H

4-8

SSB

M2-20

3(L2

)

1 BE

DROOM U

NIT 33

2

N5:H4-

9

SSB

M2-20

4(L2

)

1 BE

DROOM U

NIT

330

N5:H

4-10

SSB

M2-20

5(L2

)

1 BE

DROOM U

NIT

330

N5:H4-

11

SSB

M2-20

6(L2

)

1 BE

DROOM U

NIT

328

N5:H

4-12

SSB

M2-20

7(L2

)

1 BE

DROOM U

NIT

328

N5:H

4-13

SSB

M2-20

8(L2

)

STUDI

O UNI

T 32

7H9-

1

SSB

M2-20

9(L2

)

2 BE

DROOM U

NIT

325

H9-2

SSB

M2-21

0(L2

)

2 BE

DROOM U

NIT

325

H9-3

SSB

M2-21

1(L2

)

2 BE

DROOM U

NIT

325

H9-4

SSB

M2-21

2(L2

)

2 BE

DROOM U

NIT

323

H9-5

SSB

M2-21

3(L2

)

2 BE

DROOM U

NIT 32

3

H9-6

SSB

M2-21

4(L2

) 2

BEDR

OOM UNI

T 32

3

H9-7

SSB

M2-21

5(L2

)

1 BE

DROOM U

NIT

322

H9-8

SSB

M2-21

6(L2

)

1 BE

DROOM U

NIT

322

H9-9

SSB

M2-21

7(L2

)

1 BE

DROOM U

NIT 32

0

N6:H

4-15

SSB

M2-21

8(L2

)

1 BE

DROOM U

NIT

320

N6:H4-

14

SSB

M2-21

9(L2

)

1 BE

DROOM U

NIT

318

N6:H

4-13

SSB

M2-22

0(L2

)

1 BE

DROOM U

NIT

318

N6:H

4-12

SSB

M2-22

1(L2

)

1 BE

DROOM U

NIT

316

N6:H

4-11

SSB

M2-22

2(L2

)

1 BE

DROOM U

NIT

316

N6:H

4-10

SSB

M2-22

3(L2

)

2 BE

DROOM U

NIT

314

N6:H4-

9

SSB

M2-22

4(L2

)

2 BE

DROOM U

NIT

314

N6:H

4-8

SSB

M2-22

5(L2

)

2 BE

DROOM U

NIT 31

4

N6:H4-

7

SSB

M2-22

6(L2

)

3 BE

DROOM U

NIT

313

N6:H

4-6

SSB

M2-22

7(L2

)

3 BE

DROOM U

NIT 31

3

N6:H4-

5

SSB

M2-22

8(L2

)

3 BE

DROOM U

NIT

313

N6:H4-

4

SSB

M2-22

9(L2

)

3 BE

DROOM U

NIT 31

3

N6:H

4-3

AOM

DAMPE

R CO

NTRO

L

M2-23

0(L2

)

CORR

IDOR

344R

TO DAMPERCONTROL

SSB

M2-23

1(L2

)

1 BE

DROOM U

NIT

312

N6:H

4-2

SSB

M2-23

2(L2

)

1 BE

DROOM U

NIT 31

2

N6:H4-

1

SSB

M2-23

3(L2

)

1 BE

DROOM U

NIT

311

N6:H

2-1

SSB

M2-23

4(L2

)

1 BE

DROOM U

NIT 31

1

N6:H

2-2

SSB

M2-23

5(L2

)

2 BE

DROOM U

NIT

309

N6:H

2-3

SSB

M2-23

6(L2

)

2 BE

DROOM U

NIT 30

9

N6:H

2-4

SSB

M2-23

7(L2

)

2 BE

DROOM U

NIT

309

N6:H

2-5

SSB

M2-23

8(L2

)

1 BE

DROOM U

NIT

307

N6:H

2-6

SSB

M2-23

9(L2

)

1 BE

DROOM U

NIT

307

N6:H

2-7

SSB

M2-24

0(L2

)

1 BE

DROOM U

NIT

305

N6:H

2-8

SSB

M2-24

1(L2

)

1 BE

DROOM U

NIT 30

5

N6:H

2-9

SSB

M2-24

2(L2

)

1 BE

DROOM U

NIT

303

N6:H

2-10

SSB

M2-24

3(L2

)

1 BE

DROOM U

NIT

303

N6:H2-

11

SSB

M2-24

4(L2

)

3 BE

DROOM U

NIT 30

1

N6:H

2-12

SSB

M2-24

5(L2

)

3 BE

DROOM U

NIT

301

N6:H

2-13

SSB

M2-24

6(L2

)

3 BE

DROOM U

NIT 30

1

N6:H

2-14

SSB

M2-24

7(L2

)

3 BE

DROOM U

NIT

301

N6:H

2-15

S

M2-24

8(L2

)

CORR

IDOR

344

S

M2-24

9(L2

)

CORR

IDOR

344

S

M3-11

ELEC

T 35

9

NAC

5

M3-12

ELEC

T 35

9

AOM

DAMPE

R CO

NTRO

L M3-13

CORR

IDOR

344R

TO DAMPERCONTROL

S

M3-14

FLOOR

LOBB

Y 35

6

15

A1:1

-18(

3)

CORR

IDOR

344

15

A1:1

-19(

3)

CORR

IDOR

344

15

A1:1

-20(

3)

CORR

IDOR

344

15

A1:1

-21(

3)

CORR

IDOR

344

15

A1:1

-22(

3)

CORR

IDOR

344

15

A1:1

-23(

3)

CORR

IDOR

344

15

A1:1

-24(

3)

CORR

IDOR

344

15

A1:1

-25(

3)

CORR

IDOR

344

15

A1:1

-26(

3)

CORR

IDOR

344

15

A1:1

-27(

3)

CORR

IDOR

344

15

A1:1

-28(

3)

CORR

IDOR

344

15

A1:1

-29(

3)

STORA

GE 358

15

A1:1

-30(

3)

STORA

GE 362

FA-1

05FA

-105

D1-

41DH

D1-

42DH

S

M3-21

ELEC

T 45

9

NAC

7

M3-22

ELEC

T 45

9

AOM

DAMPE

R CO

NTRO

L M3-23

CORR

IDOR

444R

TO DAMPERCONTROL

S

M3-24

FLOOR

LOBB

Y 45

6

SSB

M3-25

2 BE

DROOM U

NIT 44

0

N7:H

1-1

SSB

M3-26

2 BE

DROOM U

NIT

440

N7:H

1-2

SSB

M3-27

2 BE

DROOM U

NIT 44

0

N7:H

1-3

SSB

M3-28

2 BE

DROOM U

NIT 44

3

N7:H

1-4

SSB

M3-29

2 BE

DROOM U

NIT

443

N7:H

1-5

SSB

M3-30

2 BE

DROOM U

NIT

443

N7:H

1-6

SSB

M3-31

2 BE

DROOM U

NIT 44

5

N7:H

1-7

SSB

M3-32

2 BE

DROOM U

NIT

445

N7:H

1-8

SSB

M3-33

2 BE

DROOM U

NIT

445

N7:H

1-9

SSB

M3-34

1 BE

DROOM U

NIT 44

8

N7:H

1-10

SSB

M3-35

1 BE

DROOM U

NIT

448

N7:H

1-11

SSB

M3-36

2 BE

DROOM U

NIT

447

N7:H

1-12

SSB

M3-37

2 BE

DROOM U

NIT

447

N7:H

1-13

SSB

M3-38

2 BE

DROOM U

NIT

447

N7:H

1-14

SSB

M3-39

STUDI

O UNI

T 43

7

N7:H

2-1

SSB

M3-40

1 BE

DROOM U

NIT

438

N7:H

2-2

SSB

M3-41

1 BE

DROOM U

NIT 43

8

N7:H

2-3

SSB

M3-42

1 BE

DROOM U

NIT

439

N7:H

2-4

SSB

M3-43

1 BE

DROOM U

NIT

439

N7:H

2-5

SSB

M3-44

STUDI

O UNI

T 44

1

N7:H

2-6

SSB

M3-45

1 BE

DROOM U

NIT 44

2

N7:H

2-7

SSB

M3-46

1 BE

DROOM U

NIT

442

N7:H

2-8

SSB

M3-47

1 BE

DROOM U

NIT 44

4

N7:H

2-9

SSB

M3-48

1 BE

DROOM U

NIT

444

N7:H

2-10

SSB

M3-49

2 BE

DROOM U

NIT

446

N7:H2-

11

SSB

M3-50

2 BE

DROOM U

NIT 44

6

N7:H

2-12

SSB

M3-51

2 BE

DROOM U

NIT

446

N7:H

2-13

SSB

M3-52

2 BE

DROOM U

NIT

433

N7:H

3-1

SSB

M3-53

2 BE

DROOM U

NIT

433

N7:H3-

2

SSB

M3-54

2 BE

DROOM U

NIT

433

N7:H

3-3

SSB

M3-55

1 BE

DROOM U

NIT

431

N7:H

3-4

SSB

M3-56

1 BE

DROOM U

NIT

431

N7:H3-

5

SSB

M3-57

3 BE

DROOM U

NIT 42

9

N7:H

3-6

SSB

M3-58

3 BE

DROOM U

NIT

429

N7:H3-

7

SSB

M3-59

3 BE

DROOM U

NIT 42

9

N7:H

3-8

SSB

M3-60

3 BE

DROOM U

NIT

429

N7:H3-

9

SSB

M3-61

2 BE

DROOM U

NIT 42

6

N7:H

3-10

SSB

M3-62

2 BE

DROOM U

NIT

426

N7:H3-

11

SSB

M3-63

2 BE

DROOM U

NIT 42

6

N7:H

3-12

SSB

M3-64

2 BE

DROOM U

NIT

424

N8:H

3-13

SSB

M3-65

2 BE

DROOM U

NIT 42

4

N8:H3-

12

SSB

M3-66

2 BE

DROOM U

NIT

424

N8:H

3-11

SSB

M3-67

2 BE

DROOM U

NIT

421

N8:H

3-10

SSB

M3-68

2 BE

DROOM U

NIT

421

N8:H3-

9

SSB

M3-69

2 BE

DROOM U

NIT

421

N8:H

3-8

SSB

M3-70

2 BE

DROOM U

NIT

419

N8:H3-

7

SSB

M3-71

2 BE

DROOM U

NIT 41

9

N8:H

3-6

SSB

M3-72

2 BE

DROOM U

NIT

419

N8:H3-

5

SSB

M3-73

2 BE

DROOM U

NIT

417

N8:H

3-4

SSB

M3-74

2 BE

DROOM U

NIT 41

7

N8:H3-

3

SSB

M3-75

2 BE

DROOM U

NIT

417

N8:H3-

2

SSB

M3-76

STUDI

O UNI

T 41

5

N8:H

3-1

S

M3-77

ELEV

LOBB

Y 46

0

S

M3-78

ELEC

T 46

4

NAC

8

M3-79

ELEC

T 46

4

SSB

M3-80

2 BE

DROOM U

NIT

410

N8:H

1-1

SSB

M3-81

2 BE

DROOM U

NIT

410

N8:H

1-2

SSB

M3-82

2 BE

DROOM U

NIT

410

N8:H

1-3

SSB

M3-83

1 BE

DROOM U

NIT

408

N8:H

1-4

SSB

M3-84

1 BE

DROOM U

NIT 40

8

N8:H

1-5

SSB

M3-85

2 BE

DROOM U

NIT

406

N8:H

1-6

SSB

M3-86

2 BE

DROOM U

NIT 40

6

N8:H

1-7

SSB

M3-87

2 BE

DROOM U

NIT

406

N8:H

1-8

SSB

M3-88

1 BE

DROOM U

NIT 40

4

N8:H

1-9

SSB

M3-89

1 BE

DROOM U

NIT

404

N8:H

1-10

SSB

M3-90

UNI

T 40

2

N8:H

1-11

SSB

M3-91

2 BE

DROOM U

NIT

400

N8:H

1-12

SSB

M3-92

2 BE

DROOM U

NIT

400

N8:H

1-13

SSB

M3-93

2 BE

DROOM U

NIT

400

N8:H

1-14

SSB

M3-94

2 BE

DROOM U

NIT

436

N7:H

4-1

SSB

M3-95

2 BE

DROOM U

NIT

436

N7:H4-

2

SSB

M3-96

2 BE

DROOM U

NIT

436

N7:H

4-3

SSB

M3-97

STUDI

O UNI

T 43

5

N7:H

4-4

SSB

M3-98

2 BE

DROOM U

NIT

434

N7:H4-

5

SSB

M3-99

2 BE

DROOM U

NIT 43

4

N7:H

4-6

SSB

M3-10

0

2 BE

DROOM U

NIT

434

N7:H4-

7

SSB

M3-10

1

1 BE

DROOM U

NIT

432

N7:H

4-8

SSB

M3-10

2

1 BE

DROOM U

NIT 43

2

N7:H4-

9

SSB

M3-10

3

1 BE

DROOM U

NIT 43

0

N7:H

4-10

SSB

M3-10

4

1 BE

DROOM U

NIT

430

N7:H4-

11

SSB

M3-10

5

1 BE

DROOM U

NIT

428

N7:H

4-12

SSB

M3-10

6

1 BE

DROOM U

NIT

428

N7:H

4-13

SSB

M3-10

7

STUDI

O UNI

T 42

7H10

-1

SSB

M3-10

8

2 BE

DROOM U

NIT

425

H10-2

SSB

M3-10

9

2 BE

DROOM U

NIT

425

H10-3

SSB

M3-11

0

2 BE

DROOM U

NIT

425

H10-4

SSB

M3-11

1

2 BE

DROOM U

NIT

423

H10-5

SSB

M3-11

2

2 BE

DROOM U

NIT

423

H10-6

SSB

M3-11

3

2 BE

DROOM U

NIT

423

H10-7

SSB

M3-11

4

1 BE

DROOM U

NIT

422

H10-8

SSB

M3-11

5

1 BE

DROOM U

NIT

422

H10-9

SSB

M3-11

6

1 BE

DROOM U

NIT 42

0

N8:H

4-15

SSB

M3-11

7

1 BE

DROOM U

NIT

420

N8:H4-

14

SSB

M3-11

8

1 BE

DROOM U

NIT

418

N8:H

4-13

SSB

M3-11

9

1 BE

DROOM U

NIT

418

N8:H

4-12

SSB

M3-12

0

1 BE

DROOM U

NIT

416

N8:H

4-11

SSB

M3-12

1

1 BE

DROOM U

NIT

416

N8:H

4-10

SSB

M3-12

2

2 BE

DROOM U

NIT

414

N8:H4-

9

SSB

M3-12

3

2 BE

DROOM U

NIT

414

N8:H

4-8

SSB

M3-12

4

2 BE

DROOM U

NIT 41

4

N8:H4-

7

SSB

M3-12

5

3 BE

DROOM U

NIT

413

N8:H

4-6

SSB

M3-12

6

3 BE

DROOM U

NIT 41

3

N8:H4-

5

SSB

M3-12

7

3 BE

DROOM U

NIT

413

N8:H4-

4

SSB

M3-12

8

3 BE

DROOM U

NIT 41

3

N8:H

4-3

SSB

M3-12

9

1 BE

DROOM U

NIT

412

N8:H4-

2

SSB

M3-13

0

1 BE

DROOM U

NIT

412

N8:H

4-1

AOM

DAMPE

R CO

NTRO

L

M3-13

1

CORR

IDOR

444R

TO DAMPERCONTROL

SSB

M3-13

2

1 BE

DROOM U

NIT

411

N8:H

2-1

SSB

M3-13

3

1 BE

DROOM U

NIT 41

1

N8:H

2-2

SSB

M3-13

4

2 BE

DROOM U

NIT

409

N8:H

2-3

SSB

M3-13

5

2 BE

DROOM U

NIT 40

9

N8:H

2-4

SSB

M3-13

6

2 BE

DROOM U

NIT

409

N8:H

2-5

SSB

M3-13

7

1 BE

DROOM U

NIT

407

N8:H

2-6

SSB

M3-13

8

1 BE

DROOM U

NIT

407

N8:H

2-7

SSB

M3-13

9

1 BE

DROOM U

NIT

405

N8:H

2-8

SSB

M3-14

0

1 BE

DROOM U

NIT 40

5

N8:H

2-9

SSB

M3-14

1

1 BED

ROOM U

NIT

403

N8:H

2-10

SSB

M3-14

2

1 BED

ROOM U

NIT

403

N8:H2-

11

SSB

M3-14

3

3 BE

DROOM U

NIT 40

1

N8:H

2-12

SSB

M3-14

4

3 BE

DROOM U

NIT

401

N8:H

2-13

SSB

M3-14

5

3 BE

DROOM U

NIT 40

1

N8:H

2-14

SSB

M3-14

6

3 BE

DROOM U

NIT

401

N8:H

2-15

S

M3-14

7

CORR

IDOR

444

S

M3-14

8

CORR

IDOR

444

15

A1:2

-26(

3)

CORR

IDOR

444

15

A1:2

-27(

3)

CORR

IDOR

444

15

A1:2

-28(

3)

CORR

IDOR

444

15

A1:2

-29(

3)

CORR

IDOR

444

15

A1:2

-30(

3)

STORA

GE 458

15

A1:2

-31(

3)

CORR

IDOR

444

15

A1:2

-32(

3)

CORR

IDOR

444

15

A1:2

-33(

3)

CORR

IDOR

444

15

A1:2

-34(

3)

CORR

IDOR

444

15

A1:2

-35(

3)

CORR

IDOR

444

15

A1:2

-36(

3)

CORR

IDOR

444

15

A1:2

-37(

3)

CORR

IDOR

444

15

A1:2

-38(

3)

STORA

GE 462

N5:

H1

10K

N5:

H2

10K

N5:

H3

10K

N5:

H4

10K

N6:

H1

10K

N6:

H2

10K

N6:

H3

10K

N6:

H4

10K

H9

10K

N7:

H1

10K

N7:

H2

10K

N7:

H3

10K

N7:

H4

10K

N8:

H1

10K

N8:

H2

10K

N8:

H3

10K

N8:

H4

10K

H10 10K

A,D

,M,V

A,D

,M,V

2A,D

,2M

,2V

JBJB

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

RISER NOTES:

1. RISER IS A DIAGRAMMATICAL REPRESENTATION OF THE SYSTEMARCHITECTURE IN BUILDING CROSS SECTION. IT IS NOT INTENDEDTO REPRESENT ACTUAL WIRE RUNS, PANEL CONFIGURATIONS ORPENETRATIONS. REFER TO FLOOR PLANS AND PANEL DETAILS FORCIRCUIT ROUTING AND CONFIGURATION INFORMATION.

2. ALL WIRING SHALL COMPLY WITH APPLICABLE ELECTRICAL CODES.REFER TO 'APPLICABLE CODES & STANDARDS' ON SHEET FA-000 FORSPECIFIC CODE REFERENCES.

3. ALL 520 Hz SOUNDER BASES: DIP SWITCH 9 SHALL BE SET TO 'ON'FOR NAC CIRCUIT SUPERVISION.

SCALE: NTS

RISER DIAGRAM

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-2

01.d

wg

9/13

/201

6 9:

52:2

2 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-202

RISER DIAGRAM

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-201.dwg, FA-202 RISER DIAGRAM, 9/13/2016 9:52:21 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 11: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

SCALE: NTS

FIRE ALARM CONTROL PANELCABINET # 1 - GARAGE

MECH. 010

56

24

P7

P6

P1

P424V

P2

P3

OVP5

P7

P6

P1

P424V

P2

P3

OVP5

P7

P6

P1

P424V

P2

P3

OVP5

R

BATT

ERY

CONNECT TO 120VAC 60HZ

P2 P3 P4P1

AC

NEU

TRAL

MOUNTS TO BACKBOX

DO NOT LOCATE POWER-LIMITED WIRING IN THE SHADED AREASOF THE BACKBOX, THIS AREA IS RESERVED FOR NON-POWERLIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES AND CITYCONNECTION.

SYSTEM CONDUIT, 3/4" MIN. (2" SHOWN)REFER TO MOUNTING DETAIL FOR TYP.CONDUIT PENETRATION LOCATIONS

V

10K

H3 - 1ST FLOOR NORTH-CENTERH4 - 2ND FLOOR NORTH-CENTER

DTO 24VDC DOOR HOLDERS

PTO LCD ANNUNCIATOR IN VEST. 005

SYSTEM POWER SUPPLY

B+

SHLD

IDNet

B- A+ A-

120VAC 60Hz

NAC

B+ B- A+ A- B+

NAC

B+ B- A-A+

NAC

A+B- A-

1TB1

2 3 4 5TB2

1 2 3 4 965 87 1110 12

BTRY (-)

BTRY (+)AUX1

+24- +

OVPOWER

TB3

AUX

NO C

TB4

CITY

NC

P6

P5

P4

P3

1 2 3

FERRITE BEAD

MM1-x - GARAGE/1ST FLOOR IDNET DEVICES

1

POWER

OV

TB2

+24

AUX

- +

2 3 4 5 6 7 8 9 10 11 12B+ B- A+ A-

4100-5101XPS POWER SUPPLY

120VAC 60Hz

B+ B- A+ A- B+ B- A+ A-

SW1

5

6

7

8

1

2

3

4

P1

V

NACNACNAC

10K

H9 - 3RD FLOOR NORTH-CENTERH10 - 4TH FLOOR NORTH-CENTER

1 2 3

CA

120VAC 60HzENHANCED TA POWER SUPPLY

4100-5311

ON1

24

35

76

8

EARTH FAULTJUMPER

B-B-B+B+IDNAC 1

B+B+ B- B-IDNAC 2

B+B+ B- B-IDNAC 3

BTRY (+)

BTRY (-)

RECT (-)

RECT (+)

POWERAUX

-+

OV+24

TB1 TB2 TB3 TB4

4100-3109IDNet2 MODULE

250 DEVICES SW19600/OFF

16

8

4

2

1

64

32

1

8

2

3

4

5

6

7

TB1

A-A- A+ B- B+A+ B- B+LOOP 1LOOP 2

AAB B

AAB B

CACA

CA P

AA1:1-x(1) - GARAGE-WESTA1:1-x(2) - GARAGE-EASTA1:1-x(3) - 3RD FLOOR

AA1:2-x(1) - 1ST FLOOR WESTA1:2-x(2) - 1ST FLOOR EASTA1:2-x(3) - 4TH FLOOR

AA1:3-x(1) - 2ND FLOOR WESTA1:3-x(2) - 2ND FLOOR EAST

1

TO LCD ANNUNCIATOR IN VEST. 005FERRITE BEAD

R+

OV-

1

RSRV

D

GN

DR- RUI

P7POWER

RCV

RTS

XMIT

24C

GN

D

CTS

PIEZ

O

RSRV

D

TB1

RS232

NETWORK

L+ RSRV

D

GN

D

L- OV-

2

P4

P5

P6

COMMP8

NET

WO

RK/R

S232

DAU

GH

TER

CARD

CPU

DAU

GH

TER

CARD

MOTHERBOARD

NETWORK

CPU

XMIT

TB3

RUI B

+

RCV

RS232

RTS

CTS

GN

D

TB2

RUI B

-

RUI A

+

SHLD

RUI A

-

1 32 4 5 1 32 4 5

AC Power

Reset

SystemFire Alarm

Event

Time

Enable

Disable

Lamp

More

Off

Disarm

On

Arm

Auto

Priority 2

Ack Ack

Supv

Ack

Menu

Test

Next

Trouble

Ack

Info

Previous

Silence

Alarm

Fire Alarm

SYSTEM WARNINGS

Priority 2 Alarm

ALARMS

Supervisory

Alarm SilencedTrouble

DEMARCATION POINTTO TELEPHONE

RUI C

ONNE

CTOR

4100

COM

M

P1P2 RU

I CON

NECT

OR

SW1

P3

SW3

SW2

P4

21

34

SW4

5678/OFF

BRACKETMOUNTS ON

DACT

EVENTREPORTING

4100-6052

RING2RING

HOUSE 2TIP

HOUSE 2TIP2

RINGHOUSE 1

RING1TIP1

TIPHOUSE 1

CA

4100-3110IDNet2+2 MODULE

250 DEVICES

SW19600/OFF

16

8

4

2

1

64

32

1

8

2

3

4

5

6

7

TB1

A- A-A+B-B+ A+B-B+

LOOP 1 LOOP 2

A ABB

A ABB

IDNet2 EXPLOOP CARD

B+ B- A+ A-

A ABB

IDNet2 EXPLOOP CARD

B+ B- A+ A-

A ABB

CA

MM2-x (L1) - 2ND FLOOR IDNET DEVICESM2-x (L2) - 3RD FLOOR IDNET DEVICES

8 SPDT 3 AMPRELAY BOARD

4100-3206

C NO NCCNC NCNONCNO NOCCRELAY R1RELAY R2

C NO NCCNC NCNONCNO NOCC

RELAY R3RELAY R4

RELAY R5RELAY R6RELAY R7RELAY R8

CA

+

2081-929650 Ah BATTERY

-

50 Ah BATTERY2081-9296

+ -

M4R

M2R

NO CONNECTION

M3-x -

2ND/

3RD/

4TH FL

OOR ID

NET

DEVI

CES

M

FERRITE BEAD

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-5

01.d

wg

9/13

/201

6 9:

52:2

6 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-501

PANEL LAYOUT

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

SCALE: NTS

PANEL LAYOUT

s:\1-current projects\7555-parkway off central\Fire\FA-501.dwg, FA-501 PANEL LAYOUT, 9/13/2016 9:52:25 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 12: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Parkway Off Central 4100es FACPStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4100-9111 1 4100 CONFIG. DOMESTIC 120V * 0.3730 0.3730 0.4700 0.4700

4100-0634 1 POWER DISTRIBUTION MODULE 120V 0.0000 0.0000 0.0000 0.0000

4100-1279 16 2" BLANK DISPLAY MODULE 0.0000 0.0000 0.0000 0.0000

4100-2300 2 EXPANSION BAY (PHASE 10 ONLY) 0.0000 0.0000 0.0000 0.0000

4100-3110 1 IDNet2+2 MODULE - UP TO 250 DEVICES 4 ISOLATED LOOPS * 0.0500 0.0500 0.1000 0.1000

4100-3206 1 8 RELAYS - 3 AMP 0.0150 0.0150 0.1900 0.1900

4100-5101 1 EXPANSION PWR SUPPLY (XPS) - 120VAC 60HZ 0.0500 0.0500 0.0500 0.0500

4100-5311 1 ENHANCED POWER SUPPLY, 3 CHANNELS, IDNet, 120V 0.2250 0.2250 0.4900 0.4900

4100-6052 1 EVENT REPORTING DACT 0.0300 0.0300 0.0400 0.0400

Panel Totals 0.7430 1.3400

IDNet Addressable Devices (SLC)

4099-9004 1 ADDRESSABLE SINGLE ACTION MANUAL STATION *

Constant current draw of .8mA standby and 1mA alarm peraddress used. Devices requiring additional current are

accounted for in the section labeled "MiscellaneousPeripheral Devices Requiring Additional System Power".

4090-9001 12 IDNET SUPERVISED IAM *

4090-9002 14 IDNET RELAY IAM *

4098-9714 490 TRUEALARM PHOTO SMOKE SENSOR

4009-9201 8 4009 IDNET NAC EXTENDER, 120 VAC *

4098-9792 29 TRUEALARM SENSOR BASE *

4098-9794 461 TRUEALARM SENSOR SOUNDER BASE *

Miscellaneous Peripheral Devices That Require (Additional) System Power

4603-9101 1 SERIAL LCD ANNUNCIATOR 0.0650 0.0650 0.1400 0.1400

Notification Appliances

4098-9772 37 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 4.7730

49AV-WRF 52 A/V WALL MT, RED, FIRE LABEL 15 0.0008 0.0416 0.0590 3.0680

49AV-WRF 1 A/V WALL MT, RED, FIRE LABEL 30 0.0008 0.0008 0.0670 0.0670

49AV-WRF 17 A/V WALL MT, RED, FIRE LABEL 75 0.0008 0.0136 0.1070 1.8190

49VO-WRF 11 VO, WALL MT, RED, FIRE LABEL 15 0.0008 0.0088 0.0470 0.5170

49VO-WRF 7 VO, WALL MT, RED, FIRE LABEL 185 0.0008 0.0056 0.2080 1.4560Peripheral Totals 0.1354 11.8400

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 3.9492

RUI Totals 1 0.0035 0.0035

Address Totals 525 Addresses 0.4200 0.5250

* Device Address current draw included below (See Additional Current Draws): System Totals*: Standby 1.3019 Alarm 17.6577

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

SPS-1 0.5330 3.3910

XPS-2 0.0500 2.3720

EPS-1 0.2954 7.4170

Sub Total 0.8784 13.1800

Additional Current Draws: IDNac Current Boost for 29vdc Regulated Output ** 0.0000 3.9492

RUI Connected Peripheral Devices 1 x 0.0035 = 0.0035 x 0.0035 = 0.0035

MAPNET/IDNet Device Address Communication Current 525 x 0.000800 = 0.4200 x 0.001000 = 0.5250

Sub Total 1.3019 17.6577

Spare addressable point capacity 0% 0 x 0.0008 = 0.0000 x 0.001 = 0.0000

Total 1.3019 17.6577

Standby Time = 24 Hrs x 1.3019 = 31.2456 Standby Ah

Alarm Time = 5 Min 0.08333 x 17.6577 = 1.4715 Alarm Ah

32.7171Additional Spare Battery Capacity = 0% + 0.0000

32.7171Battery Discharge Factor = 20% + 6.5434Minimum Battery Required 2081-9296 50AH (2x) 39.2605

Battery Supplied 2081-9296 50AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

IDNET CHANNEL M1 ADDRESSES IN USE: 147 (58.8%) | SPARE ADDRESSES: 103 (41.2%) SWITCH SETTINGS

Address Device Type Point Type Location Description 1 2 3 4 5 6 7 8 9

M1-1 PHOTO SMOKE MECH 010 1-1 X ON

M1-2 PHOTO SMOKE LOBBY 007 1-2 X ON

M1-3 ADRPUL PULL STAIR "C" 006 1-3 X X ON

M1-4 PHOTO SMOKE ELEV EQUIP 009 1-4 X ON

M1-5 RIAM PRIMARY ELEV EQUIP 009 1-5 X X ON

M1-6 RIAM ALTERN ELEV EQUIP 009 1-6 X X ON

M1-7 RIAM RELAY ELEV EQUIP 009 1-7 X X X ON

M1-8 IAM WATER MECH 113 1-8 X ON

M1-9 IAM WATER MECH 113 1-9 X X ON

M1-10 IAM WATER MECH 113 1-10 X X ON

M1-11 IAM WATER MECH 113 1-11 X X X ON

M1-12 IAM SO MECH 113 1-12 X X ON

M1-13 IAM SO MECH 113 1-13 X X X ON

M1-14 IAM SO MECH 113 1-14 X X X ON

M1-15 IAM SO MECH 113 1-15 X X X X ON

M1-16 IAM SO MECH 113 1-16 X ON

M1-17 IAM SO MECH 113 1-17 X X ON

M1-18 IAM SO MECH 113 1-18 X X ON

M1-19 IAM SO MECH 113 1-19 X X X ON

M1-20 PHOTO SMOKE LOBBY 014 1-20 X X ON

M1-21 PHOTO SMOKE ELEV. EQUIP 017 1-21 X X X ON

M1-22 RIAM PRIMARY ELEV. EQUIP 017 1-22 X X X ON

M1-23 RIAM ALTERN ELEV. EQUIP 017 1-23 X X X X ON

M1-24 RIAM RELAY ELEV. EQUIP 017 1-24 X X ON

M1-25 X X X ON

M1-26 X X X ON

M1-27 X X X X ON

M1-28 X X X ON

M1-29 X X X X ON

M1-30 X X X X ON

M1-31 NAC4PT SIGNAL ELECT ROOM 165 1-31 X X X X X ON

M1-32 PHOTO SMOKE ELECT ROOM 165 1-32 X ON

M1-33 RIAM RELAY BY CONF. ROOM 160 1-33 X X ON

M1-34 PHOTO SMOKE LOBBY 158 1-34 X X ON

M1-35 SPHOTO SMOKE 2 BEDROOM UNIT 136 1-35 X X X ON ON

M1-36 SPHOTO SMOKE 2 BEDROOM UNIT 136 1-36 X X ON ON

M1-37 SPHOTO SMOKE 2 BEDROOM UNIT 136 1-37 X X X ON ON

M1-38 SPHOTO SMOKE 2 BEDROOM UNIT 138 1-38 X X X ON ON

M1-39 SPHOTO SMOKE 2 BEDROOM UNIT 138 1-39 X X X X ON ON

M1-40 SPHOTO SMOKE 2 BEDROOM UNIT 138 1-40 X X ON ON

M1-41 SPHOTO SMOKE 2 BEDROOM UNIT 140 1-41 X X X ON ON

M1-42 SPHOTO SMOKE 2 BEDROOM UNIT 140 1-42 X X X ON ON

M1-43 SPHOTO SMOKE 2 BEDROOM UNIT 140 1-43 X X X X ON ON

M1-44 SPHOTO SMOKE 1 BEDROOM UNIT 143 1-44 X X X ON ON

M1-45 SPHOTO SMOKE 1 BEDROOM UNIT 143 1-45 X X X X ON ON

M1-46 SPHOTO SMOKE STUDIO UNIT 134 1-46 X X X X ON ON

M1-47 SPHOTO SMOKE STUDIO UNIT 135 1-47 X X X X X ON ON

M1-48 SPHOTO SMOKE 1 BEDROOM UNIT 137 1-48 X X ON ON

M1-49 SPHOTO SMOKE 1 BEDROOM UNIT 137 1-49 X X X ON ON

M1-50 SPHOTO SMOKE 1 BEDROOM UNIT 139 1-50 X X X ON ON

M1-51 SPHOTO SMOKE 1 BEDROOM UNIT 139 1-51 X X X X ON ON

M1-52 SPHOTO SMOKE 2 BEDROOM UNIT 141 1-52 X X X ON ON

M1-53 SPHOTO SMOKE 2 BEDROOM UNIT 141 1-53 X X X X ON ON

M1-54 SPHOTO SMOKE 2 BEDROOM UNIT 141 1-54 X X X X ON ON

M1-55 SPHOTO SMOKE 2 BEDROOM UNIT 142 1-55 X X X X X ON ON

M1-56 SPHOTO SMOKE 2 BEDROOM UNIT 142 1-56 X X X ON ON

M1-57 SPHOTO SMOKE 2 BEDROOM UNIT 142 1-57 X X X X ON ON

M1-58 SPHOTO SMOKE 1 BEDROOM UNIT 131 1-58 X X X X ON ON

M1-59 SPHOTO SMOKE 1 BEDROOM UNIT 131 1-59 X X X X X ON ON

M1-60 SPHOTO SMOKE 3 BEDROOM UNIT 129 1-60 X X X X ON ON

M1-61 SPHOTO SMOKE 3 BEDROOM UNIT 129 1-61 X X X X X ON ON

M1-62 SPHOTO SMOKE 3 BEDROOM UNIT 129 1-62 X X X X X ON ON

M1-63 SPHOTO SMOKE 3 BEDROOM UNIT 129 1-63 X X X X X X ON ON

M1-64 SPHOTO SMOKE 2 BEDROOM UNIT 126 1-64 X ON ON

M1-65 SPHOTO SMOKE 2 BEDROOM UNIT 126 1-65 X X ON ON

M1-66 SPHOTO SMOKE 2 BEDROOM UNIT 126 1-66 X X ON ON

M1-67 SPHOTO SMOKE 2 BEDROOM UNIT 124 1-67 X X X ON ON

M1-68 SPHOTO SMOKE 2 BEDROOM UNIT 124 1-68 X X ON ON

M1-69 SPHOTO SMOKE 2 BEDROOM UNIT 124 1-69 X X X ON ON

M1-70 SPHOTO SMOKE 2 BEDROOM UNIT 121 1-70 X X X ON ON

M1-71 SPHOTO SMOKE 2 BEDROOM UNIT 121 1-71 X X X X ON ON

M1-72 SPHOTO SMOKE 2 BEDROOM UNIT 121 1-72 X X ON ON

M1-73 SPHOTO SMOKE 2 BEDROOM UNIT 119 1-73 X X X ON ON

M1-74 SPHOTO SMOKE 2 BEDROOM UNIT 119 1-74 X X X ON ON

M1-75 SPHOTO SMOKE 2 BEDROOM UNIT 119 1-75 X X X X ON ON

M1-76 SPHOTO SMOKE 2 BEDROOM UNIT 117 1-76 X X X ON ON

M1-77 SPHOTO SMOKE 2 BEDROOM UNIT 117 1-77 X X X X ON ON

M1-78 SPHOTO SMOKE 2 BEDROOM UNIT 117 1-78 X X X X ON ON

M1-79 SPHOTO SMOKE STUDIO UNIT 115 1-79 X X X X X ON ON

M1-80 PHOTO SMOKE ELEV LOBBY 167 1-80 X X ON

M1-81 RIAM RELAY BY STORAGE 168 1-81 X X X ON

M1-82 PHOTO SMOKE ELECT/MECH 170 1-82 X X X ON

M1-83 NAC4PT SIGNAL ELECT/MECH 170 1-83 X X X X ON

M1-84 SPHOTO SMOKE 2 BEDROOM UNIT 110 1-84 X X X ON ON

M1-85 SPHOTO SMOKE 2 BEDROOM UNIT 110 1-85 X X X X ON ON

M1-86 SPHOTO SMOKE 2 BEDROOM UNIT 110 1-86 X X X X ON ON

M1-87 SPHOTO SMOKE 1 BEDROOM UNIT 108 1-87 X X X X X ON ON

M1-88 SPHOTO SMOKE 1 BEDROOM UNIT 108 1-88 X X X ON ON

M1-89 SPHOTO SMOKE 2 BEDROOM UNIT 106 1-89 X X X X ON ON

M1-90 SPHOTO SMOKE 2 BEDROOM UNIT 106 1-90 X X X X ON ON

M1-91 SPHOTO SMOKE 2 BEDROOM UNIT 106 1-91 X X X X X ON ON

M1-92 SPHOTO SMOKE 1 BEDROOM UNIT 104 1-92 X X X X ON ON

M1-93 SPHOTO SMOKE 1 BEDROOM UNIT 104 1-93 X X X X X ON ON

M1-94 SPHOTO SMOKE STUDIO UNIT 102 1-94 X X X X X ON ON

M1-95 SPHOTO SMOKE 2 BEDROOM UNIT 100 1-95 X X X X X X ON ON

M1-96 SPHOTO SMOKE 2 BEDROOM UNIT 100 1-96 X X ON ON

M1-97 SPHOTO SMOKE 2 BEDROOM UNIT 100 1-97 X X X ON ON

M1-98 SPHOTO SMOKE 2 BEDROOM UNIT 133 1-98 X X X ON ON

M1-99 SPHOTO SMOKE 2 BEDROOM UNIT 133 1-99 X X X X ON ON

M1-100 SPHOTO SMOKE 2 BEDROOM UNIT 133 1-100 X X X ON ON

M1-101 SPHOTO SMOKE 1 BEDROOM UNIT 132 1-101 X X X X ON ON

M1-102 SPHOTO SMOKE 1 BEDROOM UNIT 132 1-102 X X X X ON ON

M1-103 SPHOTO SMOKE 1 BEDROOM UNIT 130 1-103 X X X X X ON ON

M1-104 SPHOTO SMOKE 1 BEDROOM UNIT 130 1-104 X X X ON ON

M1-105 SPHOTO SMOKE 1 BEDROOM UNIT 128 1-105 X X X X ON ON

M1-106 SPHOTO SMOKE 1 BEDROOM UNIT 128 1-106 X X X X ON ON

M1-107 SPHOTO SMOKE STUDIO UNIT 127 1-107 X X X X X ON ON

M1-108 SPHOTO SMOKE 2 BEDROOM UNIT 125 1-108 X X X X ON ON

M1-109 SPHOTO SMOKE 2 BEDROOM UNIT 125 1-109 X X X X X ON ON

M1-110 SPHOTO SMOKE 2 BEDROOM UNIT 125 1-110 X X X X X ON ON

M1-111 SPHOTO SMOKE 2 BEDROOM UNIT 123 1-111 X X X X X X ON ON

M1-112 SPHOTO SMOKE 2 BEDROOM UNIT 123 1-112 X X X ON ON

M1-113 SPHOTO SMOKE 2 BEDROOM UNIT 123 1-113 X X X X ON ON

M1-114 SPHOTO SMOKE 1 BEDROOM UNIT 122 1-114 X X X X ON ON

M1-115 SPHOTO SMOKE 1 BEDROOM UNIT 122 1-115 X X X X X ON ON

M1-116 SPHOTO SMOKE 1 BEDROOM UNIT 120 1-116 X X X X ON ON

M1-117 SPHOTO SMOKE 1 BEDROOM UNIT 120 1-117 X X X X X ON ON

M1-118 SPHOTO SMOKE 1 BEDROOM UNIT 118 1-118 X X X X X ON ON

M1-119 SPHOTO SMOKE 1 BEDROOM UNIT 118 1-119 X X X X X X ON ON

M1-120 SPHOTO SMOKE 1 BEDROOM UNIT 116 1-120 X X X X ON ON

M1-121 SPHOTO SMOKE 1 BEDROOM UNIT 116 1-121 X X X X X ON ON

M1-122 SPHOTO SMOKE 2 BEDROOM UNIT 114 1-122 X X X X X ON ON

M1-123 SPHOTO SMOKE 2 BEDROOM UNIT 114 1-123 X X X X X X ON ON

M1-124 SPHOTO SMOKE 2 BEDROOM UNIT 114 1-124 X X X X X ON ON

M1-125 SPHOTO SMOKE 3 BEDROOM UNIT 113 1-125 X X X X X X ON ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

IDNET CHANNEL M1 ADDRESSES IN USE: 147 (58.8%) | SPARE ADDRESSES: 103 (41.2%) SWITCH SETTINGS

Address Location Description 1 2 3 4 5 6 7 8 9

M1-126 SPHOTO SMOKE 3 BEDROOM UNIT 113 1-126 X X X X X X ON ON

M1-127 SPHOTO SMOKE 3 BEDROOM UNIT 113 1-127 X X X X X X X ON ON

M1-128 SPHOTO SMOKE 3 BEDROOM UNIT 113 1-128 X ON ON

M1-129 SPHOTO SMOKE 1 BEDROOM UNIT 112 1-129 X X ON ON

M1-130 SPHOTO SMOKE 1 BEDROOM UNIT 112 1-130 X X ON ON

M1-131 SPHOTO SMOKE 1 BEDROOM UNIT 111 1-131 X X X ON ON

M1-132 SPHOTO SMOKE 1 BEDROOM UNIT 111 1-132 X X ON ON

M1-133 SPHOTO SMOKE 2 BEDROOM UNIT 109 1-133 X X X ON ON

M1-134 SPHOTO SMOKE 2 BEDROOM UNIT 109 1-134 X X X ON ON

M1-135 SPHOTO SMOKE 2 BEDROOM UNIT 109 1-135 X X X X ON ON

M1-136 SPHOTO SMOKE 1 BEDROOM UNIT 107 1-136 X X ON ON

M1-137 SPHOTO SMOKE 1 BEDROOM UNIT 107 1-137 X X X ON ON

M1-138 SPHOTO SMOKE 1 BEDROOM UNIT 105 1-138 X X X ON ON

M1-139 SPHOTO SMOKE 1 BEDROOM UNIT 105 1-139 X X X X ON ON

M1-140 SPHOTO SMOKE 1 BEDROOM UNIT 103 1-140 X X X ON ON

M1-141 SPHOTO SMOKE 1 BEDROOM UNIT 103 1-141 X X X X ON ON

M1-142 SPHOTO SMOKE 3 BEDROOM UNIT 101 1-142 X X X X ON ON

M1-143 SPHOTO SMOKE 3 BEDROOM UNIT 101 1-143 X X X X X ON ON

M1-144 SPHOTO SMOKE 3 BEDROOM UNIT 101 1-144 X X ON ON

M1-145 SPHOTO SMOKE 3 BEDROOM UNIT 101 1-145 X X X ON ON

M1-146 PHOTO SMOKE CORRIDOR 144 1-146 X X X ON

M1-147 PHOTO SMOKE CORRIDOR 144 1-147 X X X X ON

M1-148 X X X ON

M1-149 X X X X ON

M1-150 X X X X ON

M1-151 X X X X X ON

M1-152 X X X ON

M1-153 X X X X ON

M1-154 X X X X ON

M1-155 X X X X X ON

M1-156 X X X X ON

M1-157 X X X X X ON

M1-158 X X X X X ON

M1-159 X X X X X X ON

M1-160 X X ON

M1-161 X X X ON

M1-162 X X X ON

M1-163 X X X X ON

M1-164 X X X ON

M1-165 X X X X ON

M1-166 X X X X ON

M1-167 X X X X X ON

M1-168 X X X ON

M1-169 X X X X ON

M1-170 X X X X ON

M1-171 X X X X X ON

M1-172 X X X X ON

M1-173 X X X X X ON

M1-174 X X X X X ON

M1-175 X X X X X X ON

M1-176 X X X ON

M1-177 X X X X ON

M1-178 X X X X ON

M1-179 X X X X X ON

M1-180 X X X X ON

M1-181 X X X X X ON

M1-182 X X X X X ON

M1-183 X X X X X X ON

M1-184 X X X X ON

M1-185 X X X X X ON

M1-186 X X X X X ON

M1-187 X X X X X X ON

M1-188 X X X X X ON

M1-189 X X X X X X ON

M1-190 X X X X X X ON

M1-191 X X X X X X X ON

M1-192 X X ON

M1-193 X X X ON

M1-194 X X X ON

M1-195 X X X X ON

M1-196 X X X ON

M1-197 X X X X ON

M1-198 X X X X ON

M1-199 X X X X X ON

M1-200 X X X ON

M1-201 X X X X ON

M1-202 X X X X ON

M1-203 X X X X X ON

M1-204 X X X X ON

M1-205 X X X X X ON

M1-206 X X X X X ON

M1-207 X X X X X X ON

M1-208 X X X ON

M1-209 X X X X ON

M1-210 X X X X ON

M1-211 X X X X X ON

M1-212 X X X X ON

M1-213 X X X X X ON

M1-214 X X X X X ON

M1-215 X X X X X X ON

M1-216 X X X X ON

M1-217 X X X X X ON

M1-218 X X X X X ON

M1-219 X X X X X X ON

M1-220 X X X X X ON

M1-221 X X X X X X ON

M1-222 X X X X X X ON

M1-223 X X X X X X X ON

M1-224 X X X ON

M1-225 X X X X ON

M1-226 X X X X ON

M1-227 X X X X X ON

M1-228 X X X X ON

M1-229 X X X X X ON

M1-230 X X X X X ON

M1-231 X X X X X X ON

M1-232 X X X X ON

M1-233 X X X X X ON

M1-234 X X X X X ON

M1-235 X X X X X X ON

M1-236 X X X X X ON

M1-237 X X X X X X ON

M1-238 X X X X X X ON

M1-239 X X X X X X X ON

M1-240 X X X X ON

M1-241 X X X X X ON

M1-242 X X X X X ON

M1-243 X X X X X X ON

M1-244 X X X X X ON

M1-245 X X X X X X ON

M1-246 X X X X X X ON

M1-247 X X X X X X X ON

M1-248 X X X X X ON

M1-249 X X X X X X ON

THRU ON

M1-250 X X X X X X ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

IDNET CHANNEL M2 ADDRESSES IN USE: 254 (101.6%) | SPARE ADDRESSES: -4 (-1.6%) SWITCH SETTINGS

Address Device Type Point Type Location Description 1 2 3 4 5 6 7 8 9

M2-1 PHOTO SMOKE CORRIDOR 244 2-1 X ON

M2-2 SPHOTO SMOKE 2 BEDROOM UNIT 240 2-2 X ON ON

M2-3 SPHOTO SMOKE 2 BEDROOM UNIT 240 2-3 X X ON ON

M2-4 SPHOTO SMOKE 2 BEDROOM UNIT 240 2-4 X ON ON

M2-5 SPHOTO SMOKE 2 BEDROOM UNIT 243 2-5 X X ON ON

M2-6 SPHOTO SMOKE 2 BEDROOM UNIT 243 2-6 X X ON ON

M2-7 SPHOTO SMOKE 2 BEDROOM UNIT 243 2-7 X X X ON ON

M2-8 SPHOTO SMOKE 2 BEDROOM UNIT 245 2-8 X ON ON

M2-9 SPHOTO SMOKE 2 BEDROOM UNIT 245 2-9 X X ON ON

M2-10 SPHOTO SMOKE 2 BEDROOM UNIT 245 2-10 X X ON ON

M2-11 SPHOTO SMOKE 1 BEDROOM UNIT 248 2-11 X X X ON ON

M2-12 SPHOTO SMOKE 1 BEDROOM UNIT 248 2-12 X X ON ON

M2-13 SPHOTO SMOKE 2 BEDROOM UNIT 247 2-13 X X X ON ON

M2-14 SPHOTO SMOKE 2 BEDROOM UNIT 247 2-14 X X X ON ON

M2-15 SPHOTO SMOKE 2 BEDROOM UNIT 247 2-15 X X X X ON ON

M2-16 SPHOTO SMOKE STUDIO UNIT 237 2-16 X ON ON

M2-17 SPHOTO SMOKE 1 BEDROOM UNIT 238 2-17 X X ON ON

M2-18 SPHOTO SMOKE 1 BEDROOM UNIT 238 2-18 X X ON ON

M2-19 SPHOTO SMOKE 1 BEDROOM UNIT 239 2-19 X X X ON ON

M2-20 SPHOTO SMOKE 1 BEDROOM UNIT 239 2-20 X X ON ON

M2-21 SPHOTO SMOKE STUDIO UNIT 241 2-21 X X X ON ON

M2-22 SPHOTO SMOKE 1 BEDROOM UNIT 242 2-22 X X X ON ON

M2-23 SPHOTO SMOKE 1 BEDROOM UNIT 242 2-23 X X X X ON ON

M2-24 SPHOTO SMOKE 1 BEDROOM UNIT 244 2-24 X X ON ON

M2-25 SPHOTO SMOKE 1 BEDROOM UNIT 244 2-25 X X X ON ON

M2-26 SPHOTO SMOKE 2 BEDROOM UNIT 246 2-26 X X X ON ON

M2-27 SPHOTO SMOKE 2 BEDROOM UNIT 246 2-27 X X X X ON ON

M2-28 SPHOTO SMOKE 2 BEDROOM UNIT 246 2-28 X X X ON ON

M2-29 SPHOTO SMOKE 2 BEDROOM UNIT 233 2-29 X X X X ON ON

M2-30 SPHOTO SMOKE 2 BEDROOM UNIT 233 2-30 X X X X ON ON

M2-31 SPHOTO SMOKE 2 BEDROOM UNIT 233 2-31 X X X X X ON ON

M2-32 SPHOTO SMOKE 1 BEDROOM UNIT 231 2-32 X ON ON

M2-33 SPHOTO SMOKE 1 BEDROOM UNIT 231 2-33 X X ON ON

M2-34 SPHOTO SMOKE 3 BEDROOM UNIT 229 2-34 X X ON ON

M2-35 SPHOTO SMOKE 3 BEDROOM UNIT 229 2-35 X X X ON ON

M2-36 SPHOTO SMOKE 3 BEDROOM UNIT 229 2-36 X X ON ON

M2-37 SPHOTO SMOKE 3 BEDROOM UNIT 229 2-37 X X X ON ON

M2-38 SPHOTO SMOKE 2 BEDROOM UNIT 226 2-38 X X X ON ON

M2-39 SPHOTO SMOKE 2 BEDROOM UNIT 226 2-39 X X X X ON ON

M2-40 SPHOTO SMOKE 2 BEDROOM UNIT 226 2-40 X X ON ON

M2-41 SPHOTO SMOKE 2 BEDROOM UNIT 224 2-41 X X X ON ON

M2-42 SPHOTO SMOKE 2 BEDROOM UNIT 224 2-42 X X X ON ON

M2-43 SPHOTO SMOKE 2 BEDROOM UNIT 224 2-43 X X X X ON ON

M2-44 SPHOTO SMOKE 2 BEDROOM UNIT 221 2-44 X X X ON ON

M2-45 SPHOTO SMOKE 2 BEDROOM UNIT 221 2-45 X X X X ON ON

M2-46 SPHOTO SMOKE 2 BEDROOM UNIT 221 2-46 X X X X ON ON

M2-47 SPHOTO SMOKE 2 BEDROOM UNIT 219 2-47 X X X X X ON ON

M2-48 SPHOTO SMOKE 2 BEDROOM UNIT 219 2-48 X X ON ON

M2-49 SPHOTO SMOKE 2 BEDROOM UNIT 219 2-49 X X X ON ON

M2-50 SPHOTO SMOKE 2 BEDROOM UNIT 217 2-50 X X X ON ON

M2-51 SPHOTO SMOKE 2 BEDROOM UNIT 217 2-51 X X X X ON ON

M2-52 SPHOTO SMOKE 2 BEDROOM UNIT 217 2-52 X X X ON ON

M2-53 SPHOTO SMOKE STUDIO UNIT 215 2-53 X X X X ON ON

M2-54 PHOTO SMOKE ELEV LOBBY 260 2-54 X X X X ON

M2-55 PHOTO SMOKE ELECT 264 2-55 X X X X X ON

M2-56 NAC4PT SIGNAL ELECT 264 2-56 X X X ON

M2-57 SPHOTO SMOKE 2 BEDROOM UNIT 210 2-57 X X X X ON ON

M2-58 SPHOTO SMOKE 2 BEDROOM UNIT 210 2-58 X X X X ON ON

M2-59 SPHOTO SMOKE 2 BEDROOM UNIT 210 2-59 X X X X X ON ON

M2-60 SPHOTO SMOKE 1 BEDROOM UNIT 208 2-60 X X X X ON ON

M2-61 SPHOTO SMOKE 1 BEDROOM UNIT 208 2-61 X X X X X ON ON

M2-62 SPHOTO SMOKE 2 BEDROOM UNIT 206 2-62 X X X X X ON ON

M2-63 SPHOTO SMOKE 2 BEDROOM UNIT 206 2-63 X X X X X X ON ON

M2-64 SPHOTO SMOKE 2 BEDROOM UNIT 206 2-64 X ON ON

M2-65 SPHOTO SMOKE 1 BEDROOM UNIT 204 2-65 X X ON ON

M2-66 SPHOTO SMOKE 1 BEDROOM UNIT 204 2-66 X X ON ON

M2-67 SPHOTO SMOKE STUDIO UNIT 202 2-67 X X X ON ON

M2-68 SPHOTO SMOKE 2 BEDROOM UNIT 200 2-68 X X ON ON

M2-69 SPHOTO SMOKE 2 BEDROOM UNIT 200 2-69 X X X ON ON

M2-70 SPHOTO SMOKE 2 BEDROOM UNIT 200 2-70 X X X ON ON

M2-71 SPHOTO SMOKE 2 BEDROOM UNIT 236 2-71 X X X X ON ON

M2-72 SPHOTO SMOKE 2 BEDROOM UNIT 236 2-72 X X ON ON

M2-73 SPHOTO SMOKE 2 BEDROOM UNIT 236 2-73 X X X ON ON

M2-74 SPHOTO SMOKE STUDIO UNIT 235 2-74 X X X ON ON

M2-75 SPHOTO SMOKE 2 BEDROOM UNIT 234 2-75 X X X X ON ON

M2-76 SPHOTO SMOKE 2 BEDROOM UNIT 234 2-76 X X X ON ON

M2-77 SPHOTO SMOKE 2 BEDROOM UNIT 234 2-77 X X X X ON ON

M2-78 SPHOTO SMOKE 1 BEDROOM UNIT 232 2-78 X X X X ON ON

M2-79 SPHOTO SMOKE 1 BEDROOM UNIT 232 2-79 X X X X X ON ON

M2-80 SPHOTO SMOKE 1 BEDROOM UNIT 230 2-80 X X ON ON

M2-81 SPHOTO SMOKE 1 BEDROOM UNIT 230 2-81 X X X ON ON

M2-82 SPHOTO SMOKE 1 BEDROOM UNIT 228 2-82 X X X ON ON

M2-83 SPHOTO SMOKE 1 BEDROOM UNIT 228 2-83 X X X X ON ON

M2-84 SPHOTO SMOKE STUDIO UNIT 227 2-84 X X X ON ON

M2-85 SPHOTO SMOKE 2 BEDROOM UNIT 225 2-85 X X X X ON ON

M2-86 SPHOTO SMOKE 2 BEDROOM UNIT 225 2-86 X X X X ON ON

M2-87 SPHOTO SMOKE 2 BEDROOM UNIT 225 2-87 X X X X X ON ON

M2-88 SPHOTO SMOKE 2 BEDROOM UNIT 223 2-88 X X X ON ON

M2-89 SPHOTO SMOKE 2 BEDROOM UNIT 223 2-89 X X X X ON ON

M2-90 SPHOTO SMOKE 2 BEDROOM UNIT 223 2-90 X X X X ON ON

M2-91 SPHOTO SMOKE 1 BEDROOM UNIT 222 2-91 X X X X X ON ON

M2-92 SPHOTO SMOKE 1 BEDROOM UNIT 222 2-92 X X X X ON ON

M2-93 SPHOTO SMOKE 1 BEDROOM UNIT 220 2-93 X X X X X ON ON

M2-94 SPHOTO SMOKE 1 BEDROOM UNIT 220 2-94 X X X X X ON ON

M2-95 SPHOTO SMOKE 1 BEDROOM UNIT 218 2-95 X X X X X X ON ON

M2-96 SPHOTO SMOKE 1 BEDROOM UNIT 218 2-96 X X ON ON

M2-97 SPHOTO SMOKE 1 BEDROOM UNIT 216 2-97 X X X ON ON

M2-98 SPHOTO SMOKE 1 BEDROOM UNIT 216 2-98 X X X ON ON

M2-99 SPHOTO SMOKE 2 BEDROOM UNIT 214 2-99 X X X X ON ON

M2-100 SPHOTO SMOKE 2 BEDROOM UNIT 214 2-100 X X X ON ON

M2-101 SPHOTO SMOKE 2 BEDROOM UNIT 214 2-101 X X X X ON ON

M2-102 SPHOTO SMOKE 3 BEDROOM UNIT 213 2-102 X X X X ON ON

M2-103 SPHOTO SMOKE 3 BEDROOM UNIT 213 2-103 X X X X X ON ON

M2-104 SPHOTO SMOKE 3 BEDROOM UNIT 213 2-104 X X X ON ON

M2-105 SPHOTO SMOKE 3 BEDROOM UNIT 213 2-105 X X X X ON ON

M2-106 SPHOTO SMOKE 1 BEDROOM UNIT 212 2-106 X X X X ON ON

M2-107 SPHOTO SMOKE 1 BEDROOM UNIT 212 2-107 X X X X X ON ON

M2-108 SPHOTO SMOKE 1 BEDROOM UNIT 211 2-108 X X X X ON ON

M2-109 SPHOTO SMOKE 1 BEDROOM UNIT 211 2-109 X X X X X ON ON

M2-110 SPHOTO SMOKE 2 BEDROOM UNIT 209 2-110 X X X X X ON ON

M2-111 SPHOTO SMOKE 2 BEDROOM UNIT 209 2-111 X X X X X X ON ON

M2-112 SPHOTO SMOKE 2 BEDROOM UNIT 209 2-112 X X X ON ON

M2-113 SPHOTO SMOKE 1 BEDROOM UNIT 207 2-113 X X X X ON ON

M2-114 SPHOTO SMOKE 1 BEDROOM UNIT 207 2-114 X X X X ON ON

M2-115 SPHOTO SMOKE 1 BEDROOM UNIT 205 2-115 X X X X X ON ON

M2-116 SPHOTO SMOKE 1 BEDROOM UNIT 205 2-116 X X X X ON ON

M2-117 SPHOTO SMOKE 1 BEDROOM UNIT 203 2-117 X X X X X ON ON

M2-118 SPHOTO SMOKE 1 BEDROOM UNIT 203 2-118 X X X X X ON ON

M2-119 SPHOTO SMOKE 3 BEDROOM UNIT 201 2-119 X X X X X X ON ON

M2-120 SPHOTO SMOKE 3 BEDROOM UNIT 201 2-120 X X X X ON ON

M2-121 SPHOTO SMOKE 3 BEDROOM UNIT 201 2-121 X X X X X ON ON

M2-122 SPHOTO SMOKE 3 BEDROOM UNIT 201 2-122 X X X X X ON ON

M2-123 RIAM RELAY CORRIDOR 244 2-123 X X X X X X ON

M2-124 PHOTO SMOKE CORRIDOR 244 2-124 X X X X X ON

M2-125 X X X X X X ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

IDNET CHANNEL M2 ADDRESSES IN USE: 254 (101.6%) | SPARE ADDRESSES: -4 (-1.6%) SWITCH SETTINGS

Address Location Description 1 2 3 4 5 6 7 8 9

M2-126 SPHOTO SMOKE 2 BEDROOM UNIT 340 2-126 X X X X X X ON ON

M2-127 SPHOTO SMOKE 2 BEDROOM UNIT 340 2-127 X X X X X X X ON ON

M2-128 SPHOTO SMOKE 2 BEDROOM UNIT 340 2-128 X ON ON

M2-129 SPHOTO SMOKE 2 BEDROOM UNIT 343 2-129 X X ON ON

M2-130 SPHOTO SMOKE 2 BEDROOM UNIT 343 2-130 X X ON ON

M2-131 SPHOTO SMOKE 2 BEDROOM UNIT 343 2-131 X X X ON ON

M2-132 SPHOTO SMOKE 2 BEDROOM UNIT 345 2-132 X X ON ON

M2-133 SPHOTO SMOKE 2 BEDROOM UNIT 345 2-133 X X X ON ON

M2-134 SPHOTO SMOKE 2 BEDROOM UNIT 345 2-134 X X X ON ON

M2-135 SPHOTO SMOKE 1 BEDROOM UNIT 348 2-135 X X X X ON ON

M2-136 SPHOTO SMOKE 1 BEDROOM UNIT 348 2-136 X X ON ON

M2-137 SPHOTO SMOKE 2 BEDROOM UNIT 347 2-137 X X X ON ON

M2-138 SPHOTO SMOKE 2 BEDROOM UNIT 347 2-138 X X X ON ON

M2-139 SPHOTO SMOKE 2 BEDROOM UNIT 347 2-139 X X X X ON ON

M2-140 SPHOTO SMOKE STUDIO UNIT 337 2-140 X X X ON ON

M2-141 SPHOTO SMOKE 1 BEDROOM UNIT 338 2-141 X X X X ON ON

M2-142 SPHOTO SMOKE 1 BEDROOM UNIT 338 2-142 X X X X ON ON

M2-143 SPHOTO SMOKE 1 BEDROOM UNIT 339 2-143 X X X X X ON ON

M2-144 SPHOTO SMOKE 1 BEDROOM UNIT 339 2-144 X X ON ON

M2-145 SPHOTO SMOKE STUDIO UNIT 341 2-145 X X X ON ON

M2-146 SPHOTO SMOKE 1 BEDROOM UNIT 342 2-146 X X X ON ON

M2-147 SPHOTO SMOKE 1 BEDROOM UNIT 342 2-147 X X X X ON ON

M2-148 SPHOTO SMOKE 1 BEDROOM UNIT 344 2-148 X X X ON ON

M2-149 SPHOTO SMOKE 1 BEDROOM UNIT 344 2-149 X X X X ON ON

M2-150 SPHOTO SMOKE 2 BEDROOM UNIT 346 2-150 X X X X ON ON

M2-151 SPHOTO SMOKE 2 BEDROOM UNIT 346 2-151 X X X X X ON ON

M2-152 SPHOTO SMOKE 2 BEDROOM UNIT 346 2-152 X X X ON ON

M2-153 SPHOTO SMOKE 2 BEDROOM UNIT 333 2-153 X X X X ON ON

M2-154 SPHOTO SMOKE 2 BEDROOM UNIT 333 2-154 X X X X ON ON

M2-155 SPHOTO SMOKE 2 BEDROOM UNIT 333 2-155 X X X X X ON ON

M2-156 SPHOTO SMOKE 1 BEDROOM UNIT 331 2-156 X X X X ON ON

M2-157 SPHOTO SMOKE 1 BEDROOM UNIT 331 2-157 X X X X X ON ON

M2-158 SPHOTO SMOKE 3 BEDROOM UNIT 329 2-158 X X X X X ON ON

M2-159 SPHOTO SMOKE 3 BEDROOM UNIT 329 2-159 X X X X X X ON ON

M2-160 SPHOTO SMOKE 3 BEDROOM UNIT 329 2-160 X X ON ON

M2-161 SPHOTO SMOKE 3 BEDROOM UNIT 329 2-161 X X X ON ON

M2-162 SPHOTO SMOKE 2 BEDROOM UNIT 326 2-162 X X X ON ON

M2-163 SPHOTO SMOKE 2 BEDROOM UNIT 326 2-163 X X X X ON ON

M2-164 SPHOTO SMOKE 2 BEDROOM UNIT 326 2-164 X X X ON ON

M2-165 SPHOTO SMOKE 2 BEDROOM UNIT 324 2-165 X X X X ON ON

M2-166 SPHOTO SMOKE 2 BEDROOM UNIT 324 2-166 X X X X ON ON

M2-167 SPHOTO SMOKE 2 BEDROOM UNIT 324 2-167 X X X X X ON ON

M2-168 SPHOTO SMOKE 2 BEDROOM UNIT 321 2-168 X X X ON ON

M2-169 SPHOTO SMOKE 2 BEDROOM UNIT 321 2-169 X X X X ON ON

M2-170 SPHOTO SMOKE 2 BEDROOM UNIT 321 2-170 X X X X ON ON

M2-171 SPHOTO SMOKE 2 BEDROOM UNIT 319 2-171 X X X X X ON ON

M2-172 SPHOTO SMOKE 2 BEDROOM UNIT 319 2-172 X X X X ON ON

M2-173 SPHOTO SMOKE 2 BEDROOM UNIT 319 2-173 X X X X X ON ON

M2-174 SPHOTO SMOKE 2 BEDROOM UNIT 317 2-174 X X X X X ON ON

M2-175 SPHOTO SMOKE 2 BEDROOM UNIT 317 2-175 X X X X X X ON ON

M2-176 SPHOTO SMOKE 2 BEDROOM UNIT 317 2-176 X X X ON ON

M2-177 SPHOTO SMOKE STUDIO UNIT 315 2-177 X X X X ON ON

M2-178 PHOTO SMOKE ELEV LOBBY 360 2-178 X X X X ON

M2-179 PHOTO SMOKE ELECT 364 2-179 X X X X X ON

M2-180 NAC4PT SIGNAL ELECT 364 2-180 X X X X ON

M2-181 SPHOTO SMOKE 2 BEDROOM UNIT 310 2-181 X X X X X ON ON

M2-182 SPHOTO SMOKE 2 BEDROOM UNIT 310 2-182 X X X X X ON ON

M2-183 SPHOTO SMOKE 2 BEDROOM UNIT 310 2-183 X X X X X X ON ON

M2-184 SPHOTO SMOKE 1 BEDROOM UNIT 308 2-184 X X X X ON ON

M2-185 SPHOTO SMOKE 1 BEDROOM UNIT 308 2-185 X X X X X ON ON

M2-186 SPHOTO SMOKE 2 BEDROOM UNIT 306 2-186 X X X X X ON ON

M2-187 SPHOTO SMOKE 2 BEDROOM UNIT 306 2-187 X X X X X X ON ON

M2-188 SPHOTO SMOKE 2 BEDROOM UNIT 306 2-188 X X X X X ON ON

M2-189 SPHOTO SMOKE 1 BEDROOM UNIT 304 2-189 X X X X X X ON ON

M2-190 SPHOTO SMOKE 1 BEDROOM UNIT 304 2-190 X X X X X X ON ON

M2-191 SPHOTO SMOKE STUDIO UNIT 302 2-191 X X X X X X X ON ON

M2-192 SPHOTO SMOKE 2 BEDROOM UNIT 300 2-192 X X ON ON

M2-193 SPHOTO SMOKE 2 BEDROOM UNIT 300 2-193 X X X ON ON

M2-194 SPHOTO SMOKE 2 BEDROOM UNIT 300 2-194 X X X ON ON

M2-195 SPHOTO SMOKE 2 BEDROOM UNIT 336 2-195 X X X X ON ON

M2-196 SPHOTO SMOKE 2 BEDROOM UNIT 336 2-196 X X X ON ON

M2-197 SPHOTO SMOKE 2 BEDROOM UNIT 336 2-197 X X X X ON ON

M2-198 SPHOTO SMOKE STUDIO UNIT 335 2-198 X X X X ON ON

M2-199 SPHOTO SMOKE 2 BEDROOM UNIT 334 2-199 X X X X X ON ON

M2-200 SPHOTO SMOKE 2 BEDROOM UNIT 334 2-200 X X X ON ON

M2-201 SPHOTO SMOKE 2 BEDROOM UNIT 334 2-201 X X X X ON ON

M2-202 SPHOTO SMOKE 1 BEDROOM UNIT 332 2-202 X X X X ON ON

M2-203 SPHOTO SMOKE 1 BEDROOM UNIT 332 2-203 X X X X X ON ON

M2-204 SPHOTO SMOKE 1 BEDROOM UNIT 330 2-204 X X X X ON ON

M2-205 SPHOTO SMOKE 1 BEDROOM UNIT 330 2-205 X X X X X ON ON

M2-206 SPHOTO SMOKE 1 BEDROOM UNIT 328 2-206 X X X X X ON ON

M2-207 SPHOTO SMOKE 1 BEDROOM UNIT 328 2-207 X X X X X X ON ON

M2-208 SPHOTO SMOKE STUDIO UNIT 327 2-208 X X X ON ON

M2-209 SPHOTO SMOKE 2 BEDROOM UNIT 325 2-209 X X X X ON ON

M2-210 SPHOTO SMOKE 2 BEDROOM UNIT 325 2-210 X X X X ON ON

M2-211 SPHOTO SMOKE 2 BEDROOM UNIT 325 2-211 X X X X X ON ON

M2-212 SPHOTO SMOKE 2 BEDROOM UNIT 323 2-212 X X X X ON ON

M2-213 SPHOTO SMOKE 2 BEDROOM UNIT 323 2-213 X X X X X ON ON

M2-214 SPHOTO SMOKE 2 BEDROOM UNIT 323 2-214 X X X X X ON ON

M2-215 SPHOTO SMOKE 1 BEDROOM UNIT 322 2-215 X X X X X X ON ON

M2-216 SPHOTO SMOKE 1 BEDROOM UNIT 322 2-216 X X X X ON ON

M2-217 SPHOTO SMOKE 1 BEDROOM UNIT 320 2-217 X X X X X ON ON

M2-218 SPHOTO SMOKE 1 BEDROOM UNIT 320 2-218 X X X X X ON ON

M2-219 SPHOTO SMOKE 1 BEDROOM UNIT 318 2-219 X X X X X X ON ON

M2-220 SPHOTO SMOKE 1 BEDROOM UNIT 318 2-220 X X X X X ON ON

M2-221 SPHOTO SMOKE 1 BEDROOM UNIT 316 2-221 X X X X X X ON ON

M2-222 SPHOTO SMOKE 1 BEDROOM UNIT 316 2-222 X X X X X X ON ON

M2-223 SPHOTO SMOKE 2 BEDROOM UNIT 314 2-223 X X X X X X X ON ON

M2-224 SPHOTO SMOKE 2 BEDROOM UNIT 314 2-224 X X X ON ON

M2-225 SPHOTO SMOKE 2 BEDROOM UNIT 314 2-225 X X X X ON ON

M2-226 SPHOTO SMOKE 3 BEDROOM UNIT 313 2-226 X X X X ON ON

M2-227 SPHOTO SMOKE 3 BEDROOM UNIT 313 2-227 X X X X X ON ON

M2-228 SPHOTO SMOKE 3 BEDROOM UNIT 313 2-228 X X X X ON ON

M2-229 SPHOTO SMOKE 3 BEDROOM UNIT 313 2-229 X X X X X ON ON

M2-230 RIAM RELAY CORRIDOR 344 2-230 X X X X X ON

M2-231 SPHOTO SMOKE 1 BEDROOM UNIT 312 2-231 X X X X X X ON ON

M2-232 SPHOTO SMOKE 1 BEDROOM UNIT 312 2-232 X X X X ON ON

M2-233 SPHOTO SMOKE 1 BEDROOM UNIT 311 2-233 X X X X X ON ON

M2-234 SPHOTO SMOKE 1 BEDROOM UNIT 311 2-234 X X X X X ON ON

M2-235 SPHOTO SMOKE 2 BEDROOM UNIT 309 2-235 X X X X X X ON ON

M2-236 SPHOTO SMOKE 2 BEDROOM UNIT 309 2-236 X X X X X ON ON

M2-237 SPHOTO SMOKE 2 BEDROOM UNIT 309 2-237 X X X X X X ON ON

M2-238 SPHOTO SMOKE 1 BEDROOM UNIT 307 2-238 X X X X X X ON ON

M2-239 SPHOTO SMOKE 1 BEDROOM UNIT 307 2-239 X X X X X X X ON ON

M2-240 SPHOTO SMOKE 1 BEDROOM UNIT 305 2-240 X X X X ON ON

M2-241 SPHOTO SMOKE 1 BEDROOM UNIT 305 2-241 X X X X X ON ON

M2-242 SPHOTO SMOKE 1 BEDROOM UNIT 303 2-242 X X X X X ON ON

M2-243 SPHOTO SMOKE 1 BEDROOM UNIT 303 2-243 X X X X X X ON ON

M2-244 SPHOTO SMOKE 3 BEDROOM UNIT 301 2-244 X X X X X ON ON

M2-245 SPHOTO SMOKE 3 BEDROOM UNIT 301 2-245 X X X X X X ON ON

M2-246 SPHOTO SMOKE 3 BEDROOM UNIT 301 2-246 X X X X X X ON ON

M2-247 SPHOTO SMOKE 3 BEDROOM UNIT 301 2-247 X X X X X X X ON ON

M2-248 PHOTO SMOKE CORRIDOR 344 2-248 X X X X X ON

M2-249 PHOTO SMOKE CORRIDOR 344 2-249 X X X X X X ON

THRU ON

M2-250 X X X X X X ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-6

01.d

wg

9/13

/201

6 9:

52:3

1 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-601

CALCULATIONS AND

SCHEDULES

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-601.dwg, FA-601 CALCULATIONS AND SCHEDULES, 9/13/2016 9:52:30 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 13: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

IDNET CHANNEL M3 ADDRESSES IN USE: 148 (59.2%) | SPARE ADDRESSES: 102 (40.8%) SWITCH SETTINGS

Address Device Type Point Type Location Description 1 2 3 4 5 6 7 8 9

M3-1 PHOTO SMOKE ELECT 259 3-1 X ON

M3-2 NAC4PT SIGNAL ELECT 259 3-2 X ON

M3-3 RIAM RELAY CORRIDOR 244 3-3 X X ON

M3-4 PHOTO SMOKE FLOOR LOBBY 256 3-4 X ON

M3-5 X X ON

M3-6 X X ON

M3-7 X X X ON

M3-8 X ON

M3-9 X X ON

M3-10 X X ON

M3-11 PHOTO SMOKE ELECT 359 3-11 X X X ON

M3-12 NAC4PT SIGNAL ELECT 359 3-12 X X ON

M3-13 RIAM RELAY CORRIDOR 344 3-13 X X X ON

M3-14 PHOTO SMOKE FLOOR LOBBY 356 3-14 X X X ON

M3-15 X X X X ON

M3-16 X ON

M3-17 X X ON

M3-18 X X ON

M3-19 X X X ON

M3-20 X X ON

M3-21 PHOTO SMOKE ELECT 459 3-21 X X X ON

M3-22 NAC4PT SIGNAL ELECT 459 3-22 X X X ON

M3-23 RIAM RELAY CORRIDOR 444 3-23 X X X X ON

M3-24 PHOTO SMOKE FLOOR LOBBY 456 3-24 X X ON

M3-25 SPHOTO SMOKE 2 BEDROOM UNIT 440 3-25 X X X ON ON

M3-26 SPHOTO SMOKE 2 BEDROOM UNIT 440 3-26 X X X ON ON

M3-27 SPHOTO SMOKE 2 BEDROOM UNIT 440 3-27 X X X X ON ON

M3-28 SPHOTO SMOKE 2 BEDROOM UNIT 443 3-28 X X X ON ON

M3-29 SPHOTO SMOKE 2 BEDROOM UNIT 443 3-29 X X X X ON ON

M3-30 SPHOTO SMOKE 2 BEDROOM UNIT 443 3-30 X X X X ON ON

M3-31 SPHOTO SMOKE 2 BEDROOM UNIT 445 3-31 X X X X X ON ON

M3-32 SPHOTO SMOKE 2 BEDROOM UNIT 445 3-32 X ON ON

M3-33 SPHOTO SMOKE 2 BEDROOM UNIT 445 3-33 X X ON ON

M3-34 SPHOTO SMOKE 1 BEDROOM UNIT 448 3-34 X X ON ON

M3-35 SPHOTO SMOKE 1 BEDROOM UNIT 448 3-35 X X X ON ON

M3-36 SPHOTO SMOKE 2 BEDROOM UNIT 447 3-36 X X ON ON

M3-37 SPHOTO SMOKE 2 BEDROOM UNIT 447 3-37 X X X ON ON

M3-38 SPHOTO SMOKE 2 BEDROOM UNIT 447 3-38 X X X ON ON

M3-39 SPHOTO SMOKE STUDIO UNIT 437 3-39 X X X X ON ON

M3-40 SPHOTO SMOKE 1 BEDROOM UNIT 438 3-40 X X ON ON

M3-41 SPHOTO SMOKE 1 BEDROOM UNIT 438 3-41 X X X ON ON

M3-42 SPHOTO SMOKE 1 BEDROOM UNIT 439 3-42 X X X ON ON

M3-43 SPHOTO SMOKE 1 BEDROOM UNIT 439 3-43 X X X X ON ON

M3-44 SPHOTO SMOKE STUDIO UNIT 441 3-44 X X X ON ON

M3-45 SPHOTO SMOKE 1 BEDROOM UNIT 442 3-45 X X X X ON ON

M3-46 SPHOTO SMOKE 1 BEDROOM UNIT 442 3-46 X X X X ON ON

M3-47 SPHOTO SMOKE 1 BEDROOM UNIT 444 3-47 X X X X X ON ON

M3-48 SPHOTO SMOKE 1 BEDROOM UNIT 444 3-48 X X ON ON

M3-49 SPHOTO SMOKE 2 BEDROOM UNIT 446 3-49 X X X ON ON

M3-50 SPHOTO SMOKE 2 BEDROOM UNIT 446 3-50 X X X ON ON

M3-51 SPHOTO SMOKE 2 BEDROOM UNIT 446 3-51 X X X X ON ON

M3-52 SPHOTO SMOKE 2 BEDROOM UNIT 433 3-52 X X X ON ON

M3-53 SPHOTO SMOKE 2 BEDROOM UNIT 433 3-53 X X X X ON ON

M3-54 SPHOTO SMOKE 2 BEDROOM UNIT 433 3-54 X X X X ON ON

M3-55 SPHOTO SMOKE 1 BEDROOM UNIT 431 3-55 X X X X X ON ON

M3-56 SPHOTO SMOKE 1 BEDROOM UNIT 431 3-56 X X X ON ON

M3-57 SPHOTO SMOKE 3 BEDROOM UNIT 429 3-57 X X X X ON ON

M3-58 SPHOTO SMOKE 3 BEDROOM UNIT 429 3-58 X X X X ON ON

M3-59 SPHOTO SMOKE 3 BEDROOM UNIT 429 3-59 X X X X X ON ON

M3-60 SPHOTO SMOKE 3 BEDROOM UNIT 429 3-60 X X X X ON ON

M3-61 SPHOTO SMOKE 2 BEDROOM UNIT 426 3-61 X X X X X ON ON

M3-62 SPHOTO SMOKE 2 BEDROOM UNIT 426 3-62 X X X X X ON ON

M3-63 SPHOTO SMOKE 2 BEDROOM UNIT 426 3-63 X X X X X X ON ON

M3-64 SPHOTO SMOKE 2 BEDROOM UNIT 424 3-64 X ON ON

M3-65 SPHOTO SMOKE 2 BEDROOM UNIT 424 3-65 X X ON ON

M3-66 SPHOTO SMOKE 2 BEDROOM UNIT 424 3-66 X X ON ON

M3-67 SPHOTO SMOKE 2 BEDROOM UNIT 421 3-67 X X X ON ON

M3-68 SPHOTO SMOKE 2 BEDROOM UNIT 421 3-68 X X ON ON

M3-69 SPHOTO SMOKE 2 BEDROOM UNIT 421 3-69 X X X ON ON

M3-70 SPHOTO SMOKE 2 BEDROOM UNIT 419 3-70 X X X ON ON

M3-71 SPHOTO SMOKE 2 BEDROOM UNIT 419 3-71 X X X X ON ON

M3-72 SPHOTO SMOKE 2 BEDROOM UNIT 419 3-72 X X ON ON

M3-73 SPHOTO SMOKE 2 BEDROOM UNIT 417 3-73 X X X ON ON

M3-74 SPHOTO SMOKE 2 BEDROOM UNIT 417 3-74 X X X ON ON

M3-75 SPHOTO SMOKE 2 BEDROOM UNIT 417 3-75 X X X X ON ON

M3-76 SPHOTO SMOKE STUDIO UNIT 415 3-76 X X X ON ON

M3-77 PHOTO SMOKE ELEV LOBBY 460 3-77 X X X X ON

M3-78 PHOTO SMOKE ELECT 464 3-78 X X X X ON

M3-79 NAC4PT SIGNAL ELECT 464 3-79 X X X X X ON

M3-80 SPHOTO SMOKE 2 BEDROOM UNIT 410 3-80 X X ON ON

M3-81 SPHOTO SMOKE 2 BEDROOM UNIT 410 3-81 X X X ON ON

M3-82 SPHOTO SMOKE 2 BEDROOM UNIT 410 3-82 X X X ON ON

M3-83 SPHOTO SMOKE 1 BEDROOM UNIT 408 3-83 X X X X ON ON

M3-84 SPHOTO SMOKE 1 BEDROOM UNIT 408 3-84 X X X ON ON

M3-85 SPHOTO SMOKE 2 BEDROOM UNIT 406 3-85 X X X X ON ON

M3-86 SPHOTO SMOKE 2 BEDROOM UNIT 406 3-86 X X X X ON ON

M3-87 SPHOTO SMOKE 2 BEDROOM UNIT 406 3-87 X X X X X ON ON

M3-88 SPHOTO SMOKE 1 BEDROOM UNIT 404 3-88 X X X ON ON

M3-89 SPHOTO SMOKE 1 BEDROOM UNIT 404 3-89 X X X X ON ON

M3-90 SPHOTO SMOKE UNIT 402 3-90 X X X X ON ON

M3-91 SPHOTO SMOKE 2 BEDROOM UNIT 400 3-91 X X X X X ON ON

M3-92 SPHOTO SMOKE 2 BEDROOM UNIT 400 3-92 X X X X ON ON

M3-93 SPHOTO SMOKE 2 BEDROOM UNIT 400 3-93 X X X X X ON ON

M3-94 SPHOTO SMOKE 2 BEDROOM UNIT 436 3-94 X X X X X ON ON

M3-95 SPHOTO SMOKE 2 BEDROOM UNIT 436 3-95 X X X X X X ON ON

M3-96 SPHOTO SMOKE 2 BEDROOM UNIT 436 3-96 X X ON ON

M3-97 SPHOTO SMOKE STUDIO UNIT 435 3-97 X X X ON ON

M3-98 SPHOTO SMOKE 2 BEDROOM UNIT 434 3-98 X X X ON ON

M3-99 SPHOTO SMOKE 2 BEDROOM UNIT 434 3-99 X X X X ON ON

M3-100 SPHOTO SMOKE 2 BEDROOM UNIT 434 3-100 X X X ON ON

M3-101 SPHOTO SMOKE 1 BEDROOM UNIT 432 3-101 X X X X ON ON

M3-102 SPHOTO SMOKE 1 BEDROOM UNIT 432 3-102 X X X X ON ON

M3-103 SPHOTO SMOKE 1 BEDROOM UNIT 430 3-103 X X X X X ON ON

M3-104 SPHOTO SMOKE 1 BEDROOM UNIT 430 3-104 X X X ON ON

M3-105 SPHOTO SMOKE 1 BEDROOM UNIT 428 3-105 X X X X ON ON

M3-106 SPHOTO SMOKE 1 BEDROOM UNIT 428 3-106 X X X X ON ON

M3-107 SPHOTO SMOKE STUDIO UNIT 427 3-107 X X X X X ON ON

M3-108 SPHOTO SMOKE 2 BEDROOM UNIT 425 3-108 X X X X ON ON

M3-109 SPHOTO SMOKE 2 BEDROOM UNIT 425 3-109 X X X X X ON ON

M3-110 SPHOTO SMOKE 2 BEDROOM UNIT 425 3-110 X X X X X ON ON

M3-111 SPHOTO SMOKE 2 BEDROOM UNIT 423 3-111 X X X X X X ON ON

M3-112 SPHOTO SMOKE 2 BEDROOM UNIT 423 3-112 X X X ON ON

M3-113 SPHOTO SMOKE 2 BEDROOM UNIT 423 3-113 X X X X ON ON

M3-114 SPHOTO SMOKE 1 BEDROOM UNIT 422 3-114 X X X X ON ON

M3-115 SPHOTO SMOKE 1 BEDROOM UNIT 422 3-115 X X X X X ON ON

M3-116 SPHOTO SMOKE 1 BEDROOM UNIT 420 3-116 X X X X ON ON

M3-117 SPHOTO SMOKE 1 BEDROOM UNIT 420 3-117 X X X X X ON ON

M3-118 SPHOTO SMOKE 1 BEDROOM UNIT 418 3-118 X X X X X ON ON

M3-119 SPHOTO SMOKE 1 BEDROOM UNIT 418 3-119 X X X X X X ON ON

M3-120 SPHOTO SMOKE 1 BEDROOM UNIT 416 3-120 X X X X ON ON

M3-121 SPHOTO SMOKE 1 BEDROOM UNIT 416 3-121 X X X X X ON ON

M3-122 SPHOTO SMOKE 2 BEDROOM UNIT 414 3-122 X X X X X ON ON

M3-123 SPHOTO SMOKE 2 BEDROOM UNIT 414 3-123 X X X X X X ON ON

M3-124 SPHOTO SMOKE 2 BEDROOM UNIT 414 3-124 X X X X X ON ON

M3-125 SPHOTO SMOKE 3 BEDROOM UNIT 413 3-125 X X X X X X ON ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

IDNET CHANNEL M3 ADDRESSES IN USE: 148 (59.2%) | SPARE ADDRESSES: 102 (40.8%) SWITCH SETTINGS

Address Location Description 1 2 3 4 5 6 7 8 9

M3-126 SPHOTO SMOKE 3 BEDROOM UNIT 413 3-126 X X X X X X ON ON

M3-127 SPHOTO SMOKE 3 BEDROOM UNIT 413 3-127 X X X X X X X ON ON

M3-128 SPHOTO SMOKE 3 BEDROOM UNIT 413 3-128 X ON ON

M3-129 SPHOTO SMOKE 1 BEDROOM UNIT 412 3-129 X X ON ON

M3-130 SPHOTO SMOKE 1 BEDROOM UNIT 412 3-130 X X ON ON

M3-131 RIAM RELAY CORRIDOR 444 3-131 X X X ON

M3-132 SPHOTO SMOKE 1 BEDROOM UNIT 411 3-132 X X ON ON

M3-133 SPHOTO SMOKE 1 BEDROOM UNIT 411 3-133 X X X ON ON

M3-134 SPHOTO SMOKE 2 BEDROOM UNIT 409 3-134 X X X ON ON

M3-135 SPHOTO SMOKE 2 BEDROOM UNIT 409 3-135 X X X X ON ON

M3-136 SPHOTO SMOKE 2 BEDROOM UNIT 409 3-136 X X ON ON

M3-137 SPHOTO SMOKE 1 BEDROOM UNIT 407 3-137 X X X ON ON

M3-138 SPHOTO SMOKE 1 BEDROOM UNIT 407 3-138 X X X ON ON

M3-139 SPHOTO SMOKE 1 BEDROOM UNIT 405 3-139 X X X X ON ON

M3-140 SPHOTO SMOKE 1 BEDROOM UNIT 405 3-140 X X X ON ON

M3-141 SPHOTO SMOKE 1 BEDROOM UNIT 403 3-141 X X X X ON ON

M3-142 SPHOTO SMOKE 1 BEDROOM UNIT 403 3-142 X X X X ON ON

M3-143 SPHOTO SMOKE 3 BEDROOM UNIT 401 3-143 X X X X X ON ON

M3-144 SPHOTO SMOKE 3 BEDROOM UNIT 401 3-144 X X ON ON

M3-145 SPHOTO SMOKE 3 BEDROOM UNIT 401 3-145 X X X ON ON

M3-146 SPHOTO SMOKE 3 BEDROOM UNIT 401 3-146 X X X ON ON

M3-147 PHOTO SMOKE CORRIDOR 444 3-147 X X X X ON

M3-148 PHOTO SMOKE CORRIDOR 444 3-148 X X X ON

M3-149 X X X X ON

M3-150 X X X X ON

M3-151 X X X X X ON

M3-152 X X X ON

M3-153 X X X X ON

M3-154 X X X X ON

M3-155 X X X X X ON

M3-156 X X X X ON

M3-157 X X X X X ON

M3-158 X X X X X ON

M3-159 X X X X X X ON

M3-160 X X ON

M3-161 X X X ON

M3-162 X X X ON

M3-163 X X X X ON

M3-164 X X X ON

M3-165 X X X X ON

M3-166 X X X X ON

M3-167 X X X X X ON

M3-168 X X X ON

M3-169 X X X X ON

M3-170 X X X X ON

M3-171 X X X X X ON

M3-172 X X X X ON

M3-173 X X X X X ON

M3-174 X X X X X ON

M3-175 X X X X X X ON

M3-176 X X X ON

M3-177 X X X X ON

M3-178 X X X X ON

M3-179 X X X X X ON

M3-180 X X X X ON

M3-181 X X X X X ON

M3-182 X X X X X ON

M3-183 X X X X X X ON

M3-184 X X X X ON

M3-185 X X X X X ON

M3-186 X X X X X ON

M3-187 X X X X X X ON

M3-188 X X X X X ON

M3-189 X X X X X X ON

M3-190 X X X X X X ON

M3-191 X X X X X X X ON

M3-192 X X ON

M3-193 X X X ON

M3-194 X X X ON

M3-195 X X X X ON

M3-196 X X X ON

M3-197 X X X X ON

M3-198 X X X X ON

M3-199 X X X X X ON

M3-200 X X X ON

M3-201 X X X X ON

M3-202 X X X X ON

M3-203 X X X X X ON

M3-204 X X X X ON

M3-205 X X X X X ON

M3-206 X X X X X ON

M3-207 X X X X X X ON

M3-208 X X X ON

M3-209 X X X X ON

M3-210 X X X X ON

M3-211 X X X X X ON

M3-212 X X X X ON

M3-213 X X X X X ON

M3-214 X X X X X ON

M3-215 X X X X X X ON

M3-216 X X X X ON

M3-217 X X X X X ON

M3-218 X X X X X ON

M3-219 X X X X X X ON

M3-220 X X X X X ON

M3-221 X X X X X X ON

M3-222 X X X X X X ON

M3-223 X X X X X X X ON

M3-224 X X X ON

M3-225 X X X X ON

M3-226 X X X X ON

M3-227 X X X X X ON

M3-228 X X X X ON

M3-229 X X X X X ON

M3-230 X X X X X ON

M3-231 X X X X X X ON

M3-232 X X X X ON

M3-233 X X X X X ON

M3-234 X X X X X ON

M3-235 X X X X X X ON

M3-236 X X X X X ON

M3-237 X X X X X X ON

M3-238 X X X X X X ON

M3-239 X X X X X X X ON

M3-240 X X X X ON

M3-241 X X X X X ON

M3-242 X X X X X ON

M3-243 X X X X X X ON

M3-244 X X X X X ON

M3-245 X X X X X X ON

M3-246 X X X X X X ON

M3-247 X X X X X X X ON

M3-248 X X X X X ON

M3-249 X X X X X X ON

THRU ON

M3-250 X X X X X X ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % Drop

H3 1ST FLOOR NORTH CENTER SIG3 1.290A 11.30%H4 2ND FLOOR NORTH CENTER SIG4 1.161A 9.54%H5 SPARE SIG5 0.000A 0.00%

2.451A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.30%Circuit Capacity 3.A

Normal OperationDistance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceH3-1 4098-9772 520 Hz 167 0.129 1.323 18.18H3-2 4098-9772 520 Hz 24 0.129 1.494 18.01H3-3 4098-9772 520 Hz 25 0.129 1.652 17.85H3-4 4098-9772 520 Hz 25 0.129 1.791 17.71H3-5 4098-9772 520 Hz 26 0.129 1.914 17.59H3-6 4098-9772 520 Hz 24 0.129 2.009 17.49H3-7 4098-9772 520 Hz 26 0.129 2.092 17.41H3-8 4098-9772 520 Hz 23 0.129 2.146 17.35H3-9 4098-9772 520 Hz 24 0.129 2.185 17.32H3-10 4098-9772 520 Hz 23 0.129 2.203 17.30

Totals: 387 Ft. 1.290A

H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 9.54%Ckt Capacity 3.A

Normal OperationDistance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceH4-1 4098-9772 520 Hz 158 0.129 1.126 18.37H4-2 4098-9772 520 Hz 29 0.129 1.310 18.19H4-3 4098-9772 520 Hz 24 0.129 1.443 18.06H4-4 4098-9772 520 Hz 25 0.129 1.562 17.94H4-5 4098-9772 520 Hz 25 0.129 1.661 17.84H4-6 4098-9772 520 Hz 26 0.129 1.743 17.76H4-7 4098-9772 520 Hz 24 0.129 1.800 17.70H4-8 4098-9772 520 Hz 26 0.129 1.842 17.66H4-9 4098-9772 520 Hz 23 0.129 1.860 17.64

Totals: 360 Ft. 1.161A

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropH9 3RD FLOOR NORTH-CENTER SIG9 1.161A 9.54%H10 4TH FLOOR NORTH-CENTER SIG10 1.161A 11.07%H11 SPARE SIG11 0.000A 0.00%

2.322A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

H9 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 9.54%Circuit Capacity 3.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceH9-1 4098-9772 520 Hz 158 0.129 1.126 18.37H9-2 4098-9772 520 Hz 29 0.129 1.310 18.19H9-3 4098-9772 520 Hz 24 0.129 1.443 18.06H9-4 4098-9772 520 Hz 25 0.129 1.562 17.94H9-5 4098-9772 520 Hz 25 0.129 1.661 17.84H9-6 4098-9772 520 Hz 26 0.129 1.743 17.76H9-7 4098-9772 520 Hz 24 0.129 1.800 17.70H9-8 4098-9772 520 Hz 26 0.129 1.842 17.66H9-9 4098-9772 520 Hz 23 0.129 1.860 17.64

Totals: 360 Ft. 1.161A

H10 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.07%Ckt Capacity 3.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceH10-1 4098-9772 520 Hz 200 0.129 1.426 18.07H10-2 4098-9772 520 Hz 29 0.129 1.609 17.89H10-3 4098-9772 520 Hz 24 0.129 1.743 17.76H10-4 4098-9772 520 Hz 25 0.129 1.861 17.64H10-5 4098-9772 520 Hz 25 0.129 1.960 17.54H10-6 4098-9772 520 Hz 26 0.129 2.043 17.46H10-7 4098-9772 520 Hz 24 0.129 2.100 17.40H10-8 4098-9772 520 Hz 26 0.129 2.141 17.36H10-9 4098-9772 520 Hz 23 0.129 2.159 17.34

Totals: 402 Ft. 1.161A

Parkway Off Central - EPS-1 CIRCUIT SUMMARY & VOLTAGE DROP

Alarm Unit Wire Spare Spare

Channel Description Current % Drop Load* Length Current VoltageDropA1:1 GARAGE/3RD FLOOR 2.479A 11.32% 29 2,248 17% 45%A1:2 1ST FLOOR/4TH FLOOR 2.453A 4.07% 37 2,263 18% 80%A1:3 2ND FLOOR 1.995A 9.58% 22 1,314 34% 54%

EPRs

FOR

A1:

1

0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%

EPRs

FOR

A1:

2

0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%

EPRs

FOR

A1:

3

0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%0.000A 0.00% 0 0 100% 100%

* 139 Unit Load Limit

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.A1: ENHANCED POWER SUPPLY - CHANNEL 1 SWITCH SETTINGS

IDNac Number Device Type PID Candela Custom Label (Max 40 Characters) 1A1:1-1 AV 49AV-WRF 75cd GARAGE 001 1-1-1 X ON

A1:1-2 AV 49AV-WRF 75cd GARAGE 001 1-1-2 X ON

A1:1-3 AV 49AV-WRF 75cd GARAGE 001 1-1-3 X X ON

A1:1-4 AV 49AV-WRF 75cd GARAGE 001 1-1-4 X ON

A1:1-5 AV 49AV-WRF 75cd GARAGE 001 1-1-5 X X ON

A1:1-6 AV 49AV-WRF 75cd GARAGE 001 1-1-6 X X ON

A1:1-7 AV 49AV-WRF 75cd GARAGE 001 1-1-7 X X X ON

A1:1-8 AV 49AV-WRF 75cd GARAGE 001 1-1-8 X ON

A1:1-9 AV 49AV-WRF 75cd GARAGE 001 1-1-9 X X ON

A1:1-10 AV 49AV-WRF 75cd GARAGE 001 1-1-10 X X ON

A1:1-11 AV 49AV-WRF 75cd GARAGE 001 1-1-11 X X X ON

A1:1-12 AV 49AV-WRF 75cd GARAGE 001 1-1-12 X X ON

A1:1-13 AV 49AV-WRF 75cd GARAGE 001 1-1-13 X X X ON

A1:1-14 AV 49AV-WRF 75cd GARAGE 001 1-1-14 X X X ON

A1:1-15 AV 49AV-WRF 75cd GARAGE 001 1-1-15 X X X X ON

A1:1-16 AV 49AV-WRF 75cd GARAGE 001 1-1-16 X ON

A1:1-17 X X ON

A1:1-18 AV 49AV-WRF 15cd CORRIDOR 344 1-1-18 X X ON

A1:1-19 AV 49AV-WRF 15cd CORRIDOR 344 1-1-19 X X X ON

A1:1-20 AV 49AV-WRF 15cd CORRIDOR 344 1-1-20 X X ON

A1:1-21 AV 49AV-WRF 15cd CORRIDOR 344 1-1-21 X X X ON

A1:1-22 AV 49AV-WRF 15cd CORRIDOR 344 1-1-22 X X X ON

A1:1-23 AV 49AV-WRF 15cd CORRIDOR 344 1-1-23 X X X X ON

A1:1-24 AV 49AV-WRF 15cd CORRIDOR 344 1-1-24 X X ON

A1:1-25 AV 49AV-WRF 15cd CORRIDOR 344 1-1-25 X X X ON

A1:1-26 AV 49AV-WRF 15cd CORRIDOR 344 1-1-26 X X X ON

A1:1-27 AV 49AV-WRF 15cd CORRIDOR 344 1-1-27 X X X X ON

A1:1-28 AV 49AV-WRF 15cd CORRIDOR 344 1-1-28 X X X ON

A1:1-29 AV 49AV-WRF 15cd STORAGE 358 1-1-29 X X X X ON

A1:1-30 AV 49AV-WRF 15cd STORAGE 362 1-1-30 X X X X ON

A1:1-31 X X X X X ON

A1:1-32 X ON

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.A1: ENHANCED POWER SUPPLY - CHANNEL 2 SWITCH SETTINGS

IDNac Number Device Type Custom Label (Max 40 Characters) 1A1:2-1 AV 49AV-WRF 15cd CORRIDOR 144 1-2-1 X ON

A1:2-2 AV 49AV-WRF 15cd CORRIDOR 144 1-2-2 X ON

A1:2-3 AV 49AV-WRF 15cd CORRIDOR 144 1-2-3 X X ON

A1:2-4 AV 49AV-WRF 15cd CORRIDOR 144 1-2-4 X ON

A1:2-5 VO 49VO-WRF 15cd CONF. ROOM 160 1-2-5 X X ON

A1:2-6 AV 49AV-WRF 75cd COMMUNITY ROOM 153 1-2-6 X X ON

A1:2-7 VO 49VO-WRF 15cd THEATRE 152 1-2-7 X X X ON

A1:2-8 VO 49VO-WRF 15cd WOMEN 148 1-2-8 X ON

A1:2-9 VO 49VO-WRF 15cd MEN 149 1-2-9 X X ON

A1:2-10 VO 49VO-WRF 15cd SHOWER 150 1-2-10 X X ON

A1:2-11 AV 49AV-WRF 30cd FITNESS CENTER 147 1-2-11 X X X ON

A1:2-12 AV 49AV-WRF 15cd GROUP FITNESS 146 1-2-12 X X ON

A1:2-13 VO 49VO-WRF 15cd STUDIO UNIT 135 1-2-13 X X X ON

A1:2-14 VO 49VO-WRF 185cd STUDIO UNIT 135 1-2-14 X X X ON

A1:2-15 AV 49AV-WRF 15cd CORRIDOR 144 1-2-15 X X X X ON

A1:2-16 AV 49AV-WRF 15cd CORRIDOR 144 1-2-16 X ON

A1:2-17 AV 49AV-WRF 15cd CORRIDOR 144 1-2-17 X X ON

A1:2-18 AV 49AV-WRF 15cd CORRIDOR 144 1-2-18 X X ON

A1:2-19 AV 49AV-WRF 15cd CORRIDOR 144 1-2-19 X X X ON

A1:2-20 AV 49AV-WRF 15cd CORRIDOR 144 1-2-20 X X ON

A1:2-21 AV 49AV-WRF 15cd CORRIDOR 144 1-2-21 X X X ON

A1:2-22 AV 49AV-WRF 15cd STORAGE 168 1-2-22 X X X ON

A1:2-23 VO 49VO-WRF 15cd 1 BEDROOM UNIT 128 1-2-23 X X X X ON

A1:2-24 VO 49VO-WRF 185cd 1 BEDROOM UNIT 128 1-2-24 X X ON

A1:2-25 X X X ON

A1:2-26 AV 49AV-WRF 15cd CORRIDOR 444 1-2-26 X X X ON

A1:2-27 AV 49AV-WRF 15cd CORRIDOR 444 1-2-27 X X X X ON

A1:2-28 AV 49AV-WRF 15cd CORRIDOR 444 1-2-28 X X X ON

A1:2-29 AV 49AV-WRF 15cd CORRIDOR 444 1-2-29 X X X X ON

A1:2-30 AV 49AV-WRF 15cd STORAGE 458 1-2-30 X X X X ON

A1:2-31 AV 49AV-WRF 15cd CORRIDOR 444 1-2-31 X X X X X ON

A1:2-32 AV 49AV-WRF 15cd CORRIDOR 444 1-2-32 X ON

A1:2-33 AV 49AV-WRF 15cd CORRIDOR 444 1-2-33 X X ON

A1:2-34 AV 49AV-WRF 15cd CORRIDOR 444 1-2-34 X X ON

A1:2-35 AV 49AV-WRF 15cd CORRIDOR 444 1-2-35 X X X ON

A1:2-36 AV 49AV-WRF 15cd CORRIDOR 444 1-2-36 X X ON

A1:2-37 AV 49AV-WRF 15cd CORRIDOR 444 1-2-37 X X X ON

A1:2-38 AV 49AV-WRF 15cd STORAGE 462 1-2-38 X X X ON

A1:2-39 X X X X ON

A1:2-40 X X ON

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.A1: ENHANCED POWER SUPPLY - CHANNEL 3 SWITCH SETTINGS

IDNac Number Device Type Custom Label (Max 40 Characters) 1A1:3-1 AV 49AV-WRF 15cd CORRIDOR 244 1-3-1 X ON

A1:3-2 AV 49AV-WRF 15cd CORRIDOR 244 1-3-2 X ON

A1:3-3 AV 49AV-WRF 15cd CORRIDOR 244 1-3-3 X X ON

A1:3-4 AV 49AV-WRF 15cd CORRIDOR 244 1-3-4 X ON

A1:3-5 AV 49AV-WRF 15cd STORAGE 258 1-3-5 X X ON

A1:3-6 AV 49AV-WRF 15cd CORRIDOR 244 1-3-6 X X ON

A1:3-7 VO 49VO-WRF 15cd 3 BEDROOM UNIT 229 1-3-7 X X X ON

A1:3-8 VO 49VO-WRF 185cd 3 BEDROOM UNIT 229 1-3-8 X ON

A1:3-9 VO 49VO-WRF 185cd 3 BEDROOM UNIT 229 1-3-9 X X ON

A1:3-10 VO 49VO-WRF 185cd 3 BEDROOM UNIT 229 1-3-10 X X ON

A1:3-11 VO 49VO-WRF 15cd 3 BEDROOM UNIT 229 1-3-11 X X X ON

A1:3-12 AV 49AV-WRF 15cd CORRIDOR 244 1-3-12 X X ON

A1:3-13 AV 49AV-WRF 15cd CORRIDOR 244 1-3-13 X X X ON

A1:3-14 AV 49AV-WRF 15cd CORRIDOR 244 1-3-14 X X X ON

A1:3-15 AV 49AV-WRF 15cd CORRIDOR 244 1-3-15 X X X X ON

A1:3-16 AV 49AV-WRF 15cd CORRIDOR 244 1-3-16 X ON

A1:3-17 AV 49AV-WRF 15cd CORRIDOR 244 1-3-17 X X ON

A1:3-18 AV 49AV-WRF 15cd STORAGE 262 1-3-18 X X ON

A1:3-19 VO 49VO-WRF 15cd 2 BEDROOM UNIT 210 1-3-19 X X X ON

A1:3-20 VO 49VO-WRF 185cd 2 BEDROOM UNIT 210 1-3-20 X X ON

A1:3-21 VO 49VO-WRF 185cd 2 BEDROOM UNIT 210 1-3-21 X X X ON

A1:3-22 VO 49VO-WRF 15cd 2 BEDROOM UNIT 210 1-3-22 X X X ON

A1:3-23 X X X X ON

A1:1 Notification SLC Distributed Load Voltage Drop

Starting Voltage: 29vdcMin. Device Voltage: 23.vdc Primary Wire Gauge: 14ga Wire Res. Per Ft. 0.0031 @ 75Á Celsius

Allowable % Drop: 20.7% Home Run Wire Gauge: 14ga Wire Res. Per Ft. 0.0031 @ 75Á Celsius

Class B CalculationsDistance Device Current Voltage Voltage % Vdrop

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device Wire Length

1 A1:1-1 PANEL 65 49AV-WRF 75cd 0.1070 0.535 0.214 28.786 Branch 1: 2.39%1 A1:1-2 A1:1-1 60 49AV-WRF 75cd 0.1070 0.428 0.158 28.629 Length: 375

1 A1:1-3 A1:1-2 78 49AV-WRF 75cd 0.1070 0.321 0.154 28.4751 A1:1-4 A1:1-3 86 49AV-WRF 75cd 0.1070 0.214 0.113 28.3621 A1:1-5 A1:1-4 86 49AV-WRF 75cd 0.1070 0.107 0.057 28.306

0.0000 0.000 0.000 0.0002 A1:1-6 PANEL 38 49AV-WRF 75cd 0.1070 1.177 0.275 28.725 Branch 2: 11.32%2 A1:1-7 A1:1-6 86 49AV-WRF 75cd 0.1070 1.070 0.565 28.160 Length: 865

2 A1:1-8 A1:1-7 86 49AV-WRF 75cd 0.1070 0.963 0.509 27.6522 A1:1-9 A1:1-8 86 49AV-WRF 75cd 0.1070 0.856 0.452 27.2002 A1:1-10 A1:1-9 86 49AV-WRF 75cd 0.1070 0.749 0.396 26.8042 A1:1-11 A1:1-10 86 49AV-WRF 75cd 0.1070 0.642 0.339 26.4652 A1:1-12 A1:1-11 64 49AV-WRF 75cd 0.1070 0.535 0.210 26.2552 A1:1-13 A1:1-12 76 49AV-WRF 75cd 0.1070 0.428 0.200 26.0552 A1:1-14 A1:1-13 85 49AV-WRF 75cd 0.1070 0.321 0.168 25.8882 A1:1-15 A1:1-14 86 49AV-WRF 75cd 0.1070 0.214 0.113 25.7752 A1:1-16 A1:1-15 86 49AV-WRF 75cd 0.1070 0.107 0.057 25.718

0.0000 0.000 0.000 0.0003 TAP1 PANEL 62 JBOX 0.0000 0.767 0.292 28.708 Branch 3: 4.67%3 A1:1-18 TAP1 27 49AV-WRF 15cd 0.0590 0.295 0.049 28.659 Length: 10083 A1:1-19 A1:1-18 62 49AV-WRF 15cd 0.0590 0.236 0.090 28.5693 A1:1-20 A1:1-19 84 49AV-WRF 15cd 0.0590 0.118 0.061 28.5083 A1:1-21 A1:1-20 103 49AV-WRF 15cd 0.0590 0.059 0.037 28.4713 A1:1-22 TAP1 128 49AV-WRF 15cd 0.0590 0.472 0.371 28.3373 A1:1-23 A1:1-22 108 49AV-WRF 15cd 0.0590 0.413 0.274 28.0633 A1:1-24 A1:1-23 43 49AV-WRF 15cd 0.0590 0.354 0.093 27.9703 A1:1-25 A1:1-24 69 49AV-WRF 15cd 0.0590 0.295 0.125 27.8453 A1:1-26 A1:1-25 65 49AV-WRF 15cd 0.0590 0.236 0.094 27.7513 A1:1-27 A1:1-26 92 49AV-WRF 15cd 0.0590 0.118 0.067 27.6843 A1:1-28 A1:1-27 104 49AV-WRF 15cd 0.0590 0.059 0.038 27.6463 A1:1-29 A1:1-19 31 49AV-WRF 15cd 0.0590 0.059 0.011 28.5583 A1:1-30 A1:1-26 30 49AV-WRF 15cd 0.0590 0.059 0.011 27.740

A1:2 Distributed Load Voltage Drop

Starting Voltage: 29vdcMin. Device Voltage: 23.vdc Primary Wire Gauge: 14ga Wire Res. Per Ft. 0.0031 @ 75Á Celsius

Allowable % Drop: 20.7% Home Run Wire Gauge: 14ga Wire Res. Per Ft. 0.0031 @ 75Á Celsius

Class B CalculationsDistance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A1:2-1 PANEL 40 49AV-WRF 15cd 0.0590 0.959 0.236 28.764 Branch 1: 2.71%1 A1:2-2 A1:2-1 62 49AV-WRF 15cd 0.0590 0.746 0.284 28.480 Length: 607

1 A1:2-3 A1:2-2 84 49AV-WRF 15cd 0.0590 0.373 0.192 28.2881 A1:2-4 A1:2-3 103 49AV-WRF 15cd 0.0590 0.059 0.037 28.2511 A1:2-5 A1:2-2 38 49VO-WRF 15cd 0.0470 0.047 0.011 28.4701 A1:2-6 A1:2-1 53 49AV-WRF 75cd 0.1070 0.154 0.050 28.7141 A1:2-7 A1:2-6 43 49VO-WRF 15cd 0.0470 0.047 0.012 28.7021 A1:2-8 A1:2-2 27 49VO-WRF 15cd 0.0470 0.141 0.023 28.4571 A1:2-9 A1:2-8 21 49VO-WRF 15cd 0.0470 0.094 0.012 28.4451 A1:2-10 A1:2-9 18 49VO-WRF 15cd 0.0470 0.047 0.005 28.4401 A1:2-11 A1:2-2 51 49AV-WRF 30cd 0.0670 0.126 0.039 28.4411 A1:2-12 A1:2-11 15 49AV-WRF 15cd 0.0590 0.059 0.005 28.4361 A1:2-13 A1:2-3 23 49VO-WRF 15cd 0.0470 0.255 0.036 28.2521 A1:2-14 A1:2-13 29 49VO-WRF 185cd 0.2080 0.208 0.037 28.215

0.0000 0.000 0.000 0.0002 A1:2-15 PANEL 110 49AV-WRF 15cd 0.0590 0.727 0.491 28.509 Branch 2: 4.07%2 A1:2-16 A1:2-15 108 49AV-WRF 15cd 0.0590 0.413 0.274 28.235 Length: 691

2 A1:2-17 A1:2-16 35 49AV-WRF 15cd 0.0590 0.354 0.076 28.1592 A1:2-18 A1:2-17 77 49AV-WRF 15cd 0.0590 0.295 0.139 28.0202 A1:2-19 A1:2-18 65 49AV-WRF 15cd 0.0590 0.236 0.094 27.9252 A1:2-20 A1:2-19 92 49AV-WRF 15cd 0.0590 0.118 0.067 27.8592 A1:2-21 A1:2-20 104 49AV-WRF 15cd 0.0590 0.059 0.038 27.8212 A1:2-22 A1:2-19 30 49AV-WRF 15cd 0.0590 0.059 0.011 27.9152 A1:2-23 A1:2-15 45 49VO-WRF 15cd 0.0470 0.255 0.070 28.4392 A1:2-24 A1:2-23 25 49VO-WRF 185cd 0.2080 0.208 0.032 28.407

0.0000 0.000 0.000 0.0003 TAP1 PANEL 19 JBOX 0.0000 0.767 0.089 28.911 Branch 3: 3.97%3 A1:2-26 TAP1 27 49AV-WRF 15cd 0.0590 0.295 0.049 28.862 Length: 965

3 A1:2-27 A1:2-26 62 49AV-WRF 15cd 0.0590 0.236 0.090 28.7723 A1:2-28 A1:2-27 84 49AV-WRF 15cd 0.0590 0.118 0.061 28.7113 A1:2-29 A1:2-28 103 49AV-WRF 15cd 0.0590 0.059 0.037 28.6743 A1:2-30 A1:2-27 31 49AV-WRF 15cd 0.0590 0.059 0.011 28.7613 A1:2-31 TAP1 128 49AV-WRF 15cd 0.0590 0.472 0.371 28.5403 A1:2-32 A1:2-31 108 49AV-WRF 15cd 0.0590 0.413 0.274 28.2663 A1:2-33 A1:2-32 43 49AV-WRF 15cd 0.0590 0.354 0.093 28.1723 A1:2-34 A1:2-33 69 49AV-WRF 15cd 0.0590 0.295 0.125 28.0473 A1:2-35 A1:2-34 65 49AV-WRF 15cd 0.0590 0.236 0.094 27.9533 A1:2-36 A1:2-35 92 49AV-WRF 15cd 0.0590 0.118 0.067 27.8863 A1:2-37 A1:2-36 104 49AV-WRF 15cd 0.0590 0.059 0.038 27.8493 A1:2-38 A1:2-35 30 49AV-WRF 15cd 0.0590 0.059 0.011 27.942

A1:3 Distributed Load Voltage Drop

Starting Voltage: 29vdcMin. Device Voltage: 23.vdc Primary Wire Gauge: 14ga Wire Res. Per Ft. 0.0031 @ 75Á Celsius

Allowable % Drop: 20.7% Home Run Wire Gauge: 14ga Wire Res. Per Ft. 0.0031 @ 75Á Celsius

Class B CalculationsDistance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A1:3-1 PANEL 32 49AV-WRF 15cd 0.0590 1.072 0.211 28.789 Branch 1: 3.81%1 A1:3-2 A1:3-1 62 49AV-WRF 15cd 0.0590 0.236 0.090 28.700 Length: 561

1 A1:3-3 A1:3-2 84 49AV-WRF 15cd 0.0590 0.118 0.061 28.6391 A1:3-4 A1:3-3 103 49AV-WRF 15cd 0.0590 0.059 0.037 28.6011 A1:3-5 A1:3-2 31 49AV-WRF 15cd 0.0590 0.059 0.011 28.6881 A1:3-6 A1:3-1 111 49AV-WRF 15cd 0.0590 0.777 0.530 28.2601 A1:3-7 A1:3-6 28 49VO-WRF 15cd 0.0470 0.718 0.123 28.1361 A1:3-8 A1:3-7 29 49VO-WRF 185cd 0.2080 0.671 0.119 28.0171 A1:3-9 A1:3-8 20 49VO-WRF 185cd 0.2080 0.463 0.057 27.9601 A1:3-10 A1:3-9 37 49VO-WRF 185cd 0.2080 0.255 0.058 27.9021 A1:3-11 A1:3-10 24 49VO-WRF 15cd 0.0470 0.047 0.007 27.895

0.0000 0.000 0.000 0.0002 A1:3-12 PANEL 231 49AV-WRF 15cd 0.0590 0.923 1.309 27.691 Branch 2: 9.58%2 A1:3-13 A1:3-12 35 49AV-WRF 15cd 0.0590 0.864 0.186 27.505 Length: 753

2 A1:3-14 A1:3-13 77 49AV-WRF 15cd 0.0590 0.805 0.381 27.1252 A1:3-15 A1:3-14 65 49AV-WRF 15cd 0.0590 0.746 0.298 26.8272 A1:3-16 A1:3-15 92 49AV-WRF 15cd 0.0590 0.628 0.355 26.4722 A1:3-17 A1:3-16 104 49AV-WRF 15cd 0.0590 0.059 0.038 26.4342 A1:3-18 A1:3-15 30 49AV-WRF 15cd 0.0590 0.059 0.011 26.8162 A1:3-19 A1:3-16 38 49VO-WRF 15cd 0.0470 0.510 0.119 26.3532 A1:3-20 A1:3-19 25 49VO-WRF 185cd 0.2080 0.463 0.071 26.2822 A1:3-21 A1:3-20 35 49VO-WRF 185cd 0.2080 0.255 0.055 26.2272 A1:3-22 A1:3-21 21 49VO-WRF 15cd 0.0470 0.047 0.006 26.221

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-6

01.d

wg

9/13

/201

6 9:

52:3

3 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-602

CALCULATIONS AND

SCHEDULES

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-601.dwg, FA-602 CALCULATIONS AND SCHEDULES, 9/13/2016 9:52:32 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 14: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Parkway Off Central NAC1 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 42 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 5.4180Peripheral Totals 0.0000 5.4180

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 5.6030

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 5.6030

Sub Total 0.0850 5.6030

Total 0.0850 5.6030

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 5.603 = 0.4669 Alarm Ah

2.5069Additional Spare Battery Capacity = 0% + 0.0000

2.5069Battery Discharge Factor = 20% + 0.5014Minimum Battery Required 2081-9272 6.2AH (2x) 3.0083

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN1:H1 1ST FLOOR WEST-SE SIG1 1.419A 10.50%N1:H2 1ST FLOOR WEST-SW SIG2 1.548A 14.24%N1:H3 1ST FLOOR WEST-NE SIG3 1.161A 5.02%N1:H4 1ST FLOOR WEST-NW SIG4 1.290A 7.70%

5.418A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N1:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 10.50%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN1:H1-1 4098-9772 520 Hz 99 0.129 0.863 18.64N1:H1-2 4098-9772 520 Hz 26 0.129 1.068 18.43N1:H1-3 4098-9772 520 Hz 27 0.129 1.261 18.24N1:H1-4 4098-9772 520 Hz 24 0.129 1.413 18.09N1:H1-5 4098-9772 520 Hz 26 0.129 1.557 17.94N1:H1-6 4098-9772 520 Hz 27 0.129 1.686 17.81N1:H1-7 4098-9772 520 Hz 24 0.129 1.781 17.72N1:H1-8 4098-9772 520 Hz 26 0.129 1.863 17.64N1:H1-9 4098-9772 520 Hz 34 0.129 1.944 17.56N1:H1-10 4098-9772 520 Hz 53 0.129 2.028 17.47N1:H1-11 4098-9772 520 Hz 24 0.129 2.047 17.45

Totals: 390 Ft. 1.419A

N1:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 14.24%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN1:H2-1 4098-9772 520 Hz 147 0.129 1.397 18.10N1:H2-2 4098-9772 520 Hz 29 0.129 1.650 17.85N1:H2-3 4098-9772 520 Hz 28 0.129 1.872 17.63N1:H2-4 4098-9772 520 Hz 23 0.129 2.036 17.46N1:H2-5 4098-9772 520 Hz 29 0.129 2.219 17.28N1:H2-6 4098-9772 520 Hz 23 0.129 2.347 17.15N1:H2-7 4098-9772 520 Hz 23 0.129 2.456 17.04N1:H2-8 4098-9772 520 Hz 25 0.129 2.555 16.94N1:H2-9 4098-9772 520 Hz 27 0.129 2.641 16.86N1:H2-10 4098-9772 520 Hz 26 0.129 2.703 16.80N1:H2-11 4098-9772 520 Hz 31 0.129 2.752 16.75N1:H2-12 4098-9772 520 Hz 32 0.129 2.777 16.72

Totals: 443 Ft. 1.548A

N1:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 5.02%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN1:H3-1 4098-9772 520 Hz 36 0.129 0.257 19.24N1:H3-2 4098-9772 520 Hz 22 0.129 0.396 19.10N1:H3-3 4098-9772 520 Hz 26 0.129 0.540 18.96N1:H3-4 4098-9772 520 Hz 33 0.129 0.697 18.80N1:H3-5 4098-9772 520 Hz 27 0.129 0.804 18.70N1:H3-6 4098-9772 520 Hz 19 0.129 0.864 18.64N1:H3-7 4098-9772 520 Hz 25 0.129 0.924 18.58N1:H3-8 4098-9772 520 Hz 24 0.129 0.962 18.54N1:H3-9 4098-9772 520 Hz 21 0.129 0.978 18.52

Totals: 233 Ft. 1.161A

N1:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 7.70%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN1:H4-1 4098-9772 520 Hz 77 0.129 0.610 18.89N1:H4-2 4098-9772 520 Hz 25 0.129 0.788 18.71N1:H4-3 4098-9772 520 Hz 25 0.129 0.947 18.55N1:H4-4 4098-9772 520 Hz 25 0.129 1.085 18.41N1:H4-5 4098-9772 520 Hz 24 0.129 1.199 18.30N1:H4-6 4098-9772 520 Hz 27 0.129 1.306 18.19N1:H4-7 4098-9772 520 Hz 23 0.129 1.379 18.12N1:H4-8 4098-9772 520 Hz 25 0.129 1.438 18.06N1:H4-9 4098-9772 520 Hz 27 0.129 1.481 18.02N1:H4-10 4098-9772 520 Hz 26 0.129 1.502 18.00

Totals: 304 Ft. 1.290A

Parkway Off Central NAC2 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 55 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 7.0950Peripheral Totals 0.0000 7.0950

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 7.2800

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 7.2800

Sub Total 0.0850 7.2800

Total 0.0850 7.2800

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 7.28 = 0.6067 Alarm Ah

2.6467Additional Spare Battery Capacity = 0% + 0.0000

2.6467Battery Discharge Factor = 20% + 0.5293Minimum Battery Required 2081-9272 6.2AH (2x) 3.1760

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN2:H1 1ST FLOOR EAST-SW SIG1 1.806A 11.72%N2:H2 1ST FLOOR EAST-SE SIG2 1.935A 13.05%N2:H3 1ST FLOOR EAST-NW SIG3 1.677A 11.45%N2:H4 1ST FLOOR EAST-NE SIG4 1.677A 11.56%

7.095A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N2:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.72%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN2:H1-1 4098-9772 520 Hz 38 0.129 0.421 19.08N2:H1-2 4098-9772 520 Hz 26 0.129 0.689 18.81N2:H1-3 4098-9772 520 Hz 26 0.129 0.936 18.56N2:H1-4 4098-9772 520 Hz 25 0.129 1.154 18.35N2:H1-5 4098-9772 520 Hz 22 0.129 1.328 18.17N2:H1-6 4098-9772 520 Hz 29 0.129 1.535 17.96N2:H1-7 4098-9772 520 Hz 24 0.129 1.687 17.81N2:H1-8 4098-9772 520 Hz 27 0.129 1.837 17.66N2:H1-9 4098-9772 520 Hz 23 0.129 1.946 17.55N2:H1-10 4098-9772 520 Hz 22 0.129 2.033 17.47N2:H1-11 4098-9772 520 Hz 28 0.129 2.122 17.38N2:H1-12 4098-9772 520 Hz 40 0.129 2.217 17.28N2:H1-13 4098-9772 520 Hz 28 0.129 2.261 17.24N2:H1-14 4098-9772 520 Hz 31 0.129 2.286 17.21

Totals: 389 Ft. 1.806A

N2:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.05%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN2:H2-1 4098-9772 520 Hz 43 0.129 0.511 18.99N2:H2-2 4098-9772 520 Hz 22 0.129 0.755 18.75N2:H2-3 4098-9772 520 Hz 26 0.129 1.023 18.48N2:H2-4 4098-9772 520 Hz 25 0.129 1.260 18.24N2:H2-5 4098-9772 520 Hz 25 0.129 1.478 18.02N2:H2-6 4098-9772 520 Hz 24 0.129 1.668 17.83N2:H2-7 4098-9772 520 Hz 22 0.129 1.825 17.68N2:H2-8 4098-9772 520 Hz 29 0.129 2.009 17.49N2:H2-9 4098-9772 520 Hz 22 0.129 2.131 17.37N2:H2-10 4098-9772 520 Hz 24 0.129 2.245 17.26N2:H2-11 4098-9772 520 Hz 24 0.129 2.340 17.16N2:H2-12 4098-9772 520 Hz 30 0.129 2.435 17.07N2:H2-13 4098-9772 520 Hz 17 0.129 2.475 17.02N2:H2-14 4098-9772 520 Hz 27 0.129 2.518 16.98N2:H2-15 4098-9772 520 Hz 35 0.129 2.546 16.95

Totals: 395 Ft. 1.935A

N2:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.45%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN2:H3-1 4098-9772 520 Hz 61 0.129 0.628 18.87N2:H3-2 4098-9772 520 Hz 30 0.129 0.913 18.59N2:H3-3 4098-9772 520 Hz 25 0.129 1.131 18.37N2:H3-4 4098-9772 520 Hz 25 0.129 1.329 18.17N2:H3-5 4098-9772 520 Hz 25 0.129 1.507 17.99N2:H3-6 4098-9772 520 Hz 27 0.129 1.678 17.82N2:H3-7 4098-9772 520 Hz 26 0.129 1.823 17.68N2:H3-8 4098-9772 520 Hz 25 0.129 1.941 17.56N2:H3-9 4098-9772 520 Hz 25 0.129 2.040 17.46N2:H3-10 4098-9772 520 Hz 24 0.129 2.116 17.38N2:H3-11 4098-9772 520 Hz 24 0.129 2.173 17.33N2:H3-12 4098-9772 520 Hz 25 0.129 2.213 17.29N2:H3-13 4098-9772 520 Hz 25 0.129 2.233 17.27

Totals: 367 Ft. 1.677A

N2:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.56%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN2:H4-1 4098-9772 520 Hz 54 0.129 0.556 18.94N2:H4-2 4098-9772 520 Hz 20 0.129 0.746 18.75N2:H4-3 4098-9772 520 Hz 48 0.129 1.164 18.34N2:H4-4 4098-9772 520 Hz 18 0.129 1.307 18.19N2:H4-5 4098-9772 520 Hz 27 0.129 1.499 18.00N2:H4-6 4098-9772 520 Hz 33 0.129 1.708 17.79N2:H4-7 4098-9772 520 Hz 25 0.129 1.847 17.65N2:H4-8 4098-9772 520 Hz 23 0.129 1.956 17.54N2:H4-9 4098-9772 520 Hz 25 0.129 2.055 17.44N2:H4-10 4098-9772 520 Hz 28 0.129 2.144 17.36N2:H4-11 4098-9772 520 Hz 23 0.129 2.199 17.30N2:H4-12 4098-9772 520 Hz 25 0.129 2.238 17.26N2:H4-13 4098-9772 520 Hz 21 0.129 2.255 17.25

Totals: 370 Ft. 1.677A

Parkway Off Central NAC3 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 52 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 6.7080Peripheral Totals 0.0000 6.7080

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 6.8930

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 6.8930

Sub Total 0.0850 6.8930

Total 0.0850 6.8930

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 6.893 = 0.5744 Alarm Ah

2.6144Additional Spare Battery Capacity = 0% + 0.0000

2.6144Battery Discharge Factor = 20% + 0.5229Minimum Battery Required 2081-9272 6.2AH (2x) 3.1373

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN3:H1 2ND FLOOR-WEST-SE SIG1 1.806A 13.96%N3:H2 2ND FLOOR-WEST-SW SIG2 1.677A 11.48%N3:H3 2ND FLOOR-WEST-NE SIG3 1.548A 9.82%N3:H4 2ND FLOOR-WEST-NW SIG4 1.677A 13.47%

6.708A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N3:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.96%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN3:H1-1 4098-9772 520 Hz 64 0.129 0.710 18.79N3:H1-2 4098-9772 520 Hz 26 0.129 0.977 18.52N3:H1-3 4098-9772 520 Hz 27 0.129 1.234 18.27N3:H1-4 4098-9772 520 Hz 24 0.129 1.443 18.06N3:H1-5 4098-9772 520 Hz 26 0.129 1.649 17.85N3:H1-6 4098-9772 520 Hz 27 0.129 1.842 17.66N3:H1-7 4098-9772 520 Hz 24 0.129 1.994 17.51N3:H1-8 4098-9772 520 Hz 26 0.129 2.138 17.36N3:H1-9 4098-9772 520 Hz 34 0.129 2.299 17.20N3:H1-10 4098-9772 520 Hz 53 0.129 2.509 16.99N3:H1-11 4098-9772 520 Hz 24 0.129 2.585 16.91N3:H1-12 4098-9772 520 Hz 26 0.129 2.647 16.85N3:H1-13 4098-9772 520 Hz 32 0.129 2.698 16.80N3:H1-14 4098-9772 520 Hz 31 0.129 2.722 16.78

Totals: 444 Ft. 1.806A

N3:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.48%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN3:H2-1 4098-9772 520 Hz 61 0.129 0.628 18.87N3:H2-2 4098-9772 520 Hz 27 0.129 0.885 18.62N3:H2-3 4098-9772 520 Hz 21 0.129 1.068 18.43N3:H2-4 4098-9772 520 Hz 30 0.129 1.305 18.19N3:H2-5 4098-9772 520 Hz 22 0.129 1.462 18.04N3:H2-6 4098-9772 520 Hz 33 0.129 1.671 17.83N3:H2-7 4098-9772 520 Hz 28 0.129 1.826 17.67N3:H2-8 4098-9772 520 Hz 23 0.129 1.936 17.56N3:H2-9 4098-9772 520 Hz 29 0.129 2.051 17.45N3:H2-10 4098-9772 520 Hz 23 0.129 2.124 17.38N3:H2-11 4098-9772 520 Hz 23 0.129 2.178 17.32N3:H2-12 4098-9772 520 Hz 25 0.129 2.218 17.28N3:H2-13 4098-9772 520 Hz 27 0.129 2.239 17.26

Totals: 372 Ft. 1.677A

N3:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 9.82%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN3:H3-1 4098-9772 520 Hz 51 0.129 0.485 19.02N3:H3-2 4098-9772 520 Hz 33 0.129 0.772 18.73N3:H3-3 4098-9772 520 Hz 25 0.129 0.970 18.53N3:H3-4 4098-9772 520 Hz 30 0.129 1.184 18.32N3:H3-5 4098-9772 520 Hz 22 0.129 1.324 18.18N3:H3-6 4098-9772 520 Hz 26 0.129 1.468 18.03N3:H3-7 4098-9772 520 Hz 34 0.129 1.629 17.87N3:H3-8 4098-9772 520 Hz 28 0.129 1.740 17.76N3:H3-9 4098-9772 520 Hz 19 0.129 1.800 17.70N3:H3-10 4098-9772 520 Hz 25 0.129 1.860 17.64N3:H3-11 4098-9772 520 Hz 24 0.129 1.898 17.60N3:H3-12 4098-9772 520 Hz 21 0.129 1.914 17.59

Totals: 338 Ft. 1.548A

N3:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.47%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN3:H4-1 4098-9772 520 Hz 79 0.129 0.813 18.69N3:H4-2 4098-9772 520 Hz 35 0.129 1.146 18.35N3:H4-3 4098-9772 520 Hz 25 0.129 1.364 18.14N3:H4-4 4098-9772 520 Hz 39 0.129 1.673 17.83N3:H4-5 4098-9772 520 Hz 34 0.129 1.915 17.58N3:H4-6 4098-9772 520 Hz 25 0.129 2.074 17.43N3:H4-7 4098-9772 520 Hz 25 0.129 2.212 17.29N3:H4-8 4098-9772 520 Hz 25 0.129 2.331 17.17N3:H4-9 4098-9772 520 Hz 24 0.129 2.426 17.07N3:H4-10 4098-9772 520 Hz 27 0.129 2.512 16.99N3:H4-11 4098-9772 520 Hz 23 0.129 2.566 16.93N3:H4-12 4098-9772 520 Hz 25 0.129 2.606 16.89N3:H4-13 4098-9772 520 Hz 27 0.129 2.627 16.87

Totals: 413 Ft. 1.677A

Parkway Off Central NAC4 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 57 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 7.3530Peripheral Totals 0.0000 7.3530

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 7.5380

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 7.5380

Sub Total 0.0850 7.5380

Total 0.0850 7.5380

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 7.538 = 0.6282 Alarm Ah

2.6682Additional Spare Battery Capacity = 0% + 0.0000

2.6682Battery Discharge Factor = 20% + 0.5336Minimum Battery Required 2081-9272 6.2AH (2x) 3.2018

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN4:H1 2ND FLOOR-EAST-SW SIG1 1.806A 11.99%N4:H2 2ND FLOOR-EAST-SE SIG2 1.935A 13.05%N4:H3 2ND FLOOR-EAST-NW SIG3 1.677A 11.45%N4:H4 2ND FLOOR-EAST-NE SIG4 1.935A 14.88%

7.353A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N4:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.99%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN4:H1-1 4098-9772 520 Hz 39 0.129 0.432 19.07N4:H1-2 4098-9772 520 Hz 27 0.129 0.710 18.79N4:H1-3 4098-9772 520 Hz 29 0.129 0.986 18.51N4:H1-4 4098-9772 520 Hz 25 0.129 1.204 18.30N4:H1-5 4098-9772 520 Hz 22 0.129 1.378 18.12N4:H1-6 4098-9772 520 Hz 29 0.129 1.585 17.92N4:H1-7 4098-9772 520 Hz 24 0.129 1.737 17.76N4:H1-8 4098-9772 520 Hz 27 0.129 1.887 17.61N4:H1-9 4098-9772 520 Hz 23 0.129 1.996 17.50N4:H1-10 4098-9772 520 Hz 22 0.129 2.083 17.42N4:H1-11 4098-9772 520 Hz 29 0.129 2.175 17.33N4:H1-12 4098-9772 520 Hz 32 0.129 2.251 17.25N4:H1-13 4098-9772 520 Hz 39 0.129 2.313 17.19N4:H1-14 4098-9772 520 Hz 31 0.129 2.337 17.16

Totals: 398 Ft. 1.806A

N4:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.05%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN4:H2-1 4098-9772 520 Hz 43 0.129 0.511 18.99N4:H2-2 4098-9772 520 Hz 22 0.129 0.755 18.75N4:H2-3 4098-9772 520 Hz 26 0.129 1.023 18.48N4:H2-4 4098-9772 520 Hz 25 0.129 1.260 18.24N4:H2-5 4098-9772 520 Hz 25 0.129 1.478 18.02N4:H2-6 4098-9772 520 Hz 24 0.129 1.668 17.83N4:H2-7 4098-9772 520 Hz 22 0.129 1.825 17.68N4:H2-8 4098-9772 520 Hz 29 0.129 2.009 17.49N4:H2-9 4098-9772 520 Hz 22 0.129 2.131 17.37N4:H2-10 4098-9772 520 Hz 24 0.129 2.245 17.26N4:H2-11 4098-9772 520 Hz 24 0.129 2.340 17.16N4:H2-12 4098-9772 520 Hz 30 0.129 2.435 17.07N4:H2-13 4098-9772 520 Hz 17 0.129 2.475 17.02N4:H2-14 4098-9772 520 Hz 27 0.129 2.518 16.98N4:H2-15 4098-9772 520 Hz 35 0.129 2.546 16.95

Totals: 395 Ft. 1.935A

N4:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.45%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN4:H3-1 4098-9772 520 Hz 61 0.129 0.628 18.87N4:H3-2 4098-9772 520 Hz 30 0.129 0.913 18.59N4:H3-3 4098-9772 520 Hz 25 0.129 1.131 18.37N4:H3-4 4098-9772 520 Hz 25 0.129 1.329 18.17N4:H3-5 4098-9772 520 Hz 25 0.129 1.507 17.99N4:H3-6 4098-9772 520 Hz 27 0.129 1.678 17.82N4:H3-7 4098-9772 520 Hz 26 0.129 1.823 17.68N4:H3-8 4098-9772 520 Hz 25 0.129 1.941 17.56N4:H3-9 4098-9772 520 Hz 25 0.129 2.040 17.46N4:H3-10 4098-9772 520 Hz 24 0.129 2.116 17.38N4:H3-11 4098-9772 520 Hz 24 0.129 2.173 17.33N4:H3-12 4098-9772 520 Hz 25 0.129 2.213 17.29N4:H3-13 4098-9772 520 Hz 25 0.129 2.233 17.27

Totals: 367 Ft. 1.677A

N4:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 14.88%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN4:H4-1 4098-9772 520 Hz 54 0.129 0.642 18.86N4:H4-2 4098-9772 520 Hz 20 0.129 0.863 18.64N4:H4-3 4098-9772 520 Hz 48 0.129 1.358 18.14N4:H4-4 4098-9772 520 Hz 18 0.129 1.529 17.97N4:H4-5 4098-9772 520 Hz 27 0.129 1.764 17.74N4:H4-6 4098-9772 520 Hz 33 0.129 2.025 17.47N4:H4-7 4098-9772 520 Hz 25 0.129 2.204 17.30N4:H4-8 4098-9772 520 Hz 23 0.129 2.349 17.15N4:H4-9 4098-9772 520 Hz 25 0.129 2.488 17.01N4:H4-10 4098-9772 520 Hz 28 0.129 2.621 16.88N4:H4-11 4098-9772 520 Hz 23 0.129 2.712 16.79N4:H4-12 4098-9772 520 Hz 25 0.129 2.791 16.71N4:H4-13 4098-9772 520 Hz 21 0.129 2.841 16.66N4:H4-14 4098-9772 520 Hz 27 0.129 2.884 16.62N4:H4-15 4098-9772 520 Hz 23 0.129 2.902 16.60

Totals: 420 Ft. 1.935ASHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-6

03.d

wg

9/13

/201

6 9:

52:3

6 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-603

CALCULATIONS AND

SCHEDULES

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-603.dwg, FA-603 CALCULATIONS AND SCHEDULES, 9/13/2016 9:52:36 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 15: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Parkway Off Central NAC5 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 52 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 6.7080Peripheral Totals 0.0000 6.7080

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 6.8930

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 6.8930

Sub Total 0.0850 6.8930

Total 0.0850 6.8930

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 6.893 = 0.5744 Alarm Ah

2.6144Additional Spare Battery Capacity = 0% + 0.0000

2.6144Battery Discharge Factor = 20% + 0.5229Minimum Battery Required 2081-9272 6.2AH (2x) 3.1373

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN5:H1 3RD FLOOR-WEST-SE SIG1 1.806A 13.96%N5:H2 3RD FLOOR-WEST-SW SIG2 1.677A 11.54%N5:H3 3RD FLOOR-WEST-NW SIG3 1.548A 9.82%N5:H4 3RD FLOOR-WEST-NE SIG4 1.677A 13.47%

6.708A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N5:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.96%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN5:H1-1 4098-9772 520 Hz 64 0.129 0.710 18.79N5:H1-2 4098-9772 520 Hz 26 0.129 0.977 18.52N5:H1-3 4098-9772 520 Hz 27 0.129 1.234 18.27N5:H1-4 4098-9772 520 Hz 24 0.129 1.443 18.06N5:H1-5 4098-9772 520 Hz 26 0.129 1.649 17.85N5:H1-6 4098-9772 520 Hz 27 0.129 1.842 17.66N5:H1-7 4098-9772 520 Hz 24 0.129 1.994 17.51N5:H1-8 4098-9772 520 Hz 26 0.129 2.138 17.36N5:H1-9 4098-9772 520 Hz 34 0.129 2.299 17.20N5:H1-10 4098-9772 520 Hz 53 0.129 2.509 16.99N5:H1-11 4098-9772 520 Hz 24 0.129 2.585 16.91N5:H1-12 4098-9772 520 Hz 26 0.129 2.647 16.85N5:H1-13 4098-9772 520 Hz 32 0.129 2.698 16.80N5:H1-14 4098-9772 520 Hz 31 0.129 2.722 16.78

Totals: 444 Ft. 1.806A

N5:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.54%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN5:H2-1 4098-9772 520 Hz 62 0.129 0.638 18.86N5:H2-2 4098-9772 520 Hz 27 0.129 0.895 18.60N5:H2-3 4098-9772 520 Hz 21 0.129 1.078 18.42N5:H2-4 4098-9772 520 Hz 30 0.129 1.316 18.18N5:H2-5 4098-9772 520 Hz 22 0.129 1.472 18.03N5:H2-6 4098-9772 520 Hz 33 0.129 1.682 17.82N5:H2-7 4098-9772 520 Hz 28 0.129 1.837 17.66N5:H2-8 4098-9772 520 Hz 23 0.129 1.946 17.55N5:H2-9 4098-9772 520 Hz 29 0.129 2.061 17.44N5:H2-10 4098-9772 520 Hz 23 0.129 2.134 17.37N5:H2-11 4098-9772 520 Hz 23 0.129 2.188 17.31N5:H2-12 4098-9772 520 Hz 25 0.129 2.228 17.27N5:H2-13 4098-9772 520 Hz 27 0.129 2.249 17.25

Totals: 373 Ft. 1.677A

N5:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 9.82%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN5:H3-1 4098-9772 520 Hz 51 0.129 0.485 19.02N5:H3-2 4098-9772 520 Hz 33 0.129 0.772 18.73N5:H3-3 4098-9772 520 Hz 25 0.129 0.970 18.53N5:H3-4 4098-9772 520 Hz 30 0.129 1.184 18.32N5:H3-5 4098-9772 520 Hz 22 0.129 1.324 18.18N5:H3-6 4098-9772 520 Hz 26 0.129 1.468 18.03N5:H3-7 4098-9772 520 Hz 34 0.129 1.629 17.87N5:H3-8 4098-9772 520 Hz 28 0.129 1.740 17.76N5:H3-9 4098-9772 520 Hz 19 0.129 1.800 17.70N5:H3-10 4098-9772 520 Hz 25 0.129 1.860 17.64N5:H3-11 4098-9772 520 Hz 24 0.129 1.898 17.60N5:H3-12 4098-9772 520 Hz 21 0.129 1.914 17.59

Totals: 338 Ft. 1.548A

N5:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.47%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN5:H4-1 4098-9772 520 Hz 79 0.129 0.813 18.69N5:H4-2 4098-9772 520 Hz 35 0.129 1.146 18.35N5:H4-3 4098-9772 520 Hz 25 0.129 1.364 18.14N5:H4-4 4098-9772 520 Hz 39 0.129 1.673 17.83N5:H4-5 4098-9772 520 Hz 34 0.129 1.915 17.58N5:H4-6 4098-9772 520 Hz 25 0.129 2.074 17.43N5:H4-7 4098-9772 520 Hz 25 0.129 2.212 17.29N5:H4-8 4098-9772 520 Hz 25 0.129 2.331 17.17N5:H4-9 4098-9772 520 Hz 24 0.129 2.426 17.07N5:H4-10 4098-9772 520 Hz 27 0.129 2.512 16.99N5:H4-11 4098-9772 520 Hz 23 0.129 2.566 16.93N5:H4-12 4098-9772 520 Hz 25 0.129 2.606 16.89N5:H4-13 4098-9772 520 Hz 27 0.129 2.627 16.87

Totals: 413 Ft. 1.677A

Parkway Off Central NAC6 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 57 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 7.3530Peripheral Totals 0.0000 7.3530

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 7.5380

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 7.5380

Sub Total 0.0850 7.5380

Total 0.0850 7.5380

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 7.538 = 0.6282 Alarm Ah

2.6682Additional Spare Battery Capacity = 0% + 0.0000

2.6682Battery Discharge Factor = 20% + 0.5336Minimum Battery Required 2081-9272 6.2AH (2x) 3.2018

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN6:H1 3RD FLOOR-EAST-SW SIG1 1.806A 11.98%N6:H2 3RD FLOOR-EAST-SE SIG2 1.935A 13.05%N6:H3 3RD FLOOR-EAST-NW SIG3 1.677A 11.45%N6:H4 3RD FLOOR-EAST-NE SIG4 1.935A 14.88%

7.353A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N6:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.98%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN6:H1-1 4098-9772 520 Hz 39 0.129 0.432 19.07N6:H1-2 4098-9772 520 Hz 27 0.129 0.710 18.79N6:H1-3 4098-9772 520 Hz 29 0.129 0.986 18.51N6:H1-4 4098-9772 520 Hz 25 0.129 1.204 18.30N6:H1-5 4098-9772 520 Hz 22 0.129 1.378 18.12N6:H1-6 4098-9772 520 Hz 29 0.129 1.585 17.92N6:H1-7 4098-9772 520 Hz 24 0.129 1.737 17.76N6:H1-8 4098-9772 520 Hz 27 0.129 1.887 17.61N6:H1-9 4098-9772 520 Hz 23 0.129 1.996 17.50N6:H1-10 4098-9772 520 Hz 22 0.129 2.083 17.42N6:H1-11 4098-9772 520 Hz 29 0.129 2.175 17.33N6:H1-12 4098-9772 520 Hz 32 0.129 2.251 17.25N6:H1-13 4098-9772 520 Hz 37 0.129 2.310 17.19N6:H1-14 4098-9772 520 Hz 33 0.129 2.336 17.16

Totals: 398 Ft. 1.806A

N6:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.05%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN6:H2-1 4098-9772 520 Hz 43 0.129 0.511 18.99N6:H2-2 4098-9772 520 Hz 22 0.129 0.755 18.75N6:H2-3 4098-9772 520 Hz 26 0.129 1.023 18.48N6:H2-4 4098-9772 520 Hz 25 0.129 1.260 18.24N6:H2-5 4098-9772 520 Hz 25 0.129 1.478 18.02N6:H2-6 4098-9772 520 Hz 24 0.129 1.668 17.83N6:H2-7 4098-9772 520 Hz 22 0.129 1.825 17.68N6:H2-8 4098-9772 520 Hz 29 0.129 2.009 17.49N6:H2-9 4098-9772 520 Hz 22 0.129 2.131 17.37N6:H2-10 4098-9772 520 Hz 24 0.129 2.245 17.26N6:H2-11 4098-9772 520 Hz 24 0.129 2.340 17.16N6:H2-12 4098-9772 520 Hz 30 0.129 2.435 17.07N6:H2-13 4098-9772 520 Hz 17 0.129 2.475 17.02N6:H2-14 4098-9772 520 Hz 27 0.129 2.518 16.98N6:H2-15 4098-9772 520 Hz 35 0.129 2.546 16.95

Totals: 395 Ft. 1.935A

N6:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.45%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN6:H3-1 4098-9772 520 Hz 61 0.129 0.628 18.87N6:H3-2 4098-9772 520 Hz 30 0.129 0.913 18.59N6:H3-3 4098-9772 520 Hz 25 0.129 1.131 18.37N6:H3-4 4098-9772 520 Hz 25 0.129 1.329 18.17N6:H3-5 4098-9772 520 Hz 25 0.129 1.507 17.99N6:H3-6 4098-9772 520 Hz 27 0.129 1.678 17.82N6:H3-7 4098-9772 520 Hz 26 0.129 1.823 17.68N6:H3-8 4098-9772 520 Hz 25 0.129 1.941 17.56N6:H3-9 4098-9772 520 Hz 25 0.129 2.040 17.46N6:H3-10 4098-9772 520 Hz 24 0.129 2.116 17.38N6:H3-11 4098-9772 520 Hz 24 0.129 2.173 17.33N6:H3-12 4098-9772 520 Hz 25 0.129 2.213 17.29N6:H3-13 4098-9772 520 Hz 25 0.129 2.233 17.27

Totals: 367 Ft. 1.677A

N6:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 14.88%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN6:H4-1 4098-9772 520 Hz 54 0.129 0.642 18.86N6:H4-2 4098-9772 520 Hz 20 0.129 0.863 18.64N6:H4-3 4098-9772 520 Hz 48 0.129 1.358 18.14N6:H4-4 4098-9772 520 Hz 18 0.129 1.529 17.97N6:H4-5 4098-9772 520 Hz 27 0.129 1.764 17.74N6:H4-6 4098-9772 520 Hz 33 0.129 2.025 17.47N6:H4-7 4098-9772 520 Hz 25 0.129 2.204 17.30N6:H4-8 4098-9772 520 Hz 23 0.129 2.349 17.15N6:H4-9 4098-9772 520 Hz 25 0.129 2.488 17.01N6:H4-10 4098-9772 520 Hz 28 0.129 2.621 16.88N6:H4-11 4098-9772 520 Hz 23 0.129 2.712 16.79N6:H4-12 4098-9772 520 Hz 25 0.129 2.791 16.71N6:H4-13 4098-9772 520 Hz 21 0.129 2.841 16.66N6:H4-14 4098-9772 520 Hz 27 0.129 2.884 16.62N6:H4-15 4098-9772 520 Hz 23 0.129 2.902 16.60

Totals: 420 Ft. 1.935A

Parkway Off Central NAC7 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 52 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 6.7080Peripheral Totals 0.0000 6.7080

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 6.8930

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 6.8930

Sub Total 0.0850 6.8930

Total 0.0850 6.8930

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 6.893 = 0.5744 Alarm Ah

2.6144Additional Spare Battery Capacity = 0% + 0.0000

2.6144Battery Discharge Factor = 20% + 0.5229Minimum Battery Required 2081-9272 6.2AH (2x) 3.1373

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN7:H1 4TH FLOOR-WEST-SE SIG1 1.806A 14.07%N7:H2 4TH FLOOR-WEST-SW SIG2 1.677A 11.59%N7:H3 4TH FLOOR-WEST-NW SIG3 1.548A 9.72%N7:H4 4TH FLOOR-WEST-NE SIG4 1.677A 13.58%

6.708A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N7:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 14.07%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN7:H1-1 4098-9772 520 Hz 66 0.129 0.732 18.77N7:H1-2 4098-9772 520 Hz 26 0.129 1.000 18.50N7:H1-3 4098-9772 520 Hz 27 0.129 1.256 18.24N7:H1-4 4098-9772 520 Hz 24 0.129 1.465 18.03N7:H1-5 4098-9772 520 Hz 26 0.129 1.671 17.83N7:H1-6 4098-9772 520 Hz 27 0.129 1.864 17.64N7:H1-7 4098-9772 520 Hz 24 0.129 2.016 17.48N7:H1-8 4098-9772 520 Hz 26 0.129 2.160 17.34N7:H1-9 4098-9772 520 Hz 34 0.129 2.322 17.18N7:H1-10 4098-9772 520 Hz 53 0.129 2.531 16.97N7:H1-11 4098-9772 520 Hz 24 0.129 2.607 16.89N7:H1-12 4098-9772 520 Hz 26 0.129 2.669 16.83N7:H1-13 4098-9772 520 Hz 32 0.129 2.720 16.78N7:H1-14 4098-9772 520 Hz 31 0.129 2.744 16.76

Totals: 446 Ft. 1.806A

N7:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.59%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN7:H2-1 4098-9772 520 Hz 63 0.129 0.649 18.85N7:H2-2 4098-9772 520 Hz 27 0.129 0.905 18.59N7:H2-3 4098-9772 520 Hz 21 0.129 1.088 18.41N7:H2-4 4098-9772 520 Hz 30 0.129 1.326 18.17N7:H2-5 4098-9772 520 Hz 22 0.129 1.483 18.02N7:H2-6 4098-9772 520 Hz 33 0.129 1.692 17.81N7:H2-7 4098-9772 520 Hz 28 0.129 1.847 17.65N7:H2-8 4098-9772 520 Hz 23 0.129 1.956 17.54N7:H2-9 4098-9772 520 Hz 29 0.129 2.071 17.43N7:H2-10 4098-9772 520 Hz 23 0.129 2.144 17.36N7:H2-11 4098-9772 520 Hz 23 0.129 2.199 17.30N7:H2-12 4098-9772 520 Hz 25 0.129 2.238 17.26N7:H2-13 4098-9772 520 Hz 27 0.129 2.260 17.24

Totals: 374 Ft. 1.677A

N7:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 9.72%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN7:H3-1 4098-9772 520 Hz 49 0.129 0.466 19.03N7:H3-2 4098-9772 520 Hz 33 0.129 0.753 18.75N7:H3-3 4098-9772 520 Hz 25 0.129 0.951 18.55N7:H3-4 4098-9772 520 Hz 30 0.129 1.165 18.33N7:H3-5 4098-9772 520 Hz 22 0.129 1.305 18.20N7:H3-6 4098-9772 520 Hz 26 0.129 1.449 18.05N7:H3-7 4098-9772 520 Hz 34 0.129 1.610 17.89N7:H3-8 4098-9772 520 Hz 28 0.129 1.721 17.78N7:H3-9 4098-9772 520 Hz 19 0.129 1.781 17.72N7:H3-10 4098-9772 520 Hz 25 0.129 1.841 17.66N7:H3-11 4098-9772 520 Hz 24 0.129 1.879 17.62N7:H3-12 4098-9772 520 Hz 21 0.129 1.895 17.60

Totals: 336 Ft. 1.548A

N7:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.58%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN7:H4-1 4098-9772 520 Hz 81 0.129 0.834 18.67N7:H4-2 4098-9772 520 Hz 35 0.129 1.167 18.33N7:H4-3 4098-9772 520 Hz 25 0.129 1.385 18.12N7:H4-4 4098-9772 520 Hz 39 0.129 1.693 17.81N7:H4-5 4098-9772 520 Hz 34 0.129 1.936 17.56N7:H4-6 4098-9772 520 Hz 25 0.129 2.094 17.41N7:H4-7 4098-9772 520 Hz 25 0.129 2.233 17.27N7:H4-8 4098-9772 520 Hz 25 0.129 2.352 17.15N7:H4-9 4098-9772 520 Hz 24 0.129 2.447 17.05N7:H4-10 4098-9772 520 Hz 27 0.129 2.532 16.97N7:H4-11 4098-9772 520 Hz 23 0.129 2.587 16.91N7:H4-12 4098-9772 520 Hz 25 0.129 2.626 16.87N7:H4-13 4098-9772 520 Hz 27 0.129 2.648 16.85

Totals: 415 Ft. 1.677A

Parkway Off Central NAC8 4009 NACStandby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC 0.0850 0.0850 0.1850 0.1850

Panel Totals 0.0850 0.1850

Notification Appliances

4098-9772 57 TRUEALARM 520HZ SOUNDER BASE W/ REMOTE LED * 520 H 0.0000 0.0000 0.1290 7.3530Peripheral Totals 0.0000 7.3530

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000

RUI Totals 0 0.0000 0.0000

Address Totals 0 Addresses 0.0000 0.0000System Totals*: Standby 0.0850 Alarm 7.5380

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current TotalSelect ALL Power Supplies on this battery set:

4009 0.0850 7.5380

Sub Total 0.0850 7.5380

Total 0.0850 7.5380

Standby Time = 24 Hrs x 0.0850 = 2.0400 Standby Ah

Alarm Time = 5 Min 0.08333 x 7.538 = 0.6282 Alarm Ah

2.6682Additional Spare Battery Capacity = 0% + 0.0000

2.6682Battery Discharge Factor = 20% + 0.5336Minimum Battery Required 2081-9272 6.2AH (2x) 3.2018

Battery Supplied 2081-9272 6.2AH (2x)* System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or powersupplies as shown above.

VOLTAGE DROP SUMMARYPlan

Circuit Description Load % DropN8:H1 4TH FLOOR-EAST-SW SIG1 1.806A 11.97%N8:H2 4TH FLOOR-EAST-SE SIG2 1.935A 13.05%N8:H3 4TH FLOOR-EAST-NW SIG3 1.677A 11.45%N8:H4 4TH FLOOR-EAST-NE SIG4 1.935A 14.88%

7.353A Total

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

N8:H1 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.97%Circuit Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN8:H1-1 4098-9772 520 Hz 39 0.129 0.432 19.07N8:H1-2 4098-9772 520 Hz 27 0.129 0.710 18.79N8:H1-3 4098-9772 520 Hz 29 0.129 0.986 18.51N8:H1-4 4098-9772 520 Hz 25 0.129 1.204 18.30N8:H1-5 4098-9772 520 Hz 22 0.129 1.378 18.12N8:H1-6 4098-9772 520 Hz 29 0.129 1.585 17.92N8:H1-7 4098-9772 520 Hz 24 0.129 1.737 17.76N8:H1-8 4098-9772 520 Hz 27 0.129 1.887 17.61N8:H1-9 4098-9772 520 Hz 23 0.129 1.996 17.50N8:H1-10 4098-9772 520 Hz 22 0.129 2.083 17.42N8:H1-11 4098-9772 520 Hz 29 0.129 2.175 17.33N8:H1-12 4098-9772 520 Hz 33 0.129 2.253 17.25N8:H1-13 4098-9772 520 Hz 34 0.129 2.307 17.19N8:H1-14 4098-9772 520 Hz 33 0.129 2.333 17.17

Totals: 396 Ft. 1.806A

N8:H2 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 13.05%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN8:H2-1 4098-9772 520 Hz 43 0.129 0.511 18.99N8:H2-2 4098-9772 520 Hz 22 0.129 0.755 18.75N8:H2-3 4098-9772 520 Hz 26 0.129 1.023 18.48N8:H2-4 4098-9772 520 Hz 25 0.129 1.260 18.24N8:H2-5 4098-9772 520 Hz 25 0.129 1.478 18.02N8:H2-6 4098-9772 520 Hz 24 0.129 1.668 17.83N8:H2-7 4098-9772 520 Hz 22 0.129 1.825 17.68N8:H2-8 4098-9772 520 Hz 29 0.129 2.009 17.49N8:H2-9 4098-9772 520 Hz 22 0.129 2.131 17.37N8:H2-10 4098-9772 520 Hz 24 0.129 2.245 17.26N8:H2-11 4098-9772 520 Hz 24 0.129 2.340 17.16N8:H2-12 4098-9772 520 Hz 30 0.129 2.435 17.07N8:H2-13 4098-9772 520 Hz 17 0.129 2.475 17.02N8:H2-14 4098-9772 520 Hz 27 0.129 2.518 16.98N8:H2-15 4098-9772 520 Hz 35 0.129 2.546 16.95

Totals: 395 Ft. 1.935A

N8:H3 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 11.45%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN8:H3-1 4098-9772 520 Hz 61 0.129 0.628 18.87N8:H3-2 4098-9772 520 Hz 30 0.129 0.913 18.59N8:H3-3 4098-9772 520 Hz 25 0.129 1.131 18.37N8:H3-4 4098-9772 520 Hz 25 0.129 1.329 18.17N8:H3-5 4098-9772 520 Hz 25 0.129 1.507 17.99N8:H3-6 4098-9772 520 Hz 27 0.129 1.678 17.82N8:H3-7 4098-9772 520 Hz 26 0.129 1.823 17.68N8:H3-8 4098-9772 520 Hz 25 0.129 1.941 17.56N8:H3-9 4098-9772 520 Hz 25 0.129 2.040 17.46N8:H3-10 4098-9772 520 Hz 24 0.129 2.116 17.38N8:H3-11 4098-9772 520 Hz 24 0.129 2.173 17.33N8:H3-12 4098-9772 520 Hz 25 0.129 2.213 17.29N8:H3-13 4098-9772 520 Hz 25 0.129 2.233 17.27

Totals: 367 Ft. 1.677A

N8:H4 Distributed Load Voltage Drop

Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75Á CelsiusWire Gauge: 14ga Min. Device Voltage: 16.vdc

Starting Voltage: 19.5vdc % Voltage Drop 14.88%Ckt Capacity 2.A

Normal Operation

Distance Device Voltage Voltage At

Device # PID Candela (Feet) Current Drop DeviceN8:H4-1 4098-9772 520 Hz 54 0.129 0.642 18.86N8:H4-2 4098-9772 520 Hz 20 0.129 0.863 18.64N8:H4-3 4098-9772 520 Hz 48 0.129 1.358 18.14N8:H4-4 4098-9772 520 Hz 18 0.129 1.529 17.97N8:H4-5 4098-9772 520 Hz 27 0.129 1.764 17.74N8:H4-6 4098-9772 520 Hz 33 0.129 2.025 17.47N8:H4-7 4098-9772 520 Hz 25 0.129 2.204 17.30N8:H4-8 4098-9772 520 Hz 23 0.129 2.349 17.15N8:H4-9 4098-9772 520 Hz 25 0.129 2.488 17.01N8:H4-10 4098-9772 520 Hz 28 0.129 2.621 16.88N8:H4-11 4098-9772 520 Hz 23 0.129 2.712 16.79N8:H4-12 4098-9772 520 Hz 25 0.129 2.791 16.71N8:H4-13 4098-9772 520 Hz 21 0.129 2.841 16.66N8:H4-14 4098-9772 520 Hz 27 0.129 2.884 16.62N8:H4-15 4098-9772 520 Hz 23 0.129 2.902 16.60

Totals: 420 Ft. 1.935ASHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-6

03.d

wg

9/13

/201

6 9:

52:3

8 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-604

CALCULATIONS AND

SCHEDULES

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

s:\1-current projects\7555-parkway off central\Fire\FA-603.dwg, FA-604 CALCULATIONS AND SCHEDULES, 9/13/2016 9:52:37 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 16: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-7

01.d

wg

9/13

/201

6 9:

52:4

1 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-701

WIRING TYPICALS

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

INSTRUCTIONS

66"

FLOOR

3 17/32"

6 29/32"

24"

1 7/16"

16"

FOR SURFACE MOUNTUSE 4 HOLES TO SECURE

BACKBOX TO WALL

BATTERY AREA(IF APPLICABLE)

NO CONDUIT ENTRY ORWIRING IN THIS AREA

SEECHART

5 17/32"

FIG. 1

11 11/16"

4 3/4"

(TYPICAL, FOR5 FOOT HEIGHTTO LCD DISPLAY

CENTERLINE)

TYPICAL CONDUIT LOCATION FORPWR. LIMITED FIELD WIRING

EXAMPLE OF ADDITIONALCABINET MOUNTING

LOCATION

CONDUIT FOR INTERNALPANEL HARNESSES OR NPLWIRING.

3 1/4" MIN.10" MAX.

1. FOR ADDITIONAL INFORMATION, DOWNLOAD DATA SHEET S4100-0100 FROM HTTP://WWW.SIMPLEX-FIRE.COM

4100es BACKBOX INSTALLATION

BATTERY BOX HEIGHT REFERENCE

PID NUMBER BOX HEIGHT BOX LENGTH BOX DEPTH

2081-9280 1'-0" 2'-2 1/2" 1'-0"

4081-9306 1'-1 1/2" 2'-3 7/8" 1'-2 5/8"

4081-9308 1'-1 1/2" 2'-3 7/8" 1'-2 5/8"

WALL STUD GUIDES(SEE NOTE 3)

KNOCKOUT SCREW/NAILHOLES FOR SEMI-FLUSH

MOUNT (SEE NOTE 3)

REFER TO FIG.1 FOR TYPICAL CONDUITPENETRATION LOCATIONS

WALL

1. REMOVE ELECTRONIC CARD CAGE (IF PRESENT) AND STORE IT IN A SAFE DRY AREA.2. NO KNOCKOUTS PROVIDED. CUT CONDUIT/SERVICE ENTRANCE OPENINGS. REFER TO FIG.1

FOR PROPER LOCATIONS. CONDUIT PROTRUSION INTO BOX 1/2" MAX.3. MOUNT BOX TO WALL: BOX MUST BE LEVEL AND PLUMB. FOR SURFACE MOUNT USE TEAR

DROP AND CLEARANCE HOLES ON BACK SURFACE. FOR SEMI-FLUSH MOUNT: USE WALL STUDGUIDES FOR MAXIMUM ALLOWABLE BOX DEPTH TO PROVIDE OPEN DOOR CLEARANCE. USEKNOCKOUTS ON SIDE WALL, SCREW OR NAIL BOX TO WALL STUDS.

4. MINIMUM DISTANCE BETWEEN ANY TWO BOXES IS 3 1/4" (6" MAXIMUM).5. IF PRESENT, USE WIRE MANAGEMENT BRACKETS ON BOX SIDES TO SECURE WIRE RUNS.6. NEMA RATING: NEMA 1 - GENERAL PURPOSE.7. DO NOT LOCATE POWER-LIMITED WIRING IN THE SHADED AREAS OF THE BACKBOX, THIS

AREA IS RESERVED FOR NON-POWER LIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES ANDCITY CONNECTION.

8. REFER TO SIMPLEX BACKBOX INSTALLATION DOCUMENT 579-117 FOR DETAILEDINSTRUCTIONS.

BACKBOX AND DOOR OPTIONS

PKG. SIZEBOX W/

GLASS DOORBOX W/

SOLID DOORBOX ONLY

GLASSDOOR

SOLIDDOOR

BOXHEIGHT

1 BAY RED 2975-9441 2975-9447 2975-9407 4100-2124 4100-2134 22"

2 BAY RED 2975-9442 2975-9448 2975-9408 4100-2125 4100-2135 40"

3 BAY RED 2975-9443 2975-9449 2975-9409 4100-2126 4100-2136 56"

1 BAY PLATINUM 2975-9444 2975-9450 2975-9438 4100-2104 4100-2114 22"

2 BAY PLATINUM 2975-9445 2975-9451 2975-9439 4100-2105 4100-2115 40"

3 BAY PLATINUM 2975-9446 2975-9452 2975-9440 4100-2106 4100-2116 56"

1

3

REDRED2

RED1

5

GLDREDVLT4.7K YEL

GLDREDGRY6.8K BLU

GLDREDGRY1.8K BRN

GLDBRNBLU560 Ω GRN

GLDREDRED1.2K BRN

GLDORGBLK10K BRN

GLDBLKBLK20 Ω RED

GLDREDBLK1K BRN

GLDBRNBLKBRNGLDORGRED22K REDBRNWHTWHT4.99K YEL

GLDREDYEL2.4K RED

GLDREDGRN1.5K BRN

GLDYELGRN150K BRNGLDREDWHT3.9K ORGGLDORGBLK10K BRN

733-893

733-892

733-896

733-886

733-984

733-890

733-891

733-894

733-912

733-973

733-974733-985734-086

734-092

734-093

734-149734-171734-168

4081-9001

MODEL

4081-9002

4081-9003

4081-9004

4081-9005

4081-9006

4081-9007

4081-9008

4081-9009

4081-9010

4081-90114081-90124081-9013

4081-9014

4081-9015

4081-90164081-90174081-9018

1

1/2

1/2

1/2

1/2

1

1

1/2

1

1

1/21/21/2

1/2

1/2

1/211

4

GLD

GLD

REDORG3.3K ORG

2.2K

OHMS

BRN

N/A

N/A

N/AN/AN/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/AN/A

ANNUNCIATOR (4300)

GLDREDRED8.2K GRAYGLDREDBLU5.6K GRNGLDORGRED12K BRN

378-090378-046378-069

1/21/21/2

N/AN/AN/A

END OF LINE RESISTOR CODES

N.O. INITIATING PULL, SMOKE,HEAT, WATERFLOW, TAMPER,

ETC.24 PT. I/O SWITCH SUPV.

N.O. INITIATING PULL,SMOKE, HEAT,

WATERFLOW, TAMPER,ETC.

CURRENT LIMITED N.O.INITIATING (IN LINE)

N.C. INITIATING (EOLR)

N.C. INITIATING (EOLR)

NOTIFICATION

24 PT. I/O (ACROSS CONTACTS)N.C. INIT. (ACROSS CONTACTS)

TO MR-101 RELAY COIL

CURRENT LIMITED N.O. INIT.(IN SERIES WITH CONTACT)

ANNUNCIATOR (N2)

SPEAKER CIRCUIT

N.C. INITIATING (SECURITYMONITORING EOLR)

CURRENT LIMITED N.O. INIT.(SECURITY MONITORING EOLR)

70VRMS CONSTANT SUPV. NACSSECURITY MONITORING (EOLR)N.O. SECURITY MON. (SERIES)N.C. SECURITY MON. (SHUNT) 4100, 4100U

4100, 4100U4100, 4100U4100-1260

4090-9001 IDNET IAM

4090-9001 IDNET IAM

40034006, 4008, 4010

4090-9001 IDNET IAM

4605-7401, 4100 SERIES4005*,4090-9001 IDNET IAM

4005 8 POINT I/O

4004, 4005, 4006, 4008, 4009,4010, 4100, 4100U

4005

4005*, 4090-9001 IDNET IAM4100, 4100U

4090-9001 IDNET IAM

4-20MA ZAM (TROUBLE)

4004, 4005, 4090-9001IDNET IAM 2190-9173

MAPNETII 2 PT I/O

2080-90244090-9001 IDNET IAM (EOLR)

4605-7401, 4100 SERIES

4004*, 4004R, 4005*, 4006,4100, 4120, 4100U, ZAMs

4004, 4010 (TROUBLE)

FIRE ALARM PANEL/MODULECIRCUIT TYPEWATTS

100 Ω

REFERENCE

NUMBER

CURRENT LIMITED N.O. INIT.NOTIFICATION (DACT)

NOTE: REFER TO PANEL/MODULE AND DEVICE INSTALLATIONINSTRUCTIONS FOR PROPER TERMINATIONS.

* USE WITH RETROFIT OR HIGH CURRENT MODULE

BAND NUMBER

3

4603-9101 REMOTE ANNUNCIATOR

MOUNTING OPTION "A"

ELECTRICAL BOX

1. MAINTAIN CORRECT POLARITY ONTERMINAL CONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECUREUNDER TERMINALS. NEVER LOOP WIRESUNDER TERMINALS.

3. ONE INDICATOR MAY BE INSTALLED PERDETECTOR.

WIRING NOTES

TERMINATION VIEW

ON

OFF

MOUNTING OPTIONS

OPTION

1

BACK BOX SPECIFICATION NOTES

A FLUSH MOUNT - 6-GANG BOX, 3-1/2" (89mm) DEEP BY OTHERS

B FLUSH MOUNT - MASONRY BOX, 3-1/2" (89mm) DEEP BY OTHERS

C SURFACE MOUNT - SIMPLEX 2975-9206, 2-3/4" (70mm) DEEP ORDERED SEPARATELY

1. FOR ADDITIONAL INFORMATION, DOWNLOAD DATA SHEET 4603-0001 FROM HTTP://WWW.SIMPLEX-FIRE.COM2. REFER TO RUI DIPSWITCH SETTINGS DETAIL

LCD ANNUNCIATORASSEMBLY

TRIM PLATE

TB1

TB2++ - -

++-- SS

FROM 24VDCPOWER SOURCE

TO ADDITIONAL24VDC DEVICES

RUI FROM FACP ORPREVIOUS DEVICE

RUI TO NEXT DEVICE OR RETURNTO FACP IN CLASS A SYSTEM

SHIELD (NOT REQUIRED ONRUI+ APPLICATIONS)

RUI ADDRESSDIPSWITCH2

4

IDNET CONTROL4009 NAC PANEL WIRING

ASSY 0565-771 A B C DADDRESSABLE NAC SYSTEM

A-

IDNET

HARDWIRE

4009-9201 IDNet NAC EXTENDER

HARDWIREINPUT 2AUDIBLE

INPUT 1VISIBLE

RET OUTRET INPOS OUT

RET OUT

POS OUT

POS IN

RET IN

BATTERY+ -

NAC 4

AUX POWER

POS IN

+

-

NAC 1-+

NAC 2 NAC 3

HARDWARE ADDRESS/ CONFIG SOFTWARE

5

7

6

4

3

2

1

8SW18

1

2

3

4

6

7

5

ON

SW2

ON

SHLD

SHLD A+B- B+

TERMINALSTRIP PARTOF 733-991

CONNECT TO 120VAC 60HZ INPUT 3A MAX.NEUTRAL

HOT 120V

NEU

T120V

HARNESS 733-991

GROUND

4009-9807 FOUR POINT NAC MODULE

NAC 5

565-828NAC 8NAC 6 NAC 7

BATTERY BATTERY

HARNESS 733-945INTERNAL BATTERY

-+ -+ -+

-+ -+ -+ -+

V

V

V

V

V

V

V

V

M

M

(OPTIONAL)

TO NAC#:V8 DEVICES

TO NAC#:V7 DEVICES

TO NAC#:V6 DEVICES

TO NAC#:V5 DEVICESTO NAC#:V4 DEVICES

TO NAC#:V3 DEVICES

TO NAC#:V2 DEVICES

TO NAC#:V1 DEVICES

TO ADDITIONAL IDNet DEVICES OR RETURNTO HOST IDNet CONTROL PANEL

FROM PREVIOUS IDNet DEVICESOR HOST IDNet CONTROL PANEL

CONNECT A 12 AWG COPPER GROUND WIRE FROM SAFETYGROUND IN THE ELECTRICAL DISTRIBUTION PANEL TOTHE 4009 SAFETY GROUND STUD.

1. IF IDNet WIRING CONTINUES ON TO ANOTHER DEVICE,TAPE SHIELDS TOGETHER.

2. IF IDNet WIRING TERMINATES AT THE 4009 IDNet NACEXTENDER, TAPE SHIELD.

3. NEVER TERMINATE SHIELDS AT THE 4009 IDNet NACEXTENDER

WIRING NOTES

IF OPTIONAL SHIELDS ARE USED FOR IDNet WIRING, FOLLOWTHESE PRECAUTIONS:

2

CLASS B WIRING

1. MAINTAIN CORRECT POLARITY ON TERMINALCONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECURE UNDERTERMINALS. NEVER LOOP WIRES UNDER TERMINALS.

3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJAPPROVED METHODS.

WIRING NOTES

MOUNTING OPTIONS

OPTION

1

BACK BOX SPECIFICATION NOTES

A SINGLE GANG BOX, 2-1/2" (64mm) DEEP BY OTHERS

B4" (102mm) SQUARE BOX, 2-1/8" DEEP (MIN)W/ SINGLE GANG COVER PLATE 3/4" (19mm) EXTENSION BY OTHERS

C5H x 3-7/8"W x 2-3/16"D(127mm x 98mm x 56mm) SIMPLEX 2975-9022, ORDERED SEPARATELY

D5-3/4"H x 3-7/8"W x 2-3/16"D(132mm x 102mm x 56mm) SIMPLEX 2975-9178, ORDERED SEPARATELY

TOP OF PULL HANDLETO BE MOUNTED AT 42"

- 48" A.F.F.

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4099-0005 FROM HTTP://WWW.SIMPLEX-FIRE.COM

ALARMFIRE

PULL DOWN

12

34

IDNet SLC(-)

(+)

(-)

(+)

4099 SERIES IDNET PULL STATIONS

(-) (+)

OPTIONAL TAPLOCATION FOR

IDNet SLC

12

34

T-TAP(SPLICE)CONNECTION

SERIESCONNECTION

IDNet SLC

TERMINATION VIEW: DEVICE REAR

4099-9005BREAKGLASS

4099-9006PUSH

WITH 2099-9828INSTITUTIONAL

COVER KIT

4099-9004SINGLE ACTION

4099-9021NO GRIP

SINGLE ACTION

4099-9805NO GRIP

RETROFIT KIT

MOUNTING OPTION "B"

5

CLASS B WIRING

1. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS.2. ALWAYS CUT CONDUCTORS AND SECURE UNDER TERMINALS.

NEVER LOOP WIRES UNDER TERMINALS.3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ APPROVED

METHODS.

WIRING NOTES

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4098-0019 FROM HTTP://WWW.SIMPLEX-FIRE.COM

IDNet SLC(-)

(+)

(-)

(+)

4098-9792 STANDARD SENSOR BASE

(-) (+)

OPTIONAL TAPLOCATION FOR

IDNet SLC

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

IDNet SLC

TERMINATION VIEW: DEVICE REARSENSOR BASE

SMOKE SENSOR

HEAT SENSOR

4"(102mm)

3' (941mm)MINIMUM

CEILING MOUNTEDSENSOR

HEAT SENSORSNEVER HERE

12"(305mm)MAXIMUM

FINISHEDWALL

WALL MOUNTEDSENSOR

4"(102mm)

3' (941mm)MINIMUM

CEILING MOUNTEDSENSOR

HEAT SENSORSNEVER HERE

12"(305mm)MAXIMUM

FINISHED WALL

WALL MOUNTEDSENSOR

MOUNTING OPTION "B"

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A SINGLE GANG BOX, 2-1/2" (64mm) DEEP BY OTHERS

B4" (102mm) SQUARE BOX, 1-1/2" (38mm) DEEP MINIMUMW/ SINGLE ADAPTER BRACKET

BY OTHERS

C 4" (102mm) OCTAGONAL BOX, 1-1/2" (38mm) DEEP, MINIMUM BY OTHERS

DADAPTER PLATE KIT (FOR 4" SQUARE/OCTAGONAL SURFACE MOUNTEDELECTRICAL BOX)

SIMPLEX 4098-9832 ORDEREDSEPARATELY

6

CLASS B WIRING

1. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS.2. ALWAYS CUT CONDUCTORS AND SECURE UNDER TERMINALS.

NEVER LOOP WIRES UNDER TERMINALS.3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ

APPROVED METHODS.

WIRING NOTES

(-)

(+)

(-)

(-) (+)

OPTIONAL TAPLOCATION FOR

IDNet SLC

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

TERMINATION VIEW: DEVICE REAR

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A SINGLE GANG BOX, 2-1/2" (64mm) DEEP BY OTHERS

B4" (102mm) SQUARE BOX, 2-1/8" DEEP (MIN)W/ SINGLE GANG COVER PLATE 3/4" (19mm) EXTENSION BY OTHERS

CADAPTER PLATE KIT (FOR 4" SQUARE/OCTAGONAL SURFACE MOUNTEDELECTRICAL BOX)

SIMPLEX 4098-9832 ORDEREDSEPARATELY

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4098-0054 FROM HTTP://WWW.SIMPLEX-FIRE.COM

(+)

(-)24V or NAC

(+)

SMOKE SENSOR

HEAT SENSOR

4"(102mm)

3' (941mm)MINIMUM

CEILING MOUNTEDSENSOR

HEAT SENSORSNEVER HERE

12"(305mm)MAXIMUM

FINISHEDWALL

WALL MOUNTEDSENSOR

4"(102mm)

3' (941mm)MINIMUM

CEILING MOUNTEDSENSOR

HEAT SENSORSNEVER HERE

12"(305mm)MAXIMUM

FINISHED WALL

WALL MOUNTEDSENSOR

4098-9772 SENSOR BASE WITH 520Hz SOUNDER

IDNet SLC(+)

OPTIONAL TAPLOCATION FOR

IDNet SLC

IDNet SLC

24V or NAC(-)

(+)

REMOTE LED(-)

SOUNDER BASE

MOUNTING OPTION "B"

7

0=OFF1=ON

241

242

244

245

243

240

247

248

250

251

249

253

254

255

252

246

193

194

196

197

195

209

210

211

212

213

192 208

145

146

148

149

147

161

162

163

164

165

144 160 176

177

178

179

180

181

199

200

202

203

201

215

216

217

218

219

205

206

207

221

222

223

204 220

151

152

154

155

153

167

168

169

170

171

157

158

159

173

174

175

156 172

183

184

185

186

187

188

189

190

191

150 166 182 198 214

224

225

226

227

228

229

230

231

232

233

234

235

236

237

238

239

1286432

7 86

842

42 3 5

16

ADDRESS SHOWN ABOVE IS 120

1ON

1OFF

129

130

132

133

131

97

98

100

101

99

113

114

115

116

117

96 112 128

81

82

84

85

83

49

50

52

53

51

65

66

67

68

69

48 64 80

135

136

139

138

137

103

104

106

107

105

119

120

121

122

123

142

141

143

109

110

111

125

126

127

108 124 140

87

88

91

90

89

55

56

58

59

57

71

72

73

74

75

94

93

95

61

62

63

77

78

79

60 76 92

54 70 86 102 118 134

33

34

36

37

35

1

2

4

5

3

17

18

19

20

21

0 16 32

39

40

43

42

41

7

8

10

11

9

23

24

25

26

27

46

45

47

13

14

15

29

30

31

12 28 44

6 22 38

DIP SWITCHES 5 THRU 8

DO NOT USE ADDRESS 0 FOR AN IDNET ADDRESS

9

NOTE:THE 4098-9771, -9794, -9795, -9798 SOUNDER BASES HAVE A 9-POSITION DIP SWITCH. THE FIRST EIGHT DIP SWITCHES SETTHE SOUNDER BASE ADDRESS. DIP SWITCH POSITION 9 IS SET TO OFF OR ON DEPENDING UPON THE SOUNDER BASE POWERSOURCE. WHEN THE SOUNDER BASE IS CONNECTED TO A 24 VDC POWER SOURCE, DIP SWITCH POSITION 9 IS SET TO “OFF”AND THE 24 VDC POWER IS SUPERVISED BY THE SOUNDER BASE. WHEN THE SOUNDER BASE IS POWERED BY THE PANEL’SNOTIFICATION APPLIANCE CIRCUIT (NAC), DIP SWITCH POSITION 9 IS SET TO “ON” AND THE POWER IS SUPERVISED BY THE NACAND NOT THE SOUNDER BASE. THE 4098-9770 AND -9797 BASES HAVE THE SAME LAYOUT, BUT DOESN’T OFFER SOUNDERFUNCTIONALITY. THEY USE AN 8-WAY DIP SWITCH ONLY.

IDNet DIP SWITCH SETTINGS

SEENOTE

DIPSWITCHES1 THRU 4

8

s:\1-current projects\7555-parkway off central\Fire\FA-701.dwg, FA-701 WIRING TYPICALS, 9/13/2016 9:52:40 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

AutoCAD SHX Text
15A
AutoCAD SHX Text
+
AutoCAD SHX Text
-
AutoCAD SHX Text
+
AutoCAD SHX Text
-
AutoCAD SHX Text
PUSH
AutoCAD SHX Text
KEY
AutoCAD SHX Text
OPERATED
AutoCAD SHX Text
ONLY
AutoCAD SHX Text
KEY
AutoCAD SHX Text
OPERATED
AutoCAD SHX Text
ONLY
AutoCAD SHX Text
SIDE WALL
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
DEVICE MOUNTING HEIGHT REFERENCE (PER NFPA 72)
AutoCAD SHX Text
12" (MAX)
AutoCAD SHX Text
4"
AutoCAD SHX Text
OR RETURN
AutoCAD SHX Text
DIFFUSER
AutoCAD SHX Text
3' (MIN)
AutoCAD SHX Text
AUDIBLE/VISUAL
AutoCAD SHX Text
& VISUAL ONLY
AutoCAD SHX Text
APPLIANCES
AutoCAD SHX Text
MANUAL
AutoCAD SHX Text
PULL
AutoCAD SHX Text
STATION
AutoCAD SHX Text
FINISHED
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
FINISHED
AutoCAD SHX Text
WALL
AutoCAD SHX Text
4"
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
PHONE
AutoCAD SHX Text
JACK
AutoCAD SHX Text
MAGNETIC
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
HOLDER
AutoCAD SHX Text
ACCEPTED HERE
AutoCAD SHX Text
WALL MOUNTED
AutoCAD SHX Text
SMOKE/HEAT
AutoCAD SHX Text
DETECTOR
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
SMOKE/HEAT
AutoCAD SHX Text
DETECTOR
AutoCAD SHX Text
NOTE: MEASUREMENTS
AutoCAD SHX Text
SHOWN ARE TO THE
AutoCAD SHX Text
CLOSEST EDGE OF THE
AutoCAD SHX Text
42" MIN (NFPA)
AutoCAD SHX Text
48" MAX (ADA)
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
WIDTH
AutoCAD SHX Text
5' (MAX.)
AutoCAD SHX Text
80" MIN (NFPA)
AutoCAD SHX Text
SYNCHRONIZE %%UMORE%%U THAN
AutoCAD SHX Text
TWO APPLIANCES IN ANY
AutoCAD SHX Text
FIELD OF VIEW.
AutoCAD SHX Text
DETECTOR.
AutoCAD SHX Text
LESS 3"
AutoCAD SHX Text
5"
AutoCAD SHX Text
TO EXIT DOOR
AutoCAD SHX Text
80" MIN (ADA)
AutoCAD SHX Text
A/C SUPPLY
AutoCAD SHX Text
(914mm MIN)
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
SIMPLEX
AutoCAD SHX Text
(102mm)
AutoCAD SHX Text
(102mm)
AutoCAD SHX Text
(305mm MAX)
AutoCAD SHX Text
(76mm)
AutoCAD SHX Text
(127mm)
AutoCAD SHX Text
(1524mm)
AutoCAD SHX Text
(1067mm MIN)
AutoCAD SHX Text
(1219mm)
AutoCAD SHX Text
(2032mm MIN)
AutoCAD SHX Text
(2032mm MIN)
AutoCAD SHX Text
REF. 80" MIN (IBC)
AutoCAD SHX Text
(2032mm MIN)
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
REF. 96" MAX (IBC)
AutoCAD SHX Text
(2440mm MAX)
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
96" MAX (NFPA, ADA)
AutoCAD SHX Text
(2440mm MAX)
AutoCAD SHX Text
%%UNOTE:%%U REFER TO THE PROPER DEVICE
AutoCAD SHX Text
FOR BACKBOX MOUNTING HEIGHT.
AutoCAD SHX Text
INSTALLATION INSTRUCTIONS
AutoCAD SHX Text
VISUAL APPLIANCE MOUNTING HEIGHT CONSIDERATIONS IN SLEEPING ROOMS 1.MIN DISTANCE IN SLEEPING ROOMS IS 24" (610mm) FROM CEILING TO MIN DISTANCE IN SLEEPING ROOMS IS 24" (610mm) FROM CEILING TO TOP OF LENS FOR 110CD STROBES WITHIN 16' OF THE PILLOW 2.177CD STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" 177CD STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" (610mm) MINIMUM DISTANCE FROM THE CEILING. THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER.
AutoCAD SHX Text
FOR CEILING HEIGHTS LESS THAN 86" (2180mm),
AutoCAD SHX Text
THE VISUAL LENS MOUNTING HEIGHT SHALL BE
AutoCAD SHX Text
WITHIN 6" (150mm) OF THE CEILING.
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
AUDIBLE ONLY
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
90" MIN (2286mm MIN)
AutoCAD SHX Text
BELOW FINISHED CEILING
AutoCAD SHX Text
6" MIN (152.4mm MIN)
AutoCAD SHX Text
NFPA 72 AUDIBLE APPLIANCE
AutoCAD SHX Text
(OTHER MOUNTING HEIGHTS SHALL BE
AutoCAD SHX Text
PERMITTED BY THE AHJ PROVIDING IT
AutoCAD SHX Text
MEETS THE SOUND LEVEL OUTPUT REQUIRED.)
AutoCAD SHX Text
BEEN REMOVED FROM THE 2010 EDITION OF NFPA 72
AutoCAD SHX Text
THE 4" REQUIREMENT FOR SMOKE DETECTORS HAS
AutoCAD SHX Text
HEAT DETECTORS
AutoCAD SHX Text
NEVER HERE
AutoCAD SHX Text
48" MAX (NFPA, ADA)
AutoCAD SHX Text
(1219mm MAX)
AutoCAD SHX Text
MEASUREMENTS SHOWN ARE
AutoCAD SHX Text
TO TOP OF PULL HANDLE
AutoCAD SHX Text
TO TOP OF LENS
AutoCAD SHX Text
TO BOTTOM OF LENS
Page 17: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

SHEET:

DRAWN BY:CHECKED BY:

JOB #:PROJECT #:

DE

SC

RIP

TIO

NC

AD

DA

TE

MA

RK

SYSTEM:

CH

K

ISSUE DATE:

30"

x 42

" -

Arch

E1

Size

TM

Safer. S

marter. T

yco.

ISSU

E LO

G:

Revi

sion

s sh

own

wit

h #

sy

mbo

l

LAST

PRI

NTE

D:

LAST

SAV

ED B

Y:

IMPO

RTAN

T N

OTI

CE T

O U

SER:

By

acce

ptin

g or

usi

ng t

his

draw

ing

and/

or t

he in

form

atio

n co

ntai

ned

here

in,

the

user

agr

ees

to t

he f

ollo

win

g te

rms

and

cond

itio

ns:

The

ele

ctro

nic

info

rmat

ion

in t

he d

raw

ing

may

be

subj

ect

to in

tent

iona

l or

unin

tent

iona

l alt

erat

ion.

Any

use

, re

use,

cop

ying

mod

ific

atio

n or

alt

erat

ion

of t

he in

form

atio

n co

ntai

ned

here

in s

hall

be a

t th

e so

le r

isk

of t

he u

ser.

Thi

s in

form

atio

n m

ay n

ot b

e so

ld o

r tr

ansf

erre

d to

any

thi

rd p

arty

, us

ed o

n ot

her

proj

ects

or

addi

tion

s to

the

pro

ject

for

whi

ch it

was

pre

pare

d, o

r us

ed f

or c

ompl

etio

n of

thi

s pr

ojec

t by

any

thi

rd p

arty

. S

impl

exG

rinn

ell d

iscl

aim

s al

l lia

bilit

y fo

r th

e us

e or

reu

se o

fal

tere

d fi

les

by t

he u

ser

or a

ny t

hird

par

ty a

nd s

uch

use

will

be

a us

er's

sole

ris

k. U

ser

shal

l, t

o th

e fu

llest

ext

ent

perm

itte

d by

law

, de

fend

, in

dem

nify

, an

d ho

ld S

impl

exG

rinn

ell h

arm

less

fro

m a

ny a

nd a

ll cl

aim

s fo

r lo

ss,

dam

age

or in

jury

ari

sing

dir

ectl

y or

indi

rect

ly t

here

from

.

FILE

PAT

H:

s:\1

-cur

rent

pro

ject

s\75

55-p

arkw

ay o

ff c

entr

al\F

ire\

FA-7

01.d

wg

9/13

/201

6 9:

52:4

2 AM

DTH

URS

TON

337:994941601

G. CERRICHIO

D. THURSTON

9/7/16

FIRE ALARM SYSTEM

PA

RK

WA

Y O

FF

C

EN

TR

AL

9436 U

LY

SS

ES

S

TR

EE

T N

E

BLA

IN

E, M

N 55434

5400

NAT

HAN

LAN

E, S

UIT

E 10

0PL

YMO

UTH

, M

N 5

5442

PHO

NE:

7

63-3

67-5

000

SERV

ICE:

763

-367

-500

1FA

X:

763

-367

-500

2

337445916

DIS

TR

IC

T - 337

FA-702

WIRING TYPICALS

TYCO SIMPLEXGRINNELL © 2016

7555

PA

RK

WA

Y O

FF

C

EN

TR

AL

3

REDRED2

RED1

5

GLDREDVLT4.7K YEL

GLDREDGRY6.8K BLU

GLDREDGRY1.8K BRN

GLDBRNBLU560 Ω GRN

GLDREDRED1.2K BRN

GLDORGBLK10K BRN

GLDBLKBLK20 Ω RED

GLDREDBLK1K BRN

GLDBRNBLKBRNGLDORGRED22K REDBRNWHTWHT4.99K YEL

GLDREDYEL2.4K RED

GLDREDGRN1.5K BRN

GLDYELGRN150K BRNGLDREDWHT3.9K ORGGLDORGBLK10K BRN

733-893

733-892

733-896

733-886

733-984

733-890

733-891

733-894

733-912

733-973

733-974733-985734-086

734-092

734-093

734-149734-171734-168

4081-9001

MODEL

4081-9002

4081-9003

4081-9004

4081-9005

4081-9006

4081-9007

4081-9008

4081-9009

4081-9010

4081-90114081-90124081-9013

4081-9014

4081-9015

4081-90164081-90174081-9018

1

1/2

1/2

1/2

1/2

1

1

1/2

1

1

1/21/21/2

1/2

1/2

1/211

4

GLD

GLD

REDORG3.3K ORG

2.2K

OHMS

BRN

N/A

N/A

N/AN/AN/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/AN/A

ANNUNCIATOR (4300)

GLDREDRED8.2K GRAYGLDREDBLU5.6K GRNGLDORGRED12K BRN

378-090378-046378-069

1/21/21/2

N/AN/AN/A

END OF LINE RESISTOR CODES

N.O. INITIATING PULL, SMOKE,HEAT, WATERFLOW, TAMPER,

ETC.24 PT. I/O SWITCH SUPV.

N.O. INITIATING PULL,SMOKE, HEAT,

WATERFLOW, TAMPER,ETC.

CURRENT LIMITED N.O.INITIATING (IN LINE)

N.C. INITIATING (EOLR)

N.C. INITIATING (EOLR)

NOTIFICATION

24 PT. I/O (ACROSS CONTACTS)N.C. INIT. (ACROSS CONTACTS)

TO MR-101 RELAY COIL

CURRENT LIMITED N.O. INIT.(IN SERIES WITH CONTACT)

ANNUNCIATOR (N2)

SPEAKER CIRCUIT

N.C. INITIATING (SECURITYMONITORING EOLR)

CURRENT LIMITED N.O. INIT.(SECURITY MONITORING EOLR)

70VRMS CONSTANT SUPV. NACSSECURITY MONITORING (EOLR)N.O. SECURITY MON. (SERIES)N.C. SECURITY MON. (SHUNT) 4100, 4100U

4100, 4100U4100, 4100U4100-1260

4090-9001 IDNET IAM

4090-9001 IDNET IAM

40034006, 4008, 4010

4090-9001 IDNET IAM

4605-7401, 4100 SERIES4005*,4090-9001 IDNET IAM

4005 8 POINT I/O

4004, 4005, 4006, 4008, 4009,4010, 4100, 4100U

4005

4005*, 4090-9001 IDNET IAM4100, 4100U

4090-9001 IDNET IAM

4-20MA ZAM (TROUBLE)

4004, 4005, 4090-9001IDNET IAM 2190-9173

MAPNETII 2 PT I/O

2080-90244090-9001 IDNET IAM (EOLR)

4605-7401, 4100 SERIES

4004*, 4004R, 4005*, 4006,4100, 4120, 4100U, ZAMs

4004, 4010 (TROUBLE)

FIRE ALARM PANEL/MODULECIRCUIT TYPEWATTS

100 Ω

REFERENCE

NUMBER

CURRENT LIMITED N.O. INIT.NOTIFICATION (DACT)

NOTE: REFER TO PANEL/MODULE AND DEVICE INSTALLATIONINSTRUCTIONS FOR PROPER TERMINATIONS.

* USE WITH RETROFIT OR HIGH CURRENT MODULE

BAND NUMBER

3

CLASS B WIRING

1. MAINTAIN CORRECT POLARITY ON TERMINALCONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECURE UNDERTERMINALS. NEVER LOOP WIRES UNDER TERMINALS.

3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJAPPROVED METHODS.

WIRING NOTES

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A SINGLE GANG BOX, 2-1/2" (64mm) DEEP WITH SINGLE GANG COVER PLATE BY OTHERS

BSINGLE GANG BOX, 2-1/2" (64mm) DEEP WITH SIMPLEX 4090-9810 IAMMOUNTING BRACKET AND SIMPLEX 4090-9806 TRIM PLATE FOR SEMI-FLUSHMOUNTED BOX

BOX BY OTHERS, PLATES ORDEREDSEPARATELY

CSINGLE GANG BOX, 2-1/2" (64mm) DEEP WITH SIMPLEX 4090-9810 IAMMOUNTING BRACKET AND SIMPLEX 4090-9807 TRIM PLATE FOR SURFACEMOUNTED BOX

BOX BY OTHERS, PLATES ORDEREDSEPARATELY

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4090-0001 FROM HTTP://WWW.SIMPLEX-FIRE.COM2. OR EQUIVALENT EQUIPMENT

12

34

IDNet SLC(-)

(+)

(-)

(+)

4090-9001 ADDRESSABLE INPUT MODULE (IAM)

(-) (+)

OPTIONAL TAPLOCATION FOR

IDNet SLC

12

34

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

IDNet SLC

TERMINATION VIEW: DEVICE REAR

733-896(4.7K 1/2W)

733-886(6.8K 1/2W)

733-984(1.8K 1/2W)

SINGLE GANG ELECTRICAL BOX2-1/2" DEEP

MOUNTING OPTION "B"

IAM MOUNTING BRACKET

4090-9001 IAM

TRIM PLATE

1

CLASS B / STYLE 4 WIRING

1. MAINTAIN CORRECT POLARITY ON TERMINALCONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECURE UNDERTERMINALS. NEVER LOOP WIRES UNDER TERMINALS.

3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJAPPROVED METHODS.

WIRING NOTES

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH DOUBLE GANG COVERPLATE.

BY OTHERS

B4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9801TRIM PLATE FOR SEMI-FLUSH MOUNTED BOX

BOX BY OTHERS, PLATESORDERED SEPARATELY

C4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9802TRIM PLATE FOR SURFACE MOUNTED BOX

BOX BY OTHERS, PLATESORDERED SEPARATELY

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4090-0002 FROM HTTP://WWW.SIMPLEX-FIRE.COM

IDNet SLC(-)

(+)

(-)

(+)

4090-9002 ADDRESSABLE RELAY MODULE

(+) (-)

OPTIONAL TAPLOCATION FOR

IDNet SLC

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

IDNet SLC

TERMINATION VIEW

N.C.

1 2 3 4

5 6 7 8

1 2 3 4

5 6 7 8

1 2 3 4

5 6 7 8

1 2 3 4

5 6 7 8

C N.O.

TO CONTROLLEDDEVICE. SEE DATASHEET FOR POWER

RATINGLIMITATIONS.

MOUNTING OPTION "B"

4"(102mm) SQUARE BOX

4090-9002 RELAY IAM

COVER PLATE

CLASS B / STYLE 4 WIRING

1. MAINTAIN CORRECT POLARITY ON TERMINALCONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECURE UNDERTERMINALS. NEVER LOOP WIRES UNDER TERMINALS.

3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJAPPROVED METHODS.

WIRING NOTES

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH DOUBLE GANG COVERPLATE.

BY OTHERS

B4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9801TRIM PLATE FOR SEMI-FLUSH MOUNTED BOX

BOX BY OTHERS, PLATESORDERED SEPARATELY

C4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9802TRIM PLATE FOR SURFACE MOUNTED BOX

BOX BY OTHERS, PLATESORDERED SEPARATELY

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4090-0002 FROM HTTP://WWW.SIMPLEX-FIRE.COM

IDNet SLC(-)

(+)

(-)

(+)

4090-9002 ADDRESSABLE RELAY MODULE

(+) (-)

OPTIONAL TAPLOCATION FOR

IDNet SLC

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

IDNet SLC

TERMINATION VIEW

N.C.

1 2 3 4

5 6 7 8

1 2 3 4

5 6 7 8

1 2 3 4

5 6 7 8

1 2 3 4

5 6 7 8

C N.O.

TO CONTROLLEDDEVICE. SEE DATASHEET FOR POWER

RATINGLIMITATIONS.

MOUNTING OPTION "B"

4"(102mm) SQUARE BOX

4090-9002 RELAY IAM

COVER PLATE

2

WALL MOUNTED VISUAL ONLY

1. MAINTAIN CORRECT POLARITY ON TERMINALCONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECURE UNDERTERMINALS. NEVER LOOP WIRES UNDER TERMINALS.

3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJAPPROVED METHODS.

WIRING NOTES

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A SINGLE GANG BOX, 2-1/2" (64mm) DEEP BY OTHERS

B 4" (102mm) SQUARE BOX, 2-1/8" DEEP (MIN) BY OTHERS

CSIMPLEX 2975-9145, 7-7/8"H x 5-1/8"W x 2-3/4"D(127mm x 98mm x 56mm) REQUIRES 4905-9931 PLATE

ORDEREDSEPARATELY

BOTTOM OF LENS:80" (2032mm) A.F.F. MINIMUM

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET S49VO-0001 FROM HTTP://WWW.SIMPLEX-FIRE.COM

IDNAC SLC(-)

(+)

(-)

(+)

49VO TrueAlert ES ADDRESSABLE APPLIANCES

(-) (+)

OPTIONAL TAPLOCATION FOR

IDNAC SLC

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

IDNAC SLC

TERMINATION VIEW: DEVICE MOUNTING PLATE

CLICK HERE TOCHANGE WIRING

STYLE

TOP OF LENS:96" (2044mm) A.F.F MAXIMUMFOR CEILINGS > 86" (2180mm) A.F.F.:<= 6" (150mm) FROM CEILING

(-) (+) (-) (+)

CLASS B WIRING

CANDELA INTENSITYPLUG ACCESSIBLE FROMREAR OF HOUSING

MOUNTING OPTION "B"

6

1. VOLTAGE REGULATOR: ANY ELECTRICAL ORELECTRONIC DEVICE THAT MAINTAINS THE VOLTAGE OFA POWER SOURCE WITHIN ACCEPTABLE LIMITS. THEVOLTAGE REGULATOR IS NEEDED TO KEEP VOLTAGESWITHIN THE PRESCRIBED RANGE THAT CAN BETOLERATED BY THE ELECTRICAL EQUIPMENT USINGTHAT VOLTAGE. IN THIS CASE, THE VOLTAGEREGULATOR IS USED TO MAINTAIN A MINIMUM 29 VDCTO THE IDNAC CIRCUITS DURING AN ALARM CONDITION.

1. THE SIMPLEXGRINNELL ENHANCED POWERSUPPLY HAS A TOTAL OUTPUT OF 9A BUTMAY DRAW MORE THAN THIS FROM EITHERTHE 120VAC TRANSFORMER OR FROM THEBATTERIES.

ENHANCED POWER SUPPLY VOLTAGE DIAGRAM

VOLTAGETRANSFORMERRATED 24VDC

OUTPUT

BATTERY SET

VOLTAGEREGULATOR

24V DC POWER

PRIMARY POWER SUPPLY:DEDICATED BRANCH CIRCUIT 120 VOLTS AC.132 VAC (110%) TO 102 VAC (85%)

IDNAC ADDRESSABLENOTIFICATION CIRCUITS

29VDC, 9A

BATTERY CHARGER

AUXILIARY POWER

CARD POWER

29V DC POWER

THE VOLTAGE REGULATOR MAINTAINS A CONSTANT29VDC OUTPUT FROM IDNAC CIRCUITS, REGARDLESSOF THE VOLTAGE RECEIVED FROM THE TRANSFORMEROR BATTERY.

THE VOLTAGE REGULATOR WILL DRAW ADDITIONALCURRENT IN ALARM TO MAINTAIN THE REGULATED29VDC REGARDLESS OF INPUT VOLTAGE, WITHOUTAFFECTING THE 9A CAPACITY.

SECONDARY POWER SUPPLY:STORAGE BATTERIES24VDC. 26.4 VDC (110%) TO 20.4 VDC (85%)

29VDC STARTING SLC VOLTAGE FOR IDNAC CIRCUITS

23VDC MINIMUM SLC VOLTAGE AT FURTHEST DEVICE ON IDNAC CIRCUIT

NOTESDEFINITIONS

INPUT 4.6A @ 120VAC MAXOUTPUT 23A @ 24VDC MAX

4

WALL MOUNTED AUDIBLE / VISUAL

1. MAINTAIN CORRECT POLARITY ON TERMINALCONNECTIONS.

2. ALWAYS CUT CONDUCTORS AND SECURE UNDERTERMINALS. NEVER LOOP WIRES UNDER TERMINALS.

3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJAPPROVED METHODS.

WIRING NOTES

MOUNTING OPTIONS

OPTION

1

DESCRIPTION NOTE

A SINGLE GANG BOX, 2-1/2" (64mm) DEEP BY OTHERS

B 4" (102mm) SQUARE BOX, 2-1/8" DEEP (MIN) BY OTHERS

CSIMPLEX 2975-9145, 7-7/8"H x 5-1/8"W x 2-3/4"D(127mm x 98mm x 56mm) REQUIRES 4905-9931 PLATE

ORDEREDSEPARATELY

BOTTOM OF LENS:80" (2032mm) A.F.F. MINIMUM

1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET S49AV-0001 FROM HTTP://WWW.SIMPLEX-FIRE.COM

IDNAC SLC(-)

(+)

(-)

(+)

49AV TrueAlert ES ADDRESSABLE APPLIANCES

(-) (+)

OPTIONAL TAPLOCATION FOR

IDNAC SLC

T-TAP (SPLICE)CONNECTION

SERIESCONNECTION

IDNAC SLC

TERMINATION VIEW: DEVICE MOUNTING PLATE

CLICK HERE TOCHANGE

WIRING STYLE

TOP OF LENS:96" (2044mm) A.F.F MAXIMUMFOR CEILINGS > 86" (2180mm) A.F.F.:<= 6" (150mm) FROM CEILING

(-) (+) (-) (+)

CLASS B WIRING

CANDELA INTENSITYPLUG ACCESSIBLE FROMREAR OF HOUSING

MOUNTING OPTION "B"

7

0=OFF

128648 16 32

4 65 87

421

ON

31 2OFF

ADDRESS SHOWN ABOVE IS 2

DO NOT USE ADDRESS 0 FOR A SLC ADDRESS

1=ON

ADDRESSABLE NOTIFICATION DIP SWITCH SETTINGS

ADDRESSABLE NOTIFICATION APPLIANCE SETTINGS (SW1, SW2, SW3)

97

98

100

101

99

113

114

115

116

117

96 112

81

82

84

85

83

49

50

52

53

51

65

66

67

68

69

48 64 80

103

104

106

107

105

119

120

121

122

123

109

110

111

125

126

127

108 124

87

88

91

90

89

55

56

58

59

57

71

72

73

74

75

94

93

95

61

62

63

77

78

79

60 76 92

54 70 86 102 118

33

34

36

37

35

1

2

4

5

3

17

18

19

20

21

0 16 32

39

40

43

42

41

7

8

10

11

9

23

24

25

26

27

46

45

47

13

14

15

29

30

31

12 28 44

6 22 38

DIP SWITCHES 5 THRU 8

DIPSWITCHES1 THRU 4

5

s:\1-current projects\7555-parkway off central\Fire\FA-701.dwg, FA-702 WIRING TYPICALS, 9/13/2016 9:52:42 AM, ARCH full bleed E1 (30.00 x 42.00 Inches), 1:1

Page 18: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Parkway Off Central-9-12-16.xlsm

Equipment SubmittalSeptember 12, 2016

Project: Parkway Off Central

This page intentionally left blank for approvals.

Blaine, MN 55434

9436 Ulysses Street NE

Fire Alarm System

2-Way Communications System

Page 19: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Parkway Off Central-9-12-16.xlsm

Project:

Project Number:

Electrical Contractor:

Architect:

Presented By: SimplexGrinnell5400 Nathan Lane NorthSuite 100Plymouth, MN 55442-1953(763)367-5000(800)292-4111Fax (763)-367-5002

Sales Representative:

September 12, 2016

994941601

Berd Electric3308 Southway DriveSt. Cloud, MN 56301320-656-0847

651-379--9090

Jon Wiener

Dennis Thurston

James Kishish

Parkway Off Central

Equipment Submittal

9436 Ulysses Street NEBlaine, MN 55434

Project Systems Specialist:

Area General Manager:

Operations Manager:

Amcon Construction Company

George Glaros

5565 Blaine Avenue Suite 250Inver Grove Heights, MN 55076

Page 20: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

QTY DEVICE DESCRIPTION ROUGH IN BOX

1 4100-9111 4100U/ES FIRE CONTROL PANEL INCLUDES THE FOLLOWING FEATURES:W/ (1) 4100-0634 POWER DISTRIBUTION MODULE 120V MOUNTS IN PANEL

W/ (16) 4100-1279 2" BLANK DISPLAY MODULE MOUNTS IN PANELW/ (2) 4100-2300 EXPANSION BAY (PHASE 10 ONLY) MOUNTS IN PANEL

W/ (1) 4100-3110 IDNET 2+2 250 POINT 4 LOOP MOD MOUNTS IN PANEL

W/ (1) 4100-3206 8 RELAYS – 3 AMP MOUNTS IN PANELW/ (1) 4100-5101 EXPANSION PWR SUPPLY (XPS) - 120VAC 60HZ MOUNTS IN PANEL

W/ (1) 4100-5311 EPS+ POWER SUPPLY 120V MOUNTS IN PANELW/ (1) 4100-6052 EVENT REPORTING DACT MOUNTS IN PANELW/ 2975-9446 3 BAY BB/GDOOR/DRESS PANEL, PLATINUMW/ (2) 2081-9296 50 AH BATTERY, 12 VDCW/ 4100-0650 BATTERY SHELF MOUNTS IN PANEL

8 4009-9201 4009 IDNET NAC EXTENDER, 120 VAC INCLUDES THE FOLLOWING: W/CABINET

W/ (2) 2081-9272 6.2 AH BATTERY, 12 VDC

1 4603-9101 SERIAL LCD ANNUNCIATOR 6-GANG

1 4099-9004 MANUAL PULL STATION, LED, SA, ADDR 4" SQ. W/SINGLE RING

29 4098-9714 TRUEALARM PHOTO SMOKE SENSORW/ 4098-9792 TRUEALARM SENSOR BASE 4" SQ W/OCT. RING

461 4098-9714 TRUEALARM PHOTO SMOKE SENSORW/ 4098-9772 TRUEALARM SENSOR 520 HZ SOUNDER BASE

4" SQ W/OCT. RING

12 4090-9001 IDNET SUPERVISED IAM SINGLE GANG DEEP

14 4090-9002 IDNET RELAY IAM 4" SQ. DEEP

18 49VO-WWF VISUAL ONLY, WALL, WHITE, FIRE 4" SQ

70 49AV-WWF AUDIBLE/VISUAL, WALL, WHITE, FIRE 4" SQ

Note: See equipment data sheet for additional mounting options and details.

P:\Electronics\Submittals\[Parkway Off Central-9-12-16.xlsm]System Tab 1

EQUIPMENT LIST

FIRE ALARM SYSTEM

Page 21: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

QTY DEVICE DESCRIPTION ROUGH IN BOX

1 2500-210PSS RATH SMARTRESCUE BASE STATION, 10 ZONES, FLUSH MOUNTW/ 2500-PWR24 RATH POWER SUPPLY

10 2100-958SR RATH CALL BOX

W/ 7080_ RATH SIGN, RESCUE ASSTANCE, BRAILE

Note: See equipment data sheet for additional mounting options and details.

P:\Electronics\Submittals\[Parkway Off Central-9-12-16.xlsm]System Tab 2

EQUIPMENT LIST

2-WAY COMMUNICATIONS SYSTEM

Page 22: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

SIMPLEXGRINNELL WARRANTY STATEMENTSimplexGrinnell warrants to the purchaser of new SimplexGrinnell product(s) that during the effective period of the warranty, such product(s) shall be free from defects in the workmanship and material.

Warranty PeriodThe warranty period will terminate immediately following the earliest occurrence of either of the following:

» 18 months have elapsed following the shipment of any system or subsystem of SimplexGrinnell to the customer site, or

» 12 months have elapsed following the final connection, operation or beneficial use of all or any part of the system.

SimplexGrinnell Obligation Under the Terms of the Warranty:SimplexGrinnell sole responsibility shall be to repair, adjust or replace at its option any SimplexGrinnell product when it fails during this period provided purchaser has promptly reported such failure to SimplexGrinnell in writing. Replacement parts provided under warranty of products may contain used parts, which are equivalent to new parts when used. Replacement parts will be warranted only for the balance of the equipment warranty. SimplexGrinnell agrees to continue to honor all of the unexpired expressed warranties specified above on defective equipment after transfer of the equipment to the purchasers' customer, provided the purchasers' customer assumes the purchasers' obligations specified herein. Except for the express warranties stated herein, SimplexGrinnell disclaims all warranties on products furnished hereunder, including without limitation, all implied warranties of merchantability and fitness for a particular purpose, and the stated warranties are in lieu of or in connection with the performance of the products. The seller shall not be liable for any direct, incidental or consequential loss or damage to the purchaser or user of this equipment arising out of the failure of the equipment to operate in excess of the said equipment. SimplexGrinnell makes no warranty and no warranty shall be deemed to exist, that the purchaser holds the goods free of claim of any third person by way of patent infringement or the like.

Purchaser Obligation Under the Terms of the WarrantyThis warranty shall be contingent upon the proper installation and use of the product(s). Such warranty shall not apply if the product failure is the result of accident, unusual physical, electrical or electromechanical error, failure of electrical power, air conditioning or humidity control, construction dust, damaging foreign substances, transportation or causes other than manufacturing defects. Purchaser agrees to provide full and free access to authorized SimplexGrinnell employees.

Warranty Service HoursServices provided under this warranty will be performed during 8 a.m. and 5 p.m., Monday through Friday, excluding locally observed SimplexGrinnell Holidays. Off hours response is available as an extra cost service option.

Warranty ExclusionsLabor, travel and mileage for:

» Service provided outside of SimplexGrinnell normal business hours. » Programming and/or label changes and batteries. » Failure due to external causes (lightning surges, construction dust, etc.) other than

manufacturing defects. » Electrical work external to the equipment supplied by SimplexGrinnell or maintenance of

accessories, alterations, attachments or other devices not furnished by SimplexGrinnell. » Coverage of equipment classed as water flow monitoring/control devices installed in or

on water piping.

Page 23: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

PRELIMINARY INSTALLATION REVIEWS

Electrical Contractors Responsibilities:» Contractor to field verify building conditions, exact device locations and material

prior to performing any work or ordering of materials.» Safeguarding all material shipped to the office or job site.» Store all items (including all documentation) in a clean, dry, and safe place until

needed.» Notify all appropriate personnel if an existing system must be shut down while the

new system is being installed.» *Install all conduit and wiring, mount and terminate all field devices/equipment

including installation of end-of-line devices.» *Maintain an as-built copy of any supplied drawings for field changes or additions and

locations of end-of-line devices.» *Check all wiring for opens, grounds and shorts.» Identify high voltage circuit breaker number and location of breaker inside

any connected cabinet.» *Troubleshoot and repair of any field wiring problems.» *Terminate wiring in control panels.» *Set addresses on addressable devices.» *Schedule final/phased installation at least five (5) days in advance.» Please do not power up system.» Detectors shall not be installed until after the construction cleanup of all trades is

complete and final. (NFPA 72)» For Fire Alarm Panels, coordinate with owner to have two(2) telephone lines

installed for monitoring (one line for security systems) prior to final testing.

*Note: These items may be done by SimplexGrinnell or our sub-contractor if install is part of the our contract with the Electrical Contractor.

FINAL TESTING AND CHECK-OUT

Call763-367-5000

or 800-292-4111

Please notify SimplexGrinnell at least five (5) working days prior to the date you need our Technical Representative to check out this project.

We cannot guarantee short notice service due to prior scheduling commitments.

Page 24: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

PRELIMINARY INSTALLATION REVIEWS

We'll be happy to stop at the job site and answer questions regarding wiring andinstallation of SimplexGrinnell Equipment.

Please call 5 days in advance for an on-site visit to avoid scheduling conflicts.

Call 763-367-5000 or 800-292-4111

SimplexGrinnell Technician Responsibilities:» Perform preliminary visit to job site and answer questions.» Final check for opens, grounds and shorts.» Power up system.» Program system for proper operation.» One (1) 100% test of all systems for proper operation and supervision.» Customer Training.

Page 25: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Master Controller (top) bay: 32-Bit Master Controller with color-coded operator

interface including raised switches for high confidence feedback

Dual configuration program CPU, convenient service port access, and capacity for up to 2500 addressable points

CPU assembly includes 2 GB dedicated compact flash memory for on-site system programming and information storage

System power supply (SPS) and charger (9 A total) with on-board: NACs, IDNet addressable device interface, programmable auxiliary output and alarm relay

Available with InfoAlarm Command Center expanded content user interface (see data sheet S4100-0045)

Upgrade kits are available for existing control panels Standard addressable interfaces include: IDNet addressable device interface with 250 points that

support TrueAlarm analog sensing and operate with either shielded or unshielded twisted pair wiring

Remote annunciator module support via RUI (remote unit interface) communications port

Optional modules include: Building Network Interface Module (BNIC) for Ethernet

connectivity options (see data sheet S4100-0061) Electrically isolated output IDNet 2 (two loop) and

IDNet 2+2 (four loop) modules with short circuit isolation output loops allowing use with either shielded or unshielded, twisted or untwisted single pair wiring

Fire Alarm Network Interfaces, DACTs, city connections, and up to five (5) RS-232 ports for printers and terminals

IP communicator compatibility MAPNET II addressable device modules and

MAPNET II quad isolator modules Alarm relays, auxiliary relays, additional power

supplies, IDC modules, NAC expansion modules Service modems, VESDA Air Aspiration Systems

interface, ASHRAE BACnet Interface, TCP/IP Bridges LED/switch modules and panel mount printers Emergency communications systems (ECS) equipment;

8 channel digital audio or 2 channel analog audio Battery brackets for seismic area protection (see page 2)

Compatible with Simplex® remotely located 4009 IDNet NAC Extenders, up to ten per IDNet SLC 4100ES and upgrade kits are UL Listed to: UL 864, Fire Detection and Control (UOJZ), and Smoke

Control Service (UUKL) UL 2017, Process Management Equipment (QVAX) UL 1076, Proprietary Alarm Units-Burglar (APOU) UL 1730, Smoke Detector Monitor (UULH) UL 2572, Mass Notification Systems (PGWM) ); refer

to data sheet S4100-0034 for audio equipment ULC S527, Control Units for Fire Alarm Systems

Press ACK l ocated under fl ashin g indicator.Repeat operation unti l al l events are acknowledged.Local tone wil l silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP ' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 AlarmSYSTEM WARNINGS

Supervisory Trouble Ala rm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem ind icator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to si lence tone device.

ZONE

1SI G

2A UX

3

FB

4IO

5I DNet

6

P

7A

8L

9

N ET ADDR

0 DE L

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

Enable On Arm

Disable OffDisarm Auto Lamp

Test

MoreInfo

Menu

Previous

Next

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Lo cal to ne will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 Ala rmSYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to si lence tone device.

ZONE

1SI G

2A UX

3

FB

4IO

5I DNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

Enable On Arm

Disable OffDisarm Auto Lamp

Test

MoreInfo

Menu

Previous

Next

4100ES Cabinets are Available with One, Two or Three Bays

Software Feature Summary

CPU provides dual configuration programs: Two programs allow for optimal system protection and

commissioning efficiency with one active program and one reserve

Downtime is reduced because the system stays running during download

PC based programmer features: Convenient front panel accessed Ethernet port for quick

and easy download of site-specific programming Modifications can be uploaded as well as downloaded

for greater service flexibility AND, firmware enhancements are made via software

downloads to the on-board flash memory

Introduction

4100ES Series Fire Detection and Control Panels provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.

Modular design. A wide variety of functional modules are available to meet specific system requirements. Selections allow panels to be configured for either Stand-Alone or Networked fire control operation. InfoAlarm Command Center options provide convenient expanded display content (detailed on data sheet S4100-0045).

* See pages 5 and 6 for product that is UL or ULC listed and additional listing information. This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251(4100ES) for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

Fire Control Panels UL, ULC, CSFM Listed; FM Approved; Addressable Fire Detection and Control MEA (NYC) Acceptance* Basic Panel Modules and Accessories

S4100-0031-32 7/2015

Page 26: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Module Bay Description

The Master Controller Bay (top) includes a standard multi-featured system power supply, the master controller board, and operator interface equipment.

The Expansion Bays include a Power Distribution Interface (PDI) for new 4” x 5” flat design option modules and also accommodate 4100-style modules.

The Battery Compartment (bottom) accepts two batteries, up to 50 Ah, to be mounted within the cabinet without interfering with module space.

The following illustration identifies bay locations using a three bay cabinet for reference.

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

4100

Opt

ion

4100

Opt

ion

4100

Opt

ion

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

System Power Supply

(SPS)

IDNet NACs 1, 2 & 3

Aux Pwr Aux Relay

Btry+-

Mas

ter C

ontro

ller

Boa

rd

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

Slot 1

Slot 2

Slot 4

Slot 3

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

4100

Opt

ion

4100

Opt

ion

4100

Opt

ion

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

Master Controller Bay

Expansion Bay 1

Battery Compartment

System power supplyMaster controller with dual slot motherboard

Expansion Bay 2

Typical bays with mixed module sizes

4100ES Module Bay Reference

Mechanical Description

Boxes can be close-nippled; each box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting

Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required

Cabinet assembly design has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires 4100-7912 option for additional legacy card stabilizer brackets and battery brackets as detailed on data sheet S2081-0019

Mechanical Description (Continued)

The latching dress panel (retainer) assembly easily lifts off for internal access

NACs are mounted directly on power supply assemblies providing minimized wiring loss, compact size, and readily accessible terminations

Packaging supports traditional 4100-style motherboard with daughter cards

Modules are power-limited (except as noted, such as relay modules)

The NEMA 1/IP30 box is ordered separately and available for early installation

Doors are available with tempered glass inserts or solid; boxes and doors are available in platinum or red

Boxes and door/retainer assemblies are ordered separately per system requirements; refer to data sheet S4100-0037 for details

Operator Interface Detail Reference

The following illustration identifies the primary functions of the operator interface.

Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Local tone will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 AlarmSYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to silence tone device.

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

EnableOn

Arm

DisableOff

DisarmAuto

LampTest

MoreInfo

Menu

Previous

Next

Upload/Download Ethernet port access (under sliding cover)

Basic operator instructions are printed on the interface

mounting plate

Panel sounder

Operator interface panel is directly viewable and accessible (no access door)

Software Feature Summary

TrueAlarm individual analog sensing with front panel information and selection access

“Dirty” TrueAlarm sensor maintenance alerts, service and status reports including “almost dirty”

TrueAlarm magnet test indication appears as distinct “test abnormal” message on display when in test mode

TrueAlarm sensor peak value performance report “Install Mode” allows grouping of multiple troubles for

uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas

Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring

“Recurring Trouble Filtering” allows the panel to recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications

WALKTEST silent or audible system test performs an automatic self-resetting test cycle

2 S4100-0031-32 7/2015

Page 27: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Operator Interface

Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.

LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

Operator Interface Features

Convenient and extensive operator information is provided using a logical, menu-driven display

Multiple automatic and manual diagnostics for maintenance reduction

Alarm and Trouble History Logs (up to 1250 entries for each, 2500 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer

Convenient PC programmer label editing

Password access control

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 AlarmSYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

EnableOn

Arm

DisableOff

DisarmAuto

LampTest

MoreInfo

Menu

Previous

Next

SIX SYSTEM STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset :Fire Alarm & Priority 2 Alarm, red LEDSupervisory & Trouble, yellow LEDAlarm Silenced, yellow LEDAC Power, green LED (on for normal)

FIVE PROGRAMMABLE FUNCTION SWITCHES, each with a yellow LED indicator

POINT STATUS CONTROL KEYS:Point Enable and DisableForce On or ArmForce Off or DisarmReturn On/Off or Arm/Disarm to Auto Mode

NUMERIC KEYPAD for point category and point selection (alphabet characters are not used at this time)

ADDITIONAL FUNCTION KEYS:Event Time RequestMore Information RequestLamp Test

Elevator Recall

City Disconnect

Manual Evac

Ground Fault

Waterflow-West

Waterflow-East

Custom label insert

LCD NAVIGATION CONTROL:Menu selectionVertical and Horizontal position selection buttons

FIRE ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

TROUBLE ACK acknowledges system troubles, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

ALARM SILENCE causes audible notification appliances to be silenced (depending on panel programming) typically after evacuation is complete and while alarm source is being investigated; may allow visible notification to continue (strobes still flashing)

SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal

2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 40 characters for custom label information

FIRST ALARM DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged

THREE PROGRAMMABLE LEDs provide custom labeling, the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow

ULC SYSTEMS require designating a Ground Fault indicator

Almost Dirty

Ground Fault Latch

3 S4100-0031-32 7/2015

Page 28: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Compatible Peripheral Devices

The 4100ES is compatible with an extensive list of remote peripheral devices including printers, CRT/keyboards (up to five total), and both conventional and addressable devices including TrueAlarm analog sensors.

Addressable Device Control

Overview. The 4100ES provides standard addressable device communications for IDNet compatible devices and accepts optional modules for communications with MAPNET II compatible devices. Using a two wire communications circuit, individual devices such as manual fire alarm stations, TrueAlarm sensors, conventional IDC zones, and sprinkler waterflow switches can be interfaced to the addressable controller to communicate their identity and status.

Addressability allows the location and condition of the connected device to be displayed on the operator interface LCD and on remote system annunciators. Additionally, control circuits (fans, dampers, etc.) may be individually controlled and monitored with addressable devices.

Addressable Operation. Each addressable device on the communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation are available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuit for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel.

IDNet Channel Capacity. The CPU bay system power supply (SPS) provides an IDNet signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. Additional 250 point IDNet circuit modules are available, refer to IDNet 2 and IDNet 2+2 modules on page 7.

IDNet, MAPNET II, IDNet 2, and IDNet 2+2 SLC Wiring Common Specifications Maximum Distance from Control Panel per Device Load

1 to 125 4000 ft (1219 m); 50 ohms

126-250 2500 feet (762 m); 35 ohms

Connections Terminals for 18 to 12 AWG (0.82 mm2 to 3.31 mm2)

IDNet and MAPNET II Specifications

Wire Type Preferred Shielded twisted pair (STP)

Acceptable* Unshielded twisted pair (UTP)

IDNet and MAPNET II Wiring, Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 10,000 ft (3 km); 0.58 µF

IDNet 2 and IDNet 2+2 Wiring Specifications

Wire Type Shielded or unshielded, twisted or untwisted wire*

Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 12,500 ft (3.8 km); 0.60 µF

Maximum Capacitance Between IDNet 2 Channels 1 µF

IDNet 2 and IDNet 2+2 Module Compatibility: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2 sensors * Some applications may require shielded wiring. Review your

system with your local Simplex product supplier.

TrueAlarm System Operation

Addressable device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.

Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read and compared to the alarm threshold directly in percent.

CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, used in LED/Switch modes and custom control, and can be made public for communication across a fire alarm Network. (refer to data sheet S4098-0052 for details)

TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius.

TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4100ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.

Diagnostics and Default Device Type

Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and when end of life is reached.

Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.

4 S4100-0031-32 7/2015

Page 29: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

CPU Bay Module Details

Master Controller and Motherboard: Mounts in Slot 4 of a two slot motherboard (Slots 3 and 4

of the Master Controller Bay) and provides one Class B or Class A, RUI communications channel, available at Slot 4

RUI communications controls up to 31 devices per master controller (on one or multiple RUI channels); devices include: MINIPLEX transponders, 4603-9101 LCD Annunciators, 4602-9101 Status Command Units (SCU), 4602-9102 Remote Command Units (RCU), 4602 Series LED Annunciator Panels, and 4100 Series 24 I/O and LED/Switch modules

Up to four RUI channels are supported; use up to three 4100-1291 RUI expansion modules as required

Optional Service Modem 4100-6030 mounts onto the master controller board with its own on-board connections

Slot 3 of the motherboard is primarily for the 4100-6078 Network Interface Board with media modules, and secondarily for the 4100-6038 Dual RS-232 Board (4100-6038 is required for 2120 System connections)

System Power Supply: (see page 9 for more detail) Rating is 9 A total with “Special Application” appliances;

4 A total for “Regulated 24 DC” appliance power Outputs are power-limited, except for the battery charger Provides system power, battery charging, auxiliary power,

auxiliary relay, earth detection, on-board IDNet communications channel for 250 points, three on-board NACs, and provisions for either an optional City Connect Module or an optional Alarm Relay Module

IDNet SLC Output provides Class B or Class A communications for up to 250 addressable devices (as described on page 4)

System Power Supply (Continued): Three, 3 A On-Board NACs, conventional reverse

polarity operation; rated 3 A for Special Application appliances and 2 A for Regulated 24 DC power, with electronic control and overcurrent protection; selectable as Class B or Class A, and for synchronized strobe or SmartSync horn/strobe operation over two wires

NACs can be selected as auxiliary power outputs derated to 2 A for continuous duty; the total auxiliary power output per SPS is limited to 5 A

Battery Charger is dual rate, temperature compensated, and charges up to 50 Ah sealed lead-acid batteries mounted in the battery compartment (33 Ah for single bay cabinets); also is UL listed for charging up to 110 Ah batteries mounted in an external cabinet (see data sheet S2081-0012 for details)

Battery and Charger Monitoring includes battery charger status and low or depleted battery conditions; status information provided to the master controller includes analog values for: battery voltage, charger voltage and current, actual system voltage and current, and individual NAC currents

2 A Auxiliary Power Output is selectable for detector reset, door holder, or coded output operation

Auxiliary Relay is selectable as N.O. or N.C., rated 2 A @ 32 VDC, and is programmable as a trouble relay, either normally energized or normally de-energized, or as an auxiliary control

Optional City Connect Module (4100-6031, with disconnect switches, or 4100-6032, without disconnect switches) can be selected for conventional dual circuit city connections

Optional Alarm Relay Module (4100-6033) provides three Form C relays that are used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC

4100ES Master Controller and Expansion Bay Selection* (Canadian models have low battery cutout) Model Model Type and Listing Description Supv.** Alarm**

4100-9111 120 VAC Input UL 4100ES Master Controller Assembly with LCD and operator interface, 9 A system power supply/battery charger (SPS), 250 point IDNet interface, 3 NACs, auxiliary relay, and external RUI communications interface

373 mA 470 mA4100-9112 English 120 VAC, Canadian ULC 4100-9113 French 4100-9211 220-240 VAC Input UL 4100-9131 120 VAC Input UL 4100ES Master Controller Assembly, no display, no

operator interface, 9 A system power supply/battery charger (SPS), 250 point IDNet interface, 3 NACs, auxiliary relay, and external RUI communications interface

363 mA 425 mA4100-9132 English, 120 VAC, Canadian ULC 4100-9230 220-240 VAC Input UL

4100-9121 (not ULC

listed)

Redundant Master Controller with a two bay assembly, one for each of the primary and backup master controllers. Both bays have an LCD and operator interface, CPU card assembly, and 9 A system power supply (SPS) 120 VAC, 60 Hz input. Active SPS battery charger in Bay 1 only. External RUI connections require 4100-1291 RUI expansion modules. Do not use circuit connections (IDNet, NACs, etc.) on primary and secondary SPS power supplies.

718 mA 937 mA

4100ES Master Controller Upgrades for Existing 4100 Series Fire Alarm Control Panels* Model Panel Type Includes

4100-7150 1000 pt 4100 (4100+) New Master Controller CPU card, 4100ES door assembly with LCD and user interface, and Ethernet connection

4100-7152 512 pt 4100 Same as 4100-7150 plus a Universal Power Supply

4100-7158

4100U or 1000 pt 4100 (4100+) previously upgraded to 4100U

New Master Controller CPU card with Ethernet Connection Upgrade Kit (door assembly with LCD and user interface are not included) for: 4100U with or without LCD and operator interface, or 4100+ without LCD and operator interface, or An existing 4100 (512 pt) or 4100+ (1000 pt) panel that was previously upgraded to a 4100U

Master Controller and Display * For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045. (Continued on next page) ** Note: Master Controller current does not subtract from 9 A output rating.

5 S4100-0031-32 7/2015

Master Controller Selection Information

dthurston
Line
Page 30: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

6 S4100-0031-32 7/2015

Communication Modules Model Description Size Supv. Alarm

4100-6078 For Master Controller; mounts in Slot 3 Modular Network Interface; each requires two media modules (below)

1 Slot 46 mA 46 mA

4100-6061 For Redundant Master Controller 1 Slot 46 mA 46 mA

4100-6056 Wired Media Module Select two media cards as required; mounts on 4100-6078 or 4100-6061; Class B or Class X operation

N.A. 55 mA 55 mA

4100-6057 Fiber Optic Media Module N.A. 25 mA 25 mA

4100-6047 Building Network Interface Card (BNIC), refer to data sheet S4100-0061 for details 2 Blocks 291 mA 291 mA

4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network Interface Card, requires telephone line connection N.A. 60 mA 60 mA

4100-1291 Remote Unit Interface Module (RUI); up to three maximum per control panel 1 Slot 85 mA 85 mA

4100-6030 Service Port Modem, local panel access only, mounts to Master Controller Module, requires telephone line connection, accesses same information as front panel port N.A. 70 mA 70 mA

4100-6031 Select one per SPS (fits on SPS)

City Circuit, with disconnect switches For use with SPS only, not RPS

N.A. 20 mA 36 mA

4100-6032 City Circuit, w/o disconnect switches N.A. 20 mA 36 mA

4100-6033 Alarm Relay, 3 Form C relays, 2 A @ 32 VDC; for SPS or RPS N.A. 15 mA 37 mA

4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA

4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA

4100-6038 Dual Port RS-232 with 2120 interface (slot module) 3 maximum of RS-232 type modules per panel

1 Slot 132 mA 132 mA

4100-6046 Dual Port RS-232 standard interface (4 x 5 module) 1 Block 60 mA 60 mA

4100-6045 Decoder Module 3 Slots 85 mA 163 mA

4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA

4100-6052 DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs 1 Slot 30 mA 40 mA

Expansion, System and Remote Power Supplies and Accessories (Canadian models have low battery cutout) Model Voltage/Listing Description Size Supv. Alarm

4100-5101 120 VAC UL Expansion Power Supply (XPS); 9 A output, 3 built-in Class A/B NACs; NAC operation is same as SPS, see page 5 for details

2 Blocks 50 mA 50 mA 4100-5103 120 VAC, Canadian ULC

4100-5102 220-240 VAC UL

4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA

4100-5111 120 VAC UL Additional System Power Supply (SPS); 9 A power supply/charger with 250 point IDNet channel, 3 Class A/B NACs, add IDNet device currents separately

4 Blocks 175 mA 185 mA 4100-5112 120 VAC, Canadian ULC

4100-5113 220-240 VAC UL

4100-5125 120 VAC UL Remote Power Supply (RPS); 9 A power supply/charger similar to SPS except no IDNet channel or City Circuits; will accept one 4100-6033

4 Blocks 150 mA 185 mA 4100-5126 120 VAC, Canadian ULC

4100-5127 220-240 VAC UL

Continued on next page

Master Controller Accessories 4100-2300 Expansion Bay Assembly; order for each required expansion bay (not required for 4100-9121)

4100-2303 Legacy Module Stabilizer Bracket, used when expansion bays have legacy slot style modules

4100-2301 Expansion Bay Upgrade Kit for mounting 4100ES style (4” x 5” modules) in existing 4100 style panels; Note: When using this kit to upgrade a 4100+ transponder, a 4100-0620 Transponder Interface Card (TIC) is also required for communications to the 4100ES module

Master Controller Upgrades for Existing 4020 Series Fire Alarm Control Panel Model Description

4100-9833

4020 Master Controller Upgrade to 4100ES; Includes New Master Controller with LCD & operator interface assembly, 8 VDC Converter and RUI Interface in a single bay cabinet with locking glass door and retainer; mounts as an adjunct panel close-nippled to existing 4020 cabinet; also includes 8 VDC box-to-box power and communications harness and solid filler panel for the existing 4020 Master Controller bay

Module Selection Information

Master Controller Selection Information (Continued)

dthurston
Line
dthurston
Line
dthurston
Line
Page 31: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

7 S4100-0031-32 7/2015

Expansion, System and Remote Power Supplies and Accessories (Continued) Model Description Size Current

4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum

4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads

4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet 4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from SPS

8 Zone Initiating Device Circuits* Expansion Signal Module and Options (1.5 A Class B except as noted) Model Type Supv. Alarm Model Description Supv. Alarm

4100-5005 Class B 75 mA 195 mA 4100-5116 Converts 1 NAC in to 3 NACs out; 1 Block size 18 mA 80 mA

4100-5015 Class A 75 mA 195 mA 4100-1266 Expands 3 NACs to 6 select one; mounts on 4100-5116

0.6 mA 60 mA

* IDC Modules are 1 Slot size 4100-1267 Converts 3 NACs to Class A 0.6 mA 30 mA

Addressable Interface Modules (refer to location reference on pages 8 and 9) Model Description Supv. Alarm

4100-3109*

IDNet 2 Module, 250 point capacity; electrically isolated output with two short circuit isolating Class B or Class A output loops, 1 block; standard on EPS with IDNet 2 Module; alarm currents for 50 and above devices includes 20 device LEDs in alarm

no devices 50 mA 60 mA 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA 250 devices 250 mA 350 mA

4100-3110*

IDNet 2+2 Module, 250 point capacity; electrically isolated output with four short circuit isolating Class B or Class A output loops, 1 block; mounts in expansion bay or available master controller bay module locations only, not applicable for EPS mounting; alarm currents for 50 and above devices includes 20 device LEDs in alarm

no devices 50 mA 60 mA 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA 250 devices 250 mA 350 mA

4100-3111* IDNet Short Circuit Isolating Loop Output Module; mount up to two on a 4100-3109 module; for use with 4100-3109 modules; this option is for aftermarket field installation only

*Note: Loading per IDNet device (no LEDs on) = 0.8 mA supervisory and 1 mA alarm. Each IDNet 2 and IDNet 2+2 Short Circuit Isolating Loop Output can be individually controlled for system diagnostics and can be assigned a public point for Fire Alarm Network annunciation.

Model Description Supv. Alarm

4100-3102 MAPNET II Module, 127 point capacity, add devices separately; Module size = 2 Slots; Loading per MAPNET II device = 1.7 mA

Module without devices 255 mA 275 mA

Fully loaded module, total 471 mA 491 mA

4100-3103

Isolator Module for MAPNET II communications; converts a single connected SLC into four isolated outputs selectable as Class A or Class B; up to two Isolator Modules can be connected to one SLC; Module size = 1 Slot; NOTE: Compatible with MAPNET II Remote Isolators only

50 mA 50 mA

Relay Modules; Nonpower-limited (for mounting in expansion bay only, refer to location reference on pages 8 and 9) Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm

4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA

4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC 1/2 A 30 VDC/120 VAC 1 Block 15 mA 60 mA 4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1-1/2 A 30 VDC/120 VAC 1 Block 15 mA 190 mA

System Option for Seismic Compliance Model Description

4100-7912 System option for Seismic compliance, provides additional stabilizer brackets required for legacy style cards

Current Calculation Notes: 1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered

by panel power supplies. 2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads

and all external loads powered from panel power supplies.

Continued on next page

Module Selection Information (Continued)

dthurston
Line
dthurston
Line
Page 32: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

8 S4100-0031-32 7/2015

End User Programming Software (requires 4100-8802) Model Description

4100-8802 Programming Software (select)

End User Programming Software Selection (select maximum of one each from below) Model Description

4100-0292 Custom Labels Editing; allows editing of 40 Character Custom Labels for non-system user points

4100-0296 Access Level/Passcode Editing; allows user to re-assign Access Levels and Passcodes for each display function; Acknowledge, Alarm Silence, System Reset, Point Enable/Disable, WALKTEST Enable/Disable, Clear History Logs, Change Time & Date, etc.

4100-0295 Port Vectoring Setup and Control; Allows vectoring of events to PC Annunciator, Printers, LCD Annunciators, etc.

4100-0298

WALKTEST Configuration Setup and Control; Allows user to create or edit WALKTEST groups used to test system initiating devices and signals by a single person, these groups allow an inspector to conduct a one-person WALKTEST in a specific area of a building (or different buildings), and limit the activation of the building signals to only the intended area; up to 8 WALKTEST groups are supported

Miscellaneous Accessories Model Description

4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay

4100-9856* 4100ES Canadian French Appliqué Kit; Simplex, 4100ES, Contrôle Incendie

4100-9857* 4100ES English Appliqué Kit; Simplex, 4100ES, Fire Control

4100-9858* 4100ES InfoAlarm Remote Display English Appliqué Kit; Simplex, Operator Interface, 4100ES

4100-9859* 4100ES InfoAlarm Remote Display Canadian French Appliqué Kit; Simplex, Interface de l’operateur, 4100ES

4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES

4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES

4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules

4100-6029 Smoke Management Application Guide; required for UUKL listing

4100-6034 Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM

2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)

* Note: 4100ES English Appliqués are included with 4100ES Upgrade and Retrofit Kits for mounting 4100ES in 4100, 2120, 2001, and Autocall back boxes so that upgrades can be easily identified as 4100ES. 4100ES Appliqué Kits are available for applications such as to update Remote InfoAlarm Displays connected to a panel that was upgraded to 4100ES or for an existing 4100U when the New Master Controller is upgraded to 4100ES and only a software upgrade is required. When required, French appliqués are ordered separately.

Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2

Expansion Bay Chassis

Block A

Block B

Block C

Block D

Block E

Block F

Block G

Block H

Size Definitions: Block = 4” W x 5” H (102 mm x 127 mm) card area Slot = 2” W x 8” H (51 mm x 203 mm) motherboard with daughter card

Module Selection Information (Continued)

Expansion Bay Module Loading Reference

Description Mounting IDNet 2, IDNet 2+2 Modules 1 Block 4, 2 A Relays

NON Power-limited

1 block 4, 10 A Relays 4”, 2 slots 8, 3 A Relays 1 block VESDA Interface 2”, 1 Slot Class B IDC 2”, 1 Slot Class A IDC 2”, 1 Slot MAPNET II Module 4”, 2 Slots MAPNET II/IDNet Isolator 2”, 1 Slot Class B Physical Bridge 2”, 1 Slot Class X Physical Bridge 4”, 2 Slots Decoder Module 6”, 3 Slots

System or Remote Power Supply Blocks E, F, G & H ONLY

Expansion Power Supply Blocks G & H ONLY NAC Expansion Module On XPS ONLY

Page 33: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

9 S4100-0031-32 7/2015

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

System Power Supply

(SPS)

IDNet NACs 1, 2 & 3

Aux Pwr Aux Relay

Btry+-

City Circuit4100-60314100-6032

Alarm Relay4100-6033

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

*System power supply*Master controller with motherboard

Optional semi-flush trim kit

4100-6031 or 4100-6032 City Circuit or 4100-6033Alarm Relay

4100-6030 Service Modem mounts only on master controller board

Slot 3, one 2" card: either 4100-6078 Network Module with media cards or 4100-6038 Dual RS-232

Slot 1

Slot 2

Slot 3

Cabinet height:(2 bay shown for reference)

1 Bay = 22"(559 mm)

2 Bay = 40"(1016 mm)

3 Bay = 56"(1422 mm)

Stud alignment markers, each side

Knockout screw/nail holes (for semi-flush mounting)

4" stud

6" stud

Two, 2", or one, 4" slot for one or two modules installed per the following:

4100-6052 DACT, Slot 1

4100-6101 Physical Bridge, Slot 2

4100-6102 Physical Bridge (4" module) Slots 1 and 2

4100-6048 VESDA Interface, Slot 1 or 2

4100-5005/5015 IDC Modules, Slot 1 or 2

4100-6038 Dual RS-232, Slot 2, if Network Module is in Slot 3

Master Controller Bay

Typical Expansion Bay(showing mixed module sizes)

Battery Compartment

Door can be hunghinged left or right

Wall board reference for semi-flush mounting, 6" stud

Two bay cabinet shown without retainer

11-11/16"(296 mm)

6-29/32"(175 mm)

For semi-flushmounting provide1/2" (12.7 mm)

minimum extensionbeyond finished wall

24" (610 mm)

Door 4-3/4"(121 mm)

Input Power

System Power Supplies (SPS) Expansion Power Supplies (XPS)

Remote Power Supplies (RPS)

120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz 220-240 VAC Models

2 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC

Power Supply Output Ratings for SPS, XPS, and RPS (nominal 28 VDC on AC; 24 VDC on battery backup)

Total Power Supply Output Rating

Including module currents and auxiliary power outputs; 9 A total for “Special Application” appliances; 4 A total for “Regulated 24 DC” power (see below for details)

Output switches to battery backup during mains AC failure or brownout conditions

Auxiliary Power Tap 2 A maximum Rated 19.1 to 31.1 VDC NACs Programmed

for Auxiliary Power 2 A maximum per NAC; 5 A maximum total

Special Application Appliances

Simplex horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative for compatible appliances)

Regulated 24 DC Appliances Power for other UL listed appliances; use associated external synchronization modules where required

Battery Charger Ratings for SPS and RPS (sealed lead-acid batteries)

Battery capacity range UL listed for battery charging of 6.2 Ah up to 110 Ah (batteries larger than 50 Ah require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries

Charger characteristics and performance

Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527

Environmental Operating Temperature 32° to 120°F (0° to 49° C)

Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Additional Technical Reference

Installation Instructions 574-848 Operating Instructions 579-197

NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

Mounting and CPU Bay Module Reference (* indicates supplied modules)

General Specifications

Page 34: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Microsoft and Windows are trademarks of Microsoft Corporation. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0031-32 7/2015 www.simplex-fire.com

© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Subject Data Sheet Subject Data Sheet Introducing the 4100ES S4100-0060 SafeLINC Internet Interface S4100-0062 4100ES Enclosures S4100-0037 Agent Release Applications S4100-0040 4100ES Control Panels with EPS+ Power Supplies for TrueAlert Addressable Notification S4100-0100

Fire Alarm Network Overview S4100-0055 Network Communications S4100-0056

4100ES Audio and Firefighter Phone Modules S4100-0034 Network Display Unit (NDU) S4100-0036 LED/Switch Modules & Printer S4100-0032 Addressable Device Compatibility S4090-0011 Remote Annunciators S4100-0038 Remote Battery Charger S4081-0002 MINIPLEX Transponders S4100-0035 TFX Interface Module S4100-0042 Building Network Interface (BNIC) S4100-0061 Master Clock Interface S4100-0033 InfoAlarm Command Center S4100-0045 2120 BMUX Module S4100-0048 Graphic I/O Modules S4100-0005 TrueInsight Remote Service S4100-0063

Additional 4100ES Data Sheet Reference

Page 35: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Master Controller (top) bay standard equipment: 32-Bit Master Controller with color-coded operator

interface and raised switches for high confidence feedback Dual configuration program CPU, convenient service port

access, and capacity for up to 2500 addressable points CPU assembly includes 2 GB dedicated compact flash

memory for on-site system programming and information storage

An Enhanced Power Supply (EPS) and battery charger (9 A output) with on-board: IDNAC SLCs (signaling line circuit) for addressable appliance control, an IDNet 2 Module for addressable device control; and programmable function auxiliary output

Also available with InfoAlarm Command Center expanded content user interface (see data sheet S4100-0045)

Standard addressable device interfaces include: 250 point addressable device IDNet 2 SLC that supports

TrueAlarm analog sensors and IDNet communications monitoring and control devices with an electrically isolated output channel allowing use with either shielded or unshielded, twisted or untwisted single pair wiring; and providing dual short circuit isolating output loops

MINIPLEX Transponder and remote LCD and LED annunciator support via RUI+ (remote unit interface) communications port with electrically isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring (refer to details on page 6)

Standard power supplies (EPS) provide enhanced power delivery IDNAC SLCs to addressable notification appliances: With IDNAC SLCs, a constant 29 VDC source voltage is

maintained during alarm, even during battery operation, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby

Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, and the ability to use smaller gauge wiring – all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will also operate during worst case alarm conditions

IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther

Optional modules and connections include: Fire Alarm Network Interfaces, city connections, and up

to five (5) RS-232 ports for printers and terminals Building Network Interface Module (BNIC) for Ethernet

connectivity options (see data sheet S4100-0061) Side mounted DACT assembly requiring minimal panel

space; DACT is compatible with IP Communicators Emergency communications systems (ECS) equipment;

8 channel digital audio or 2 channel analog audio

Press ACK l ocated under fl ashin g indicator.Repeat operation unti l al l events are acknowledged.Local tone wil l silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP ' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 AlarmSYSTEM WARNINGS

Supervisory Trouble Ala rm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem ind icator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to si lence tone device.

ZONE

1SI G

2A UX

3

FB

4IO

5I DNet

6

P

7A

8L

9

N ET ADDR

0 DE L

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

Enable On Arm

Disable OffDisarm Auto Lamp

Test

MoreInfo

Menu

Previous

Next

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Lo cal to ne will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 Ala rmSYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to si lence tone device.

ZONE

1SI G

2A UX

3

FB

4IO

5I DNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

Enable On Arm

Disable OffDisarm Auto Lamp

Test

MoreInfo

Menu

Previous

Next

4100ES Cabinets are Available with One, Two or Three Bays

Option Modules (Continued) Additional IDNet 2 communications SLCs, IDNet 2+2

Modules with quad short circuit isolating output loops; additional power supplies, alarm relays, and auxiliary relays

LED/switch modules and panel mount printers; VESDA Air Aspiration Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges

Battery brackets for seismic area protection (see page 2) 4100ES compatible legacy interface modules,

including control of conventional (non-addressable) NACS (see data sheet reference list on page 12)

4100ES Listings reference: UL 864, Fire Detection and Control (UOJZ), and Smoke

Control Service (UUKL) UL 2017, Process Management Equipment (QVAX) UL 1076, Proprietary Alarm Units-Burglar (APOU) UL 1730, Smoke Detector Monitor (UULH) UL 2572, Mass Notification Systems (PGWM); refer to

data sheet S4100-0034 for audio equipment ULC S527, Control Units for Fire Alarm Systems

Software Feature Summary

CPU provides dual configuration programs: Two programs allow for optimal system protection and

commissioning efficiency with one active program and one reserve; downtime is reduced because the system stays running during download

PC based programmer features: Convenient front panel accessed Ethernet port for quick

and easy download of site-specific programming Modifications can be uploaded as well as downloaded for

greater service flexibility; AND, firmware enhancements are made via software downloads to the on-board flash memory

* See pages 6 and 7 for product that is UL or ULC listed and additional listing information. This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

4100ES Fire Control Panels UL, ULC, CSFM Listed; Addressable Fire Detection and Control FM, NYC Fire Dept Approved* Basic Panel Modules and Accessories

S4100-0100-13 1/2016

Page 36: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Introduction

4100ES Series Fire Detection and Control Panels provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.

Modular design. A wide variety of functional modules are available to meet specific system requirements. Selections allow panels to be configured for either Stand-Alone or Networked fire control operation.

Module Bay Description

The Master Controller Bay (top) includes a standard multi-featured enhanced power supply (EPS) with IDNet 2 Module, the master controller board, two vertical expansion blocks, and operator interface equipment.

The Expansion Bays include a Power Distribution Interface (PDI) for connection of single or multiple block modules, and/or slot style (motherboard/daughter card) modules.

The Battery Compartment (bottom) accepts two batteries, up to 50 Ah, to be mounted within the cabinet without interfering with module space.

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

4100

Opt

ion

4100

Opt

ion

4100

Opt

ion

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

PDI

Mas

ter C

ontro

ller

Boar

d

Slot 1 Slot 2 Slot 3 Slot 4

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

4100

Opt

ion

4100

Opt

ion

4100

Opt

ion

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

Master Controller Bay

Expansion Bay 1

Battery Compartment

EPS Power Supply with IDNet 2 Module

Master controller with dual slot motherboard

Expansion Bay 2

Typical bays with mixed module sizes

PDI board with two connectors available

4100-6080 DACT mounting location

Optional 4190-6104 TrueInsight Module mounting location

4100ES Module Placement Reference in 3-Bay Cabinet

Mechanical Description

Boxes can be close-nippled; each box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting

Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required

Cabinet assembly design has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires 4100-7912 option for additional legacy card stabilizer brackets and battery brackets as detailed on data sheet S2081-0019

The latching front panel assembly easily lifts off for internal access

Modules are power-limited (except as noted, such as relay modules)

The NEMA 1/IP30 box is ordered separately and available for early installation

Doors are available with tempered glass inserts or solid; boxes and doors are available in platinum or red

Boxes and door/retainer assemblies are ordered separately per system requirements; refer to data sheet S4100-0037

Operator Interface Detail Reference

The following illustration identifies the primary functions of the operator interface.

Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Local tone will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 AlarmSYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to silence tone device.

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

EnableOn

Arm

DisableOff

DisarmAuto

LampTest

MoreInfo

Menu

Previous

Next

Upload/Download Ethernet port access (under sliding cover)

Basic operator instructions are printed on the interface

mounting plate

Panel sounder

Operator interface panel is directly viewable and accessible (no access door)

Software Feature Summary

“Install Mode” allows grouping of multiple troubles for uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas

Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring

“Recurring Trouble Filtering” allows the panel to recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications

WALKTEST silent or audible system test performs an automatic self-resetting test cycle

Support for TrueAlarm individual analog sensing and IDNAC addressable notification with front panel information and selection access

2 S4100-0100-13 1/2016

Page 37: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Operator Interface

Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.

LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

Operator Interface Features

Convenient and extensive operator information is provided using a logical, menu-driven display

Multiple automatic and manual diagnostics for maintenance reduction

Alarm and Trouble History Logs (up to 1250 entries for each, 2500 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer

Convenient PC programmer label editing Password access control

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priority 2 AlarmSYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

EnableOn

Arm

DisableOff

DisarmAuto

LampTest

MoreInfo

Menu

Previous

Next

3 S4100-0100-13 1/2016

Page 38: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Overview. The 4100ES EPS power supply with IDNet 2 Module provides addressable initiating device and IDNAC addressable notification appliance Signaling Line Circuits (SLCs) that supervise wiring connections and the individual device/appliance communications status on their SLC. With these 2-wire SLCs, initiation, monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches; and notification appliances such as strobes and horns can communicate their identity and status and receive fire alarm system control. Additional interface modules include circuit isolators, conventional IDC zone adapters, and interface to other system circuits such as fans, dampers, and elevator controls.

IDNet Addressable Device Operation

Each addressable device on an IDNet communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation is available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuits for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel. With addressable devices, the location and status of the connected device is monitored and logged, and displayed on the operator interface LCD and on remote system annunciators with each device having its own 40 character custom label for precise identification.

TrueAlarm Addressable Sensor Operation

Addressable initiating device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.

TrueAlarm Addressable Sensor Reference

TrueAlarm Photo Sensor with Base

TrueAlarm Photo/Heat

Sensor in CO Base

Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read (or downloaded as a report) and compared to the alarm threshold directly in percent.

CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, used in LED/Switch modes and custom control, and can be made public for communication across a fire alarm Network. (refer to data sheet S4098-0052 for details)

TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius.

TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4100ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.

Diagnostics and Default Device Type

Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and end of life.

Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.

IDNet Addressable Device Wiring Reference

IDNet Addressable Channel Capacity. The CPU bay standard power supply (EPS) provides an IDNet 2 Module providing a signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. IDNet 2 and IDNet 2+2 Module SLCs are isolated from other system reference voltages to reduce common mode noise interaction with adjacent system wiring. Additional 250 address IDNet 2 or IDNet 2+2 Modules are available. IDNet 2 and IDNet 2+2 SLC Wiring Specifications Maximum Distance from Control Panel per Device Load

1 to 125 4000 ft (1219 m); 50 ohms

126-250 2500 feet (762 m); 35 ohms

Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 12,500 ft (3.8 km); 0.60 µF

Maximum Capacitance Between IDNet 2 Channels 1 µF

Loading per device 0.8 mA supv., 1 mA alarm; 2 mA per activated device LED

Wire Type and Connections Shielded or unshielded, twisted or untwisted wire*

Connections Terminals for 18 to 12 AWG (0.82 mm2 to 3.31 mm2)

IDNet 2 and IDNet 2+2 Module Compatibility: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2 sensors * Some applications may require shielded wiring. Review your

system with your local Simplex product supplier.

4 S4100-0100-13 1/2016

IDNet Addressable Device and IDNAC Addressable Notification Appliance Control

Page 39: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Addressable notification appliance communications include operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible (S/V) notification appliances. (S/V appliances require separate speaker wiring.) IDNAC SLC addressable communications allow each horn and strobe to be individually controlled using a single two-wire circuit, confirms the wiring connections to the individual notification appliance’s electronic circuit, and confirms communications between each appliance and the fire alarm control panel. Addressable communications increases supervision integrity versus conventional notification systems by providing supervision beyond the circuit wiring to each individual appliance and by constantly verifying the ability of each appliance to communicate with the control panel. Individual Appliance Status and Settings. The fire alarm control panel monitors and records each addressable notification appliance status, type of appliance, and its configured appliance settings. A fault in any individual appliance automatically reports a trouble condition to the control panel.

TrueAlert ES Addressable Appliance Reference

A/O (horn) V/O (strobe) A/V (horn/strobe)

Virtual NACs Provide Control Convenience. For control convenience, IDNAC notification appliances can be grouped into Virtual NACS (VNACs) for group control, grouping that can be made across SLCs, not defined by their wiring connection.

Panel Control Convenience. Applicable operation settings for each appliance can be programmed without having to replace appliances or remove them from the wall or ceiling. An appliance’s VNAC notification zone can be easily changed through programming without having to add additional circuits, conduit, and wiring. Audible and visible appliances for non-Fire Emergency Communications notification can be programmed to operate separately on the same pair of wires as the fire alarm notification appliances. The result is lower installation, retrofit, and overall life-cycle cost of ownership compared with traditional conventional notification systems.

Installation, Retrofit, and Life-Cycle Cost Benefits. With each addressable appliance capable of being controlled separately on the same two-wire IDNAC SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T-tapped” allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency.

Location Information, Diagnostics and Troubleshooting. Each addressable notification appliance has its own 40 character custom label to identify the location of the appliance and to aid in troubleshooting fault conditions. In conventional notification systems, conventional appliances are not capable of communicating with the control panel. Fault reporting on a conventional system is limited to the circuit wiring and the entire area (zone) covered by appliances on the notification appliance circuit (NAC) making it much more difficult and costly to locate and correct the source of a

problem. Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired, and using the TrueAlert ES Appliance Self-Test feature provides detailed performance verification per appliance.

TrueAlert ES Appliance Self-Test Operation

On-Board Test Sensors. TrueAlert ES appliances are equipped with on-board sensors to detect strobe and/or horn output allowing efficient and unobtrusive Self-Testing. When Automatic Self-Test is initiated from the control panel, each appliance within the selected VNAC group will briefly operate and then report its Self-Test status to the control panel, all within several seconds. Silent Self-Test can be selected to test only visible appliance if desired. The control panel is in a trouble condition during testing and in the event of an alarm, Self-Test is automatically terminated. Additionally, Automatic Self-Test can be scheduled to occur at a convenient time on a regular basis. (Requires version 2.03.01 or higher software.) Automatic Self-Test results are communicated to the control panel with a time and date stamp and are stored in memory. Results are viewable at the front panel display and printed reports can be generated from the panel service port. (See sample reports on page 11.) Individual Self-Test is selected from the control panel when individual appliances need to be observed to operate. Each appliance in the selected VNAC group will turn on its LED until individually activated by applying a magnet. After performing the individual test, the appliance LED turns off to indicate completion. Results are recorded the same as during the automatic test.

IDNAC SLC Hardware Reference

EPS Power Supplies provide three, 3 A IDNAC SLCs for control and power to TrueAlert ES and TrueAlert addressable notification appliances. Both power supplies incorporate an efficient switching design that provides a regulated output of 29 VDC, even during battery operation. With 29 VDC minimum output at the panel, addressable notification SLCs can support wiring distances 2 to 3 times farther than available with conventional notification, or support more appliances per SLC, or work with smaller gauge wiring, or combinations of these benefits, all resulting in installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.

IDNAC SLC Appliance Wiring Reference

IDNAC SLC Capacity: Up to 127 addresses and up to 139 unit loads (appliances are typically one unit load, devices such as Isolators may require more than one load, refer to individual device data sheet for specific information) Recommended wire type UTP, unshielded twisted pair Maximum wire length allowed with “T-Taps” for Class B wiring, per SLC

10,000 ft (3048 m)

Maximum wire length per SLC to any appliance 4000 ft (1219 m)

Appliance Supervisory Current 1 unit load = 0.8 mA per appliance

Wiring connections Terminals for 18 to 12 AWG (0.82 mm2 to 3.31 mm2)

Installation Instructions (see for more information) 579-1015

5 S4100-0100-13 1/2016

IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification

Page 40: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Master Controller and Motherboard: Mounts in Slot 2 of a two slot motherboard and provides

one Class B or Class A, RUI+ isolated communications channel with earth fault detection

RUI+ isolated communications controls up to 31 remote devices per master controller at up to 2500 ft (762 m) for single run, or 10,000 ft (3048 m) total if wiring is Class B and T-tapped; if more distance is required, up to four total RUI channels are supported; add up to three 4100-1291 RUI Expansion Modules (4100-1291 provides unisolated RUI communications)

Compatible RUI+ remote equipment includes: MINIPLEX transponders, 4603-9101 LCD Annunciators, and 4100 Series 24 I/O and LED/Switch modules

RUI Expansion Module 4100-1291 is also compatible with the RUI+ remote equipment listed above; and is required for control of 4602 Series LED/Switch and I/O Annunciator modules, including 4602-9101 Status Command Units (SCU), and 4602-9102 Remote Command Units (RCU); (refer to data sheet S4602-0001)

Open slot space on the left of the CPU motherboard is available for either another dual slot motherboard, or for one or two block modules (refer to diagram on page 2)

Slot 1 of the motherboard is primarily for the 4100-6078 Network Interface Board with media modules

EPS (Enhanced Power Supply) with IDNet 2 Module Details: (see page 9 for specifications) Rating is 9 A output with “Special Application” appliances Outputs are power-limited, except for the battery charger Provides system power, battery charging, auxiliary power,

earth detection, on-board electrically isolated IDNet 2 Module with 250 point SLC, three on-board 3 A IDNAC SLCs, and provisions for either an optional City Connect Module or an optional Alarm/Supv/Tbl Relay Module

IDNet 2 Module SLC Output provides Class B or Class A communications for up to 250 addressable devices with dual short circuit isolating loop outputs (see details on page 4)

Note: The “IDNet 2 Module” replaced the “IDNet 1+ Module” and the term “EPS with IDNet 2 Module” replaces the term “EPS+”

EPS with IDNet 2 Module Details (Continued): DCAI (Dual Class A IDNAC Isolator) Module creates

two Class A outputs from one IDNAC SLC Class B Input; up to two can be connected to one IDNAC SLC, with up to 6 total per EPS; total Class A output loop current is limited to the 3 A rating of the IDNAC SLC

Battery Charger is dual rate, temperature compensated, and charges up to 50 Ah sealed lead-acid batteries mounted in the battery compartment (33 Ah for single bay cabinets); also is UL listed for charging up to 115 Ah batteries mounted in an external cabinet (see data sheet S2081-0012 for details)

Battery and Charger Monitoring includes battery charger status and low or depleted battery conditions; status information provided to the master controller includes analog values for: battery voltage, charger voltage and current, actual system voltage and current, and individual IDNAC SLC currents

Low Battery Cutout is selectable for each EPS power supply, Canadian models are shipped selected, other models are shipped unselected

2 A Programmable Output: Select for conventional non-synchronous NAC

operation to provide supervised reverse polarity for sounder base power, Suppression Release Peripheral (SRP) power, or other coded NAC operation requirements

Select for Auxiliary (AUX) operation for sounder base power, 4-wire detector power, or door holder; supervised AUX operation does not require an end-of-line relay to provide Power-Limited operation

EPS Mounted Optional Modules (select one): City Connect Module (4100-6031, with disconnect

switches, or 4100-6032, without disconnect switches) can be selected for conventional dual circuit city connections

Alarm Relay Module (4100-6033) provides three Form C relays that are used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC

6 S4100-0100-13 1/2016

Master Controller and Expansion Bay SelectionModel Model Type and Listing Description Current

4100-9311 120 VAC, 50/60 Hz Input UL 4100ES Master Controller Assembly with LCD display, operator interface and RUI+ isolated output communications interface; 9 A EPS (Enhanced Power Supply) with battery charger, electrically isolated 250 point IDNet 2 Module, three Class B IDNAC SLCs, one 2 A output configurable for Auxiliary Power or Simple NAC operation and expansion slot for City Circuit or Alarm/Supv/Tbl Relay option

Without IDNet devices: Supervisory = 425 mA Alarm = 735 mA

Note: Master Controller current does not subtract from 9 A output rating

4100-9312 English 120 VAC, 50/60 Hz Canadian ULC

4100-9313 French

4100-9511 220-240 VAC, 50/60 Hz Input UL

4100-9331 120 VAC, 50/60 Hz input UL 4100ES Master Controller Assembly ; same as above models except without LCD Display and Operator Interface

4100-9332 120 VAC, 50/60 Hz input, Canadian, English ULC

4100-2300 Expansion Bay Assembly; order for each required expansion bay 4100-2303 Slot Module Stabilizer Bracket, used when expansion bays have style modules

(Continued on next page)

Master Controller Selection Information

Standard CPU Bay Module Details

Page 41: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

7 S4100-0100-13 1/2016

Communication Modules Model Description Size Supv. Alarm

4100-6078 For Master Controller; mounts in Slot 3 Modular Network Interface; each requires two media modules (below)

1 Slot 46 mA 46 mA

4100-6061 For Redundant Master Controller 1 Slot 46 mA 46 mA

4100-6056 Wired Media Module Select two media cards as required; mounts on 4100-6078 or 4100-6061; Class B or Class X operation

N.A. 55 mA 55 mA

4100-6057 Fiber Optic Media Module N.A. 25 mA 25 mA

4100-6047 Building Network Interface Card (BNIC), refer to data sheet S4100-0061 for details 2 Blocks 291 mA 291 mA

4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network Interface Card, requires telephone line connection N.A. 60 mA 60 mA

4100-1291 Remote Unit Interface Module (RUI, unisolated); up to 3 maximum per control panel 1 Slot 85 mA 85 mA

4100-6031 Select one per EPS (Note: maximum one City Circuit module per panel)

City Circuit, with disconnect switches N.A. 20 mA 36 mA

4100-6032 City Circuit, w/o disconnect switches N.A. 20 mA 36 mA

4100-6033 Alarm/Supv/Tbl Relay, 3 Form C relays, 2 A @ 32 VDC N.A. 15 mA 37 mA

4100-6046 Dual Port RS-232 standard interface (single block) 3 maximum RS-232 Modules per panel

1 Block 60 mA 60 mA

4100-6038 Dual Port RS-232 with 2120 interface (slot module) 1 Slot 132 mA 132 mA

4100-6079 SafeLINC Internet Interface (refer to data sheet S4100-0062 for details) 2 Blocks 145 mA 145 mA

4190-6104 TrueInsight Remote Monitoring Module (refer to data sheet S4100-0063 for details) Side Mt. 62 mA 73 mA

4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA

4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA

4100-6048 VESDA Aspiration System Interface (refer to data sheet S4100-0026 for details) 1 Slot 132 mA 132 mA

4100-6080 DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs Side Mt. 30 mA 40 mA

Additional Enhanced Power Supplies, Expansion Power Supply, and Accessories (for additional non-addressable Power Supplies, refer to data sheet S4100-0031)

Model Voltage/Listing Description Size Supv. Alarm

4100-5311 120 VAC UL & ULC

Expansion EPS with IDNet 2 Module; 9 A Expansion Power Supply (EPS) with battery charger, electrically isolated 250 point IDNet 2 Module, three Class B IDNAC SLCs, one 2 A output configurable for Auxiliary Power or Simple NAC operation, and expansion slot for City Circuit or Alarm/Supv/Tbl Relay option; 120 VAC model has selectable low battery cutout

4 Blocks Right Side

225 mA 490 mA

4100-5313 220-240 VAC UL add IDNet device currents separately

4100-5325 120 VAC UL & ULC Enhanced Power Supply (EPS); 9 A EPS, functionally identical

to the Expansion EPS except without the IDNet 2 Module 4 Blocks

Right Side

125 mA 220 mA 4100-5327 220-240 VAC UL

4100-5101 120 VAC UL Expansion Power Supply (XPS); 9 A output, 3 built-in Class A/B conventional (non-addressable) 3 A NACs that can also be selected as 2 A auxiliary power output, 2 A separate auxiliary power output; without battery charger; Canadian model has low battery cutout

2 Blocks 50 mA 50 mA 4100-5103 120 VAC, Canadian ULC

4100-5102 220-240 VAC UL

4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA

4100-6103

Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit isolation between each Class A or B output circuit; connect up to two DCAI Modules per IDNAC SLC input up to a maximum of 6 DCAI Modules per EPS; each isolated output SLC used requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum

1 Block 8.3 mA 18.5 mA

4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum

4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads

4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet 4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from EPS

System Option for Seismic Compliance Model Description 4100-7912 System option for Seismic compliance, provides additional stabilizer brackets required for legacy style cards

Module Selection is continued on next page

Module Selection Information

dthurston
Line
Page 42: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

8 S4100-0100-13 1/2016

Addressable Interface Modules (Note: Total of initiating SLCs per CPU, including VESDA Interface, is 30) Model Description Supv. Alarm

4100-3109*

IDNet 2 Module, 250 point capacity; electrically isolated output with two short circuit isolating Class B or Class A output loops, 1 block; standard on EPS with IDNet 2 Module; alarm currents for 50 and above devices includes 20 device LEDs in alarm

no devices 50 mA 60 mA 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA 250 devices 250 mA 350 mA

4100-3110*

IDNet 2+2 Module, 250 point capacity; electrically isolated output with four short circuit isolating Class B or Class A output loops, 1 block; mounts in expansion bay or available master controller bay module locations only, not applicable for EPS mounting; alarm currents for 50 and above devices includes 20 device LEDs in alarm

no devices 50 mA 60 mA 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA 250 devices 250 mA 350 mA

4100-3111* IDNet Short Circuit Isolating Loop Output Module; mount up to two on a 4100-3109 module; for use with 4100-3109 modules in expansion bays or available master controller bay module locations only; not applicable for mounting on a 4100-3109 mounted on an EPS; this option is for aftermarket field installation only

4100-3112

Four Loop IDNet Master Controller; for the Master Controller Assemblies listed on page 6, this option moves the standard IDNet 2 Module from the Master Controller EPS to an available block space in the master controller bay and adds 2, 4100-3111 IDNet Loop Output Modules; requires selection of Factory Built Option 4100-7905; current requirements remain the same

*Note: Loading per IDNet device (no LEDs on) = 0.8 mA supervisory and 1 mA alarm. Each IDNet 2 and IDNet 2+2 Short Circuit Isolating Loop Output can be individually controlled for system diagnostics and can be assigned a public point for Fire Alarm Network annunciation.

Relay Modules; Nonpower-limited (for mounting in expansion bay only, refer to location reference on page 10) Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm

4100-3202 4 DPDT w/feedback 10 A @ 250 VAC 10 A @ 250 VAC 2 Slots 15 mA 175 mA 4100-3204 4 DPDT w/feedback 2 A @ 30 VDC/VAC 1/2 A @ 30 VDC/120 VAC 1 Block 15 mA 60 mA 4100-3206 8 SPDT 3 A @ 30 VDC/120 VAC 1-1/2 A @ 30 VDC/120 VAC 1 Block 15 mA 190 mA

Current Calculation Notes: 1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered

by panel power supplies. 2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel SLC and

NAC loads and all external loads powered from panel power supplies.

End User Programming Software (requires 4100-8802) Model Description

4100-8802 Programming Software (select)

End User Programming Software Selection (select maximum of one each from below) Model Description

4100-0292 Custom Labels Editing; allows editing of 40 Character Custom Labels for non-system user points

4100-0296 Access Level/Passcode Editing; allows user to re-assign Access Levels and Passcodes for each display function; Acknowledge, Alarm Silence, System Reset, Point Enable/Disable, WALKTEST Enable/Disable, Clear History Logs, Change Time & Date, etc.

4100-0295 Port Vectoring Setup and Control; Allows vectoring of events to PC Annunciator, Printers, LCD Annunciators, etc.

4100-0298

WALKTEST Configuration Setup and Control; Allows user to create or edit WALKTEST groups used to test system initiating devices and signals by a single person, these groups allow an inspector to conduct a one-person WALKTEST in a specific area of a building (or different buildings), and limit the activation of the building signals to only the intended area; up to 8 WALKTEST groups are supported

Miscellaneous Accessories Model Description

4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay 4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules 4100-9856 4100ES Canadian French Appliqué Kit; Simplex, 4100ES, Contrôle Incendie 4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES 4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES 4100-6029 Smoke Management Application Guide; required for UUKL listing

4100-6034 Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM

2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)

Module Selection Information (Continued)

Page 43: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Input Power

Enhanced Power Supplies (EPS)

120 VAC Models 4.6 A maximum @ 102 to 132 VAC, 50/60 Hz

220-240 VAC Models 2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC

Battery Input Rating 12 A maximum @ 24 VDC (during battery operation)

Expansion Power Supplies (XPS) 120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz

220-240 VAC Models 2 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC

Power Supply Output Ratings for EPS

Total Power Supply Output Rating

9 A output for “Special Application” appliances Note: The 9 A output rating of the EPS was determined such that optional module currents, and external device and appliance currents can be directly added together, not to exceed 9 A total.

Output switches to battery backup during mains AC failure or brownout conditions

IDNAC SLC Ratings 3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; DC-DC converter circuit is >92% efficient over operating range

IDNAC SLC Wiring

Output terminals are rated for 18 to 12 AWG with duplicate output terminals rated for two wires each, allowing up to four (4) Class B branch circuit T-taps to be made in the cabinet; additional T-taps may be made in external wiring junction cabinets or boxes

Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)

Compatible Special Application Appliances Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances

Battery Charger Ratings for EPS (sealed lead-acid batteries)

Battery capacity range UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries

Charger characteristics and performance

Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527

Power Supply Output Ratings for XPS (nominal 28 VDC on AC; 24 VDC on battery backup)

Total Power Supply Output Rating

Including module currents and auxiliary power outputs; NAC outputs are rated 9 A output for “Special Application” non-addressable appliances; 4 A output for “Regulated 24 DC” power (see details below); 6 A output with each NAC selected as auxiliary power output

Output switches to battery backup during mains AC failure or brownout conditions Auxiliary Power Tap 2 A maximum

Rated 19.1 to 31.1 VDC NACs Programmed for Auxiliary Power

2 A maximum per NAC; 5 A maximum total

Special Application Appliances

Simplex horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative for compatible appliances)

Regulated 24 DC Appliances Power for other UL listed appliances; use associated external synchronization modules where required

Environmental Operating Temperature 32° to 120°F (0° to 49° C)

Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Additional Technical Reference

Description Document Description Document

ES Installation Instructions 574-848 IDNet 2 and 2+2 Module Installation Instructions 579-1169

ES Operating Instructions 579-197 EPS Installation Instructions 579-1015

DCAI Module Installation Instructions 579-1029

9 S4100-0100-13 1/2016

General Specifications

Page 44: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Size Definitions: 1 Block = 4” W x 5.65” H (102 mm x 144 mm); (often

called 4 x 5 modules) 1 Slot = 2” W x 11.3” H (51 mm x 287 mm), typically a

motherboard with daughter card

NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

10 S4100-0100-13 1/2016

Expansion Bay Module Loading Reference

Mounting and CPU Bay Module Reference (* indicates supplied modules)

Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2

Expansion Bay Chassis

Block A

Block B

Block C

Block D

Block E

Block F

Block G

Block H

Page 45: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Service Port Page 1

REPORT 10 TrueAlertES Self-Test Report 12:34:56pm WED 03-DEC-14

Point ID Custom Label Date Visual Audible T1-1-1 VO FIRST FLOOR (up to 40 characters) 03-DEC-14 NO OUT N/AT1-2-5 AV FIRST FLOOR EAST WING 03-DEC-14 NO OUT NORMALT7-3-55 AO SECOND FLOOR EAST WING 03-DEC-14 N/A NO OUTT8-2-45 AV SECOND FLOOR ROOM 29 03-DEC-14 NOT TST N/AT8-2-60 AV SECOND FLOOR ROOM 22 03-DEC-14 NORMAL NORMALT1-2-4 AO FIRST FLOOR ROOM 17 03-DEC-14 N/A UNSUPPTRUEALERT_ES SELF-TEST REPORT COMPLETED Press RETURN for next Screen OR CTRL-X to abort

Results Description: NORMAL = works correctly NO OUT = No Output, no light or sound was detected NOT TST = no result; either the appliance did not return a result before the test ended or the test was conducted as silent (strobes only) and audible appliance was not activated N/A = not applicable (no strobe on audible only, etc.) UNSUPP = appliance not compatible with Self-Test (TrueAlert addressable appliance not TrueAlert ES addressable appliance) Note: Additional TrueAlert ES Self-Test information is detailed in ES Operating Instructions 579-197 shipped with the panel.

Service Port Page 1

REPORT 10 TrueAlertES Self-Test Report 12:34:56pm WED 03-DEC-14

Point ID Custom Label Date Visual Audible T1-1-1 VO FIRST FLOOR 03-DEC-14 NO OUT N/AT1-2-5 AV FIRST FLOOR EAST WING 03-DEC-14 NO OUT NORMALT1-2-6 AV FIRST FLOOR NORTH ENTRANCE 30-OCT-14 NO OUT NORMALT7-3-55 AO SECOND FLOOR EAST WING 03-DEC-14 N/A NO OUTT8-2-45 AV SECOND FLOOR ROOM 29 03-DEC-14 NOT TST N/AT1-1-11 AV FIRST FLOOR SOUTH ENTRANCE 30-OCT-14 NORMAL NORMALT8-2-60 AV SECOND FLOOR ROOM 22 03-DEC-14 NORMAL NORMALT1-2-4 AO FIRST FLOOR ROOM 17 03-DEC-14 N/A UNSUPPT1-2-7 AO FIRST FLOOR ROOM 12 30-OCT-14 N/A UNSUPPT8-3-43 AV SECOND FLOOR ROOM 25 30-OCT-14 UNSUPP UNSUPPTRUEALERT_ES SELF-TEST REPORT COMPLETED Press RETURN for next Screen OR CTRL-X to abort

CUSTOM LABEL 4-1-2 AV POINT ADDRESS: 4-1-2 Type: AV CARD: 4 CHANNEL: 1 DEVICE: 2 EXTENDED POWER SUPPLY UNIT NUMBER: 2 RUI NUMBER: LOCAL PRIMARY STATUS NORMAL AUDIBLE GROUP CONFIG: 0 0 0 VISUAL GROUP CONFIG: 0 0 0 STYLE: INDOOR OPERATION: GENERAL EVAC CANDELA RATING 15 CD COLOR LENS YES TONE TYPE BROADBAND CODING TYPE TEMPORAL VOLUME HIGH LAST TEST TIME: MON 02-JUN-14 01:00 AM LAST VISUAL TEST: NORMAL LAST AUDIBLE TEST: NORMAL LAST TEST VOLUME: NORMAL DEVICE TEST TROUBLE: NORMAL

11 S4100-0100-13 1/2016

TrueAlert ES Appliance Self-Test Last Test Results Report Example

TrueAlert ES Appliance Self-Test All Test Results Report Example

TrueAlert ES Appliance Self-Test Individual Appliance Report Example

Page 46: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0100-13 1/2016 www.simplex-fire.com

© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.

Subject Data Sheet Subject Data Sheet Introducing the 4100ES S4100-0060 Fire Alarm Network Overview S4100-0055 4100ES Enclosures S4100-0037 Network Communications S4100-0056 4100ES Audio and Firefighter Phone Modules S4100-0034 Network Display Unit (NDU) S4100-0102 LED/Switch Modules & Printer S4100-0032 Addressable Device Compatibility S4090-0011 Remote Annunciators S4100-0038 4009 IDNAC Repeater S4009-0004 MINIPLEX Transponders S4100-0103 Remote Battery Charger S4081-0002 Building Network Interface (BNIC) S4100-0061 SafeLINC Internet Interface S4100-0062 InfoAlarm Command Center S4100-0101 4100ES Panels for Conventional Notification S4100-0031 Graphic I/O Modules S4100-0005 TrueAlarm Sensors S4098-0019 TrueInsight Remote Service S4100-0063 Remote IDNet Isolator S4090-0005 Agent Release Applications S4100-0040 TrueAlarm IDNet Isolator Base S4098-0025 TrueAlert ES Audible Only Appliances S49AO-0001 TrueAlert ES Weatherproof Appliances, UL Listed S49WP-0001 TrueAlert ES Visible Only Appliances S49VO-0001 TrueAlert ES Weatherproof Appliances, ULC Listed S49WP-0002 TrueAlert Appliance/IDNAC SLC Isolator S4905-0001 TrueAlert ES Emergency Communications

Appliances with Color Lenses S49LENS-0001 TrueAlert ES Audible/Visible Appliances S49AV-0001

Additional 4100ES Data Sheet and Related Product Reference

Page 47: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Simplex® 4100ES Box and door options: Boxes are available sized for one, two, or three

equipment bays, each with a battery bay located at the bottom

Colors include platinum or red

Doors are glass front with modular dress panels, or solid

Models are available with box and door combined for single package shipping, or packaged separately

Enclosures are NEMA 1 rated; wall mount enclosures are also IP30 rated

Refer to individual 4100ES data sheets for product application listings (see list on page 2)

Door and dress panel selection is coordinated with cabinet function: Glass doors with modular dress panels provide

visibility of annunciation and interface modules for Control Panels, Network Display Units (NDU), and Remote Annunciators

Solid doors are for MINIPLEX Transponders and utility function cabinets where module visibility is not required

4100ES Enclosure details: Latching dress panels easily lift off for internal access

Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required

Alignment markers are provided at the top and bottom of each box side for 6” (152 mm) or 4” (102 mm) wall studs

Knockout screw/nail holes are supplied for semi-flush mounting

Upright cabinet rack packaging reference: For use with Bud Industries Inc. special cabinet rack

model number 45964

Refer to page 2 for cabinet rack listing * For 4100ES one, two, and three bay cabinets with associated equipment: Products are

listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

CAUTIONDIS CON NECTA.C. PO W ER

ANDB ATT ERYB EF ORE

S ERV ICING

4100ES One Bay Cabinets

On

Of f

Auto

On

Off

Auto

On

Of f

Auto

On

Off

Auto

On

Of f

Auto

On

Off

Auto

On

Of f

Auto

On

Off

Auto

P ress ACK located under flashing indicator.Repeat operat ion until all events are acknowledged.Local tone will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /ALARMS

Fire Alarm Priori ty 2 AlarmS YSTEM WARNINGS

S upervisory Trouble Alarm Silenced

Emergency Operating Instructions

A larm or Warning Condition

H ow to Ac knowledge / Vie w Ev ents

How to Silence Building SignalsS ystem indicator fl ashing. Tone On. P ress Alarm Silence.

How to Res et Syste mP ress System Reset.P ress Ack to s ilence tone device.

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR0 DEL

En ter C/Exit

Fi re AlarmAck

Priority 2Ack

S upvAck

TroubleAck

AlarmSilence

SystemReset

E ventTime

Enable On Arm

Disable OffDisarm

Auto LampTest

MoreInfo

Menu

Pre vious

Ne xt

CAUTIONDIS CO NNE CTA .C. P OW E R

A NDB AT TE RYB E FOR E

S ER VICING

4100ES Two Bay Cabinets

4100ES Three Bay Cabinets

Cabinet Rack Enclosure (shown with door open)

Fire Control Panels UL, ULC, CSFM Listed; FM Approved; Cabinet Reference; Boxes, Doors, MEA (NYC) Acceptance* Dress Panels, Rack Mounting, and Accessories

S4100-0037-14 12/2014

Page 48: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

2 S4100-0037-14 12/2014

Note: Door keys are shipped with system Master Controller, see Miscellaneous Accessories below for additional keys

Combined Box and Door Selection (select if box and door are to be shipped together) Description Platinum 1 Bay Platinum 2 Bay Platinum 3 Bay Red 1 Bay Red 2 Bay Red 3 Bay Box with Glass Door and Dress Panel 2975-9444 2975-9445 2975-9446 2975-9441 2975-9442 2975-9443 Box with Solid Door 2975-9450 2975-9451 2975-9452 2975-9447 2975-9448 2975-9449

Separate Box and Door Selection (select if boxes and doors are required to be shipped separately) Description Platinum 1 Bay Platinum 2 Bay Platinum 3 Bay Red 1 Bay Red 2 Bay Red 3 Bay Box 2975-9438 2975-9439 2975-9440 2975-9407 2975-9408 2975-9409 Glass Door and Dress Panel 4100-2104 4100-2105 4100-2106 4100-2124 4100-2125 4100-2126 Solid Door 4100-2114 4100-2115 4100-2116 4100-2134 4100-2135 4100-2136

Cabinet Rack Mounting (refer to page 4 for additional details) Model Description #45964 Listings

#45964, from Bud

Industries Inc.

Special upright cabinet rack for 4100ES; 19” (483 mm) E.I.A.; gray texture; includes front polycarbonate door and rear louvered door, both keyed with Simplex “B” keys

UL and ULC listed only as of document revision date; cabinets are listed with the Simplex 4100ES product line

4100-2140 Master Controller Rack Mount Kit, one required per master controller Master Controller and Option Bays each require 9 Rack Units; 15.75” height (400 mm) 4100-2145 Option Bay Rack Mounting Kit, one required per expansion bay

4100-2144 Power Distribution Module (PDM) Rack Mount Kit, order PDM separately per system voltage, one required per cabinet rack

Power Distribution Modules Model Voltage Description

4100-0634 120 VAC Power Distribution Module (PDM); select per system voltage; one required per 4100ES box or cabinet rack 4100-0635 220/230/240 VAC

Miscellaneous Accessories Model Description

252-019 Door key, one is shipped with system Master Controller, order for replacement or when extra keys are needed; (Simplex “B” key)

4100-9856 Canadian French Appliqué Kit, for 1, 2, or 3 bay sizes

4100-9857 4100ES Appliqué Retrofit Kit, for 1, 2, or 3 bay sizes; use to identify 4100ES features when new door is not used; included with Master Controller Upgrade kits as detailed on data sheet S4100-0031

4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES

4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES

4100-9835 Termination and Address Label Kit, for module marking NOTE: One kit is supplied for each cabinet; order this if required for additional field module installation

4100-9837 Green LED Power-on Indicator Kit, required for ULC listing of MINIPLEX transponder Mounts using knockout provided in solid door

2975-9813 Platinum semi-flush box trim 1 7⁄16” (37 mm) wide, four corners and trim pieces for top, bottom, and sides 2975-9812 Red semi-flush box trim

Battery Reference Model Capacity Model Capacity Battery Notes

2081-9272 6.2 Ah 2081-9287 25 Ah 1. Sealed lead-acid batteries, 12 VDC each; two required per battery location.

2. Battery selection is required if batteries are internal. 3. Select one size per battery set 4. Refer to data sheet S2081-0006 for battery details.

2081-9274 10 Ah 2081-9276 33 Ah 2081-9288 12.7 Ah 2081-9296 50 Ah 2081-9275 18 Ah

Battery Accessories Model Description

4100-0650 Battery Shelf, required for 50 Ah batteries

4100-5128 Battery Distribution Terminal Block, mounts to side of box, required for all close-nippled cabinets unless cabinet receives all power from power supplies and batteries located in the adjacent cabinet

Enclosure Selection Chart (refer to pages 3 and 4 for dimensions)

dthurston
Line
dthurston
Line
dthurston
Line
Page 49: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Subject Data Sheet Subject Data Sheet 4100ES Panels with EPS Power Supplies S4100-0100 Network Display Unit (NDU) with EPS

Power Supplies S4100-0102 4100ES Basic Panel Modules and Accessories S4100-0031 MINIPLEX Transponders with EPS Power Supplies S4100-0103 Network Display Unit (NDU) S4100-0036 MINIPLEX Transponders S4100-0035 Remote Annunciators S4100-0038 LED/Switch Modules S4100-0032 InfoAlarm Command Center S4100-0045 4100ES Audio/Phone Modules S4100-0034 Remote Battery Charger S4081-0002

3 S4100-0037-14 12/2014

Door thickness4-3/4" (121 mm)

Exposed cabinet forsemi-flush mounting

1/2" (12.7 mm) minimum

24" (610 mm)

11-11/16"(296 mm)

6-29/32"(175 mm)

4" stud

6" stud

Knockout screw/nail holes (for semi-flush mounting)

Stud alignment markers, each side

Wall board reference for semi-flush mounting, 6" stud

Optional semi-flushtrim kit reference

Front view, box outline without door Side view with door attached

2 Bay height = 40" (1016 mm)

3 Bay height = 56" (1422 mm)

1 Bay height = 22" (559 mm)

Doors can be hinged left or right

Wall Mounted Enclosure Installation Reference

NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780. For additional installation information refer to Installation Instructions 579-117.

Additional Data Sheet Reference

Page 50: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

Front View Side View Rear View

Type Upright cabinet rack for exclusive use with Simplex 4100ES Fire Alarm Products Supplier Order from Bud Industries Inc. (www.budind.com) Model Number 45964

Outside Dimensions Height 69-7/8” (1775 mm) Width 24-1/16” (611 mm) Depth 22” (559 mm)

Color Gray texture Panel Space Width 19” E.I.A. (483 mm)

Front Door Surface mount with 1/8” thick (3.18 mm) smoke gray polycarbonate, locked with Simplex “B” key, hinged on left of cabinet

Rear Door Ventilated top and bottom, locked with Simplex “B” key Sides Side panels are removable from the inside for rack-to-rack mounting Bottom Pan attached for battery mounting Levelers Includes 4 stem levelers on bottom Installation Instructions 579-229

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0037-14 12/2014

www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Console Package Reference

Cabinet Rack Specifications

Page 51: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Rechargeable, sealed lead-acid batteries: Lead-calcium grid structure with immobilized

electrolyte in absorbent separator

Low maintenance with no need to add water

Low self-discharge characteristics

One-piece, high impact polystyrene cell cover with high reliability dual seal construction

UL 924 recognized pressure relief valves Available in a variety of capacities: Batteries for internal mounting range from 6.2 Ah up to

50 Ah, depending on control panel cabinet size

Larger batteries, up to 110 Ah, mount in external battery cabinets with models available with internal chargers

Battery cabinets with chargers: Battery cabinets with charger communicate with their

connected fire alarm control panel and are available for 4100ES/4010ES/4100U Series and 4010 Series panels

Description

Simplex® rechargeable sealed-lead acid batteries provide reliable and repeatable discharge and recharge characteristics for use in fire alarm and other systems applications. They are designed with immobilized electrolyte in an absorbent separator, allowing them to provide rated capacity on the first cycle.

Because of their sealed construction, packaging is allowed within the system electronics enclosure (see illustration on page 2). When this is applicable, the quantity of system cabinets and the battery wiring distances are both minimized. Where required, external battery cabinets can be close-nippled to the control panel to house larger batteries with battery chargers available in some battery cabinet sizes.

Battery Details

Charging. These batteries are intended to be used with compatible Simplex battery chargers.

Series Connections. These batteries are required to be connected in series to produce 24 V system voltage. Battery sets must be of identical voltage, model number, appearance, and approximately the same date of manufacture for proper operation.

Testing. Battery capacity testing is recommended to be performed by using a sealed lead-acid battery tester designed to withdraw a minimum of battery charge. The preferred tester applies a variety of amplitude and duration controlled test pulses that compares terminal voltage against those predicted for the specific battery size. (Testing is available through your local Simplex product supplier.)

Compatible Sealed Lead-Acid Batteries can be Installed Inside Fire Alarm Control Panel Cabinets

Remote Battery Cabinets are Available for Larger Battery Requirements

Battery Details (Continued)

Shipping. Sealed lead-acid batteries are shipped via ground or sea transportation only. They are not shipped via air.

Disposal. Battery chemicals and materials can be recycled. Refer to information shipped with the battery or on its case. Return to the battery manufacturer or to a similarly qualified battery processing facility for proper disposal.

Seismic Activity Applications. Battery brackets are available for systems tested for compliance with specific batteries. Please refer to data sheet S2081-0019 for details. * Refer to details on page 4 and to the referenced individual product data sheets for agency

listing status of battery cabinets and chargers. The batteries detailed in this document meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers as listed on page 3. Contact your local Simplex product supplier for proper battery selection per system requirements. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

Fire Alarm Control Panel Accessories Listings* System Batteries, Sealed Lead-Acid; with Applications Reference for Battery Cabinets, and Battery Cabinets with Charger

S2081-0006-21 12/2014

Page 52: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Actual appearance will vary with battery size.

2 S2081-0006-21 12/2014

Nominal Voltage Rating 12 Volts per battery

Discharge Rating 20 Hour Rate

Typical Charge/Discharge Cycles 100 to 150

Preferred Charge Temperature Range 60° F to 90° F (15.6°C to 32.2° C)

Quick connect or post type terminal(type varies with battery size)

Inner cover

Absorbent separator usedto immobilize electrolyte

Lead-calcium grids

Cell groupCell case (high impactpolystyrene)

Sealed outer cover

Vent holePotting material, black fornegative, red for positive(polarity is also clearlymarked with + and -)

Pressure relief valve

Semi-permeablemembrane separator

Battery Model Capacity @ 20 Hour Discharge Rate Width* Depth* Height with

Terminals Approximate

Weight* 2081-9272 6.2 Ah 6-1/8” (156 mm) 2-5/8” (67 mm) 4” (102 mm) 5.75 lbs (2.6 kg)

2081-9274 10 Ah 6” (153 mm) 4-1/16” (103 mm) 4” (102 mm) 9.2 lbs (4.2 kg)

2081-9288 12.7 Ah 6” (153 mm) 4” (102 mm) 4” (102 mm) 9 lbs (4.1 kg)

2081-9275 18 Ah 7-1/4” (184 mm) 3-3/8” (86 mm) 6-5/8” (168 mm) 14.3 lbs (6.5 kg)

2081-9287 25 Ah 6-5/8” (168 mm) 5” (127 mm) 7” (178 mm) 19.4 lbs (8.8 kg)

2081-9271 (rectangular case,

typically for service) 33 Ah 12-1/2” (318 mm) 3-3/8” (86 mm) 7-1/16” (179 mm) 26.6 lbs (12.1 kg)

2081-9276 (“square” case,

use for new) 33 Ah 7-3/4” (197 mm) 5-1/4” (133 mm) 6-3/4” (171 mm) 26.5 lbs (12 kg)

2081-9296 50 Ah 9” (229 mm) 5-1/2” (140 mm) 8-7/8” (225 mm) 41.8 lbs (19 kg)

2081-9279 110 Ah 11-3/16” (284 mm) 10-1/2” (267 mm) 9” (230 mm) 82 Lbs (37 kg)

* Dimensions and weight are per battery and are for reference only. Exact size may vary. Refer to the tables on page 3 for mounting compatibility. These batteries are 12 V each and series connected for 24 V system use.

NOTE: When wired in series for 24 V output, these batteries are to be of identical voltage, appearance, model number, and approximately the same date of manufacture.

Battery Construction Reference

Battery Size Specifications

General Battery Specifications

Page 53: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

3 S2081-0006-21 12/2014

Battery Cabinets without Chargers (connects to charger in panel)

Cabinet Panel Compatibility Battery

2081-927518 Ah*

2081-9287 25 Ah

2081-9271 Rectangular 33 Ah

2081-9276 Square 33 Ah

2081-929650 Ah

2081-9279110 Ah

2081-9280 4100ES, 4010ES, 4100U, and 4100+ NA NA NA NA NA

2081-9281 2081-9282 multiple NA

4009-9801 multiple ** NA NA NA NA

4009-9802 multiple NA NA NA NA

Battery Cabinets with Chargers

Cabinet Panel Compatibility 2081-9275

18 Ah* 2081-9287

25 Ah 2081-9271

Rectangular 33 Ah 2081-9276

Square 33 Ah 2081-9296

50 Ah 2081-9279

110 Ah

4081-9301 4081-9302 4004R and 4010 NA

4081-9306 4081-9308

4100ES, 4010ES, and 4100U NA NA NA NA

* Batteries smaller than those listed are normally mounted in the product cabinet ** 25 Ah capacity was effective as of 7/2005.

= Can be placed in the respective equipment cabinet NA = Not applicable/not compatible

NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information

Battery Model Capacity

Simplex Control Panel Model Series (see legend and notes below)

4003EC 4004R 4007ES & 4005

4006 & 4008

4009 (all models) 4010 4010ES 4100ES/

4100U 4100 & 4120

(2, 4 or 6-Unit)

2081-9272 6.2 Ah 2081-9274 10 Ah 2081-9288 12.7 Ah 2081-9275 18 Ah Ext Note 3 Ext Ext Note 2 2081-9287 25 Ah Ext Note 3 Ext Ext NA 2081-9271 rectangular 33 Ah Ext Note 3 Ext NA NA Note 3 Ext

2081-9276 “square” 33 Ah Ext Note 3 Ext NA NA Note 3

2081-9296 50 Ah NA Note 3 NA NA NA Note 3 Note 6 2 or 3 bay Ext 2081-9279 110 Ah Requires external battery cabinet, compatible with 4100ES, 4010ES, 4100, and 4120 Series only

= Can be placed in the respective equipment cabinet Ext = External battery cabinet is required, refer to selection chart on page 4 NA = Not applicable/not compatible

NOTES: 1. These batteries meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers

listed above. Contact your local Simplex product supplier for proper battery selection per system requirements. 2. 4010 Cabinets will accommodate 2081-9275, 18 Ah batteries, but will not allow bottom entry conduit. 3. Use 4081 series companion cabinet and charger, refer to page 4. 4. Some control panel models are listed for battery replacement reference only. 5. For 2 bay international applications only, 50 Ah batteries will fit in the cabinet.

Battery Compatibility for Fire Alarm Control Panel Mounting

External Battery Cabinet Compatibility Reference

dthurston
Line
dthurston
Line
Page 54: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Battery Cabinets Without Chargers; Shallow Design with Front Door Model Color Listings Description Dimensions

2081-9281 Beige UL and FM

2-Unit, 4100 style cabinet without charger; with locking solid door and battery shelf, primarily for use with 50 Ah batteries

25-3/4” W x 20-3/4” H x 6-3/4” D(654 mm x 527 mm x 171 mm) 2081-9282 Red

4003-9860 Beige Multiple Intended for use with 4003EC systems, for up to 33 Ah batteries (refer to 4003EC data sheet S4003-0002)

9-1/2” H x 24” W x 9” D (241 mm x 610 mm x 229 mm)

4009-9801* Beige UL and FM

For up to 25 Ah batteries*

External battery cabinet without charger, with locking solid door and battery harness; for close-nippled mounting to fire alarm control panel cabinet

16-1/4” W x 13-1/2” H x 5-3/4” D(413 mm x 343 mm x 146 mm)*

4009-9802 Beige UL For up to 33 Ah batteries

25-3/4” W x 20-3/4” H x 4-1/8” D (654 mm x 527 mm x 105 mm)

* Depth increased for 25 Ah batteries effective 7/2005.

Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems (refer to data sheet S4081-0001)

Model Color Input Voltage Description Dimensions

4081-9301 Beige

120 VAC

Battery cabinet with charger for the 4010 and 4004R fire alarm control panel; for up to 50 Ah batteries; with front door Listings include: UL, ULC, FM, CSFM, and MEA (NYC), see data sheet for details

22-1/2” W x16-3/4” H x 8-3/8” D (572 mm x 425 mm x 213 mm)

4081-9302 Red

Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers (refer to data sheet S2081-0012)

Model & Listings Color Cabinet Description Compatible

Chargers Charger Description Dimensions

2081-9280 Listings

include: UL and CSFM

Red

Battery cabinet for 2081-9279, 110 Ah batteries; includes 80 A battery fuse, terminals and battery connection cables; see data sheet for details

4010-9xxx Series

4010ES Main System Supply (MSS)

26-1/2” W x 12” H x 12” D (673 mm x 305 mm x 305 mm)

4100-9xxx Series

4100ES/4100U System Power Supplies (SPS)

4100-5111 4100-5112 4100-5113

4100ES/4100U Additional SPS

4100-5125 4100-5126 4100-5127

4100ES/4100U Remote Power Supply (RPS)

4100-5120 4100-5121 4100-5122

4100ES/4100U TrueAlert Addressable Power Supply (TPS)

4100-0104 4100-0114 4100-0124

4100 Legacy power supplies

4100ES/4010ES/4100U Compatible Battery Cabinet With Charger for 110 Ah Batteries (for ULC listed systems and for other applications unable to use panel mounted power supply charger; refer to data sheet S4081-0002)

Model Color Input Voltage Description Dimensions

4081-9306 Red 120 VAC Battery cabinet with charger for up to 110 Ah batteries; NOTE: Required for ULC listed charging of 110 Ah batteries; Listings include: UL, ULC, FM, CSFM, and MEA (NYC), see data sheet for details

27-7/8” W x 13-1/2” H x 14-5/8” D(708 mm x 343 mm x 371 mm)

4081-9308 Red 220/230/240 VAC, multi-tapped

4100-9837 Green LED Power-on Indicator Kit, required for ULC listing, mounts above access panel using knockout provided

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S2081-0006-21 12/2014

www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

External Battery Cabinet Specification Reference

Page 55: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Provides additional notification appliance circuit (NAC) capacity with flexible operation modes and power-limited design Four, Class B NACs are standard: Rated 2 A each for conventional reverse polarity

24 VDC notification appliances and providing multiple operation modes

Can be selected to provide synchronization for Simplex® visible notification strobe flashes

Capable of controlling TrueAlert non-addressable notification appliances operating with SmartSync two-wire control mode**

Input control options: IDNet addressable communications from a Simplex

model 4007ES, 4010, 4010ES, 4100ES, or 4100U Fire Alarm Control Panel**

Or from one or two conventional 24 VDC NACs with multiple output control options

IDNet communications control benefits: Provides status monitoring and individual NAC control

using a single address per 4009 IDNet NAC Extender Supports IDNet “Device Level” earth fault location

WALKTEST operation is available with either input choice Internal 8 A power supply/battery charger: Charges internal batteries up to 12.7 Ah or up to 18 Ah

batteries in external cabinet Provides status monitoring of battery, input power, and

earth faults Rated 8 A for “Special Application” appliances;

including Simplex 4901, 4903, 4904, and 4906 Series horns, strobes, horn/strobes, and speaker/strobes

Rated 6 A for “Regulated 24 DC” appliance power Optional 4009 IDNet NAC Extender modules: IDNet Communications Repeater provides Class B or

Class A output IDNet Communications Fiber Optic Receiver/Repeater,

available as Class B or Class X Four additional Class B NACs, rated 1.5 A for Special

Application appliances; 1 A for Regulated 24 DC appliance power

Class A, Two Circuit Adapter Module

UL Listed to Standard 864

External Accessories

IDNet communication fiber optic transmitters: For applications requiring the data integrity available

with fiber optic communications Available as Class B or Class X Mounts in standard six-gang electrical box

External battery cabinet for 18 Ah batteries

ALARMFIRE

PULL DOWN

PO W ERBEFO RE

SERVI CI NG

CAUTIONDI SCO NNECT

4009 IDNet NAC EXTENDERTM

Optional IDNet Channel Repeater

SIMPLEX T IME RECORDER CO.

4090- 91 01

MONITOR ZAM, CLASS B

INSTAL. INS TR. 574- 183

DATE CODE:

1

5

6

7

8

1

2

3

4

1234

5678

+ 24V0V

+I DNET- I DNET

ZONE PWR +ZONE PWR -I DC +I DC -

Up to 8 NACs

4007ES, 4010 (shown), 4010ES, 4100ES, or 4100U

Fire Alarm Control PanelFire Alarm Control Panel with

Conventional NACs

Fiber Optic IDNet Communications

NAC Control

2-Wire IDNet Communications or

or

4009 IDNet NAC Extender

IDNet FiberOptic Transmitter

FI RE ALARMCO NTRO L

D I S C O N N E C TP O W E R B E F O R

S E R V I C I N G

CAUTI O N

* * SYSTEM I S NO RM AL * * 12: 02: 15pm M on 9- Feb- 98

S U P VA C K

S Y S T E MS U P E R V I S O R Y

A L A R MA C K

F I R EA L A R M

T R O U B L EA C K

S Y S T E MT R O U B L E

A L A R MS I L E N C E

A L A R MS I L E N C E D

S Y S T E MR E S E T

A CP O W E R

4009 IDNet NAC Extender Connection Reference Drawing

Introduction

ADA Compliance. Complying with the notification requirements of ADA (Americans with Disabilities Act) may require more notification appliance power than is available within the fire alarm control panel. When additional power is required, a Simplex 4009 IDNet NAC Extender can provide up to 8 A of NAC power with up to eight, supervised reverse polarity NACs.

Location Flexibility. The 4009 IDNet NAC Extender can be mounted close to a compatible dedicated host panel or can be located remotely for convenient power distribution. Multiple operation modes and multiple connection options further increase location flexibility.

Additional Information. For additional operation detail and application information, refer to Installation Instructions 574-181 and field wiring diagram 842-068.

* ULC listed model is 4009-9202CA. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:214 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

** 4100U requires revision 11 software or higher for compatibility. 4010 requires revision 2 software or higher for compatibility.

LifeAlarm Fire Alarm Controls UL, ULC, CSFM Listed; FM Approved; 4009 IDNet NAC Extender for Control with MEA (NYC) Acceptance* IDNet Communications or Conventional NACs

S4009-0002-14 9/2015

Page 56: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Application and Operation Information

IDNet Addressable Communications Compatible. Up to ten (10), 4009 IDNet NAC Extenders can be controlled per 4007ES, 4010ES, 4100ES, or 4100U IDNet communications channel; up to five (5) can be controlled on the 4010 IDNet communications channel. Each output NAC can be individually controlled for general alarm or selective area notification requiring only one point address per Extender. Individual Extender NACs can also be manually controlled from the host panel. IDNet controlled extenders will inform the host panel of troubles via IDNet communications. 4007ES, 4010ES, 4100ES, and 4100U control panels control using multi-point rules, refer to data sheet S4090-0011 for details.

Optional IDNet Repeaters. IDNet communications can be repeated with the optional IDNet Repeater Module or with the optional Fiber Optic Receiver Module. Up to 100 of the IDNet channel points can be repeated once (refer to pages 3 and 5 for details). Repeated IDNet communications also support the “device level” earth fault location utility of the host panel.

Hardwire Control Applications. For applications where an existing (or new) conventional NAC needs additional power, the 4009 IDNet NAC Extender can be controlled directly from the NAC. Either one or two NACs, from either the same, or from different host fire alarm control panels, can be connected to control the 4009 IDNet NAC Extender output NACs. Multiple control selections provide flexible operation. (Refer to page 4 for more detail.) Alarms from the host panel will activate the four, 4009 IDNet NAC Extender NACs (or optionally, eight NACs) to extend the alarm.

The 4009 IDNet Extender monitors itself and each of its output NACs for trouble conditions, including earth faults. Extenders wired to conventional NACs will indicate a trouble by opening the path to the NAC’s end-of-line resistor, but retaining the ability to respond to alarms. Individual troubles are also annunciated by LEDs located on the 4009 IDNet NAC Extender main circuit board. (Refer to page 7 for more diagnostic information.)

Standard Models Model Description

4009-9201** 120 VAC input

4009 IDNet NAC Extender with 4, Class B NACs and 8 A power supply 4009-9202CA* 4009-9301 240 VAC input

* ULC listed model ** 4009-9201 has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires battery brackets as detailed on data sheet S2081-0019

Optional Modules (for on-site installation) Model Description Comments

4009-9807 Additional four point NAC module, rated 1.5 A Special Application appliances; 1 A for Regulated 24 DC appliance power, Class B

One maximum

4009-9808 Dual Class A adapter (for two NAC outputs) Select as required (4 maximum) 4009-9809 IDNet Repeater, output is Class A or Class B Select either an IDNet Repeater or a Fiber

Optic Receiver as required; one transmitter can connect to one receiver

4009-9810 Fiber Optic Receiver

Class B 4009-9811 Class A (IDNet), Class X (fiber) 4009-9805 Red Appliqué for door Select if required 2975-9801

Semi-Flush Trim Kit Beige trim 1-7/16” wide (78 mm), use if required for

semi-flush installations 2975-9802 Red trim

Battery Selection (select battery size per system requirements) Model Description Comments

2081-9272 6.2 Ah Battery, 12 VDC Two batteries are required, 24 VDC operation 2081-9274 10 Ah Battery, 12 VDC

2081-9288 12.7 Ah Battery, 12 VDC

2081-9275 18 Ah Battery, 12 VDC Requires external battery cabinet, two batteries are required, 24 VDC operation

External Accessories (select per system requirements) Model Description Comments

4090-9105 IDNet Fiber Optic Transmitter

Class B operation Mounts in six-gang electrical box, refer to page 4 for mounting details 4090-9107 Class X operation

4009-9801 External battery cabinet for up to 18 Ah batteries, beige 16-1/4” W x 13-1/2” H x 5-3/4” D (413 mm x 343 mm x 146 mm)

4081 Series End-of-Line Resistor Harnesses; see data sheet S4081-0003 for details 2 S4009-0002-14 9/2015

Product Selection

dthurston
Line
dthurston
Line
Page 57: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

IDNet devices and additional 4009 IDNet NAC Extender(s)

ALARMFIRE

PULL DOWNSIMPLEX T IME RECORDER CO.

4090- 9101

MONITOR ZAM, CLASS B

INSTAL . INSTR. 57 4- 18 3

DATE CODE:

1

5

6

7

8

1

2

3

4

1234

5678

+ 24V0V

+I DNET- IDNET

ZO NE PWR +ZO NE PWR -I DC +I DC -

ALARMFIRE

PULL DOWNSIMPLEX TIME RECORDER CO.

4090-9101

MONITOR ZAM, CLASS B

INSTAL. INSTR. 5 74 - 1 8 3

DATE CODE:

1

5

6

7

8

1

2

3

4

1234

5678

+ 24V0V

+IDNET- I DNET

ZO NE PWR +ZO NE PWR -IDC +IDC -

PO W ERBEFO RE

SERVI CI NG

CAUTI ONDI SCO NNECT

4009 IDNet NAC EXTENDERT M

FIRE

4009 IDNet NAC Extender with optional internal IDNet Repeater

Repeated IDNet Channel:up to 100 devices maximum on repeater output,

250 devices total on IDNet Channel

Output NACs, four standard, eight with expansion option

Typical IDNet compatible devices

(Refer to individual devices for actual wiring requirements, some wiring is not shown.)

4007ES, 4010, 4010ES, 4100ES (shown), or 4100UFire Alarm Control Panel

IDNet addressable communications channel,shown Class B (Style 4)

PO W ERBEFO RE

SERVI CI NG

CAUTI ONDI SCO NNECT

4009 IDNet NAC EXTENDERT M

Conventional NAC operation (horns)

SmartSync operation (horns and strobes)

Conventional NAC operation (strobes)

FIRE

Select conventional or SmartSync operation per NAC

NOTE: Up to ten (10) 4009 IDNet NAC Extenders may be connected per 4007ES, 4010ES, 4100ES, or

4100U IDNet channel, up to five (5) on the 4010 IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver).

FI RE ALARMCO NTRO L

D I S C O N N E C TP O W E R B E F O R

S E R V I C I N G

CAUTI O N

* * SYSTEM I S NO RM AL * * 12: 02: 15pm M on 9- Feb- 98

S U P VA C K

S Y S T E MS U P E R V I S O R Y

A L A R MA C K

F I R EA L A R M

T R O U B L EA C K

S Y S T E MT R O U B L E

A L A R MS I L E N C E

A L A R MS I L E N C E D

S Y S T E MR E S E T

A CP O W E R

4090-9105, Class B(Style 4) Output Fiber

Optic Transmitter

Two fiber cables, 3000 ft (914 m) maximum distance

Four fiber cables, 3000 ft (914 m) maximum distance

4090-9107, Class A (Style 7) Output Fiber Optic Transmitter

24 VDC power forfiber optic transmitters

4009 IDNet NAC Extenders with optional internal IDNet Fiber Receivers

IDNet addressable communications channel Class B (Style 4) or Class A (Style 6), Class B shown Repeated IDNet Channel: up to 100 devices maximum

on repeater output, 250 devices total on IDNet Channel

ALARMFIRE

PULL DOWNSIMPLEX TIME RECORDER CO.

4090- 9101

MONITOR ZAM, CLASS B

INSTAL. INSTR. 574- 183

DATE CODE:

1

5

6

7

8

1

2

3

4

1234

5678

+ 24V0V

+I DNET- I DNET

ZO NE PWR +ZO NE PWR -I DC +I DC -

PO W ERBEFO RE

SERVI CI NG

CAUTIONDI SCO NNECT

4009 IDNet NAC EXTENDERT M

Output NACs

ALARMFIRE

PULL DOWNSIMPLEX TIME RECORDER CO.

4090- 9101

MONITOR ZAM, CLASS B

INSTAL. INSTR. 574- 183

DATE CODE:

1

5

6

7

8

1

2

3

4

1234

5678

+ 24V0V

+I DNET- I DNET

ZO NE PWR +ZO NE PWR -I DC +I DC -

PO W ERBEFO RE

SERVI CI NG

CAUTIONDI SCO NNECT

4009 IDNet NAC EXTENDERT M

Output NACs

4007ES, 4010 (shown), 4010ES, 4100ES, or 4100U

Fire Alarm Control Panel

NOTE: Up to ten (10) 4009 IDNet NAC Extenders may be connected per 4007ES, 4010ES, 4100ES, or 4100U IDNet

channel, up to five (5) on the 4010 IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). Fiber optic transmitters connect to only one receiver in a 4009 IDNet NAC Extender.

3 S4009-0002-14 9/2015

Typical IDNet Connection Example

Typical Fiber Optic System Connections

Page 58: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Hardwire Control Connection Information

NAC Input Selections. The 4009 IDNet NAC Extender can be selected to:

Track input NAC operation or to provide a locally generated code, selectable per NAC input

If selected for local coding, NAC outputs can be either Temporal Coded or 60 Beats/min March Time Coded, one code selection per extender (input NACs must be on continuous with Alarm)

Additionally, NAC outputs can be selected to provide the Simplex strobe synchronization signal. This signal will synchronize the flashes of synchronized strobes but will be ignored by free-run strobes and audible devices. (Strobes are for operation by noncoded NACs.)

NAC input to NAC output control can be selected for standard and optional NACs per the following table:

Conventional NAC Output Operation Options Input A B C NAC 1 NACs 1 & 2, 5 & 6 NACs 1-4 NACs 1-8 NAC 2 NACs 3 & 4, 7 & 8 NACs 5-8 None

SmartSync NAC Output Operation Input NAC Control Function NAC 1 Strobe Control

All NAC outputs (1-8) NAC 2 Horn Control

SmartSync Notification Appliance Control

The TrueAlert Notification Appliance product line includes addressable and non-addressable operation. Non-addressable models are available with 2-wire SmartSync operation or conventional 4-wire operation. The following details apply to use with the 4009 IDNet NAC Extender:

TrueAlert non-addressable models with SmartSync operation allow audible notification to be separately controlled over the same wire pair that controls visible notification

4009 IDNet NAC Extenders can be selected to provide SmartSync operation whether controlled by IDNet communications or conventional NACs

IDNet control allows output NACs to be individually selected for conventional or SmartSync operation

With NAC input control, all output NACs are selected for either conventional or SmartSync operation

Refer to data sheet S4009-0003 for TrueAlert Addressable operation details, contact your local Simplex product supplier for further information on specific TrueAlert notification appliances

P O W E RB E F O R E

S E R VI C I N G

CAUTI O NDI SC O N NE C T

4009 IDNet NAC EXTENDERTM

Up to eight (8) output NACs total; hardwire control can be selected to map NAC inputs to different combinations of NAC outputs depending on system requirements

Fire Alarm Control Panel with Conventional NACs

4009 IDNet NAC Extender

NAC 1 input(see Note 1)

NAC 2 input(optional, see Note 1)

Conventional NACs

Output NACs

SmartSync operation

Notes:

1. For separate audible and visible output NAC control, or SmartSync NAC output operation, two (2) input NACs are required. NAC 1 is "on-until-reset" and NAC 2 is "on-until-silenced."

2. To synchronize strobe flash outputs for up to four (4) 4009 IDNet NAC Extenders, use the synchronized strobe output from a Synchronized Flash Module (4905-9914 for Class B operation, 4905-9922 for Class A operation) or, if available, from a NAC selected to provide synchronized strobe flash output. NOTE: DO NOT USE a NAC selected for SmartSync operation for this function.

With hardwire control, NAC outputs are all conventional or all SmartSync operation

To additional 4009 IDNet NAC Extenders (up to four (4), 4009 IDNet NAC Extenders per NAC); see Note 2

Refer to Installation Instructions 574-181 for additional information and application guidance

Class A operation, either mode, requires 4009-9808 Dual Class A Adapter

4 S4009-0002-14 9/2015

Hardwire Control NAC Connection One-Line Reference Diagram

Page 59: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Input Ratings

120 VAC Input (4009-9201) 3A @ 102-132 VAC, 60 Hz 240 VAC Input (4009-9301) 1.5A @ 204-264 VAC, 50/60 Hz

Hardwire Control from External NACs, Input Requirements

Conventional reverse polarity operation 5 mA maximum; 16 to 33 VDC

Output Ratings

Total Rating 8 A, Special Application appliances 6 A, Regulated 24 DC appliance power

Standard NACs 2 A each, Special Application or Regulated 24 DC appliance power Optional NACs

(requires 4009-9807) 1.5 A each, Special Application appliances 1 A each, Regulated 24 DC appliance power

Special Application Appliances

Simplex non-addressable horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative for compatible appliances)

Regulated 24 DC Appliances

Power for other UL listed appliances; use associated external synchronization modules where required

Strobe Operation Up to 33 strobes per NAC can be synchronized; output NACs configured for Simplex synchronized strobe operation are synchronized to each other

Auxiliary Output 500 mA @ 24 VDC nominal

Optional Modules Ratings

IDNet Repeater Module (4009-9809)

Input Power 70 mA @ 24 VDC, system supplied IDNet Input, One Address Maximum distance from IDNet source is 2500 ft (762 m)

IDNet Output Specifications

Repeated IDNet output for up to 100 devices (total IDNet devices not to exceed 250 per channel) Maximum distance to farthest device is 2500 ft (762 m) Total distance including “T-taps” is 10,000 ft (3048 m) Class A loop maximum distance is 2500 ft (762 m), no “T” taps

Fiber Optic Receiver Modules

Input Current 4009-9810, Class B, 65 mA @ 24 VDC, system supplied 4009-9811, Class X, 80 mA @ 24 VDC, system supplied

IDNet Output Specifications Same as those for Repeater Module (see above) Fiber Optic Transmission Distance 3000 ft (914 m) maximum

General (LED status indicators are listed on page 7, dimensions and mounting details are on page 6) Operating Temperature 32° to 120° F (0° to 49° C) Operating Humidity Range 10% to 90% RH from 32° F to 104° F (0° C to 40° C) Wiring Connections* Terminal blocks for 18 AWG (stranded) to 12 AWG (solid)

Input Voltage 18.9-32 VDC from compatible listed fire alarm supply

Input Current 4090-9105, Class B, 30 mA @ 24 VDC 4090-9107, Class X, 35 mA @ 24 VDC

Fiber Optic Connections and cable requirements

Multimode, graded index, 50/125µm, 62.5/125 µm, 100/40 µm, or 200 µm Type ST connectors 4090-9105, Class B operation, two fiber cables required 4090-9107, Class X operation, four fiber cables required

Module Size (with mounting bracket) 6-13/16” W x 3-3/4” H x 1-1/8” D (173 mm x 95 mm x 29 mm)

On-board Status Indicators Green LED flashing = transmit Red LED flashing = receive Separate red LED on 4090-9107 = Class X receive

Communications Simplex IDNet Fiber Optic Transmission Distance 3000 ft (914 m) maximum Wiring Connections* Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Operating Humidity 10% to 90% RH from 32° to 104° F (0° to 40° C) Operating Temperature 32° F to 120° F (0° to 49° C)

* Metric wire equivalents: 18 AWG = 0.82 mm2; 12 AWG = 3.31 mm2

5 S4009-0002-14 9/2015

4009 IDNet NAC Extender Specifications

Fiber Optic Transmitter Specifications

Page 60: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Door, 5/8"(16 mm) thick

Cabinet depth4-1/4" (108 mm)16-1/4" (413 mm)

13-1/2"(343 mm)

Wall surface reference for semi-flush mount

Non-power limited wiring area (AC input)

12" (305 mm)

Battery location, no conduit entry or wiring inthis area (12.7 Ah battery outline shown)

IDNet repeater orFiber optic receiver

Optional Class Aadapter modules

4009-9807 Additional Fourpoint module (shown with

Class A adapters)

10-29/32" (277 mm)

Knockouts for screwor nail mounting holes

System Module

Semi-flush trim option1-3/16" wide (30 mm),

3/8" (9.5 mm) thick

Exposed cabinetdimension for

semi-flush mount1" (25.4 mm),

1-3/8" (35 mm) withsemi-flush trim

NOTE: Recommended conduit entrance varies with module selection. Refer to general installation

instructions 574-181, specific module installation instructions, and to field wiring diagrams 842-068 before locating conduit entrance.

POWERBEFORE

SERVICING

CAUTIONDISCONNECT

4009 IDNet NAC EXTENDERTM

Optional red appliqué(4009-9805 )

6 S4009-0002-14 9/2015

4009 IDNet NAC Extender Mounting and Module Placement Information

4009 IDNet NAC Extender Cabinet with Door Detail

Page 61: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Service Diagnostic Features

Power-up Self-Diagnostics. Upon power-up, the 4009 IDNet NAC Extender tests each module and performs earth fault diagnostics. Trouble conditions are communicated to the host control panel and are also displayed on diagnostic status LEDs in the 4009 IDNet NAC Extender. When connected via IDNet communications, detailed status information is available at the host. When controlled with conventional NAC inputs, common troubles are signaled by providing a polarized open circuit that disconnects the NAC wiring from its end-of-line resistor but still allows a reversed polarity alarm to be received.

Door Mounted Reference Label. The 4009 IDNet NAC Extender has a detailed programming and diagnostic label inside the front door that provides a quick reference for both installation and checkout.

LED Status Indicators are provided for the following:

Each NAC (standard and optional) has a dedicated yellow LED that:

– During supervision provides a slow flash to indicate a short circuit condition and a fast flash to indicate an open circuit

– During an alarm, the LED follows the NAC output (on steady or flashing with coded output)

Four, general status yellow LEDs provide nine separate indications listed in priority of urgency. As a trouble is eliminated, any remaining trouble(s) will then be indicated until the 4009 IDNet NAC Extender is returned to normal operation.

AC power status is indicated by a green LED that is on when AC is normal. During low AC (brownout) conditions or with no AC, the LED is off. Additional power and battery status is indicated by the general status LEDs.

7 S4009-0002-14 9/2015

Surface mount box:Simplex model 2975-9217

(ordered separately)

Flush mount masonry box:use 6-gang box, RACO # 960, 2-1/2" deep(64 mm), or RACO # 965, 3-1/2" (89 mm)

deep, or equal (supplied by others)

Six-gang blank cover plate Mulberry MetalProducts 97156 or equal (by others)

Flush mount ganged boxes:use 6-gang box, 1-1/2" (38 mm)

minimum depth; six, RACO # 400or equal, (supplied by others)

IDNet fiber optic transmitter:4090-9107, Shown, Class A (Style 7) output4090-9105, Not shown, Class B (Style 4) output

INSTALLATION NOTE:Fiber optic cable bend radius should be 2" (51 mm)minimum, or per Manufacturer's specification.

4090-9105/9107 IDNet Fiber Optic Transmitter Mounting Information

Page 62: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Step 1. Calculate Basic Extender Battery Requirements (minus NAC loads) Panel, NAC Options, and Auxiliary Power (underlined model numbers are optional modules)

Model Descript ion Supervisory Current

Actual Supervisory Alarm Current Actual Alarm

4009-9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA

4009-9301 240 VAC input

4009-9807 Additional Four Point NAC 40 mA +_______ 40 mA +_______

4009-9808 Dual Class A Adapter (no additional current) – – – –

Auxiliary Power Output (500 mA maximum) +_______ (500 mA

maximum) + [A1] _______

Basic Panel Supervisory Current = [S1] _____

Basic Panel Alarm Current = [A2] ______

Step 2. Calculate IDNet Output Module and Device Current (if used) 4009-9809 IDNet Repeater

Select one per Extender

70 mA +_______

70 mA +_______ 4009-9810* Fiber Optic Receiver, Class B 65 mA 65 mA

4009-9811* Fiber Optic Receiver, Class X 80 mA 80 mA

IDNet Devices (connected to Repeater or Receiver above), 0.7 mA each, maximum of 100

Total devices x 0.7 mA each +_______ Total devices

x 0.7 mA each +_______

* Note: IDNet Fiber Optic Transmitter current is supplied from the host fire alarm control panel

IDNet Module Supervisory Current [S2] = ____

= [A3] ______ IDNet Module Alarm Current

Step 2. Calculate Available NAC Current Maximum Available Current = 8 A*

Subtract Auxiliary Power Output - [A1] ______

Subtract IDNet Module Current - [A3] ______

* 8 A for Special Application Appliances; 6 A for Regulated 24 DC Appliances Available NAC Current = [A4] ______

Step 3. Calculate Actual NAC Loading (Limited to Available NAC Current per Step 2.)

NAC Type NAC Circuit # NAC Alarm Current

Standard Panel NACS, 2 A maximum per NAC

Circuit 1 +_______

Circuit 2 +_______

Circuit 3 +_______

Circuit 4 +_______

Optional Four Point NAC Module, 1.5 A maximum Special Application rating, 1 A maximum Regulated 24 DC rating, per NAC

Circuit 5 +_______

Circuit 6 +_______

Circuit 7 +_______

Circuit 8 +_______

Total Actual NAC Load Alarm Current = [A5] _______

Step 4. Calculate Total Supervisory Current Total Supervisory Current = Basic Panel Current [S1] + IDNet Module Current [S2] = ________

Step 5. Calculate Total Alarm Current Total Alarm Current = Basic Panel Current [A2] + IDNet Module Current [A3] + Actual NAC Current [A5] = ________

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4009-0002-14 9/2015

www.simplex-fire.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

4009 IDNet NAC Extender Current Calculation Chart

Page 63: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Remote LCD annunciator for use with Simplex® model: 4100ES and 4100U fire alarm control panels Legacy products 4100, 4120, and 4020 fire alarm control

panels, and 4100/4120 Universal Transponders Information display features: Maintained display of first alarm is available with

4100ES and with 4100U at software revision 11.11 or higher

Wide viewing angle, super-twist LCD technology with green LED backlighting

Two lines of 40 characters each LED status indicators During battery backup, backlighting is disabled until

there is switch activity Controls include: Switches for system acknowledge, alarm silence, and

system reset Four programmable control switches Lamp/LCD test Wiring information: RUI (Remote Unit Interface) communications require a

single twisted wire pair (see p. 3 for more information)

Separate wiring is required for 24 VDC control panel power

Flush mount on standard electrical boxes Options: 2975-9206, Surface mount box

4603-9111, Brushed stainless steel trim

UL Listed to Standard 864 Description

Remote Control and Annunciation is provided using an 80 character, back-lit, alphanumeric display. Information is presented in clear, descriptive English language and includes: Point Status (alarm, trouble, etc.); Alarm Type (smoke detector, manual station, etc.); Number of System Alarms, Supervisory Conditions, and Trouble Conditions; and a Custom Location Label.

Wiring. A single twisted wire pair provides serial RUI communications that also supports other Simplex serial annunciators on the same wire pair.

Multiple Indications. Alarm, Supervisory, and Trouble conditions are also indicated by dedicated LEDs and a tone-alert audible sounder. Each condition has a dedicated acknowledge push-button switch that silences the tone-alert but leaves the LED on until all conditions in that category are restored to normal. Switch operation is either globally or individually acknowledgeable, determined by the control panel operation.

4603-9101 LCD Annunciator Description (Continued)

Repeated operation of the appropriate acknowledge switch will scroll the LCD display showing activity in the sequence of occurrence. The tone-alert also pulses to indicate the operation of any of the push-button switches.

Consult local code requirements for guidance in determining applications and location of the 4603-9101 LCD annunciator.

Operation

System Controls. Notification appliances can be deactivated by pressing the “ALARM SILENCE” switch. (Exact operation is determined by the host control panel such as visible appliances remaining on until system is reset.) Pressing the “SYSTEM RESET” switch restores the system to normal operation. When system activity is normal, the LCD displays the time, date, and “SYSTEM IS NORMAL.”

Control Switches. Four programmable “CONTROL” switches and associated LEDs are included. Typical applications include manual evacuation, door holder release bypass, and elevator capture bypass.

Keyswitch Enable. All switches on the annunciator are controlled by the “ENABLE” keyswitch with a key that is removable only in the disabled position. A brief lamp/LCD test is performed whenever the keyswitch is changed from enabled to disabled.

Battery Backup Operation. During battery backup, the LED backlighting is disabled to conserve battery power. When an annunciator switch is activated, the backlighting is automatically enabled. After approximately 30 seconds of inactivity, the backlighting will again be disabled.

* This product has been approved by the California State Fire Marshal (CSFM) pursuant to

Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7120-0026:0179 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

System Accessories, LCD Annunciators UL, ULC Listed; FM, CSFM, 4603-9101 LCD Annunciator for and MEA (NYC) Approved* 4100ES and 4100U Fire Alarm Control Panels

S4603-0001-13 1/2016

dthurston
Line
Page 64: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

FIREALARM

ALARM SILENCED

PRIORITY 2ALARM

SYSTEM SUPERVISORY

SYSTEM TROUBLE

POWERON

SYSTEMRESET

DISPLAYTIME

ALARMACK

ALARMACK

SUPVACK

TBLACK

ALARMSILENCE

2 X 40 LCD READOUT, green LED backlighted during normal conditions and abnormal operating conditions

SUPV ACK acknowledges System Supervisory conditions and silences the panel and all annunciator tone-alerts

TROUBLE ACK acknowledges System Troubles and silences the panel and all annunciator tone-alerts

CONTROL ENABLE KEYSWITCH controls all switch functions; key is removable only in disabled position

ALARM SILENCE causes audible and visible notification appliances to be silenced (default operation, may be modified through panel programming for compliance with local requirements)

SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal

ALARM ACK/FIRE ALARM acknowledges a Fire Alarm condition and silences the panel and all annunciator tone-alerts

FOUR PROGRAMMABLE (Yellow) LEDs, each with pushbutton switch and custom labeling pocket

SIX STATUS INDICATOR LEDs provide system status indications in addition to LCD information; LEDs flash to indicate the condition and then when acknowledged, remain on steady until reset; Fire Alarm and Priority 2 Alarm are red; System Supervisory, System Trouble, and Alarm Silenced are yellow; Power On is green

DISPLAY TIMEdisplays time of last occurrence of event list being displayed; or displays current time when viewing system status information

ALARM ACK/PRIORITY 2 acknowledges a Priority 2 Alarm condition and silences the panel and all annunciator tone-alerts

2 S4603-0001-13 1/2016

Model Description

4603-9101 Remote LCD Annunciator with beige trim

Refer to specifications on page 3 for additional details

4603-9101CF Remote LCD Annunciator with beige trim, with French keypad for Canada

4603-9111 Brushed stainless steel trim option

2975-9206 Matching surface mount box; ivory finish

2081-9044 Overvoltage protector; required where annunciator communications and power wiring exits and enters a building; refer to data sheet S2081-0016 for details

4603-9101 Operator Information

Product Selection

Page 65: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

3 S4603-0001-13 1/2016

General Operating Specifications Voltage 18 to 32 VDC, system supplied Normal Operating Current 110 mA (with LED backlighting on)

Battery Standby Current 65 mA (during battery backup, LED backlighting is turned off after 30 seconds without switch activity)

Alarm Current 140 mA maximum (LED backlighting is on and tone-alert is sounding)

Operating Temperature Range 32° to 120° F (0° to 49° C) Operating Humidity Range Up to 93% RH, non-condensing at 100° F (38° C)

Communications

4100ES/4100U Capacity, Per RUI Output

Type RUI (Remote Unit Interface) external annunciator communications line SLC (signaling line circuit)

Capacity

Up to 31 remote annunciators/MINIPLEX transponders per channel including the 4603-9101 LCD Annunciator, the 4602-9101 Status Command Unit (SCU), and 4602-9102 Remote Command Unit (RCU); refer to data sheet S4100-0031 for additional 4100ES information

Wiring Requirements

RUI Data

Standard Wiring Type Unshielded twisted pair (UTP), 18 AWG (0.82 mm2) for most applications, see below

Wiring Characteristics 0.58 µF (580 nF) maximum capacitance between conductors; 35 maximum total line resistance

Wiring Applications Requiring Shielded,

Twisted Pair (STP)

1. Wiring that leaves the building. Also requires Isolated Loop Circuit Protectors on each end, refer to data sheet S2081-0007 for 2081-9027 (200 mA), or S2081-0008 for 2081-9028 (5 A)

2. Wiring run in 500 ft (152 m) or more of conduit. 3. Wiring closely bundled with standard IDNet communications or TrueAlert

addressable communications (not required when run with IDNet+ communications).

Class B “T-Tap” wiring distance Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device

Class X wiring distance Up to 2500 ft (762 m)

Power Wiring 18 to 12 AWG (0.82 mm2 to 3.31 mm2) wires for 24 VDC system power

Earth Wiring A dedicated earth ground connection to the electrical box is required for proper ESD and EMI protection; wire in accordance with NFPA 70 (National Electrical Code) Article 250

Mounting Information NOTE: General Conduit Entrance Requirement

Conduit entrance must be located a minimum of 2 ¾” (70 mm) from the front of the box to clear assembly

Trim Dimensions 4 ½” H x 11 13⁄16” W (114 mm x 300 mm) Standard Trim Finish Steel, painted beige

4603-9111, Optional Trim Brushed stainless steel (ordered separately); supplied with both slotted and tamper resistant screws

Boxes for Flush Mounting (supplied by others)

6-Gang, 3 ½” (89 mm) deep: RACO 965, 6-gang masonry box; RACO 590, gangable switch box, 6 required; or equal

2975-9206, Surface Mount Box Option (ordered separately) Dimensions 11 31⁄32” W x 4 ⅝” H x 2 ¾” D (304 mm x 117 mm x 70 mm) Finish Painted steel, ivory finish

4603-9101 LCD Annunciator Specifications For additional information, refer to Installation Instructions 579-979.

Page 66: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. National Electrical Code and NFPA are registered trademarks of the National Fire Protection Association (NFPA).

Flush Mount Masonry Box:Use RACO # 965, 3-1/2" (89 mm) deep

or equal (supplied separately)

Flush Mount Ganged Boxes:Requires 6-gang box, 3-1/2" (89 mm) min.

depth, use (6) RACO # 590 or equal (supplied separately)

FIREALARM

ALARM SILENCED

PRIORITY 2ALARM

SYSTEM SUPERVISORY

SYSTEM TROUBLE

POWERON

SYSTEMRESET

DISPLAYTIME

ALARMACK

ALARMACK

SUPVACK

TBLACK

ALARMSILENCE

Surface Mount Box:Simplex model 2975-9206

2-3/4” deep (70 mm) (ordered separately)

Trim plate

LCD Annunciator Assembly

Terminal block access at rear of

assembly, this side

Note: Review box choice with assembly layout before selecting conduit entrance location to allow easy access to terminals

Wiring Notes:1. Communications require a single 18 AWG twisted pair.

2. Power requires two, 18 to 12 AWG wires for 24 VDC system power, plus Earth Ground to each electrical box.

3. Refer to Installation Instructions 579-979 for additional wiring specifications.

Fire Alarm Control Panel (4100ES shown)

4603-9101 LCD Annunciators

FIRE

ALARM

ALARM

SILENCED

PRIORITY 2

ALARM

SYSTEM

SUPERVISORY

SYSTEM

TROUBLE

POWER

ON

ALARMACK

SUPVACK

TBLACK

ALARMACK

ALARMSILENCE

SYSTEMRESET

DISPLAYTIME

FIRE

ALARM

ALARM

SILENCED

PRIORITY 2

ALARM

SYSTEM

SUPERVISORY

SYSTEM

TROUBLE

POWER

ON

ALARMACK

SUPVACK

TBLACK

ALARMACK

ALARMSILENCE

SYSTEMRESET

DISPLAYTIME

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4603-0001-13 1/2016

www.simplexgrinnell.com © 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Wiring Reference

Mounting Information

Page 67: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Individually addressable manual fire alarm stations with: Power and data supplied via IDNet or MAPNET II

addressable communications using a single wire pair Operation that complies with ADA requirements Visible LED indicator that flashes during

communications and is on steady when the station has been activated

The NO GRIP Single Action Station and Retrofit Kit are available with a more easily operated pull lever for applications where anticipated users may find the standard station lever difficult to activate

Pull lever that protrudes when alarmed Break-rod supplied (use is optional) Models are available with single or double action

(breakglass or push) operation UL listed to Standard 38 Compatible with the following Simplex® control panels: Model Series 4007ES, 4008, 4010, 4010ES, 4100ES,

4100U, 4020, 4100, and 4120 fire alarm control panels equipped with either IDNet or MAPNET II communications

Model Series 2120 Communicating Device Transponders (CDTs) equipped with MAPNET II communications

Compact construction: Electronics module enclosure minimizes dust

infiltration Allows mounting in standard electrical boxes Screw terminals for wiring connections

Tamper resistant reset key lock (keyed same as Simplex fire alarm cabinets) Multiple mounting options: Surface or semi-flush with standard boxes or matching

Simplex boxes Flush mount adapter kit Adapters are available for retrofitting to commonly

available existing boxes

Description

The Simplex addressable manual station combines the familiar Simplex manual station housing with a compact communication module that is easily installed to satisfy demanding applications. Its integral individual addressable module (IAM) constantly monitors status and communicates changes to the connected control panel via IDNet or MAPNET II communications wiring.

* Refer to page 2 for specific model listings. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7150-0026:224 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

4099-9004

Single action

4099-9021 NO GRIP

Single action

4099-9805 NO GRIP Retrofit kit

ALARMFIRE

PULL DOWN

PUSH

ALARMFIRE

KEYOPERATED

ONLY

ALARMFIRE

KEYOPERATED

ONLY

4099-9005 Breakglass

4099-9006 Push

With 2099-9828 Institutional Cover kit

Operation

Activation of the 4099-9004 single action manual station requires a firm downward pull to activate the alarm switch. Completing the action breaks an internal plastic break-rod (visible below the pull lever, use is optional). The use of a break-rod can be a deterrent to vandalism without interfering with the minimum pull requirements needed for easy activation. The pull lever latches into the alarm position and remains extended out of the housing to provide a visible indication.

Single Action NO GRIP Station 4099-9021. For applications such as California Building Code, Title 24, which requires “Controls and operating mechanisms shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist” the model 4099-9021 station provides a more easily operated pull lever compared to standard stations. Retrofit of existing stations is available using the 4099-9805 Retrofit kit.

Double Action Stations (Breakglass) require the operator to strike the front mounted hammer to break the glass and expose the recessed pull lever. The pull lever then operates as a single action station.

Double Action Stations (Push Type) require that a spring loaded interference plate (marked PUSH) be pushed back to access the pull lever of the single action station.

Station reset requires the use of a key to reset the manual station lever and deactivate the alarm switch. (If the break-rod is used, it must be replaced.)

Station testing is performed by physical activation of the pull lever. Electrical testing can be also performed by unlocking the station housing to activate the alarm switch.

Multi-Application Peripherals UL, ULC, CSFM Listed; IDNet or MAPNET II Communicating Devices FM Approved * Addressable Manual Stations

S4099-0005 10/2014

dthurston
Line
Page 68: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

2 S4099-0005 10/2014

Addressable Manual Stations, Red Housing with White Letters and White Pull Lever Model Description Housing Pull Lever Listings

4099-9004 Single Action, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM 4099-9004CB Single Action, Bilingual English and French FEU FIRE TIREZ PULL

ULC 4099-9004CF Single Action, French ALARME FEU ABAISSEZ 4099-9004PO Single Action, Portuguese FOGO ALARME PUXE

UL, FM 4099-9004SP Single Action, Spanish ALARMA FUEGO JALE 4099-9005 Double Action, Breakglass operation, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM 4099-9005PO Double Action, Breakglass operation, Portuguese FOGO ALARME PUXE

UL, FM 4099-9005SP Double Action, Breakglass operation, Spanish ALARMA FUEGO JALE 4099-9006 Double Action, Push operation, English FIRE ALARM PUSH PULL DOWN UL, ULC, FM, CSFM 4099-9006PO Double Action, Push operation, Portuguese FOGO ALARME EMPURRE PUXE

UL, FM 4099-9006SP Double Action, Push operation, Spanish ALARMA FUEGO EMPUJE JALE 4099-9021 Single Action NO GRIP operation, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM

Accessories (refer to pages 3 and 4 for details) Model Description Model Description

2975-9022 Cast aluminum surface mount box, red 2099-9803 Replacement breakglass 2975-9178 Surface mount steel box, red 2099-9804 Replacement break-rod

2099-9813 Semi-flush trim plate for double gang switch box, red 2099-9828 Institutional cover kit for field installation on 4099-9004;

Note: Covers LED indicator 2099-9819 Flush mount adapter kit, black

2099-9814 Surface trim plate for Wiremold box V5744-2, red 2099-9820 Flush mount adapter kit, beige

4099-9805 Retrofit Kit for field conversion of a single action station to a NO GRIP station; refer to Installation Instructions 579-1007 for details

Power and Communications IDNet or MAPNET II communications, 1 address per station Address Means DIP switch, 8 position Wire Connections Screw terminal for in/out wiring, for 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2) UL Listed Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° F) Housing Color Red with white raised lettering Material Housing and pull lever are Lexan polycarbonate or equal Pull Lever Color White with red raised lettering Housing Dimensions 5” H x 3 ¾” W x 1” D (127 mm x 95 mm x 25 mm)

Single gang cover plate, 3/4" (19 mm) extension, RACO #773

or equal (supplied by others)

Stationside view

Wall surface

Single gang box outline

4" Square boxwith cover plate

Semi-Flush Mount Side View

Single Gang Box MountSingle gang box, 2 1/2" deep

(64 mm), RACO #500 or equal(supplied by others)

Mount flush or with1/16" (2 mm)

maximum extensionDO NOT RECESS

ALARMFIRE

PULL DOWN

LED Indicator

4" Square Box Mount4" (102 mm) square box, 2 1/8" (54 mm) minimum

depth, RACO #231 or equal (supplied by others)

Addressable Manual Station Semi-Flush Mounting

Specifications (refer to Installation Instructions 579-1135 for additional information)

Addressable Manual Station Product Selection

Page 69: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Preferred Mounting. For surface mounting of these addressable manual stations, the preferred electrical boxes are shown in the illustration to the right.

Additional Mounting Reference. Refer to page 4 for Wiremold box mounting compatibility.

3 S4099-0005 10/2014

Application Reference

Refer to NFPA 72, the National Fire Alarm and Signaling Code, and all applicable local codes for complete requirements for manual stations. The following summarizes the basic requirements.

1. Stations shall be located in the normal path of exit and distributed in the protected area such that they are unobstructed and readily accessible.

2. Mounting shall be with the operable part not less than 42 in (1.07 m) and not more than 48 in (1.22 m) above floor level.

3. At least one station shall be provided on each floor. Additional stations shall be provided to obtain a travel distance not more than 200 ft (61 m) to the nearest station from any point in the building.

4. When manual station coverage appears limited in any way, additional stations should be installed.

2975-9178 Box5-3/16" H x 4" W x 2-3/16" D (132 mm x 102 mm x 56 mm)

(ordered separately)

Knockouts located top and bottom

2975-9022 Cast Box5" H x 3-7/8" W x 2-3/16" D (127 mm x 98 mm x 56 mm)

(ordered separately)

Access for 3/4" threaded conduit located top and bottom5"

(127 mm)

FIRE ALARMFIRE

PULL DOWN

4099 Series Addressable Manual Station

1" (25.4 mm)

3-3/4" (95 mm)

Station coverhinges open for

installation access

Simplex 2975-9178 box(shown for reference)

Address setting underresealable label (accessible

with cover open)

Switch wiring(prewired)

Field wiring(shown for reference)

1-1/4"(32 mm)

2-5/8"(67 mm)

Addressable Manual Stations Surface Mounting

Surface Mount Side View with Internal Detail

Page 70: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

For retrofit and new installations, additional compatible mounting boxes and the required adapter plates are shown in the illustration to the right.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). Lexan is a trademark of the General Electric Co. Wiremold is a trademark of the Wiremold Company.

8" (203 mm)

6" (152 mm)

4-3/4" (121 mm)

6-3/4" (171 mm)

Front View

Flush mount adapter kit2099-9819, Black2099-9820, Beige

Wall surface

4-11/16" (119 mm) square box, 2-1/8" (54 mm) minimum depth (by others)

Side View

Box must be recessed into wall 1" to 1-1/8" (25.4 mm to 29 mm)

Hole cutout must be a minimum of 6" H by 5" W

(152 mm by 127 mm)

2099-9814 Surface trim for Wiremold box

5-1/8" H x 5" W (130 mm x 127 mm)

Addressable station

Two gang switch box, each3" H x 2" W x 2-3/4" D (76 mm x 51 mm x 70 mm)(supplied by others)

2099-9813 Semi-flush trim for 2 gang switch box, 6" H x 4-1/2" W

(152 mm x 114 mm)

Wiremold receptacle box model V5744-2 (supplied by others)

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4099-0005 10/2014

www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Addressable Manual Station, Additional Mounting Information

Addressable Manual Station, Flush Mounting Information

Page 71: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

TrueAlarm analog sensing provides: Digital transmission of analog sensor values via IDNet

or MAPNET II two-wire communications

For use with the following Simplex® products: 4007ES, 4010, 4010ES, 4100ES, and 4100U Series

control panels; and 4008 Series control panels with reduced feature set (refer to data sheet S4008-0001 for details)

4020, 4100, and 4120 Series control panels, Universal Transponders, and 2120 TrueAlarm CDTs equipped for MAPNET II operation

Fire alarm control panel provides: Peak value logging allowing accurate analysis of each

sensor for individual sensitivity selection Sensitivity monitoring satisfying NFPA 72 sensitivity

testing requirements; automatic individual sensor calibration check verifies sensor integrity

Automatic environmental compensation, multi-stage alarm operation, and display of sensitivity directly in percent per foot

Ability to display and print detailed sensor information in plain English language

Photoelectric smoke sensors provide: Seven levels of sensitivity from 0.2% to 3.7%

(refer to additional information on page 3)

Heat sensors provide: Fixed temperature sensing Rate-of-rise temperature sensing Utility temperature sensing Listed to UL 521 and ULC-S530

General features: Listed to UL 268 and ULC-S529 Louvered smoke sensor design enhances smoke

capture by directing flow to chamber; entrance areas are minimally visible when ceiling mounted

Designed for EMI compatibility Magnetic test feature is provided Different bases are available to support a supervised

or unsupervised output relay, and/or a remote LED alarm indicator

Additional base reference: For isolator bases, refer to data sheet S4098-0025 For sounder bases, refer to data sheet S4098-0028 For photo/heat sensors, refer to data sheet S4098-0024

(single address) and S4098-0033 (dual address)

* These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listings 7272-0026:218, 7271-0026:231, 7270-0026:216, and 7300-0026:217 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

4098-9714 TrueAlarm Photoelectric Sensor Mounted in Base

Description Digital Communication of Analog Sensing. TrueAlarm analog sensors provide an analog measurement digitally communicated to the host control panel using Simplex addressable communications. At the control panel, the data is analyzed and an average value is determined and stored. An alarm or other abnormal condition is determined by comparing the sensor’s present value against its average value and time.

Intelligent Data Evaluation. Monitoring each sensor’s average value provides a continuously shifting reference point. This software filtering process compensates for environmental factors (dust, dirt, etc.) and component aging, providing an accurate reference for evaluating new activity. With this filtering, there is a significant reduction in the probability of false or nuisance alarms caused by shifts in sensitivity, either up or down.

Control Panel Selection. Peak activity per sensor is stored to assist in evaluating specific locations. The alarm set point for each TrueAlarm sensor is determined at the host control panel, selectable as more or less sensitive as the individual application requires.

Timed/Multi-Stage Selection. Sensor alarm set points can be programmed for timed automatic sensitivity selection (such as more sensitive at night, less sensitive during day). Control panel programming can also provide multi-stage operation per sensor. For example, a 0.2% level may cause a warning to prompt investigation while a 2.5% level may initiate an alarm.

Sensor Alarm and Trouble LED Indication. Each sensor base’s LED pulses to indicate communications with the panel. If the control panel determines a sensor is in alarm, or is dirty or has some other type of trouble, the details are annunciated at the control panel and that sensor base’s LED will be turned on steadily. During a system alarm, the control panel will control the LEDs such that an LED indicating a trouble will return to pulsing to help identify the alarmed sensors.

TrueAlarm Analog Sensing UL, ULC, CSFM Listed; FM Approved; TrueAlarm Analog Sensors – Photoelectric MEA (NYC) Acceptance* and Heat; Standard Bases and Accessories

S4098-0019-19 11/2014

Page 72: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

ALARM

Sensor Base Features

Base mounted address selection: Address remains with its programmed location Accessible from front (DIP switch under sensor) General features: Automatic identification provides default sensitivity when

substituting sensor types Integral red LED for power-on (pulsing), or alarm or trouble

(steady on) Locking anti-tamper design mounts on standard outlet box Magnetically operated functional test

Sensor Bases

4098-9792, Standard Sensor Base 4098-9789, Sensor Base with wired connections for: 2098-9808 Remote LED alarm indicator or 4098-9822 relay

(relay is unsupervised and requires separate 24 VDC) Supervised Relay Bases (not compatible with 2120 CDT): 4098-9791, 4-Wire Sensor Base, use with remote or

locally mounted 2098-9737 relay, requires separate 24 VDC 4098-9780, 2-Wire Sensor Base, use with remote or

locally mounted 4098-9860 relay, no separate power required

Supervised relay operation is programmable and can be manually operated from control panel

Includes wired connections for remote LED alarm indicator or 4098-9822 relay (relay is unsupervised and requires separate 24 VDC)

Sensor Base Options

2098-9737, Remote or local mount supervised relay: DPDT contacts for resistive/suppressed loads, power limited

rating of 3 A @ 28 VDC; non-power limited rating of 3 A @ 120 VAC (requires external 24 VDC coil power)

4098-9860, Remote or local mount supervised relay: SPDT dry contacts, power limited rating of 2 A @ 30 VDC,

resistive; non-power limited rating of 0.5 A @ 125 VAC, resistive

4098-9822, LED Annunciation Relay: Activates when base LED is on steady, indicating local

alarm or trouble DPDT contacts for resistive/suppressed loads, power limited

rating of 2 A @ 28 VDC; non-power limited rating of 1/2 A @ 120 VAC, (requires external 24 VDC coil power)

4098-9832, Adapter plate: Required for surface or semi-flush mounting to 4” square

electrical box and for surface mounting to 4” octagonal box Can be used for cosmetic retrofitting to existing 6-3/8”

diameter base product 2098-9808, Remote red LED Alarm Indicator: Mounts on single gang box (shown in

illustration to right)

Description

TrueAlarm sensor bases contain integral addressable electronics that constantly monitor the status of the detachable photoelectric or heat sensors. Each sensor’s output is digitized and transmitted to the system fire alarm control panel every four seconds.

Since TrueAlarm sensors use the same base, different sensor types can be easily interchanged to meet specific location requirements. This feature also allows intentional sensor substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect sensor type, the heat sensor will operate at a default sensitivity providing heat detection for building protection at that location.

Mounting Reference

Electrical Box Requirements: (boxes are by others)

Without relay in the box: 4" octagonal or 4" square, 1-1/2" deep; single gang, 2" deep

With relay in the box : 4" octagonal or 4" square, 1-1/2" deep, with 1-1/2" extension ring

TrueAlarm Bases4098-9780, 4098-9789, 4098-9791, & 4098-9792

4-7/8" (124 mm)

15/16" (24 mm)

6-3/8" (162 mm)

1/4"(6.4 mm)

4098-9832 Adapter Plate, required for mounting to surface mounted boxes

and 4" square flush box

2098-9737 Supervised Relay(mounts in base electrical box or remotely)

4098-9822 Relay (mounts in base electrical box)

NOTE: Review total wire count, wire size, and accessories being wired to determine required box volume.

Relay Size: 2-1/2" X 1-1/2" X 1"(3.75 in3 ) (64 mm X 38 mm X 25.4 mm)

4098-9860 Supervised Relay (mounts in base electrical box or remotely; 2-3/8" X 1-1/4" X 11/32"(1 in3 ) (60.4 mm X 31.8 mm X 8.6 mm)

Surface mount reference 4" (102 mm) Square Box 4" (102 mm) Octagonal Box

Flush mount reference, mount even with finalsurface, or with up to 1/4" (6.4 mm) maximum recess

1-1/2" (38 mm)minimum box depth

2 S4098-0019-19 11/2014

TrueAlarm Sensor Bases and Accessories

dthurston
Line
Page 73: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TrueAlarm Sensors Features

Sealed against rear air flow entry Interchangeable mounting EMI/RFI shielded electronics Heat sensors: Selectable rate compensated, fixed temperature

sensing with or without rate-of-rise operation

Rated spacing distance between sensors:

Fixed Temp. Setting

UL & ULC Spacing

FM Spacing, Either Fixed Temperature Setting

135° F (57.2° C)

60 ft x 60 ft (18.3 m)

20 ft x 20 ft (6.1 m) for fixed temperature only; RTI = Quick 50 ft x 50 ft (15.2 m) for fixed temperature with either rate-of-rise selection; RTI = Ultra Fast

155° F (68° C)

40 ft x 40 ft (12.2 m)

Smoke Sensors: Photoelectric technology sensing

360° smoke entry for optimum response

Built-in insect screens

4098-9714 Photoelectric Sensor

TrueAlarm photoelectric sensors use a stable, pulsed infrared LED light source and a silicon photodiode receiver to provide consistent and accurate low power smoke sensing. Seven levels of sensitivity are available for each individual sensor, ranging from 0.2% to 3.7% per foot of smoke obscuration. Sensitivities of 0.2%, 0.5%, and 1% are for special applications in clean areas. Standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and 3.7%. Application type and sensitivity are selected and then monitored at the fire alarm control panel.*

The sensor head design provides 360° smoke entry for optimum response to smoke from any direction. Due to its photoelectric operation, air velocity is not normally a factor, except for impact on area smoke flow.

2-1/8"(54 mm)

LED status indicator

4-7/8" (124 mm)

4098-9714 Photoelectric Sensor with Base

4098-9733 Heat Sensor

TrueAlarm heat sensors are self-restoring and provide rate compensated, fixed temperature sensing, selectable with or without rate-of-rise temperature sensing. Due to its small thermal mass, the sensor accurately and quickly measures the local temperature for analysis at the fire alarm control panel.

Rate-of-rise temperature detection is selectable at the control panel for either 15° F (8.3° C) or 20° F (11.1° C) per minute. Fixed temperature sensing is independent of rate-of-rise sensing and programmable to operate at 135° F (57.2° C) or 155° F (68° C). In a slow developing fire, the temperature may not increase rapidly enough to operate the rate-of-rise feature. However, an alarm will be initiated when the temperature reaches its rated fixed temperature setting.

TrueAlarm heat sensors can be programmed as a utility device to monitor for temperature extremes in the range from 32° F to 155° F (0° C to 68° C). This feature can provide freeze warnings or alert to HVAC system problems. Refer to specific panels for availability.

2-3/8"(60 mm)

LED status indicator

4-7/8" (124 mm)

4098-9733 Heat Sensor with Base

WARNING: In most fires, hazardous levels of smoke and toxic gas can build up before a heat detection device would initiate an alarm. In cases where Life Safety is a factor, the use of smoke detection is highly recommended.

Application Reference

Sensor locations should be determined only after careful consideration of the physical layout and contents of the area to be protected. Refer to NFPA 72, the National Fire Alarm and Signaling Code. On smooth ceilings, smoke sensor spacing of 30 ft (9.1 m) may be used as a guide.*

* For detailed application information including sensitivity selection, refer to Installation Instructions 574-709.

3 S4098-0019-19 11/2014

dthurston
Line
Page 74: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TrueAlarm Sensor Bases (for use with Sensors 4098-9714 and 4098-9733) (Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information)

Model Description Compatibility Mounting Requirements

4098-9792 Standard Sensor Base No options 4” octagonal or 4” square box, 1-1/2” min. depth; or single gang box, 2” min. depth

4098-9789 Sensor Base with connections for Remote LED Alarm Indicator or Unsupervised Relay

2098-9808 Remote Alarm Indicator or 4098-9822 Unsupervised Relay 4” octagonal or 4” square box

Note: Box depth requirements depend on total wire count and wire size, refer to accessories list below for reference.

** NOTE: 4098-9791 and 4098-9780 are NOT compatible with the 2120 CDT

4098-9791** 4-Wire Sensor Supervised Relay Base with connections for LED Indicator or Unsupervised Relay

2098-9737 Supervised Remote Relay 2098-9808 Remote Alarm Indicator or 4098-9822 Unsupervised Relay

4098-9780** 2-Wire Sensor Supervised Relay Base with connections for LED Indicator or Unsupervised Relay

4098-9860 Supervised Remote Relay 2098-9808 Remote Alarm Indicator or 4098-9822 Unsupervised Relay

TrueAlarm Sensors Model Description Compatibility Mounting Requirements

4098-9714 Photoelectric Smoke Sensor Bases 4098-9792, 4098-9789, 4098-9791, and 4098-9780 Refer to base requirements

4098-9733 Heat Sensor

TrueAlarm Sensor/Base Accessories Model Description Compatibility Mounting Requirements

2098-9737 Supervised Relay, mounts remote or in base electrical box For use with 4098-9791 base Remote Mounting requires 4” octagonal

or 4” square box, 1-1/2” minimum depth Base Mounting requires 4” octagonal box, 2-1/8” deep with 1-1/2” extension ring4098-9860 Supervised Relay, mounts remote or in base

electrical box For use with 4098-9780 base

2098-9808 Remote Red LED Alarm Indicator on single gang stainless steel plate

Bases 4098-9789, 4098-9791, and 4098-9780 Single gang box, 1-1/2” minimum depth

4098-9822 Unsupervised Relay, tracks base LED status; Note: Mounts only in base electrical box

Bases 4098-9789, 4098-9791, and 4098-9780

4” octagonal box, 2-1/8” deep with 1-1/2” extension ring

4098-9832 Adapter Plate Bases 4098-9792, 4098-9789, 4098-9791, and 4098-9780

Required for surface or semi-flush mounted 4” square box and for surface mounted 4” octagonal box

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4098-0019-19 11/2014

www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

General Operating Specifications Communications and Sensor Supervisory Power IDNet or MAPNET II communications, auto-selected, 1 address per base Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm2 to 2.08 mm2) Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm2 ) UL Listed Operating Temperature Range 32° to 100° F (0° to 38° C)

Operating Temperature Range

with 4098-9733 Heat Sensor 32° to 122° F (0° to 50° C) with 4098-9714 Smoke Sensor 15° to 122° F (-9° to 50° C)

Storage Temperature Range 0° F to 140° F (-18° C to 60° C) Humidity Range 10 to 95% RH 4098-9714 Smoke Sensor Air Velocity Rating 0-4000 ft/min (0-1220 m/min) Housing Color Frost White

4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC) Supervisory Current 270 A, from 24 VDC supply Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply

4098-9780 Base With Supervised Remote Relay 4098-9860 (see page 2 for contact ratings) Power Supplied from communications

4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789. 4098-9791, and 4098-9780 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC) Supervisory Current Supplied from communications Alarm Current 13 mA from separate 24 VDC supply

TrueAlarm Analog Sensing Product Selection Chart

Specifications

Page 75: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a

TrueAlarm photoelectric, photo/heat or heat sensor (ordered separately)

TrueAlarm sensor bases with 520 Hz tone are multi-point devices, use a single IDNet address, and receive communications and sensor power from the IDNet channel (the sounder base requires separate 24 VDC system power or NAC connection)

IDNet circuit allows the sounder to be supervised and coded by compatible NACs, allowing synchronized temporal, march time, or other channel coding.

Sensor and sounder operation is listed to UL Standard 268, UL Standard 464, and ULC Standard S529

Sounder operation is also listed to UL Standard 464 as an audible notification appliance

Sensor base with photoelectric or photo/heat sensor operation Independent sensor operation or selectable multi-sensor

modes for false alarm reduction or faster detection Photoelectric, photo/heat, or heat sensors can be

analyzed to reject non-fire conditions that can trigger false alarms (steam, dust, etc)

520 Hz Sounder base operation Low Frequency sound output (520Hz at 85 dBA)

The base can supervise the sounder drive circuit when an AUX 24V power line is used for sounder power. Alternatively, base supervision can be disabled if a supervised NAC is needed to power the sounder for coded outputs.

Sounder can be manually activated from the panel

Panel operation summary Analog sensor information is digitally transmitted to the

host control panel via IDNet communications for processing to evaluate and track status

General features Ceiling mount operation Optional accessories include remote alarm LED and

mounting adapter plate Designed for EMI compatibility Magnetic test feature

TrueAlarm Sensor Base with 520 hz sounder 4098-9772 with Heat Sensor installed

520 Hz Sounder Base Features

Base mounted address selection allows the address to remain with its programmed location when the sensor is removed for service or type change.

Automatic sensor type identification provides default sensitivity when substituting sensor types. Different sensor types can be easily interchanged to meet specific location requirements. This feature also allows intentional sensor substitution during building construction. Instead of covering the smoke sensors when conditions are temporarily dusty, heat sensors may be installed without reprogramming the control panel.

Integral red LED indicates power-on by pulsing, or alarm or trouble when steady on. The exact status is annunciated at the fire alarm control panel.

Application Reference

Determine sensor locations after careful consideration of the physical layout and contents of the area to be protected.

For fire alarm applications: Refer to NFPA 72, the National Fire Alarm and

Signaling Code

On smooth ceilings, smoke sensor spacing of 30 ft (9.1 m) may be used as a guide.

For detailed application information: Refer to 4098 Detectors, Sensors, and Bases Application

Manual, Part Number 574-709.

* Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

TrueAlarm ES Analog Sensing UL listed, FM approved* TrueAlarm 4098-9772 Sensor Base

with 520 Hz Sounder

S4098-0054-1 11/2015

dthurston
Line
Page 76: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Control Panel Operations

Smoke sensor features include: sensitivity monitoring satisfying NFPA 72 sensitivity testing requirements, automatic individual sensor calibration checking to verify sensor integrity, automatic environmental compensation, available multi-stage alarm operation, display of sensitivity directly in percent per foot, monitoring of peak activity per sensor, alarm set point, and time of day or multi-stage alarm selection.

Sensor Alarm and Trouble LED Indications The sensor base LED pulses to indicate communications with the panel. If a sensor is in alarm, or has a trouble condition, the status is annunciated at the control panel and that base LED will turn on steady. During a system alarm, the panel will control LEDs such that a trouble indication will return to pulsing to help identify the sensors in alarm. Multi-Point Allocation 4007ES, 4010ES, and 4100ES control panels require only one (1) point at the host panel per sensor base. Depending on sensor base and sensor choice, up to seven (7) points can be made public to a connected Simplex Fire Alarm Network. Each sensor base uses a single address with “sub-points” layered underneath (such as 1-1-0, 1-1-1, 1-1-2, ….1-1-6).

For 4100U control panels, the requirement is three (3) points at the host panel per sensor base with the 4098-9754 multi-sensor, and two (2) points for the other sensors. Additional multi-point allocation detail is described in reference data sheet S4090-0011.

Control Panel Operations (Continued)

Sensor Base with 520 Hz Power Requirements Power for the sensor base is provided by IDNet communications. No additional wiring is required for upgrading of existing installed TrueAlarm sensor bases. Sensor sounder bases do require system supplied separate VDC (or NAC) wiring, the same as the standard sounder base. Accessories

2098-9808, Remote red LED Alarm Indicator mounts on a single gang box to provide status indications where the sensor location may not be readily visible. (See illustration to right.)

2098-9808 Remote LED Alarm Indicator

TrueAlarm Analog Sensor Features

Sealed against rear air flow entry Electronics are EMI/RFI shielded Heat sensing: Selectable rate compensated, fixed temperature

sensing with or without rate-of-rise operation

Rated spacing distance between sensors:

Fixed Temp. Setting

UL& ULC Spacing

FM Spacing, Either Fixed Temperature Setting

135° F (57.2° C)

60 ft x 60 ft (18.3 m)

20 ft x 20 ft (6.1 m) for fixed temperature only; RTI = Quick 50 ft x 50 ft (15.2 m) for fixed temperature with either rate-of-rise selection; RTI = Ultra Fast

155° F (68° C)

40 ft x 40 ft (12.2 m)

Smoke Sensors: Photoelectric technology sensing

360° smoke entry for optimum response

Built-in insect screens

4098-9714 Photoelectric Sensor

TrueAlarm photoelectric sensors use a stable, pulsed infrared LED light source and a silicon photodiode receiver to provide consistent and accurate low power smoke sensing. Seven levels of sensitivity are available for each individual sensor, ranging from 0.2% to 3.7% per foot of smoke obscuration. Sensitivities of 0.2%, 0.5%, and 1% are for special applications in clean areas. Standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and 3.7%. Application type and sensitivity are selected and then monitored at the fire alarm control panel. (For detailed application information about sensitivity selection, refer to Installation Instructions 574-709.)

The sensor head design provides 360° smoke entry for optimum smoke response. Due to its photoelectric operation, air velocity is not normally a factor, except for impact on area smoke flow.

4098-9714 Photoelectric Sensor on sensor base

4098-9754 Multi-Sensor

TrueAlarm multi-sensors combine the performance of TrueAlarm photoelectric smoke sensing with TrueAlarm thermal sensing to provide both features in a single assembly. Each sensing element provides data for evaluation at the fire alarm control panel where the following four independent detection modes are evaluated:

Fixed temperature heat detection Rate-of-rise heat detection TrueAlarm photoelectric smoke detection And TrueSense correlation detection

2 S4098-0054-1 11/2015

ALARM

dthurston
Line
Page 77: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

4098-9754 Multi-Sensor (Continued)

Multi-Sensor on Sensor Base

TrueSense analysis correlates thermal activity and smoke activity at a single multi-sensor location using an extensively tested covariance relationship. As a result, TrueSense detection improves response to conditions indicative of faster acting, hot flaming fires when compared to the response of either photoelectric smoke activity or thermal activity alone.

4098-9733 Heat Sensor

TrueAlarm heat sensors are self-restoring and provide rate compensated, fixed temperature sensing, selectable with or without rate-of-rise temperature sensing. Due to its small thermal mass, the sensor accurately and quickly measures the local temperature for analysis at the fire alarm control panel.

Rate-of-rise temperature detection is selectable at the control panel for either 15° F (8.3° C) or 20° F (11.1° C) per minute. Fixed temperature sensing is independent of rate-of-rise sensing and programmable to operate at 135° F (57.2° C) or 155° F (68° C). In a slow developing fire, the temperature may not increase rapidly enough to operate the rate-of-rise feature. However, an alarm will be initiated when the temperature reaches its rated fixed temperature setting.

TrueAlarm heat sensors can be programmed as a utility device to monitor for temperature extremes in the range from 32° F to 155° F (0° C to 68° C). This feature can provide freeze warnings or alert to HVAC system problems.

4098-9733 Heat Sensor on Sensor Base

WARNING: In most fires, hazardous levels of smoke and toxic gas can build up before a heat detection device would initiate an alarm. In cases where Life Safety is a factor, the use of smoke detection is highly recommended.

Install Reference

3 S4098-0054-1 11/2015

Page 78: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TrueAlarm Sensor Base

Model Description 4098-9772 Sensor base with 520 Hz Sounder

TrueAlarm Sensors (select one per Sensor Base with 520 Hz Sounder) Model Description

4098-9714 Photoelectric Smoke Sensor Refer to selection table below for available operation modes 4098-9754 Multi-Sensor Photoelectric and Heat Sensing

4098-9733 Heat Sensor Accessories (ordered separately as required)

Model Description Mounting Requirements 4098-9863 Adapter Plate required for surface flush 4” square electrical

boxes. Refer to page 6, mounting reference

2098-9808 Remote red LED Alarm Indicator on single gang stainless steel plate. Single gang box, 1-1/2” minimum depth

Note: Refer to Installation Instructions 574-707 and Application Manual 574-709 for additional information.

4 S4098-0054-1 11/2015

Sensor Choice Mode Operational Mode Choices* ( = operation selected)

False Alarm Reduction

Faster Detection

TrueSense Photo/Heat Photo Fire Heat Fire** Utility Temp. Ion Fire

Photoelectric Smoke Sensor 4098-9714

1 — — — — — —

2 — — option — — —

Photo/Heat Multi-Sensor 4098-9754

3 — — — option option —

4 — — option option option —

5 — option option option

Heat Sensor 4098-9733

6 — — — — option —

7 — — — — option —

* NOTE: Duct detection modes are not applicable and are not available. Refer to the Multi-Point Allocation discussion on page 3 for panel point requirement information.

** Heat Fire Mode is 135° F or 155° F, fixed or rate-of-rise.

Sensor Base Operation Options with Sensor Choice

Sensors and Accessories Product Selection

Page 79: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

General Operating Specifications Communications and Sensor Supervisory Power IDNet communications, 1 address per base Communications and Sounder Power Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm2 to 2.08 mm2)

Remote LED Alarm Indicator Current 1 mA typical supplied from communications, no impact to alarm current

LED Connections Color coded wire leads, 18 AWG (0.82 mm2 )

UL Listed Temperature Range 32° F to 100° F (0° C to 38° C)

Operating Temperature Range

with 4098-9733, 4098-9714 or 4098-9754 32° F to 122° F (0° C to 50° C)

Humidity Range 10 to 95% RH Smoke Sensor Ambient Ratings

4098-9714, Photoelectric Sensor Air velocity is 0-4000 ft/min (0-1220 m/min)

Housing Color Frost White

Installation Instructions 574-707 Sounder Operation Sounder Voltage 24 VDC nominal, 16 to 32 VDC from NAC

Alarm Current (Sounder On) 520Hz signal 129 mA @ 16 V, 115 mA @ 18 V

Broadband signal 139 mA @ 16 V, 125 mA @ 18 V

Sounder Output

Minimum sound output @ 10 ft (3 m) per UL Standard 464, Audible Signaling Appliance

Minimum sound output @ 10 ft (3 m) per UL Standard 268, Smoke Detectors for Fire Protective Signaling Systems and CSA 6.19-01

520 Hz signal 80 dBA 86 dBA

Broadband signal 81 dBA 87 dBA

Base Supervision of Sounder Power Input (Selectable)

Supervised Select for continuous 24 VDC power, loss of power is communicated to panel

Unsupervised Select when connected to NAC for sounder power, NAC provides supervision

NAC Powered Operation When in alarm, will sound when NAC is in alarm, allowing synchronized pattern (Temporal or March Time, etc.) controlled by the NAC control

Product Data Sheet Product Data Sheet Temporal Code 4 Module S4905-0006 4100ES Control Panels with EPS

Power Supplies S4100-0100

Standard Bases S4098-0019 4100ES Standard Control Panels S4100-0031 Isolator Bases S4098-0025 4100ES Audio Control Reference S4100-0034 Standard Sounder Base S4098-0028 4010ES Control Panels S4010-0004 TrueSense Multi-Sensor S4098-0024 4007ES Hybrid Control Panels S4007-0001 TrueAlarm 4098-9773 CO Sensor Base with 520 Hz Sounder

S4098-0053

5 S4098-0054-1 11/2015

Specifications

Additional Information Reference

Page 80: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4098-0054-1 11/2015

www.simplex-fire.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA).

Page 81: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

IDNet or MAPNET II addressable communications supply both data and power over a single wire pair to provide**: Supervised Class B monitoring of normally open, dry

contacts Total wiring distance from IAM to supervision

resistor(s) of up to 500 ft (152 m) Monitored connection is compatible with Simplex®

2081-9044 Overvoltage Protectors for outdoor wiring or electrically noisy applications

For use in indoor locations up to 158° F (70° C) such as attic spaces or similar applications

For use with following Simplex control panels: Model Series 4007ES, 4008, 4010, 4010ES, and 4100ES

fire alarm control panels for IDNet communications Model Series 4100/4100U/4100ES, 4120, 4020, and

2120 Communicating Device Transponders (CDTs) equipped with MAPNET II communications

Model 4090-9001: Enclosed design minimizes dust infiltration Mounts in standard single gang electrical box Screw terminals for wiring connections Visible LED flashes to indicate communications Optional covers are available to allow LED to be

viewed after installation (requires mounting bracket, ordered separately)

Model 4090-9051: Encapsulated design for extended exposure to high

humidity (LED is not present on this model) Color coded 18 AWG leads for wiring

IDNet communications provides current limited monitoring: Provides monitoring of tamper switch (supervisory)

and waterflow switch (alarm) on same circuit using one point

Available with IDNet communications only

Multiple operation modes are available and are selectable at the control panel: Contact closure status can be tracked Momentary contact closure conditions can be selected at

the panel to be latched or tracked (not available with the 2120 CDT)

UL listed to Standard 864 * These products have been approved by the California State Fire Marshal (CSFM) pursuant

to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products .

- IDNET IN ++IDNET IN -

4090-9001 Supervised IAM (shown approximately 3/4 size)

LISTEDSIGNALING DEVICEISSUE NO.

4090-9051 Supervised IAM (shown approximately 3/4 size)

Description

Individual addressable modules (IAMs) receive both power and communications from a two-wire MAPNET II or IDNet circuit. They provide location specific addressability to a single initiating device (such as single station smoke detector alarm contacts or heat detector contacts) or multiple devices at the same location by monitoring normally open dry contacts and the wiring to an end-of-line resistor.

Model 4090-9001 is packaged in a thermoplastic housing and provides screw terminal connections and a status indicating LED.

Model 4090-9051 is an encapsulated package with wire leads. It does not provide a status indicating LED.

Multi-Application Peripherals UL, ULC, CSFM Listed; FM Approved; IDNet and MAPNET II Communicating Devices, MEA (NYC) Acceptance* Individual Addressable Modules (IAMs)

S4090-0001-11 11/2014

dthurston
Line
Page 82: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Operation

Contact Closure. Closure of the monitored contact(s) initiates an alarm or other response as programmed at the fire alarm control panel. An open in the monitored circuit wiring will cause a trouble to be reported.

Panel Selections. Selections can be made at the control panel to maintain the alarm condition if the initiating device contacts are momentary, such as from a rate-of-rise heat detector, or to track the device contact status (not available with the 2120 CDT).

Current Limited Operation Applications

For use with IDNet communications only, these IAMs can provide quad-state sensing of normal, open circuit, short circuit, and current limited conditions. (Program type is “T-sense.”) With the proper end-of-line and current limiting resistors, dual functions such as tamper switch and waterflow switch monitoring can be determined and communicated by a single addressable point.

Model Description 4090-9001 Supervised IAM, mounted in thermoplastic housing with screw terminals; see applicable options below

4090-9051 Supervised IAM, encapsulated with wire leads

Optional Trim Plates and Mounting Bracket for Model 4090-9001 Model Description

4090-9806 For semi-flush mounted box Trim plate with LED viewing window, requires 4090-9810 mounting bracket, includes mounting screws; galvanized steel 4090-9807 For surface mounted box

4090-9810 Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim plates

End-of-Line Resistor Harnesses (ordered separately as required) Model Reference No. Description

4081-9004 733-886 6.8 k, 1/2 W; Standard end-of-line resistor harness for N.O. contact supervision

4081-9003 733-896 4.7 k, 1/2 W Use for current limited monitoring applications

4081-9005 733-984 1.8 k, 1/2 W

Electrical Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM

Input Requirements Normally open, dry contacts

Wire Connections 4090-9001 Screw terminals for in/out wiring, 18 to 14 AWG wire

(0.82 mm2 to 2.08 mm2)

4090-9051 Color coded wire leads, 18 AWG (0.82 mm2), 8” long (203 mm)

Reference Documents Installation Instructions 574-331 for 4090-9001; 579-572 for 4090-9151

Field Wiring Diagrams 842-073 for IDNet operation; 841-804 for MAPNET II operation

Wiring Distances

Distance from IAM to Contacts 500 ft (152 m) maximum without protectors

400 ft (122 m) maximum with 2081-9044 Overvoltage Protectors

Wiring Distance Reference per channel, MAPNET II or IDNet Communications

2500 ft (762 m) maximum from fire alarm control panel

10,000 ft (3048 m) maximum total wiring distance (including T-Taps)

Mechanical

Dimensions 4090-9001 1-9/16” W x 1-3/4” H x 1-1/4” D (40 mm x 44 mm x 32 mm)

4090-9051 1-9/16” W x 1-9/16” H x 9/16” D (40 mm x 40 mm x 14 mm)

Housing Material, 4090-9001 Black thermoplastic

Encapsulation Material, 4090-9051 Epoxy, beige

Temperature Range 32° to 158° F (0° to 70° C); intended for indoor operation

Humidity Range Up to 93% RH at 100° F (38° C)

2 S4090-0001-11 11/2014

IAM Product Selection

Specifications

Page 83: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Optional Trim Plates and Mounting Bracket for Visible LED

Single gang electricalbox 2-1/2" (64mm)minimum depth(supplied by others)

Single gang blank cover plate and mounting screws, for use whenLED is not required to be externally viewed (supplied by others)

4090-9001 IDNetsupervised IAM

Field wiring shownfor reference

Address setting under resealable label

- IDNET IN ++IDNET IN -

LED viewing port

4090-9806, Trim plate for semi-flush mounted box

4090-9807, Trim plate for surface mounted box

4-1/4"(108 mm)

2-1/2"(64 mm)

2-13/16"(72 mm)

4-1/2"(114 mm)

Light pipe forLED viewing

NOTE: These mounting plates require mounting bracket 4090-9810.

4090-9810 Mountingbracket, ordered

separately

Mounting Reference, Single Gang Blank Cover Plate

2 S4090-0001-11 11/2014

Mounting Information

Page 84: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Single gang electricalbox 2-1/2" (64mm)minimum depth(supplied by others)

Single gang blank cover plate andmounting screws (supplied by others)

4090-9051Encapsulated

Supervised IAM

Address setting isat rear of housing

LISTEDSIGNALING DEVICEISSUE NO.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4090-0001-11 11/2014

www.simplex-fire.com © 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

4090-9051 Mounting Information

Page 85: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Individual Addressable Relay Module (Relay IAM): IDNet addressable control for use with Simplex® fire

alarm control panel models 4100ES, 4010ES, 4100U, 4008, and 4010

A single addressable point provides control and status tracking of a Form “C” contact

Low power latching relay design allows IDNet communications to supply both data and module power

Relay is set to OFF on initial power up and upon loss of IDNet communications

Compact, sealed construction: Enclosed design minimizes dust infiltration

Mounts in standard 4” (102 mm) square electrical box, optional adapter bracket is available to mount in a 4 11⁄16” (119 mm) square electrical box

Screw terminals for wiring connections

Visible LED flashes to indicate communications

Optional covers are available to allow LED to be viewed after installation

UL listed to Standard 864

Description

IDNet Relay IAMs allow fire alarm control panels to control a remotely located Form “C” contact using IDNet addressable communications for both data and module power. Typical applications would be for switching local power for control functions such as elevator capture, or control of HVAC components, pressurization fans, dampers, etc. Relay status is also communicated requiring only one device address.

Product Selection

Model Description 4090-9002 Relay IAM

Optional Adapter and Trim Plates Model Description

4090-9813 Adapter plate to fit 4 11⁄16” (119 mm) square electrical box

4090-9801 For semi-flush mounted box

Trim Plate, galvanized steel, with LED viewing window; includes mounting screws 4090-9802 For surface

mounted box * This product has been approved by the California State Fire Marshal (CSFM) pursuant to

Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

4090-9002 IDNet Relay IAM Package (shown approximately 1/2 size)

Specifications

Communications IDNet communications, 1 address per device

Relay IAM Power Supplied by IDNet communications

Contact Ratings* (not rated for incandescent switching)

Type Form C, SPDT

Power-Limited 2 A @ 24 VDC, resistive from listed

fire alarm supply 1 A @ 24 VDC, inductive

Nonpower-Limited 0.5 A @ 120 VAC, resistive

* Provide circuit fusing and transient suppression as required per application. DC inductive loads can typically be diode suppressed; 120 VAC loads may require RC networks or varistors, depending on device type. Refer to the installation instructions for additional information.

Wire Connections Screw terminals for in/out wiring, 18 to 14 AWG wire (0.82 to 2.08 mm2)

IDNet Communications Wiring Reference

Up to 2500 ft (762 m) from control panel

Up to 10,000 ft (3048 m) total wiring distance (including T-Taps)

Compatible with Simplex 2081-9044 Overvoltage Protectors

Dimensions 4 ⅛” H x 4 ⅛” W x 1 ⅜” D (105 mm x 105 mm x 35 mm)

Housing Material Black thermoplastic

Mounting Plate Sheet metal, galvanized

Temperature Range

32° to 120° F (0° to 49° C), intended for indoor operation

Humidity Range Up to 93% RH at 100° F (38° C)

Installation Instructions 574-184

Multi-Application Peripherals UL, ULC, CSFM Listed; FM Approved; IDNet Communicating Devices MEA (NYC) Acceptance* Model 4090-9002 Relay IAM

S4090-0002-9 11/2013

dthurston
Line
Page 86: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4090-0002-9 11/2013

www.simplex-fire.com © 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

4" (102 mm) square box, 2-1/8" (54 mm) minimum depth, RACO 232 or equal (supplied by others)

Double gang blank cover plate and mounting screws, for use when LED is not required to be externally viewed (supplied by others)

4090-9002 Relay IAM

Address setting under resealable label

Optional Trim Plates for Visible LED

4090-9802, Trim plate forsurface mounted box

4090-9801, Trim plate forsemi-flush mounted box

Mounting Reference, Double Gang Blank Cover Plate

4-9/16"(116 mm)

4-9/16" (116 mm)

4-5/16"(109 mm)

Light pipe for LED viewing

4-5/16" (109 mm)

Relay IAM Mounting Information

Page 87: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Individually addressed and controlled multi-candela TrueAlert ES V/O (visible only) notification appliances provide: • Multi-candela xenon strobe with synchronized 1 Hz flash

rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, 110, 135, or 185 cd

• Advanced addressable notification controlled by IDNAC SLCs providing regulated 29 VDC allowing strobes to operate with lower current even under battery backup

• Wiring supervision to each appliance allowing “T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)

• Self-Test Mode allows an on-board sensor to detect the strobe output and then report its status to the control panel

• TrueAlert Device Reports at the control panel detailing appliance point ID, custom label, type, and candela setting (see sample on page 3)

• Magnet Test diagnostics to assist checkout and testing of appliances and wiring and Electrical test point access without removing cover

• Compatibility with ADA requirements; (refer to important installation information on page 3)

• Compatibility with legacy TrueAlert addressable systems for upgrade and replacement (see page 4)

• Listed to UL Standard 1971 and ULC Standard S526 LED Indicator and Magnet Test feature: • Appliance LED can be selected to display each polling

cycle to indicate appliance supervision • When the controller is in diagnostic mode, the Magnet

Test pulses the LED to indicate appliance address and can be set to also briefly flash the strobe

Mechanical design features include: • Rugged, high impact, flame retardant thermoplastic

housing in red with white letters or white with red letters, with clear lens, available with FIRE, ALERT, FEU, FEU/FIRE, or blank lettering

• Separate covers are available to change appliance type on-site or for replacement; covers can be easily removed without disturbing the connected housing and avoiding trouble conditions

• A separate mounting plate allows wiring to be completed before appliance is mounted; use with single gang, double gang, or 4-inch square box, flush or surface mount

• In/out wiring terminals for 18 AWG to 12 AWG • Optional mounting adapters are available to cover

surface mounted electrical boxes and to adapt to Simplex 2975-9145 boxes

• Optional red wire guards (see page 2 for details)

* These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0373 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

TrueAlert ES Addressable Strobes are Available in Red

with White Lettering and White with Red Lettering

Description

TrueAlert ES addressable strobes are individually addressed visible notification appliances that receive power, supervision, and control signals from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 4.)

Strobe Application Reference

Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).

TrueAlert ES Operation Advantage

TrueAlert ES addressable appliances on IDNAC SLCs provide separate visible (and audible) notification using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections.

Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VDC source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.

TrueAlert Addressable Notification Appliances UL, ULC, CSFM Listed; Visible Notification Appliances, Wall Mount FM Approved* Multi-Candela Strobes, Model Series 49VO

S49VO-0001-5 6/2015

Page 88: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TrueAlert ES Operation Advantage (Cont’d)

Reducing Installation and Testing Time. With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of Self-Test and Magnet Test features improves installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.

TrueAlert ES Diagnostics

Test Features. When IDNAC SLCs are in diagnostic mode, Self-Test and Magnet Test features provide individual appliance testing. With the Self-Test feature, appliance operation can be confirmed without leaving the control panel. Additionally, each appliance’s LED can be selected to pulse when it receives a supervision poll during normal operation.

Self-Test Details. Selecting Self-Test Mode from the control panel allows on-board sensors, depending on the device type, to detect its own strobe and/or horn output and then report their status to the control panel.

TrueAlert ES Diagnostics (Continued)

Self-Test Details (Continued). Operation is by selected VNAC appliance groups and is either automatic (all briefly simultaneously activated) or individually activated by applying a magnet. (Refer to control panel data sheet for more Self-Test information, see list on page 4.)

Silent Appliance Magnet Test. In this test mode, in response to application of a magnet, the appliance LED pulses sequentially to conveniently indicate the appliance’s address.

Operational Appliance Magnet Test. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to indicate proper operation.

TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert ES appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.

TrueAlert Addressable Wiring Isolator

Isolator Model 4905-9929 is available for remote mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. (See data sheet S4905-0001.)

TrueAlert ES Wall Mount Addressable Strobes TrueAlert ES addressable VO (strobe) appliances include cover and matching mounting plate except as noted; Dimensions with Cover = 5 ⅛” H x 5” W x 2 ⅝” D (130 mm x 127 mm x 67 mm)

Model* Cover Color Wording Lens Color Model* Cover Color Wording Lens Color 49VO-WRF(-BA) Red

FIRE Clear

49VO-WRQ Red FEU

Clear 49VO-WWF(-BA) White 49VO-WWQ White 49VO-WRA(-BA) Red

ALERT 49VO-WRS(-BA) Red

Blank 49VO-WWA(-BA) White 49VO-WWS(-BA) White 49VO-APPLW Select cover and mounting plate separately

Separate Mounting Plate Model Color Note

49MP-AVVOWR Red Mounting Plate is required when ordering model 49VO-APPLW

49MP-AVVOWW White

Separate Covers (Required when ordering model 49VO-APPLW) Model* Color Wording Model* Color Wording

49VOC-WRFIRE Red FIRE

49VOC-WRFEU Red FEU

49VOC-WWFIRE White 49VOC-WWFEU White 49VOC-WRALT Red

ALERT 49VOC-WRBLNG Red

FEU/FIRE 49VOC-WWALT White 49VOC-WWBLNG White 49VOC-WRS Red Blank 49VOC-WWS White Blank * Note: (-BA) indicates model is available either with or without the -BA suffix. Model numbers ending in -BA, APPLW models, and separate mounting plates are assembled in the USA.

Mounting Adapters and Wire Guard Model Color Description Dimensions

4905-9937 Red Surface Mount Adapter Skirt 5 ⅜” H x 5 ¼” W x 1 ⅝” D (136 mm x 133 mm x 41 mm)

Total depth with strobe = 4 ⅜” (111 mm) 4905-9940 White

4905-9931 Red Adapter Plate for mounting to Simplex 2975-9145 Box (typically for retrofit, mount vertical or horizontal)

8 5⁄16” x 5 ¾” x 0.060” Thick (211 mm x 146 mm x 1.5 mm)

2975-9145 Red Mounting Box, requires 4905-9931 Adapter Plate 7 ⅞" x 5 ⅛" x 2 ¾" D (200 mm x 130 mm x 70 mm)

4905-9961 Red wire guard with mounting plate, compatible with semi-flush or surface mount boxes

6 1⁄16” H x 6 1⁄16” W x 3 ⅛” D (154 mm x 154 mm x 79 mm)

2 S49VO-0001-5 6/2015

Product Selection

dthurston
Line
Page 89: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

3 S49VO-0001-5 6/2015

Removable cover (when installed, use flat bladed screwdriver to release latch on left side)

Mounting is compatible with single gang, double gang, and 4" (102 mm) square boxes,

1-1/2" (38 mm) deep, supplied separately

Mounting Holes:Single gang (2)Double gang (4)4" square (4)

Magnetic test location (bottom of housing)

LED indicator location

Transparent housing assembly

Mounting plate

Electrical test point access holes(on bottom)

Wiring access hole

Wiring terminals and connection clips

Strobe intensity viewing slot on

side of appliance (not to scale)

Intensity selection plug, accessible from rear of housing; factory setting is FACP, controlled by panel

110753015

FACP135185

Address setting DIP switch, accessible

from rear of housing

NFPA 72 requires that the entire lens be not less than 80" and not greater than 96" above the finished floor (confirm with your local codes)

Electrical box outline

80" (2.03 m)minimum

IMPORTANT! WALL MOUNT INSTALLATION HEIGHT REFERENCE

Bottom of lens is either even with, or slightly above bottom of compatible boxes

TrueAlert ES Addressable Strobe

2975-9145 Box

4905-9931 Adapter Plate

4905-9931 Adapter Plate

4905-9961 Optional Wire Guard (shown here for reference only, can be used on other mounting options)

Optional 4905-9961

Wire Guard

4" square box profile,1-1/2" (38 mm) deep

(Surface mount conduit and box shown for reference)

Optional surface mount adapter skirt,1-1/2" deep: 4905-9937, Red;

4905-9940, White (conduit knockouts are provided on all four sides)

TrueAlert ES Addressable

Strobe

Surface Mount Side View Reference2975-9145 Box Mounting Reference

Service Port Page 1 REPORT 5 : TrueAlert Device Report 12:34:56am TUE 27-Jan-15 POINT ID

CUSTOM LABEL

DEVICE TYPE

CANDELA

T14-1-1 Location Label . . . up to 40 characters V/O 15 T14-1-2 Break Room 5 A/V 110 T14-1-3 Boiler Room A/V 75 T14-1-4 Elec. Room 7 A/V 135

Adapter Plate and Surface Mount Installation Reference

Installation Reference

TrueAlert Device Reports Reference

Page 90: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Electrical Ratings Typical Operating Voltage Range 23 VDC to 31 VDC, Special Application (see below for 17 VDC rating)

Supervisory Requirements 1 unit load (= 0.8 mA control panel current) IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads

Candela Setting 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd

23 VDC RMS Current Ratings, for typical design of IDNAC Addressable SLCs (6 VDC drop)

47 mA 57 mA 100 mA 132 mA 160 mA 208 mA

General Specifications

Temperature Range 32° to 122° F (0° to 50° C)

Humidity Range 10% to 93%, non-condensing @ 104° F (40° C)

IDNAC SLC Wiring Specifications (refer to control panel installation instructions for more information)

UTP, unshielded twisted pair recommended Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft (3048 m) Maximum wire length to any appliance = 4000 ft (1219 m)

Connections Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring

Installation Instructions 579-1031

Notes: Refer to compatibility table above for fire alarm control panel and power supply operation type.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S49VO-0001-5 6/2015

www.simplex-fire.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Compatible Controller Data Sheet Reference Controller Output Available Strobe

Intensity Appliance Voltage

Minimum 4100ES or 4100U with TrueAlert Power Supply S4100-0031

TrueAlert Addressable SLC 15, 30, 75, and 110 cd 17 VDC 4009 TPS, Remote

TrueAlert Power Supply S4100-0037

TrueAlert Addressable Controller (4009T) S4009-0003

Electrical Ratings Reference for Retrofit Applications

Voltage Range 17 VDC to 31 VDC, Special Application

Candela Setting 15 cd 30 cd 75 cd 110 cd

17 VDC RMS Current Ratings, use when connected to TrueAlert Addressable SLCs per above

62 mA 75 mA 133 mA 178 mA

Compatible Controllers Data Sheet Reference Controller Output IDNAC SLC Output

Voltage Appliance Voltage Design Reference

4100ES with EPS+ or EPS Power Supply S4100-0100

IDNAC SLC 29 VDC (regulated)

23 VDC (with 6 VDC drop)

4009 IDNAC Repeater S4009-0004 4007ES with IDNAC Notification S4007-0002 4010ES with ESS Enhanced System Supply S4010-0011

TrueAlert ES Strobe Specifications

TrueAlert ES Strobe LEGACY Compatibility Reference

IDNAC SLC Controller Compatibility Reference

Page 91: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Features

Individually addressed and controlled multi-candela TrueAlert ES A/V (audible/visible) notification appliances provide: • Multi-candela xenon strobe with synchronized 1 Hz flash

rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, 110, 135, or 185 cd

• Advanced addressable notification controlled by IDNAC SLCs providing regulated 29 VDC allowing strobes to operate with lower current even under battery backup

• Wiring supervision to each appliance allowing “T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring)

• Self-Test Mode allows on-board sensors to detect the strobe and horn output and then report their status to the control panel

• TrueAlert Device Reports at the control panel detailing appliance point ID, custom label, type, and candela setting (see sample on page 3)

• Magnet Test diagnostics to assist checkout and testing of appliances and wiring

• Electrical test point access without removing cover • Compatibility with ADA requirements; (refer to

important installation information on page 3) • Compatibility with legacy TrueAlert addressable

systems for upgrade and replacement (see page 4) • Strobe operation is listed to UL Standard 1971 and ULC

Standard S526; Horn operation is listed to UL Standard 464 and ULC Standard S525

LED Indicator and Magnet Test feature: • Appliance LED can be selected to display each polling

cycle to indicate appliance supervision • When the controller is in diagnostic mode, the Magnet

Test pulses the LED to indicate appliance address and can be set to also briefly flash the strobe and sound the horn

Mechanical design features include: • Rugged, high impact, flame retardant thermoplastic

housing in red with white letters or white with red letters, with clear lens, available with FIRE, FEU, ALERT, FEU/FIRE, or blank lettering

• Separate covers are available to change application type on-site or for replacement

• A separate mounting plate allows wiring to be completed before appliance is mounted; use with single gang, double gang, or 4-inch square box, flush or surface mount

• Covers can be easily removed without disturbing the connected housing and avoiding trouble conditions

• In/out wiring terminals for 18 AWG to 12 AWG • Optional mounting adapters are available to cover

surface mounted electrical boxes and to adapt to Simplex 2975-9145 boxes

• Optional red wire guards (see page 2 for details)

TrueAlert ES Addressable A/Vs are Available in Red with

White Lettering and White with Red Lettering Features (Continued)

Audible notification appliance (horn): • Harmonically rich output sound for either coded or

steady operation • Horns sound as Temporal Code 3, March Time pattern,

continuous; or Temporal Code 4, controlled separately from visible appliances on the same two-wire circuit

• Selectable March Time rates of 20, 60, or 120 beats per minute

• Output is “high” or “low” (~5 dBA difference) selectable at the appliance or from the controller with FACP mode selected at the appliance

Description

TrueAlert ES addressable A/Vs are individually addressed audible/visible notification appliances that receive power, supervision, and control signals from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). (See compatibility list on page 4.)

Strobe Application Reference

Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).

* These products have been approved by the California State Fire Marshal (CSFM)

pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0373 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

TrueAlert Addressable Notification Appliances UL, ULC, CSFM Listed; Audible/Visible Notification Appliances, Wall Mount FM Approved* Multi-Candela Horn/Strobe, Model Series 49AV

S49AV-0001-5 6/2015

Page 92: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TrueAlert ES Operation Advantage

TrueAlert ES addressable appliances on IDNAC SLCs provide separate visible and audible notification using a single two-wire circuit that also confirms connection to the individual notification appliance’s electronic circuit. This operation increases circuit supervision integrity by providing supervision that extends beyond the appliance wiring connections.

Reduced current allows efficient IDNAC SLC operation. With IDNAC SLCs, a constant 29 VDC source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby. Efficiencies include wiring distances up to 2 to 3 times farther than with conventional notification, or support for more appliances per IDNAC SLC, or use of smaller gauge wiring, or combinations of these benefits, all providing installation and maintenance savings with high assurance that appliances that operate during normal system testing will operate during worst case alarm conditions.

Reducing Installation and Testing Time. With separate controls on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T” tapped, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency. Use of Self-Test and Magnet Test features improve installation efficiency. TrueAlert device reports conveniently identify information about each connected appliance.

TrueAlert ES Diagnostics

Test Features. When IDNAC SLCs are in diagnostic mode, Self-Test and Magnet Test features provide individual appliance testing. With the Self-Test feature, appliance operation can be confirmed without leaving the control panel. Additionally, each appliance’s LED can be selected to pulse when it receives a supervision poll during normal operation. Self-Test Details. Selecting Self-Test Mode from the control panel allows on-board sensors, depending on the device type, to detect its own strobe and/or horn output and then report their status to the control panel. Operation is by selected VNAC appliance groups and is either automatic (all briefly simultaneously activated) or individually activated by applying a magnet. (Refer to control panel data sheet for more Self-Test information, see list on page 4.) Silent Appliance Magnet Test. In this test mode, in response to application of a magnet, the appliance LED pulses sequentially to conveniently indicate the appliance’s address. Operational Appliance Magnet Test. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash and the horn will briefly sound to indicate proper operation. TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert ES appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex representative for additional information.

TrueAlert Addressable Wiring Isolator

Isolator Model 4905-9929 is available for remote mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring. (See data sheet S4905-0001.)

TrueAlert ES Wall Mount Addressable Audible/Visible Appliances TrueAlert ES addressable A/V appliances include cover and matching mounting plate except as noted; Dimensions with Cover = 5 ⅛” H x 5” W x 2 ⅝” D (130 mm x 127 mm x 67 mm)

Model* Cover Color Wording Lens Color Model* Cover Color Wording Lens Color 49AV-WRF(-BA) Red

FIRE Clear

49AV-WRS(-BA) Red Blank Clear 49AV-WWF(-BA) White 49AV-WWS-BA White

49AV-WRQ Red FEU 49AV-APPLW Select cover and mounting plate separately

Separate Mounting Plate Model Color Model Color Note

49MP-AVVOWR Red 49MP-AVVOWW White Mounting Plate is required when ordering model 49AV-APPLW

Separate Covers (Required when ordering model 49AV-APPLW) Model* Color Wording Model* Color Wording

49AVC-WRFIRE Red FIRE 49AVC-WRFEU Red FEU 49AVC-WWFIRE White 49AVC-WWFEU White 49AVC-WRALT Red

ALERT 49AVC-WRBLNG Red

FEU/FIRE 49AVC-WWALT White 49AVC-WWBLNG White 49AVC-WRS Red Blank 49AVC-WWS White Blank * Note: (-BA) indicates model is available either with or without the -BA suffix. Model numbers ending in -BA, APPLW models, and separate mounting plates are assembled in the USA.

Mounting Adapters and Wire Guard Model Color Description Dimensions

4905-9937 Red Surface Mount Adapter Skirt 5 ⅜” H x 5 ¼” W x 1 ⅝” D (136 mm x 133 mm x 41 mm) Total depth with strobe = 4 ⅜” (111 mm) 4905-9940 White

4905-9931 Red Adapter Plate for mounting to Simplex 2975-9145 Box (typically for retrofit, mount vertical or horizontal) 8 5⁄16” x 5 ¾” x 0.060” Thick (211 mm x 146 mm x 1.5 mm)

2975-9145 Red Mounting Box, requires 4905-9931 Adapter Plate 7 ⅞" x 5 ⅛" x 2 ¾" D (200 mm x 130 mm x 70 mm)

4905-9961 Red wire guard with mounting plate, compatible with semi-flush or surface mount boxes 6 1⁄16” H x 6 1⁄16” W x 3 ⅛” D (154 mm x 154 mm x 79 mm)

2 S49AV-0001-5 6/2015

Product Selection

dthurston
Line
Page 93: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

3 S49AV-0001-5 6/2015

NFPA 72 requires that the entire lens be not less than 80" and not greater than 96" above the finished floor (confirm with your local codes)

Removable cover (when installed, use flat bladed screwdriver to release latch on left side)

Mounting is compatible with single gang, double gang, and 4" (102 mm) square boxes,

1-1/2" (38 mm) deep, supplied separately

Mounting Holes:Single gang (2)Double gang (4)4" square (4)

Magnetic test location(bottom of housing)

LED indicator location

Transparent housing assembly

Mounting plate

Electrical test point access holes(on bottom)

Wiring access hole

Wiring terminals and connection clips Electrical

box outline

80" (2.03 m)minimum

IMPORTANT! WALL MOUNT INSTALLATION HEIGHT REFERENCE

Bottom of lens is either even with, or slightly above bottom of compatible boxes

Strobe intensity viewing slot on

side of appliance (not to scale)

Intensity selection plug, accessible from rear of housing; factory setting is FACP, controlled by panel

110753015

FACP135185

Address setting DIP switch, accessible

from rear of housing

A/V configuration switch

TrueAlert ES Addressable A/V

2975-9145 Box

4905-9931 Adapter Plate

4905-9931 Adapter Plate

4905-9961 Optional Wire Guard (shown here for reference only, can be used on other mounting options)

Optional 4905-9961

Wire Guard

4" square box profile,1-1/2" (38 mm) deep

(Surface mount conduit and box shown for reference)

Optional surface mount adapter skirt,1-1/2" deep: 4905-9937, Red;

4905-9940, White (conduit knockouts are provided on all four sides)

TrueAlert ES Addressable A/V

Surface Mount Side View Reference2975-9145 Box Mounting Reference

Service Port Page 1 REPORT 5 : TrueAlert Device Report 12:34:56am TUE 27-Jan-15 POINT ID

CUSTOM LABEL

DEVICE TYPE

CANDELA

T14-1-1 Location Label . . . up to 40 characters V/O 15 T14-1-2 Break Room 5 A/V 110 T14-1-3 Boiler Room A/V 75 T14-1-4 Elec. Room 7 A/V 135

Adapter Plate and Surface Mount Installation Reference

Installation Reference

TrueAlert Device Reports Reference

Page 94: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S49AV-0001-5 6/2015

www.simplex-fire.com © 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Compatible Controller Data Sheet Reference

Controller Output

Available Strobe Intensity

Available Horn Control

Appliance Voltage Minimum

4100ES or 4100U with TrueAlert Power Supply S4100-0031

TrueAlert Addressable

SLC

15, 30, 75, and 110 cd

Continuous, Temporal Code 3, and March

Time of 60 or 120 bpm 17 VDC 4009 TPS, Remote

TrueAlert Power Supply S4100-0037

TrueAlert Addressable Controller (4009T) S4009-0003

Electrical Ratings Differences for Legacy Applications (refer to above specifications for other ratings) Voltage Range 17 VDC to 31 VDC, Special Application

Sound Output Ratings @ 10 ft (3 m) @ 17 VDC

Sound Type/Setting Steady/High Steady/Low Coded/High Coded/Low Reverberant Chamber, UL 464 Test 87.8 dBA 81.6 dBA 83.4 dBA 77.0 dBA

Anechoic Chamber, ULC 525 Test 91.7 dBA 85.4 dBA 91.7 dBA 85.4 dBA Candela Setting 15 cd 30 cd 75 cd 110 cd

17 VDC RMS Current Ratings, with horn on continuous at high setting, use when connected to TrueAlert Addressable SLCs per above

74 mA 85 mA 140 mA 185 mA

Compatible Controllers Data Sheet Reference Controller Output IDNAC SLC Output

Voltage Appliance Voltage Design Reference

4100ES with EPS+ or EPS Power Supply S4100-0100

IDNAC SLC 29 VDC (regulated)

23 VDC (with 6 VDC drop)

4009 IDNAC Repeater S4009-0004 4007ES with IDNAC Notification S4007-0002 4010ES with ESS Enhanced System Supply S4010-0011

Electrical Ratings

Typical Operating Voltage Range 23 VDC to 31 VDC, Special Application (see below for 17 VDC rating) Supervisory Requirements 1 unit load (= 0.8 mA control panel current)

IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads

Sound Output Ratings @ 10 ft (3 m) @ 23 VDC (with IDNAC SLCs) Sound Type/Setting Steady/High Steady/Low Coded/High Coded/Low

Reverberant Chamber, UL 464 Test 90.1 dBA 83.6 dBA 85.7 dBA 80.1 dBA Anechoic Chamber, ULC 525 Test 94.1 dBA 88.1 dBA 94.1 dBA 88.1 dBA

Sound Output Dispersion per ULC S541 Anechoic Testing Horizontal -3 dBA @ 50°; -6 dBA @ 63°; left and right from center

Vertical -3 dBA @ 20° above, 48° below; -6 dBA @ 65° above, 60° below; ref. to center Candela Setting 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd

23 VDC RMS Current Ratings, with horn on continuous at high setting 59 mA 67 mA 107 mA 139 mA 166 mA 215 mA

General Specifications Sound Characteristics 2400 to 3700 Hz sweep, modulated at 120 Hz rate

Connections

Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per terminal for in/out wiring

Temperature Range 32° to 122° F (0° to 50° C) Humidity Range 10% to 93%, non-condensing @ 104° F (40° C)

Installation Instructions 579-1031

IDNAC SLC Wiring Specifications (refer to control panel installation instructions for more information)

UTP, unshielded twisted pair recommended Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft (3048 m) Maximum wire length to any appliance = 4000 ft (1219 m)

Note: UL 464 test coded values are typical of the output measured with a Temporal or a March Time pattern and with a sound level meter reading on a “fast” setting. Under the same test conditions, coded horn output “peak” sound level readings are typically 4 dBA higher. Anechoic horn output ratings are typically more representative of actual installed sound output.

TrueAlert ES A/V Specifications

TrueAlert ES A/V LEGACY Compatibility Reference

IDNAC SLC Controller Compatibility Reference

Page 95: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

8/16 Made in the USA3 Year Warranty

N56 W24720 N. Corporate Circle • Sussex, WI 53089800-451-1460 • 262-246-4828 (fax) • www.area-of-refuge.com

SmartRescue Base Station2500-210PSS

Stainless Steel Face Plate: 14.66” H x 13.68” W (2.67” D with handset)Steel Back Box: 12.57” H x 11.6” W x 1.69” D Style: Flush mount, coil cord

Features:• Use with up to 10 Call Boxes on the same telephone line• Run twisted and shielded 4 wire set from each Call Box to Base Station unit and one standard phone line to outside world• Can be installed on a VoIP phone system when used with our 2100-VoIP Interface Device• Can be used as an Intercom System when used with our 2100-LINESIM Line Simulator• Easy to use push buttons• Passively monitor communications between Call Boxes and outside world via the LEDs: 1. Solid lit LED indicates there is an emergency call in progress 2. Slow blinking LED indicates there is a call on hold• Audible alert when Call Box initiates call, silenced when call is joined from Base Station• Includes relay contact that trips if any Call Box has been activated• Includes connections for (2) Sub-Stations• The Base Station is able to: 1. Call into all or individual Call Boxes as needed 2. Join existing conversations between Call Boxes and outside world 3. Hang up and original conversation will continue 4. Terminate outside world so it is only talking to the Call Boxes or terminate the call with all parties entirely• Volume control handset meets ADA requirements• Designed for either 120vac or 24vdc power• Built-in battery backup recharges from 120vac or 24vdc power (allows for a minimum of 4 hours talk time upon loss of power)• Telephone Line Voltage: 24v-48v• Meets all IBC, ADAAG, and NFPA Code requirements• 3 year warranty

dthurston
Line
Page 96: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

Area of RefugePower Supply

• Model: 2500-PWR24• Size: 9.275" H x 8.125" W x 3.75" D• Shipping Weight: 11 lbs. • 24vdc, 9 Outputs• Install up to (5) phones per output • 4 Amp (100VA) Supply Current • Integral Surge Protection • Underwriters Laboratory (UL) recognized • Individual LED power indication

N56 W24720 N. Corporate Circle • Sussex, WI 53089800-451-1460 • 262-246-4828 (fax) • www.area-of-refuge.com2/16 Made in the USA

3 Year Warranty

dthurston
Line
Page 97: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

5/16 Made in the USA3 Year Warranty

N56 W24720 N. Corporate Circle • Sussex, WI 53089800-451-1460 • 262-246-4828 (fax) • www.area-of-refuge.com

2100-958NSRCall Box

Face Plate Size: 9-1/2” H x 7-1/2” WBack Box Size: 8” H x 6” W x 3” DStyle: Brushed Stainless Steel, Flush MountOptions: Strobe Interface & Relay, Mushroom Push Button

Features:• Meets all IBC, ADAAG, and NFPA Code requirements• Requires analog telephone line (POTS, PBX, or central office line)• Power Requirements: 24vdc from model 2500-PWR24 • Built-in battery backup recharges from 24vdc power (allows for a minimum of 4 hours of talk time upon power loss)• Built-in 10 phone consolidator feature allows you to install 10 Call Boxes and 1 Base Station on a single telephone line • Programmable with up to 5 emergency numbers • On-site programming• Remote or on-site diagnostic test• Recordable location message (18 seconds) • Phone checks every 24 hours for an active phone line, if one is not detected, phone will provide a relay trip • Compatible with SmartRescue Base Station or Command Center for in-building rescue coordination• Automatic dialer (31 digit programmable memory)• Automatic answer feature with audible ring• Touch Tone operation only (Touch Tone is an AT&T registered trademark)• 3 year warranty

dthurston
Line
Page 98: PANEL DESIGNATOR...4098-9714 head 29 m 4k simplex 4g single action manual pull station 4099-9004 1 m 1e simplex addressable multi-candela horn/strobe, white, 4a fire, clear lens 49av-wwf

3/16 Made in the USA3 Year Warranty

N56 W24720 N. Corporate Circle • Sussex, WI 53089800-451-1460 • 262-246-4828 (fax) • www.area-of-refuge.com

• IBC, NFPA, and ADAAG Code compliant• Raised letter and braille• Peel and stick mounting for easy installation• Sign should be mounted at 60" above the floor to center line of the sign

Features:

Area of Rescue Assistance Sign7080

6”

9”

dthurston
Line