  • PANEL CHECK

    CUSTOMER : PT. TIRTA INVESTAMA SUBANGPROJECT : AQUA - SUBANGPANEL NAME : PANEL HEATERCHECKER : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 ACB 1000 A 3P 2 MCCB 400 A 3P 3 MCCB 400A 3P 4 MCCB 400A 3P 5 MCCB 600A 3P 6789

    101112131415161718192021222324252627282930

  • PANEL CHECK

    REMARK

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOINGTIDAK ADA LAMPU PENERANGAN DI DALAM PANELTATA LETAK BREAKER DAN PANEL TIDAK TERTATA RAPI

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL AC1Checker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 MCCB 630A 3P 2 MCCB 100A 3P 3 MCCB 60A 3P 4 MCCB 50A 3P 5 MCCB 250A 3P 6 MCCB 125A 3P 789

    101112131415161718192021222324252627282930

  • PANEL CHECK

    REMARK

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOINGTIDAK ADA LAMPU PENERANGAN DI DALAM PANEL

    KABEL INCOMING PHASA T PADA BREAKER 630A OVERHEAT MENCAPAI 66 DERAJAT CELCIUS

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL HUSKYChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 ACB 1250 A 3P 2 ACB 1000 A 3P 3 MCCB 400A 3P 4 MCCB 400A 3P 5 MCCB 63A 3P 6 MCCB 63A 3P 7 MCCB 40A 3P 8 MCCB 40A 3P 9 VOLTMETER

    10 AMPEREMETER 11 PILOT LIGHT R,S,T 12131415161718192021222324252627282930

  • PANEL CHECK

    REMARK

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOINGTIDAK ADA LAMPU PENERANGAN DI DALAM PANELTATA LETAK BREAKER DAN PANEL TIDAK TERTATA RAPI

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : SDP LOW COMPRESSORChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 PM 5500 2 FUSE 16A (3X) 3 VOLT METER 4 AMPERE METER 5 PILOT LIGHT R,S,T 6 MCCB 630A 3P 7 MCCB 25A 3P 8 MCCB 100A 3P 9 MCCB 630A 3P

    10 MCCB 250A 3P 11 MCB 10A 3P 12 MCB 10A 3P 131415161718192021222324252627282930

  • PANEL CHECK

    REMARK

    COVER PANEL TIDAK SAFETY, JARI BISA MASUK KE DALAM PANEL.TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOINGTIDAK ADA LAMPU PENERANGAN DI DALAM PANELPANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : SDP SPS 600 mlChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 SEL 1

    ACB 4000A 4P PM 500 PILOT LIGHT R-S-T VOLTMETER (3X) AMPEREMETER (3X)

    2 SEL 2MCCB 400A 3P MCCB 400A 3P MCCB 630A A 3P MCCB 160 A 3P MCCB 80 A 3P MCCB 100A 3P MCCB 80 A 3P KWH METER 5A FUSE 32A (3X) PM 500 PM 5500 PM 500

    3 SEL 3 ACB 1250 A 3P MCCB 400A 3P MCCB 80 A 3P MCCB 80 A 3P MCCB 63 A 3P MCCB 63 A 3P MCCB 40 A 3P MCCB 40 A 3P MCCB 200 A 3P KWH METER 5A FUSE 32A (3X) TIMER THEBEN PM 5500 PM 800 PM 500 PM 5500

  • PM 500 PM 800

    4 SEL 4ACB 1250 A 3P MCCB 630A 3P MCCB 400A 3P KWH METER 5A FUSE 32A (3X) TIMER THEBEN PM 500 PM 500 PM 500

    5 SEL 5MCCB 250A 3P MCB 25A 3P MCB 25A 3P MCB 25A 3P MCB 25A 3P MCB 25A 3P

  • PANEL CHECK

    REMARK

    VOLTMETER TIDAK BERFUNGSIPILOT R,S,T TIDAK BERFUNGSIAMPEREMETER TIDAK BERFUNGSI

    COVER PANEL TIDAK SAFETY, JARI BISA MASUK KE DALAM PANEL.TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOINGTIDAK ADA LAMPU PENERANGAN DI DALAM PANELPM500 SEL 1,PM5500 SEL 3, PM500 SEL 4 TIDAK BERFUNGSIPANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL GENSETChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 ACB 2500A 4P 2 ACB 2500A 4P 3 ACB 2500A 4P 4 ACB 2500A 4P 5 DEPSEA GENSET 1 6 DEPSEA GENSET 2 789

    101112131415161718192021222324252627282930

  • PANEL CHECK

    REMARK

    COVER PANEL (OK) JARI TIDAK BISA MASUK KE DALAM PANEL DAN SAFETYPANEL AMAN DARI MASUKNYA AIR. IP3X (OK)TIDAK ADA LAMPU PENERANGAN DI DALAM PANEL

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL LVMDP HODChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 SEL 1

    ACB 2500A 4P MCCB 800A 3P

    2 SEL 2 ACB 2500A 4P MCCB 800A 3P MCCB 160A 3P

    3 SEL 3 MCCB 32A 3P MCCB 250A 3P MCCB 160A 3P MCCB 160A 3P MCCB 160A 3P MCCB 200A 3P MCCB 80A 3P MCCB 63A 3P MCCB 100A 3P MCCB 80A 3P MCCB 80A 3P MCCB 80A 3P MCCB 40A 3P MCCB 200A 3P ACB 1000A 3P MCCB 250A 3P

    4 SEL 4 MCCB 250A 3P MCCB 630A 3P PILOT LIGHT RED (12x) PILOT LIGHT GREEN (12x) PUSH BUTTON RED(12x) PUSH BUTTON GREEN (12x) POWER FACTOR REGULATOR CONTACTOR 125A (12x) MCCB 125A (12x) NH FUSE (36x) FUSE HOLDER (36x)

  • CAPACITOR 25 kVAR (24x) PILOT LIGHT R,S,T (CAPACITOR) SEL 5

    5 MCCB 800A 3P

  • PANEL CHECK

    REMARK

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)

    TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOING BREAKER

    TIDAK ADA LAMPU PENERANGAN DI DALAM PANEL

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL LINE DChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 MCCB 800 A 3P 2 MCCB 63 A 3P 3 MCCB 250 A 3P 4 MCCB 250 A 3P 5 MCCB 250 A 3P 6 MCCB 125 A 3P 7 MCB 25 A 3P 8 MCB 25 A 3P 9 MCB 25 A 3P

    10 MCB 40 A 3P 11 MCB 40 A 3P 12131415161718192021222324252627282930

  • PANEL CHECK

    REMARK

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOING BREAKERTIDAK ADA LAMPU PENERANGAN DI DALAM PANELTATA LETAK BREAKER DAN PANEL TIDAK TERTATA RAPI

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL COMPRESSOR 5 GALONChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 MCCB 200A 3P 2 MCCB 100A 3P 3 MCCB 100A 3P 4 MCCB 100A 3P 5 MCCB 100A 3P 6 MCCB 80 A 3P 7 MCCB 80 A 3P 8 MCCB 63 A 3P 9 MCCB 63 A 3P

    10 MCCB 63 A 3P 11 MCB 40 A 3P 12 MCB 20 A 3P 13 MCB 20 A 3P 14 MCB 20 A 3P 15 MCB 20 A 3P 16 MCB 10 A 3P 17 PM 700 18 PM 200 19 CT 100A (3X) 20 CT 75A (3X) 21 FUSE 15A (8X) 22 PILOT LIGHT R,S,T 2324252627282930

  • PANEL CHECK

    REMARK

    KABEL TIDAK RAPI

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOING BREAKERTIDAK ADA LAMPU PENERANGAN DI DALAM PANELTATA LETAK BREAKER DAN PANEL TIDAK TERTATA RAPIPM 500 DAN CT 75A (MATI) UNTUK OUTGOING CHILLER LINE A TIDAK BERFUNGSI.

    PANEL TYPE OUTDOOR, AMAN DARI MASUKNYA AIR. IP3X (OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL COMPRESSOR 5 GALONChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 ACB 800A 3P 2 MCCB 160A 3P 3 MCCB 80 A 3P 4 MCCB 100 A 3P 5 MCCB 100 A 3P 6 MCCB 6 A LP 7 MCCB 6 A LP 8 MCCB 6 A LP 9 MCCB 6 A LP

    10 MCCB 20 A LP 11 MCCB 16 A LP 12 MCCB 10 A LP 13 MCCB 16 A3P 14 MCCB 16 A 3P 15 MCCB 10 A LP 16 TIMER 17 RELAY CONTACTOR (2x) 18 PM 200 19 SELECTOR SWITCH M-O-A 20 PILOT LIGHT R-S-T 21222324252627282930

  • PANEL CHECK

    REMARK

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)TIDAK ADA NAMEPLATE UNTUK SETIAP OUTGOING BREAKERTIDAK ADA LAMPU PENERANGAN DI DALAM PANELTATA LETAK BREAKER DAN PANEL TIDAK TERTATA RAPIPANEL TYPE OUTDOOR, AMAN DARI MASUKNYA AIR. IP3X (OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL LINE BChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 MCCB 200A 3P 2 MCCB 160A 3P 3 MCCB 100A 3P 4 MCCB 80A 3P 5 MCCB 50A 3P 6 MCCB 40A 3P 7 MCCB 40A 3P 8 MCCB 40A 3P 9 MCCB 20A 3P

    10 MCCB 20A 3P 11 MCCB 20A 3P 12 MCCB 16A 3P 13 MCCB 63A 3P 14 CT 200A (3x) 15 PM 700 16 PILOT LIGHT R,S,T 17 FUSE (6x) 18192021222324252627282930

  • PANEL CHECK

    REMARK

    TATA LETAK BREAKER TIDAK STANDAR

    BANYAK MCB TIDAK TERPAKAI

    UKURAN BUSBAR UNTUK ARUS BAGI TERLALU KECIL (UK. 30mmx10mm)TIDAK ADA CABLE DUCT SEHINGGA KABEL TIDAK RAPITIDAK ADA LAMPU PENERANGAN DI DALAM PANELPOSISI KABEL YANG MASUK KE DALAM PANEL TIDAK STANDAR

    ADA KABEL YAG TIDAK MEMAKAI BREAKER DAN LANGSUNG KE OUT GOIG PANEL

    PANEL TIDAK AMAN DARI MASUKNYA AIR. BISA MASUK MELALUI JALUR KABEL INCOMING YANG TIDAK STANDAR

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL GALON LINE CChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 MCCB 160A 3P 2 MCCB 100A 3P 3 MCCB 100A 3P 4 MCCB 25A 3P 5 MCCB 25A 3P 6 MCCB 25A 3P 7 MCCB 15A 3P 8 MCCB 15A 3P 9 MCCB 15A 3P

    10 MCCB 15A 3P 11 PM700 12 PILOT LIGHT R,S,T 13 FUSE (4x) 14 CT 200A (3X)15161718192021222324252627282930

  • PANEL CHECK

    REMARK

    TIDAK ADA LAMPU PENERANGAN DI DALAM PANEL

    TIDAK ADA CABLE DUCT SEHINGGA KABEL TIDAK RAPI

    TATA LETAK BREAKER TIDAK STANDAR

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    BANYAK KABEL YANG TERMINASINYA TIDAK MEMAKAI SCONE

    TIDAK MENGGUNAKAN BUSBAR UNTUK ALIRAN ARUS/ LANGSUNG JUMPER DENGAN KABELKOMPONEN ADA YANG TIDA DI DALAM PANEL (CT 200A x 3)

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL BARDIE LINE EChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 ACB 800A 3P 2 MCCB 630A 3P 3 MCCB 100A 3P 4 MCCB 100A 3P 5 MCCB 100A 3P 6 MCCB 80A 3P 7 MCCB 25A 3P 8 PM800 P0WER LOGIC 9 CT x 3 (800A)

    10 MCB 6A 3p 11 MCB 10A 1P 12 MCB 20A 1P (2x) 13 MCB 6A 1P 14 TEND R-S-T 15 SELECTOR SWITCH T-S-R-OF 16 PILOT LIGHT R,S,T 17 VOLT AMPER METER ANALOG 18 AMPERE METER ANALOG 192021222324252627282930

  • PANEL CHECK

    REMARK

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    TIDAK ADA LAMPU PENERANGAN DI DALAM PANEL

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)

  • PANEL CHECK

    Customer : PT. TIRTA INVESTAMA SUBANGProject : AQUA - SUBANGPanel Name : PANEL LVMDP SPS DAN CAPACITOR 800 KVAChecker : BUDI KURNIAWAN

    NO COMPONENT CONDITIONGOOD BAD OTHER1 ACB 4000A 4P 2 ACB 4000A 4P 3 ACB 1600A 3P 4 ACB 2500A 4P 5 ACB 800A 6 PILOT LIGHT R,S,T (GENSET) 7 PILOT LIGHT R,S,T (PLN) 8 POWER MONITORING PM710 9 PILOT LIGHT RED

    10 PILOT LIGHT RED 11 PUSH BUTTON RED 12 PUSH BUTTON RED 13 PUSH BUTTON GREEN 14 PUSH BUTTON GREEN 15 EMERGENCY STOP 16 SELECTOR SWITCH M-O-A 17 CT x 3 (1500A) 18 PILOT LIGHT RED (12x) 19 PILOT LIGHT GREEN (12x) 20 PUSH BUTTON RED(12x) 21 PUSH BUTTON GREEN (12x) 23 CONTACTOR 125A (16x) 24 MCCB 125A (16x) 25 NH FUSE (48x) 26 FUSE HOLDER (48x) 27 CAPACITOR 25 kVAR (32x) 28 PILOT LIGHT R,S,T (CAPACITOR) 2930

  • PANEL CHECK

    : PANEL LVMDP SPS DAN CAPACITOR 800 KVA

    REMARK

    CAPACITOR 800 KVAR (OK)

    INTERLOCK PLN -GENSET (OK)

    PANEL AMAN DARI MASUKNYA AIR. IP3X (OK)

    PILOT LIGHT DAN PUSH BUTTON HARUSNYA ADA 16 STEP

    TIDAK ADA BUSBAR PENGAMAN/ISOLATOR UNTUK PANEL CAPASITOR JARAK ANTARA DINDING DAN PANEL TERLALU BERDEKATAN (HARUSNYA MINIMAL 800 mm) AGAR MUDAH SAAT PERBAIKAN KETIKA ADA TROUBLE SHOOTING

    TIDAK ADA LAMPU PENERANGAN DI DALAM PANEL

    COVER PANEL SAFETY, JARI TIDAK BISA MASUK KE DALAM PANEL. 2B(OK)

    PANEL HEATERPANEL AC 1PANEL HUSKYPANEL LOW COMPRESSORPANEL SDP 600mlPANEL GENSETPANEL LVMDP HODPANEL LINE DPANEL LINE APANEL KOMPRESSOR 5 GALONPANEL LINE BPANEL LINE CPANEL BARDIE LINE EPANEL LVMDP SPS DAN CAP.800 KAV