1 Sales 800-633-0405 www.productivity1000.com COM 1B 1Z 3IN COM 2A 2B 2Z 4IN 1A P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input Module provides two independent single ended 5–24 VDC inputs that accept up to 100kHz of pulse/direction and quadrature signals. Additionally, two 5–24 VDC general purpose high-speed inputs are included for use with the Productivity1000 System. Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1 General Specifications . . . . . . . . . . . . . . . . . . . . . . 2 Connector Specifications. . . . . . . . . . . . . . . . . . . . . 2 Terminal Block Specifications . . . . . . . . . . . . . . . . . 2 Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Module Installation Procedure . . . . . . . . . . . . . . . . . 4 QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5 Open Collector Output Encoder Wiring . . . . . . . . . . 6 Totem Pole Output Encoder Wiring . . . . . . . . . . . . . 6 Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Warranty: Thirty-day money-back guarantee. Two-year limited replacement. (See www.productivity1000.com for details). Input Specifications Inputs per Module Single ended Counter Inputs (6pts: 1A, 1B, 1Z, 2A, 2B, 2Z) General Purpose Inputs (3IN, 4IN) Rated Voltage 5–24 VDC Operating Voltage Range 4.25–27.6 VDC Input Current 1.5 mA typical @ 4.25VDC 11mA maximum @ 27.6 VDC Input Impedance 2.5 K Minimum ON Current 1mA Maximum OFF Current 0.4 mA Minimum ON Voltage 4.5 VDC Maximum OFF Voltage 2.2 VDC OFF to ON, ON to OFF Response Time 2μs Minimum Direction Setup Time 20μs Maximum Input Frequency 100kHz Module Range Target position range ±2.147 billion (32-bit signed integer) Status Indicators Logic Side (8 points) Commons 2 (4 points / common)

Upload: others

Post on 15-Mar-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

1Sales 800-633-0405 www.productivity1000.com

COM

1B1Z3INCOM2A2B2Z4IN

1A

P1-02HSC

5-24VDCINPUT

CNT1

CNT2

1000

P1-02HSC High-Speed Isolated Sinking/Sourcing InputThe P1-02HSC High-Speed Input Module provides two independent single ended 5–24 VDC inputs that accept up to 100kHz of pulse/direction and quadrature signals. Additionally, two 5–24 VDC general purpose high-speed inputs are included for use with the Productivity1000 System.

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1General Specifications . . . . . . . . . . . . . . . . . . . . . . 2Connector Specifications . . . . . . . . . . . . . . . . . . . . . 2Terminal Block Specifications . . . . . . . . . . . . . . . . . 2Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Module Installation Procedure . . . . . . . . . . . . . . . . . 4QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5Open Collector Output Encoder Wiring . . . . . . . . . . 6Totem Pole Output Encoder Wiring . . . . . . . . . . . . . 6Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Warranty: Thirty-day money-back guarantee. Two-year limited replacement. (See www.productivity1000.com for details).

Input Specifications

Inputs per ModuleSingle ended Counter Inputs (6pts: 1A, 1B, 1Z, 2A, 2B, 2Z)General Purpose Inputs (3IN, 4IN)

Rated Voltage 5–24 VDC

Operating Voltage Range 4.25–27.6 VDC

Input Current 1.5 mA typical @ 4.25VDC11mA maximum @ 27.6 VDC

Input Impedance 2.5 K�

Minimum ON Current 1mA

Maximum OFF Current 0.4 mA

Minimum ON Voltage 4.5 VDC

Maximum OFF Voltage 2.2 VDC

OFF to ON, ON to OFF Response Time 2µs

Minimum Direction Setup Time 20µs

Maximum Input Frequency 100kHz

Module Range Target position range ±2.147 billion (32-bit signed integer)

Status Indicators Logic Side (8 points)

Commons 2 (4 points / common)

Page 2: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

2 Tech Support 770-844-4200www.productivity1000.com

Terminal Block SpecificationsPart Number P1-10RTB P1-10RTB-1

Positions 10 Screw Terminals 10 Spring Clamp Terminals

Wire Range

30–16 AWG (0.051–1.31 mm²)Solid / Stranded Conductor3/64 in (1.2 mm) Insulation Max.1/4 in (6–7 mm) Strip Length

28–16 AWG (0.081–1.31 mm²)Solid / Stranded Conductor3/64 in (1.2 mm) Insulation Max.19/64 in (7–8 mm) Strip Length

Conductors “USE COPPER CONDUCTORS, 75ºC” or equivalent.

Screw Driver 0.1 in (2.5 mm) Maximum*

Screw Size M2 N/A

Screw Torque 2.5 lb·in (0.28 N·m) N/A*Recommended Screw Driver TW-SD-MSL-1

General SpecificationsOperating Temperature 0º to 60ºC (32º to 140ºF)

I/O Points Used None, mapped directly to tags in CPU

Storage Temperature -20º to 70ºC (-4º to 158ºF)

Humidity 5 to 95% (non-condensing)

Environmental Air No corrosive gases permitted

Vibration IEC60068-2-6 (Test Fc)

Shock IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation 1800VAC applied for 1 second

Insulation Resistance > 10M� @ 500VDC

Heat Dissipation 1300mW

Field Wiring See “Wiring Options” on page 5.

EU DirectiveSee the “EU Directive” topic in the Productivity Suite Help File. Information can also be obtained at:www.productivity1000.com

Terminal Type (included)

10-position Removable Terminal Block

Weight 54g (2oz)

Agency ApprovalsUL 61010-1 and UL 61010-2-201 file E139594, Canada & USACE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)**

*Note: For complete system limits, please refer to the “Hardware and Communication Limits” table in the Productivity Suite Help File, “Hardware Configuration” topic (P050).**Meets EMC and Safety Requirements. See the D.O.C. for details.

Page 3: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

3Sales 800-633-0405 www.productivity1000.com

P1-02HSC Schematic

Sourcing FieldDevice

+ COM

1A

1B

1Z

3IN

COM

2A

2B

2Z

4IN

12

34

56

78

910

+

Sinking FieldDevice

5–24VDC

High Speed General Purpose Inputs

STEP1

DIR1INDEX1

(GP INPUT)

GP INPUT

STEP2

DIR2INDEX2

(GP INPUT)

GP INPUT

P1-02HSC Wiring Diagram

Equivalent Input Circuit

Internal Module Circuitry

COM

COM

INPUT

+

Sourcing Field Device

Sinking Field Device

+

ISOLATOR

Page 4: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

4 Tech Support 770-844-4200www.productivity1000.com

Module Installation

WARNING: Do not add or remove modules with field power applied.

Step One: With latch in “locked” position, align connectors on the side of each module and stack by pressing together. Click indicates lock is engaged.

Step Three: To unstack modules, pull locking latch up into the unlocked position and then pull modules apart.

Step Two: Attach field wiring using the removable terminal block or ZIPLink wiring system.

LOC

K

UN

LOC

K

WIRE STRIPLENGTH

MINMAX

P1-08TD1

Check all latches are secure after modules are connected.

QR Code

Use any QR Code reader application to display the module’s product insert.

P1-08TD1P1-08TD1

12

34

56

78

910

LLLL

LL

LL

24V12340V

5678

12 - 24VDC+ -

+ -

12

34

56

78

910

LLLL

LL

LL

24V12340V

5678

12 - 24VDC+ -

Dual Power Source

Single Power Source

3.3 - 24VDC

P1-08TD1 Wiring Diagram

Page 5: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

5Sales 800-633-0405 www.productivity1000.com

Wiring Options

1 Screw Terminal Block onlyP1-10RTB(Quantity 1)

2 Spring Clamp Terminal Block onlyP1-10RTB-1(Quantity 1)

3 Accessories¹ZL-RTB-COM

TW-SD-SL-1

TW-SD-MSL-1

1. ZL-RTB-COM provides a common connection point for power or ground

Module Configuration

Using the Hardware Configuration tool in the Productivity Suite programming software, drag and drop the P1-02HSC module into the base configuration.

If desired, assign a User Tagname to each output point channel selected.

Page 6: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

6 Tech Support 770-844-4200www.productivity1000.com

P1-02HSC Open Collector Encoder Wiring

P1-02HSC

COM

1A

1B

1Z

3IN

COM

2A

2B

2Z

4IN

12

34

56

78

910

Koyo Open Collector Output Encoder

+-

PWR

ABZ

0VSHLD

BROWNBLACKWHITE

ORANGEBLUE

PWR

ABZ

0VSHLD

BROWNBLACKWHITE

ORANGEBLUE

SENSOR

SINKING FIELD DEVICE+

-

Line Driver Output Encoders Not Reccommended for P1-02HSC

SHLD CABLE

SHLD CABLE

5–24VDC

P1-02HSC Totem Pole Output Encoder Wiring

P1-02HSC

COM

1A

1B

1Z

3IN

COM

2A

2B

2Z

4IN

12

34

56

78

910

Koyo Totem Pole Output Encoder

+ -

PWR

ABZ

0VSHLD

BROWNBLACKWHITE

ORANGEBLUE

PWR

ABZ

0VSHLD

BROWNBLACKWHITE

ORANGEBLUE

SENSOR

SOURCING FIELD DEVICE+

-

SHLD CABLE

SHLD CABLE

5–24 VDC

Note: The P1-02HSC requires 7VDC minimum power to Totem Pole Encoders

Page 7: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

7Sales 800-633-0405 www.productivity1000.com

Page 8: P1-02HSC High-Speed Isolated P1-02HSC Sinking/Sourcing Input · P1-02HSC 5-24VDC INPUT CNT1 CNT2 1000 P1-02HSC High-Speed Isolated Sinking/Sourcing Input The P1-02HSC High-Speed Input

8 Tech Support 770-844-4200www.productivity1000.com

Document Name Edition/Revision DateP1-02HSC-DS 1st Edition, Rev A 4/2/2019

Copyright 2019, AutomationDirect.com Incorporated/All Rights Reserved Worldwide

WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes.

Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation.

If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call Technical Support at 770-844-4200.

This publication is based on information that was available at the time it was printed. At AutomationDirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without any obligation. This publication may also discuss features that may not be available in certain revisions of the product.

8 Tech Support 770-844-4200www.productivity1000.com